Hoshizaki America, Inc.
Hoshizaki
Cubelet Icemaker/Dispenser
Models
DCM-751BAH(-OS)
DCM-751BWH(-OS)
SERVICE MANUAL
“A Superior Degree
of Reliability”
Number: 73184
Issued: 8-31-2012
Revised: 9-24-2014
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read
the warnings and guidelines contained in this manual carefully as they provide
essential information for the continued safe use, service, and maintenance of the
appliance. Retain this manual for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. Construction and Water/Refrigeration Circuit Diagrams ..................................................... 7
A. Construction.................................................................................................................. 7
1. DCM-751BAH(-OS).................................................................................................. 7
2. DCM-751BWH(-OS)................................................................................................ 8
3. Ice Making Unit........................................................................................................ 9
B. Water/Refrigeration Circuit Diagrams.......................................................................... 10
1. DCM-751BAH(-OS)................................................................................................ 10
2. DCM-751BWH(-OS) ..............................................................................................11
II. Sequence of Operation and Service Diagnosis............................................................... 12
A. Sequence of Operation Flow Chart............................................................................. 12
B. Service Diagnosis ....................................................................................................... 13
C. Control Board Check................................................................................................... 18
D. Bin Control Check ....................................................................................................... 26
E. Float Switch Check and Cleaning ............................................................................... 27
F. Diagnostic Tables......................................................................................................... 29
1. No Ice Production................................................................................................... 29
2. Ice/Water Dispensing............................................................................................. 31
III. Controls and Adjustments............................................................................................... 32
A. Control Board Layout .................................................................................................. 33
1. DCM-751B_H......................................................................................................... 33
2. DCM-751B_H-OS.................................................................................................. 34
B. LED Lights and Audible Alarm Safeties....................................................................... 35
C. Settings and Adjustments............................................................................................ 36
1. Default Dip Switch Settings.................................................................................... 36
2. Infrared Sensor Shutdown Delay (S1 dip switch 1, 2, 3) ....................................... 36
3. Drain Frequency Control (S1 dip switch 4) ............................................................ 36
4. Continuous Dispensing Timer (S1 dip switch 5 & 6).............................................. 37
5. Bin Control Selector (S1 dip switch 7) ................................................................... 37
6. Bin Control Shutdown Delay (S1 dip switch 8) ...................................................... 37
7. Factory Use (S1 Dip Switch 9 & 10)....................................................................... 37
D. Power Switch, Control Switch, and Dispense Mode Switch ....................................... 38
IV. Removal and Replacement of Components ................................................................... 40
A. Service for Refrigerant Lines....................................................................................... 40
1. Refrigerant Recovery ............................................................................................. 41
2. Brazing .................................................................................................................. 41
3. Evacuation and Recharge (R-404A)...................................................................... 41
3
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Important Notes for Component Replacement............................................................ 42
C. Icemaking Unit ............................................................................................................ 44
1. Upper Bearing Wear Check .................................................................................. 44
2. Removal and Replacement of Extruding Head...................................................... 45
3. Removal and Replacement of Auger ..................................................................... 45
4. Removal and Replacement of Evaporator............................................................. 46
5. Removal and Replacement of Mechanical Seal and Lower Housing ................... 47
6. Removal and Replacement of Gear Motor ............................................................ 48
D. Dispense Components................................................................................................ 49
1. Dispense Auger and Agitator.................................................................................. 49
2. Dispense and Agitating Motors.............................................................................. 49
V. Maintenance .................................................................................................................... 50
VI. Preparing the Appliance for Periods of Non-Use............................................................ 51
VII. Disposal......................................................................................................................... 53
VIII. Technical Information.................................................................................................... 54
A. Specification Sheets.................................................................................................... 54
1. DCM-751BAH ....................................................................................................... 54
2. DCM-751BAH-OS ................................................................................................. 55
3. DCM-751BWH....................................................................................................... 56
4. DCM-751BWH-OS ................................................................................................ 57
B. Performance Data ....................................................................................................... 58
1. DCM-751BAH(-OS)................................................................................................ 58
2. DCM-751BWH(-OS).............................................................................................. 59
C. Wiring Diagrams.......................................................................................................... 60
1. DCM-751B_H......................................................................................................... 60
2. DCM-751B_H-OS.................................................................................................. 61
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Important Safety Information
Throughout this manual, notices appear to bring your attention to situations which could
result in death, serious injury, damage to the appliance, or damage to property.
WARNING
NOTICE
IMPORTANT
Indicates a hazardous situation which could result in death or
serious injury.
Indicates a situation which could result in damage to the
appliance or property.
Indicates important information about the use and care of the
appliance.
WARNING
The appliance should be destined only to the use for which it has been expressly
conceived. Any other use should be considered improper and therefore dangerous.
The manufacturer cannot be held responsible for injury or damage resulting from
improper, incorrect, and unreasonable use. Failure to service and maintain the
appliance in accordance with this manual will adversely affect safety, performance,
component life, and warranty coverage and may result in costly water damage.
To reduce the risk of death, electric shock, serious injury, or fire, follow basic
precautions including the following:
• Only qualified service technicians should install and service the appliance.
• The appliance must be installed in accordance with applicable national, state, and
local codes and regulations
• Electrical connection must be hard-wired and must meet national, state, and local
electrical code requirements. Failure to meet these code requirements could result
in death, electric shock, serious injury, fire, or damage to equipment.
• The appliance requires an independent power supply of proper capacity. See the
nameplate for electrical specifications. Failure to use an independent power supply
of proper capacity can result in a tripped breaker, blown fuse, damage to existing
wiring, or component failure. This could lead to heat generation or fire.
• THE APPLIANCE MUST BE GROUNDED. Failure to properly ground the appliance
could result in death, serious injury, or damage to equipment.
• To reduce the risk of electric shock, do not touch the power switch or control switch
with damp hands.
• Before servicing, move the power switch and control switch to the "OFF" position,
then turn off the power supply. Lockout/Tagout to prevent the power supply from
being turned back on inadvertently.
• Do not make any alterations to the appliance. Alterations could result in electric
shock, injury, fire, or damage to the appliance.
• Do not place fingers or any other objects into the ice discharge opening.
• The appliance is not intended for use by persons (including children) with reduced
physical, sensory, or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING, continued
• Children should be properly supervised around the appliance.
• Do not climb, stand, or hang on the appliance or allow children or animals to do so.
Serious injury could occur or the appliance could be damaged.
• Do not use combustible spray or place volatile or flammable substances near the
appliance. They might catch fire.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance
could cause harm to individuals or damage to the appliance.
NOTICE
• Follow the instructions in this manual carefully to reduce the risk of costly water
damage.
• In areas where water damage is a concern, install in a contained area with a floor
drain.
• Install the appliance in a location that stays above freezing. Normal operating
ambient temperature must be within 45°F to 100°F (7°C to 38°C).
• Do not leave the appliance on during extended periods of non-use, extended
absences, or in sub-freezing temperatures. To properly prepare the appliance for
these occasions, follow the instructions in "V.D. Preparing the Appliance for Periods
of Non-Use."
• Keep ventilation openings, in the appliance enclosure or in the built-in structure,
clear of obstruction.
• Do not place objects on top of the appliance.
• The storage bin is for ice use only. Do not store anything else in the storage bin.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
I. Construction and Water/Refrigeration Circuit Diagrams
A. Construction
Spout B
Storage Bin
1. DCM-751BAH(-OS)
Bin Control Switch
Control Box
Agitator (L)
Agitator (R)
Power Switch
Dispense Auger
Agitating Motor (L)
Agitating Motor (R)
4A1038-014
CONTROL
ICE
OFF
DISPENSE MODE
PORTION
Dispensing Motor
DRAIN
CONTINUOUS
Compressor
Spout A
Inlet Water Valve
Float Switch
Evaporator Assembly
Reservoir
Thermostatic Expansion Valve
Gear Motor
Dispense Water Valve
Shutter Assembly
Air-Cooled Condenser
Drain Valve
Spout Cover
Safety Switch (Door)
7
Download from Www.Somanuals.com. All Manuals Search And Download.
2. DCM-751BWH(-OS)
Spout B
Storage Bin
Bin Control Switch
Control Box
Agitator (L)
Agitator (R)
Power Switch
Dispense Auger
Agitating Motor (L)
Agitating Motor (R)
4A1038-014
CONTROL
ICE
OFF
DISPENSE MODE
PORTION
Dispensing Motor
DRAIN
CONTINUOUS
Compressor
Spout A
Inlet Water Valve
Float Switch
Evaporator Assembly
Reservoir
Thermostatic
Expansion Valve
Dispense Water Valve
Shutter Assembly
Gear Motor
Water Regulating Valve
Water-Cooled Condenser
Spout Cover
Drain Valve
Safety Switch (Door)
8
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Ice Making Unit
Cubelet Cutter
Extruding Head
and Upper Bearing
Allen Head Cap Screw
Washer
Extruding Head Heater
Auger
Cylinder
Evaporator
Insulation
Allen Head Cap Screw
with Washer
Mechanical Seal
O-Ring
Housing and
Lower Bearing
Hex Head Bolt
with Washer
Gear Motor
9
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Water/Refrigeration Circuit Diagrams
1. DCM-751BAH(-OS)
Spout
Inlet Water Valve
Water Supply
Float
Switch
Water Level
Reservoir
Overflow
Evaporator
Drier
Thermostatic
Expansion Valve
To Drain
Drain Valve
Gear Motor
Dispense Water Valve
Fan
Air-Cooled Condenser
High-Pressure Switch
Compressor
Refrigeration Circuit
Water Circuit
10
Download from Www.Somanuals.com. All Manuals Search And Download.
2. DCM-751BWH(-OS)
Spout
Inlet Water Valve
Water Supply
Float
Switch
Water Level
Evaporator
Reservoir
Overflow
Drier
Thermostatic
Expansion Valve
To Drain
Drain Valve
Gear Motor
Dispense Water Valve
Water In
Water Out
Water-Cooled Condenser
Water Regulating
Valve
High-Pressure Switch
Compressor
Refrigeration Circuit
Water Circuit
11
Download from Www.Somanuals.com. All Manuals Search And Download.
II. Sequence of Operation and Service Diagnosis
A. Sequence of Operation Flow Chart
12
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Service Diagnosis
WARNING
• The appliance should be diagnosed and repaired only by qualified service
personnel to reduce the risk of death, electric shock, serious injury, or fire.
• Risk of electric shock. Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are
securely in place after the appliance is serviced. Make sure that none have fallen
into the storage bin.
• Make sure all food zones in the appliance are clean after service. For cleaning
procedures, see the instruction manual or the maintenance label.
1. Ice Production Check
To check production, prepare a bucket or pan to catch the ice and a set of scales to
weigh the ice. After the appliance has operated for 10 to 20 minutes, catch the ice
production for 10 minutes. Weigh the ice to establish the batch weight. Multiply the batch
weight by 144 to calculate 24hr production. When confirming production or diagnosing
low production, see "VIII.B. Performance Data."
2. Diagnostic Procedure
This diagnostic procedure is a sequence check that allows you to diagnose the electrical
system and components. Before proceeding, check for correct installation, proper
voltage per unit nameplate, and adequate water supply. Check that the 24VAC 1A fuse
and GM 115VAC 3A fuse are good. When checking high-voltage (115VAC), always
choose a neutral (W) to establish a good neutral connection. When checking low-voltage
(24VAC), always choose a neutral (LBU) from CT to establish a good neutral connection.
When checking CB DC-voltage (5VDC), use CB red K4 connector pin closest to CB
black K3 connector for DC ground (GND). CB "POWER" LED remains on unless
power supply is interrupted. Check CB using the steps in "II.C. Control Board Check."
IMPORTANT! Appliance will not start unless the safety switch is engaged.
1) Turn on the power supply. Remove the front panel. Move the power switch to the "ON"
position, then move the control switch to the "DRAIN" position. Engage the safety
switch.
2) Allow the water system to drain for 5 minutes. If water does not drain, see step 12.
3) Disengage the safety switch, then move the control switch to the "OFF" position.
4) Move the power switch to the "OFF" position.
5) Remove the control box cover.
6) Engage the safety switch.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
7) Startup–"POWER OK" LED is on: Move the power switch to the "ON" position,
then move the control switch to the "ICE" position. CB "POWER OK" LED is on.
