| 48VT(N)---A   Performancet 14 SEER Single---Packaged HYBRID HEAT®   Dual Fuel System with Puronr (R---410A) Refrigerant   Single And Three Phase   2 --- 5 N o m i n a l To n s ( S i z e s 2 4 --- 6 0 )   Installation Instructions   NOTE: Read the entire instruction manual before starting the   installation.   NOTE: Installer: Make sure the Owner’s Manual and Service   Instructions are left with the unit after installation.   TABLE OF CONTENTS   PAGE   SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1   INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2   RECEIVING AND INSTALLATION . . . . . . . . . . . . . . . . . 2--13   Check Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2   Identify Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2   Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2   Provide Unit Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2   Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2   Slab Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2   Field Fabricate Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2   Provide Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2   Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6   Connect Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 7   Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7   Install Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7   A09042   Fig. 1 -- Unit 48VT--A   Install Duct Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8   Configuring Units for Downflow (Vertical)   Outdoor Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29   Electrical Controls and Wiring . . . . . . . . . . . . . . . . . . . . . . . 29   Refrigerant Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29   Gas Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30   Indoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30   Check Defrost Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . 30   PuronR Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30   TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33   START--UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33   Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8   Install Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . 11   High--Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . 11   Special Procedures for 208--V Operation . . . . . . . . . . . . . . 11   Control Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . 11   Balance Point Setting Thermidistat or Hybrid Heat   Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12   Transformer Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . 12   PRE--START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12   START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13--17   Check for Refrigerant Leaks . . . . . . . . . . . . . . . . . . . . . . . . . 13   Unit Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . 13   Start--Up Heating and Make Adjustments . . . . . . . . . . . . . . . 13   Checking Heating Control . . . . . . . . . . . . . . . . . . . . . . . . . 14   Check Gas Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14   Adjust Gas Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14   Check Burner Flame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15   Start--Up Cooling and Make Adjustments . . . . . . . . . . . . . . . 16   Checking Cooling Control Operation . . . . . . . . . . . . . . . . 16   Checking and Adjusting Refrigerant . . . . . . . . . . . . . . . . . 16   Indoor Airflow and Airflow Adjustments . . . . . . . . . . . . . 16   Continuous Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . 17   MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27--33   Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27   Indoor Blower and Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . 27   Flue Gas Passageways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28   Limit Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28   Burner Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28   Main Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28   Outdoor Coil, Indoor Coil, & Condensate Drain Pan . . . . . . 28   SAFETY CONSIDERATIONS   Improper installation, adjustment, alteration, service maintenance,   or use can cause explosion, fire, electrical shock, or other   conditions which may cause death, personal injury, or property   damage. Consult a qualified installer, service agency, or your   distributor or branch for information or assistance. The qualified   installer or agency must use factory--authorized kits or accessories   when modifying this product. Refer to the individual instructions   packaged with the kits or accessories when installing.   Follow all safety codes. Wear safety glasses, protective clothing,   and work gloves. Have a fire extinguisher available. Read these   instructions thoroughly and follow all warnings or cautions   included in literature and attached to the unit. consult local   building codes, the current editions of the National Fuel Gas Code   (NFGC) NFPA 54/ANSI Z223.1, and the National Electrical Code   (NEC) NFPA 70.   In Canada refer to the current editions of the National Standards of   Canada CAN/CSA--B149.1 and .2 Natural Gas and Propane   Installation codes, and Canadian Electrical Code CSA C22.1   Recognize safety information. This is the safety--alert symbol   . When you see this symbol on the unit and in instructions or manu-   als, be alert to the potential for personal injury. Understand these   1 A09146   Fig. 2 -- 48VT--A24--30 Unit Dimensions   3 A09147   Fig. 3 -- 48VT--A36--60 Unit Dimensions   4 HVAC unit   basepan   B HVAC unit   base rails   C Sealing   Gasket   F Roofcurb   Anchor screw   Wood nailer*   Roofcurb*   A Flashing field   supplied   Insulation   (field supplied)   Roofing material   field supplied   Cant strip   field supplied   E D SMALL CURB   A09110   *Provided with roofcurb   A09090   ROOF CURB DETAIL   B C F A E D LARGE CURB   A09095   A09111   CATALOG   NUMBER   A B C D E F UNIT SIZE   IN. (mm)   IN. (mm)*   IN. (mm)   IN. (mm)   IN. (mm)   IN. (mm)   CPRFCURB010A00   CPRFCURB011A00   CPRFCURB012A00   CPRFCURB013A00   11 (279)   14 (356)   11 (279)   14 (356)   Small   Large   10 (254)   32.4 (822)   16 (406)   47.8 (1214)   2.7 (69)   14 (356)   43.9 (1116)   NOTES:   1. Roof curb must be set up for unit being installed.   2. Seal strip must be applied, as required, to unit being installed.   3. Roof curb is made of 16--gauge steel.   4. Attach ductwork to curb (flanges of duct rest on curb).   5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.   IMPORTANT: Do not install large base pan HYBRID HEAT   units onto the small base pan (common curb). The center of gravity   on a large base pan HYBRID HEAT unit could overhang the curb   causing an unsafe condition. Before installing any large base pan   unit onto the common curb, check the “Y” distance in the product   literature dimensional drawing to ensure that “Y” is greater than 14   in. (356 mm). Do not install any large base pan unit onto the   common curb with a “Y” dimension (center of gravity) less than 14   in. (356 mm).   Fig. 4 -- Roof Curb Dimensions   5 CAUTION - NOTICE TO RIGGERS   PRUDENCE - AVIS AUX MANIPULATEUR   ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.   PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.   Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition   DUCTS   MINIMUM HEIGHT: 36" (914.4 mm)   HAUTEUR MINIMUM   BANDE SCELLANT DOIT ÊTRE   EN PLACE AVANT DE PLACER   L'UNITÉ SUR LA BASE DE TOIT   SEAL STRIP MUST BE IN   PLACE BEFORE PLACING   UNIT ON ROOF CURB   UNIT HEIGHT   HAUTEUR D'UNITÉ   DETAIL A   VOIR DÉTAIL A   SEE DETAIL A   VOIR DÉTAIL A   50CY502286 2.0   A09051   24   kg   30   36   42   48   60   Unit   Unit   lb   368   lb   kg   lb   kg   lb   kg   lb   kg   lb   543   kg   Rigging   Weight   Rigging   Weight   167   378   171   450   204   491   223   513   233   246   NOTE: See dimensional drawing for corner weight distribution.   Fig. 5 -- 48VT--A Suggested Rigging   Inspection   Step 5 — Rig and Place Unit   Prior to initial use, and at monthly intervals, all rigging shackles,   clevis pins, and straps should be visually inspected for any   damage, evidence of wear, structural deformation, or cracks.   Particular attention should be paid to excessive wear at hoist   hooking points and load support areas. Materials showing any kind   of wear in these areas must not be used and should be discarded.   ! WARNING   PERSONAL INJURY OR PROPERTY DAMAGE   HAZARD   Failure to follow this warning could result in personal   injury, death or property damage.   ! WARNING   When installing the unit on a rooftop, be sure the roof will   support the additional weight.   UNIT FALLING HAZARD   Rigging and handling of this equipment can be hazardous for   many reasons due to the installation location (roofs, elevated   structures, etc.).   Failure to follow this warning could result in personal   injury or death.   Never stand beneath rigged units or lift over people.   Only trained, qualified crane operators and ground support staff   should handle and install this equipment.   ! When working with this equipment, observe precautions in the   literature, on tags, stickers, and labels attached to the equipment,   and any other safety precautions that might apply.   WARNING   PROPERTY DAMAGE HAZARD   Training for operators of the lifting equipment should include, but   not be limited to, the following:   Failure to follow this warning could result in personal   injury/death or property damage.   1. Application of the lifter to the load, and adjustment of the   lifts to adapt to various sizes or kinds of loads.   When straps are taut, the clevis should be a minimum of 36   in. (914 mm) above the unit top cover.   2. Instruction in any special operation or precaution.   3. Condition of the load as it relates to operation of the lifting   kit, such as balance, temperature, etc.   Rigging/Lifting of Unit (See Fig. 5)   Lifting holes are provided in base rails as shown in Fig. 2 and 3.   1. Leave top shipping skid on the unit for use as a spreader bar   to prevent the rigging straps from damaging the unit. If the   skid is not available, use a spreader bar of sufficient length   to protect the unit from damage.   Follow all applicable safety codes. Wear safety shoes and work   gloves.   2. Attach shackles, clevis pins, and straps to the base rails of   the unit. Be sure materials are rated to hold the weight of the   unit (See Fig. 5).   6 3. Attach a clevis of sufficient strength in the middle of the   straps. Adjust the clevis location to ensure unit is lifted level   with the ground.   Install the flue hood as follows:   1. This installation must conform with local building codes   and with the National Fuel Gas Code (NFGC) NFPA 54 /   ANSI Z223.1, (in Canada, CAN/CGA B149.1, and   B149.2) latest revision. Refer to Provincial and local   plumbing or wastewater codes and other applicable local   codes.   2. Remove flue hood from shipping location (inside the return   section of the blower compartment--see Fig. 8). Remove the   return duct cover to locate the flue hood. Place flue hood   assembly over flue panel. Orient screw holes in flue hood   with holes in the flue panel.   After the unit is placed on the roof curb or mounting pad, remove   the top skid.   Step 6 — Connect Condensate Drain   NOTE: When installing condensate drain connection be sure to   comply with local codes and restrictions.   Model 48VT--A disposes of condensate water through a 3/4 in.   NPT fitting which exits through the compressor access panel (See   Fig. 2 and 3 for location).   Condensate water can be drained directly onto the roof in rooftop   installations (where permitted) or onto a gravel apron in ground   level installations. Install a field--supplied condensate trap at end   of condensate connection to ensure proper drainage. Make sure that   the outlet of the trap is at least 1 in. (25 mm) lower than the   drain--pan condensate connection to prevent the pan from   overflowing (See Fig. 6). Prime the trap with water. When using a   gravel apron, make sure it slopes away from the unit.   If the installation requires draining the condensate water away   from the unit, install a 2--in. (51 mm) trap at the condensate   connection to ensure proper drainage (See Fig. 6). Make sure that   the outlet of the trap is at least 1 in. (25 mm) lower than the   drain--pan condensate connection. This prevents the pan from   overflowing.   3. Secure flue hood to flue panel by inserting a single screw on   the top flange and the bottom flange of the hood.   Step 8 — Install Gas Piping   The gas supply pipe enters the unit through the access hole   provided. The gas connection to the unit is made to the 1/2--in.   (12.7 mm) FPT gas inlet on the gas valve.   Install a gas supply line that runs to the heating section. Refer to   Table 2 and the NFGC for gas pipe sizing. Do not use cast--iron   pipe. It is recommended that a black iron pipe is used. Check the   local utility for recommendations concerning existing lines. Size   gas supply piping for 0.5 IN. W.C. maximum pressure drop. Never   use pipe smaller than the 1/2--in. (12.7 mm) FPT gas inlet on the   unit gas valve.   Prime the trap with water. Connect a drain tube -- using a minimum   of 3/4--in. PVC or 3/4--in. copper pipe (all field--supplied) -- at the   outlet end of the 2--in. (51 mm) trap. Do not undersize the tube.   Pitch the drain tube downward at a slope of at least 1--in. (25 mm)   for every 10 ft (3 m) of horizontal run. Be sure to check the drain   tube for leaks.   For natural gas applications, the gas pressure at unit gas connection   must not be less than 4.0 IN. W.C. or greater than 13 IN. W.C.   while the unit is operating. For propane applications, the gas   pressure must not be less than 11.0 IN. W.C. or greater than 13 IN.   W.C. at the unit connection.   A 1/8--in. (3.2 mm) NPT plugged tapping, accessible for test gauge   connection, must be installed immediately upstream of the gas   supply connection to the gas valve.   TRAP   OUTLET   When installing the gas supply line, observe local codes pertaining   to gas pipe installations. Refer to the NFGC NFPA 54/ANSI   Z223.1 latest edition (in Canada, CAN/CGA B149.1).   1-in. (25 mm) min.   NOTE: In the state of Massachusetts:   2-in. (51 mm) min.   1. Gas supply connections MUST be performed by a licensed   plumber or gas fitter.   2. When flexible connectors are used, the maximum length   shall not exceed 36 in. (915 mm).   A09052   Fig. 6 -- Condensate Trap   Step 7 — Install Flue Hood   3. When lever handle type manual equipment shutoff valves   are used, they shall be T--handle valves.   The flue assembly is secured and shipped in the return air duct.   