		 CM67   
					CHRONOTHERM   
					PRODUCT SPECIFICATION SHEET   
					The CM67 Chronotherm is designed to provide automatic   
					time and temperature control of heating or cooling systems   
					in villas and apartments. It can be used as part of a system   
					in conjunction with combi boilers, oil- burners and gas fired   
					boilers, circulation pumps, thermal actuators, zone valves   
					and electric heat systems (<8A).   
					The CM67 is designed with the installer in mind and includes   
					a moulded backplate with trunking guides and wiring   
					breakouts to make installation quick and easy.   
					The CM67 display, buttons and slider layout are based on   
					the same simple programming philosophy used on the   
					acclaimed CM51 product. The unit is ideal for consumers   
					who want reliable precise temperature control from a simple   
					to program easy to use product.   
					FEATURES   
					• Attractive slim styling makes it ideal for location in   
					• Surface or wallbox mounting options, trunking   
					any home.   
					guides and wiring breakouts simplify installation.   
					• 7-day program   
					• 6 daily independent time and temperature level   
					changes let you set 6 time and temperatures pairs to   
					suit your life style.   
					• OFF position on the slider has an integral fixed frost   
					protection setting at minimum of 5°C (installer   
					adjustable) so that pipes in the house will never   
					freeze in winter.   
					• Installer Set-Up Mode allows extra functions to be   
					set at the discretion of the installer to match the   
					consumers applications :   
					• Temporary programmed temperature override to   
					temporarily override the programmed temperature   
					till the next switch point.   
					• Optimisation   
					• 
					• 
					Party button to temporarily maintain (or adjust)   
					the current temperature for 1-23 hours.   
					• Pump Exercise   
					• Upper / Lower Setpoint Limit Adjust   
					• Temperature offset   
					• Minimum ON time   
					• Cycle rate   
					Day Off button copies Sunday’s program into   
					tomorrow or today to allow a rest day program   
					without having to re-program the CM67.   
					• 
					Holiday button provides energy savings by   
					reducing the temperature for 1 to 99 days when   
					people are on holiday, returning to normal operation   
					(AUTO or MANUAL) on the day of return.   
					• Heat / Cool Operation   
					• Proportional Band Width   
					• EEPROM memory holds the user program   
					• CM67 has provision for add-on modules to allow the   
					installer to sell additional features during or after the   
					first CM67 installation, giving the installer an   
					additional sale.   
					indefinitely.   
					• Telephone Interface (optional) can be fitted to the   
					CM67 to allow switching between programmed mode   
					(slider position) and fixed set-point of 21 oC.   
					• Outside Temperature Sensor accessory (optional)   
					can be fitted to the CM67 to display the external   
					temperature.   
					• 24...230V 8A resistive, 3A inductive SPDT relay   
					provides compatibility with most domestic central   
					heating systems without stocking many different   
					models.   
					• Remote Temperature Sensor (optional) can be fitted   
					to the CM67 to control the temperature from another   
					room.   
					EN0R 8498 R2 11/98   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				CM67 CHRONOTHERM   
					INSTALLER SET-UP   
					To enter the installer set-up mode :   
					a) Set the program slider to OFF.   
					b) Press and hold Info i button and press PROG 3,4   
					together.   
					c) The unit will display the first parameter of the installer   
					parameter group category 1 (from n.1 to n.5).   
					d) Press TEMP   
					or   
					to change factory setting. The   
					display will flash indicating that a change has been   
					made.   
					e) Press INFO i button to confirm the change. The display   
					will stop flashing.   
					f) Press   
					+ or - to go to next parameter.   
					Abbreviated Set-Up Description   
					g) Press PROG 2 button to go to Installer parameter group   
					e.g. OP = Optimisation   
					category 2 (from parameter n.6 to parameter n.16).   
					h) To exit installer mode move the slider in MAN or AUTO   
					Installer Set-up Number   
					position.   
