| GEAppliances.com   Safety Instructions . . . . . . . . . . .2   Owner’s Manual and   Installation Instructions   Operating Instructions   Controls—Dip Switches . . . . . .3–5   Controls—Terminal   Connections . . . . . . . . . . . . . .6, 7   On/Off Switch . . . . . . . . . . . . . . .8   Ventilation Control . . . . . . . . . . .8   Heat/Cool and   Heat Pump Models   7500 Series   Care and Cleaning   Air Filters . . . . . . . . . . . . . . . . . . .9   Base Pan . . . . . . . . . . . . . . . . . . .9   Exhaust Coils . . . . . . . . . . . . . . . .9   Installation Instructions   Electrical Supply . . . . . . . . .11–13   Installing the Zoneline . . . .14–21   Preparation . . . . . . . . . . . . . . . .10   Servicing . . . . . . . . . . . . . . . . . .22   Troubleshooting Tips . . . . . . .23   Normal Operating Sounds . . . .24   Consumer Support   Consumer Support . . .Back Cover   Product Registration . . . . . .25, 26   Warranty . . . . . . . . . . . . . . . . . .27   Write the model and serial   numbers here:   Model # __________________   Serial #____________________   Find these numbers on a label   on the front case panel.   49-7419-2 04-02 JR   Controls–dip switches.   GEAppliances.com   Controls–Dip Switches   The dip switch controls are located behind the   Dip   front case panel, through an opening on the   front of the unit.   Switches   To access the dip switches, remove the front   case panel by removing the filter, taking out the   four front screws, the upper two screws from the   top of the panel and the shipping screws on each   side, if present. (Discard the two side shipping   screws, if present).   The factory settings will be in the DOWN position.   NOTE: The owner is responsible for setting   the appropriate dip switches and connecting   terminals.   Side   shipping   screw   Side   shipping   screw   TL1 (H) (Temp. Limit 1–Heat)   TL2 (H) (Temp. Limit 2–Heat)   TL3 (H) (Temp. Limit 3–Heat)   TL1 (C) (Temp. Limit 1–Cool)   TL2 (C) (Temp. Limit 2–Cool)   TL3 (C) (Temp. Limit 3–Cool)   2 No Function (Reserved for future use)   DUCT (Blower Fan)   OCCUPIED (Occupancy Sensor)   ALL I R (All Electric Heat) (Heat-pump models only)   FREEZ S (Freeze Sentinel)   CONST FAN (Constant ON Fan)   All Electric Heat (Heat pump models only)   When this switch is enabled (UP), heat pump   operation is locked out, causing the unit to   provide only electric resistance heat.   2 ALL I R (All Electric Heat)   3 Controls–dip switches.   Freeze Sentinel (Requires room air sensor kit–RAVRMS)   When this switch is enabled (UP), it turns OFF the   freeze sentinel protection feature. With the   switch disabled (DOWN), the freeze sentinel is   activated which automatically provides heat   without user interface. This helps to prevent   plumbing damage by turning the heater and   fans ON at 41° F and OFF at 46° F.   FREEZE S (Freeze Sentinel)   Constant ON Fan   When this switch is enabled (UP), it allows the   fans to run continuously, at high speed, even if   the unit is in the STOP position.   CONST FAN (Constant   ON Fan)   Occupancy Sensor   When this switch is enabled (UP), it allows the   unit to utilize an infrared motion sensor and a   door switch for occupancy detection. This feature   allows an energy management system to be   installed and operated in conjunction with   the unit.   OCCUPIED   (Occupancy Sensor)   Duct   The duct select function allows the indoor   fan to be operated at two variable fan speeds,   depending on the duct length. When this switch   is enabled (UP), the unit automatically selects   either high or middle fan speed for longer   ductwork applications. When set in the down   position, the unit is automatically operated in   either the middle or low fan speed for shorter   ductwork applications.   DUCT   (Blower Fan)   4 GEAppliances.com   Temperature Limiting (Requires room air sensor kit–RAVRMS)   Temperature limiting can reduce energy costs   by limiting the lowest temperature that can be   set for cooling and the highest temperature that   can be set for heating. Temperature limiting is   controlled by switches 1–6 on the top block   of auxiliary controls. The first three switches are   used to select the cooling limits. The next three   switches are used to control the heating limits.   TL1 (H) (Temp. Limit 1–Heat)   TL2 (H) (Temp. Limit 2–Heat)   TL3 (H) (Temp. Limit 3–Heat)   TL1 (C) (Temp. Limit 1–Cool)   TL2 (C) (Temp. Limit 2–Cool)   TL3 (C) (Temp. Limit 3–Cool)   Temperature limiting during HEAT mode   (all temperatures shown in °F)   Temperature limiting during COOL mode   (all temperatures shown in °F)   UP   NONE   4 4, 5   5 DOWN   4, 5, 6   5, 6   6 4, 6   4 NONE   5 4, 5   Minimum Maximum   UP   NONE   1 1, 2   2 DOWN   1, 2, 3   2, 3   3 1, 3   1 NONE   2 1, 2   Minimum Maximum   60°   60°   60°   60°   60°   60°   60°   60°   85°   80°   78°   76°   74°   72°   70°   65°   60°   64°   66°   68°   70°   72°   74°   76°   85°   85°   85°   85°   85°   85°   85°   85°   5,6   2,3   4, 5, 6   4, 6   6 1, 2, 3   1, 3   3 5 Controls—terminal connections.   Controls–Terminal Connections   The terminal connections are located behind the   front case panel through an opening on the   front of the unit.   To access the terminal connections, remove the   front panel by removing the filter, taking out the   four front screws, the upper two screws from the   top of the panel and the shipping screws on each   side, if present. (Discard the two side shipping   screws, if present).   Terminal   connections   Insert the building hook-up wires into the   bottom of the terminals and tighten screws   securely to make the desired connections.   