| IMI CORNELIUS INC g One Cornelius Place g Anoka, MN 55303-6234   Telephone (800) 238-3600   Facsimile (612) 422-3246   Installation Manual   1550 UNIVERSAL BEER DISPENSER   (R-404A REFRIGERANT)   Part No. 569000246   August 11, 1998   Revised: June 11, 1999   Control Code A   THIS DOCUMENT CONTAINS IMPORTANT INFORMATION   This Manual must be read and understood before installing or operating this equipment   PRINTED IN U.S.A   IMI CORNELIUS INC; 1998–99   TABLE OF CONTENTS (cont’d)   Page   15   SERVICE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   PREPARING UNIT FOR SHIPPING, RELOCATING, OR STORING . . . . . . . . . .   ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   UNIT MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   CLEANING CONDENSER COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   CHECKING ICE WATER BATH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   CLEANING WATER TANK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   CLEANING AND SANITIZING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   15   15   18   18   19   19   20   DAILY CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20   SANITIZE BEER SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20   REPLENISHING CO2 SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   REPLENISHING BEER SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   CLEANING CO2 GAS CHECK VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   21   22   23   25   NO CO2 GAS PRESSURE ON BEER SYSTEMS. . . . . . . . . . . . . . . . . . . . . . . . . .   INSUFFICIENT CO2 GAS PRESSURE ON BEER SYSTEMS. . . . . . . . . . . . . . . .   DISPENSED BEER FLOW RATE TOO LOW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   DISPENSED BEER FLOW RATE TOO HIGH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   OFF-TASTE BEER (SOUR AND UNPALATABLE). . . . . . . . . . . . . . . . . . . . . . . . . .   DISPENSED BEER FLAT (DISAPPEARING FOAM). . . . . . . . . . . . . . . . . . . . . . . .   DISPENSED BEER TEMPERATURE TOO WARM . . . . . . . . . . . . . . . . . . . . . . . . .   EXCESSIVE FOAMING (WILD BEER) WHILE BEER IS BEING DISPENSED. .   COMPRESSOR DOES NOT OPERATE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   25   25   25   26   26   26   26   26   27   COMPRESSOR WILL NOT STOP AFTER GLYCOL (COOLANT) HAS BEEN   SUFFICIENTLY COOLED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   27   COMPRESSOR OPERATES CONTINUOUSLY BUT DOES NOT COOL   GLYCOL (COOLANT) SUFFICIENTLY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   27   27   28   29   CONDENSER FAN MOTOR NOT OPERATING. . . . . . . . . . . . . . . . . . . . . . . . . . . .   REFRIGERATION COMPRESSOR NOT OPERATING . . . . . . . . . . . . . . . . . . . . .   WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   LIST OF FIGURES   FIGURE 1. 1550 UNIVERSAL BEER DISPENSER . . . . . . . . . . . . . . . . . . . . . . . . .   FIGURE 2. FLOW DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   FIGURE 3. 1550 UNIVERSAL BEER DISPENSER . . . . . . . . . . . . . . . . . . . . . . . . .   FIGURE 4. DISPENSER COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   FIGURE 5. PARTS IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   FIGURE 6. BEER FAUCET ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   FIGURE 7. CO2 GAS CHECK VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   FIGURE 8. WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   4 5 12   16   17   18   22   24   LIST OF TABLES   TABLE 1. DESIGN DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   TABLE 2. LOOSE-SHIPPED PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   3 7 ii   569000246   SAFETY INFORMATION   Recognize Safety Information   This is the safety-alert symbol. When you see this   symbol on our machine or in this manual, be alert to   the potentially of personal injury.   Follow recommended precautions and safe operating   practices.   Understand Signal Words   DANGER   A signal word - DANGER, WARNING, OR CAUTION   is used with the safety-alert symbol. DANGER identi-   fies the most serious hazards.   WARNING   Safety signs with signal word DANGER or WARNING   are typically near specific hazards.   General precautions are listed on CAUTION safety   signs. CAUTION also calls attention to safety mes-   sages in this manual.   CAUTION   Follow Safety Instructions   Carefully read all safety messages in this manual and on your machine safety signs. Keep safety signs in   good condition. Replace missing or damaged safety signs. Learn how to operate the machine and how to   use the controls properly. Do not let anyone operate the machine without instructions. Keep your machine in   proper working condition. Unauthorized modifications to the machine may impair function and/or safety and   affect the machine life.   CO2 (Carbon Dioxide) Warning   CO Displaces Oxygen. Strict Attention must be observed in the prevention of CO (carbon dioxide)   2 2 gas leaks in the entire CO system. If a CO gas leak is suspected, particularly in a small area, im-   2 2 mediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to   high concentration of CO gas will experience tremors which are followed rapidly by loss of con-   2 sciousness and suffocation.   Shipping, Storing, Or Relocating Unit   CAUTION: Before shipping, storing, or relocating this Unit, the beer systems must be sanitized and   all sanitizing solution must be purged from the beer systems. A freezing ambient temperature will   cause residual water remaining inside the Unit to freeze resulting in damage to internal components   of the Unit.   1 569000246   THIS PAGE LEFT BLANK INTENTIONALLY   569000246   2 GENERAL INFORMATION   IMPORTANT: To the user of this manual – This manual is a guide for installing, operating, and main-   taining this equipment. Refer to the Table of Contents for page location for detailed information per-   taining to questions that arise during installation, operation, service, or maintenance of this equip-   ment.   GENERAL DESCRIPTION   The 1550 Universal Beer Dispenser (see Figure 1) is equipped with manually operated self-closing beer faucets.   The Unit that is not equipped with a handle and wheels may be installed free standing or under a counter or bar.   