Honeywell Carbon Monoxide Alarm 19546GM1 User Manual

Gas Monitoring Alarm System  
Manning GM-1  
Instruction and Installation Manual  
07/09  
Release D Draft  
Honeywell Confidential & Proprietary  
This work contains valuable, confidential, and proprietary information. Disclosure, use  
or reproduction outside of Honeywell Inc. is prohibited except as authorized in writing.  
This unpublished work is protected by the laws of the United States and other countries.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About This Document  
World Wide Web  
The following Honeywell web sites may be of interest.  
Honeywell Organization  
WWW Address (URL)  
Corporate  
Honeywell Analytics  
Manning Gas Detection  
Telephone  
Contact us by telephone at the numbers listed below.  
Organization  
Phone Number  
United States  
Honeywell Analytics Inc.  
1-800-538-0363  
1-913-712-5576  
1-913-712-5580 Fax  
Canada  
Honeywell Analytics Inc.  
Honeywell PACE  
1-888-749-8878  
Europe  
+44 (0)1202 676161  
+82 (0)2 2025 0307  
+971 4 3458 338  
Asia Pacific  
Middle East  
Honeywell Asia Pacific Inc.  
Honeywell Analytics Inc.  
Sales Information  
Contact us at [email protected]  
Symbol Definitions  
The following table lists those symbols used in this document to denote certain conditions.  
Symbol  
Definition  
ATTENTION: Identifies information that requires special consideration.  
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result  
in minor or moderate injury. It may also be used to alert against unsafe practices.  
CAUTION symbol on the equipment refers the user to the product manual for  
additional information. The symbol appears next to required information in the manual.  
WARNING: Indicates a potentially hazardous situation, which, if not avoided, could  
result in serious injury or death. WARNING symbol on the equipment refers the user to  
the product manual for additional information. The symbol appears next to required  
information in the manual.  
indicates a situation which, if not avoided, may result in equipment or work (data) on  
the system being damaged or lost, or may result in the inability to properly operate  
the process.  
CAUTION  
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Serial number:  
Page  
Section  
Title  
1
2
3
4
System Description  
Installation  
Operation  
Limited Warranty  
Introduction  
This manual has been prepared to help in the use and installation of the Manning GM-1 Gas Monitoring Alarm  
System. This manual will convey the operating details of the alarm system, ensure proper installation, and  
demonstrate start-up and routine maintenance procedures.  
ATTENTION: This manual must be carefully followed by all individuals who have or will have the  
responsibility for using or servicing the Manning GM-1 alarm system. Warranties made by Honeywell  
Analytics with respect to this equipment will be voided if the equipment is not used and serviced in accordance  
with the instructions in this manual. If in doubt about a procedure, please contact Honeywell Analytics before  
proceeding.  
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
1 System Description  
The Manning GM-1 is designed to accept a single  
4/20 mA current input signal, plus provide a regulated  
24 VDC supply to operate all sensors manufactured by  
Honeywell Analytics.  
The Manning GM-1 is housed in a rugged 14 gauge  
gasketed steel enclosure. Behind the clear plexiglass  
window is a 20-segment vertical LED bargraph display  
which gives a visual indication of the gas  
concentration.  
The unit has warning and alarm level indications on the  
front panel, and warning and alarm relays allowing the  
user to incorporate functions such as ventilation  
control, remote horns, security system monitoring, and  
automatic shutdown.  
Designed to be highly reliable when properly installed,  
all relays are energized during normal operation, and a  
sensor fault monitoring circuit will indicate a fault and  
trip a dedicated fault relay if the signal falls below  
1.4 mA.  
The unit has an audible horn which will sound if an  
alarm or fault condition is detected. The silence switch  
will silence the horn until the next event. If an alarm  
condition initiates the horn, the horn will clear  
automatically when the alarm relay clears.  
The unit has a power-up delay feature that places all  
outputs in normal conditions for one minute to allow for  
sensor stabilization.  
The Manning GM-1 will support all of Manning  
sensors, including oxygen, which requires a down-  
scale alarm.  
All components that are in contact with voltages above  
40 volts are UL listed, including the enclosure.  
Note: The Manning GM-1 is for use in  
non-classified areas only.  
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1 System Description  
continued  
Enclosure: 14 gauge steel, gasketed, 10" high x 8"  
System Specifications  
wide x 4" deep, NEMA 1 rated enclosure with  
plexiglass window  
Electrical Power: 120 VAC, 50/60 Hz at 0.35 amp  
(230 VAC 50/60 Hz is available as an option)  
Weight: 11 lbs.  