Route the wires from the terminal connections   through the unit wire guides and out through   the case wire guide.   NOTE: The owner is responsible for setting   the appropriate dip switches and connecting   terminals.   CAUTION:   Improper CDC wiring may damage the Zoneline   electronics or cause erratic Zoneline operation.   No common busing is permitted. A separate wire   pair must be run from each separate controlling   switch to each individual Zoneline.   Route wires   through wire   guides   Common–Ground   White–Heater   Yellow–Compressor   Black–Reversing Valve   Green–High Speed Fan   Green–Low Speed Fan   Red–24V AC only   Room Air Sensor   Motion Sensor   Door Sensor   Central Desk Control   Room Air Sensor (Requires room air sensor kit – RAVRMS)   When connected, the room air sensor will allow   utilization of the temperature limiting and freeze   sentinel features.   NOTE: If GE thermostat RAK147P2 or RAK163P2   is used with the unit, the room sensor kit is not   needed, since temperature limiting and freeze   sentinel features are incorporated in the   thermostats.   Room Air   Sensor   6 GEAppliances.com   Motion Sensor (Obtained locally)   The Occupancy Sensor dip switch must be in   the up position to use this feature.   When connected, the wall mounted motion   sensor will detect motion in the room and   automatically cycle the unit between normal   operation and energy management operation.   Motion Sensor   The door and motion sensors work together   to automatically cycle the unit between normal   operation and energy management operation.   Door Sensor (Obtained locally)   The Occupancy Sensor dip switch must be in the   up position to use this feature.   When connected, the door sensor will detect   when the door in the room is opened or closed.   This feature must be used in conjunction with   the motion sensor.   Door Sensor   The door and motion sensors work together   to automatically cycle the unit between normal   and energy management operations.   Central Desk Control   When connected, the unit lock-out is released   and it can be turned ON or OFF with a switch   located at the Central Desk Control. A separate   wire pair must be run from each separate   controlling switch to each individual Zoneline.   Central Desk Control   Remote Thermostat   The unit will be controlled by a remote   thermostat.   IMPORTANT:   The Zoneline thermostat connections   provide 24V AC only.   Red–24V AC only   Green–Low Speed Fan   Green–High Speed Fan   Black–Reversing Valve   Yellow–Compressor   White–Heater   If using a digital/electronic wall thermostat,   you must set it to the 24V AC setting. See the   Installation Instructions for the wall thermostat.   Common–Ground   CAUTION:   Damage to a wall thermostat or to the   Zoneline electronics can result from improper   connections. Exercise extra attention when   connecting blue and black wires. No line   voltage connections should be made to any   circuit in the thermostat. Isolate all wires in   building from line voltage.   7 Other features of your Zoneline.   On/Off Switch   The unit on/off switch is located on the front of   the Zoneline.   To turn the unit on, press the top of the switch in.   To turn the unit off, press the bottom of the   switch in.   ON/OFF   switch   Ventilation Control   The ventilation control lever is located on the   left side of the Zoneline unit, behind the front   case panel.   To access the ventilation control lever, remove   the front panel by removing the filter, taking out   the four front screws, the upper two screws from   the top of the panel and the shipping screws on   each side, if present. (Discard the two side   shipping screws, if present).   Open   Close   Vent control   (push lever down   and pull forward   or back to   When the lever is in the CLOSE position, only the   air inside the room is circulated and filtered.   operate)   When the lever is in the OPEN position, some   outdoor air will be drawn into the room. This   will reduce the heating or cooling efficiency.   Energy Tip: Keep the vent control in the   CLOSE position. The room air will be filtered   and circulated.   To close the vent, push the vent lever handle   down, pull it forward and lock it up in place.   To open the vent, push the vent lever handle down,   push it back and lock it up in place.   About Heat Pumps (on some models)   Heat pumps can reduce operating costs by   exchanging heat from the outside air—even   when the outside temperature is below   freezing— and releasing that heat indoors.   There is a three minute minimum compressor   run time at any setting to prevent short cycling.   The indoor fan motor starts before the   compressor and stops after the compressor   cycles off.   To get the best economic benefit from your heat   pump, don’t change the room thermostat setting   very often. Raising the heat setting 2–3 degrees   will cause the Zoneline to use its electric heating   elements in order to reach the new temperature   setting quickly.   The electric heating elements use much   more electricity than heat pumps and cost   more to operate.   8 Care and cleaning.   GEAppliances.com   Turn the Zoneline off and disconnect the power supply before cleaning.   Indoor/Outdoor Coils   The exhaust coils on the Zoneline should be   checked regularly. If they are clogged with dirt or   soot, they may be professionally steam cleaned by   your GE service center. You will need to remove   the unit from the case to inspect the coils   because the dirt build-up occurs on the   exhaust side.   Outdoor coils   Have the coils cleaned regularly.   Drain   Clean the drain system regularly to   prevent clogging.   