The Unit that is equipped with a handle and wheels makes it a mobile Unit. The refrigeration system is equipped   with a 3/4 H.P. compressor that is easily accessible for service and maintenance.   This Unit must be installed and serviced by a qualified Service Person. This Unit contains no User serviceable   parts.   Installation of LOOSE-SHIPPED PARTS (see Table 2), filling the water tank with water, connection to beer kegs   with regulated CO gas pressure, and connection to an electrical outlet with proper electrical requirements is all   2 that is required to set the Unit up for operation.   WARRANTY REFERENCE INFORMATION   Warranty Registration Date   (to be filled out by customer)   Unit Part Number:   Serial Number:   Install Date:   Local Authorized   Service Center:   DESIGN DATA   Table 1. Design Data   Unit Part Numbers:   See Unit Nameplate   Overall Dimensions:   Height   42-1/2 inches   21-3/4-inches   31–1/2 inches   Width   Depth (with drip tray)   Weights:   Shipping (1 Carton)   Dry Weight   With Water Tank Full of Water   Ice Bank Weight   189 pounds   170 pounds   403 pounds   120 pounds   Capacities:   Unit Water Bath (no ice bank) approx.   28 gallons   See Unit Nameplate   40° F to 100° F   569000246   Refrigerant Requirement   Ambient Operating Temperature   3 Table 1. Design Data (cont’d)   Electrical Requirements:   Operating Voltage   Current Draw   See Unit Nameplate   See Unit Nameplate   THEORY OF OPERATION   (see Figure 2)   A CO cylinder delivers carbon dioxide (CO ) gas through adjustable CO regulators to the beer kegs. When   2 2 2 dispensing valves are opened, CO gas pressure exerted upon the beer kegs pushes beer from the kegs,   2 through the Unit cooling coils, and on to the beer faucets resulting in cold beer being dispensed.   When the Unit power cord has been plugged into an electrical outlet and the main power switch on back of the   Unit (115 VAC, 60 Hz Units only) has been positioned in the ‘‘ON’’ (up) position, the compressor, condenser fan   motor, and agitator motor will start and begin forming an ice bank. When a full ice bank has been formed, the   compressor and condenser fan motor will stop but the agitator motor will continue to operate, circulating ice wa-   ter bath in the water tank. The water tank ice bank sensing bulb will cycle the compressor and condenser fan   motor on and off as required to maintain a full ice bank.   FIGURE 1. 1550 UNIVERSAL BEER DISPENSER   569000246   4 DISPENSING   FAUCET (2)   1550 UNIVERSAL   BEER DISPENSER   COIL NO. 1   1 2 LINE LEGEND   BEER   CO   2 COIL NO. 2   BEER KEG SECONDARY   CO REGULATOR (2)   2 COILS IN PARALLEL   DISPENSING   FAUCET (2)   BEER   SHUTOFF   VALVE   PRIMARY CO   REGULATOR   2 TEE   FITTING   1 2 CO GAS   CHECK VALVE (2)   2 CO SHUTOFF   VALVE (2)   2 TEE   FITTING   COIL NO. 1   SEE NOTE 2   SYRUP TANK   CO QUICK   DISCONNECT   2 COIL NO. 2   BEER KEG   TAPPER (2)   COILS IN SERIES   (561600074 ONLY)   SEE NOTE 1   1550 UNIVERSAL   BEER DISPENSER   SYRUP TANK   LIQUID QUICK   DISCONNECT   NO. 1   NO. 2   BEER KEG (2)   NOTE 1: THESE PARTS MUST BE INSTALLED IN UNIT BEER   INLET LINES CLOSE TO BEER KEG TAPPERS TO   FACILITATE SANITIZING THE BEER SYSTEMS.   CO CYLINDER   2 NOTE 2: THESE PARTS MUST BE INSTALLED IN THE CO   2 LINE TO FACILITATE CONNECTING CO TO SYRUP   2 TANK CONTAINING SANITIZING SOLUTION.   FIGURE 2. FLOW DIAGRAM   THIS PAGE LEFT BLANK INTENTIONALLY   569000246   6 INSTALLATION   This section covers unpacking and inspection, selecting location, installing Unit, preparing for operation, and   operation.   UNPACKING AND INSPECTION   NOTE: The Unit was thoroughly inspected before leaving the factory and the carrier has accepted and   signed for it. Any damage or irregularities should be noted at the time of delivery (or not later than 15   days from date of delivery) and immediately reported to the delivering carrier. Request a written inspec-   tion report from Claims Inspector to substantiate any necessary claim. File claim with the delivering   carrier, not with IMI Cornelius Inc.   Unpack Unit as follows:   1. After the Unit has been unpacked, remove shipping tape and other packing material.   2. Carefully inspect the Unit for evidence of damage. If evidence of damage or irregularities is present, file a   claim with the delivering carrier.   3. Unpack LOOSE-SHIPPED parts. Make sure all items are present and in good condition.   Table 2. Loose-Shipped Parts   Name   Item   No.   Part No.   186573039   186642000   319941000   700768   Qty.   1 1 Drip Tray   Cup Rest   2 1 3 Thread Rolling Screw, Hex Washer Hd; No. 8–32 By 1/2–in. Long   4 4 Knob, Beer Valve (Perlick)   2 SELECTING LOCATION   CAUTION: This Unit is intended for indoor installation only. Do not install this Unit in an   outdoor environment which would expose it to the outside elements.   IMPORTANT: Ambient operating temperature for the Unit Must not exceed 1005 F. Satisfactory   temperatures may be obtained using blowers, air conditioning, etc. Check local codes.   This Unit may be installed free standing or under a countertop or a bar.   1. Locate the Unit to provide the following minimum clearances:   A. A minimum of 12-inches clearance must be maintained above the Unit to the nearest obstruction .   B. 12–inches between back-side of the Unit and the wall.   C. 12-inches on each side of the Unit.   D. The front dide of the Unit must be unobstructed to allow air to enter the Unit.   WARNING: To avoid possible fatal electrical shock or serious injury to the operator, it is   required that a GFCI (ground fault circuit interrupt) be installed in the electrical circuit for   the 115 VAC, 60 Hz Units. It is required that an ELCB (earth leakage circuit breaker) be   installed in the electrical circuit for the 230 VAC, 50 Hz Units   7 569000246   2. The Unit must be installed near a properly grounded electrical outlet with proper electrical require-   ments.The electrical circuit must be properly fused (slow-blow type fuse) or the circuit must be connected   through an equivalent HACR circuit breaker.The electrical outlet must be accessible for ease of connecting   and disconnecting the Unit power cord. No other electrical equipment should be connected to this circuit.   REFER TO UNIT NAMEPLATE FOR THE REQUIRED POWER CIRCUIT OPERATING VOLTAGE, HZ,   AND THE MINIMUM CIRCUIT AMPACITY OF THE UNIT. ALL ELECTRICAL WIRING MUST CONFORM   TO NATIONAL AND LOCAL ELECTRICAL CODES.   