					(Press   
					+ or - to change)   
					e.g. 1 = Optimisation   
					Installer Set-Up Mode   
					1 
					Selected   
					Factory Setting or New Choice   
					In Installer set up we can :   
					Press TEMP L or Mto change   
					e.g. O = Optimisation disabled   
					1 = Optimisation enabled   
					❑ Set-up specific applications   
					❑ Enable special features   
					❑ Establish support for Optional Accessories   
					Specific Applications   
					Setting   
					Minimum   
					What do you need to change ?   
					Note :   
					a. To change Cycle/Hour, please go to parameter n. 9 in the   
					installer set-up mode.   
					Cycle/   
					Hour   
					ON time   
					(in minutes)   
					b. To change Minimum ON Time, please go to parameter n. 2 in   
					the installer set-up mode.   
					Heating   
					Gas Boilers   
					(<30KW)   
					6 
					3 
					1 
					4 
					No action required   
					Oil Boiler   
					1. Set Minimum ON Time to 4 minutes.   
					2. Set Cycle/Hour to 3.   
					Thermal   
					Actuator   
					12   
					1 
					Set Cycle/Hour to 12.   
					Zone valve   
					6 
					1 
					1 
					No action required.   
					Electric heating   
					(for applications   
					<8A)   
					12   
					1. Configure the Chronotherm for electric heating (set parameter   
					n.7 in the installer set up mode to 1).   
					2. Set Cycle/Hour to 12.   
					1. For cooling application only, set the Chronotherm to cooling   
					(set parameter n.6 in the installer set-up mode to 0)   
					2. For heat/ cool application, set the Chronotherm accordingly to   
					required mode of operation   
					Air   
					conditioning   
					winter = heating   
					summer = cooling   
					by changing parameter n.6 in the installer set-up mode. Explain to   
					the end-user how to implement the change-over.   
					Heat Pump/   
					Air conditioner   
					3 
					4 
					1. Set Minimum ON Time to 4 minutes .   
					2. Set Cycle/Hour to 3.   
					3 
					EN0R 8498 R2 11/98   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				CM67 CHRONOTHERM   
					Special Features   
					Description   
					What to do if we wish this   
					feature   
					Optimisation (Variable   
					Start Time)   
					Adaptive Intelligence   
					recovery TM   
					The Chronotherm will adjust the start time in the   
					morning/ afternoon so the desired temperature is   
					reached by the start of the program period e.g. Time   
					7:00, Temp 21 oC. The Chronotherm will monitor the   
					accuracy of the start up and use this information to   
					modify the calculation for the following day by   
					changing the ramp rate (initial 3 K/hr) .The system will   
					restrict the start time to a max of 3 hours.   
					Set parameter. 1 in the installer set-   
					up mode to 1.   
					Optimisation will not work in cooling mode.   
					AM-PM/ 24hr Display   
					Pump exercise   
					Change display format (default 24hr)   
					Set parameter n.3 in the installer set -   
					up mode to 1.   
					When enabled the Pump Exercise will switch the relay   
					on for 1 minute at 12:00 if the relay has not been   
					switched on since 12:00 the previous day.   
					Set parameter n.8 in the installer set -   
					up mode to 1.   
					While in Holiday mode the Pump Exercise feature, if   
					enabled, will operate.   
					Upper Temperature   
					Limit   
					The normal upper temperature limit of 30 oC can be   
					Set parameter n.11 in the installer set   
					reduced down to 21 oC to save energy. Useful for small -up mode to the desired limit.   
					commercial premises.   
					Lower Temperature   
					Limit   
					The normal lower temperature limit of 5 oC can be   
					increased up to 16 oC to protect the inhabitants from   
					cold. Useful if the inhabitants include the elderly,   
					children or disabled.   
					Set parameter n.12 in the installer set   
					-up mode to the desired limit.   