"POWER OK" LED Diagnosis: Check that CB "POWER" LED is on. If not, check for
proper power supply voltage (115VAC) input to CT. If 115VAC is not present, check the
breaker, power switch, and safety switch. Next, check that the power protect relay is
de-energized and contacts between terminals #6 (BR) and #2 (BK) are closed. Check
for proper control voltage (24VAC) output from CT. Next, check the 24VAC 1A fuse. If
open, replace. Check for 24VAC at CB K8 connector pin #1 (W/R) to CB K8 connector
pin #2 (LBU). If 24VAC is not present at CB K8 connector pin #1 (W/R) but is present at
1A fuse (W/R), check continuity of control switch. If open, replace. If 24VAC is present
between CB K8 connector pin #1 (W/R) and pin #2 (LBU), and "POWER OK" LED is
off, replace CB.
BC Diagnosis: Check that the actuator paddle is properly positioned. Check for
continuity across BC proximity switch. When BC proximity switch is closed 0VDC is
read across CB K8 connector pin #3 (GY) and #4 (GY). 5VDC is present between CB
K8 connector pin #3 (GY) or #4 (GY) to CB red K4 connector pin closest to CB black K3
black connector (5VDC GND). If 5VDC is not present, replace CB.
HPS Diagnosis: HPS automatically resets when refrigeration circuit high-side pressure
is within an acceptable range. 5VDC is supplied from CB K9 connector pin #3 (Y) and
back onto CB K9 connector pin #4 (Y). If 5VDC is not present at CB K9 connector pin
#3 (Y) to CB red K4 connector pin closest to CB black K3 connector (5VDC GND)
and CB "POWER OK" LED is on, replace CB. If refrigerant pressures have returned
to an acceptable range and HPS does not close, replace HPS. If pressures have not
equalized, and refrigeration circuit high-side pressure does not drop, recover, evacuate,
and recharge if necessary. On air-cooled model, check that the condenser is not dirty
or clogged, check for proper FM operation and fan blade for binding. On water-cooled
model, check WRV and water flow in and out of condenser. Check for refrigeration
circuit refrigerant restriction (TXV and drier).
8) Fill Cycle–"WTRIN" LED is on: WV energizes. 90-sec. FT starts. LFS closes. Nothing
happens at this time. Reservoir continues to fill. UFS closes, WV de-energizes, 90-sec.
FT terminates. Diagnosis: If the reservoir is empty, LFS open, "WTRIN" LED on, and
WV off, check for 24VAC at CB K2 connector pin #8 (W/BR) to a neutral (LBU).
If 24VAC is not present, confirm 24VAC power supply at CB K2 connector pin #7 (W/R)
to a neutral (LBU). If 24VAC is not present on CB K2 connector pin #7 (W/R), check
wiring connections from CT. If 24VAC is present on CB K2 connector pin #7 (W/R)
and not on CB K2 connector pin #8 (W/BR), replace CB. If 24VAC is present on CB
K2 connector pin #8 (W/BR), check for 24VAC at WV solenoid. If 24VAC is present,
replace WV. If WV is energized and fill/refill exceeds 90-sec. FT with no water in the
reservoir, check for clogged WV screen or DV leaking. Note: If UFS remains open
90 seconds after LFS opens (WV energized), a 1-beep alarm sounds (90 sec. FT). This
alarm resets automatically once UFS closes. If reservoir is full and overflowing, check
for open UFS. See "II.E. Float Switch Check and Cleaning." If WV de-energizes and
water continues to fill the reservoir, replace WV.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
9) Ice Purge Cycle–"GM" LED is on. UFS closes (WV de-energizes) and "WTRIN"
LED turns off. 5-sec. GM delay timer and 30-min. FZT start. 5-sec. GM delay timer
terminates. GM and GMPR energize. 5-min. IPT starts. GM runs for 5 min. to clear
any ice from the evaporator. Diagnosis: If "GM" LED is off, check that UFS closed.
If UFS is closed and "GM" LED does not turn on, replace CB. If "GM" LED is on and
GM is off, confirm 115VAC at CB K1 connector pin #2 (BR) to neutral (W). Check for
115VAC at CB K1 connector pin #3 (DBU) to a neutral (W). If no voltage is present at
CB K1 connector pin #2 (BR), check wiring connections. If no voltage is present at CB
K1 connector pin #3 (DBU), replace CB. If 115VAC is present, check 115VAC 3A GM
fuse, GM internal protector, GM windings, capacitor, and GM coupling between auger
and GM. If GM internal protector is open, allow to cool and reset. If reset does not
occur, replace GM. If Comp energizes at the same time GM energizes, check CB.
See "II.C. Control Board Check."
10) Freeze Cycle–"COMP" and "GM" LEDs are on. 5 min. IPT terminates. GM continues.
CB confirms GM operation through GMPR terminal #3 (W/O) and terminal #5 (W/O).
Comp and FM energize. Ice production begins 4 to 6 min. after Comp and FM energize
depending on ambient and water temperature conditions. Diagnosis: 5 min. after GM
energizes, confirm Comp LED turns on and Comp and FM energize. If not, check
that GMPR is energized (115VAC). Next, check continuity between GMPR terminal
#3 (W/O) and terminal #5 (W/O). If open, GMPR is de-energized or defective. If closed,
and "COMP" LED is not on, replace CB. If "COMP" LED turns on and Comp and FM
do not energize, confirm 115VAC at CB Comp X1 relay (BR) to a neutral (W). If 115VAC
is not present, check connections. If 115VAC is present, confirm 115VAC at CB Comp
X1 relay (R) to a neutral (W). If 115VAC is not present and "COMP" LED is on, replace
CB. If 115VAC is present, check Comp external protector (overload), allow to cool and
reset. If reset does not occur, replace external protector. Check Comp start and run
capacitors, Comp start relay, and Comp windings. If FM does not energize, check FM
run capacitor, that the fan blade is not binding, and that FM windings are good.
11) Refill/Low Water Safety–"COMP," "GM," and "WTRIN" are on. As ice is produced,
the water level in the reservoir drops. UFS opens. Nothing happens at this time. When
LFS opens, 90-sec. FT starts. WV energizes. Comp, FM, and GM continue. As water
fills the reservoir, LFS closes. Nothing happens at this time. When UFS closes, WV
de-energizes, 90-sec. FT terminates, and 30-min. FZT resets. This continues until BC
shuts down the appliance or power is turned off to the appliance. Diagnosis: Confirm
that the water level has dropped and UFS and LFS are open. See "II.E. Float Switch
Check and Cleaning." Check for dirty or sticking float switches, clogged WV screen,
defective WV coil, or DV leaking by. If UFS remains open 90 seconds after LFS opens
(WV energized), a 1-beep alarm sounds (90 sec. FT). This alarm resets automatically
once UFS closes. Comp and FM de-energize. GM de-energizes 90 sec. later. WV and
alarm continue until UFS closes.
Note: Each time UF/S closes, 30-minute FZT starts. 30-minute FZT resets when UF/S
closes again. If UF/S does not close again within 30 minutes, CB shuts down the
appliance and sounds a 5-beep alarm every 5 seconds. See "III.B. LED Lights
and Audible Alarm Safeties."
15
Download from Www.Somanuals.com. All Manuals Search And Download.
12) Drain Cycle–"FLUSH" (drain) LED is on. IMPORTANT! Drain valve will not energize
unless the safety switch is engaged. The appliance is factory set to drain the
evaporator and reservoir once every hour for 2 seconds. A manual drain is provided
when cleaning the appliance by moving the control switch from the "ICE" position to the
"DRAIN" position. A 1-in-12 drain cycle is also available. For further details, see "III.C. 3.
Drain Frequency Control (S1 dip switch 4)."
a) Automatic Drain Cycle: A drain cycle occurs once every hour for 2 seconds.
DCT terminates and DVT starts. Once DVT terminates, DCT resets and DV
de-energizes. DCT resets every time the power supply is turned off and on again.
Diagnosis: Once DCT terminates, DV energizes. If not, check for 24VAC from
K2 connector pin #10 (W/BU) to a neutral (LBU). If 24VAC is not present, replace CB.
If 24VAC is present, check for 24VAC at DV. If 24VAC is present and DV does not
energize, check DV solenoid continuity.
b) Manual Drain: Move control switch to the "OFF" position, pause momentarily, then
move to the "DRAIN" position. DV energizes.
DV continues until control switch is moved to "OFF" or "ICE" position or power is
turned off.
Note: a) A momentary pause in the "OFF" position is necessary to de-energize the
control board when moving the control switch between "ICE" and "DRAIN."
Otherwise there is a delay of several minutes before the new selection takes
effect.
b) If the control switch is left in the "DRAIN" position for 10 minutes or more, a
2-beep alarm sounds every 5 seconds. Move the control switch out of the
"DRAIN" position to clear the alarm.
Diagnosis: DV energizes. If not, check for 24VAC at CB K2 connector pin
#10 (W/BU) to a neutral (LBU). If 24VAC is not present, confirm 24VAC power
supply to CB K2 connector pin #9 (W/R) to a neutral (LBU). If 24VAC is present on
CB K2 connector pin #9 (W/R) and not on CB K2 connector pin #10 (W/BU), check
for 5VDC at CB K9 connector pin #1 (W/BK) to CB red K4 connector pin closest to
CB black K3 connector. If 5VDC is not present on CB K9 connector pin #1 (W/BK),
replace CB. If 5VDC is present on CB K9 connector pin #1 (W/BK), check for 5VDC
at CB K9 connector pin #2 (W/BK) to CB red K4 connector pin closest to CB black
K3 connector. If 5VDC is not present on pin #2 (W/BK), check continuity of control
switch. If open, place in "DRAIN" position or replace control switch.
If 24VAC is present at CB K2 connector pin #10 (W/BU), check for 24VAC at DV. If
24VAC is present and DV does not energize, check DV solenoid continuity.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
13) Shutdown–Bin fills and ice engages BC actuator paddle. 6 to 10-sec. shutdown
sequence begins. Diagnosis: Check that BC actuator paddle is activated and not
sticking. Check BC proximity switch continuity to confirm BC proximity switch is open.
If BC actuator is engaged and BC proximity switch is closed, replace BC proximity
switch. If BC proximity switch is open and Comp, FM, and GM do not de-energize,
replace CB. See "II.C. Control Board Check."
Legend: AM–agitating motor; BC–bin control; CB–control board; Comp–compressor;
CT–control transformer; DCT–drain cycle timer (1-hr.); DV–drain valve;
DVT–drain valve timer (2-sec.); FM–fan motor; FT–fill timer (90-sec. low water
safety); FZT–freeze timer; GM–gear motor; GMPR–gear motor protect relay;
HPS–high-pressure switch; IPT–ice purge timer; LFS–lower float switch;
TXV–thermostatic expansion valve; UFS–upper float switch;
WRV–water regulating valve; WV–inlet water valve
17
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Control Board Check
Before replacing a CB that does not show a visible defect and that you suspect is bad,
always conduct the following check procedure. This procedure will help you verify your
diagnosis. Before proceeding, check for proper voltage per appliance nameplate. Check
that the 24VAC 1A fuse and 115VAC 3A GM fuse are good.
• Check the S1 dip switch settings to assure that they are in the factory default position.
For factory default settings, see "III.C.1. Default Dip Switch Settings." S1 dip switch
7 determines bin control application. WARNING! Do not adjust S1 dip switch 7 out
of the factory default position.This dip switch must be left in the factory default
position or the appliance will not operate correctly.
• When checking for 115VAC high-voltage (primary), always choose a 115VAC neutral
(W) to establish a good neutral connection.
• When checking for 24VAC low-voltage (secondary), always choose a 24VAC neutral
(LBU) to establish a good neutral connection. If the appliance is in alarm, see "III.B.
LED Lights and Audible Alarm Safeties."
• When checking for 5VDC, use CB red K4 connector pin closest to CB black
K3 connector for DC ground (GND).
1) Startup-"POWER OK" LED on: Move control switch to "ICE" position, then move
power switch to "ON" position. "POWER OK" LED turns on. "POWER" LED remains
on unless power supply is interrupted. NOTICE! Appliance will not start unless the
safety switch is engaged. Diagnosis: Check that "POWER OK" LED is on. If not,
check for proper 115VAC supply voltage to CT (main breaker or fuse and power switch).
Next, check for proper 24VAC output from CT. Next, check that 1A fuse is good. Check
for 24VAC from CB K8 connector pin #1 (W/R) to CB K8 connector pin #2 (LBU).
If 24VAC is present and "POWER OK" LED is off, replace CB.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
2) 5VDC Output Checks: There are seven 5VDC circuits on the appliance, "DRAIN"
position through control switch, high-pressure switch (HPS), gear motor protect
relay (GMPR), bin control (BC), float switch (FS), ice dispense switch, and water
dispense switch.