3. Unit not equipped with handle and wheels.   Close to a permaneant drain to route drip tray drain hose, water tank drain hose, and the water tank   overflow tube.   INSTALLATION   WARNING: The Unit must be electrically grounded to avoid possible fatal electrical shock   or serious injury to the Operator. The Unit power cord is equipped with a three-prong plug.   If a three-hole (grounded) electrical outlet is not available, use an approved method to   ground the Unit.   SEALING UNIT TO FLOOR REQUIREMENT (UNIT NOT EQUIPPED WITH HANDLE AND WHEELS)   To comply with NSF International (NSF) requirements within the United States, the Unit must be sealed to the   floor and all access holes to the Unit base must be closed and sealed. Proceed as follows to seal Unit base to   the floor.   1. Place Unit in operating position.   2. Tilt Unit up to expose bottom of it’s base.   3. Liberally apply silastic sealant such as Dow Corning RTV 731 or equivalent around edges on bottom of the   Unit base.   NOTE: Do not move Unit after positioning or seal from Unit base to the floor will be broken.   4. Lower Unit into operating position to complete seal from Unit base to the floor.   5. Apply additional sealant around bottom of the Unit base. Seal must have a minimum radius of 1/2–inch to   prevent crevices and to insure a complete seal.   FILL WATER TANK AND START REFRIGERATION SYSTEM   1. Remove four screws securing the Unit top cover, then remove cover.   NOTE: Use low-mineral content water where a local water problem exist.   2. Make sure plug is secure in end of water tank drain hose inside the Unit.   3. Route water tank overflow tube out through hole in back of Unit cabinet to a permanent drain.   4. Fill water tank with clean water until water starts flowing from the overflow tube into the permanent drain.   5. Install Unit top cover and secure with four screws.   WARNING: The Unit must be electrically grounded to avoid possible fatal electrical shock   or serious injury to the operator. The Unit power cord is equipped with a three-prong plug.   If a three-hole (grounded) electrical outlet is not available, use an approved method to   ground the Unit.   569000246   8 6. Make sure the main power switch (115 VAC, 60 Hz Unit), located on back side of the Unit, is in the “OFF”   (down) position.   7. Plug Unit power cord into electrical outlet. If Unit is 115 VAC, 60 Hz, place main power switch on back side   of the Unit in “ON” position.   8. The compressor, condenser fan motor, and the agitator motor will start and begin forming an ice bank.   When a full ice bank has been formed, the compressor and condenser fan motor will stop but the agitator   motor will continue to operate circulating ice water bath in the water tank. Water will continue to drip from   the water tank overflow tube until a full ice bank has been formed, then the tube may be stored inside the   Unit.   CONNECTING CO2 SYSTEM TO BEER KEG TAPPERS   (see Figure 2)   WARNING: CO displaces oxygen. Strict attention must be observed in the prevention of   2 CO (carbon dioxide) gas leaks in the entire CO and soft drink system. If a CO gas leak is   2 2 2 suspected, particularly in a small area, immediately ventilate the contaminated area before   attempting to repair the leak. Personnel exposed to high concentration of CO gas will experience   2 tremors which are followed rapidly by loss of consciousness and suffocation.   Connect CO system to beer keg tappers as shown in Figure 2. DO NOT INSTALL BEER KEG   2 TAPPERS IN BEER KEGS AT THIS TIME.   CONNECTING BEER SOURCE SUPPLIES TO UNIT   (see Figure 2)   NOTE: The numbered Unit beer inlet lines are labeled to identify the beer faucets they serve. For exam-   ple: The line labeled No. “1” is connected to system that provides beer to be dispensed from the No. 1   beer faucet (No. 1 beer faucet is faucet on right side when facing front of the Unit).   1. All Unit beer inlet lines internal connections have been made at the factory. Connect Unit beer inlet lines to   beer keg tappers as shown in Figure 2. DO NOT INSTALL BEER KEG TAPPERS IN BEER KEGS AT   THIS TIME.   NOTE: A short length of tubing, with a syrup tank liquid quick disconnect on it’s end (tubing, liquid   quick disconnects, and tee fittings not provided), must be installed in the beer lines close to the beer   keg tappers as shown in Figure 2). Purpose of the liquid quick disconnects is to enable a syrup tank   containing sanitizing solution to be connected into the beer systems.   A length of tubing, with a syrup tank CO quick disconnect on it’s end (parts not provided), must be   2 installed in one of the beer kegs tappers CO source line as shown in Figure 2). Purpose of the CO   2 2 quick disconnect is to connect regulated CO gas pressure to the syrup tank containing sanitizing   2 solution.   2. The beer systems should be sanitized at this time as instructed in SERVICE AND MAINTENANCE section   of this manual.   PREPARING UNIT FOR OPERATION   (see Figure 2)   1. Make sure primary and secondary CO regulators assemblies adjustment screws are backed out until all   2 tension is relieved from the adjusting screws springs.   2. Make sure shutoff valves, located in CO lines connected between the secondary CO regulators and the   2 2 beer kegs tappers, are in the closed positions.   9 569000246   3. Open the CO cylinder shutoff valve slightly to allow the primary CO regulator to fill with gas, then open   2 2 the valve fully to back-seat the valve. Back-seating the valve prevents leakage around the valve shaft.   4. Adjust the primary CO regulator by loosening the regulator adjusting screw lock nut, then turn the adjust-   2 ing screw to the right (clockwise) until the gage reads 50-PSI. Tighten the adjustment screw lock nut after   adjustment has been completed.   5. Adjust beer kegs secondary CO regulators as follows:   2 The beer kegs secondary CO regulators pressures adjustments require calculations of each beer system   2 total beer system pressure. The total beer system pressure, required to push beer from the beer keg to the   dispensing faucet, is the result of computing the length of the beer line of a certain size, vertical line lift, and   internal beer keg pressure. The internal beer keg pressure differs from one beer brand to another. Contact   your local Beer Distributor for the proper secondary CO regulators pressure settings. Adjust the secon-   2 dary CO regulators by loosening the adjusting screws lock nuts, then turn the adjusting screws to the right   2 (clockwise) until regulators gages register the recommended pressures. Tighten the adjustments screws   lock nuts after adjustments have been completed.   