Signal input: 4/20 mA  
Operating Ambient Temperature range: 0o F to  
+120o F  
DC Power available for sensors: Heavy-duty  
internal 24 VDC, 1 amp maximum regulated supply  
Operating Humidity: 5-95% Relative Humidity, non-  
Display: 20-segment LED bargraph  
Light Outputs and Relays:  
Alarm Light and Relay  
condensing  
Options: Down-scale Alarm for oxygen  
Push-button Controls:  
Setpoint field adjustable  
Silence — Silences internal horn  
Alarm Light and Relay independently latchable  
by board mounted DIP switch  
Reset — Clears signal, latched functions, and  
relays. If warning, alarm, or fault condition  
exists, indications will return after a short time  
delay.  
10 second on delay, 2 second off delay  
Warning Light and Relay  
Note: The Manning GM-1 is for use only in  
non-classified areas.  
Setpoint field adjustable  
Warning Light and Relay are NOT latchable  
10 second on delay, 2 second off delay  
Fault Light and Relay  
Setpoint NOT adjustable — all mA signals below  
1.4 mA will initiate fault output  
Fault Light and Relay always latch  
10 second on delay  
Note: All relays are normally energized  
and monitored by individual LEDs for  
ease of troubleshooting  
Relay Ratings: 3 amps at 24 VDC or 120 VAC  
Form C providing NO (normally open) or NC  
(normally closed) option  
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 Installation  
A
Locating the Manning GM-1  
Figure 1: Mounting dimensions for the Manning GM-1  
Gas Monitoring Alarm System  
When unpacking the unit, inspect all boxes and  
contents for shipping damage. If any screws or  
other metal parts are missing, these must be found  
to ensure that the printed circuit boards will not be  
damaged when power is applied.  
6"  
5/16"  
The control unit is designed to be mounted on a  
solid (non-vibrating) wall through four holes in the  
two mounting flanges. While the physical location  
must be determined in part by local conditions, it is  
important to consider the following:  
Gas Monitor  
CAUTION  
Manning GM-1  
Protect the Manning GM-1 from rain, snow,  
water sprays, cleaning crews, and physical  
damage.  
10 3/4"  
Reset  
Silence  
Mount the unit on a solid wall (non-  
vibrating) at eye level for convenience in  
taking readings, servicing, etc.  
The Manning GM-1 is NOT explosion proof.  
DO NOT MOUNT in a hazardous  
atmosphere.  
Operating temperature for the Manning  
GM-1 is 0o F to +120o F.  
Pre-punched holes are provided in the  
bottom of the enclosure for cable access.  
DO NOT drill holes in the top of the cabinet  
as this will void the warranty.  
If hole drilling is required, be sure to remove  
all metal filings.  
Mounting dimensions are included in Figure 1.  
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2 Installation  
continued  
B Wiring  
Relay Wiring:  
All three relays have Form C, dry contacts. Any  
required power source must be within the 3 amp  
rating and fused or current limited to keep from  
damaging the contacts.  
Electrical wiring must comply with all applicable  
codes. Plant equipment that may be involved and  
operating conditions should be discussed with local  
operating personnel to determine if any special  
needs should be taken into account.  
Relay wiring must be run in separate conduit  
from the sensor cable if the relay circuit is AC.  
Nearly all start-up problems are due to improper  
wiring or monitor configuration. Please follow these  
guidelines carefully. Figure 2 presents a wiring  
diagram for the Manning GM-1.  
Sensor Wiring:  
See sensor manual for proper sensor cable.  
See sensor manual for proper sensor location.  
AC Power Wiring:  
Never run AC circuits in the same conduit as  
the sensor cable.  
Use only stranded cable for AC power,  
relay outputs, and sensor input cables.  
Note: Relays are energized in a non-alarmed  
condition so that a power loss in the Manning GM-  
1 will result in an alarm.  
The units must have a proper third wire  
ground for safety and sensor shielding.  
Be sure to follow local codes.  
All AC cables must be kept away from the  
incoming sensor cables, i.e., do not put AC  
cables inside conduit containing sensor  
cables.  
Keep all wiring away from variable speed  
drives and SCR control units to minimize  
electrical noise exposure.  
Electrical Power: 120 VAC, 50/60 Hz, 0.35  
amps.  
Electrical power ground: The unit must be  
properly grounded.  
Risk of electric shock.  