• 5VDC CB K9 Connector: See Fig. 1.
5VDC CB K9 Connector
Component
Pin # (Wire Color)
"DRAIN" Position Through Control Switch #1 (W/BK) and #2 (W/BK)
High-Pressure Switch (HPS)
#3 (Y) and #4 (Y)
Gear Motor Protect Relay (GMPR)
(terminals #3 and #5)
#5 (W/O) and #6 (W/O)
Multimeter
5VDC
Red positive
test lead to
red K4 connector
pin closest
to black K3
connector
"DRAIN" Position on
Control Switch
(W/BK)
Black Negative
Test Lead
Red Positive
Test Lead
High-Pressure Switch (HPS)
(Y)
Gear Motor Protect Relay (GMPR)
Terminals #3 and #5 (W/O)
Control Board K9 Connector
Fig. 1
a. "DRAIN" Position on Control Switch
CB K9 connector pins #1 and #2 (W/BK):
• When control switch is in the "ICE" position, CB K9 connector pin #1 and pin #2 are
open. 5VDC is present between CB K9 connector pin #1 (W/BK) and pin
#2 (W/BK). If not, confirm 5VDC between pin #1 (W/BK) and CB red K4 connector,
pin closest to CB black K3 connector. If 5VDC is not present, replace CB.
• When control switch is in the "DRAIN" position, CB K9 connector pin #1 (W/BK)
and pin #2 (W/BK) are closed. 5VDC is present between both CB K9 connector
pin #1 (W/BK) and pin #2 (W/BK) to CB red K4 connector, pin closest to CB black
K3 connector. If 5VDC is not present, replace CB.
b. High-Pressure Switch (HPS)
CB K9 connector pins #3 (Y) and #4 (Y): When HPS is closed, 5VDC is present
between both CB K9 connector pins #3 (Y) and pin #4 (Y) to CB red K4 connector
pin closest to CB black K3 connector. If 5VDC is not present on pin #3 (Y) or pin
#4 (Y), replace CB. If 5VDC is present on CB K9 connector pin #3 (Y) and not on
CB K9 connector pin #4 (Y), HPS is most likely open. CB sounds a 3-beep alarm.
Check HPS continuity. If HPS is open and CB is not in alarm, replace CB.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
c. Gear Motor Protect Relay (GMPR)
CB K9 connector pins #5 (W/O) and #6 (W/O): When GMPR is de-energized,
GMPR terminals #3 and #5 are open and 5VDC is present between
CB K9 connector pin #5 (W/O) and CB red K4 connector pin closest to CB black
K3 connector. If 5VDC is not present, replace CB. When GMPR is energized, GMPR
terminals #3 and #5 are closed and 5VDC is present between CB K9 connector
pin #5 (W/O) and pin #6 (W/O) to CB red K4 connector pin closest to CB black
K3 connector. If GM is energized and GMPR terminals #3 & #5 are open, an 8-beep
alarm occurs. See "III.B. LED Lights and Audible Alarm Safeties."
• 5VDC CB K8 Connector: See Fig. 2.
5VDC CB K8 Connector
Component
Pin # (Wire Color)
Bin Control (BC)
#3 (GY) and #4 (GY)
Float Switch (FS) Common #5 (BK) Common
Upper Float Switch (UFS) #6 (R)
Lower Float Switch (LFS)
#7 (DBU)
d. Bin Control (BC)
CB K8 connector pins #3 (GY) and #4 (GY): When BC is closed (calling for ice),
5VDC is present between CB K8 connector pin #3 (GY) and pin #4 (GY) to CB red
K4 connector pin closest to CB black K3 connector. If 5VDC is not present on either
pin, replace CB. If 5VDC is present on pin #3 (GY) and not on pin #4 (GY), BC is
open. See "II.D. Bin Control Check."
e. Float Switch (FS): CB K8 connector pins #5 common (BK), #6 UFS (R), and
#7 LFS (DBU): 5VDC is present between CB K8 connector pin #5 common (BK)
and CB red K4 connector pin closest to CB black K3 connector at all times. If 5VDC
is not present, replace CB. For further float switch diagnostics, see "II.E. Float Switch
Check and Cleaning."
Multimeter
Red positive
test lead to red
K4 connector
pin closest
5VDC
to black K3
connector
Red Positive
Test Lead
Black Negative
Test Lead
Control Board K8 Connector
Bin Control (GY)
Lower Float Switch (LFS) (DBU)
Float Switch (FS) Common (BK)
Upper Float Switch (UFS) (R)
Fig. 2
20
Download from Www.Somanuals.com. All Manuals Search And Download.
• 5VDC CB K7 Connector: See Figs. 3, 4, 5, and 6.
• Water Dispense Switch/Water Dispense Sensor
f. Push Button Model–"WTRDP" LED is on: Before engaging the water dispense
switch, check for the correct VDC from the locations given in the "Disengaged"
column in the table below. If the VDC is different than in the table, replace CB. If
the VDC is correct, engage the water dispense switch. "WTRDP" LED turns on. If
not, confirm that the water dispense signal VDC matches the "Engaged" column in
the table below. If not, check the water dispense switch continuity when engaged
(closed). If the water dispense switch is open when engaged, replace the water
dispense switch. If the VDC matches the "Engaged" column below and the "WTRDP"
LED does not turn on, replace CB.
5VDC CB K7 Connector
Component
Pin # (Wire Color) To CB VDC Ground
Disengaged Engaged
5VDC Power Supply
Water Dispense Signal #8 (DBU)
#3 (BR)
5VDC
0VDC
5VDC
5VDC
Red K4 pin closest
to black K3
To
Multimeter
5VDC
Red Positive
Test Lead
Red positive
test lead to red
K4 connector
pin closest
Black Negative
Test Lead
to black K3
Control Board K7 Connector
connector
Water Dispense (BR)
(5VDC power supply)
Water Dispense (DBU)
(switch signal)
Fig. 3
21
Download from Www.Somanuals.com. All Manuals Search And Download.
g. Opti-Serve Model–"WTRDP" LED is on: Before engaging the water dispense
Opti-Serve sensor, check for the correct VDC from the locations given in the
"Disengaged" column in the table below. If the VDC is different than in the table,
replace CB. If the VDC is correct, engage the Opti-Serve sensor. "WTRDP" LED
turns on. If not, confirm that the water dispense signal VDC matches the "Engaged"
column in the table below. If not, replace the Opti-Serve sensor. If the VDC matches
the "Engaged" column below and the "WTRDP" LED does not turn on, replace CB.
5VDC CB K7 Connector
Component
Pin # (Wire Color) To CB VDC Ground
Disengaged Engaged
VDC Sensor Ground
Water Dispense Signal #8 (W)
5VDC Power Supply
#7 (R)
0VDC
0VDC
5VDC
0VDC
5VDC
5VDC
Red K4 pin closest
to black K3
To
#9 (BK)
Multimeter
5VDC
Red Positive
Test Lead
Red positive
test lead to red
K4 connector
pin closest
Black Negative
Test Lead
Control Board K7 Connector
to black K3
connector
Water Dispense (BK)
(5VDC power)
Water Dispense (W)
(switch signal)
Water Dispense (R)
(VDC GND)
Fig. 4
22
Download from Www.Somanuals.com. All Manuals Search And Download.
• Ice Dispense Switch/Ice Dispense Sensor:
h. Push Button Model–"ICE" and "AM" LEDs are on: Before engaging the
ice dispense switch, check for the correct VDC from the locations given in the
"Disengaged" column in the table below. If the VDC is different than in the table,
replace CB. If the VDC is correct, engage the ice dispense switch. "ICE" LED
turns on. If not, confirm position of dispense mode switch and that the portion and
continuous VDC matches the "Engaged" column in the table below. If not, check the
ice dispense switch continuity when engaged (closed) and the dispense mode switch
continuity. If dispense switch is open when engaged, replace. If dispense mode
switch is open, replace. If the VDC matches the "Engaged" column below and the
"ICE" LED does not turn on, replace CB.
Note: "AM" LED turns on .6 sec. for every 12 sec. of cumulative dispense time.
5VDC CB K7 Connector
Component
Pin # (Wire Color) To CB VDC Ground Disengaged Engaged
Portion Signal
5VDC Power Supply
Continuous Signal
#5 (R)
#3 (BR)
#2 (Y)
0VDC
5VDC
0VDC
5VDC
5VDC
5VDC
Red K4 pin closest
to black K3
To
Multimeter
5VDC
Red positive
test lead to red
K4 connector
pin closest
Red Positive
Test Lead
to black K3
connector
Black Negative
Test Lead
Control Board K7 Connector
Ice Dispense (Y)
(continuous signal)
Ice Dispense (R)
(portion signal)
Ice Dispense (BR)
(5VDC power supply)
Fig. 5
23
Download from Www.Somanuals.com. All Manuals Search And Download.
i. Opti-Serve Model–"ICE" and "AM" LEDs are on: Before engaging the ice dispense
Opti-Serve sensor, check for the correct VDC from the locations given in the
"Disengaged" column in the table below. If the VDC is different than in the table,
replace CB. If the VDC reading is correct, engage the Opti-Serve sensor. "ICE" LED
turns on. If not, confirm position of dispense mode switch and that the portion and
continuous VDC matches the "Engaged" column in the table below. If not, check the
dispense mode switch continuity. If open, replace. If dispense mode switch is closed
(portion or continuous), replace the Opti-Serve sensor. If the VDC matches the
"Engaged" column below and the "ICE" LED does not turn on, replace CB.
Note: "AM" LED turns on .6 sec. for every 12 sec. of cumulative dispense time.
5VDC CB K7 Connector
Component
Pin # (Wire Color) To CB VDC Ground Disengaged Engaged
5VDC
0VDC
0VDC
0VDC
5VDC
0VDC
5VDC
5VDC
5VDC Power Supply
VDC Sensor Ground
Continuous Signal
Portion Signal
#3 (W/BK)
#1 (W/R)
#2 (W)
To
Red K4 pin closest
to black K3
#5 (W/O)
Multimeter
5VDC
Red Positive
Test Lead
Red positive
test lead to red
K4 connector
pin closest
to black K3
connector
Black Negative
Test Lead
Control Board K7 Connector
Ice Dispense (W/R)
(VDC ground)
Ice Dispense (W)
Ice Dispense (W/O)
(portion signal)
(continuous signal)
Ice Dispense (W/BK)
(5VDC power supply)
Fig. 6
24
Download from Www.Somanuals.com. All Manuals Search And Download.
3) Fill Cycle–"WTRIN" LED is on: "WTRIN" LED turns on only when the reservoir water
level is low enough to open LFS. Diagnosis: Confirm LFS is open. If "WTRIN" LED
is off and LFS is open and the control switch is in the "ICE" position (open), replace
CB. If "WTRIN" LED is on and water is not filling the reservoir, check for 24VAC at
CB K2 connector between pin #8 (W/BR) and a neutral (LBU). If the "WTRIN" LED is
on and 24VAC is not present between CB K2 connector pin # 8 (W/BR) and neutral
(LBU), confirm 24VAC at CB K2 connector between pin #7 (W/R) and a neutral (LBU).
If 24VAC is present between CB K2 connector pin #7 (W/R) and a neutral (LBU) and
not between CB K2 connector pin #8 (W/BR) and a neutral (LBU), replace CB.
24VAC CB K2 Connector
LFS
LFS
Connector
Pin # (Wire Color) To Neutral (LBU)
Open
Closed
K2 (CB input power)
K2 (WV power)
Pin #7 (W/R)
Pin #8 (W/BR)
24VAC
0VAC
24VAC
24VAC
K8 pin #2 (LBU)
To
4) Ice Purge Cycle–"GM" LED is on: "GM" LED turns on once UFS closes (reservoir
full). If UFS is closed and "GM" LED is off, replace CB. If "GM" LED is on but GM does
not start, check for 115VAC from CB K1 connector pin #3 (DBU) to a neutral (W).
If 115VAC is not present, confirm 115VAC from CB K1 connector pin #2 (BR) to a
neutral (W). If 115VAC is present on CB K1 connector pin #2 (BR) but not on CB
K1 connector pin #3 (DBU), replace CB.
5) Freeze Cycle–"GM" and "COMP" LED are on: 5-minute ice purge timer terminates
or press the "SERVICE" button on CB after the "GM" LED turns on to bypass ice purge
cycle. WARNING! Risk of electric shock. Care should be taken not to touch live
terminals. After 5-minute ice purge timer terminates, "COMP" LED turns on. If not,
replace CB. If "COMP" LED turns on and Comp does not start, check for 115VAC from
the CB X1 relay (BR) and (R) to a neutral (W). If 115VAC is present on CB X1 relay (BR)
and not on CB X1 relay (R), replace CB.
