TECHNICAL MANUAL
GPH 13 M Series Multi Position
Package Heat Pump Units
with R410A
•
•
•
•
Refer to Service Manual RS6300008 for installation, operation, and troubleshooting information.
All safety information must be followed as provided in the Service Manual.
Refer to the appropriate Parts Catalog for part number information.
Models listed on page 3.
This manual is to be used by qualified, professionally trained HVAC technicians only.
Goodman does not assume any responsibility for property damage or personal injury due to
improper service procedures or services performed by an unqualified person.
RT6332013r1
November2010
Copyright © 2010 Goodman Manufacturing Company, L.P.
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT IDENTIFICATION
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please
use these numbers when requesting service or parts information.
GPH1324M41AB
GPH1330M41AB
GPH1336M41AB
GPH1342M41AB
GPH1348M41AB
GPH1360M41AB
The United States Environmental Protection Agency (“EPA”) has issued various regulations re-
garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
WARNING
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.
Do not connect or use any device
To prevent the risk of property
WARNING
WARNING
that is not design certified by
Goodman for use with this unit.
damage, personal injury, or death,
do not store combustible materials or use gasoline or
other flammable liquids or vapors in the vicinity of this
appliance.
Serious property damage, personal injury, reduced unit
performance and/or hazardous conditions may result
from the use of such non-approved devices.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT DESIGN
GPH13 (M Series) Package Units are designed for outdoor
installations only in either residential or light commercial ap-
plications and are available in 2, 2.5, 3, 3.5, 4 & 5 ton sizes.
Air for condensing (cooling cycle) or evaporation (heating
cycle) is drawn through the outdoor coil by a propeller fan,
and is discharged vertically out the top of the unit. The out-
They are designed for 208/230 volt single phase applications. door coil is designed for .0 static. No additional restriction
(ductwork) shall be applied.
The connecting ductwork (Supply and Return) can be con-
Conditioned air is drawn through the filter(s), field installed,
across the coil and back into the conditioned space by the
indoor blower.
nected for either horizontal or vertical airflow. In the vertical
application, a matching Roof Curb is recommended and a
horizontal duct cover kit is required.
Package Heat Pump indoor sections are designed to accept
optional components such as auxiliary electric heaters and
circuit breakers. Provisions for these components have been
made at time of manufacture.
A return air filter must be installed behind the return air grille(s)
or provision must be made for a filter in an accessible loca-
tion within the return air duct. The minimum filter area should
not be less than those sizes listed in the Specification Sec-
tion. Under no circumstances should the unit be operated
without return air filters.
GPH13 series package units use the Compliant Scroll com-
pressor; there are a number of design characteristics which
are different from the traditional reciprocating compressor.
A 3/4" pipe is provided for removal of condensate water from
the indoor coil. A trap must be provided to have proper con-
densate drainage. (Do not reduce the drain line size).
- Due to their design Scroll compressors are inherently more
tolerant of liquid refrigerant. NOTE: Even though the com-
pressor section of a Scroll compressor is more tolerant of
liquid refrigerant, continued flood back or flooded start condi-
Refrigerant flow control is achieved by use of restrictor ori-
fices.
All heat pump models also have a suction line accumulator tions may wash oil from the bearing surfaces causing prema-
installed between the reversing valve and the compressor.
The object of the accumulator is to:
ture bearing failure.
- These Scroll compressors use "POE" or polyolester oil which
is NOT compatible with mineral oil based lubricants like 3GS.
"POE" oil must be used if additional oil is required.
1. Provide a liquid refrigerant storage vessel during prolonged
system off cycles.
2. Store excess liquid refrigerant not needed by the system
while running.
- Compliant scroll compressors perform “quiet” shutdowns
that allow the compressor to restart immediately without the
need for a time delay. This compressor will restart even if the
system has not equalized.
3. Return oil and saturated vapor to the compressor at a
controlled rate.
4. Retain stored excess refrigerant during a sudden system
pressure fluctuation such as seen in defrost cycles.
- Operating pressures and amp draws may differ from stan-
dard reciprocating compressors. This information may be
found in the “Cooling Performance Data” section.