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 Installation  
continued  
Figure 2: Wiring diagram for the Manning GM-1 Gas Monitoring Alarm System  
WARNING  
ADJUST  
ALARM  
ADJUST  
TP  
TP  
GND  
+20V  
BOT TOP  
7
TP  
WARNING  
TP  
ALARM  
TP  
SIG  
WARNING  
RELAY  
ALARM  
RELAY  
FAULT  
RELAY  
1
6
C11  
+
+
+
FUSE RATING  
250V 1.0 AMP  
+
SHLD GND  
24  
SIG  
L
N
NO  
C
NC  
NO  
C
NC  
NO  
C
NC  
120 VAC  
WARNING  
RELAY*  
ALARM  
RELAY*  
FAULT  
RELAY*  
MODEL G/M  
MAINBOARD REV D  
*Relay rating 3 amp. User must fuse to protect.  
Note: Green wire earth ground must be connected to grounding  
stud marked  
Bare wrap— to "SHLD" terminal of sensor  
Black— to "GND" terminal of sensor  
Red— to "+24" terminal of sensor  
White— to "SIG" terminal of sensor  
Risk of electrical shock.  
Potential hazard.  
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
3 Operation  
A Display Panel  
C DIP Switch Setting  
A 20-segment Bargraph Display indicates the gas  
concentration level. The bottom LED is always lit to  
indicate power to the display.  
The two position DIP switch in the center of the bottom  
board controls the latching of the alarm light and alarm  
relay. Switch 1 (left) controls the alarm relay. Switch 2  
(right) controls the alarm light. Putting the switch in the  
on (up) position will latch the corresponding function.  
Putting the switch in the off (down) position will cause  
the corresponding function to be not latched (see  
Figure 3).  
The Warning LED indicates the warning level as  
determined by the warning setpoint has been  
exceeded. The Warning LED and Warning Relay  
operate together and never latch.  
The Alarm LED indicates the alarm level as  
determined by the alarm setpoint has been  
exceeded. The Alarm LED and Alarm Relay are  
independently latchable or non-latchable as  
determined by the DIP switch on the main board.  
Standard factory settings are to latch the LED and  
not latch the relay.  
This allows the alarm condition to remain activated if  
desired even if the gas concentration goes back to  
below the setpoint.  
Figure 3: Warning adjustment and DIP switch settings  
The Power LED indicates power to the monitoring  
unit. This LED will flash during the one minute  
power up delay indicating that all relays are held in  
the normal condition to allow for sensor stabilization  
during power up.  
The Fault LED indicates a signal input of less than  
1.4 mA (0.14 volts) at TP Sig. The Fault LED and  
Fault Relay always latch.  
WARNING  
ADJUST  
ALARM  
ADJUST  
SW1  
1
2
TP  
GND  
TP  
+20V  
BOT TOP  
7
TP  
WARNING  
TP  
ALARM  
TP  
SIG  
AA  
WARNING  
RELAY  
ALARM  
RELAY  
FAULT  
RELAY  
B
Reset and Silence Switches  
Pushing the Reset switch will reset the fault light,  
fault relay, alarm light, and alarm relay. If either  
condition still exists, the appropriate light and relay  
will return to its tripped state after a time delay.  
1
6
C11  
+
+
+
FUSE RATING  
250V 1.0 AMP  
+
SHLD GND  
24  
SIG  
L
N
NO  
C
NC  
NO  
C
NC  
NO  
C
NC  
120 VAC  
WARNING  
RELAY*  
ALARM  
RELAY*  
FAULT  
RELAY*  
Pushing the Silence switch will silence the horn on  
the bottom of the Manning GM-1 until the next event  
occurs. The horn is triggered by a fault or an alarm  
condition. The horn will clear itself if the alarm and  
fault relay clear. A warning condition does not  
trigger the horn.  
MODEL G/M  
MAINBOARD REV  
D
Warning adjust pot  
0.4 - 2.0 V  
VDC  
DIP switches on  
bottom of board  
Do Not Adjust!  
Factory set pots  
Black  
Red  
-
+
Risk of electrical shock.  
Potential hazard.  
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3 Operation  
continued  
D Signal and Setpoints  
F Troubleshooting  
The voltage between TP Gnd and TP Sig indicates  
the current signal received from the sensor. The  
normal range is 0.4 volts to 2.0 volts, which  
The Fault Light and Fault Relay always latch when a  
fault condition is detected. After the condition is  
corrected the Reset switch must be pressed to clear  
the Fault Light and Fault relay.  
corresponds with 4/20 mA. This manual will use the  
voltage at TP Sig to describe the input signal. When  
this signal exceeds the voltage at TP Warning or TP  
Alarm, the warning or alarm function will take place.  