Remove duct cover to locate the assembly (See Fig. 8).   4. The use of copper tubing for gas piping is NOT approved   by the state of Massachusetts.   NOTE:   Dedicated low NOx models MUST be installed in   In the absence of local building codes, adhere to the following   pertinent recommendations:   California Air Quality Management Districts where a Low NOx   rule exists.   1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in.   (6.35 mm) for every 15 ft (4.6 m) of length to prevent traps.   Grade all horizontal runs downward to risers. Use risers to   connect to heating section and to meter.   These models meet the California maximum oxides of nitrogen   (NOx) emissions requirements of 40 nanograms/joule or less as   shipped from the factory.   2. Protect all segments of piping system against physical and   thermal damage. Support all piping with appropriate straps,   hangers, etc. Use a minimum of one hanger every 6 ft (1.8   m). For pipe sizes larger than 1/2 in., (12.7 mm) follow   recommendations of national codes.   3. Apply joint compound (pipe dope) sparingly and only to   male threads of joint when making pipe connections. Use   only pipe dope that is resistant to action of liquefied   petroleum gases as specified by local and/or national codes.   Never use Teflon tape.   NOTE: Low NOx requirements apply only to natural gas   installations.   ! WARNING   CARBON MONOXIDE POISONING HAZARD   Failure to follow this warning could result in personal   injury or death.   The venting system is designed to ensure proper venting.   The flue hood assembly must be installed as indicted in this   section of the unit installation instructions.   4. Install sediment trap in riser leading to heating section (See   Fig. 7). This drip leg functions as a trap for dirt and   condensate.   7 made specifically for the detection of leaks (or method   specified by local codes and/or regulations).   IN   Step 9 — Install Duct Connections   The unit has duct flanges on the supply-- and return--air openings   on the side and bottom of the unit. For downshot applications, the   ductwork connects to the roof curb (See Fig. 2 and 3 for   connection sizes and locations).   Configuring Units for Downflow (Vertical) Discharge   WARNING   ! TEE   OUT   ELECTRICAL SHOCK HAZARD   Failure to follow this warning could result in personal injury   or death.   NIPPLE   CAP   Before installing or servicing system, always turn off main   power to system. There may be more than one disconnect   switch. Tag the disconnect switch with a suitable warning   label.   C99020   Fig. 7 -- Sediment Trap   5. Install an accessible, external, manual main shutoff valve in   gas supply pipe within 6 ft (1.8 m) of heating section.   6. Install ground--joint union close to heating section between   unit manual shutoff and external manual main shut--off   valve.   1. Open all electrical disconnects before starting any service   work.   2. Remove horizontal (metal) duct covers to access vertical   (downflow) discharge duct knockouts in unit basepan. (See   Fig. 8.)   3. Starting in a corner as shown in Fig. 9, score the panel in   both directions from the corner. Tap the panel out from the   scored corner using a small hammer. Be careful and not   damage any other part of the unit.   4. If unit ductwork is to be attached to vertical opening flanges   on the unit base (jackstand applications only), do so at this   time.   7. Pressure test all gas piping in accordance with local and   national plumbing and gas codes before connecting piping   to unit.   NOTE: Pressure test the gas supply system after the gas supply   piping is connected to the gas valve. The supply piping must be   disconnected from the gas valve during the testing of the piping   systems when test pressure is in excess of 0.5 psig. Pressure test the   gas supply piping system at pressures equal to or less than 0.5 psig.   The unit heating section must be isolated from the gas piping   system by closing the external main manual shutoff valve and   slightly opening the ground--joint union.   ! CAUTION   PROPERTY DAMAGE HAZARD   Failure to follow this caution may result in property damage.   Collect ALL screws that were removed. Do not leave screws   on rooftop as permanent damage to the roof may occur.   ! WARNING   5. It is recommended that the base insulation around the   perimeter of the vertical return--air opening be secured to   the base with aluminum tape. Applicable local codes may   require aluminum tape to prevent exposed fiberglass.   FIRE OR EXPLOSION HAZARD   Failure to follow this warning could result in personal injury,   death and/or property damage.   --Connect gas pipe to unit using a backup wrench to avoid   damaging gas controls.   6. Reinstall both horizontal duct covers. Ensure opening is   air-- and watertight.   7. After completing unit conversion, perform all safety checks   and power up unit.   --Never purge a gas line into a combustion chamber. Never   test for gas leaks with an open flame. Use a commercially   available soap solution made specifically for the detection of   leaks to check all connections.   NOTE: The design and installation of the duct system must be in   accordance with the standards of the NFPA for installation of   nonresidence--type air conditioning and ventilating systems, NFPA   90A or residence--type, NFPA 90B; and/or local codes and   ordinances.   --Use proper length of pipe to avoid stress on gas control   manifold.   Adhere to the following criteria when selecting, sizing, and   installing the duct system:   --If a flexible connector is required or allowed by authority   having jurisdiction, black iron pipe shall be installed at   furnace gas valve and extend a minimum of 2 in. (51 mm)   outside furnace casing.   1. Units are shipped for horizontal duct installation (by   removing duct covers).   2. Select and size ductwork, supply--air registers, and   return--air grilles according to American Society of Heating,   Refrigeration and Air Conditioning Engineers (ASHRAE)   recommendations.   --If codes allow a flexible connector, always use a new   connector. do not use a connector which has previously   serviced another gas appliance.   3. Use flexible transition between rigid ductwork and unit to   prevent transmission of vibration. The transition may be   screwed or bolted to duct flanges. Use suitable gaskets to   ensure weather tight and airtight seal.   8. Check for gas leaks at the field--installed and   factory--installed gas lines after all piping connections have   been completed. Use a commercially available soap solution   8 Table 1 – Physical Data -- Unit 48VT--A   UNIT SIZE   NOMINAL CAPACITY ---ton   SHIPPING WEIGHT ---lb.   (kg)   024040   2 368   167   024060   2 368   167   030040   2 --- 1 / 2   378   030060   2 --- 1 / 2   378   036060   3 450   204   036090   3 450   204   042060   3 --- 1 / 2   491   042090   3 --- 1 / 2   491   171   171   223   223   COMPRESSORS   Quantity   Scroll   1 REFRIGERANT (R---410A)   Quantity ---lb   9.5   4.3   9.5   4.3   10.5   4.8   10.5   4.8   9.0   4.1   9.0   4.1   14.0   6.4   14.0   6.4   (kg)   REFRIGERANT METERING   DEVICE   Indoor---TXV, Outdoor---Accurater   OUTDOOR ORIFICE   0.038 (Left OD Coil)   0.040 (Right OD Coil)   .97/1.02   0.032 (2)   .81   0.032 (2)   .81   0.038 (2)   .97   0.038 (2)   .97   0.040 (2)   1.02   0.040 (2)   1.02   in. (qty)   (mm)   OUTDOOR COIL   Rows...Fins/in.   2...21   13.6   2...21   13.6   2...21   15.4   2...21   15.4   2...21   13.6   2...21   13.6   2...21   19.4   2...21   19.4   Fa c e A r e a --- s q f t   OUTDOOR FAN   Nominal Cfm   2500   22   559   2500   22   559   2600   22   559   2600   22   559   3000   22   559   3000   22   559   3500   22   3500   22   Diameter---in.   (mm)   559   559   Motor Hp (Rpm)   INDOOR COIL   1/8 (825)   1/8 (825)   1/8 (825)   1/8 (825)   1/4 (1100)   1/4 (1100)   1/8 (825)   1/8 (825)   3...17   3.7   3...17   3.7   3...17   3.7   3...17   3.7   3...17   4.7   3...17   4.7   3...17   4.7   3...17   4.7   Rows...Fins/in.   Fa c e A r e a --- s q f t   INDOOR BLOWER   Nominal Cooling Airflow---(CFM)   S i z e --- i n .   800   10x10   254x254   1/2   800   10x10   254x254   1/2   1000   10x10   254x254   1/2   1000   10x10   254x254   1/2   1200   11x10   279x254   3/4   1200   11x10   279x254   3/4   1400   11x10   279x254   3/4   1400   11x10   279x254   3/4   (mm)   M o t o r --- h p   FURNACE SECTION*   Burner Orifice   2...44   2...55   2...38   2...53   2...44   2...55   2...44   2...53   2...38   2...53   3...38   3...53   2...38   2...53   3...38   3...53   Natural Gas Qty...Drill Size   Propane GasQty...Drill Size   HIGH---PRESSURE SWITCH   ( p s i g ) C u t --- o u t   650 +/---15   420 +/---25   Reset (Auto)   L O S S --- O F --- C H A R G E /   LOW---PRESSURE SWITCH   (Liquid Line) (psig)   C u t --- o u t   2 0 +/ --- 5   45 +/---10   Reset (auto)   RETURN---AIR FILTERS † }   Throwaway (in.)   (mm)   20x20x1   508x508x25   20x24x1   508x610x25   24x30x1   610x762x25   *Based on altitude of 0 to 2000 ft (0---610 m).   {Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of   300 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN. W.C.   } If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity.   4 3 4 1 3 1 2 2 Horizontal Duct Covers   A09076   INSTRUCTIONS FOR REMOVING DOWNSHOT PANELS   1. Score groove in corner 1 in both directions as far as you can reach.   2. Starting in corner 1, tap-out all sides with a small hammer. Be careful   not to damage any other part of unit.   3. If side from corner 3 to 4 is not accessible due to heat exchanger,   pivot panel up and down by hand until remaining side breaks off.   Basepan   Downflow   (Vertical)   Supply   Basepan   A09054   Downflow   (Vertical)   Return   Fig. 9 -- Vertical (Downflow) Discharge Duct Knockouts   Knockout   Knockout   A09077   Fig. 8 -- Supply and Return Duct Opening   9 Table 1 -- Physical Data -- Unit 48VT--A Cont’d)   UNIT SIZE   NOMINAL CAPACITY ---ton   SHIPPING WEIGHT---lb   (kg)   048090   4 048115   4 048130   4 060090   5 060115   5 060130   5 513   233   513   233   513   233   543   246   543   246   546   246   COMPRESSORS   Quantity   Scroll   1 REFRIGERANT (R---410A)   Quantity ---lb   17.0   7.7   17.0   7.7   17.0   7.7   16.0   7.3   16.0   7.3   16.0   7.3   (kg )   REFRIGERANT METERING DEVICE   OUTDOOR ORIFICE---in. (qty)   (mm)   TXV   0.040 (2)   1.02   0.049 (2)   1.24   OUTDOOR COIL   Rows...Fins---in.   Fa c e A r e a --- s q f t   OUTDOOR FAN   Nominal Cfm   2...21   19.4   2...21   19.4   2...21   19.4   2...21   23.3   2...21   23.3   2...21   23.3   3500   22   559   3500   22   559   3500   22   559   3800   22   559   3800   22   559   3800   22   559   Diameter---in.   (mm)   M o t o r H p --- R p m   INDOOR COIL   1/4 (1100)   1/4 (1100)   1/4 (1100)   1/3 (1100)   1/3 (1100)   1/3 (1100)   3...17   5.7   3...17   5.7   3...17   5.7   4...17   5.7   4...17   5.7   4...17   5.7   Rows...Fins---in.   Fa c e A r e a --- s q f t   INDOOR BLOWER   Nominal Cooling Airflow---(CFM)   S i z e --- i n .   1600   11x10   279x254   1.0   1600   11x10   279x254   1.0   1600   11x10   279x254   1.0   1750   11x10   279x254   1.0   1750   11x10   279x254   1.0   1750   11x10   279x254   1.0   (mm)   M o t o r --- h p   FURNACE SECTION*   Burner Orifice   3...38   3...53   3...33   3...51   3...31   3...49   3...38   3...53   3...33   3...51   3...31   3...49   Natural Gas Qty...Drill Size   Propane GasQty...Drill Size   HIGH---PRESSURE SWITCH (psig)   C u t --- o u t   650 +/---15   420 +/---25   Reset (Auto)   L O S S --- O F --- C H A R G E /   LOW---PRESSURE SWITCH   (Liquid Line) (psig)   C u t --- o u t   20 +/ --- 5   45 +/---10   Reset (auto)   RETURN---AIR FILTERS †   Throwaway (in.)   (mm)   24x36x1   (610x914x25)   *Based on altitude of 0 to 2000 ft (0---610 m).   {Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of   300 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN. W.C.   } If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity.   Table 2 – Maximum Gas Flow Capacity*   NOMINAL   IRON   PIPE, SIZE   (IN.)   LENGTH OF PIPE, FT (m)†   INTERNAL   DIAMETER   (IN.)   10   20   30   40   50   60   70   (21.3)   80   (24.4)   90   (27.4)   100   125   150   175   200   (3.0)   (6.1)   (9.1)   (12.2)   (15.2)   (18.3)   (30.5)   (31.1)   (45.7)   (53.3)   (61.0)   1/2   .622   .824   1.049   1.380   1.610   175   360   120   250   97   200   375   770   1180   82   73   66   61   57   53   50   44   93   175   360   550   40   84   160   325   500   — 77   145   300   460   — 72   135   280   430   3/4   1 1 --- 1/4   1 --- 1/2   170   320   600   990   151   285   580   900   138   260   530   810   125   240   490   750   118   220   460   690   110   205   430   650   103   195   400   620   680   465   1400   2100   950   1460   * Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5--IN. W.C. (based on a 0.60 specific gravity gas). Refer to Table 2   and the NFGC NFPA 54/ANSI.   † This length includes an ordinary number of fittings.   Table 3 – Heating Inputs   GAS SUPPLY PRESSURE (IN. W.C.)   Natural{ Propane*{   MANIFOLD PRESSURE   (IN. W.C.)   HEATING INPUT   (BTUH)   NUMBER OF   ORIFICES   Min   4.0   4.0   4.0   4.0   4.0   Max   13.0   13.0   13.0   13.0   13.0   Min   11.0   11.0   11.0   11.0   11.0   Max   13.0   13.0   13.0   13.0   13.0   Natural{   3.2∼3.8   3.2∼3.8   3.2∼3.8   3.2∼3.8   3.2∼3.8   Propane*†   10.0∼11.0   10.0∼11.0   10.0∼11.0   10.0∼11.0   10.0∼11.0   40,000   60,000   90,000   115,000   130,000   2 2 3 3 3 *When a unit is converted to propane, different size orifices must be used. See separate, natural---to---propane conversion kit instructions.   {Based on altitudes from sea level to 2000 ft (610 m) above sea level. In th e U.S.A. for altitudes above 2000 ft (610 m), reduce input rating 4 percent for each   additional 1000 ft (305 m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent.   10   4. All units must have field--supplied filters or accessory filter   rack installed in the return--air side of the unit.   Recommended sizes for filters are shown in Table 1.   The unit must have   a separate electrical service with   a field--supplied, waterproof disconnect switch mounted at, or within   sight from, the unit. Refer to the unit rating plate, NEC and local   codes for maximum fuse/circuit breaker size and minimum circuit   amps (ampacity) for wire sizing.   The field--supplied disconnect switch box may be mounted on the   unit over the high--voltage inlet hole when the standard power and   low--voltage entry points are used (See Fig. 2 and 3 for acceptable   location).   5. Size all ductwork for maximum required airflow (either   heating or cooling) for unit being installed. Avoid abrupt   duct size increases or decreases or performance may be   affected.   