| 48SS-3SB   48SS018, 024, 030, 036, 042, 048 & 060   STANDARD-EFFICIENCY   COMBINATION GAS HEATING/   ELECTRIC COOLING UNITS   — PERFORMANCE DATA   — CERTIFIED DIMENSION PRINT   — CERTIFIED ROOF CURB   DIMENSION PRINT    1997 Carrier Corporation • Syracuse, New York 13221   Form 48SS-3SB Supersedes 48SS-2SB   Printed in U.S.A.   5-97   Catalog No. 514-847   CERTIFIED DIMENSION PRINT   REQ’D CLEARANCES FOR SERVICING — in. (mm)   UNIT   CORNER WEIGHT   (lb/kg)   UNIT   48SS   ELECTRICAL   Duct Panel   Unit Top .   . . . . . . . . . . . . . . . . . . . . . . . . 0   WEIGHT   CHARACTERISTICS   . . . . . . . . . . . . . . . . . . . . 36 (914.4)   . 36 (914.4)   . 36 (914.4)   lb   kg   A B C D Side Opposite Ducts   Compressor Access   . . . . . . . . . . . . . . . . . . . . . . . . . . OUTDOOR COIL   018040   024040   024060   030040   208/230-1-60   208/230-1-60   208/230-1-60   208/230-1-60   208/230-1-60   208/230-1-60   208/230-1-60   208/230-1-60   208/230-1-60   272   303   315   320   324   336   348   375   387   123   138   143   145   147   153   158   170   176   81/37   97/44   100/45   100/45   94/43   86/39   89/40   95/43   98/45   62/28   43/20   46/21   47/21   63/29   76/35   79/36   86/39   89/40   76/35   53/24   40/18   43/20   47/21   52/24   63/29   66/30   75/34   78/35   (Except for NEC requirements)   123/56   126/57   126/57   115/52   111/50   114/52   119/54   122/55   REQ’D CLEARANCES TO COMBUSTIBLE MAT’L   — in. (mm)   Maximum Extension of Overhangs   . . . . . . . . . . . 48 (1219.2)   . 14 (355.6)   030060/080   036060/080   036100/120   042060/080   042100/120   Unit Top .   Duct Side of Unit   Side Opposite Ducts   Bottom of Unit   Flue Panel   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)   . . . . . . . . 14 (355.6)   . 0   . 36 (914.4)   . . . . . . . . . . . . . . . . . . . . . . . . INDOOR COIL   . . . . . . . . . . . . . . . NEC (National Electrical Code) REQ’D CLEARANCES   — in. (mm)   UNIT   Between Units, Control Box Side   Unit and Ungrounded Surfaces,   . . . . . . . 42 (1066.8)   . 36 (914.4)   . 42 (1066.8)   DIMENSION   (in./mm)   CENTER OF GRAVITY   (in./mm)   HEIGHT   (in./mm)   UNIT   48SS   Control Box Side   . . . . . . . . . . . . . . Unit and Block or Concrete Walls and Other   Grounded Surfaces, Control Box Side   E F G X Y Z . . 018040   024040   024060   030040   24.12/612.8 169⁄16/420.7 1815⁄16/481.0 25.07/637 20.59/523 10.85/276   24.12/612.8 169⁄16/420.7 1815⁄16/481.0 27.07/688 23.35/693 10.85/276   24.12/612.8 169⁄16/420.7 1815⁄16/481.0 26.98/685 23.27/591 10.85/276   24.12/612.8 169⁄16/420.7 1815⁄16/481.0 26.71/678 23.46/596 10.85/276   030060/080 24.12/612.8 169⁄16/420.7 1815⁄16/481.0 27.15/689 22.36/568 10.85/276   036060/080 24.12/612.8 169⁄16/420.7 1815⁄16/481.0 27.50/698 22.48/571 10.85/276   036100/120 24.12/612.8 169⁄16/420.7 1815⁄16/481.0 27.40/696 22.44/570 10.85/276   042060/080 28.12/714.2 209⁄16/522.3 2215⁄16/582.6 27.01/686 22.44/570 12.65/321   042100/120 28.12/714.2 209⁄16/522.3 2215⁄16/582.6 26.94/684 22.44/570 12.65/321   NOTE: Clearances must be maintained to prevent recircu-   lation of air from outdoor fan discharge.   INDOOR COIL ACCESS   CERTIFIED DIMENSION PRINT   REQ’D CLEARANCES FOR SERVICING   — in. (mm)   UNIT WEIGHT   CORNER WEIGHT (lb/kg)   UNIT   48SS   ELECTRICAL   CHARACTERISTICS   lb   kg   A B C D Duct Panel   Unit Top   Side Opposite Ducts   Compressor Access .   . . . . . . . . . . . . . . . . . . . 