The warning setpoint is user adjustable by looking at  
the voltage on TP Warning and adjusting the warning  
adjust pot until the desired setpoint is reached (see  
Figure 3). The alarm adjust pot and TP Alarm function  
the same way.  
The unit will indicate a fault if the signal is less than  
0.14 volts at TP Sig.  
Some Manning sensors are configured to send a  
signal of 0.05 volts at TP Sig if a sensor fault exists. If  
TP Sig = 0.05 volts, this indicates a properly wired  
sensor is in a fault condition. Proceed to investigate  
the sensor.  
If TP Sig = 0.00 volts, this indicates no signal from the  
sensor. Check for correct wiring or loose connections  
between the sensor and monitoring unit.  
The warning and alarm setpoints are factory adjusted  
as indicated on the data sheet included with your  
GM-1. Never adjust these setpoints outside the range  
of 0.4 to 2.0 volts. Contact Honeywell Analytics if you  
have any questions or want help in determining  
setpoints for your particular sensor and application.  
Each relay has a green LED in series with its coil. If  
this LED is on, this indicates that the relay is  
energized and contacts will be in the normal position.  
If this LED is off, the contacts will be in the tripped  
condition.  
After setpoint adjustment always expose sensor to  
the gas being monitored and verify that the warning  
and alarm lights trigger at the desired concentration  
as displayed by the bargraph.  
Power supply voltages should be checked at  
TP +20V on the display board and at +24 on  
the sensor input terminal block (see Figure 4).  
Both points should be DC Volts as labeled.  
E Start-Up Procedures  
Before applying power, make a final check of all  
wiring for continuity, shorts, grounds, etc. It is usually  
best to disconnect external alarms and other  
equipment from the unit until the initial start-up  
procedures are completed.  
The total sensor current draw can be checked by  
looking at the voltage between the two TP Current  
Draw test points. 1.0mV corresponds to 10 mA, and  
50.0mV corresponds to 500mA, etc. Compare this  
reading with the current draw expected for the  
sensor you are using (see appropriate sensor  
manual).  
After power-up, allow 24 hours for the system to  
stabilize before testing the sensor. Because sensors  
are normally located at a distance from the  
monitoring unit, the test time required and accuracy  
of the response checks will be improved if two  
people perform the start-up procedures and use  
radio contact.  
If questions arise, call Honeywell Analytics.  
Start-Up Test: One person exposes the sensor to a  
small amount of the gas that is being monitored. The  
second person stays at the monitoring unit to  
determine that the sensor, when exposed to the  
target gas, is connected to the proper input,  
responds, and causes appropriate alarm functions.  
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3 Operation  
continued  
G Maintenance  
H Replacement Parts  
The Manning GM-1 is designed for long life and high  
reliability. Honeywell Analytics recommends  
For replacement parts, contact Honeywell Analytics.  
Be sure to give serial number and model number of  
unit.  
checking signal voltages monthly and logging them  
on the data sheet included with your Manning GM-1.  
Additionally, the sensor being monitored should be  
exposed to the target gas on a monthly basis while  
all alarm functions are verified at the Manning GM-1.  
This will test the sensor and any equipment con-  
nected to the relays in addition to the Manning GM-1.  
Figure 4: Troubleshooting the Manning GM-1 Gas Monitoring Alarm System  
Display power  
supply voltage  
Sensor current draw  
(1mV per 10 mA)  
SENSOR DEPENDENT  
+20V  
VDC  
mVDC  
Black  
Red  
Black  
Red  
+
-
+
-
WARNING  
ADJUST  
ALARM  
ADJUST  
TP  
GND  
TP  
+20V  
BOT TOP  
7
TP  
WARNING  
TP  
ALARM  
TP  
SIG  
WARNING  
RELAY  
ALARM  
RELAY  
FAULT  
RELAY  
0.4 - 2.0 V  
+24V  
VDC  
VDC  
AC fuse  
1
6
C11  
+
+
+
FUSE RATING  
250V 1.0 AMP  
+
SHLD GND  
24  
SIG  
Black  
Red  
Black  
Red  
+
-
+
-
L
N
NO  
C
NC  
NO  
C
NC  
NO  
C
NC  
120 VAC  
WARNING  
RELAY*  
ALARM  
RELAY*  
FAULT  
RELAY*  
MODEL G/M  
MAINBOARD REV  
D
Signal from sensor  
Power supply  
voltage to sensor  
Risk of electrical shock.  