6. Install tappers in the beer kegs.   7. Open shutoff valves located in the CO lines connected between the secondary CO regulators and the   2 2 beer kegs tappers.   UNIT OPERATION   8. Dispense beer from the beer faucets until all air is purged from the beer systems.   9. Check beer systems for leaks and repair if evident.   10. Adjust beer faucets for beer flow rate as instructed in SERVICE AND MAINTENANCE section of this   manual.   569000246   10   OPERATOR’S INSTRUCTIONS   This section covers operating controls, pre-operation check, Unit operation, and maintenance procedures that   may be performed by the Operator.   IMPORTANT: Only qualified Personnel should service internal components of the Unit.   PROPER BEER STORAGE   Beer is a perishable product that can be materially changed by improper handling. Undesirable dispensed beer   can be created by improper cooling of the beer or lack of cleaning/sanitizing the beer systems. Proper tempera-   ture control of stored beer is important. It helps retard growth of mold, yeast, and bacteria that are non-toxic but   do affect taste and appearance of the dispensed beer. These organisms can be satisfactorily controlled by   maintaining stored beer within a specified temperature range and regularly sanitizing the beer systems. Stored   beer temperature should be maintained at 33° F to 40° F.   OPERATING CONTROLS   (see Figure 3)   BEER FAUCET   The beer faucet lever needs only be pulled forward to dispense beer, then close faucet when cup or glass is full.   UNIT POWER SWITCH (115 VAC, 60 HZ UNIT ONLY)   The Unit power switch, located on back of the Unit. must be in the “ON” (up) position before Unit will operate.   UNIT OPERATION   1. If applicable, make sure drip tray drain hose is routed to a waste container or drain.   2. Make sure Unit power switch (115 VAC, 60 Hz Unit only), located on back side of the Unit, is in the “ON”   (up) position.   3. Hold cup or glass under the beer faucet. Pull beer faucet lever forward and dispense until cup or glass is   full, then close faucet.   DAILY PRE-OPERATION CHECK   1. Make sure CO cylinder regulator assembly 1800 psi gage indicator is not in shaded (“change CO cylin-   2 2 der”) portion of the dial. If so, CO cylinder is almost empty and must be replaced as instructed.   2 2. Be sure beer supply is sufficient. If not, replenish beer supply as instructed.   11   569000246   BEER FAUCET (2)   UNIT POWER SWITCH   DRIP TRAY/CUP REST   (115 VAC, 60 HZ UNIT ONLY)   FIGURE 3. 1550 UNIVERSAL BEER DISPENSER   OPERATING CLEARANCES   Check area in front, back, sides, and above the Unit for obstructions. These areas must be kept clear at all   times. Listed below are the minimum clearances that must be maintained.   A. Clearance above the Unit ––––––––––––––––––––––––––––– 12 inches to nearest obstruction.   B. Clearance back of Unit ––––––––––––––––––––––––––––––– 12 inches to nearest obstruction.   C. Clearance on sides of Unit –––––––––––––––––––––––––––––12 inches to nearest obstruction.   D. Clearance on front of Unit ––––––––––––––––––––––––––––– Open   ADJUSTMENTS   ADJUSTING CO2 REGULATORS   (see Figure 2)   The CO regulators should be periodically checked for proper pressure settings and if necessary, be adjusted   2 by a qualified Service Person.   ADJUSTING DISPENSED BEER FLOW RATE   Dispensed beer flow rate of the dispensing faucets should be periodically checked and if necessary, be adjusted   by a qualified Service Person.   COOLING UNIT MAINTENANCE   CLEANING CONDENSER COIL   NOTE: Air circulation through the condenser coil, required to cool the coil, is drawn in through grille   on Unit front panel and is exhausted out through grilles on sides and back of the Unit. Restricting air   flow through the condenser coil will decrease cooling efficiency of the Unit.   Area in front, sides, and back of the Unit must be kept free of obstructions at all times which would   prevent air flow in and out of the Unit.   569000246   12   An excessive accumulation of dust, lint, and grease on the condenser coil will restrict air flow through the coil   which will decrease cooling efficiency of the Unit. The Unit condenser coil should be periodically cleaned to   maintain cooling efficiency of the Unit. Contact a qualified Service Person to clean the Unit condenser coil.   CHECKING ICE WATER BATH   A gurgle heard from the Unit while it is operating, indicates the water level in the water tank is low and more   water should be added to the tank. Contact a qualified Service Person to replenish the water tank water supply   and if necessary, also clean the water tank.   CLEANING AND SANITIZING   DAILY CLEANING   The Unit should be cleaned daily as instructed SERVICE AND MAINTENANCE section of this manual.   SANITIZING BEER SYSTEMS   The beer systems (tappers, beer lines, Unit beer cooling coils, and the beer faucets) should be completely sani-   tized at least every two weeks as instructed in SERVICE AND MAINTENANCE section of this manual.   REPLENISHING CO2 SUPPLY   WARNING: CO displaces oxygen. Strict attention must be observed in the prevention of   2 CO (carbon dioxide) gas leaks in the entire CO and soft drink system. If a CO gas leak is   2 2 2 suspected, particularly in a small area, immediately ventilate the contaminated area before   attempting to repair the leak. Personnel exposed to high concentration of CO gas will experience   2 tremors which are followed rapidly by loss of consciousness and suffocation.   NOTE: When indicator on CO cylinder regulator assembly 1800 psi gage is in shaded (‘‘change CO   2 2 cylinder’’) portion of dial, CO cylinder is almost empty and should be replaced.   2 The CO supply should be checked daily and if necessary, replenished as instructed.   2 REPLENISHING BEER SUPPLY   The beer supply should be checked periodically and if necessary, replenished as instructed.   CLEANING CO2 SYSTEM GAS CHECK VALVES   (see Figure 2)   The CO gas check must be inspected and serviced as instructed at least once a year under normal conditions   2 and after any servicing or disruption of the CO system.   