Legend: AM–agitating motor; BC–bin control; CB–control board; Comp–compressor;
CT–control transformer; DCT–drain cycle timer (1-hr.); DV–drain valve;
DVT–drain valve timer (2-sec.); FM–fan motor; FT–fill timer (90-sec. low water
safety); GM–gear motor; GMPR–gear motor protect relay; IPT–ice purge timer;
LFS–lower float switch; UFS–upper float switch; WV–inlet water valve
25
Download from Www.Somanuals.com. All Manuals Search And Download.
D. Bin Control Check
When the actuator paddle is not engaged, BC is closed and the appliance produces ice.
S1 dip switch 7 must be in the "OFF" position. When ice fills the chute and engages
the actuator paddle, BC opens and CB shuts down the appliance within 10 seconds.
NOTICE! Do not place S1 dip switch 7 in the "ON" position. For details, see "III.C.1.
Default Dip Switch Settings."
1) Remove the front and top panels.
2) Remove the storage bin cover. If necessary, dispense ice or remove ice manually so
that the BC actuator paddle is not engaged.
IMPORTANT! Appliance will not start unless the safety switch is engaged.
WARNING! Keep hands, hair, and loose clothing clear of the agitator rotating
inside of the storage bin.
3) Move the control switch to the "OFF" position.
4) Move the power switch to the "OFF" position.
5) Turn off the power supply.
6) Disconnect BC connector from the back of the control box.
7) Check for continuity across BC proximity switch. If BC actuator is not engaged and BC
proximity switch is open, replace BC proximity switch.
8) Press and hold BC actuator paddle. While BC actuator is engaged, check for continuity
across BC proximity switch. If BC actuator is engaged and BC proximity switch is open,
replace BC proximity switch.
9) Disengage BC actuator paddle.
10) Reconnect BC connector. Remove the control box cover.
11) Turn on the power supply. Move the power switch to the "ON" position.
12) Move the control switch to the "ICE" position.
13) Engage the safety switch to start the automatic icemaking process.
14) Make sure the "GM" LED is on. There is a delay of at least 5 seconds before the "GM"
LED turns on after power-up. After the "GM" LED turns on, press the "SERVICE" button
on CB to bypass the 5-minute compressor delay. WARNING! Risk of electric shock.
Care should be taken not to touch live terminals. The "COMP" LED turns on.
15) When Comp starts, press and hold BC actuator paddle.
16) Comp and GM should de-energize within 10 seconds. Diagnosis: If not, and BC is
found open and the appliance continues to run, replace CB.
17) Move the power switch to the "OFF" position and turn off the power supply.
18) Move the power switch to the "ON" position.
19) Replace the storage bin cover, control box cover, top panel, and front panel in their
correct positions.
20) Turn on the power supply to start the automatic icemaking process.
Legend: BC–bin control; CB–control board; Comp–compressor;GM–gear motor
26
Download from Www.Somanuals.com. All Manuals Search And Download.
E. Float Switch Check and Cleaning
1. Float Switch Check
1) Remove the front panel and move the control switch to the "DRAIN" position.
2) Press and hold the safety switch to start draining the appliance.
IMPORTANT! Appliance will not start unless the safety switch is engaged.
3) Allow the water to drain from the reservoir, then release the safety switch. Move the
control switch to the "ICE" position.
4) Remove the FS molex plug from the control box and check continuity across FS wires.
Black (BK) to red (R) for the upper float and black (BK) to dark blue (DBU) for the lower
float. See Fig. 7. With the water reservoir empty, the float switches are open. If open,
continue to step 5. If closed, follow the steps in "II.E.2. Float Switch Cleaning." After
cleaning the float switches, check them again. Replace if necessary.
5) Replace the FS molex plug on the control box.
6) Press and hold the safety switch to start filling the reservoir.
7) Once the reservoir is full and GM starts, release the safety switch.
8) Remove the FS molex plug from the control box and check continuity across FS wires.
Black (BK) to red (R) for the upper float and black (BK) to dark blue (DBU) for the lower
float. They should be closed. If open, follow the steps in "II.E.2. Float Switch Cleaning."
After cleaning the float switches, check them again. Replace if necessary.
2. Float Switch Cleaning
Depending on water conditions, scale may build up on FS. Scale on the switch can cause
the floats to stick. In this case, FS should be cleaned and checked.
1) Remove the front panel and move the control switch to the "DRAIN" position.
2) Press and hold the safety switch to start draining the appliance.
3) Allow the water to drain from the reservoir, then release the safety switch.
4) Turn off the power supply.
5) Remove FS assembly from the reservoir cover. See Fig. 8.
6) Wipe down FS assembly with a mixture of 1 part Hoshizaki Scale Away and 25 parts
warm water. Rinse the FS assembly thoroughly with clean water.
7) While not necessary, the floats can be removed from the shaft during cleaning. If you
remove them, note that the blue float is on top. The floats must be installed with the
magnets inside them towards the top of the switch. See Fig. 8. Installing the floats
upside down will affect the timing of FS operation.
8) Rinse FS assembly thoroughly with clean water and replace in its original position.
9) Replace the front panel in its correct position.
10) Move the control switch to the "ICE" position.
11) Turn on the power supply to start the automatic icemaking process.
Legend: Comp–compressor; FS–float switch; GM–gear motor
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Red (R)
(upper float switch)
Black (BK)
(common)
Dark Blue (DBU)
(lower float switch)
Magnet (towards top)
Upper Float (blue)
Spring Retainer Clip
Plastic Retainer Clip
Magnet (towards top)
Lower Float (white)
Fig. 7
Float Switch Assembly
Reservoir Cover
Reservoir
Fig. 8
28
Download from Www.Somanuals.com. All Manuals Search And Download.
F. Diagnostic Tables
Before consulting the diagnostic tables, check for correct installation, proper voltage per
appliance nameplate, and adequate water pressure (10 to 113 PSIG). Check control
board using the steps in "II.C. Control Board Check."
1. No Ice Production
No Ice Production - Possible Cause
Startup
1. Power Supply
a) Off, blown fuse, or tripped breaker.
b) Loose connection.
c) Not within specifications.
a) "OFF" position.
2. Power Switch
b) Defective.
3. Safety Switch
a) Safety switch not engaged.
b) Defective.
4. Power Protect Relay
a) Energized. Voltage not within specifications.
b) Defective.
5. Control Transformer
a) Coil winding open or shorted.
a) Blown.
6. 1A 24VAC Fuse (Control Box)
7. Control Board
See "II.C. Control Board Check"
a) In alarm. See "III.B. LED Lights and Audible Alarm Safeties."
b) Defective.
8. Control Switch
a) In "DRAIN" position.
b) Bad contacts.
9. Bin Control
a) Tripped with bin filled with ice.
b) Proximity switch defective.
c) Actuator paddle does not move freely.
10. High-Pressure Switch
a) Control board in 3 or 4-beep alarm. See "III.B. LED Lights and
Audible Alarm Safeties."
Fill Cycle
1. Control Board
2. Inlet Water Valve
3. Water Supply
4. Float Switch
5. Drain Valve
a) No power to inlet water valve.
b) No power to float switch or not reading float switch condition.
a) Screen or orifice clogged.
b) Coil winding.
a) Water supply off or improper water pressure.
b) External water filters clogged.
a) Float does not move freely.
b) Defective.
a) Sticking.
Ice Purge Cycle
1. Control Board
2. Gear Motor
a) No power to gear motor.
b) No power to gear motor protect relay circuit (5VDC).
a) 3A fuse blown.
b) Internal protector open.
c) Motor winding.
d) Mechanical failure.
3. Coupling
a) Defective.
4. Gear Motor Protect Relay
a) Defective.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
No Ice Production - Possible Cause
Freeze Cycle
a) Defective.
a) Defective.
1. Control Board
2. Start Relay
3. Start Capacitor or Run Capacitor a) Defective.
4. Compressor a) External protector.
b) Motor winding.
c) Mechanical failure.
5. High-Pressure Switch Activates a) Dirty condenser.
b) Ambient temperature too warm.
c) Fan motor not operating.
d) Refrigerant overcharged.
e) Defective.
f) Refrigerant lines or components restricted.
a) Capacitor defective.
b) Motor winding.
6. Fan Motor
7. Evaporator
c) Bearing worn out or locked rotor.
a) Dirty.
b) Damaged or defective.
a) Bulb loose.
8. Thermostatic Expansion Valve
(TXV)
b) Operating erratically.
a) Low.
9. Refrigerant Charge
10. Drain Valve
a) Dirty, leaking by.
b) Defective coil.
c) Defective control board.
a) Water leaks.
11. Water System
Refill
1. Water Supply
2. Control Board
a) Off.
a) No power to float switch or not reading float switch condition.
b) No power to inlet water valve.
a) Float does not move freely.
b) Defective.
3. Float Switch
4. Inlet Water Valve
1. Bin Control
a) Clogged or defective.
Shutdown
a) Actuator paddle sticking open.
b) Proximity switch defective.
a) Defective.
2. Control Board
30
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Ice/Water Dispensing
Ice Dispense-Push Button
1. Power Supply
2. Control Board
a) Off, blown fuse, or tripped breaker.
a) Ice dispense switch circuit open or no power (5VDC) from control
board.
b) No power (115VAC) to ice dispense solenoid, ice dispense motor, or
agitating motor.
3. Ice Dispense Switch
4. Dispense Mode Switch
5. Ice Dispense Motor
a) Defective.
a) Defective.
a) Motor windings.
b) Mechanical failure.
6. Ice Dispense Solenoid
7. Shutter Assembly
8. Agitating Motor
a) Defective or loose connection.
a) Defective.
a) Motor windings.
b) Mechanical failure.
Ice Dispense-Opti-Serve
a) Off, blown fuse, or tripped breaker.
a) No power to dispense mode switch.
b) Dispense mode switch circuit open.
1. Power Supply
2. Control Board
c) No power to ice dispense solenoid, ice dispense motor, or agitating
motor.
3. Infrared Sensor
a) Defective.
4. Dispense Mode Switch
5. Ice Dispense Motor
a) Defective (open).
a) Motor windings.
b) Mechanical failure.
a) Defective or loose connection.
a) Defective.
6. Ice Dispense Solenoid
7. Shutter Assembly
8. Agitating Motor
a) Motor windings.
b) Mechanical failure.
Water Dispense-Push Button
a) Off, blown fuse, or tripped breaker.
a) Defective.
1. Power Supply
2. Water Dispense Switch
3. Water Dispense Valve
a) Water supply turned off.
b) Defective.
Water Dispense-Opti-Serve
a) Off, blown fuse, or tripped breaker.
a) Defective.
1. Power Supply
2. Infrared Sensor
3. Control Board
a) No power to infrared sensor.
b) No power to water dispense valve.
a) Water supply turned off.
b) Defective.
4. Water Dispense Valve
31
Download from Www.Somanuals.com. All Manuals Search And Download.
III. Controls and Adjustments
• A Hoshizaki exclusive control board is employed in the DCM-751 series.
• All models are pretested and factory set.
• For a control board check procedure, see "II.C. Control Board Check."
NOTICE
• Fragile, handle very carefully.
• The control board contains integrated circuits, which are susceptible to failure
due to static discharge. It is especially important to touch the metal part of the
appliance when handling or replacing the control board.
• Do not touch the electronic devices on the control board or the back of the control
board.
• Do not change wiring and connections. Do not misconnect terminals.
• Do not short out power supply to test for voltage.
• Always replace the whole control board assembly if it goes bad.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
A. Control Board Layout
1. DCM-751B_H
High-Pressure Switch
#3 to #4 (Y)
Gear Motor Protect Relay Circuit
#5 to #6 (W/O)
Relay De-Energized-Open-5VDC
Relay Energized-Closed-0VDC
Open-5VDC
Closed-0VDC
Control Switch
#1 to #2 (W/BK)
"ICE"-Open-5VDC
"DRAIN"-Closed-0VDC
• K9 Connector
• "SERVICE" Button
(Ice Purge Cycle Bypass)
5VDC
• K8 Connector
Transformer 24VAC Input
#1 (W/R)
• K1 Connector
#3 GM (DBU)
#2 GM Voltage
Input (BR)
Transformer 24VAC Neutral
#2 (LBU)
Mechanical Bin Control
#3 to #4 (GY)
• K2 Connector
Drain Valve
#10 (W/BU)
Float Switch Output
#5 (BK)(+)
Transformer Input
#9 (W/R)
Inlet Water Valve
#8 (W/BR)
Upper Float Switch
#6 (R)
Transformer Input
#7 (W/R)
Lower Float Switch
#7 (DBU)
Dispense Water
Valve #6 (W/O)
24VAC Input
#5 (W/R)
• K7 Connector
Continuous Ice Dispense
Signal #2 (Y)
Water/Ice Dispense
Output #3 (BR)(+)
Agitating Motor
#4 (O)
115VAC Input
#3 (BK)
Portion Ice Dispense
Signal #5 (R)
Dispense Motor
#2 (P)
115VAC Input
#3 (BK)
Water Dispense Signal
#8 (DBU)
• "POWER OK" LED
LED Legend:
• S1 Dip Switch
AM-agitating motor
COMP-compressor
FLUSH-drain valve
GM-gear motor
ICE-dispense motor
WTRDP-water dispense valve
WTRIN-inlet water valve
5VDC Ground (GND) Terminals
• K6 Connector
Open
Fig. 9a
33
Download from Www.Somanuals.com. All Manuals Search And Download.