6. Adequately insulate and weatherproof all ductwork located   outdoors. Insulate ducts passing through unconditioned   space, and use vapor barrier in accordance with latest issue   of Sheet Metal and Air Conditioning Contractors National   Association (SMACNA) and Air Conditioning Contractors   of America (ACCA) minimum installation standards for   heating and air conditioning systems. Secure all ducts to   building structure.   See unit wiring label (Fig. 15 and 16) and Fig. 10 for reference   when making high voltage connections. Proceed as follows to   complete the high--voltage connections to the unit.   Single phase units:   1. Run the high--voltage (L1, L2) and ground lead into the   control box.   7. Flash, weatherproof, and vibration--isolate all openings in   building structure in accordance with local codes and good   building practices.   2. Connect ground lead to chassis ground connection.   3. Locate the black and yellow wires connected to the line side   of the contactor.   Step 10 — Install Electrical Connections   4. Connect field L1 to black wire on connection 11 of the   compressor contactor.   ! 5. Connect field wire L2 to yellow wire on connection 23 of   the compressor contactor.   WARNING   ELECTRICAL SHOCK HAZARD   Three--phase units:   Failure to follow this warning could result in personal injury   or death.   1. Run the high--voltage (L1, L2, L3) and ground lead into the   control box.   The unit cabinet must have an uninterrupted, unbroken   electrical ground. This ground may consist of an electrical   wire connected to the unit ground screw in the control   compartment, or conduit approved for electrical ground when   installed in accordance with NEC, NFPA 70 National Fire   Protection Association (latest edition) (in Canada, Canadian   Electrical Code CSA C22.1) and local electrical codes.   2. Connect ground lead to chassis ground connection.   3. Locate the black and yellow wires connected to the line side   of the contactor.   4. Connect field L1 to black wire on connection 11 of the   compressor contactor.   5. Connect field wire L3 to yellow wire on connection 13 of   the compressor contactor.   6. Connect field wire L2 to blue wire from compressor.   Special Procedures for 208-V Operation   ! CAUTION   UNIT COMPONENT DAMAGE HAZARD   ! WARNING   Failure to follow this caution may result in damage to the unit   being installed.   ELECTRICAL SHOCK HAZARD   1. Make all electrical connections in accordance with NEC   NFPA 70 (latest edition) and local electrical codes   governing such wiring. In Canada, all electrical   connections must be in accordance with CSA standard   C22.1 Canadian Electrical Code Part 1 and applicable   local codes. Refer to unit wiring diagram.   2. Use only copper conductor for connections between   field--supplied electrical disconnect switch and unit. DO   NOT USE ALUMINUM WIRE.   Failure to follow this warning could result in personal injury   or death.   Makesurethepower supplyto theunit isswitched OFFbefore   making any wiring changes. Tag the disconnect switch with a   suitable warning label. With disconnect switch open, move   black wire from transformer (3/16 in.) terminal marked 230 to   terminal marked 200. This retaps transformer to primary   voltage of 208 vac.   3. Be sure that high--voltage power to unit is within   operating voltage range indicated on unit rating plate. On   3--phase units, ensure phases are balanced within 2   percent. Consult local power company for correction of   improper voltage and/or phase imbalance.   ! WARNING   ELECTRICAL SHOCK HAZARD   Failure to follow this warning could result in personal injury   or death.   4. Insulate low--voltage wires for highest voltage contained   within conduit when low--voltage control wires are in   same conduit as high--voltage wires.   Before making any wiring changes, makesure the gas supply   is switched off first. Then switch off the power supply to the   unit and install lockout tag.   5. Do not damage internal components when drilling   through any panel to mount electrical hardware, conduit,   etc.   Control Voltage Connections   Do not use any type of power--stealing thermostat. Unit control   problems may result.   High-Voltage Connections   When routing power leads into unit, use only copper wire between   disconnect and unit. The high voltage leads should be in a conduit   until they enter the duct panel; conduit termination at the duct   panel must be watertight.   Use no. 18 American Wire Gage (AWG) color--coded, insulated   (35_C minimum) wires to make the control voltage connections   between the thermostat and the unit. If the thermostat is located   11   more than 100 ft (30.5 m) from the unit (as measured along the   control voltage wires), use no. 16 AWG color--coded, insulated   (35_C minimum) wires.   3. Comfort Balance Temperature: When the heat pump is   operating below this point, the indoor supply air feels   uncomfortable (i.e. too cool). This is purely subjective and   will depend on the homeowner’s idea of comfort. Below   this temperature the gas furnace should operate in order to   satisfy the desire for indoor comfort.   Locate the seven (eight on 3--phase) low voltage thermostat leads   in 24 volt splice box. See Fig. 10 for connection diagram. Run the   low--voltage leads from the thermostat, through the control wiring   inlet hole grommet (Fig. 2 and 3), and into the low--voltage splice   box. Provide a drip loop before running wires through panel.   Secure and strain relief all wires so that they do not interfere with   operation of unit. A gray wire is standard on 3--phase unit for   connection to an economizer.   Transformer Protection   The transformer is of the energy--limiting type. It is set to withstand   a 30--sec. overload or shorted secondary condition. If an overload   or short is present, correct overload condition and check for blown   fuse on gas control board or Interface Fan Board. Replace fuse as   required with correct size and rating.   HIGH VOLTAGE   PRE--START--UP   POWER LEADS   POWER   (SEE UNIT WIRING   SUPPLY   LABEL)   ! WARNING   FIRE,EXPLOSION,ELECTRICAL SHOCKHAZARD   EQUIP GR   FIELD-SUPPLIED   FUSED DISCONNECT   Failure to follow this warning could result in personal injury,   death or property damage.   CONTROL BOX   WHT(W1)   W 1. Follow recognized safety practices and wear protective   goggles when checking or servicing refrigerant system.   YEL(Y)   Y GRN(G)   G 2. Do not operate compressor or provide any electric power   to unit unless compressor terminal cover is in place and   secured.   RED(R)   BRN(C)   ORN(O)   THERMOSTAT   (TYPICAL)   R C LOW-VOLTAGE   POWER LEADS   (SEE UNIT   WIRING LABEL)   3. Do not remove compressor terminal cover until all   electrical sources are disconnected and tagged.   O BLU (DH)   GRA (Y2)   DH   4. Relieve and recover all refrigerant from system before   touching or disturbing anything inside terminal box if   refrigerant leak is suspected around compressor   terminals.   3-Phase   Only   SPLICE BOX   A09067   5. Never attempt to repair soldered connection while   refrigerant system is under pressure.   6. Do not use torch to remove any component. System   contains oil and refrigerant under pressure.   To remove a component, wear protective goggles and   proceed as follows:   Fig. 10 -- High and Control--Voltage Connections   Balance Point Setting-Thermidistat or Hybrid   Thermostat   BALANCE POINT TEMPERATURE--The “balance point”   temperature is a setting which affects the operation of the heating   mode. This is a field--selected input temperature (range 5 to 55_F)   (--15 to 12_C) where the Thermidistat or dual fuel thermostat will   monitor outdoor air temperature and decide whether to enable or   disable the heat pump. If the outdoor temperature is above the   “balance point”, the heat pump will energize first to try to satisfy   the indoor temperature demand. If the heat pump does not make a   sufficient improvement within a reasonable time period (i.e. 15   minutes), then the gas furnace will come on to satisfy the indoor   temperature demand. If the outdoor temperature is below the   “balance point”, the heat pump will not be allowed to operate (i.e.   locked out), and the gas furnace will be used to satisfy the indoor   temperature. There are three separate concepts which are related to   selecting the final “balance point” temperature. Read each of the   following carefully to determine the best “balance point” in a   hybrid installation:   a. Shut off electrical power to unit and install lockout   tag.   b. Relieve and reclaim all refrigerant from system   using both high-- and low--pressure ports.   c. Cut component connecting tubing with tubing   cutter and remove component from unit.   d. Carefully unsweat remaining tubing stubs when   necessary. Oil can ignite when exposed to torch   flame.   Proceed as follows to inspect and prepare the unit for initial   start--up:   1. Remove access panels (see Fig. 19).   2. Read and follow instructions on all WARNING,   CAUTION, and INFORMATION labels attached to, or   shipped with, unit.   1. Capacity Balance Temperature: This is a point where the   heat pump cannot provide sufficient capacity to keep up   with the indoor temperature demand because of declining   outdoor temperature. At or below this point, the furnace is   needed to maintain proper indoor temperature.   3. Make the following inspections:   a. Inspect for shipping and handling damages such as   broken lines, loose parts, disconnected wires, etc.   b. Inspect for oil at all refrigerant tubing connections and   on unit base. Detecting oil generally indicates a   refrigerant leak.   2. Economic Balance Temperature: Above this point, the heat   pump is the most cost efficient to operate, and below this   point the furnace is the most cost efficient to operate. This   can be somewhat complicated to determine and it involves   knowing the cost of gas and electricity, as well as the   efficiency of the furnace and heat pump. For the most   economical operation, the heat pump should operate above   this temperature (assuming it has sufficient capacity) and the   furnace should operate below this temperature.   c. Leak test all refrigerant tubing connections using   electronic leak detector, halide torch, or liquid--soap   solution. If a refrigerant leak is detected, see the Check   for Refrigerant Leaks section.   d. Inspect all field-- and factory--wiring connections. Be   sure that connections are completed and tight.   12   e. Ensure wires do not touch refrigerant tubing or sharp   sheet metal edges.   f. Inspect coil fins. If damaged during shipping and   handling, carefully straighten fins with a fin comb.   (1.) On a call for heating, terminals “Y” and “G“ of the   Hybrid thermostat are energized. The “Y“ signal is   sent to the Defrost Board (DB) terminal “Y”. The   DB has a built in five minute anti--short cycle timer   which will not allow the compressor to restart   before the time delay has expired.   ! WARNING   (2.) “T2” energizes the compressor contactor via the   High Pressure Switch (HPS) and Low Pressure   Switch (LPS). The compressor and outdoor fan   start. Thermostat “G” energizes the Interface Fan   Board terminal “G”. The blower motor is energized   through contacts of the IFB.   (3.) When the thermostat removes the “Y” and “G”   calls, the compressor contactor and outdoor fan are   de--energized. The evaporator motor is de--ener-   gized after a 90 sec. delay.   FIRE, EXPLOSION HAZARD   Failure to follow this warning could result in personal injury,   death or property damage.   Do not purge gas supply into the combustion chamber. Do not   use a match or other open flame to check for gas leaks. Use a   commercially available soap solution made specifically for   the detection of leaks to check all connections.   4. Verify the following conditions:   a. Make sure gas line is free of air. Before lighting the unit   for the first time, perform the following with the gas   valve in the “OFF” position:   d. GAS HEATING MODE   Outdoor temperature below balance point setpoint of   thermostat.   NOTE: If the gas supply pipe was not purged before connecting   the unit, it will be full of air. It is recommended that the ground   joint union be loosened, and the supply line be allowed to purge   until the odor of gas is detected. Never purge gas lines into a   combustion chamber. Immediately upon detection of gas odor,   retighten the union. Allow 5 minutes to elapse, then light unit.   Heating Sequence of Operation   (See Fig. 15 and 16 and unit wiring label.)   On a call for heating, terminal W of the thermostat is energized,   starting the induced--draft motor. When the pressure switch senses   that the induced--draft motor is moving sufficient combustion air,   the burner sequence begins. This function is performed by the   integrated gas unit controller (IGC). The indoor (evaporator)--fan   motor is energized 45 sec after flame is established. When the   thermostat is satisfied and W is de--energized, the burners stop   firing and the indoor (evaporator) fan motor shuts off after a   45--sec time--off delay. Please note that the IGC has the capability   to automatically reduce the indoor fan motor on delay and increase   the indoor fan motor off delay in the event of high duct static   and/or partially--clogged filter.   b. Make sure that condenser--fan blade is correctly   positioned in fan orifice. Leading edge of condenser--fan   blade should be 1/2 in. (12 mm) maximum from fan   orifice.   c. Make sure that air filter(s) is in place.   d. Make sure that condensate drain trap is filled with water   to ensure proper drainage.   e. Make sure that all tools and miscellaneous loose parts   have been removed.   NOTE: An LED (light--emitting diode) indicator is provided on   the control board to monitor operation. The control board is   located by removing the burner access panel (see Fig. 19). During   normal operation, the LED is continuously on.   START--UP   Step 1 — Check for Refrigerant Leaks   Proceed as follows to locate and repair a refrigerant leak and to   charge the unit:   Step 3 — Start--up Heating and Make Adjust-   ments   1. Locate leak and make sure that refrigerant system pressure   has been relieved and reclaimed from both high-- and   low--pressure ports.   ! CAUTION   2. Repair leak following Refrigerant Service procedures.   UNIT COMPONENT DAMAGE HAZARD   NOTE: Install a bi--flow filter drier whenever the system has been   opened for repair.   Failure to follow this caution may result in damage to the unit   being installed.   3. Add a small charge of R--410A refrigerant vapor to system   and leak--test unit.   4. Recover refrigerant from refrigerant system and evacuate to   500 microns if no additional leaks are not found.   