2 13   569000246   THIS PAGE LEFT BLANK INTENTIONALLY   569000246   14   SERVICE AND MAINTENANCE   This section describes the service and maintenance procedures to be performed on the Unit.   IMPORTANT: Only qualified Personnel should service the Unit internal components or electrical wiring.   WARNING: Disconnect electrical power from the Unit to prevent personnel injury before   attempting any internal maintenance. Only qualified personnel should service the internal   components or electrical wiring.   PREPARING UNIT FOR SHIPPING, RELOCATING, OR STORING   CAUTION: Before shipping, relocating, or storing the Unit, the beer cooling coils must be   sanitized, all sanitizing solution must be purged from the beer coils, the ice bank must be   melted, and all water must be drained from the water tank. A freezing ambient environment   will cause residual water remaining inside the Unit to freeze resulting in damage to internal   components of the Unit.   PERIODIC INSPECTION   1. Check Unit condenser coil (see Figure 5) for accumulation of dust, lint, or grease and if necessary, clean   the coil as instructed. Restriction of air flow through the condenser coil will decrease cooling efficiency of   the Unit.   2. Check area in front, back, sides, and above the Unit for obstructions. These areas must be kept clear at all   times. Listed below are the minimum clearances that must be maintained.   A. Clearance above the Unit ––––––––––––––––––––––––––––– 12 inches to nearest obstruction.   B. Clearance back of Unit ––––––––––––––––––––––––––––––– 12 inches to nearest obstruction.   C. Clearance on sides of Unit –––––––––––––––––––––––––––––12 inches to nearest obstruction.   D. Clearance on front of Unit ––––––––––––––––––––––––––––– Open   3. Check beer faucets for dripping that indicates leaking and repair as necessary.   ADJUSTMENTS   ADJUSTING CO REGULATORS   2 (see Figure 2)   NOTE: To readjust CO regulator to a lower setting, loosen adjusting screw lock nut, then turn screw to   2 the left (counterclockwise) until pressure gage reads 5-psi lower than new setting will be. Turn adjust-   ing screw to the right (clockwise) until gage registers new setting, then tighten lock nut.   Adjusting Primary CO Regulator.   2 Adjust primary CO regulator by loosening regulator adjusting screw lock nut, then turn adjusting screw to the   2 right (clockwise) until gage registers 50-psi. Tighten adjustment screw lock nut after adjustment has been com-   pleted.   15   569000246   UNIT BEER INLET   LINES (2)   POWER   CORD   UNIT POWER   SWITCH   (115 VAC UNIT ONLY)   DRIP TRAY   DRAIN HOSE   PLUG   WATER TANK   OVERFLOW TUBE   WATER TANK   DRAIN HOSE   TOP COVER   COVER RETAINING   SCREW (4)   BEER FAUCET (2)   CUP REST   VALVE TRIM   PANEL   DRIP TRAY   DRAIN HOSE   RETAINING   SCREW (4)   ACCESS GRILLE (4)   DRIP TRAY   AIR INTAKE   FIGURE 4. DISPENSER COMPONENTS   569000246   16   BEER INLET   LINES (2)   ELECTRICAL   CONTROL BOX   POWER CORD   TERMINAL   BLOCK   RETAINING   SCREW   CONDENSER   COIL   UNIT POWER   SWITCH   (115 VAC   CONDENSER   FAN MOTOR   UNIT ONLY)   ACCESS   GRILLE   COMPRESSOR   FIGURE 5. PARTS IDENTIFICATION   17   569000246   Adjusting Beer Kegs Secondary CO Regulators.   2 Beer kegs secondary CO regulators pressures adjustments require calculations of each beer system total beer   2 system pressure. Total beer system pressure, required to push beer from keg to faucet, is the result of comput-   ing length of beer line of a certain size, vertical line lift, and internal keg pressure. Internal keg pressure differs   from one beer brand to another   Contact your local Beer Distributor for proper secondary CO regulators pressure settings. Adjust secondary   2 CO regulators by loosening adjusting screws lock nuts, then turn adjusting screws to the right (clockwise) until   2 regulator gages register recommended pressures. Tighten adjustments screws lock nuts after adjustments have   been completed.   Adjusting Dispensed Beer Flow Rate.   (see Figure 6)   Adjust the beer flow rate at approximately 2-ounces per second by rotating the beer faucet compensator adjust-   ing screw to the left (counterclockwise) for a higher beer flow rate or to the right (clockwise) for a lower beer   flow rate.   CORNELIUS BEER FAUCET   PERLICK BEER FAUCET   BEER FLOW RATE   ADJUSTMENT   BEER FLOW RATE   ADJUSTMENT   FIGURE 6. BEER FAUCET ADJUSTMENT   UNIT MAINTENANCE   CLEANING CONDENSER COIL   (see Figure 5)   NOTE: Air circulation through the condenser coil, required to cool the coil, is drawn in through grille   on Unit front panel and is exhausted out through grilles on sides and back of the Unit. Restricting air   flow through the condenser coil will decrease cooling efficiency of the Unit.   Area in front, sides, and back of the Unit must be kept free of obstructions at all times which would   prevent air flow in and out of the Unit.   An excessive accumulation of dust, lint, and grease on the condenser coil will restrict air flow through the coil   which will decrease cooling efficiency of the Unit. The Unit condenser coil should be periodically cleaned by per-   forming the following:   1. Unplug Unit power cord from electrical outlet.   569000246   18   2. Remove four screws securing air intake grille on the Unit front panel, then remove the grille.   3. Vacuum or use a soft brush to clean the condenser coil. If available, use low-pressure compressed air.   4. Install air intake grille on the Unit and secure with four screws.   5. Plug Unit power cord into electrical outlet.   CHECKING ICE WATER BATH   A “gurgle’ heard from the Unit, indicates water level in the water tank is low and more water should be added for   maximum product cooling. Before adding more water to the water tank, the ice water bath and the ice bank   should be checked for cleanliness and the water tank components checked for excessive mineral deposit   build-up.   1. Unplug Unit power cord from electrical outlet.   2. Remove four screws securing the Unit top cover, then remove cover.   3. Check condition of the ice water bath and the ice bank. The ice water bath should be clear and the ice   bank should be free of foreign particles.   