Base Pan   In some installations, dirt or other debris may be   In some areas of the United States, a “gel-like”   blown into the unit from the outside and settle in substance may be present in the base pan.   the base pan (the bottom of the unit).   Check it periodically and clean, if necessary.   Air Filters   To maintain optimum performance, change the filter at least every 30 days.   The most important thing you can do to   maintain the Zoneline is to change the filter at   least every 30 days. Dirty filters reduce cooling,   heating and air flow.   To remove   and replace   the filter:   Remove filter   Changing the filter will: Decrease cost of operation,   save energy, prevent clogged heat exchanger   coils and reduce the risk of premature   component failure.   CAUTION:   Do not operate the   Unit-mounted filter   Zoneline without the filter in place. If a filter   becomes torn or damaged, it should be replaced   immediately.   Operating without the filter in place or with a   damaged filter will allow dirt and dust to reach   the indoor coil and reduce the cooling, heating,   airflow and efficiency of the unit.   Filter   Replacement filters should be purchased from   your local retailer where air conditioner and   furnace accessories are sold.   Filter   Return air grille   Filter size required is 20″ x 20″ x 1″.   Access-panel with   return air grille   9 Installation   Instructions   Zoneline Air   Conditioners   Questions? Visit our Website at: GEAppliances.com or call 800.GE.CARES (800.432.2737).   BEFORE YOU BEGIN   IMPORTANT ELECTRICAL   SAFETY–READ CAREFULLY   CAUTION:   Read these instructions completely and carefully.   • IMPORTANT   Save these   – instructions for local inspector’s use.   • All electrical connections and wiring MUST be   • installed by a qualified electrician.   • Follow the National Electrical Code (NEC) and/or   local codes and ordinances.   • For personal safety, this Zoneline unit and case   must be properly grounded.   • Protective devices (fuses or circuit breakers)   acceptable for Zoneline installations are specified   on the nameplate of each unit.   IMPORTANT   Observe all   – governing codes and ordinances.   • Note to Installer – Be sure to leave these   instructions with the owner.   • Note to Owner – Keep these instructions for   future reference.   • Proper installation is the responsibility of the   installer.   • Do not use an extension cord with this unit.   • Aluminum building wiring may present special   problems—consult a qualified electrician.   • Product failure due to improper installation is not   covered under the Warranty.   • When the unit is not running there is still voltage to   the electrical controls.   • Disconnect the power to the unit before   servicing by:   TOOLS YOU WILL NEED   1. Removing the power cord (if it has one) from   the wall receptacle.   OR   Phillips screwdriver   Adjustable wrench   2. Removing the branch circuit fuses or turning   the circuit breakers off at the panel.   Saw   Hammer   Tape measure   WARNING: Before beginning the   installation, switch power off at the service panel   and lock the area to prevent power from being   switched on accidentally. When the area cannot   be locked, securely fasten a prominent warning   device, such as a tag, to the service panel.   10   Installation Instructions   ELECTRICAL REQUIREMENTS   • Use ONLY the wiring size recommended for single   FOR 230/208 VOLT POWER CORD   outlet branch circuit.   CONNECTIONS ONLY   • Proper current protection is the responsibility   1. Remove the front panel by taking out the four   front screws, the upper two screws from the top   of the panel and the shipping screws on each   side, if present. (Discard the two side shipping   screws, if present.)   of the owner.   Recommended branch circuit wire sizes*   Nameplate   maximum circuit   breaker size   AWG Wire   size**   15A   20A   30A   14   12   10   Side   shipping   screw   AWG – American Wire Gauge   * Single circuit breaker from main box   Side   shipping   screw   ** Based on copper wire, single insulated conductor at 60° C   NOTE: Use copper conductors only.   230/208 VOLT   ELECTRICAL SUPPLY   2. Remove the junction box cover and the   junction box and discard.   A power supply kit must be used to supply power to the   Zoneline unit. The appropriate kit is determined by the   voltage, the means of electrical connection and the   amperage of the branch circuit. See the POWER   CONNECTION CHART on page 13 to select the   appropriate kit.   Remove   junction box   and cover   3. Connect the power cord, with a loop, through   Power supply kit   the strain relief.   All wiring, including installation of the receptacle,   must be in accordance with the NEC and local codes,   ordinances and regulations.   Strain relief   Tandem   15 Amp   Perpendicular   Large Tandem   IMPORTANT:   Power cord must   have a loop.   20 Amp   30 Amp   230/208 volt receptacle configuration   11   Installation Instructions   DIRECT CONNECT APPLICATIONS   FOR 265 VOLT DIRECT CONNECT   FOR 230/208 VOLT DIRECT   APPLICATIONS ONLY   CONNECT APPLICATIONS ONLY   IMPORTANT: Connection of a 265V AC product to a   branch circuit MUST be done by direct connection in   accordance with the National Electric Code. Plugging   this unit into a building mounted exposed receptacle is   not permitted by code.   1. Remove the cordset from the power supply kit.   Measure 7″ down the cord from where it emerges   from the back of the nylon plastic connector and   cut the cord through at this point.   2. Carefully remove 6″ of the cordset insulation   so as to expose the three insulated wires.   