					Temperature Offset   
					If the Chronotherm is located in a hot/cold location and Set parameter n.13 in the installer set   
					cannot be moved because of wiring then the measured/ -up mode to the desired offset value.   
					displayed temperature can be adjusted by +/- 3 oC.   
					Useful if the homeowner wants the reading to match   
					another appliance temperature display.   
					Proportional Band Width Can be adjusted up to 3 oC (default is 1.5 oC) to provide Set parameter n.15 in the installer set   
					better temperature control (less overshoot).   
					-up mode to the desired value.   
					Useful for:   
					a. Well insulated homes with over-sized heating   
					systems   
					b. Air systems with fast response   
					Optional   
					Accessories   
					Description   
					What to do if we wish this   
					feature   
					Outside Temperature   
					Sensor   
					An Outside Temperature Sensor can be fitted to your   
					CM67 to allow the homeowner to display the outside   
					temperate on the Chronotherm display by using the   
					INFO i button. CM67 will read the outside temperature   
					every 10 minutes. Outside temperature display range is   
					from -30 oC to +45 oC. The sensor can be connected up   
					to 50 meters from the unit.   
					1. Fit the sensor (instructions   
					included in the sensor package)   
					2. Set parameter n. 10 in the   
					installer set-up mode to 1   
					Remote Temperature   
					Sensor   
					A Remote Temperature Sensor can be fitted to your   
					CM67 to allow the Chronotherm to control temperature   
					from another room or space where it is inconvenient to   
					locate the CM67 It will read the remote sensor every 1   
					minute. The sensor can be connected up to 50 meters   
					from the unit. Useful for commercial premises where   
					the public may tamper with the product.   
					1. Fit the sensor (instructions   
					included in the sensor package)   
					2. Set parameter n. 10 in the   
					installer set-up mode to 2   
					Automatic Time Setting   
					(ATS) Module   
					The ATS module picks up a time signal daily from a   
					European transmitter, so you never need to set or   
					adjust the time.   
					1. Fit the ATS module   
					2. Set parameter n. 4 in the installer   
					set-up mode to 1   
					EN0R 8498 R2 11/98   
					4 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				CM67 CHRONOTHERM   
					Parameter   
					Installer Set-   
					Up Number /   
					Abbreviation   
					(Press + or -   
					key to   
					Factory Setting   
					Optional Setting   
					Installer Set-   
					Up Category   
					(Press keys   
					PROG 1 or 2   
					to select)   
					1 2   
					change)   
					Display   
					Description   
					Display/Setting   
					Description   
					Optimisation   
					1:0P   
					2:0t   
					0 
					1 
					Optimisation disabled   
					1 
					Optimisation enabled   
					1 
					1 
					MinimumONTime   
					1minuteminimumONtime   
					2to5   
					2- 2minutes   
					3 - 3 minutes   
					4 - 4 minutes   
					5 - 5 minutes   
					AM-PM / 24hr Display   
					Accessory Module Type   
					3:Cl   
					4:At   
					0 
					0 
					24 hr clock display   
					1 
					12hrAM/PMclockdisplay   
					1 
					1 
					No accessory module   
					plugged in   
					1, 2   
					1 - Auto Time Setting Module   
					2 - Weatherstation Module   
					RESET Time /   
					Temperature Program   
					5:rP   
					1 
					Time / Temperature profile set   
					to factory default   
					Changes to 0 when one of the   
					time/temp profiles are changed   
					0 
					1 
					Time / Temperature are as   
					programmed   
					To restore the factory profile   
					set to 1   
					1 
					You must now press the PROG 2 key to enter the next section   
					Heat / Cool Operation   
					Electric Heat   
					6:HC   
					7:Eh   
					8:PE   
					9:Cr   
					1 
					0 
					0 
					6 
					Heating Operation   
					0 