Complete the required procedures given in the Pre--Start--Up   section before starting the unit. Do not jumper any safety   devices when operating the unit.   5. Charge unit with Puron (R--410A) refrigerant, using an   electronic scale. Refer to unit rating plate for required   charge.   Complete the required procedures given in the Pre--Start--Up   section before starting the unit. Do not jumper any safety devices   when operating the unit. Make sure that burner orifices are   properly aligned. Unstable operation my occur when the burner   orifices in the manifold are misaligned.   Step 2 — Unit Sequence of Operation   48VT-A Sequence of Operation   a. CONTINUOUS FAN   Follow the lighting instructions on the heating section operation   label (located on the inside of the control access panel) to start the   heating section.   (1.) Thermostat closes circuit R to G energizing the   blower motor for continuous fan.   NOTE: Make sure that gas supply has been purged, and that all   gas piping has been checked for leaks.   b. COOLING MODE   (1.) If indoor temperature is above temperature set   point thermostat closes circuits R to G, R to Y and   R to O--The unit delivers cooling airflow.   c. HEAT PUMP HEATING MODE   Outdoor temperature above balance point setpoint of   thermostat.   13   specific gravity, or propane gas with a heating value of 2500   3 Btu/ft at 1.5 specific gravity.   IN THE U.S.A.:   The input rating for altitudes above 2,000 ft (610 m) must be   reduced by 4% for each 1,000 ft (305 m) above see level.   For installations below 2,000 ft (610 m), refer to the unit rating   plate.   For installations above 2,000 ft (610 m) multiply the input by on   the rating plate by the derate multiplier in Table 4 for correct input   rate.   Table 4 – Altitude Derate Multiplier for U.S.A.*   DERATE MULTIPLIER   ALTITUDE FT (M)   PERCENT OF DERATE   FACTOR{   0---2000   (0---610)   0 1.00   Pipe Plug   Manifold   2001---3000*   (610---914)   8 --- 1 2   0.90   0.86   0.82   0.78   0.74   0.70   0.66   0.62   A07679   Fig. 11 -- Burner Assembly   3001---4000   (315---1219)   12---16   16---20   20---24   24---28   28---32   32---36   36---40   BURNER FLAME   4001---5000   (1220---1524)   5001---6000   (1524---1829)   BURNER   6001---7000   (1829---2134)   7001---8000   (2134---2438)   8001---9000   (2439---2743)   9001---10,000   (2744---3048)   MANIFOLD   * In Canada see Canadian Altitude Adjustment.   {Derate multiplier factors are based on midpoint altitude for altitude range.   IN CANADA:   The input rating for altitudes from 2,000 to 4,500 ft (610 m to   1372 m) above sea level must be derated 10% by an authorized   Gas Conversion Station or Dealer.   C99021   Fig. 12 -- Monoport Burner   EXAMPLE:   Check Heating Control   90,000 Btu/hr Input Furnace Installed at 4300 ft (1311 m).   Start and check the unit for proper heating control operation as   follows (see furnace lighting instructions located on the inside of   the control access panel):   Furnace Input Rate at   Sea Level   X Derate Multiplier   Factor   = Furnace Input Rate at   Installation Altitude   90,000   X 0.90   = 81,000   1. Place room thermostat SYSTEM switch in the HEAT   position and the fan switch is placed in AUTO position.   2. Set the heating temperature control of the thermostat above   room temperature.   When the gas supply being used has a different heating value or   specific gravity, refer to national and local codes, or contact your   distributor to determine the required orifice size.   3. The induced--draft motor will start.   ! CAUTION   4. On a call for heating, the main burner should light within 5   sec. of the spark being energized. If the burners do not light,   there is a 22--sec. delay before another 5--sec. try. If the   burners still do not light, this sequence is repeated. If the   burners do not light within 15 minutes from the initial call   for heat, there is a lockout. To reset the control, break the   24--v power to W.   5. The evaporator fan will turn on 45 sec. after the flame has   been established. The evaporator fan will turn off 45 sec.   after the thermostat has been satisfied. Please note that the   integrated gas unit controller (IGC) has the capability to   automatically reduce the evaporator “ON” delay and in-   crease the evaporator “OFF” delay in the event of high duct   static and/or partially--clogged filter.   UNIT DAMAGE HAZARD   Failure to follow this caution may result in reduced unit   and/or component life.   Do Not redrill an orifice. Improper drilling (burrs,   out--of--round holes, etc.) can cause excessive burner noise   and misdirection of burner flame. If orifice hole appears   damaged or it is suspected to have been redrilled, check   orifice hole with a numbered drill bit of correct size.   Adjust Gas Input   The gas input to the unit is determined by measuring the gas flow   at the meter or by measuring the manifold pressure. Measuring the   gas flow at the meter is recommended for natural gas units. The   manifold pressure must be measured to determine the input of   propane gas units.   Check Gas Input   Check gas input and manifold pressure after unit start--up (See   Table 3). If adjustment is required proceed as follows:   Measure Gas Flow (Natural Gas Units)   S The rated gas inputs shown in Table 3 are for altitudes from sea   Minor adjustment to the gas flow can be made by changing the   manifold pressure. The manifold pressure must be maintained   between 3.2 and 3.8 IN. W.C.   level to 2000 ft (610 m) above sea level. These inputs are based   3 on natural gas with a heating value of 1025 Btu/ft at 0.60   14   REGULATOR   COVER SCREW   ! WARNING   PLASTIC   ADJUSTMENT   SCREW   FIRE AND UNIT DAMAGE HAZARD   ON/OFF SWITCH   Failure to follow this warning could result in personal   injury or death and/or property damage.   REGULATOR SPRING   (PROPANE - WHITE)   ( NATURAL - SILVER)   Unsafe operation of the unit may result if manifold pressure   is outside this range.   GAS PRESSURE   REGULATOR   ADJUSTMENT   INLET   PRESSURE TAP   3. Replace regulator cover screw on gas valve (See Fig. 13).   4. Turn off gas supply to unit. Remove manometer from   pressure tap and replace pipe plug on gas valve. (See Fig.   11.) Turn on gas to unit and check for leaks.   Measure Manifold Pressure (Propane Units)   MANIFOLD   PRESSURE TAP   Refer to propane kit installation instructions for properly checking   gas input.   A07751   Fig. 13 -- Single--Stage Gas Valve   If larger adjustments are required, change main burner orifices   following the recommendations of national and local codes.   NOTE: For installations below 2,000 ft (610 m), refer to the unit   rating plate for proper propane conversion kit. For installations   above 2,000 ft (610 m), contact your distributor for proper propane   conversion kit.   NOTE: All other appliances that use the same meter must be   turned off when gas flow is measured at the meter.   Check Burner Flame   Proceed as follows:   With control access panel (see Fig. 19) removed, observe the unit   heating operation. Watch the burner flames to see if they are light   blue and soft in appearance, and that the flames are approximately   the same for each burner. Propane will have blue flame (See Fig.   12). Refer to the Maintenance section for information on burner   removal.   1. Turn off gas supply to unit.   2. Remove pipe plug on manifold (See Fig. 11) and connect   manometer. Turn on gas supply to unit.   3. Record number of seconds for gas meter test dial to make   one revolution.   Normal Operation   4. Divide number of seconds in Step 3 into 3600 (number of   seconds in one hr).   5. Multiply result of Step 4 by the number of cubic feet (cu ft)   shown for one revolution of test dial to obtain cubic feet (cu   ft) of gas flow per hour.   An LED (light--emitting diode) indicator is provided on the   integrated gas unit controller (IGC) to monitor operation. The IGC   is located by removing the control access panel (see Fig. 19).   During normal operation, the LED is continuously on (See Table 5   for error codes).   6. Multiply result of Step 5 by Btu heating value of gas to   obtain total measured input in Btuh. Compare this value   with heating input shown in Table 3 (Consult the local gas   supplier if the heating value of gas is not known).   Airflow and Temperature Rise   The heating section for each size unit is designed and approved for   heating operation within the temperature--rise range stamped on the   unit rating plate.   EXAMPLE: Assume that the size of test dial is 1 cu ft, one   revolution takes 32 sec, and the heating value of the gas is 1050   Table 10 shows the approved temperature rise range for each   heating input, and the air delivery cfm at various temperature rises   for a given external static pressure. The heating operation airflow   must produce a temperature rise that falls within the approved   range.   3 Btu/ft . Proceed as follows:   1. 32 sec. to complete one revolution.   2. 3600 ÷ 32 = 112.5.   3 3. 112.5 x 1 =112.5 ft of gas flow/hr.   4. 112.5 x 1050 = 118,125 Btuh input.   Refer to Indoor Airflow and Airflow Adjustments section to adjust   heating airflow when required.   If the desired gas input is 115,000 Btuh, only a minor change in the   manifold pressure is required.   Limit Switches   Normally closed limit switch (LS) completes the control circuit.   Should the leaving--air temperature rise above the maximum   allowable temperature, the limit switch opens and the control   circuit “breaks.” Any interruption in the control circuit instantly   closes the gas valve and stops gas flow to the burners and pilot.   The blower motor continues to run until LS resets.   Observe manifold pressure and proceed as follows to adjust gas   input:   1. Remove regulator cover screw over plastic adjustment   screw on gas valve (See Fig. 13).   2. Turn plastic adjustment screw clockwise to increase gas   input, or turn plastic adjustment screw counterclockwise to   decrease input (See Fig. 13). Manifold pressure must be   between 3.2 and 3.8 IN. W.C.   When the air temperature at the limit switch drops to the   low--temperature setting of the limit switch, the switch closes and   15   completes the control circuit. The direct--spark ignition system   cycles and the unit returns to normal heating operation.   NOTE: Adjustment of the refrigerant charge is not required unless   the unit is suspected of not having the proper PuronR (R--410A)   charge.   Table 5 – LED Indications   The charging label and the tables shown refer to system   temperatures and pressures in cooling mode only. A refrigerant   charging label is attached to the inside of the compressor access   panel (see Fig. 19). The chart includes the required liquid line   temperature at given discharge line pressures and outdoor ambient   temperatures.   STATUS CODE   Normal Operation   LED INDICATION   On   2 No Power Hardware Failure   Limit Switch Fault   Off   2 Flashes   3 Flashes   4 Flashes   5 Flashes   6 Flashes   7 Flashes   8 Flashes   9 Flashes   Flame Sense Fault   An accurate thermocouple-- or thermistor--type thermometer, and a   gauge manifold are required when using the subcooling charging   method for evaluating the unit charge. Do not use mercury or small   dial--type thermometers because they are not adequate for this type   of measurement.   Four Consecutive Limit Switch Faults   Ignition Lockout Fault   Pressure Switch Fault   Rollout Switch Fault   Internal Control Fault   Temporary 1 hr auto reset   1 ! NOTES:   CAUTION   1.This code indicates an internal processor fault that will reset itself in one   hr. Fault can be caused by stray RF signals in the structure or nearby. This   is a UL requirement.   UNIT DAMAGE HAZARD   2. LED indicates acceptable operation. Do not change ignition control   board.   3. When W is energized the burners will remain on for a minimum of 60 sec.   4. If more than one error mode exists they will be displayed on the LED in   sequence.   Failure to follow this caution may result in unit damage.   When evaluating the refrigerant charge, an indicated   adjustment to the specified factory charge must always be   very minimal. If a substantial adjustment is indicated, an   abnormal condition exists somewhere in the cooling system,   such as insufficient airflow across either coil or both coils.   Rollout Switch   The function of the rollout switch is to close the main gas valve in   the event of flame rollout. The switch is located above the main   burners. When the temperature at the rollout switch reaches the   maximum allowable temperature, the control circuit trips, closing   the gas valve and stopping gas flow to the burners. The indoor   (evaporator) fan motor (IFM) and induced draft motor continue to   run until switch is reset. The IGC LED will display FAULT CODE   7.   Proceed as follows:   1. Remove caps from low-- and high--pressure service fittings.   2. Using hoses with valve core depressors, attach low-- and   high--pressure gauge hoses to low-- and high--pressure   service fittings, respectively.   3. Start unit in Cooling Mode and let unit run until system   pressures stabilize.   Step 4 — Start--up Cooling and Make Adjust-   ments   Complete the required procedures given in the Pre--Start--Up   section before starting the unit. Do not jumper any safety devices   when operating the unit. Do not operate the compressor when the   outdoor temperature is below 40°F (4.4°C) (unless accessory   low--ambient kit is installed). Do not rapid--cycle the compressor.   Allow 5 minutes between on cycles to prevent compressor damage.   4. Measure and record the following:   a. Outdoor ambient--air temperature (°F (°C) db).   b. Liquid line temperature (°F (°C).   c. Discharge (high--side) pressure (psig).   d. Suction (low--side) pressure (psig) (for reference only).   5. Using “Cooling Charging Charts,” compare outdoor--air   temperature(°F (°C) db) with the discharge line pressure   (psig) to determine desired system operating liquid line   temperature (See Fig. 17).   6. Compare actual liquid line temperature with desired liquid   line temperature. Using a tolerance of ± 2°F (±1.1°C), add   refrigerant if actual temperature is more than 2°F (1.1°C)   higher than proper liquid line temperature, or remove   refrigerant if actual temperature is more than 2°F (1.1°C)   lower than required liquid line temperature.   Checking Cooling Control Operation   Start and check the unit for proper cooling control operation as   follows:   1. Place room thermostat SYSTEM switch in OFF position.   Observe that blower motor starts when FAN switch is   placed in ON position and shuts down when FAN switch is   placed in AUTO position.   