These models must be installed using the appropriate   GE power supply kit for the branch circuit amperage   and the electrical resistance heater wattage desired.   See the POWER CONNECTION CHART on page 13   to select the appropriate kit.   3. Strip 3/4″ of the insulation away at the end of   each of the three wires (L1, L2 and Ground).   4. Direct connection to branch circuit wiring inside the   provided junction box must be made by connecting   as follows in steps 1–3 below.   It is the responsibility of the installer to ensure the   connection of components is done in accordance   with electrical codes.   3/4″   Connector   Direct connection to branch circuit wiring inside the   provided junction box must be made by connecting   as follows in steps 1–3 below.   6″   7″   2 1 ATTACH CONDUIT   REMOVE JUNCTION BOX COVER   • Remove the junction box cover by taking out the   front two screws.   • Use the round knockout hole at the top of the   junction box to install conduit coming from the   branch circuit. Install and clamp the conduit   through the conduit clamp and bring wire leads   into the junction box. Leave 8″ of wire free from   the end of the conduit.   Conduit   clamp   Conduit   Junction box   Junction box cover   12   Installation Instructions   DIRECT CONNECT APPLICATIONS   3 MAKE WIRE LEAD CONNECTIONS INSIDE THE JUNCTION BOX   1.   2.   Make all wire connections by using appropriate UL-listed electrical connectors and techniques.   Select the applicable wiring situation and follow the instructions accordingly:   • 1-Phase 220-240 VAC   • 3-Phase 208 VAC with “Crazy Leg”   When connecting the Zoneline to a three-phase circuit with   “Crazy Leg” for 208V applications:   When connecting the Zoneline to a single-phase circuit for   230V applications:   Connect the white and black leads of the Zoneline   power supply kit to the branch circuit L1 and L2   leads. (The white lead of the power supply kit should   be identified by the installer using electrical tape with   some color other than green or white.) Connect the   green lead of the power supply kit to the power   supply and branch circuit ground.   Connect the white and black leads of the Zoneline   power supply kit to the branch circuit Neutral and L1   leads. (The white lead of the power supply kit should   be connected to neutral.) Connect the green lead of   the power supply kit to the power supply and branch   circuit ground.   • 3-Phase 253-277 VAC   • 3-Phase 208 VAC   When connecting the Zoneline to a three-phase circuit for   265V applications:   When connecting the Zoneline to a three-phase circuit for   208V applications:   Connect the white and black leads of the Zoneline   power supply kit to the branch circuit Neutral and L1   leads. (The white lead of the power supply kit should   be connected to neutral.) Connect the green lead of   the power supply kit to the power supply and branch   circuit ground.   Connect the white and black leads of the Zoneline   power supply kit to the branch circuit L1 and L2   leads. (The white lead of the power supply kit should   be identified by the installer using electrical tape with   some color other than green or white.) Connect the   green lead of the power supply kit to the power   supply and branch circuit ground.   3.   Be sure that all wire leads are inside the junction box and not   pinched between the box and the unit. The green insulated   ground wire from the Zoneline MUST be connected to the branch   circuit ground wire.   Conduit   4.   5.   Plug the 9-pin connector into the 9-pin receptacle in the   junction box.   Replace the junction box cover by replacing the two screws   removed earlier.   Make wire lead   connections   POWER CONNECTION CHART   230/208 Volt   Power Supply Kits   Wall Plug   Configuration   Heater Wattage   @ 230/208 Volts   Circuit Protective Device   RAK3152   RAK3202   RAK3302   Tandem   Perpendicular   Large Tandem   15 Amp Time-Delay Fuse or Breaker   20 Amp Time-Delay Fuse or Breaker   30 Amp Time-Delay Fuse or Breaker   2.55/2.09 KW   3.45/2.82 KW   5.00/4.10 KW   265 Volt   Power Supply Kits   Wall Plug   Configuration   Heater Wattage   @ 265 Volts   Circuit Protective Device   RAK5157   RAK5207   RAK5307   Does Not Apply   Does Not Apply   Does Not Apply   15 Amp Time-Delay Fuse or Breaker   20 Amp Time-Delay Fuse or Breaker   30 Amp Time-Delay Fuse or Breaker   2.55 KW   3.45 KW   5.00 KW   13   Installation Instructions   ZONELINE COMPONENTS   Case   Zoneline unit   Front Case Panel   REQUIRED ACCESSORIES   (Check the “Essential Elements” label on the unit.)   Cutout   Dimensions:   20″ W x 321⁄4″ H   Wall Plenum   RAVWP6 - 6″D x 193⁄4″W x 32″H   RAVWP8 - 8″D x 193⁄4″W x 32″H   RAVWP12 - 12″D x 193⁄4″W x 32″H   RAVWP15 - 15″D x 193⁄4″W x 32″H   Architectural Louver   RAVAL1   30″   Cutout   Cutout   Dimensions:   28″W x 48″H   22 1⁄2″   Dimensions:   203⁄8″W x 203⁄8″H   50″   Access Panel with   Return Air Grille   RAVRG1   Return Air Grille   RAVRG2   OR   22 1⁄2″   Wall Thermostat   Model Type   Mechanical Thermostat Electronic Thermostat   Heat/Cool Models   Heat Pump Models   4-wire   6-wire   5-wire   6-wire   Check the thermostat instructions for correct wiring and installation requirements.   14   Installation Instructions   TYPICAL UTILITY CLOSET AND DIMENSIONS   (FOR REFERENCE ONLY)   UNIT INSTALLED THROUGH FRONT OF CASE   UNIT INSTALLED THROUGH SIDE OF CASE   Top View   Top View   Architectural Louver   Architectural Louver   111⁄2″   111⁄2″   3″ min.   3″ min.   10″   10″   Door/access panel   duct   10″   10″   duct   3″   min.   3″   min.   4″ min.   Unit   front   Unit front   5″ min.   Door/access panel   Side View   Rigid   ductwork   Inside wall   Outside wall   Flexible or   rigid duct   Unit   Air discharge   outlet   Wall plenum   • 4″ min. from front of case – Unit   installed through FRONT of case.   • 5″ min. from front of case – Unit   installed through SIDE of case.   Exterior/Outside   31″   • 3″ min. from two sides of case.   Wall plenum   divider   Plenum   cutout   Option 1   Access panel with   return air grille   321⁄4″ H   x 20″ W   Filter bracket   Option 2   Return air grille   Drain fitting 3⁄4″   Bottom of case approx. 2″   above bottom of plenum   A Secure platform   to the floor   Wall plenum   Platform: 231⁄4″ x 231⁄4″ square   Min. load capacity: 175 lbs.   8″ min.   for drain   access   Bottom of case approx. 2″   above bottom of plenum   B Platform   Field supplied   outer flashing   A Minimum recommended access door width: 30″   B Minimum recommended access door height: 50″   Outside wall   15   Installation Instructions   UTILITY CLOSET CONNECTION LOCATIONS   IMPORTANT: Plan and locate plenum, wall plug, drain and   thermostat carefully to avoid interference. Hard-to-reach locations   will make installation and service difficult!   Flex duct may be used   for transitions only   Reference Dimensions   A Thermostat cable: 91⁄2′ long   Use rigid duct for 90°   bends and tees   B Power cord: 60″ long   C Case width and depth: 231⁄8″   Outside wall   D Case height: 31″   E Condensate drain: 3/4″ connector   (Centerline of cutout is approximately 51⁄4″ from   left case wall and 81⁄2″ from back case wall.)   F Typical wall plug: 6″–12″ above case   G Room air sensor kit: 10′ long   230/208 VAC   wall receptacle   or   G A B conduit for direct   connection   F C C D 51⁄4″   81⁄2″   E Platform   16   Installation Instructions   RETURN AIR GRILLE INSTALLATION OPTIONS   The room return air grille may be installed toward the front or either side of the unit. Improper return air   arrangements will cause performance problems.   There are three indoor Return Air Grille Installation options. Choose the option that best suits your installation   requirements. Follow the Installation Instructions provided with the return air grille accessory for installation   details.   NOTE: Use only one filter in the installation. The filter may be installed on the unit or in the access panel/door.   Outside wall   RAVRG1 – Access panel with   return air grille   Filter   Option 1   RAVRG2 – Return air grille   Unit-mounted filter with a field-supplied return   air grille and access door/panel   Filter   Filter   Option 3   Option 2   17   Installation Instructions   WALL PLENUM AND ARCHITECTURAL LOUVER INSTALLATION   • Install the appropriate wall plenum through the exterior wall in accordance with the Installation Instructions   provided with the plenum.   IMPORTANT: The wall plenum is not designed to carry structural loads.   Proper wall header construction is required. The plenum requires proper   flashing, shim and caulk for a weather resistant installation.   Proper header for   structural support.   Apply proper caulking   and flashing.   Properly square and   level plenum.   Architectural   Louver—RAVAL1   Exterior/Outside Wall   Wall Plenum   RAVWP6 – 6″D x 193⁄4″W x 32″H   RAVWP8 – 8″D x 193⁄4″W x 32″H   RAVWP12 – 12″D x 193⁄4″W x 32″H   RAVWP15 – 15″D x 193⁄4″W x 32″H   Case   2. Place the platform in the utility closet with the   following clearance between it and the interior   surface of the walls/door/panel:   BUILD AND INSTALL THE   1 ZONELINE BASE PLATFORM   1. Construct a 231⁄4″ min. x 231⁄4″ min. square platform.   NOTE: The platform must have a load-bearing   capacity of 175 lbs. minimum.   • 4″ min. from front of the case – Unit to be   installed through FRONT of case   • 5″ min. from front of the case – Unit to be   installed through SIDE of case   • 3″ min. from two sides of the case   231⁄4″ min.   231⁄4″ min.   3. Align the platform with the opening of   the wall plenum and secure to the floor   using appropriate brackets and bolts.   8″ min.   for drain   access   Cutout for drain   connection   18   Installation Instructions   2 3 DUCTWORK   Prepare the closet ductwork for later connection to   the case.   INSTALL THE DRAIN   An external or an internal drain must be attached to   the drain connector.   The total flow rate (CFM) and external static pressure   (ESP) available can be estimated from the chart below.   Use these charts to select your fan speed setting. The   collar on top of the case accepts standard 10″ duct.   Pull all duct tight. Extra duct slack can greatly increase   static pressure.   CAUTION: Flex duct can collapse and cause airflow   restrictions. Do not use flex duct for 90° bends or   unsupported runs of 5 ft. or more.   External Drain   Attach a 90° PVC elbow to the unit’s female 3/4″ NPT   drain connector. Use the other end of the elbow to   run a 3/4″ Sch.40 PVC pipe through the knockout   holes of both the wall plenum and the architectural   louver to the outside. Seal the gap between the   plenum hole and PVC tube. See the Installation   Instructions in the RAVAL1.   Side View   Inside wall   Airflow – CFM@230 Volts and @ 265 Volts   Indoor Fan CFM   DUCT SELECT SWITCH   UP   DOWN   High   CFM   Medium Medium   Low   CFM   ESP   (in. water)   CFM   CFM   0.0   0.1   0.2   0.3   0.4   390   370   350   330   310   340   320   300   280   260   340   320   300   280   260   305   290   270   250   230   Female drain   fitting 3⁄4″   PVC   (External drain)   0.0   0.1   0.2   0.3   0.4   475   450   425   400   375   390   370   350   330   315   390   370   350   330   315   350   325   300   275   250   PVC   90° Elbow   0.0   0.1   0.2   0.3   0.4   630   610   590   570   550   545   530   515   495   475   545   530   515   495   475   490   480   470   455   440   Internal Drain   Attach PVC to the unit’s female 3/4″ NPT drain   connector. See the Installation Instructions in the   RAVAL1. Local codes may apply.   