					Cooling Operation   
					2 
					2 
					2 
					2 
					Applications < 3A   
					1 
					1 
					Applications 3 - 8A   
					Pump Exercise Enabled   
					Pump Exercise   
					Cycle Rate   
					Pump Exercise Disabled   
					6 cycles per hour (cph) for gas   
					boilers, zone valves and fan-   
					coil   
					3, 9, 12   
					3 - 3 cph   
					9 - 9cph   
					12 - 12 cph   
					Second Temperature   
					Sensor   
					10:SS   
					0 
					No sensor fitted   
					1, 2   
					1 - Outside Temperature   
					Sensor fitted   
					2 
					2 - Remote Temp. Sensor   
					fitted   
					Upper Temperature Limit   
					Lower Temperature Limit   
					Temperature Offset   
					11:UL   
					12:LL   
					13:tO   
					14:PO   
					30   
					5 
					30°C Upper Temp. Limit   
					5°C Lower Temp. Limit   
					No offset   
					21 to 29   
					6 to 16   
					21°C to 29°C adjustment in   
					1°C steps   
					2 
					2 
					2 
					2 
					6°C to 16°C adjustment in   
					1°C steps   
					0 
					-3 to +3   
					-99 to +3   
					-3°C to +3°C adjustment in   
					0.1°C steps   
					Pressure Offset   
					(needed for   
					0 
					No offset   
					-99 mbar to +99 mbar   
					adjustment in 1 mbar steps   
					Weatherstation accessory   
					only)   
					Proportional Band Width   
					15:Pb   
					16:FS   
					1.5   
					1 
					1.5°C Proportional Band   
					1.6 to 3.0   
					1.6°C to 3.0°C adjustment in   
					0.1°C steps   
					2 
					2 
					Return all Set-Up   
					Features to Factory   
					Settings   
					All settings held are the factory   
					defaults. Changes to 0 when   
					one of the parameter values   
					are changed   
					0 
					1 
					Settings are as modified   
					above   
					To restore the factory profile   
					set to 1   
					5 
					EN0R 8498 R2 11/98   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				CM67 CHRONOTHERM   
					DIMENSIONS   
					INSTALLATION   
					LOCATION   
					The CM67 Chronotherm is the temperature control element   
					in the heating/cooling system and MUST be located in a   
					position with good air circulation at average room   
					temperature on an inside wall 1.5 metres above the floor   
					level. Do not position the CM67 Chronotherm near sources   
					of heat (radiators, hot air vents, TV or lights), near doors or   
					windows, or in direct sunlight.   
					MOUNTING   
					The CM67 Chronotherm can be mounted directly on the wall   
					surface or on an electrical wallbox.   
					WIRING   
					The CM67 Chronotherm is designed for fixed wiring only and   
					must be installed in accordance with latest l.E.E. regulations.   
					Ensure the wiring connection to the supply is via a fuse rated   
					at no more than 8 amps and a Class "A" switch (having   
					contact separation of at least 3 mm in all poles).   
					IMPORTANT   
					1. The installer must be a trained service engineer   
					2. Disconnect the power supply before beginning   
					installation   
					EN0R 8498 R2 11/98   
					6 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				CM67 CHRONOTHERM   
					WIRING   
					ORDERING SPECIFICATION   
					Description   
					Model   
					Logo   
					Literature   
					Spec Sheet   
					NOTE: The model shown opposite   
					can be ordered as samples to   
					establish the exact   
					7-day   
					programmable   
					thermostat   
					T6667B1002   
					Honeywell   
					English   
					ENOR8498   
					customisation requirements   
					Remote sensor T7043G1004   
					Honeywell   
					Multi-   
					Language   
					ENOR8496   
					ENOR8495   
					ENOR8501   
					Outside temp   
					sensor   
					F42009537-   
					001   
					Multi-   
					Language   
					Automatic   
					Time Setting   
					Module Europe   
					Q6667B1007   
					Multi-   
					Language   
					Honeywell Control Systems Limited   
					Newhouse Industrial Estate   
					Motherwell ML1 5SB   
					
					United Kingdom   
					EN0R 8498 R2 11/98   