4. Check agitator motor shaft and ice bank sensing bulb for excessive mineral deposit build-up.   5. If cleaning of water tank is necessary, refer to CLEANING WATER TANK in this section for cleaning   procedure.   6. Make sure end of water tank overflow tube is placed in a waste container. Fill water tank with clean water   until water starts flowing from overflow tube into the waste container. USE A LOW-MINERAL-CONTENT   WATER WHERE A LOCAL WATER PROBLEM EXIST.   7. Install Unit top cover and secure with four screws.   8. Plug Unit power cord into electrical outlet. After water has stopped dripping from the water tank overflow   tube, remove tube from the waste container and place back inside the Unit.   CLEANING WATER TANK   NOTE: The ice water bath should be changed as often as necessary to keep the water tank clean. A   convenient time to perform this operation is at the time the Unit is being sanitized. To save time, water   can be drained from the water tank while the Unit is being sanitized.   1. Unplug Unit power cord from electrical outlet.   2. Remove screws securing the Unit top cover, then remove cover.   3. Remove four screws securing either the side or the back access grille, then remove the grille.   4. Route water tank drain hose out hole in back of the Unit to a waste container or to a drain.   5. Remove plug from end of the drain hose and allow water to drain from the water tank.   NOTE: If ice bank is clear and contains no foreign particles, it does not have to be melted down. Skip   steps 6, 7, and 8 and proceed with step 9 .   6. If ice bank is dirty, allow it to melt. Hot water may be used to speed up melting.   CAUTION: Never use an ice pick or other instrument to remove ice from the evaporator coil.   Such practice can result in a punctured refrigerant circuit or damage to the water tank.   7. Wash inside of the water tank with a mild soap solution.   19   569000246   8. Using a fiber brush, carefully clean mineral deposit build-up from the agitator motor shaft and the ice bank   sensing bulb.   9. Rinse all parts and flush water tank with clean water.   10. Install plug in end of the water tank drain hose, then place drain hose back inside the Unit.   11. Place end of the Unit water tank overflow tube in a waste container.   12. Fill water tank with clean water until water starts flowing from the overflow tube into the waste container.   USE A LOW-MINERAL-CONTENT WATER WHERE A LOCAL WATER PROBLEM EXIST.   13. Install Unit top cover and secure with four screws.   14. Plug Unit power cord into electrical outlet. Make sure compressor, condenser fan motor, and agitator motor   are operating.   15. After water has stopped dripping from the water tank overflow tube, remove tube from the waste container,   then place tube back inside the Unit.   16. Install access grille on the Unit and secure with screws.   CLEANING AND SANITIZING   DAILY CLEANING   NOTE: A drip tray that does not have a drain hose routed to a waste container or a permanent drain   must be removed from the Unit and be thoroughly cleaned. A drip tray that has a drip tray drain hose   routed to a waste container or a permanent drain may be cleaned in place on the Unit as follows:   1. Remove cup rest from the drip tray.   2. Wash drip tray in place on the Unit, then rinse drip tray with hot water allowing water to drain out through   the drip tray drain hose.   3. Wash cup rest, then rinse the cup rest with clean water. Install cup rest in the drip tray.   4. Clean all external surfaces of the Unit with a sponge. Rinse out the sponge with clean water, then wring   excess water out of the sponge and wipe off all external surfaces of the Unit. Wipe Unit dry with a clean   soft cloth. DO NOT USE ABRASIVE-TYPE CLEANERS.   SANITIZE BEER SYSTEMS   IMPORTANT: Only qualified Personnel should perform the sanitizing procedure on the beer system.   The beer systems (tappers, beer lines, Unit beer cooling coils, and the beer faucets) should be completely sani-   tized at least every two weeks using a non-scented household liquid bleach such as Hilex or Chlorox containing   a 5.25% sodium hypochlorite concentration. Proceed as follows to sanitize the beer system:   1. Close CO shutoff valve in beer keg tapper CO line, then close beer shutoff valve in beer keg tapper beer   2 2 line on beer system that will be sanitized.   2. Remove beer keg tapper from the beer keg.   3. Using a clean empty syrup tank, prepare a full tank of non-scented liquid dishwasher detergent solution by   using 70° F (21° C) to 100° F (38° C) potable water and 0.5 oz. (15 ml) of liquid dishwasher detergent   (such as Joy, Ivory, etc.) to one gallon of potable water. Shake tank containing detergent solution to thor-   oughly mix the solution.   4. Connect CO line to tank containing detergent solution.   2 569000246   20   5. Connect tank containing detergent solution into the beer system.   6. Place waste container under applicable beer faucet.   7. Activate the beer faucet to permit detergent solution to purge beer out of the line, coil, and the beer faucet.   Continue to dispense until all beer has been purged from the beer system and only detergent solution is   dispensed from the beer faucet.   8. Disconnect tank containing detergent solution from the beer system.   9. Using a clean syrup tank, prepare sanitizing solution using 70° F (21° C) to 100° F (38° C) potable water   and 0.5 oz. (15 ml) of household liquid bleach such as non-scented Hi-Lex or Chlorox that contains a   5.25 % sodium hypochlorite concentration to one gallon of potable water. This mixture must not exceed   200 PPM of chlorine. Shake tank containing sanitizing solution to thoroughly mix the solution.   10. Connect tank containing sanitizing solution into the beer system.   11. Place waste container under the applicable beer faucet.   12. Activate the beer faucet to permit sanitizing solution to purge detergent solution out of the line, coil, and the   beer faucet. Continue to dispense until all detergent solution has been purged from the beer system and   until only sanitizing solution is dispensed.   13. Allow sanitizing solution to remain in the beer system for not less than 10-minutes or for more than 15-min-   utes.   14. Disconnect tank containing sanitizing solution from the beer system.   WARNING: Flush all sanitizing solution from the beer system as instructed. Residual   sanitizing solution left in the beer system could create a health hazard.   