2. DCM-751B_H-OS
High-Pressure Switch
#3 to #4 (Y)
Open-5VDC
Closed-0VDC
Control Switch
Gear Motor Protect Relay Circuit
#5 to #6 (W/O)
Relay De-Energized-Open-5VDC
Relay Energized-Closed-0VDC
#1 to #2 (W/BK)
"ICE"-Open-5VDC
"DRAIN"-Closed-0VDC
• K9 Connector
• "SERVICE" Button
(Ice Purge Cycle Bypass)
5VDC
• K8 Connector
• K1 Connector
#3 GM (DBU)
#2 GM Voltage
Input (BR)
Transformer
24VAC Input
#1 (W/R)
Transformer
24VAC Neutral
#2 (LBU)
• K2 Connector
Drain Valve
#10 (W/BU)
Mechanical Bin Control
#3 to #4 (GY)
Transformer Input
#9 (W/R)
Float Switch Output
#5 (BK)(+)
Inlet Water Valve
#8 (W/BR)
Upper Float Switch #6 (R)
Lower Float Switch #7 (DBU)
Transformer Input
#7 (W/R)
Dispense Water
Valve #6 (W/O)
• K7 Connector
Ice OS Sensor GND
#1 (W/R)
24VAC Input
#5 (W/R)
Continuous Ice Dispense
Signal #2 (W)
Agitating Motor
#4 (O)
115VAC Input
#3 (BK)
Ice OS Sensor Output
#3 (W/BK)(+)
Portion Ice Dispense
Signal #5 (W/O)
Dispense Motor
#2 (P)
115VAC Input
#3 (BK)
• "POWER OK" LED
• S1 Dip Switch
Water OS Sensor GND
#7 (R)
Water Dispense Signal
#8 (W)
Water OS Sensor
Output #9 (BK)(+)
• K6 Connector
Open
LED Legend:
5VDC Ground (GND) Terminals
AM-agitating motor
COMP-compressor
FLUSH-drain valve
GM-gear motor
ICE-dispense motor
WTRDP-water dispense valve
WTRIN-inlet water valve
Fig. 9b
34
Download from Www.Somanuals.com. All Manuals Search And Download.
B. LED Lights and Audible Alarm Safeties
The "POWER" LED indicates proper control voltage and will remain on unless a control
voltage problem occurs. For further details, see "II. Sequence of Operation and Service
Diagnosis."
Icemaking Sequence
Energized
Sequence Step
LED
Components
Min.
Max.
Fill Cycle
WTRIN
WV
-
On until UFS closes. Alarm sounds
after 90 sec.
Ice Purge Cycle GM
GM, FM
5 min.
-
5 min.
Freeze Cycle
(with refill)
GM, WTRIN* (refill), GM, Comp,
COMP
*On until UFS closes. Alarm
sounds after 90 sec.
FM, WV*
(refill)
Drain Cycle
FLUSH (Drain)
DV
2 sec.
10 min.
Dispensing Sequence
Energized
Components
IDS**, IDM**, *AM energizes
**Dispense Mode Switch
Sequence Step
LED
Time LEDs are on
Continuous
Portion
Ice Dispense
Activation
ICE, AM*
60 sec. per
activation
Adjustable
between 0.2 sec.
and 20 sec.
AM*
.6 sec. every 12
sec. of cumulative
dispense time
Dispense Water WTRDP
Valve Activation
DispWV
The built-in alarm safeties shut down the appliance.
No. of Beeps
Type of Alarm
(every 5 sec.)
Reset Options
Automatic reset once water supply is restored
1
2
3
Low Water Safety
UFS open > 90 seconds after WV energized. and UFS closes.
Control Switch
In "DRAIN" position longer than 15 minutes. moved to the "ICE" position.
High-Pressure Switch
Automatic reset once the control switch is
Automatic reset once pressure drops
below the high pressure threshold and the
high-pressure switch closes.
First and second activation in 1 hour.
4
High-Pressure Switch
Third activation in 1 hour.
Call for service. To avoid possible catastrophic
failure, it is recommended to leave the
appliance off until this alarm is resolved.
Manual reset. Turn power off and on again.
5
6
7
8
9
Freeze Timer
WV off > 30 minutes since last WV activation.
Low Voltage
(92Vac 5% or less)
High Voltage
(147Vac 5% or more)
Gear Motor
GMPR contacts fail to close.
Manual reset. Turn power off and on again.
"POWER OK" LED turns off if voltage
protection operates.
The control voltage safeties automatically
reset when voltage is corrected.
Manual reset. Turn power off and on again.
Infrared Sensor (S1 dip switch 7)
(Not used on this model)
Manual reset. Turn power off and on again.
Legend: AM–agitating motors, Comp–compressor; DispWV–dispense water valve;
DV–drain valve; EH–evaporator heater; FM–fan motor; GM–gear motor;
GMPR–gear motor protect relay; IDM–ice dispensing motor; IDS–ice dispensing
shutter solenoid; UFS–upper float switch; WV–inlet water valve
35
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Settings and Adjustments
NOTICE
Dip switches are factory set. Failure to maintain factory settings may adversely
affect performance and warranty coverage. For more information, contact Hoshizaki
Technical Support at 1-800-233-1940.
1. Default Dip Switch Settings
The S1 dip switch settings are factory-set to the following positions:
Dip Switch No.
1
2
3
4
5
6
7
8
9
10
DCM-751B_H
OFF OFF OFF OFF ON ON OFF ON OFF OFF
DCM-751B_H(-OS) OFF OFF OFF OFF OFF ON OFF ON OFF OFF
Normally off (factory use)
Mechanical Bin Control Shutdown Delay
Bin Control Selector
Continuous Dispensing Timer
(DCM models only, do not adjust on modular appliances)
Drain Frequency Control
Infrared Sensor Shutdown Delay
2. Infrared Sensor Shutdown Delay (S1 dip switch 1, 2, 3)
NOTICE
Do not adjust. Setting not used on this model. When dip switch 7 is off, 1, 2, and 3
are ignored.
Factory set. DCM-751B_H(-OS) does not use an infrared sensor bin control. The
appliance uses a mechanical bin control for ice level control.
3. Drain Frequency Control (S1 dip switch 4)
The appliance is factory set for optimum performance with the 1-in-1 drain cycle (S1 dip
switch 4 in the "OFF" position). This setting allows for removal of sediment from the
evaporator without interrupting the icemaking process. 1-in-12 drain cycle is available.
S1 Dip Switch Setting
Drain Timer Interval Drain Valve Open
No. 4
OFF (1-in-1)
ON (1-in-12)
1 Hour
2 Seconds
10 Minutes
11 Hours 45 Minutes
36
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Continuous Dispensing Timer (S1 dip switch 5 & 6)
The dispense mode switch must be in the "CONTINUOUS" position for this setting to
apply. The factory setting allows ice to be dispensed continuously on push button models
and for a maximum of 60 sec. on Opti-Serve models.
S1 Dip Switch Setting
Dispense Time
No. 5
OFF
ON
No. 6
OFF
OFF
ON
No Limit
20 Seconds
60 Seconds
No Limit
OFF
ON
ON
5. Bin Control Selector (S1 dip switch 7)
The appliance is factory set for mechanical bin control operation. No adjustment is
required. In the factory default position (S1 dip switch 7 in the off position), the gear
motor delay after the upper float switch closes is 5 seconds. WARNING! Do not adjust
S1 dip switch 7 out of the factory default position.This dip switch must be left in
the factory default position or the appliance will not operate correctly.
S1 Dip Switch
Setting
No. 7
OFF
Bin Control Application
Mechanical Bin Control
Gear Motor Delay
5 seconds
Infrared Sensor with
Mechanical Bin Control Backup
ON
30 seconds
6. Bin Control Shutdown Delay (S1 dip switch 8)
Factory set for normal operation. No adjustment is required. The shutdown delay is the
time between the mechanical bin control proximity switch opening and the control board
shutting off the appliance.
S1 Dip Switch
Bin Control #1
Setting
Shutdown Delay
No. 8
OFF
ON
0.25 Seconds
6.7 Seconds
7. Factory Use (S1 Dip Switch 9 & 10)
Factory set for optimum performance. Do not adjust.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
D. Power Switch, Control Switch, and Dispense Mode Switch
The power switch, control switch, and dispense mode switch are used to control the
operation of the appliance.
1. Power Switch
WARNING! The power switch does not turn off all power
supply to the unit. 115VAC power supply is present on
control board K1 connector pin #2 (BR) and control board
X1 relay (BR) when the power switch is in the "OFF"
Fig. 10
position.
2. Control Switch
The control switch has 3 positions, "ICE," "OFF," and "DRAIN." See Fig. 11.
a) ICE
When the control switch is in the "ICE" position, 24VAC is
directed to control board K8 connector pin #1. 24VAC is present
between control board K8 connector pins #1 (power) and
pin #2 (neutral).
CONTROL
ICE
OFF
b) OFF
DRAIN
When the control switch is in the "OFF" position, 24VAC is
broken to control board K8 connector pin #1.
Fig. 11
c) DRAIN
When the control switch is in the "DRAIN" position, 24VAC is
directed to control board K8 connector pin #1. 24VAC is present
between control board K8 connector pins #1 (power) and
pin #2 (neutral). Also, a 5VDC circuit is closed on control board
K9 connector pins #1 and #2. This energizes an internal relay
on the control board which allows 24VAC to the drain valve from
control board connector K2 pin #10.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Dispense Mode Switch
The dispense mode switch has 2 positions, "CONTINUOUS" and "PORTION." See
Fig. 12.
a) CONTINUOUS
When the dispense mode switch is in the "CONTINUOUS" position, ice dispenses as
follows:
Push Button: Ice dispenses continuously with button engaged.
OS: Ice dispenses for a maximum of 60 seconds per activation.
b) PORTION
When the dispense mode switch is in the "PORTION" position, ice dispenses for the
amount of time determined by the ice dispense time setting.
DISPENSE MODE
PORTION
Fig. 12
CONTINUOUS
The ice dispense time control is located on the control board. The dial indicates
dispense time in seconds and is adjustable between 0.6 and 20 seconds. When
shipped, the ice dispense time control is set to the minimum dispense time of 0.6 sec.
(approximately 0.72 oz.).
Ice Dispense
Time Control
Fig. 13
39
Download from Www.Somanuals.com. All Manuals Search And Download.
IV. Removal and Replacement of Components
WARNING
• The appliance should be diagnosed and repaired only by qualified service
personnel to reduce the risk of death, electric shock, serious injury, or fire.
• Move the control switch and the power switch to the "OFF" position and turn off
the power supply before servicing. Lockout/Tagout to prevent the power supply
from being turned back on inadvertently.
• CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are
securely in place after the equipment is serviced. Make sure that none have fallen
into the storage bin.
• Make sure all food zones in the appliance and storage bin are clean after the
appliance is serviced.
• When replacing evaporator assembly and water circuit components, make sure
there are no water leaks after the repair is complete.
A. Service for Refrigerant Lines
WARNING
• Repairs requiring the refrigeration circuit to be opened must be performed by
properly trained and EPA-certified service personnel.
• Always recover the refrigerant and store it in an approved container. Do not
discharge the refrigerant into the atmosphere.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with
pressurized air for leak testing.
NOTICE
• Do not leave the system open for longer than 15 minutes when replacing or
servicing parts. The Polyol Ester (POE) oils used in R-404A appliances can
absorb moisture quickly. Therefore it is important to prevent moisture from
entering the system when replacing or servicing parts.
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made.