2. Place SYSTEM switch in COOL position and FAN switch   in AUTO position. Set cooling control below room   temperature. Observe that compressor, condenser fan, and   evaporator blower motors start. Observe that cooling cycle   shuts down when control setting is satisfied. The evaporator   fan will continue to run for 90 sec.   NOTE: If the problem causing the inaccurate readings is a   refrigerant leak, refer to the Check for Refrigerant Leaks section.   Indoor Airflow and Airflow Adjustments   ! CAUTION   IMPORTANT:   Three--phase, scroll compressors units are   direction oriented. Unit must be checked to ensure proper   compressor 3--phase power lead orientation. If not corrected within   5 minutes, the internal protector will shut off the compressor. The   3--phase power leads to the unit must be reversed to correct   rotation. When turning backwards, the difference between   compressor suction and discharge pressures will be near zero.   UNIT OPERATION HAZARD   Failure to follow this caution may result in unit damage.   For cooling operation, the recommended airflow is 350 to   450 cfm for each 12,000 Btuh of rated cooling capacity. For   heating operation, the airflow must produce a temperature   rise that falls within the range stamped on the unit rating   plate.   Checking and Adjusting Refrigerant Charge   The refrigerant system is fully charged with PuronR (R--410A)   refrigerant and is tested and factory sealed. Allow system to operate   a minimum of 15 minutes before checking or adjusting charge.   NOTE: Be sure that all supply--and return--air grilles are open,   free from obstructions, and adjusted properly.   16   3. Connect the desired speed tap wire to the “LOW” terminal   on the interface fan board (IFB).   ! WARNING   Two Cooling Fan Speeds Set-up (Dehumidification   feature used)   ELECTRICAL SHOCK HAZARD   Failure to follow this warning could result in personal   injury or death.   IMPORTANT: Dehumidification control must open control   circuit on humidity rise above set point.   Before making any indoor wiring adjustments, shut off gas   supply. Then disconnect electrical power to the unit and   install lockout tag before changing blower speed.   Use of the dehumidification cooling fan speed requires use of   either a 24 VAC dehumidistat or a thermostat which includes   control of a 24 VAC dehumidistat connection. In either case, the   dehumidification control must open the control circuit on humidity   rise above the dehumidification set point. Dehumidification   controls are available with the reverse logic; these must not be   used.   This unit has independent fan speeds for gas heating and cooling.   In addition, this unit has the field-selectable capability to run two   different cooling fan speeds: A normal cooling fan speed (350~400   CFM/Ton) and an enhanced dehumidification fan speed (As low as   320 CFM/Ton) for use with either a dehumidistat or a thermostat   that supports dehumidification.   1. Remove fan speed tap wire from the “LOW” terminal on   the interface fan board (IFB) (Fig. 14).   2. Determine correct normal cooling fan speed for unit and   application. Add the wet coil pressure drop in Table 8 to   the system static to determine the correct cooling airflow   speed in Table 10 that will deliver the nominal cooling   airflow as listed in Table 1 for each size.   3. Remove the vinyl cap off of the desired speed tap wire   (Refer to Table 6 for color coding) for the normal cooling   fan speed and place desired speed tap wire on “HIGH” on   the interface board.   This unit is factory-set up for use with a single cooling fan speed.   The cooling speed is marked “LOW” on the interface fan board   (IFB) (Fig. 14) . The factory-shipped settings are noted in Table   10. There are 3 additional speed tap wires available for use in   either gas heating or cooling (For color coding on the indoor fan   motor leads, see Table 6). The additional 3 speed tap wires are   shipped loose with vinyl caps and are located in the control box,   near the interface fan board (IFB) (Fig. 14).   4. Refer to airflow tables (Table 10) to determine allowable   speeds for the dehumidification cooling fan speed. In Table   10, speeds that are not allowed for dehumidification cooling   are shaded.   5. Remove the vinyl cap off of the desired speed tap wire   (Refer to Table 6 for color coding) for the dehumidification   cooling fan speed and place desired speed tap wire on the   “LOW” connection on the interface board (IFB). Verify   that static pressure is in the acceptable range for the speed   tap to be used for dehumidification cooling.   Gas Heating Fan Speed Set-up   To change the gas heating speed:   1. Remove the vinyl cap off of the desired speed tap wire   (Refer to Table 6 for color coding). Table 10 shows the   temperature rise associated with each fan speed for a given   static pressure. Make sure that the speed chosen delivers a   temperature rise within the rise range listed on the unit   rating plate.   2. Remove the current speed tap wire from the “GAS HEAT”   terminal on the interface fan board (IFB) (Fig.14) and place   vinyl cap over the connector on the wire.   3. Connect the desired speed tap wire to the “GAS HEAT”   terminal on the interface fan board (IFB).   6. Use any spare vinyl plugs to cap any unused speed tap   wires.   NOTE: For heat pump operation, the recommended airflow is 350   to 450 CFM for each 12,000 Btuh of rated cooling capacity.   Single Cooling Fan Speed Set-up (Dehumidification   feature not used)   To change cooling speed:   Continuous Fan Operation   When the DEHUM feature is not used, the continuous fan speed   will be the same as cooling fan speed. When the DEHUM feature   is used, the continuous fan will operate on IFB “LOW” speed   when the DH control lead is not energized, or IFB “HIGH” speed   when the DH lead is energized (see Fig. 14).   1. Remove the vinyl cap off of the desired speed tap wire   (Refer to Table 6 for color coding). Add the wet coil   pressure drop in Table 8 to the system static to determine the   correct cooling airflow speed in Table 10 that will deliver   the nominal cooling airflow as listed in Table 1 for each   size.   2. Remove the current speed tap wire from the “LOW”   terminal on the interface fan board (IFB) (Fig. 14) and place   vinyl cap over the connector on the wire.   Table 6 – Color Coding for Indoor Fan Motor Leads   Black = High Speed   Orange = Med---High Speed   Red = Med Speed   Pin k = Med --- L ow Speed   Blue = Low Speed   17   GAS   HEAT   HIGH   QC7   LOW   QC4   COM   QC3   QC6   K2   K1   D2   DCR   QCR   QC1   C RL3 C8 R1L   Q1   RI0   JM6   Q3   RI2   C9   C4   RI DL   JM5   G1   G2   OILL C2 D6 D4   A7   R9 AB A15   F1   C0   U1   R4   RL4   C3   D5 D3   C7   JW3   R3 R5   P2R6   R2   QCB   JW7   JW2   JW4   Y Y R U C 24VAC   JW1   P1   SSTZ-8   Y2/   DH   Y1/   W2   G Y C R A09058   Fig. 14 -- Interface Fan Board (IFB)   Table 7 – Filter Pressure Drop Table (IN. W.C.)   CFM   FILTER SIZE   in. (mm)   500   600   700   800   900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300   20X20X1   0.05 0.07 0.08   0.1   0.12 0.13 0.14 0.15   0.09 0.10 0.11 0.13 0.14 0.15 0.16   0.1   — — — — — — — — — — — — — — — — — — — — — — — — — — — (508X508X25)   20X24X1   (508X610x25 )   24X30X1   (610X762x25)   24X36X1   (610X914X25)   — — — — — — — — — — 0.04 0.05 0.06 0.07 0.07 0.08 0.09   — — — — 0.06 0.07 0.07 0.08 0.09 0.09 0.10 0.11 0.12 0.13 0.14 0.14   Table 8 – 48VT--A Wet Coil Pressure Drop   Standard CFM (S.C.F.M)   Unit Size   500   600   0.06   700   0.07   800   0.08   0.12   900   0.09   0.15   1000   0.1   0.19   0.07   1100   1200   1300   1400   1500   1600   1700   1800   1900   2000   24   30   36   42   48   60   0.23   0.11   0.27   0.18   0.04   0.26   0.07   0.35   0.1   0.11   0.15   0.14   0.21   0.17   0.1   0.22   0.17   0.28   0.23   0.31   0.36   Table 9 – Wet Coil Air Delivery - Downflow -- High Speed with 1--in. Filter and Economizer   EXTERNAL STATIC PRESSURE (in. W.C.)   UNIT SIZE   0.1   0.2   0.3   0.4   0.5   0.6   0.7   0.8   0.9   1.0   36, 42   48   60   1612   2298   2000   1569   2239   1926   1527   2180   1825   1481   2110   1820   1451   2044   1759   1393   1951   1705   1351   1862   1634   1317   1777   1496   1278   1697   1412   1242   1591   1328   18   Table 10 – Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 48VT--A24--60   HEATING   RISE   EXTERNAL STATIC PRESSURE (in. W.C.)   MOTOR   SPEED   WIRE   UNIT   COLOR   0.1   741   0.2   638   0.3   0.4   0.5   0.6   0.7   0.8   ---   0.9   ---   RANGE   CFM   547   415   ---   ---   ---   Heating   41   47   55   NA   NA   NA   NA   NA   NA   o Rise ( F)   Low   Blue   Pink   Heating   23   898   34   26   820   37   31   738   41   NA   662   46   NA   536   56   NA   ---   NA   ---   NA   ---   NA   ---   o Rise ( C)   CFM   Heating   NA   NA   NA   NA   o 2 Rise ( F)   Med-Low   Heating   19   973   31   20   887   34   23   823   37   25   733   41   31   665   45   NA   538   56   NA   451   NA   NA   ---   NA   ---   o Rise ( C)   CFM   Heating   o NA   NA   30 - 60 F   o 1 Rise ( F)   48VT(-,N)A24040   Medium   Med-High   High   Red   o (17 - 33 C)   Heating   17   1140   NA   19   1064   NA   20   996   30   23   915   33   25   840   36   31   758   40   NA   687   44   NA   564   54   NA   480   NA   o Rise ( C)   CFM   Heating   o Rise ( F)   Orange   Black   Blue   Heating   NA   1202   NA   NA   1140   NA   17   1082   NA   18   1015   30   20   961   31   22   881   34   24   810   37   30   732   41   NA   631   48   o Rise ( C)   CFM   Heating   o Rise ( F)   Heating   NA   741   NA   NA   638   NA   NA   547   NA   17   415   NA   17   ---   19   ---   21   ---   23   ---   27   ---   o Rise ( C)   CFM   Heating   NA   NA   NA   NA   NA   o Rise ( F)   Low   Heating   NA   898   49   NA   820   54   NA   738   NA   NA   662   NA   NA   536   NA   NA   ---   NA   ---   NA   ---   NA   ---   o Rise ( C)   CFM   Heating   NA   NA   NA   NA   o 2 Rise ( F)   Med-Low   Medium   Pink   Heating   27   973   46   30   887   50   NA   823   54   NA   733   NA   NA   665   NA   NA   538   NA   NA   451   NA   NA   ---   NA   ---   o Rise ( C)   CFM   Heating   o NA   NA   25 - 55 F   o Rise ( F)   48VT(-,N)A24060   Red   o (14 - 31 C)   Heating   25   1140   39   28   1064   42   30   996   45   NA   915   49   NA   840   53   NA   758   NA   NA   687   NA   NA   564   NA   NA   480   NA   o Rise ( C)   CFM   Heating   o Rise ( F)   Med-High   Orange   Black   Blue   Heating   22   1202   37   23   1140   39   25   1082   41   27   1015   44   29   961   46   NA   881   50   NA   810   55   NA   732   NA   NA   631   NA   o Rise ( C)   CFM   Heating   o 1 Rise ( F)   High   Heating   21   741   41   22   638   47   23   547   55   24   415   NA   26   ---   28   ---   30   ---   NA   ---   NA   ---   o Rise ( C)   CFM   Heating   NA   NA   NA   NA   NA   o Rise ( F)   Low   Heating   23   898   34   26   820   37   31   738   41   NA   662   46   NA   536   56   NA   ---   NA   ---   NA   ---   NA   ---   o Rise ( C)   CFM   Heating   NA   NA   NA   NA   o Rise ( F)   Med-Low   Pink   Heating   19   973   31   20   887   34   23   823   37   25   733   41   31   665   45   NA   538   56   NA   451   NA   NA   ---   NA   ---   o Rise ( C)   CFM   Heating   o NA   NA   30 - 60 F   o 1 Rise ( F)   48VT(-,N)A30040   Medium   Red   o (17 - 33 C)   Heating   17   1140   NA   19   1064   NA   20   996   30   23   915   33   25   840   36   31   758   40   NA   687   44   NA   564   54   NA   480   NA   o Rise ( C)   CFM   Heating   o 2 Rise ( F)   Med-High   High   Orange   Black   Heating   NA   1202   NA   NA   1140   NA   17   1082   NA   18   1015   30   20   961   31   22   881   34   24   810   37   30   732   41   NA   631   48   o Rise ( C)   CFM   Heating   o Rise ( F)   Heating   NA   NA   NA   17   17   19   21   23   27   o Rise ( C)   19   Table 10 -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 48VT--A24--60 Cont   HEATING   RISE   EXTERNAL STATIC PRESSURE (in. W.C.)   MOTOR   SPEED   WIRE   UNIT   COLOR   0.1   741   NA   0.2   638   NA   0.3   547   NA   0.4   415   NA   0.5   ---   0.6   ---   0.7   ---   0.8   ---   0.9   ---   RANGE   CFM   Heating   NA   NA   NA   NA   NA   o Rise ( F)   Low   Blue   Pink   Heating   NA   898   49   NA   820   54   NA   738   NA   NA   662   NA   NA   536   NA   NA   ---   NA   ---   NA   ---   NA   ---   o Rise ( C)   CFM   Heating   NA   NA   NA   NA   o Rise ( F)   Med-Low   Medium   Heating   27   973   46   30   887   50   NA   823   54   NA   733   NA   NA   665   NA   NA   538   NA   NA   451   NA   NA   ---   NA   ---   o Rise ( C)   CFM   Heating   o NA   NA   25 - 55 F   o Rise ( F)   48VT(-,N)A30060   Red   o (14 - 31 C)   Heating   25   1140   39   28   1064   42   30   996   45   NA   915   49   NA   840   53   NA   758   NA   NA   687   NA   NA   564   NA   NA   480   NA   o Rise ( C)   CFM   Heating   o 2 Rise ( F)   Med-High   Orange   Black   Blue   Heating   22   1202   37   23   1140   39   25   1082   41   27   1015   44   29   961   46   NA   881   50   NA   810   55   NA   732   NA   NA   631   NA   o Rise ( C)   CFM   Heating   o 1 Rise ( F)   High   Heating   21   1295   34   22   1234   36   23   1182   38   24   1126   39   26   1075   41   28   1016   44   30   955   47   NA   898   49   NA   857   52   o Rise ( C)   CFM   Heating   o 1 Rise ( F)   Low   Heating   19   1345   33   20   1282   35   21   1235   36   22   1194   37   23   1140   39   24   1095   41   26   1027   43   27   974   46   29   921   48   o Rise ( C)   CFM   Heating   o Rise ( F)   Med-Low   Medium   Pink   Heating   18   1505   30   19   1452   31   20   1413   31   21   1358   33   22   1323   34   23   1282   35   24   1234   36   25   1169   38   27   1130   39   o Rise ( C)   CFM   Heating   o 25 - 55 F   o Rise ( F)   48VT(-,N)A36060   Red   o (14 - 31 C)   Heating   16   1545   29   17   1492   30   17   1449   31   18   1411   31   19   1362   33   19   1313   34   20   1278   35   21   1231   36   22   1188   37   o Rise ( C)   CFM   Heating   o 2 Rise ( F)   Med-High   High   Orange   Black   Blue   Heating   16   1705   26   17   1643   27   17   1607   28   17   1568   28   18   1518   29   19   1483   30   19   1448   31   20   1404   32   21   1360   33   o Rise ( C)   CFM   Heating   o Rise ( F)   Heating   14   1295   53   15   1234   55   15   1182   58   16   1126   60   16   1075   63   17   1016   NA   17   955   NA   18   898   NA   18   857   NA   o Rise ( C)   CFM   Heating   o Rise ( F)   Low   Heating   29   1345   51   31   1282   53   32   1235   55   34   1194   57   35   1140   60   NA   1095   62   NA   1027   NA   NA   974   NA   NA   921   NA   o Rise ( C)   CFM   Heating   o Rise ( F)   Med-Low   Pink   Heating   28   1505   45   29   1452   47   31   1413   48   32   1358   50   33   1323   51   35   1282   53   NA   1234   55   NA   1169   58   NA   1130   60   o Rise ( C)   CFM   Heating   o 35 - 65 F   o 1 Rise ( F)   48VT(-,N)A36090   Medium   Red   o (19 - 36 C)   Heating   25   1545   44   26   1492   46   27   1449   47   28   1411   48   29   1362   50   29   1313   52   31   1278   53   32   1231   55   33   1188   57   o Rise ( C)   CFM   Heating   o 2 Rise ( F)   Med-High   High   Orange   Black   Heating   24   1705   40   25   1643   41   26   1607   42   27   1568   43   28   1518   45   29   1483   46   30   1448   47   31   1404   48   32   1360   50   o Rise ( C)   CFM   Heating   o Rise ( F)   Heating   22   23   24   24   25   25   26   27   28   o Rise ( C)   20   Table 10 -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 48VT--A24--60 Cont   HEATING   RISE   EXTERNAL STATIC PRESSURE (in. W.C.)   