Refrigerant flow control is achieved by use of restrictor
orifices. These models use the FasTest Access Fitting
System, with a saddle that is either soldered to the suction
andliquidlinesorisfastenedwithalockingnuttotheaccess
fitting box (core) and then screwed into the saddle. Do not
remove the core from the saddle until the refrigerant
charge has been removed. Failure to do so could result
in property damage or personal injury.
LocationandClearances
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
The single phase units use permanent split capacitor (PSC)
design compressors. Starting components are not required
for these units. A low microfarad run capacitor assists the
compressor to start and remains in the circuit during opera-
tion.
The outdoor fan motors are single phase capacitor type mo-
tors. Some models use PSC type indoor blower motors while
others use EEM type blower motors. EEM motors are ener-
gized by a 24V signal from the thermostat and are constant
torque motors with very low power consumption.
The EEM features an integral control module.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT DESIGN
In installations where the unit is installed above ground level
and not serviceable from the ground (Example: roof top in-
stallations) the installer must provide service platform for ser-
vice person with rails or guards in accordance with local codes
or ordinances, or, in their absence, with the latest edition of
the Uniform Mechanical Code Section 305.
NOTE: Unit can also use roof curb (and platform for leveling,
where necessary) to utilize bottom discharge.
WARNING
TO PREVENT POSSIBLE PROPERTY DAMAGE, THE
UNIT SHOULD REMAIN IN AN UPRIGHT POSITION
DURING ALL RIGGING AND MOVING OPERATIONS.
TO FACILITATE LIFTING AND MOVING IF A CRANE IS
USED, PLACE THE UNIT IN AN ADEQUATE CABLE
SLING.
OutsideSlabInstallation-Multi-positional(M)
IMPORTANT: If using bottom discharge with roof curb,
ductwork should be attached to the curb prior to installing
the unit.
NOTE: Roof overhang should be no more than 36" and provi-
sions made to deflect the warm discharge air out from the
overhang.
NOTE: Single phase models require installation of horizontal
duct kit #20464501PDGK (medium chassis) and
#20464502PDGK (large chassis) when using bottom dis-
charge.
Minimum clearances are required to avoid air recirculation
and keep the unit operating at peak efficiency.
Refer to Roof curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with the
National Roofing Contractors Association Manual.
Roof Curb
Rooftop Installation - -Multi-positional (M)
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT DESIGN
GPH13[24-60]M41*
HKR ELECTRICAL DATA
Circuit #1
Circuit #2
Maximum
Overcurrent
Protection (amps)
at 208 / 240V
Maximum
Actual
kW & BTU
at 240V
Minimum Circuit
Ampacity
at 208 / 240V
Minimum Circuit
Ampacity
at 208 / 240V
Overcurrent
Protection (amps)
at 208 / 240V
GPH1324M41*
HKR05A,CA
HKR08A,CA
HKR10A,CA
24 / 27
33 / 28
45 / 51
30 / 30
40 / 40
60 / 60
----
----
----
----
----
----
4.75 / 16,200
7.00 / 23,800
9.50 / 32,400
GPH1330M41*
HKR05A,CA
24 / 27
34 / 39
45 / 52
45 / 52
30 / 30
40 / 40
60 / 60
60 / 60
--
--
--
--
4.75 / 16,200
7.0 / 23,800
9.5 / 32,400
14.25 / 48,600
HKR08A,CA
HKR10A,CA
HKR15A,CA
GPH1336M41*
HKR05A,CA
HKR08A,CA
HKR10A,CA
HKR15A,CA
GPH1342M41*
HKR05A,CA
HKR08A,CA
HKR10A,CA
HKR15A,CA
GPH1348M41*
HKR05A,CA
HKR08A,CA
HKR10A,CA
HKR15A,CA
HKR20A,CA
GPH1360M41*
HKR05A,CA
HKR08A,CA
HKR10A,CA
HKR15A,CA
HKR20A,CA
--
--
22 / 25
30 / 30
24 / 27
34 / 39
30 / 30
40 / 40
----
----
----
----
4.75 / 16,200
7.00 / 23,800
45 / 52
45 / 52
60 / 60
60 / 60
----
22 / 25
----
30 / 30
9.50 / 32,400
14.25 / 48,600
24 / 27
34 / 39
45 / 52
45 / 52
30 / 30
40 / 40
60 / 60
60 / 60
--
--
--
--
4.75 / 16,200
7.0 / 23,800
9.5 / 32,400
14.25 / 48,600
--
--
22 / 25
30 / 30
25 / 28
34 / 40
46 / 53
30 / 30
40 / 40
60 / 60
----
----
----
----
----
----
4.75 / 16,200
7.00 / 23,800
9.50 / 32,400
46 / 52
46 / 52
60 / 60
60 / 60
22 / 25
43 / 49
30 / 30
60 / 60
14.25 / 48,600
19.50 / 66,500
26 / 30
36 / 40
48 / 54
48 / 54
48 / 54
30 / 30
40 / 40
60 / 60
60 / 60
60 / 60
----
----
----
----
4.75 / 16,200
7.00 / 23,800
9.50 / 32,400
14.25 / 48,600
19.50 / 66,500
----
----
22 / 25
43 / 49
30 / 30
60 / 60
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.