To correct for 208 volts: 0.91   Your airflow should be balanced based on many   factors, such as available ESP, room CFM, and   ductwork. Consult an HVAC engineer for proper   applications. External static pressure (ESP) can be   measured with a manometer or pitot tube. Once this   ESP is established, you can calculate the CFM using   the above chart.   Side View   Inside wall   CFM Recommendations   9,000 BTU   12,000 BTU   18,000 BTU   275 300 325 350 375 400 450 500 550   Female drain   • • • fitting 3⁄4″   • = Recommended Mid Range   Higher CFMs tend to increase Sensible capacity,   enhance room circulation and increase duct noise,   while lower CFMs tend to increase Latent capacity   and reduce noise.   PVC   (Internal drain)   19   Installation Instructions   4 INSTALL AND CONNECT   THE CASE   1. Remove the front case panel and pull the unit   out of the case. Place the empty case onto the   platform in the closet with the outdoor side facing   the wall plenum opening. Align the case to the   plenum opening and attach with six screws.   5a   INSTALL AND GROUND THE   UNIT TO THE CASE   UNIT INSTALLED THROUGH FRONT   OF CASE   1. Slide the back of the unit into the case. Push the   unit all of the way into the case until it stops.   2. Adjust all four leveling legs until the case is level.   NOTE: Either of the case sides may be removed to   enable the unit to be slid into the case.   2. Ground the unit to the case by installing the front   case-to-unit hex-bolt and/or case-to-unit side screw.   Inside   wall   Rigid   ductwork   Air   discharge   outlet   Leveling legs   Side screw   Hex bolt   5b   INSTALL AND GROUND THE   UNIT TO THE CASE   UNIT INSTALLED THROUGH SIDE   OF CASE   3. Using field-supplied screws, bolt the case to the   1. Slide the side of the unit into the case. Push the   platform.   unit all of the way into the case until it stops.   4. Connect the internal or external drain as necessary.   NOTE: Either of the case sides may be removed to   enable the unit to be slid into the case.   2. Attach the case side panel to the main case.   3. Ground the unit to the case by installing the front   unit-to-case hex-bolt and/or case-to-unit side screw.   Drain fitting 3⁄4″   External   drain   OR   Internal   drain   Bolt case to   platform   Side screw   (may be   installed on   either side)   Hex bolt   20   Installation Instructions   7 6 CONNECT THE TOP DUCT   MAKE UNIT ELECTRICAL   CONNECTIONS   1. Install the duct onto the air discharge outlet.   1. Connect the thermostat wires to the unit and set   the dip switches to the appropriate settings.   NOTE: See the Controls–Terminal Connections   and Controls–Dip Switches sections of this   manual and the manual with the separate   thermostat for proper connections   Inside   wall   Rigid   ductwork   Flexible or rigid   ductwork   and settings.   Thermostat   Air   discharge   outlet   Maximum Wiring   Length for Thermostat   Connection to the Unit   66 ft. for AWG 18   60 ft. for AWG 20   40 ft. for AWG 24   AWG – American Wire Gauge   Unit Connections   2. Secure the top duct to the unit by turning the four   case top duct adjusting screws until they are tight.   Use a field supplied clamp to lock the top duct to   the case.   2. Make power connections to the unit.   NOTE: See the ELECTRICAL REQUIREMENTS and   DIRECT CONNECT APPLICATIONS sections,   as appropriate, of this manual for proper   connections.   3. Replace the case front panel by replacing the four   front screws and the two top screws.   Top duct   Clamp   Case top   duct adjusting   screws   21   Installation Instructions   8 SERVICING   FINAL CHECK   Review this Checklist before restoring power.   • Correct line voltage?   WARNING: Before servicing,   switch power off at the service panel and lock the   area to prevent power from being switched on   accidentally. When the area cannot be locked,   securely fasten a prominent warning device, such   as a tag, to the service panel.   • Single circuit only?   • HVACR type breaker/fuse?   • Ductwork connected?   • Case and unit level?   • Wall plenum caulked? Level? Flashing?   • Drain connected?   NOTE: We strongly recommend that any servicing be   performed by a qualified individual.   For ease of service, the unit can be removed from   the case:   1. Unplug the power cord and disconnect the wall   thermostat connections.   • Wall thermostat wired correctly?   • Unit wired correctly?   2. Raise the top duct by turning all four case top duct   adjusting screws counterclockwise.   3. Remove the front case panel.   4. Remove the front and/or side case-to-unit   grounding screw, if present.   9 CONNECT POWER   1. If all the above items are correct, turn the power on   at the main service panel.   2. Turn the unit power switch, on the front of the unit,   to ON by pressing the top of the switch in.   5. Slide the unit out of the case.   22   Before You Call For Service…   GEAppliances.com   Troubleshooting Tips   Problem   Possible Causes   What To Do   Zoneline does   not start   The unit is   unplugged.   • Make sure the Zoneline plug is pushed completely   into the outlet.   The fuse is blown/circuit   breaker is tripped.   • Check the house fuse/circuit breaker box and replace   the fuse or reset the breaker.   The unit is waiting for   the compressor overload   protector to reset.   • This is normal. The Zoneline will start again after   it resets.   Power failure.   • There is a protective time delay (up to 3 minutes) to   prevent tripping of the compressor overload. For this   reason, the unit may not start normal heating or cooling   for 3 minutes after it is turned back on.   Zoneline does not cool   or heat as it should   Indoor airflow   is restricted.   • Make sure there are no curtains, blinds or furniture   blocking the air discharge grille or the return air grille.   Outdoor airflow is   restricted or recirculated.   • Make sure the architectural louver is not restricted.   This can cause the unit to cycle off due to the   compressor overload.   • Outdoor grille must have a minimum of 65% free area.   Non-GE grilles may be too restrictive for proper   performance. Consult your salesperson for assistance.   The air filter is dirty.   • Change the filter at least every 30 days.   See the Care and Cleaning–Air Filter section.   The room may have   been hot or cold.   • When the Zoneline is first turned on you need to   allow time for the room to cool down or warm up.   Outdoor air is   entering the room.   • Set the vent control to the CLOSE position.   Burning odor at the start Dust is on the surface   • This can cause a “burning” odor at the beginning of   the heating operation. This odor should quickly fade.   of heating operation   of the heating element.   The air is not always   cool or hot during   operation   The heat pump is not   producing hot air.   • This is normal. The heat pump will produce warm air   but not as hot as air produced when the higher-cost   electric heat is used.   The fan switch may be   set at continuous fan   • This causes the fan to blow room temperature air   even when the compressor or heater cycles off.   The continuous air movement provides better   overall temperature control.   The air does not feel   warm enough during   heating operation   The heat pump alone   produces air that feels   cooler than desired.   • Use the Electric Heat Option. This turns off the   heat pump and warms with electric heat only.   NOTE: Use of this option will result in increased energy   consumption.   23   Things that are normal.   Normal Operating Sounds   You may hear a pinging noise caused by water being   picked up and thrown against the condenser on   rainy days or when the humidity is high. This design   feature helps remove moisture and improve   efficiency.   You may hear relays click when the controls cycle on   and off or are adjusted to change the room   temperature.   “CLICK”   Water will collect in the base pan during high   humidity or on rainy days. The water may overflow   and drip from the outdoor side of the unit.   The indoor fan runs continuously when the unit is   operating in the cooling mode, unless the fan switch   behind the case front panel is set at fan cycle (up).   This will cause the fan to cycle on and off with the   compressor. You may also hear a fan noise stop   and start.   You may notice a few minutes delay in starting if you   try to restart the Zoneline too soon after turning it   off or if you adjust the thermostat right after the   compressor has shut off. This is due to a built-in   restart protector for the compressor that causes a   3-minute delay.   During the defrost cycle, both indoor and outdoor   fans stop and the compressor will operate in the   cooling mode to remove frost from the outdoor coil.   After defrost, the unit will restart in electric heat to   quickly warm the room to the desired comfort level.   SILENCE   To protect the compressor and prevent short   cycling, the unit is designed to run for a minimum   of 3 minutes after the compressor starts at any   thermostat setting.   COMPRESSOR   PROTECTION   24   Cut here   ✁ Please place in envelope and mail to:   General Electric Company   Warranty Registration Department   P.O. Box 32150   Louisville, KY 40232-2150   25   Consumer Product Ownership Registration   Dear Customer:   Thank you for purchasing our product and thank you for placing your confidence in us.   We are proud to have you as a customer!   Follow these three steps to protect your new appliance investment:   Complete and mail   your Consumer   After mailing the   registration below,   store this document   in a safe place. It   contains information   you will need should   you require service.   Our service number is   Read your Owner’s   Manual carefully.   It will help you   operate your new   appliance properly.   Product Ownership   Registration today.   Have the peace of   mind of knowing we   can contact you in   the unlikely event of   safety modification.   a 1 800.GE.CARES   2 3   (800.432.2737).   Model Number   Serial Number   Important: If you did not get a registration card with your   product, detach and return the form below to   ensure that your product is registered, or register   online at GEAppliances.com.   Cut here   ✁ Consumer Product Ownership Registration   Model Number   Serial Number   Mr. I Ms. I   Mrs. I   Miss I   First   Name   Last   Name   Street   Address   Apt. #   City   E-mail Address*   Zip   Code   State   Date Placed   In Use   Month   Phone   Number   _ _ Day   Year   * Please provide your e-mail address to receive, via e-mail, discounts, special offers and other important   communications from GE Appliances (GEA).   I Check here if you do not want to receive communications from GEA’s carefully selected partners.   General Electric Company   Louisville, Kentucky   GEAppliances.com   26   Vertical Zoneline Warranty.   All warranty service provided by our Factory Service Centers,   Staple your receipt here.   Proof of the original purchase   date is needed to obtain service   under the warranty.   or an authorized Customer Care® technician. To schedule service,   on-line, 24 hours a day, visit us at GEAppliances.com, or call   800.GE.CARES (800.432.2737). For service in Canada, call   1.800.361.3400.   