0   018040   024040   024060   030040   208/230-1-60   208/230-1-60   296   327   339   344   356   135   149   155   157   162   87/40 68/31   82/37 59/27   OUTDOOR COIL   . . . . . . . . . . . . . . . . 36 (914.4)   . 36 (914.4)   . 36 (914.4)   103/47 49/22 129/59 46/21   106/48 52/24 132/60 49/22   106/48 53/24 132/60 53/24   102/46 71/32 123/56 60/27   . . . . . . . . . . . . . . . . 208/230-1-60   (Except for NEC requirements)   208/230-1-60, 208/230-3-60   208/230-1-60, 208/230-3-60   REQ’D CLEARANCES TO COMBUSTIBLE   MAT’L — in. (mm)   030060/080   208/230-1-60, 208/230-3-60,   460-3-60, 575-3-60   036060/080   360   372   399   411   164   169   181   187   92/42 82/37 117/53 69/31   95/43 85/39 120/55 72/33   101/46 92/42 125/57 81/37   104/47 95/43 128/58 84/38   Maximum Extension of   Overhangs   . . . . . . . . . . . . . . . . . . . . 48 (1219.2)   . 14 (355.6)   208/230-1-60, 208/230-3-60,   460-3-60, 575-3-60   036100/120   042060/080   042100/120   Unit Top   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Duct Side of Unit .   . . . . . 2 (50.8)   . 14 (355.6)   . 0   . 36 (914.4)   208/230-1-60, 208/230-3-60,   460-3-60   Side Opposite Ducts   Bottom of Unit .   Flue Panel .   INDOOR COIL   . . . . . . . . . . . . . 208/230-1-60, 208/230-3-60   460-3-60   NEC (National Electrical Code) REQ’D   CLEARANCES — in. (mm)   UNIT   HEIGHT   (in./mm)   DIMENSION   (in./mm)   CENTER OF GRAVITY   (in./mm)   Between Units, Control Box   UNIT   48SS   Side .   . . . . . . . . . . . . . . . . 42 (1066.8)   . . 36 (914.4)   Unit and Ungrounded Surfaces,   Control Box Side .   E F G X Y Z . . . . . . . . 018040   024040   024060   030040   27.43/696.7 197⁄8/504.8 221⁄4/565.4 25.04/636.0 22.72/577.0 13.16/334.3   27.43/696.7 197⁄8/504.8 221⁄4/565.4 26.90/683.3 20.17/512.3 13.16/334.3   27.43/696.7 197⁄8/504.8 221⁄4/565.4 26.82/681.2 20.22/513.6 13.16/334.3   27.43/696.7 197⁄8/504.8 221⁄4/565.4 26.57/674.9 20.05/509.3 13.16/334.3   Unit and Block or Concrete Walls and   Other Grounded Surfaces,   Control Box Side   . . . . . . . . . . 42 (1066.8)   030060/080 27.43/696.7 197⁄8/504.8 221⁄4/565.4 26.93/684.0 21.08/535.4 13.16/334.3   036060/080 27.43/696.7 197⁄8/504.8 221⁄4/565.4 27.31/693.7 20.97/532.6 13.16/334.3   036100/120 27.43/696.7 197⁄8/504.8 221⁄4/565.4 27.23/691.6 20.99/533.1 13.16/334.3   042060/080 31.43/798.3 237⁄8/606.4 261⁄4/666.8 26.87/682.5 20.99/533.1 14.96/380.0   042100/120 31.43/798.3 237⁄8/606.4 261⁄4/666.8 26.81/681.0 21.01/533.7 14.96/380.0   NOTE: Clearances must be maintained to prevent recircu-   lation of air from outdoor fan discharge, with the exception   of the outdoor coil as stated. A removable fence or barri-   cade requires no clearance.   INDOOR COIL ACCESS   CERTIFIED DIMENSION PRINT   OUTDOOR COIL   REQ’D CLEARANCES FOR SERVICING — in. (mm)   UNIT   CORNER WEIGHT   (lb/kg)   UNIT   48SS   ELECTRICAL   Duct Panel   Unit Top .   . . . . . . . . . . . . . . . . . . . . . . . . 0   WEIGHT   CHARACTERISTICS   . . . . . . . . . . . . . . . . . . . . 36 (914.4)   . 36 (914.4)   . 36 (914.4)   lb   kg   A B C D Side Opposite Ducts   Compressor Access   . . . . . . . . . . . . . . . . . . . . . . . . . . 048080   048100/120/140   060080   208/230-1-60   208/230-1-60   208/230-1-60   208/230-1-60   414 188 107/49 83/38 158/72 66/30   426 193 110/50 86/39 159/72 71/32   453 206 117/53 93/42 167/76 76/35   465 211 120/55 96/44 167/76 82/37   (Except for NEC requirements)   REQ’D CLEARANCES TO COMBUSTIBLE MAT’L   — in. (mm)   INDOOR COIL   060100/120/140   Maximum Extension of Overhangs   . . . . . . . . . . . 