Heating kW Correction Factor
Supply Votage
240
1.0
230
220
210
208
Correction Factor
0.93
0.85
0.78
0.76
Multiply rated kW by correction factor to get actual kW
All wires and overcurrent protection devices are sized for use with electric heaters only and without
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See
PACKAGE UNIT SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent pro-
tection during refrigeration cycle.
WARNING
6
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT DIMENSIONS
GPH13[24-60]M41*
47
51
POWER
WIRE
ENTRANCE
A
16
4 1/8
2 1/8
1 3/8
5 ½
16
6 ½
8
B
2 34
RETURN
B
SUCTION/LIQUID
PRESSURE PORT
SUPPLY
3
CONDENSATE
DRAIN
CONNECTION
3/4” NPT FEMALE
CONTROL
WIRE
ENTRANCE
18 7/8
BLOWER
ACCESS PANEL
MEDIUM CHASSIS
GPH1324M41*
GPH1330M41*
GPH1336M41*
GPH1342M41*
LARGE CHASSIS
GPH1348M41*
GPH1360M41*
7
Download from Www.Somanuals.com. All Manuals Search And Download.
PACKAGE HEAT PUMP SPECIFICATIONS GPH13[24-36]M41AB
GPH1324M41*
GPH1330M41*
GPH1336M41*
COOLING
CAPACITY
HEATING
RATING
COOLING CAPACITY, BTUH
SEER / EER
24,000
13/11
23000
12600
7.7
29,000
13/10.8
28800
17000
7.7
34600
13/10.9
34200
19000
7.7
BTU/h (47°)
BTU/h (17°)
HSPF
VOLTAGE (NAMEPLATE)
AMPS
208/230-60-1
15.8
208/230-60-1
19.0
208/230-60-1
21.3
UNIT
ELECTRICAL
SPECIFICATION
MIN CIRCUIT AMPACITY
19.0
23.0
25.4
MAX OVERCURRENT PROTECTION(1 )
TYPE
30
35
40
SCROLL
12.8
SCROLL
16.0
SCROLL
16.7
COMPRESSOR
RATED LOAD AMPS
LOCKED ROTOR AMPS
HORSEPOWER
58.3
77
79
1/4
1/4
1/4
CONDENSER
FAN MOTOR
RPM
830
830
830
FULL LOAD AMPS
LOCKED ROTOR AMPS
1.5
1.5
1.5
3
3
3
BLADE DIAMETER (INCHES)
NUMBER OF BLADES
CONDENSER FAN
22/3
22/3
22/4
CONDENSER
COIL
FACE AREA (SQ. FT.)
17.02
1
17.02
1
16.83
1
NUMBER OF ROWS
FINS PER INCH
24
24
22
HORSEPOWER - NUMBER OF SPEEDS
FULL LOAD AMPS
1/4 - 3
1.5
1/3 - 3
1.5
1/3 - 3
3.06
4.1
EVAPORATOR
BLOWER
LOCKED ROTOR AMPS
MOTOR SPEED TAP - COOLING X-13
RPM
2.13
High
952
3.2
MOTOR
High
869
High
910
DIAMETER X WIDTH (INCHES)
RATED SCFM COOLING
MAX EXTERNAL STATIC PRESS ("w.c.)