For The Period Of:   GE Will Replace:   One Year   From the date of the   original purchase   Any part of the Zoneline which fails due to a defect in materials or workmanship. During this   full one-year warranty, GE will also provide, free of charge, all labor and on-site service to   replace the defective part.   Five Years   From the date of the   original purchase   Any part of the sealed refrigerating system (the compressor, condenser, evaporator and all   connecting tubing) which fails due to a defect in materials or workmanship. During this   full five-year sealed refrigerating system warranty, GE will also provide, free of charge, all labor   and on-site service to replace the defective part.   Five Years   From the date of the   original purchase   For the second through the fifth year from the date of original purchase, GE will replace   certain parts that fail due to a defect in materials or workmanship. Parts covered are fan   motors, switches, thermostats, heater, heater protectors, compressor overload, solenoids,   circuit boards, auxiliary controls, thermistors, frost controls, ICR pump, capacitors, varistors   and indoor blower bearing. During this limited four-year parts warranty, you will be   responsible for any labor or on-site service costs.   What GE Will Not Cover:   I Service trips to your site to teach you how to use the   product.   I Replacement of fuses or resetting of circuit breakers.   I Filters.   I Improper installation.   I Failure of the product resulting from modifications to   the product or due to unreasonable use including   failure to provide reasonable and necessary   maintenance.   I If you have an installation problem, or if the air   conditioner is of improper cooling or heating capacity   for the intended use, contact your dealer or installer.   You are responsible for providing adequate electrical   connecting facilities.   I Failure or damage resulting from corrosion due to   installation in a coastal environment, except for models   treated with special factory-applied anti-corrosion   protection as designated in the model number.   I In commercial locations, labor necessary to move the   unit to a location where it is accessible for service by an   individual technician.   I Damage to product caused by improper power supply   I Failure or damage resulting from corrosion due to   installation in an environment containing corrosive   chemicals.   voltage, accident, fire, floods or acts of God.   I Incidental or consequential damage caused by possible   defects with this air conditioner.   This warranty is extended to the original purchaser and any succeeding owner for products purchased for use   within the USA and Canada. In Alaska, the warranty excludes the cost of shipping or service calls to your site.   Some states or provinces do not allow the exclusion or limitation of incidental or consequential damages. This   warranty gives you specific legal rights, and you may also have other rights which vary from state to state or   province to province. To know what your legal rights are, consult your local, state or provincial consumer   affairs office or your state’s Attorney General.   Warrantor: General Electric Company. Louisville, KY 40225   27   Consumer Support.   GE Appliances Website   GEAppliances.com   Have a question or need assistance with your appliance? Try the GE Appliances Website 24 hours a day,   any day of the year! For greater convenience and faster service, you can now download Owner’s Manuals,   order parts, catalogs, or even schedule service on-line. You can also “Ask Our Team of Experts™”   your questions, and so much more...   Schedule Service   GEAppliances.com   Expert GE repair service is only one step away from your door. Get on-line and schedule your service at   your convenience 24 hours any day of the year! Or call 800.GE.CARES (800.432.2737) during normal   business hours.   Real Life Design Studio   GEAppliances.com   GE supports the Universal Design concept—products, services and environments that can be used by   people of all ages, sizes and capabilities. We recognize the need to design for a wide range of physical and   mental abilities and impairments. For details of GE’s Universal Design applications, including kitchen   design ideas for people with disabilities, check out our Website today. For the hearing impaired, please call   800.TDD.GEAC (800.833.4322).   Parts and Accessories   GEAppliances.com   Individuals qualified to service their own appliances can have parts or accessories sent directly to their   homes (VISA, MasterCard and Discover cards are accepted). Order on-line today, 24 hours every day or by   phone at 800.626.2002 during normal business hours.   Instructions contained in this manual cover procedures to be performed by any user. Other servicing generally   should be referred to qualified service personnel. Caution must be exercised, since improper servicing may cause   unsafe operation.   Contact Us   GEAppliances.com   If you are not satisfied with the service you receive from GE, contact us on our Website with all the details   including your phone number, or write to: General Manager, Customer Relations   GE Appliances, Appliance Park   Louisville, KY 40225   Register Your Appliance   GEAppliances.com   Register your new appliance on-line—at your convenience! Timely product registration will allow for   enhanced communication and prompt service under the terms of your warranty, should the need arise.   You may also mail in the pre-printed registration card included in the packing material.   Printed in China   |