Install the new drier with the arrow on the drier in the direction of the refrigerant
flow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
40
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Refrigerant Recovery
The appliance is provided with refrigerant access valves. Using proper refrigerant
practices, recover the refrigerant from the access valves and store it in an approved
container. Do not discharge the refrigerant into the atmosphere.
2. Brazing
WARNING
• R-404A itself is not flammable at atmospheric pressure and temperatures up to
176°F (80°C).
• R-404A itself is not explosive or poisonous. However, when exposed to high
temperatures (open flames), R-404A can be decomposed to form hydrofluoric
acid and carbonyl fluoride both of which are hazardous.
• Do not use silver alloy or copper alloy containing arsenic.
1) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
NOTICE
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made.
Install the new drier with the arrow on the drier in the direction of the refrigerant
flow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). WARNING! Do not use R-404A as a mixture
with pressurized air for leak testing.
3. Evacuation and Recharge (R-404A)
1) Attach a vacuum pump to the system. Be sure to connect charging hoses to both high
and low-side access valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current
refrigerants. However, the rubber hose and gauge manifold to be used for
evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump. Open the gauge manifold valves. Never allow the oil in the
vacuum pump to flow backwards.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends
on pump capacity.
4) Close the low-side valve and high-side valve on the gauge manifold.
41
Download from Www.Somanuals.com. All Manuals Search And Download.
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a
refrigerant service cylinder. Remember to loosen the connection and purge the air from
the hose. See the nameplate inside the appliance for the required refrigerant charge.
Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets
ARI Standard 700 (latest edition) be used.
6) A liquid charge is required for charging an R-404A system (to prevent fractionation).
Place the service cylinder on the scales: if the service cylinder is not equipped with
a dip tube, invert the service cylinder, then place it on the scales. Open the high-side
valve on the gauge manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) If necessary, add any remaining charge to the system through the low-side.
NOTICE! To prevent compressor damage, use a throttling valve or liquid
dispensing device to add the remaining liquid charge through the low-side
service valve with the appliance running.
9) Close the high and low-side gauge manifold valves, then disconnect the gauge manifold
hoses.
10) Cap the access valves to prevent a possible leak.
B. Important Notes for Component Replacement
NOTICE
When replacing a component listed below, see the notes to help ensure proper
operation. See Fig. 14.
Component
Notes
• Install a new drier, start capacitor, run capacitor, and start relay.
• Install a new drier.
Compressor
Thermostatic
Expansion Valve
• Attach the thermostatic expansion valve bulb to the suction line in the same location as
the previous bulb.
• The bulb should be between the 10 and 2 o'clock positions on the tube.
• Secure the bulb with the clamp and holder, then insulate it.
• Install a new fan motor capacitor.
Fan Motor
Evaporator Assembly Components. See Fig. 14.
Upper and
Lower Bearings
• Inspect the upper bearing for wear. See "IV.C.1. Upper Bearing Wear Check." Replace if
necessary.
• When replacing the upper bearing it is advised to also change the lower bearing at the
same time.
Evaporator
• Install a new drier.
• Inspect the mechanical seal and O-ring prior to installing the new evaporator. If worn,
cracked, or scratched, the mechanical seal should also be replaced.
Gear Motor
• Install a new gear motor capacitor.
Extruding Head • Extruding head allen head cap screws (with seals) are not reusable. New allen head cap
screws (with seals) must be used.
Bolts
42
Download from Www.Somanuals.com. All Manuals Search And Download.
Evaporator Assembly
Evaporator Assembly
Spout B
Spout A
Power Switch
Cutter
Extruding Head and
Upper Bearing
Auger
4A1038-014
CONTROL
ICE
OFF
DISPENSE MODE
PORTION
Safety Switch
Evaporator Heater
Washer
DRAIN
CONTINUOUS
Allen Head Cap Screw (with seal)
Not reusable
Evaporator
Allen Head Cap Screw with Washer
Mechanical Seal
"O" Ring
Housing and Lower Bearing
Hex Head Bolt with Washer
Spline Coupling
Gear Motor
Fig. 14
43
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Icemaking Unit
1. Upper Bearing Wear Check
To ensure that the bearing inside the extruding head does not exceed the wear tolerance
of .02", follow the instructions below. See Fig. 15.
1) Move the control switch to the "OFF" position, then turn off the power supply. Remove
the front and top panels, then move the power switch to the "OFF" position.
2) Remove the storage bin cover. Remove spout B, then remove spout A and the cutter.
See Fig. 14.
.02" Round Stock
or Pin Gauge
3) Grasp the top of the auger and move the
auger towards you, then try to insert a
.02" round stock or pin gauge in between
the back side of the auger shaft and the
bearing surface. Check several locations
around the auger shaft. If the gauge goes
between the shaft and the bearing at
any point or if the bearing is scratched
or cracked, both the top bearing in the
extruding head and the lower bearing in the
housing should be replaced. Instructions
for removing the extruding head and
Auger
Extruding
Head
Fig. 15
housing are located later in this procedure.
Note: Replacing the bearing requires a bearing press adaptor. If one is not available,
replace the whole extruding head and housing.
4) Replace the cutter, spout A, spout B, and the storage bin cover in their correct positions.
5) Move the power switch to the "ON" position, then replace the panels in their correct
positions.
6) Turn on the power supply, then move the control switch to the "ICE" position to start the
automatic icemaking process.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Removal and Replacement of Extruding Head
1) Move the control switch to the "DRAIN" position and drain all of the water from the
evaporator.
2) After the water has stopped draining, move the control switch to the "OFF" position, then
turn off the power supply. Remove the front and top panels, then move the power switch
to the "OFF" position.
3) Remove the storage bin cover. Remove spout B, then remove spout A and the cutter.
See Fig. 14.
4) Remove the apron panel, then remove the left side panel.
5) Remove the allen head cap screws (with seals) securing the extruding head and
discard. NOTICE! The allen head cap screws (with seals) are not reusable. New
allen head cap screws (with seals) must be used.
6) Lift off the extruding head.
7) Place the new extruding head in place and tighten down with new allen head cap
screws.
8) Replace the cutter in its correct position.
9) Replace spout A, spout B, and the storage bin cover in their correct positions.
10) Move the power switch to the "ON" position, then replace the panels in their correct
positions.
11) Turn on the power supply, then move the control switch to the "ICE" position to start the
automatic icemaking process.
3. Removal and Replacement of Auger
1) Move the control switch to the "DRAIN" position and drain all of the water from the
evaporator.
2) After the water has stopped draining, move the control switch to the "OFF" position, then
turn off the power supply. Remove the front and top panels, then move the power switch
to the "OFF" position.
3) Remove the storage bin cover. Remove spout B, then remove spout A. See Fig. 14.
4) Remove the apron panel, then remove the left side panel.
5) Remove the allen head cap screws (with seals) securing the extruding head and
discard. Using the cutter, lift out the auger assembly.
6) Remove the cutter, extruding head, and upper part of the mechanical seal from the
auger and place them on the new auger. NOTICE! To help prevent water leaks, be
careful not to damage the surfaces of the O-ring or mechanical seal.
7) Install the new auger assembly with the upper part of the mechanical seal attached.
Secure the auger assembly using new allen head cap screws.
8) Replace spout A, spout B, and the storage bin cover in their correct positions.
9) Move the power switch to the "ON" position, then replace the panels in their correct
positions.
10) Turn on the power supply, then move the control switch to the "ICE" position to start the
automatic icemaking process.
45
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Removal and Replacement of Evaporator
NOTICE
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made.
Install the new drier with the arrow on the drier in the direction of the refrigerant
flow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
1) Move the control switch to the "DRAIN" position and drain all of the water from the
evaporator.
2) After the water has stopped draining, move the control switch to the "OFF" position, then
turn off the power supply. Remove the front and top panels, then move the power switch
to the "OFF" position.
3) Remove the apron panel, then remove the left side panel.
4) Recover the refrigerant and store it in an approved container.
5) Remove the storage bin cover. Remove spout B, then remove spout A. See Fig. 14.
6) Remove the extruding head heater and the allen head cap screws securing the
extruding head and discard the allen head cap screws. Using the cutter, lift out the
auger assembly.
7) Remove the evaporator bracket and disconnect the water hoses.
8) Disconnect the inlet and outlet tubing.
9) Remove the allen head cap screws securing the evaporator to the lower housing.
10) Lift off the evaporator.
11) Inspect the mechanical seal and O-ring prior to installing the new evaporator. The
mechanical seal consists of two parts. One moves along with the auger, and the other
is fixed on the lower housing. NOTICE! If the contact surfaces of these two parts
are worn, cracked, or scratched, the mechanical seal may cause water leaks and
should be replaced. Instructions for removing the mechanical seal and lower housing
are located later in this procedure.
12) Make sure the lower mechanical seal is in place, then place the new evaporator in
position. Secure the evaporator to the lower housing using the allen head cap screws.
13) Remove the drier, then place the new drier in position.
14) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
15) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with
pressurized air for leak testing.
46
Download from Www.Somanuals.com. All Manuals Search And Download.
16) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge.
17) Install the new auger assembly with the upper part of the mechanical seal attached.
Secure the auger assembly using new allen head cap screws.
18) Replace the evaporator bracket and reconnect the water hoses.
19) Replace spout A, spout B, and the storage bin cover in their correct positions.
20) Move the power switch to the "ON" position, then replace the panels in their correct
positions.
21) Turn on the power supply, then move the control switch to the "ICE" position to start the
automatic icemaking process.
5. Removal and Replacement of Mechanical Seal and Lower Housing
5a. Mechanical Seal
1) Move the control switch to the "DRAIN" position and drain all of the water from the
evaporator.
2) After the water has stopped draining, move the control switch to the "OFF" position, then
turn off the power supply. Remove the front and top panels, then move the power switch
to the "OFF" position.
3) Remove storage bin cover. Remove spout B, then remove spout A. See Fig. 14.
4) Remove the apron panel, then remove the left side panel.
5) Remove the extruding head heater and the allen head cap screws securing the
extruding head and discard the allen head cap screws.
6) Using the cutter, lift out the auger assembly, then remove the evaporator bracket.
7) The mechanical seal consists of two parts. One moves along with the auger, and the
other is fixed on the lower housing. NOTICE! If the contact surfaces of these two
parts are worn, cracked, or scratched, the mechanical seal may cause water leaks
and should be replaced.
8) Remove the allen head cap screws securing the evaporator to the lower housing.
9) Raise the evaporator up to access the lower housing.
10) Remove the mechanical seal from the housing. If only replacing the mechanical seal,
proceed to step 13. NOTICE! To help prevent water leaks, be careful not to damage
the surfaces of the O-ring or mechanical seal.
5b. Lower Housing
11) Remove the O-ring and the bolts securing the housing to the gear motor and remove
the housing from the gear motor. If inspection of the upper bearing inside the extruding
head (see "IV.C.1. Upper Bearing Wear Check") indicates that it is out of tolerance,
replace both it and the bearing inside the lower housing.
Note: Replacing the bearing requires a bearing press adaptor. If one is not available,
replace the whole extruding head and housing.
12) Install the O-ring and mount the lower housing on the gear motor.
47
Download from Www.Somanuals.com. All Manuals Search And Download.
13) Install the lower part of the mechanical seal on the lower housing.
14) Lower the evaporator down and secure it to the lower housing.
15) Install the auger assembly with the upper part of the mechanical seal attached. Secure
the auger assembly using new allen head cap screws.
16) Replace the evaporator bracket in its correct position.
17) Replace spout A, spout B, and the front cover of the storage bin in their correct
positions.
18) Move the power switch to the "ON" position, then replace the panels in their correct
positions.
19) Turn on the power supply, then move the control switch to the "ICE" position to start the
automatic icemaking process.
6. Removal and Replacement of Gear Motor
1) Move the control switch to the "DRAIN" position and drain all of the water from the
evaporator.
2) After the water has stopped draining, move the control switch to the "OFF" position, then
turn off the power supply. Remove the front and top panels, then move the power switch
to the "OFF" position.
3) Remove the storage bin cover. Remove spout B, then remove spout A. See Fig. 14.
4) Remove the apron panel, then remove the left side panel.
5) Remove the evaporator bracket.
6) Remove the bolts securing the lower housing to the gear motor. Lift the evaporator up
slightly.
7) Remove the 3 gear motor bolts.
8) Disconnect the wiring from the gear motor, then remove the gear motor.
9) Remove the spline coupling from the old gear motor and attach to the new gear motor.
10) Place the new gear motor in the drain pan.
11) Secure the gear motor.
12) Connect the gear motor wires.
13) Lower the evaporator down and secure it to the gear motor.