48 (1219.2)   . 14 (355.6)   Unit Top .   Duct Side of Unit   Side Opposite Ducts   Bottom of Unit   Flue Panel   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)   CENTER OF GRAVITY   (in./mm)   . . . . . . . . 14 (355.6)   . 0   . 36 (914.4)   UNIT   48SS   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X Y Z NEC (National Electrical Code) REQ’D CLEARANCES   — in. (mm)   048080   060080   28.76/731   23.46/596   23.42/595   23.27/591   23.23/590   15.35/390   15.35/390   15.35/390   15.35/390   048100/120/140   28.42/722   28.36/720   27.95/710   Between Units, Control Box Side   Unit and Ungrounded Surfaces,   . . . . . . . 42 (1066.8)   . 36 (914.4)   . 42 (1066.8)   060100/120/140   Control Box Side   . . . . . . . . . . . . . . Unit and Block or Concrete Walls and Other   Grounded Surfaces, Control Box Side   . . NOTE: Clearances must be maintained to prevent recircu-   lation of air from outdoor fan discharge.   INDOOR COIL ACCESS   CERTIFIED DIMENSION PRINT   REQ’D CLEARANCES FOR SERVICING   — in. (mm)   OUTDOOR COIL   UNIT   CORNER WEIGHT   (lb/kg)   UNIT   ELECTRICAL   WEIGHT   48SS   CHARACTERISTICS   Duct Panel   Unit Top .   . . . . . . . . . . . . . . . . . 0   lb   kg   A B C D . . . . . . . . . . . . . 36 (914.4)   . 36 (914.4)   . 36 (914.4)   208/230-1-60, 208/230-3-60,   460-3-60, 575-3-60   Side Opposite Ducts   Compressor Access   . . . . . . . . . . . . 048080   048100/120/140   060080   438 199 113/51   450 205 116/53   477 217 123/56   89/40 164/75 72/33   92/42 165/75 77/35   99/45 173/79 82/37   (Except for NEC requirements)   208/230-1-60, 208/230-3-60,   460-3-60, 575-3-60   REQ’D CLEARANCES TO COMBUSTIBLE   MAT’L — in. (mm)   208/230-1-60, 208/230-3-60,   460-3-60, 575-3-60   Maximum Extension of   208/230-1-60, 208/230-3-60,   460-3-60, 575-3-60   060100/120/140   489 222 126/57 102/46 173/79 88/40   Overhangs .   . . . . . . . . . . . . . . 48 (1219.2)   . 14 (355.6)   INDOOR COIL   Unit Top .   . . . . . . . . . . . . . . . . . . Duct Side of Unit   . . . . . . 2 (50.8)   . 14 (355.6)   . 0   . 36 (914.4)   Side Opposite Ducts   Bottom of Unit   Flue Panel   . . . . . . . . . . . . . . CENTER OF GRAVITY   (in./mm)   . . . . . . . . . . . UNIT   48SS   X Y Z 048080   060080   28.54/724.9   20.00/508.0   20.05/509.3   20.19/512.8   20.23/513.8   17.66/448   17.66/448   17.66/448   17.66/448   048100/120/140   28.22/716.8   28.18/715.8   27.79/705.9   060100/120/140   NEC (National Electrical Code) REQ’D CLEARANCES — in. (mm)   Between Units, Control Box Side   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 (1066.8)   Unit and Ungrounded Surfaces, Control Box Side   Unit and Block or Concrete Walls and Other   . . . . . . . . . . . . . . . . . . . . 36 (914.4)   Grounded Surfaces, Control Box Side   . . . . . . . . . . . . . . . . 42 (1066.8)   NOTE: Clearances must be maintained to prevent   recirculation of air from outdoor fan discharge.   INDOOR COIL ACCESS   CERTIFIED ROOF CURB DIMENSION PRINT   NOTES:   ‘‘A’’   1. Roof curb must be set up for unit being installed.   2. Seal strip must be applied as required for unit being installed.   3. Dimensions in [ ] are in millimeters.   4. Roof curb is made of 16 gage steel.   5. Attach ductwork to curb (flanges of duct rest on curb).   6. Service clearance 4 ft on each side.   PART NUMBER   CURB   (in./mm)   CPRFCURB001A00   CPRFCURB002A00   CPRFCURB003A00   8 [203]   FLAT   11 [279]   14 [356]   7.   Direction of airflow.   8. Insulated Panels: 1-in. thick fiberglass 1 lb density.   |