15. Connect tank containing potable water into the beer system.   16. Place waste container under the applicable beer faucet.   17. Activate the beer faucet to permit potable water to purge sanitizing solution out of the beer system. Contin-   ue to dispense until all sanitizing has been purged from the beer system and only potable water is   dispensed.   18. Disconnect tank containing potable water from the beer system.   19. Place the beer keg tapper in a pail container containing sanitizing. Completely wash the beer keg tapper in   the sanitizing solution, then thoroughly rinse the tapper with potable water.   20. Install beer keg tapper in beer keg.   21. Open CO shutoff valve in beer keg tapper CO line, then open beer shutoff valve in beer keg tapper beer   2 2 line.   22. Place waste container under applicable beer faucet. Dispense from beer faucet until all potable water has   been purged from the beer system and only beer is dispensed.   23. Repeat preceding steps 1 through 22 to sanitize the other beer system.   REPLENISHING CO2 SUPPLY   NOTE: When indicator on CO cylinder regulator assembly 1800 psi gage is in shaded (‘‘change CO   2 2 cylinder’’) portion of dial, CO cylinder is almost empty and should be replaced.   2 CAUTION: Wear protective eyewear to avoid injury from gas-driven particles.   21   569000246   WARNING: CO displaces oxygen. Strict attention must be observed in the prevention of   2 CO (carbon dioxide) gas leaks in the entire CO and soft drink system. If a CO gas leak is   2 2 2 suspected, particularly in a small area, immediately ventilate the contaminated area before   attempting to repair the leak. Personnel exposed to high concentration of CO gas will experience   2 tremors which are followed rapidly by loss of consciousness and suffocation.   1. Fully close (clockwise) CO cylinder valve.   2 2. Slowly loosen CO regulator assembly coupling nut allowing CO pressure to escape, then remove regula-   2 2 tor assembly from empty CO cylinder.   2 3. Unfasten safety chain and remove empty CO cylinder.   2 WARNING: To avoid personal injury and/or property damage, always secure CO cylinder   2 in an upright position with safety chain to prevent it from falling over. Should the shutoff   valve become accidentally broken off, CO cylinder can cause serious personal injury.   2 4. Position CO cylinder and secure with safety chain.   2 5. Make sure gasket is in place inside CO regulator coupling nut, then install regulator on CO cylinder.   2 2 6. Open (counterclockwise) CO cylinder valve slightly to allow lines to slowly fill with gas, then open valve   2 fully to back-seat valve. (Back-seating valve prevents leakage around valve shaft).   7. Check CO connections for leaks.   2 REPLENISHING BEER SUPPLY   (see Figure 2)   1. Close CO and beer line shutoff valves for the empty beer keg.   2 2. Remove beer keg tapper from the empty beer keg.   3. Make sure beer keg tapper and top of the full beer keg are clean, then then install tapper in the keg.   4. Open CO and beer line shutoff valves.   2 QUAD RING   183294-000   BALL   183296-000   SPRING   183297000   RETAINER   183298000   BODY   183295000   *Quad ring seal must be replaced each   time check valve is serviced.   FIGURE 7. CO GAS CHECK VALVE   2 569000246   22   CLEANING CO2 GAS CHECK VALVE   (see Figures 2 and 7)   CO gas check valves must be inspected and serviced at least once a year under normal conditions and after   2 any servicing or disruption of the CO system. ALWAYS REPLACE QUAD RING SEALS EACH TIME CHECK   2 VALVES ARE SERVICED.   23   569000246   FIGURE 8. WIRING DIAGRAM   569000246   24   TROUBLESHOOTING   IMPORTANT: Only qualified Personnel should service internal components or electrical wiring.   WARNING: If repairs are to be made to the beer system, close shutoff valve in applicable   beer inlet line, then relieve system pressure before proceeding. If repairs are to be made to   the CO system, shut off CO supply, shut off beer keg tappers CO lines shutoff valves,   2 2 2 then relieve system pressure before proceeding. If repairs are to be made to the refrigeration   system, make sure electrical power is disconnected from the Unit.   Trouble   TROUBLESHOOTING CO SYSTEM   Probable Cause   Remedy   2 NO CO GAS PRESSURE ON A. Empty CO cylinder.   A. Replenish CO supply as   2 2 2 BEER SYSTEMS.   instructed.   B. CO shutoff valve closed at   B. Open CO shutoff valve at CO   2 2 2 CO cylinder.   cylinder.   2 C. CO shutoff valves in lines   C. Open CO shutoff valves in lines   2 2 leading to beer kegs tappers   closed.   leading to beer kegs tappers.   D. CO regulators improperly   D. Adjust CO regulators as   2 2 adjusted.   instructed.   E. Leak in CO system.   E. Repair leaks in CO system.   2 2 INSUFFICIENT CO GAS   A. Empty CO cylinder.   A. Replenish CO supply as   2 2 2 PRESSURE ON BEER   SYSTEMS.   instructed.   B. CO shutoff valve in CO   B. Open CO shutoff valve all the   2 2 2 system partially closed.   way.   C. CO regulator improperly   C. Adjust CO regulator as   2 2 adjusted.   instructed.   D. Leak in CO system.   D. Repair leak in CO system.   2 2 Trouble   Probable Cause   Remedy   TROUBLESHOOTING BEER SYSTEM   DISPENSED BEER FLOW   RATE TOO LOW.   A. Beer faucet not properly   adjusted for beer flow rate.   A. Adjust dispensed beer flow rate   as instructed.   B. Insufficient CO /gas pressure   B. Refer to ‘‘INSUFFICIENT CO   GAS PRESSURE ON BEER   SYSTEM’’ in this section.   2 2 on beer system.   25   569000246   Trouble   Probable Cause   Remedy   DISPENSED BEER FLOW   RATE TOO HIGH.   A. Beer faucet not properly   adjusted for beer flow rate.   A. Adjust dispensed beer flow rate   as instructed.   OFF-TASTE BEER (SOUR   AND UNPALATABLE).   A. Beer system needs to be   cleaned and sanitized.   A. Clean and sanitize beer system   as instructed.   B. Beer spoilage (secondary   fermentation) due to   B. Rotate stock. Make sure oldest   beer in stock is used first.   inadequate beer storage   C. Mixed beers.   C. Clean and sanitize beer system,   then install new beer supply.   DISPENSED BEER FLAT   (DISAPPEARING FOAM).   A. Dirty beer glasses.   A. Glasses must be free of all film.   B. CO regulators improperly   B. Adjust CO regulators as   2 2 adjusted.   instructed.   DISPENSED BEER   TEMPERATURE TOO WARM   A. Electrical power Unit turned   off.   