14) Replace the evaporator bracket in its correct position.
15) Replace spout A, spout B, and the front cover of the storage bin in their correct
positions.
16) Move the power switch to the "ON" position, then replace the panels in their correct
positions.
17) Turn on the power supply, then move the control switch to the "ICE" position to start the
automatic icemaking process.
48
Download from Www.Somanuals.com. All Manuals Search And Download.
D. Dispense Components
1. Dispense Auger and Agitator
1) Move the control switch to the "OFF" position, then turn off the power supply. Remove
the front and top panels, then move the power switch to the "OFF" position.
2) Remove the storage bin cover.
3) Remove the thumbscrews from the vertical plane, then loosen the thumbscrews from
the horizontal plane of the motor bracket. Slide the motor back.
Note: Hold the dispense auger/agitator to prevent it from dropping when sliding back the
motor. See Fig. 16.
4) Replace the dispense auger/agitator with the new one.
5) Assemble the removed parts in the reverse order of which they were removed.
6) Move the power switch to the "ON" position, then replace the panels in their correct
positions.
7) Turn on the power supply, then move the control switch to the "ICE" position to start the
automatic icemaking process.
2. Dispense and Agitating Motors
1) Move the control switch to the "OFF" position, then turn off the power supply. Remove
the front and top panels, then move the power switch to the "OFF" position.
2) Remove the storage bin cover.
3) Remove the thumbscrews from the vertical plane, then loosen the thumbscrews from
the horizontal plane of the motor bracket. Slide the motor back.
Note: Hold the dispense auger/agitator to prevent it from dropping when sliding back the
motor. See Fig. 16.
4) Remove the thumbscrews from the horizontal plane of the motor bracket.
5) Remove the motor from the bracket.
6) Install the new motor.
7) Assemble the removed parts in the reverse order of which they were removed.
8) Move the power switch to the "ON" position,
Agitator
Agitating Motor
then replace the panels in their correct
positions.
9) Turn on the power supply, then move the
control switch to the "ICE" position to start
the automatic icemaking process.
Dispense Motor
Fig. 16
Dispense Auger
49
Download from Www.Somanuals.com. All Manuals Search And Download.
V. Maintenance
The maintenance schedule below is a guideline. More frequent maintenance may be
required depending on water quality, the appliance's environment, and local sanitation
regulations.
WARNING
• Only qualified service technicians should service the appliance.
• Move the control switch and power switch to the "OFF" positions, then turn off the
power supply before servicing. Lockout/Tagout to prevent the power supply from
being turned back on inadvertently.
Maintenance Schedule
Frequency Area
Task
Every 2
Weeks
Air Filter
Inspect. Wash with warm water and neutral cleaner if dirty.
Monthly
External Water
Filters
Check for proper pressure and change if necessary.
Appliance Exterior Wipe down with a clean, soft cloth. Use a damp cloth containing a neutral
cleaner to wipe off oil or dirt build up. Clean any chlorine staining (rust
colored spots) using a non-abrasive cleaner.
Every 6
Months
Icemaker and
Storage Bin
Clean and sanitize per the cleaning and sanitizing instructions provided in
the instruction manual or maintenance label on the appliance.
Evaporator
Wipe down with a clean cloth and warm water. Dilute 0.82 fl. oz. (25 ml) of a
Condensate Drain 5.25% sodium hypochlorite solution (chlorine bleach) with 1.6 gal. (6.0 l) of
Pan and Gear
Motor Drain Pan
warm water. Slowly pour one cup of sanitizing solution into the evaporator
condensate drain pan. Be careful not to overflow the pan. This solution will
flow down to the gear motor drain pan and out the drain line to sanitize
these areas. Repeat with a cup of clean water to rinse.
Icemaker, Storage Check to make sure they are clear.
Bin, and Drip Tray
Drains
Yearly
Inlet Water Valve
and Drain Valve
Close the water supply line shut-off valve and drain the water system. Clean
the inlet water valve screen and clean and inspect the drain valve.
Water Hoses
Condenser
Appliance
Inspect the water hoses and clean/replace if necessary.
Inspect. Clean if necessary by using a brush or vacuum cleaner.
Inspect for oil spots, loose components, fasteners, and wires.
Upper Bearing
(extruding head)
Check for wear using .02" round stock or pin gauge. Replace both upper
bearing and lower bearing if wear exceeds factory recommendations. See
"IV.C.1. Upper Bearing Wear Check".
After
3 Years,
then Yearly Lower Bearing
and O-Ring
Upper Bearing
(extruding head);
Inspect. Replace both upper bearing and lower bearing if wear exceeds
factory recommendations. Replace the mechanical seal if the seal's contact
surfaces are worn, cracked, or scratched.
(lower housing);
Mechanical
Seal; Evaporator
Cylinder; Auger
50
Download from Www.Somanuals.com. All Manuals Search And Download.
VI. Preparing the Appliance for Periods of Non-Use
NOTICE
When storing the appliance for an extended time or in sub-freezing temperatures,
follow the instructions below to prevent damage.
When the appliance is not used for two or three days under normal conditions,
it is sufficient to only move the control switch to the "OFF" position. When
storing the appliance for extended time or in sub-freezing temperatures, follow
the instructions below.
1. Remove the ice from the storage bin, drain the water system, and remove the water
from the icemaker/water dispenser water supply line:
1) Close the icemaker water supply line shut-off valve and open the icemaker water supply
line drain valve.
2) Move the control switch to the "OFF" position, pause momentarily, then move to the
"DRAIN" position. Allow the water system to drain for 5 minutes.
Note: a) A momentary pause in the "OFF" position is necessary to de-energize the
control board when moving the control switch between "ICE" and "DRAIN."
Otherwise there is a delay of several minutes before the new selection takes
effect.
b) If the control switch is left in the "DRAIN" position for 10 minutes or more, a
2-beep alarm sounds every 5 seconds. Move the control switch out of the
"DRAIN" position to clear the alarm.
3) Move the dispense mode switch to the "CONTINUOUS" position, then dispense all of
the ice from the storage bin.
Note: Ice dispenses continuously for a maximum of 60 seconds per activation.
4) Attach a compressed air or carbon dioxide supply to the icemaker water supply line
drain valve.
5) While engaging the water dispense switch, blow out the water dispense valve using the
compressed air or carbon dioxide supply. After blowing out the water dispense valve,
leave the compressed air or carbon dioxide supply flowing. Move the control switch to
the "OFF" position, pause momentarily, then move to the "ICE" position to open the inlet
water valve and briefly blow out the inlet water valve. After blowing out the inlet water
valve, move the control switch to the "OFF" position.
6) Close the icemaker water supply line drain valve.
7) Turn off the power supply, then remove the front panel and move the power switch to the
"OFF" position.
8) Remove the storage bin cover. Clean the storage bin liner and the storage bin cover
using a neutral cleaner. Rinse thoroughly after cleaning. Replace the storage bin cover
and the front panel in their correct positions.
Note: If your unit has a water-cooled condenser, leave the front panel off and go to the
next section.
51
Download from Www.Somanuals.com. All Manuals Search And Download.
2. On water-cooled model only, remove the water from the water-cooled condenser:
1) Make sure the control switch and the power switch are in the "OFF" position and that
the power supply is off. Remove the top, apron, and left side panels.
2) Close the condenser water supply line shut-off valve. If connected to a closed loop
system, also close the condenser return line shut-off valve.
3) Open the condenser water supply line drain valve. If connected to a closed loop system,
also open the condenser return line drain valve.
4) Attach a compressed air or carbon dioxide supply to the condenser water supply line
drain valve.
5) Open the water regulating valve by using a screwdriver to pry up on the spring retainer
underneath the spring. While holding the valve open, blow out the condenser using the
compressed air or carbon dioxide supply until water stops coming out.
6) Close the drain valve(s).
7) Replace the panels in their correct positions..
52
Download from Www.Somanuals.com. All Manuals Search And Download.
VII. Disposal
The appliance contains refrigerant and must be disposed of in accordance with
applicable national, state, and local codes and regulations. Refrigerant must be
recovered by properly certified service personnel.
53
Download from Www.Somanuals.com. All Manuals Search And Download.
VIII.Technical Information
A. Specification Sheets
1. DCM-751BAH
AC SUPPLY VOLTAGE
COMPRESSOR
GEAR MOTOR
115/60/1
115 V
115 V
115 V
120 V
115 V
115 V
20 A
20 A
20 A
20 A
Ambient
Temp.(°F)
70
77 LRA
3.0 FLA
1.0 FLA
1.8 FLA (TOTAL)
0.9 FLA
11.0 RLA
1/4 HP
50 W
110 W (TOTAL)
55 W
FAN MOTOR
AGITATING MOTOR
DISPENSING MOTOR
OTHER
MAXIMUM FUSE SIZE
MAX. HACR BREAKER (USA ONLY)
MAX. CIRC. BREAKER (CANADA ONLY)
MINIMUM CIRCUIT AMPACITY
APPROXIMATE ICE PRODUCTION
PER 24 HR.
0.6 A
WATER TEMP. (°F)
70
*801 (363) 757 (343)
695 (315) 666 (302)
50
90
725 (329)
639 (290)
lbs./day (kg/day)
Reference without *marks
80
90
100
612 (278) *583 (265) 562 (255)
539 (245) 517 (234) *490 (222)
SHAPE OF ICE
Cubelet
ICE HARDNESS FACTOR
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)
POTABLE WATER
90% (90/70°F, Conductivity 200 µs/cm)
95 lbs.
90/70°F
1388 (5.94)
70 (12.0)
70/50°F
1292 (4.08)
96 (12.0)
gal./24HR (gal./100 lbs.)
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
34-1/16" x 28-1/2" x 48-1/16" (865 x 723 x 1221 mm) (No legs)
Stainless Steel; Galvanized Steel (Rear)
Net 300 lbs. (136 kg), Shipping 345 lbs. (156 kg)
Permanent Connection
Inlet 1/2" FPT
- DRAIN
Drip Tray Drain Outlet 3/4" FPT
Storage Bin Drain Outlet 3/4" FPT
Auger Type
ICE MAKING SYSTEM
HARVESTING SYSTEM
ICE MAKING WATER CONTROL
DISPENSER CONTROL SYSTEM
BIN CONTROL SYSTEM
COMPRESSOR
Direct Driven Auger (1/4 HP Gear Motor)
Float Switch
Push Button
Mechanical Bin Control and Timer
Hermetic, Model RST61C1E-CFA-202
Air-Cooled, Fin and Tube Type
Copper Tube on Cylinder
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
GEAR MOTOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES - SUPPLIED
- OPTIONAL
Thermostatic Expansion Valve
R-404A, 1 lb. 10 oz. (737 g)
High 460 PSIG, Low 290 PSIG
High Voltage Power Protect Relay
Auto-Reset Internal Protector
Auto-Reset Internal Protector and Fuse (3A)
Auto-Reset High Pressure Switch
Float Switch and Timer
Spare Fuse (2-3A), Legs
HS-5003, Apron kit when drip tray removed
OPERATING CONDITIONS
VOLTAGE RANGE
AMBIENT TEMP.
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
104-127 V
45-100° F
45-90° F
10-113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
54
Download from Www.Somanuals.com. All Manuals Search And Download.
2. DCM-751BAH-OS
AC SUPPLY VOLTAGE
COMPRESSOR
GEAR MOTOR
115/60/1
115 V
115 V
115 V
120 V
115 V
115 V
20 A
20 A
20 A
20 A
Ambient
Temp.(°F)
70
77 LRA
3.0 FLA
1.0 FLA
1.8 FLA (TOTAL)
0.9 FLA
11.0 RLA
1/4 HP
50 W
110 W (TOTAL)
55 W
FAN MOTOR
AGITATING MOTOR
DISPENSING MOTOR
OTHER
MAXIMUM FUSE SIZE
MAX. HACR BREAKER (USA ONLY)
MAX. CIRC. BREAKER (CANADA ONLY)
MINIMUM CIRCUIT AMPACITY
APPROXIMATE ICE PRODUCTION
PER 24 HR.
0.6 A
WATER TEMP. (°F)
70
*801 (363) 757 (343)
695 (315) 666 (302)
50
90
725 (329)
639 (290)
lbs./day (kg/day)
Reference without *marks
80
90
100
612 (278) *583 (265) 562 (255)
539 (245) 517 (234) *490 (222)
SHAPE OF ICE
Cubelet
ICE HARDNESS FACTOR
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)
POTABLE WATER
90% (90/70°F, Conductivity 200 µs/cm)
95 lbs.