MOTOR   SPEED   WIRE   UNIT   COLOR   0.1   1295   34   0.2   1234   36   0.3   1182   38   0.4   1126   39   0.5   1075   41   0.6   1016   44   0.7   955   47   0.8   898   49   0.9   857   52   RANGE   CFM   Heating   o 1 Rise ( F)   Low   Blue   Pink   Heating   19   1345   33   20   1282   35   21   1235   36   22   1194   37   23   1140   39   24   1095   41   26   1027   43   27   974   46   29   921   48   o Rise ( C)   CFM   Heating   o Rise ( F)   Med-Low   Medium   Heating   18   1505   30   19   1452   31   20   1413   31   21   1358   33   22   1323   34   23   1282   35   24   1234   36   25   1169   38   27   1130   39   o Rise ( C)   CFM   Heating   o 25 - 55 F   o Rise ( F)   48VT(-,N)A42060   Red   o (14 - 31 C)   Heating   16   1545   29   17   1492   30   17   1449   31   18   1411   31   19   1362   33   19   1313   34   20   1278   35   21   1231   36   22   1188   37   o Rise ( C)   CFM   Heating   o 2 Rise ( F)   Med-High   High   Orange   Black   Blue   Heating   16   1705   26   17   1643   27   17   1607   28   17   1568   28   18   1518   29   19   1483   30   19   1448   31   20   1404   32   21   1360   33   o Rise ( C)   CFM   Heating   o Rise ( F)   Heating   14   1295   53   15   1234   55   15   1182   58   16   1126   60   16   1075   63   17   1016   NA   17   955   NA   18   898   NA   18   857   NA   o Rise ( C)   CFM   Heating   o Rise ( F)   Low   Heating   29   1345   51   31   1282   53   32   1235   55   34   1194   57   35   1140   60   NA   1095   62   NA   1027   NA   NA   974   NA   NA   921   NA   o Rise ( C)   CFM   Heating   o Rise ( F)   Med-Low   Pink   Heating   28   1505   45   29   1452   47   31   1413   48   32   1358   50   33   1323   51   35   1282   53   NA   1234   55   NA   1169   58   NA   1130   60   o Rise ( C)   CFM   Heating   o 35 - 65 F   o 1 Rise ( F)   48VT(-,N)A42090   Medium   Red   o (19 - 36 C)   Heating   25   1545   44   26   1492   46   27   1449   47   28   1411   48   29   1362   50   29   1313   52   31   1278   53   32   1231   55   33   1188   57   o Rise ( C)   CFM   Heating   o 2 Rise ( F)   Med-High   High   Orange   Black   Blue   Heating   24   1705   40   25   1643   41   26   1607   42   27   1568   43   28   1518   45   29   1483   46   30   1448   47   31   1404   48   32   1360   50   o Rise ( C)   CFM   Heating   o Rise ( F)   Heating   22   1445   47   23   1389   49   24   1341   51   24   1281   53   25   1236   55   25   1189   57   26   1139   60   27   1072   63   28   1027   NA   o Rise ( C)   CFM   Heating   o 1 Rise ( F)   Low   Heating   26   1678   41   27   1635   42   28   1602   42   29   1558   44   31   1513   45   32   1474   46   33   1438   47   35   1404   48   NA   1349   50   o Rise ( C)   CFM   Heating   o 2 Rise ( F)   Med-Low   Medium   Med-High   High   Pink   Heating   23   1962   35   23   1915   36   24   1880   36   24   1843   37   25   1794   38   26   1753   39   26   1711   40   27   1675   41   28   1628   42   o Rise ( C)   CFM   Heating   o 35 - 65 F   o Rise ( F)   48VT(-,N)A48090   Red   o (19 - 36 C)   Heating   19   2131   NA   20   2088   NA   20   2065   NA   20   2013   NA   21   1982   NA   22   1941   35   22   1888   36   23   1860   37   23   1785   38   o Rise ( C)   CFM   Heating   o Rise ( F)   Orange   Black   Heating   NA   2461   NA   NA   2409   NA   NA   2339   NA   NA   2286   NA   NA   2192   NA   19   2140   NA   20   2062   NA   20   1968   35   21   1874   36   o Rise ( C)   CFM   Heating   o Rise ( F)   Heating   NA   NA   NA   NA   NA   NA   NA   19   20   o Rise ( C)   21   Table 10 -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 48VT--A24--60 Cont   HEATING   RISE   EXTERNAL STATIC PRESSURE (in. W.C.)   MOTOR   SPEED   WIRE   UNIT   COLOR   0.1   1445   60   0.2   1389   NA   0.3   1341   NA   0.4   1281   NA   0.5   1236   NA   0.6   1189   NA   0.7   1139   NA   0.8   1072   NA   0.9   1027   NA   RANGE   CFM   Heating   o Rise ( F)   Low   Blue   Pink   Heating   33   1678   52   NA   1635   53   NA   1602   54   NA   1558   56   NA   1513   57   NA   1474   59   NA   1438   60   NA   1404   NA   NA   1349   NA   o Rise ( C)   CFM   Heating   o 2 Rise ( F)   Med-Low   Medium   Med-High   High   Heating   29   1962   44   30   1915   45   30   1880   46   31   1843   47   32   1794   48   33   1753   50   34   1711   51   NA   1675   52   NA   1628   53   o Rise ( C)   CFM   Heating   o 30 - 60 F   o Rise ( F)   48VT(-,N)A48115   Red   o (17 - 33 C)   Heating   25   2131   41   25   2088   42   26   2065   42   26   2013   43   27   1982   44   28   1941   45   28   1888   46   29   1860   47   30   1785   49   o Rise ( C)   CFM   Heating   o 1 Rise ( F)   Orange   Black   Blue   Heating   23   2461   35   23   2409   36   23   2339   37   24   2286   38   24   2192   40   25   2140   41   26   2062   42   26   1968   44   27   1874   46   o Rise ( C)   CFM   Heating   o Rise ( F)   Heating   20   1445   NA   20   1389   NA   21   1341   NA   21   1281   NA   22   1236   NA   23   1189   NA   23   1139   NA   25   1072   NA   26   1027   NA   o Rise ( C)   CFM   Heating   o Rise ( F)   Low   Heating   NA   1678   57   NA   1635   59   NA   1602   60   NA   1558   62   NA   1513   64   NA   1474   65   NA   1438   NA   NA   1404   NA   NA   1349   NA   o Rise ( C)   CFM   Heating   o 2 Rise ( F)   Med-Low   Medium   Med-High   High   Pink   Heating   32   1962   49   33   1915   50   33   1880   51   34   1843   52   35   1794   54   36   1753   55   NA   1711   56   NA   1675   57   NA   1628   59   o Rise ( C)   CFM   Heating   o 35 - 65 F   o Rise ( F)   48VT(-,N)A48130   Red   o (19 - 36 C)   Heating   27   2131   45   28   2088   46   28   2065   47   29   2013   48   30   1982   49   31   1941   50   31   1888   51   32   1860   52   33   1785   54   o Rise ( C)   CFM   Heating   o 1 Rise ( F)   Orange   Black   Blue   Heating   25   2461   39   26   2409   40   26   2339   41   27   2286   42   27   2192   44   28   2140   45   28   2062   47   29   1968   49   30   1874   51   o Rise ( C)   CFM   Heating   o Rise ( F)   Heating   22   1448   47   22   1362   50   23   1296   52   23   1226   55   24   1168   58   25   1108   61   26   1071   63   27   998   NA   29   905   NA   o Rise ( C)   CFM   Heating   o 1 Rise ( F)   Low   Heating   26   1722   39   28   1675   41   29   1614   42   31   1543   44   32   1499   45   34   1442   47   35   1408   48   NA   1356   50   NA   1308   52   o Rise ( C)   CFM   Heating   o Rise ( F)   Med-Low   Pink   Heating   22   1887   36   23   1847   37   23   1783   38   24   1726   39   25   1677   41   26   1625   42   27   1578   43   28   1527   45   29   1432   47   o Rise ( C)   CFM   Heating   o 35 - 65 F   o 2 Rise ( F)   48VT(-,N)A60090   Medium   Red   o (19 - 36 C)   Heating   20   2055   NA   20   2008   NA   21   1958   35   22   1927   35   23   1900   36   23   1768   38   24   1685   40   25   1581   43   26   1458   47   o Rise ( C)   CFM   Heating   o Rise ( F)   Med-High   High   Orange   Black   Heating   NA   2292   NA   NA   2238   NA   19   2158   NA   20   2049   NA   20   1935   35   21   1840   37   22   1732   39   24   1635   42   26   1513   45   o Rise ( C)   CFM   Heating   o Rise ( F)   Heating   NA   NA   NA   NA   20   21   22   23   25   o Rise ( C)   22   Table 10 -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 48VT--A24--60 Cont   HEATING   RISE   EXTERNAL STATIC PRESSURE (in. W.C.)   MOTOR   SPEED   WIRE   UNIT   COLOR   0.1   1448   60   0.2   1362   NA   0.3   1296   NA   0.4   1226   NA   0.5   1168   NA   0.6   1108   NA   0.7   1071   NA   0.8   998   NA   0.9   905   NA   RANGE   CFM   Heating   o Rise ( F)   Low   Blue   Pink   Heating   33   1722   50   NA   1675   52   NA   1614   54   NA   1543   56   NA   1499   58   NA   1442   60   NA   1408   NA   NA   1356   NA   NA   1308   NA   o Rise ( C)   CFM   Heating   o Rise ( F)   Med-Low   Heating   28   1887   46   29   1847   47   30   1783   49   31   1726   50   32   1677   52   33   1625   53   NA   1578   55   NA   1527   57   NA   1432   NA   o Rise ( C)   CFM   Heating   o 30 - 60 F   o 2 Rise ( F)   48VT(-,N)A60115   Medium   Red   o (17 - 33 C)   Heating   26   2055   42   26   2008   43   27   1958   44   28   1927   45   29   1900   46   30   1768   49   31   1685   52   32   1581   55   NA   1458   60   o Rise ( C)   CFM   Heating   o 1 Rise ( F)   Med-High   High   Orange   Black   Blue   Heating   23   2292   38   24   2238   39   25   2158   40   25   2049   42   25   1935   45   27   1840   47   29   1732   50   31   1635   53   33   1513   57   o Rise ( C)   CFM   Heating   o Rise ( F)   Heating   21   1448   NA   22   1321   NA   22   1282   NA   24   1235   NA   25   1192   NA   26   1145   NA   28   1101   NA   30   1057   NA   32   1011   NA   o Rise ( C)   CFM   Heating   o Rise ( F)   Low   Heating   NA   1722   56   NA   1675   57   NA   1614   60   NA   1543   62   NA   1499   64   NA   1442   NA   NA   1408   NA   NA   1356   NA   NA   1308   NA   o Rise ( C)   CFM   Heating   o Rise ( F)   Med-Low   Pink   Heating   31   1887   51   32   1847   52   33   1783   54   35   1726   56   36   1677   57   NA   1625   59   NA   1578   61   NA   1527   63   NA   1432   NA   o Rise ( C)   CFM   Heating   o 35 - 65 F   o 2 Rise ( F)   48VT(-,N)A60130   Medium   Red   o (19 - 36 C)   Heating   28   2055   47   29   2008   48   30   1958   49   31   1927   50   32   1900   51   33   1768   54   34   1685   57   35   1581   61   NA   1458   NA   o Rise ( C)   CFM   Heating   o 1 Rise ( F)   Med-High   High   Orange   Black   Heating   26   2292   42   27   2238   43   27   2158   45   28   2049   47   28   1935   50   30   1840   52   32   1732   56   34   1635   59   NA   1513   64   o Rise ( C)   CFM   Heating   o Rise ( F)   Heating   23   24   25   26   28   29   31   33   35   o Rise ( C)   * Air delivery values are without air filter and are for dry coil (See 48VT---A Wet Coil Pressure Drop table).   1 Factory---shipped gas heating speed   Factory---shipped heat pump speed   2 NA --- Not allowed for heating speed   Note: Deduct field---supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.   Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.   23   A09068   Fig. 15 -- 208/230--1--60 Wiring Diagram, Unit 48VT--A   24   A09209   Fig. 16 -- 208/230--3--60 Wiring Diagram, Unit 48VT--A   25   A09099   Fig. 17 -- Cooling Charging Table--Subcooling   26   5. Check and inspect heating section before each heating   season. Clean and adjust when necessary.   6. Check flue hood and remove any obstructions, if necessary.   MAINTENANCE   To ensure continuing high performance and to minimize the   possibility of premature equipment failure, periodic maintenance   must be performed on this equipment. This combination   heating/cooling unit should be inspected at least once each year by   a qualified service person. To troubleshoot cooling or heating of   units, refer to Tables 10, 11 and 12.   Air Filter   IMPORTANT: Never operate the unit without a suitable air filter   in the return--air duct system. Always replace the filter with the   same dimensional size and type as originally installed. (See Table 1   for recommended filter sizes.)   NOTE: Consult your local dealer about the availability of a   maintenance contract.   Inspect air filter(s) at least once each month and replace   (throwaway--type) or clean (cleanable--type) at least twice during   each heating and cooling season or whenever the filter(s) becomes   clogged with dust and/or lint.   ! WARNING   PERSONAL INJURY AND UNIT DAMAGE HAZARD   Indoor Blower and Motor   NOTE: All motors are prelubricated. Do not attempt to lubricate   these motors.   Failure to follow this warning could result in personal injury   or death and unit component damage.   The ability to properly perform maintenance on this   equipment requires certain expertise, mechanical skills, tools   and equipment. If you do not possess these, do not attempt to   perform any maintenance on this equipment, other than those   procedures recommended in the Owner’s Manual.   For longer life, operating economy, and continuing efficiency,   clean accumulated dirt and grease from the blower wheel and   motor annually.   ! WARNING   ! ELECTRICAL SHOCK HAZARD   WARNING   Failure to follow this warning could result in personal injury   or death.   ELECTRICAL SHOCK HAZARD   Failure to follow these warnings could result in personal   injury or death:   Disconnect and tag electrical powerto theunit beforecleaning   the blower motor and wheel.   1. Turn off electrical power to the unit and install a lockout   tag before performing any maintenance or service on this   unit.   Cleaning the Blower Motor and Wheel   1. Remove and disassemble blower assembly as follows:   a. Remove blower access panel (see Fig. 19).   b. Disconnect 5 pin plug and 4 pin plug from indoor   blower motor. Remove capacitor if required.   c. On all units, remove blower assembly from unit.   Remove screws securing blower to blower partition and   slide assembly out. Be careful not to tear insulation in   blower compartment.   2. Use extreme caution when removing panels and parts.   3. Never place anything combustible either on or in contact   with the unit.   4. Should overheating occur or the gas supply fail to shut   off, turn off external main manual gas valve to the unit.   Then shut off electrical supply.   d. Ensure proper reassembly by marking blower wheel and   motor in relation to blower housing before disassembly.   e. Loosen setscrew(s) that secures wheel to motor shaft.   Remove screws that secure motor mount brackets to   housing, and slide motor and motor mount out of   housing.   ! CAUTION   UNIT OPERATION HAZARD   Failure to follow this caution may result in improper   operation.   2. Remove and clean blower wheel as follows:   a. Ensure proper reassembly by marking wheel orientation.   Errors made when reconnecting wires may cause improper   and dangerous operation. Label all wires prior to   disconnecting when servicing.   