FACE AREA (SQ. FT.)
10 x 9
825
10 x 9
1050
0.5
10 x 9
1150
0.5
EVAPORATOR
BLOWER
0.5
EVAPORATOR
COIL
4.52
4.52
4
4.52
4
NUMBER OF ROWS
4
FINS PER INCH
16
16
14
GENERAL
FILTER SIZE *
25 x 25 x 1
3/4"
25 x 25 x 1
3/4"
25 x 25 x 1
3/4"
DRAIN SIZE (INCHES)
INFORM ATION
EXPANSION DEVICE (ID/OD)
REFRIGERANT CHARGE R410A (OZS.)
0.057/0.045
110
0.070/0.055
115
0.071/0.057
135
POWER SUPPLY
CONDUIT KNOCKOUT SIZE (INCHES)
3/4, 1, 1-1/4
1/2
3/4, 1, 1-1/4
1/2
3/4, 1, 1-1/4
1/2
LOW VOLTAGE
CONDUIT KNOCKOUT SIZE (INCHES)
LO PRESSURE SWITCH
OPENS / CLOSES PSIG
22 / 50
22 / 50
22 / 50
HI PRESSURE SWITCH - OPENS PSIG
OPENS / CLOSES PSIG
660 / 420
405
660 / 420
410
660 / 420
435
SHIPPING WEIGHT (LBS.)
OPERATING WEIGHT (LBS.)
395
400
425
(1)
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
PACKAGE HEAT PUMP SPECIFICATIONS
GPH13[42-60]M41AB
GPH1342M41*
GPH1348M41*
GPH1360M41*
COOLING
CAPACITY
HEATING
RATING
COOLING CAPACITY, BTUH
SEER / EER
40000
13/11
40000
21000
7.7
46500
13/11
45500
26000
8.0
56000
13/10.9
55500
31200
8.0
BTU/h (47°)
BTU/h (17°)
HSPF
VOLTAGE (NAMEPLATE)
AMPS
208/230-60-1
22.4
208/230-60-1
29.0
208/230-60-1
35.4
UNIT
ELECTRICAL
SPECIFICATION
MIN CIRCUIT AMPACITY
26.8
34.5
42.0
MAX OVERCURRENT PROTECTION(1)
TYPE
40
50
60
SCROLL
17.9
SCROLL
21.8
SCROLL
26.4
COMPRESSOR
RATED LOAD AMPS
LOCKED ROTOR AMPS
HORSEPOWER
112
117
134
1/4
1/4
1/4
CONDENSER
FAN MOTOR
RPM
1075
1.4
1075
1.4
1075
FULL LOAD AMPS
LOCKED ROTOR AMPS
1.4
2.9
2.9
2.9
BLADE DIAMETER (INCHES)
NUMBER OF BLADES
CONDENSER FAN
22/3
22/3
22/3
CONDENSER
COIL
FACE AREA (SQ. FT.)
16.83
2
19.24
21.04
NUMBER OF ROWS
2
16
2
16
FINS PER INCH
16
HORSEPOWER - NUMBER OF SPEEDS
FULL LOAD AMPS
1/3 - 3
3.06
3/4 - 5
5.8
1 - 5
7.6
EVAPORATOR
BLOWER
LOCKED ROTOR AMPS
MOTOR SPEED TAP - COOLING X-13
RPM
4.1
---
---
MOTOR
High
910
T2/T3
1050
10 x 9
1720
0.5
T2/T3
1050
10 x 9
1800
0.5
DIAMETER X WIDTH (INCHES)
RATED SCFM COOLING
MAX EXTERNAL STATIC PRESS ("w.c.)
FACE AREA (SQ. FT.)