90/70°F
1388 (5.94)
70 (12.0)
70/50°F
1292 (4.08)
96 (12.0)
gal./24HR (gal./100 lbs.)
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
34-1/16" x 28-1/2" x 48-1/16" (865 x 723 x 1221 mm) (No legs)
Stainless Steel; Galvanized Steel (Rear)
Net 300 lbs. ( 136 kg ), Shipping 345 lbs. ( 156 kg )
Permanent Connection
Inlet 1/2" FPT
- DRAIN
Drip Tray Drain Outlet 3/4" FPT
Storage Bin Drain Outlet 3/4" FPT
Auger Type
Direct Driven Auger (1/4 HP Gear Motor)
Float Switch
Photoelectric Sensor (Infrared)
Mechanical Bin Control and Timer
Hermetic, Model RST61C1E-CFA-202
Air-Cooled, Fin and Tube Type
Copper Tube on Cylinder
ICE MAKING SYSTEM
HARVESTING SYSTEM
ICE MAKING WATER CONTROL
DISPENSER CONTROL SYSTEM
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
Thermostatic Expansion Valve
R-404A, 1 lb. 10 oz. (737 g)
High 460 PSIG, Low 290 PSIG
CONTROL BOARD CIRCUIT PROTECTION High Voltage Power Protect Relay
COMPRESSOR PROTECTION
GEAR MOTOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES - SUPPLIED
- OPTIONAL
Auto-Reset Internal Protector
Auto-Reset Internal Protector and Fuse (3A)
Auto-Reset High Pressure Switch
Float Switch and Timer
Spare Fuse (2-3A), Legs
HS-5002, Apron kit when drip tray removed
OPERATING CONDITIONS
VOLTAGE RANGE
104-127VAC
AMBIENT TEMP.
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45-100°F
45-90°F
10-113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
55
Download from Www.Somanuals.com. All Manuals Search And Download.
3. DCM-751BWH
AC SUPPLY VOLTAGE
COMPRESSOR
GEAR MOTOR
AGITATING MOTOR
DISPENSING MOTOR
OTHER
MAXIMUM FUSE SIZE
MAX. HACR BREAKER (USA ONLY)
MAX. CIRC. BREAKER (CANADA ONLY)
MINIMUM CIRCUIT AMPACITY
APPROXIMATE ICE PRODUCTION
PER 24 HR.
115/60/1
115 V
115 V
120 V
115 V
115 V
20 A
20 A
20 A
20 A
77 LRA
3.0 FLA
1.8 FLA (TOTAL)
0.9 FLA
0.6 A
11.0 RLA
1/4 HP
110 W (TOTAL)
55 W
Ambient
Temp.(°F)
70
WATER TEMP. (°F)
70
*800 (363) 779 (353)
738 (335) 719 (326)
50
90
758 (344)
700 (317)
lb./day (kg/day)
Reference without *marks
80
90
100
681 (309) *685 (311) 646 (293)
629 (285) 612 (278) *563 (255)
SHAPE OF ICE
Cubelet
ICE HARDNESS FACTOR
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lb.)
POTABLE WATER
WATER-COOLED CONDENSER
gal./24HR (gal./100 lb.)
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
90% (90/70°F, Conductivity 200 µs/cm)
95 lb.
90/70°F
1281 (4.77)
82 (12.0)
517 (76)
70/50°F
1274 (3.86)
96 (12.0)
380 (47)
34-1/16" x 28-1/2" x 48-1/16" (865 x 723 x 1221 mm) (No legs)
Stainless Steel; Galvanized Steel (Rear)
Net 300 lb. (136 kg), Shipping 345 lb. (156 kg)
Permanent Connection
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
Inlet 1/2" FPT
Condenser Inlet 1/2" FPT
Condenser Outlet 3/8" FPT
- DRAIN
Drip Tray Drain Outlet 3/4" FPT
Storage Bin Drain Outlet 3/4" FPT
Auger Type
ICE MAKING SYSTEM
HARVESTING SYSTEM
ICE MAKING WATER CONTROL
DISPENSER CONTROL SYSTEM
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
Direct Driven Auger (1/4 HP Gear Motor)
Float Switch
Push Button
Water Regulating Valve
Mechanical Bin Control and Timer
Hermetic, Model RST61C1E-CFA-202
Water Cooled, Tube in Tube Type
Copper Tube on Cylinder
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
GEAR MOTOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES - SUPPLIED
- OPTIONAL
Thermostatic Expansion Valve
R-404A, 1 lb. 6 oz. (624 g)
High 460 PSIG, Low 290 PSIG
High Voltage Power Protect Relay
Auto-Reset Internal Protector
Auto-Reset Internal Protector and Fuse (3A)
Auto-Reset High Pressure Switch
Float Switch and Timer
Spare Fuse (2-3A), Legs
HS-5003, Apron kit when drip tray removed
OPERATING CONDITIONS
VOLTAGE RANGE
104-127 VAC
AMBIENT TEMP.
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45-100° F
45-90° F
10-113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
56
Download from Www.Somanuals.com. All Manuals Search And Download.
4. DCM-751BWH-OS
AC SUPPLY VOLTAGE
COMPRESSOR
GEAR MOTOR
AGITATING MOTOR
DISPENSING MOTOR
OTHER
MAXIMUM FUSE SIZE
MAX. HACR BREAKER (USA ONLY)
MAX. CIRC. BREAKER (CANADA ONLY)
MINIMUM CIRCUIT AMPACITY
APPROXIMATE ICE PRODUCTION
PER 24 HR.
115/60/1
115 V
115 V
120 V
115 V
115 V
20 A
20 A
20 A
20 A
77 LRA
3.0 FLA
1.8 FLA (TOTAL)
0.9 FLA
0.6 A
11.0 RLA
1/4 HP
110 W (TOTAL)
55 W
Ambient
Temp.(°F)
70
WATER TEMP. (°F)
70
*800 (363) 779 (353)
738 (335) 719 (326)
50
90
758 (344)
700 (317)
lb./day (kg/day)
Reference without *marks
80
90
100
681 (309) *685 (311) 646 (293)
629 (285) 612 (278) *563 (255)
SHAPE OF ICE
Cubelet
ICE HARDNESS FACTOR
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lb.)
POTABLE WATER
WATER-COOLED CONDENSER
gal./24HR (gal./100 lb.)
EXTERIOR DIMENSIONS (WxDxH)
EXTERIOR FINISH
90% (90/70°F, Conductivity 200 µs/cm)
95 lb.
90/70°F
1281 (4.77)
82 (12.0)
517 (76)
70/50°F
1274 (3.86)
96 (12.0)
380 (47)
34-1/16" x 28-1/2" x 48-1/16" (865 x 723 x 1221 mm) (No legs)
Stainless Steel; Galvanized Steel (Rear)
Net 300 lb. (136 kg), Shipping 345 lb. (156 kg)
Permanent Connection
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
Inlet 1/2" FPT
Condenser Inlet 1/2" FPT
Condenser Outlet 3/8" FPT
- DRAIN
Drip Tray Drain Outlet 3/4" FPT
Storage Bin Drain Outlet 3/4" FPT
Auger Type
ICE MAKING SYSTEM
HARVESTING SYSTEM
ICE MAKING WATER CONTROL
DISPENSER CONTROL SYSTEM
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
Direct Driven Auger (1/4 HP Gear Motor)
Float Switch
Photoelectric Sensor (Infrared)
Water Regulating Valve
Mechanical Bin Control and Timer
Hermetic, Model RST61C1E-CFA-202
Water Cooled, Tube in Tube Type
Copper Tube on Cylinder
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
GEAR MOTOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES - SUPPLIED
- OPTIONAL
Thermostatic Expansion Valve
R-404A, 1 lb. 6 oz. (624 g)
High 460 PSIG, Low 290 PSIG
High Voltage Power Protect Relay
Auto-Reset Internal Protector
Auto-Reset Internal Protector and Fuse (3A)
Auto-reset High Pressure Switch
Float Switch and Timer
Spare Fuse (2-3A), Legs
HS-5002, Apron kit when drip tray removed
OPERATING CONDITIONS
VOLTAGE RANGE
104-127 VAC
AMBIENT TEMP.
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
45-100° F
45-90° F
10-113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
57
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Performance Data
1. DCM-751BAH(-OS)
APPROXIMATE
ICE PRODUCTION
PER 24 HR.
Ambient
Water Temp. (°F)
70
Temp. (°F)
50
90
70
80
801
695
612
539
1292
1333
1374
1414
96
363
315
278
245
--
757
666
583
517
1306
1347
1388
1426
91
343
302
265
234
--
725
639
562
490
1319
1361
1401
1439
87
329
290
255
222
--
90
lb./day kg/day
100
70
APPROXIMATE ELECTRIC
CONSUMPTION
80
--
--
--
90
--
--
--
watts
100
70
--
--
--
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
364
316
278
245
344
303
265
235
330
290
256
223
80
83
80
77
90
73
70
68
gal./day l/day
100
65
62
59
EVAPORATOR OUTLET TEMP.
70
80
14
-10
14
18
-10
-8
14
18
-10
-8
14
-10
90
18
-8
18
-8
20
-7
°F °C
100
70
20
217
253
289
327
32
-7
20
217
253
289
327
32
-7
20
217
253
289
327
32
-7
HEAD PRESSURE
15.3
17.8
20.3
23.0
2.2
15.3
17.8
20.3
23.0
2.2
15.3
17.8
20.3
23.0
2.2
80
90
PSIG kg/cm²G
100
70
SUCTION PRESSURE
80
34
2.4
34
2.4
34
2.4
90
36
2.5
36
2.5
36
2.5
PSIG kg/cm²G
100
38
2.7
38
2.7
38
2.7
TOTAL HEAT OF REJECTION
9,300 BTU/h (AT 90°F /WT 70°F)
Note:
1. The data not in bold should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
58
Download from Www.Somanuals.com. All Manuals Search And Download.
2. DCM-751BWH(-OS)
APPROXIMATE
ICE PRODUCTION
PER 24 HR.
Ambient
Water Temp. (°F)
70
Temp. (°F)
50
90
70
80
800
738
363
335
309
285
--
779
719
353
326
311
278
--
758
700
344
317
293
255
--
90
681
685
646
lb./day kg/day
100
70
629
612
563
APPROXIMATE ELECTRIC
CONSUMPTION
1274
1277
1280
1286
474
1275
1278
1281
1289
513
1276
1279
1284
1291
686
80
--
--
--
90
--
--
--
watts
100
70
--
--
--
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
1.79
1.91
1.94
2.36
1.94
2.14
2.31
2.49
2.60
3.04
3.11
3.86
80
504
565
804
90
513
609
823
gal./day l/day
100
623
659
1019
EVAPORATOR OUTLET TEMP.
70
80
12
-11
12
12
-11
-11
12
12
-11
-11
12
-11
90
12
-11
12
-11
13
-10
°F °C
100
70
13
258
259
260
257
32
-10
18.1
18.2
18.3
18.1
2.3
13
258
259
260
257
32
-10
18.1
18.2
18.3
18.1
2.3
13
258
259
260
257
32
-10
18.1
18.2
18.3
18.1
2.3
HEAD PRESSURE
80
90
PSIG kg/cm²G
100
70
SUCTION PRESSURE
80
33
2.3
33
2.3
33
2.3
90
33
2.3
33
2.3
33
2.3
PSIG kg/cm²G
100
35
2.4
35
2.4
35
2.4
WATER FLOW FOR CONDENSER
20gal/h (AT 90°F /WT 70°F)
Less than 7 PSIG
PRESSURE DROP OF COOLING WATER LINE
HEAT OF REJECTION FROM CONDENSER
HEAT OF REJECTION FROM COMPRESSOR
HEAT OF REJECTION FROM GEAR MOTOR
8,100 BTU/h (AT 90°F /WT 70°F)
1,300 BTU/h (AT 90°F /WT 70°F)
700 BTU/h (AT 90°F /WT 70°F)
Note:
1. The data not in bold should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
59
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Wiring Diagrams
1. DCM-751B_H
*
* High Pressure Switch
Air-Cooled Model Water-Cooled Model
412 21 PSIG
384 21 PSIG
Cut-out
Cut-in
0
0
327 21 PSIG
284 21 PSIG
60
Download from Www.Somanuals.com. All Manuals Search And Download.
2. DCM-751B_H-OS
*
* High Pressure Switch
Air-Cooled Model Water-Cooled Model
412 21 PSIG
384 21 PSIG
Cut-out
Cut-in
0
0
327 21 PSIG
284 21 PSIG
61
Download from Www.Somanuals.com. All Manuals Search And Download.
|