b. Lift wheel from housing. When handling and/or   cleaning blower wheel, be sure not to disturb balance   weights (clips) on blower wheel vanes.   The minimum maintenance requirements for this equipment are as   follows:   c. Remove caked--on dirt from wheel and housing with a   brush. Remove lint and/or dirt accumulations from   wheel and housing with vacuum cleaner, using soft   brush attachment. Remove grease and oil with mild   solvent.   1. Inspect air filter(s) each month. Clean or replace when   necessary. Certain geographical locations may require more   frequent inspections.   2. Inspect indoor coil, outdoor coil, drain pan, and condensate   drain each cooling season for cleanliness. Clean when   necessary.   d. Reassemble wheel into housing.   e. Reassemble motor into housing. Be sure setscrews are   tightened on motor shaft flats and not on round part of   shaft. Reinstall blower into unit. Reinstall capacitor.   3. Inspect blower motor and wheel for cleanliness at the   beginning of each heating and cooling season. Clean when   necessary. For first heating and cooling season, inspect   blower wheel bi--monthly to determine proper cleaning   frequency.   f. Connect 5 pin plug and 4 pin plug to indoor blower   motor.   g. Reinstall blower access panel (see Fig. 19).   3. Restore electrical power to unit. Start unit and check for   proper blower rotation and motor speeds during heating and   cooling cycles.   4. Check electrical connections for tightness and controls for   proper operation each heating and cooling season. Service   when necessary. Ensure electrical wiring is not in contact   with refrigerant tubing or sharp metal edges.   27   directions in the Induced Draft Blower Assembly section.   Integrated   Gas Unit   Controller   (IGC)   2. Remove the 11 screws holding the flue collector box cover   (See Fig. 18) to the heat exchanger assembly. Inspect the   heat exchangers.   Auto Transformer   fuses used on 460   volt units only.   (Hidden)   3. Clean all surfaces, as required, using a wire brush.   Limit Switch   Interface Fan   Board (IFB)   Remove blower access panel (see Fig. 19). Limit switch is located   on the fan partition.   Induced Draft   Motor   Burner Ignition   Unit is equipped with a direct spark ignition 100 percent lockout   system. Ignition module (IGC) is located in the control box (See   Fan Partition   Mounting   Bracket   Flue   Collector   Box   Rollout   Switch   Inducer   Blower   Housing   Burner   Rack   Mounting   Screw   Fig. 18). Module contains   a self--diagnostic LED. During   servicing, refer to label diagram or Table 5 in these instructions for   LED interpretation.   A09199   Fig. 18 -- Blower Housing and Flue Collector Box   If lockout occurs, unit may be reset by either momentarily   interrupting power supply to unit or by turning selector switch to   OFF position at the thermostat.   Main Burners   At the beginning of each heating season, inspect for deterioration   or blockage due to corrosion or other causes. Observe the main   burner flames and adjust, if necessary.   Removal of Gas Train   To remove the gas train for servicing:   1. Shut off main gas valve.   2. Shut off power to unit and install lockout tag.   3. Remove control access panel (See Fig. 19).   4. Disconnect gas piping at unit gas valve.   5. Remove fan partition mounting bracket (2 screws located   on the left side of control compartment on the fan partition   panel). Slide bracket forward, bottom first to remove. (See   Fig. 18).   Control   Access   Panel   Blower   Access   Panel   Compressor   Access Panel   6. Remove wires connected to gas valve. Mark each wire.   7. Remove ignitor and sensor wires at the ignitor module.   A09210   8. Remove the mounting screw that attaches the burner rack to   the unit base (See Fig. 18).   Fig. 19 -- Unit Access Panels   Induced Draft (combustion air) Blower Assembly   The induced--draft blower assembly consists of the inducer motor,   the blower housing, and the induced--draft blower wheel.   Clean periodically to assure proper airflow and heating efficiency.   Inspect blower wheel every fall and periodically during the heating   season. For the first heating season, inspect blower wheel   bimonthly to determine proper cleaning frequency.   To inspect blower wheel, remove draft hood assembly. Shine a   flashlight into opening to inspect wheel. If cleaning is required,   remove induced--draft blower assembly as follows:   9. Slide the burner rack out of the unit (See Fig. 18 and 21).   10. To reinstall, reverse the procedure outlined above.   Outdoor Coil, Indoor Coil, and Condensate Drain Pan   Inspect the outdoor coil, indoor coil, and condensate drain pan at   least once each year. The coils are easily cleaned when dry;   therefore, inspect and clean the coils either before or after each   cooling season. Remove all obstructions, including weeds and   shrubs, that interfere with the airflow through the condenser coil.   Straighten bent fins with a fin comb. If coated with dirt or lint,   clean the coils with a vacuum cleaner, using the soft brush   attachment. Be careful not to bend the fins. If coated with oil or   grease, clean the coils with a mild detergent--and--water solution.   Rinse coils with clear water, using a garden hose. Be careful not to   splash water on motors, insulation, wiring, or air filter(s). For best   results, spray outdoor coil fins from inside to outside the unit. On   units with an outer and inner condenser coil, be sure to clean   between the coils. Be sure to flush all dirt and debris from the unit   base.   Inspect the drain pan and condensate drain line when inspecting   the coils. Clean the drain pan and condensate drain by removing all   foreign matter from the pan. Flush the pan and drain tube with   clear water. Do not splash water on the insulation, motor, wiring, or   air filter(s). If the drain tube is restricted, clear it with a “plumbers   snake” or similar probe device. Ensure that the auxiliary drain port   above the drain tube is also clear.   1. Remove control access panel (See Fig. 19).   2. Remove the 5 screws that attach induced--draft blower as-   sembly to the flue collector box cover.   3. Slide the assembly out of the unit. (See Fig. 20). Clean the   blower wheel. If additional cleaning is required, continue   with Steps 4 and 5.   4. To remove blower wheel, remove 2 setscrews.   5. To remove inducer motor, remove screws that hold the   inducer motor to the blower housing.   6. To reinstall, reverse the procedure outlined above.   Flue Gas Passageways   To inspect the flue collector box and upper areas of the heat   exchanger:   1. Remove the induced draft blower assembly according to   28   Outdoor Fan   ! BLOWER   HOUSING   CAUTION   UNIT OPERATION HAZARD   Failure to follow this caution may result in damage to unit   components.   Keep the outdoor fan free from all obstructions to ensure   proper cooling operation. Never place articles on top of the   unit.   1. Remove 6 screws holding outdoor grille and motor to top   cover.   2 SETSCREWS   (HIDDEN)   2. Turn motor/grille assembly upside down on top cover to   expose the fan blade.   3. Inspect the fan blades for cracks or bends.   4. If fan needs to be removed, loosen the setscrew and slide the   fan off the motor shaft.   5. When replacing fan blade, position blade back to the same   position as before.   C99085   6. Ensure that setscrew engages the flat area on the motor shaft   when tightening.   Fig. 20 -- Removal of Motor and Blower Wheel   7. Replace grille.   Electrical Controls and Wiring   Inspect and check the electrical controls and wiring annually. Be   sure to turn off the gas supply, and then the electrical power to the   unit.   Remove access panels (see Fig. 19) to locate all the electrical   controls and wiring. Check all electrical connections for tightness.   Tighten all screw connections. If any discolored or burned   connections are noticed, disassemble the connection, clean all the   parts, re--strip the wire end and reassemble the connection properly   and securely.   After inspecting the electrical controls and wiring, replace the   access panels (see Fig. 19). Start the unit, and observe at least one   complete heating cycle and one complete cooling cycle to ensure   proper operation. If discrepancies are observed in any operating   cycle, or if a suspected malfunction has occurred, check each   electrical component with the proper electrical instrumentation.   Refer to the unit wiring label when making these checkouts.   A07680   Fig. 21 -- Burner Rack Removed   FEEDER TUBE   STUB TUBE   NOTE: Refer to the heating and/or cooling sequence of operation   in this publication as an aid in determining proper control   operation.   Refrigerant Circuit   Annually inspect all refrigerant tubing connections and the unit   base for oil accumulations. Detecting oil generally indicates a   refrigerant leak.   ! WARNING   DEFROST   THERMOSTAT   EXPLOSION,   ENVIRONMENTAL HAZARD   PERSONAL   INJURY   AND   C99029   Failure to follow this warning could result in personal injury,   death or property damage.   Fig. 22 -- Defrost Thermostat Location   System under pressure. Relieve pressure and recover all   refrigerant before system repair or final unit disposal. Use all   service ports and open all flow--control devices, including   solenoid valves.   If oil is detected or if low cooling performance is suspected,   leak--test all refrigerant tubing using an electronic leak--detector,   halide torch, or liquid--soap solution. If a refrigerant leak is   detected, refer to the Check for Refrigerant Leaks section.   29   If no refrigerant leaks are found and low cooling performance is   suspected, refer to the Checking and Adjusting Refrigerant Charge   section.   switches are specifically designed to operate with Puron (R--410A)   systems. R--22 pressure switches must not be used as replacements   for the Puron (R--410A) system.   Gas Input   Loss of Charge Switch   The gas input does not require checking unless improper heating   performance is suspected. If a problem exists, refer to the Start--Up   section.   This switch is located on the liquid line and protects against low   suction pressures caused by such events as loss of charge, low   airflow across indoor coil, dirty filters, etc. It opens on a pressure   drop at about 20 psig. If system pressure is above this, switch   should be closed. To check switch:   Indoor Airflow   The heating and/or cooling airflow does not require checking   unless improper performance is suspected. If a problem exists, be   sure that all supply-- and return--air grilles are open and free from   obstructions, and that the air filter is clean. When necessary, refer to   the Indoor Airflow and Airflow Adjustments section to check the   system airflow.   1. Turn off all power to unit.   2. Disconnect leads on switch.   3. Apply ohm meter leads across switch. You should have   continuity on a good switch.   NOTE: Because these switches are attached to refrigeration   system under pressure, it is not advisable to remove this device for   troubleshooting unless you are reasonably certain that a problem   exists. If switch must be removed, remove and recover all system   charge so that pressure gauges read 0 psi. Never open system   without breaking vacuum with dry nitrogen.   Check Defrost Thermostat   The defrost thermostat is usually located on the lowest liquid   leaving circuit of the left condenser coil (see Fig. 22). The   thermostat closes at 32_F (0_C) and opens at 65_F (18_C).   Puron Items   High--Pressure Switch   Metering Device (Thermostatic Expansion Valve &   Piston)   This unit uses both a hard shutoff, balance port TXV in the indoor   coil and a piston in each side of the outdoor coil. The TXV   maintains a constant superheat at the evaporator coil exit (cooling   mode) resulting in higher overall system efficiency.   The high--pressure switch is located in the discharge line and   protects against excessive condenser coil pressure. It opens at 650   psig.   High pressure may be caused by a dirty outdoor coil, failed fan   motor, or outdoor air recirculation. To check switch:   1. Turn off all power to unit.   2. Disconnect leads on switch.   Pressure Switches   Pressure switches are protective devices wired into control circuit   (low voltage). They shut off compressor if abnormally high or low   pressures are present in the refrigeration circuit. These pressure   3. Apply ohm meter leads across switch. You should have   continuity on a good switch.   30   Speedup   Pins   Quiet   Shift   Defrost interval   DIP switches   A08020   Fig. 23 -- Defrost Control   Copeland Scroll Compressor (Puron Refrigerant)   The scroll compressor pumps refrigerant throughout the system by   the interaction of a stationary and an orbiting scroll. The scroll   compressor has no dynamic suction or discharge valves, and it is   more tolerant of stresses caused by debris, liquid slugging, and   flooded starts. The compressor is equipped with an internal   pressure relief port. The pressure relief port is a safety device,   designed to protect against extreme high pressure. The relief port   has an operating range between 550 and 625 psi differential   pressure.   The compressor used in this product is specifically designed to   operate with Puron (R--410A) refrigerant and cannot be   interchanged.   The compressor is an electrical (as well as mechanical) device.   Exercise extreme caution when working near compressors. Power   should be shut off, if possible, for most troubleshooting techniques.   Refrigerants present additional safety hazards.   ! WARNING   EXPLOSION HAZARD   Failure to follow this warning could result in personal injury   or death and/or property damage.   Wear safety glasses and gloves when handling refrigerants.   Keep torches and other ignition sources away from   refrigerants and oils.   31   C99097   Fig. 24 -- Refrigerant Circuit   INDOOR COIL   OUTDOOR COIL   TXV in Metering   Position   LCS   HPS   Bypass   Position   LEGEND   HPS – High Pressure Switch   LCS – Loss of Charge Switch   ® Accurater Metering Device   Arrow indicates direction of flow   C03011   Fig. 25 -- Typical Heat Pump Operation, Cooling Mode   32   INDOOR COIL   OUTDOOR COIL   TXV in Bypass   Position   LCS   HPS   Metering   Position   LEGEND   HPS – High Pressure Switch   LCS – Loss of Charge Switch   ® Accurater Metering Device   Arrow indicates direction of flow   C03012   Fig. 26 -- Typical Heat Pump Operation, Heating Mode   Synthetic Roof Precautionary Procedure   ! WARNING   1. Cover extended roof working area with an impermeable   polyethylene (plastic) drip cloth or tarp. Cover an   approximate 10x10 ft (3x3 m) area.   