Potential hazard.  
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 Limited Warranty  
1.  
Limited Warranty  
3.  
Warranty Limitation and Exclusion  
Honeywell Analytics, Inc. warrants to the  
original purchaser and/or ultimate customer  
(“Purchaser”) of Manning products (“Product”)  
that if any part thereof proves to be defective in  
material or workmanship within eighteen (18)  
months of the date of shipment by Honeywell  
Analytics or twelve (12) months from the date of  
first use by the purchaser, whichever comes  
first, such defective part will be repaired or  
replaced, free of charge, at Honeywell Analytics’  
discretion if shipped prepaid to Honeywell  
Analytics at 405 Barclay Blvd., Lincolnshire, IL  
60069, in a package equal to or in the original  
container. The Product will be returned freight  
prepaid and repaired or replaced if it is  
determined by Honeywell Analytics that the  
part failed due to defective materials or  
workmanship. The repair or replacement of any  
such defective part shall be Honeywell  
Honeywell Analytics will have no further  
obligation under this limited warranty. All  
warranty obligations of Honeywell Analytics are  
extinguishable if the Product has been subject  
to abuse, misuse, negligence, or accident or if  
the Purchaser fails to perform any of the duties  
set forth in this limited warranty or if the Product  
has not been operated in accordance with  
instructions, or if the Product serial number has  
been removed or altered.  
4.  
Disclaimer of Unstated Warranties  
THE WARRANTY PRINTED ABOVE IS THE  
ONLY WARRANTY APPLICABLE TO THIS  
PURCHASE. ALL OTHER WARRANTIES,  
EXPRESS OR IMPLIED, INCLUDING, BUT NOT  
LIMITED TO, THE IMPLIED WARRANTIES OF  
MERCHANTABILITY OR FITNESS FOR A  
PARTICULAR PURPOSE ARE HEREBY  
DISCLAIMED.  
Analytics’ sole and exclusive responsibility and  
liability under this limited warranty.  
5.  
Limitation of Liability  
2.  
Exclusions  
IT IS UNDERSTOOD AND AGREED THAT  
HONEYWELL ANALYTIC’S LIABILITY,  
A. If gas sensors are part of the Product, the  
gas sensor is covered by a twelve (12)  
month limited warranty of the manufacturer.  
WHETHER IN CONTRACT, IN TORT, UNDER  
ANY WARRANTY, IN NEGLIGENCE OR  
OTHERWISE SHALL NOT EXCEED THE  
AMOUNT OF THE PURCHASE PRICE PAID BY  
THE PURCHASER FOR THE PRODUCT AND  
UNDER NO CIRCUMSTANCES SHALL  
HONEYWELL ANALYTICS BE LIABLE FOR  
SPECIAL, INDIRECT, OR CONSEQUENTIAL  
DAMAGES. THE PRICE STATED FOR THE  
PRODUCT IS A CONSIDERATION LIMITING  
HONEYWELL ANALYTICS’ LIABILITY. NO  
ACTION, REGARDLESS OF FORM, ARISING  
OUT OF THE TRANSACTIONS UNDER THIS  
WARRANTY MAY BE BROUGHT BY THE  
PURCHASER MORE THAN ONE YEAR AFTER  
THE CAUSE OF ACTIONS HAS OCCURRED.  
B. If gas sensors are covered by this limited  
warranty, the gas sensor is subject to  
inspection by Honeywell Analytics for  
extended exposure to excessive gas con-  
centrations if a claim by the Purchaser is  
made under this limited warranty. Should  
such inspection indicate that the gas sensor  
has been expended rather than failed  
prematurely, this limited warranty shall not  
apply to the Product.  
C. This limited warranty does not cover consum-  
able items, such as batteries, or items  
subject to wear or periodic replacement,  
including lamps, fuses, valves, vanes, sensor  
elements, cartridges, or filter elements.  
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 

Graco Stroller 1762856 User Manual
Grandstream Networks Security Camera GXV3504 User Manual
Harbor Freight Tools Grinder 91174 User Manual
Harbor Freight Tools Tool Storage 94582 User Manual
Honeywell Crib Toy MKXXII User Manual
Honeywell Personal Computer Thor VX8 User Manual
HP Hewlett Packard Laptop xe310 User Manual
HP Hewlett Packard Server RP4410 User Manual
HSM Electronic Keyboard HSM 4112 User Manual
IBM Computer Monitor C220p User Manual