A. Restore electrical power to Unit.   B. Unit power switch (115 VAC,   B. Make sure power switch is turned   60 Hz Unit only) turned “OFF”.   “OFF”.   C. Electrical circuit fuse blown or   circuit breaker tripped.   C. Replace blown fuse or reset   circuit breaker.   D. Glycol circulating pump power D. Make sure circulating pump   switch in ‘‘OFF’’ (down)   position or inoperable pump or   motor.   power switch is in ‘‘ON’’ (up)   position or repair or replace pump   or motor.   E. Cooling Unit POWER switch in E. Place Cooling Unit POWER   ‘‘OFF’’ (down) position.   switch in ‘‘ON’’ (up) position.   F. Inoperable Cooling Unit   refrigeration system.   F. Repair Cooling Unit refrigeration   system.   EXCESSIVE FOAMING (WILD A. Dispensed beer flow rate too   A. Beer flow rate should be   approximately 2-ounces per   second. Adjust beer flow rate as   instructed.   BEER) WHILE BEER IS   BEING DISPENSED.   high.   B. Dispensed beer temperature   too warm.   B. Refer to ‘‘DISPENSED BEER   TEMPERATURE TOO WARM’’ in   this section.   569000246   26   Trouble   Probable Cause   Remedy   TROUBLESHOOTING COOLING UNIT REFRIGERATION SYSTEM   COMPRESSOR DOES NOT   OPERATE.   A. Glycol (coolant) sufficiently   cooled.   A. Refrigeration not called for.   B. Cooling Unit POWER switch in B. Place Cooling Unit POWER   ‘‘OFF’’ (down) position.   switch in ‘‘ON’’ (up) position.   C. No power source (blown fuse   or tripped circuit breaker).   C. Replace blown fuse or reset   circuit breaker.   D. Low voltage.   D. Voltage must be at least 103 VAC   at compressor terminals when   compressor is trying to start.   E. Loose, disconnected, or   broken wiring.   E. Tighten connections or replace   broken wiring.   F. Overload protector cut out;   overheated compressor.   Condenser fan motor not   operating as required.   F. Compressor will cool enough to   restart. Refer to ‘‘CONDENSER   FAN MOTOR NOT OPERATING’’   in this section;   G. Inoperative overload protector G. Replace inoperative part.   or start relay.   H. Inoperative contactor.   I. Inoperative control board.   J. Evaporator or condenser outlet J. Replace inoperative temperature   H. Replace contactor.   I. Replace control board.   temperature sensor   inoperative (open).   sensor.   K. No voltage to control board.   K. Check for loose or broken wiring.   Check transformer for 24 ± VAC   output.   L. Inoperative compressor.   L. Replace compressor.   COMPRESSOR WILL NOT   STOP AFTER GLYCOL   (COOLANT) HAS BEEN   SUFFICIENTLY COOLED.   A. Glycol tank temperature   control inoperative.   A. Replace temperature control   sensor.   B. Circuit board inoperative.   B. Replace circuit board.   COMPRESSOR OPERATES   CONTINUOUSLY BUT DOES   NOT COOL GLYCOL   A. Cooling Unit located in   excessively hot area.   A. Refer to IMPORTANT note at   start of SELECTING COOLING   UNIT LOCATION in   (COOLANT) SUFFICIENTLY.   INSTALLATION SECTION.   B. Air circulation through Cooling B. Clean air filter on back of Cooling   Unit restricted.   Unit as instructed.   CONDENSER FAN MOTOR   NOT OPERATING.   A. Jumper cord loose or   disconnected from condenser   fan motor or compressor   A. Tighten connections or replace   cord.   terminals. Broken wire in cord.   B. Fan blade obstructed.   B. Remove obstruction.   C. Inoperative condenser fan   motor.   C. Replace condenser fan motor.   NOTE: If overload protector cuts out compressor,condenser fan motor will continue to operate;   otherwise, troubleshooting condenser fan motor problems are same as for ‘‘COMPRESSOR DOES NOT   OPERATE’’ paragraph plus the preceding:   27   569000246   Trouble   Probable Cause   Remedy   REFRIGERATION   COMPRESSOR NOT   OPERATING   A. Refrigeration system   overheated. Clogged   A. Clean air filter as instructed.   condenser coil air intake filter.   B. Refrigeration system   overheated. Condenser fan   motor not operating.   B. Replace condenser fan motor.   C. Glycol tank temperature   control sensor inoperable.   Loose or broken sensor   electrical wire.   C. Check or repair sensor electrical   wire.   D. Glycol tank temperature   control sensor inoperable,   Inoperable sensor.   D. Replace sensor.   569000246   28   IMI CORNELIUS INC.   ONE CORNELIUS PLACE   ANOKA, MN. 55303–6234   TELEPHONE (800) 238–3600   FACSIMILE (612) 422–3232   WARRANTY   IMI Cornelius Inc. warrants that all equipment and parts are free from defects in material and workman-   ship under normal use and service. For a copy of the warranty applicable to your Cornelius product, in   your country, please write, fax or telephone the IMI Cornelius office nearest you. Please provide the   equipment model number and the date of purchase.   IMI Cornelius Offices   AUSTRALIA D P.O. 210, D RIVERWOOD, D NSW 2210, AUSTRALIA D (61) 2 533 3122 D FAX (61) 2 534 2166   AUSTRIA D AM LANGEN FELDE 32 D A-1222 D VIENNA, AUSTRIA D (43) 1 233 520 D FAX (43) 1-2335-2930   BELGIUM D BOSKAPELLEI 122 D B-2930 BRAASCHAAT, BELGIUM D (32) 3 664 0552 D FAX (32) 3 665 2307   BRAZIL D RUA ITAOCARA 97 D TOMAS COELHO D RIO DE JANEIRO, BRAZIL D (55) 21 591 7150 D FAX (55) 21 593 1829   ENGLAND D TYTHING ROAD ALCESTER D WARWICKSHIRE, B49 6 EU, ENGLAND D (44) 789 763 101 D FAX (44) 789 763 644   FRANCE D 71 ROUTE DE ST. DENIS D F-95170 DEUIL LA BARRE D PARIS, FRANCE D (33) 1 34 28 6200 D FAX (33) 1 34 28 6201   GERMANY D CARL LEVERKUS STRASSE 15 D D-4018 LANGENFELD, WEST GERMANY D (49) 2173 7930 D FAX (49) 2173 77 438   GREECE D 488 MESSOGION AVENUE D AGIA PARASKEVI D 153 42 D ATHENS, GREECE D (30) 1 600 1073 D FAX (30) 1 601 2491   HONG KONG D 1104 TAIKOTSUI CENTRE D 11-15 KOK CHEUNG ST D TAIKOKTSUE, HONG KONG D (852) 789 9882 D FAX (852) 391 6222   ITALY D VIA PELLIZZARI 11 D 1-20059 D VIMARCATE, ITALY D (39) 39 608 0817 D FAX (39) 39 608 0814   NEW ZEALAND D 20 LANSFORD CRES. D P.O. BOX 19-044 AVONDALE D AUCKLAND 7, NEW ZEALAND D (64) 9 8200 357 D FAX (64) 9 8200 361   SINGAPORE D 16 TUAS STREET D SINGAPORE 2263 D (65) 862 5542 D FAX (65) 862 5604   SPAIN D POLIGONO INDUSTRAIL D RIERA DEL FONOLLAR D E-08830 SANT BOI DE LLOBREGAT D BARCELONA, SPAIN D (34) 3 640 2839 D FAX (34) 3 654 3379   USA D ONE CORNELIUS PLACE D ANOKA, MINNESOTA D (612) 421-6120 D FAX (612) 422-3255   29   569000246   IMI CORNELIUS INC.   CORPORATE HEADQUARTERS:   One Cornelius Place   Anoka, Minnesota 55303-6234   (612) 421-6120   (800) 238-3600   301137000   |