UNIT OPERATION AND SAFETY HAZARD   2. Cover area in front of the unit service panel with a terry   cloth shop towel to absorb lubricant spills and prevent   run--offs, and protect drop cloth from tears caused by tools   or components.   Failure to follow this warning could result in personal injury   or equipment damage.   This system uses Puron (R--410A) refrigerant which has   higher operating pressures than R--22 and other refrigerants.   No other refrigerant may be used in this system. Gauge set,   hoses,andrecoverysystemmustbe designedto handlePuron.   If you are unsure, consult the equipment manufacturer.   3. Place terry cloth shop towel inside unit immediately under   component(s) to be serviced and prevent lubricant run--offs   through the louvered openings in the unit base.   4. Perform required service.   5. Remove and dispose of any oil contaminated material per   local codes.   Refrigerant System   This information covers the refrigerant system of the 48VT--A   including the compressor oil needed, servicing systems on roofs   containing synthetic materials, the filter drier and refrigerant   charging.   Liquid Line Filter Drier   This filter drier is specifically designed to operate with Puron. Use   only factory--authorized components. Filter drier must be replaced   whenever the refrigerant system is opened. When removing a filter   drier, use a tubing cutter to cut the drier from the system. Do not   unsweat a filter drier from the system. Heat from unsweating will   release moisture and contaminants from drier into system.   Compressor Oil   If additional oil is needed use Uniqema RL32--3MAF. If this oil is   not available, use Copeland Ultra 32CC or Mobil Artic EAL22CC.   This oil is extremely hygroscopic, meaning it absorbs water   readily. POE oils can absorb 15 times as much water as other oils   designed for HCFC and CFC refrigerants. Take all necessary   precautions to avoid exposure of the oil to the atmosphere.   Puron (R--410A) Refrigerant Charging   Refer to unit information plate and charging chart. Some R--410A   refrigerant cylinders contain a dip tube to allow liquid refrigerant to   flow from cylinder in upright position. For cylinders equipped   with a dip tube, charge Puron units with cylinder in upright   position and a commercial metering device in manifold hose.   Charge refrigerant into suction--line.   Servicing Systems on Roofs and with Synthetic materials   POE (polyolester) compressor lubricants are known to cause long   term damage to some synthetic roofing materials.   Exposure, even if immediately cleaned up, may cause   embrittlement (leading to cracking) to occur in one year or more.   When performing any service that may risk exposure of   compressor oil to the roof, take appropriate precautions to protect   roofing. Procedures which risk oil leakage include, but are not   limited to, compressor replacement, repairing refrigerant leaks,   replacing refrigerant components such as filter drier, pressure   switch, metering device, coil, accumulator, or reversing valve.   TROUBLESHOOTING   Use the Troubleshooting Guides (See Tables 10--12) if problems   occur with these units.   START--UP CHECKLIST   Use Start--Up checklist to ensure proper start--up procedures are   followed.   33   PURONR (R--410A) QUICK REFERENCE GUIDE   S Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement   components are designed to operate with Puron   S S S Puron refrigerant cylinders are rose colored.   Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.   Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when   charging into suction line with compressor operating   S S S S S S S S S S S S S S S Manifold sets should be minimum 700 psig high side and 180 psig low side with 550 psig low--side retard.   Use hoses with minimum 700 psig service pressure rating.   Leak detectors should be designed to detect HFC refrigerant.   Puron, as with other HFCs, is only compatible with POE oils.   Vacuum pumps will not remove moisture from oil.   Do not use liquid--line filter driers with rated working pressures less than 600 psig.   Do not leave Puron suction line filter driers in line longer than 72 hrs.   Do not install a suction--line filter drier in liquid line.   POE oils absorb moisture rapidly. Do not expose oil to atmosphere.   POE oils may cause damage to certain plastics and roofing materials.   Wrap all filter driers and service valves with wet cloth when brazing.   A factory approved liquid--line filter drier is required on every unit.   Do NOT use an R--22 TXV.   Never open system to atmosphere while it is under a vacuum.   When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter   driers. Evacuate to 500 microns prior to recharging.   S S S Do not vent Puron into the atmosphere.   Observe all warnings, cautions, and bold text.   All indoor coils must be installed with a hard shutoff Puron TXV metering device.   34   Table 11 – Troubleshooting Guide -- Cooling or Heat Pump Heating Mode   SYMPTOM   CAUSE   REMEDY   Power Failure   Call power company.   Replace fuse or reset circuit breaker.   Fuse blown or circuit breaker tripped   Defective thermostat, contactor, transformer, or control   relay   Compressor and Outdoor fan will not   start.   Replace component.   Insufficient line voltage   Determine cause and correct.   Incorrect or faulty wiring   Check wiring diagram and rewire correctly.   Lower thermostat setting below room temperature.   Check wiring and repair or replace.   Thermostat setting too high   Faulty wiring or loose connections in compressor circuit   Compressor motor burned out, seized, or internal over-   load open   Determine cause Replace compressor.   Compressor will not start but Outdoor   fan runs.   Defective run/start capacitor, overload, start relay   Determine cause and replace.   Replace fuse or reset circuit breaker. Determine   cause.   One leg of 3---phase power dead   Three---phase scroll compressor makes   excessive noise, and there may   be a low pressure differential.   Correct the direction of rotation by reversing the   3---phase power leads to the unit.   Scroll compressor is rotating in the wrong direction   Refrigerant overcharge or undercharge   Recover refrigerant, evacuate system, and recharge   to capacities shown on nameplate.   Replace and determine cause.   Determine cause and correct.   Determine cause and correct.   Determine cause and replace.   Replace thermostat.   Defective compressor   Insufficient line voltage   Compressor cycles (other than normally   satisfying thermostat).   Blocked Outdoor   Defective run/start capacitor, overload or start relay   Defective thermostat   Faulty Outdoor---fan motor or capacitor   Damaged reversing valve   Restriction in refrigerant system   Dirty air filter   Replace.   Determine cause and correct   Locate restriction and remove.   Replace filter.   Unit undersized for load   Thermostat set too low   Low refrigerant charge   Mechanical damage in compressor.   Air in system   Decrease load or increase unit size.   Reset thermostat.   Locate leak, repair, and recharge.   Replace compressor.   Recover refrigerant, evacuate system, and recharge.   Check defrost time settings, Reset as necessary   Check defrost temperature switch, Replace as nec-   essary   Compressor operates continuously.   Excessive head pressure.   Frosted coil with incorrect defrost operation   Outdoor coil dirty or restricted   Dirty air filter   Dirty Indoor or Outdoor coil   Refrigerant overcharged   Air in system   Indoor or Outdoor air restricted or air short---cycling   Low refrigerant charge   Compressor IPR leaking   Restriction in liquid tube   High heat load   Compressor IPR leaking   Refrigerant overcharged   Reversing valve hung up or leaking internally   Dirty air filter   Low refrigerant charge   Metering device or low side restricted   Clean coil or remove restriction .   Replace filter.   Clean coil.   Recover excess refrigerant.   Recover refrigerant, evacuate system, and recharge.   Determine cause and correct.   Check for leaks, repair, and recharge.   Replace compressor.   Head pressure too low.   Remove restriction.   Check for source and eliminate.   Replace compressor.   Excessive suction pressure.   Recover excess refrigerant.   Replace valve   Replace Filter.   Check for leaks, repair, and recharge.   Remove source of restriction.   Increase air quantity. Check filter — replace if neces-   sary.   Insufficient Indoor airflow   Suction pressure too low.   Temperature too low in conditioned area   Outdoor ambient below 55°F (12.8°C)   Field---installed filter---drier restricted   Reset thermostat.   Install low---ambient kit.   Replace.   Move timer on control board to 30 minutes between   defrost cycles   (Heat) Outdoor coil frosted   Compressor runs but outdoor fan does   not   Check condition of relay on board Replace if neces-   sary   NC (normally closed) contacts on defrost board open   35   Table 12 – Troubleshooting Guide–Heating   SYMPTOM   CAUSE   REMEDY   Water in gas line   Drain. Install drip leg.   No power to furnace   Check power supply fuses, wiring or circuit breaker.   Check transformer.   NOTE: Some transformers have internal over--current protection   that requires a cool--down period to reset.   No 24--v power supply to control circuit   Burners will not ignite   Mis--wired or loose connections   Misaligned spark electrodes   Check all wiring and wire nut connections   Check flame ignition and sense electrode positioning.   Adjust as necessary.   1. Check gas line for air. Purge as necessary. NOTE: After purging   gas line of air, wait at least 5 minutes for any gas to dissipate be-   fore attempting to light unit.   No gas at main burners   2. Check gas valve.   Dirty air filter   Clean or replace filter as necessary   Gas input to furnace too low   Unit undersized for application   Restricted airflow   Check gas pressure at manifold match with that on unit nameplate   Replace with proper unit or add additional unit   Clean or replace filter. Remove any restriction.   Inadequate heating   Check rotation of blower, temperature rise of unit. Adjust as neces-   sary.   Limit switch cycles main burners   1. Tighten all screws around burner compartment   2. Cracked heat exchanger. Replace.   3. Unit over--fired. Reduce input (change orifices or adjust gas line   or manifold pressure).   4. Check burner alignment.   Incomplete combustion results in: Aldehyde odors,   carbon monoxide, sooting flame, floating flame   Poor flame characteristics   5. Inspect heat exchanger for blockage. Clean as necessary.   Table 13 – Troubleshooting Guide–LED Status Codes   SYMPTOM   CAUSE   REMEDY   Check 5--amp fuse son IGC*, power to unit, 24--v circuit breaker,   and transformer. Units without a 24--v circuit breaker have an   internal overload in the 24--v transformer. If the overload trips,   allow 10 minutes for automatic reset.   No Power Hardware failure   (LED OFF)   Loss of power to control module (IGC)*.   Check the operation of the indoor (evaporator) fan motor. Ensure   that the supply--air temperature rise is in accordance with the   range on the unit nameplate. Clean or replace filters.   Limit switch faults   (LED 2 flashes)   High temperature limit switch is open.   The IGC* sensed flame that should not be present.   Inadequate airflow to unit.   Flame sense fault   (LED 3 flashes)   Reset unit. If problem persists, replace control board.   4 consecutive limit switch   faults   (LED 4 flashes)   Check the operation of the indoor (evaporator) fan motor and that   supply--air temperature rise agrees with range on unit nameplate   information.   Check ignitor and flame sensor electrode spacing, gaps, etc.   Ensure that fame sense and ignition wires are properly terminated.   Verify that unit is obtaining proper amount of gas.   Verify wiring connections to pressure switch and inducer motor.   Verify pressure switch hose is tightly connected to both inducer   housing and pressure switch. Verify inducer wheel is properly   attached to inducer motor shaft. Verify inducer motor shaft is turn-   ing.   Ignition lockout   (LED 5 flashes)   Unit unsuccessfully attempted ignition for 15 minutes.   Open pressure switch.   Pressure Switch motor fault   (LED 6 flashes)   Rollout switch will automatically reset, but IGC* will continue to   lockout unit. Check gas valve operation. Ensure that induced--draft   blower wheel is properly secured to motor shaft. Inspect heat   exchanger. Reset unit at unit disconnect.   Rollout switch fault   (LED 7 flashes)   Rollout switch has opened.   Internal control fault   (LED 8 flashes)   Microprocessor has sensed an error in the software   or hardware.   If error code is not cleared by resetting unit power, replace the   IGC*.   Temporary 1 hr auto reset   (LED 9 flashes)   Reset 24--v. to control board or turn thermostat off, then on again.   Fault will automatically reset itself in one (1) hour.   Electrical interference impeding IGC software   *WARNING   : If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that my be present before handling new control   board. The IGC is sensitive to static electricity and my be damaged if the necessary precautions are not taken.   IMPORTANT: Refer to Table 12---Troubleshooting Guide---Heating for additional troubleshooting analysis.   LEGEND   IGC—Integrated Gas Unit Controller   LED—Light---Emitting Diode   36   START--UP CHECKLIST   (Remove and Store in Job Files)   I. PRELIMINARY INFORMATION   MODEL NO.:   SERIAL NO.:   DATE:   TECHNICIAN:   II. PRESTART--UP (Insert check mark in box as each item is completed)   ( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT   ( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS   ( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS   ( ) CHECK GAS PIPING FOR LEAKS (WHERE APPLICABLE)   ( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE   ( ) VERIFY THAT UNIT INSTALLATION IS LEVEL   ( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS   III. START--UP   ELECTRICAL   SUPPLY VOLTAGE   COMPRESSOR AMPS   INDOOR (EVAPORATOR) FAN AMPS   TEMPERATURES   OUTDOOR (CONDENSER) AIR TEMPERATURE   RETURN--AIR TEMPERATURE   DB   DB   WB   COOLING SUPPLY AIR   DB   WB   HEAT PUMP SUPPLY AIR__________________   GAS HEAT SUPPLY AIR   PRESSURES   GAS INLET PRESSURE   IN. W.C.   GAS MANIFOLD PRESSURE   REFRIGERANT SUCTION   REFRIGERANT DISCHARGE   IN. W.C.   PSIG, SUCTION LINE TEMP*   PSIG, LIQUID TEMP{   ( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS   GAS HEAT TEMPERATURE RISE   TEMPERATURE RISE (See Literature) RANGE   MEASURED TEMPERATURE RISE   * Measured at suction inlet to compressor   { Measured at liquid line leaving condenser.   37   Catalog No: 48VT---05SI   Copyright 2009 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231   Edition Date: 04/09   Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.   Replaces: 48VT---04SI   38   |