10 x 9
1300
0.5
EVAPORATOR
BLOWER
EVAPORATOR
COIL
4.52
6.17
6.17
NUMBER OF ROWS
4
4
4
FINS PER INCH
14
14
14
GENERAL
FILTER SIZE *
25 x 25 x 1
3/4"
(2) 20 x 20 x 1
3/4"
(2) 20 x 20 x 1
3/4"
DRAIN SIZE (INCHES)
INFORM ATION
EXPANSION DEVICE (ID/OD)
REFRIGERANT CHARGE R410A (OZS.)
0.072/0.063
180
0.080/0.065
190
0.084/0.076
220
POWER SUPPLY
CONDUIT KNOCKOUT SIZE (INCHES)
3/4, 1, 1-1/4
1/2
3/4, 1, 1-1/4
1/2
3/4, 1, 1-1/4
1/2
LOW VOLTAGE
CONDUIT KNOCKOUT SIZE (INCHES)
LO PRESSURE SWITCH
OPENS / CLOSES PSIG
22 / 50
22 / 50
22 / 50
HI PRESSURE SWITCH - OPENS PSIG
OPENS / CLOSES PSIG
660 / 420
440
660 / 420
520
660 / 420
533
SHIPPING WEIGHT (LBS.)
OPERATING WEIGHT (LBS.)
430
510
523
(1)
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
ACCESSORIES
GPH13[24-60]M41*
ACCESSORIES - GPC/GPH****M MODELS
Description
Part Number
OT18-60A
Outdoor Thermostat Kit w/Lockout Stat
Emergency Heat Relay Kit
OT/EHR18-60
HKR
Electric Heat Kit
PGC101/102/103
PEHH101/102
PEHH103
Roof Curb
Horizontal Economizer For Heat Pump, Small and Medium Chassis
Horizontal Economizer For Heat Pump, Large Chassis
Horizontal Economizer For A/C, Small and Medium Chassis
Horizontal Economizer For A/C, Large Chassis
PEHC101/102
PEHC103
PGMDD101/102
PGMDD103
Manual 25% Fresh Air Damper Downflow Application, Small and Medium Chassis
Manual 25% Fresh Air Damper Downflow Application, Large Chassis
Manual 25% Fresh Air Damper Horizontal Application, Medium Chassis
Manual 25% Fresh Air Damper Horizontal Application, Large Chassis
Motorized 25% Fresh Air Damper Downflow Application,Small and Medium Chassis
Motorized 25% Fresh Air Downflow Application, Large Chassis
Motorized 25% Fresh Air Damper Horizontal Application, Medium Chassis
Motorized 25% Fresh Air Damper Horizontal Application, Large Chassis
Downflow Economizer For A/C, Medium Chassis
PGMDH102
PGMDH103
PGMDMD101/102
PGMDMD103
PGMDMH102
PGMDMH103
GPC13MED102
GPC13MED103
GPH13MED102
GPH13MED103
GPH13MFR102
GPH13MFR103
GPGHFR101-103
SQRPG101/102
SQRPG103
Downflow Economizer For A/C, Large Chassis
Downflow Economizer For Heat Pump, Medium Chassis
Downflow Economizer For Heat Pump, Large Chassis
Internal Filter Rack, Medium Chassis
Internal Filter Rack, Large Chassis
External Horizontal Filter Rack for Goodman/Amana Gas/Electric and Multi-position Package Units All Chassis
Square to Round Adapter w/ 16" Round Downflow Application, Medium Chassis
Square to Round Adapter w/ 18" Round Downflow Application, Large Chassis
Square to Round Adapter w/ 16" Round Horizontal Application, Medium Chassis
Square to Round Adapter w/ 18" Round Horizontal Application, Large Chassis
Flush Mount Concentric Duct Kit
SQRPGH101/102
SQRPGH103
CDK36
CDK36515
Flush Mount Concentric Duct Kit w/ Filter
CDK36530
Step Down Concentric Duct Kit
CDK36535
Step Down Concentric Duct Kit w/ Filter
CDK4872
Flush Mount Concentric Duct Kit
CDK4872515
CDK4872530
CDK4872535
Flush Mount Concentric Duct Kit w/ Filter
Step Down Concentric Duct Kit
Step Down Concentric Duct Kit w/ Filter
NOTE: Complete lineup of thermostats can be found in the Thermostat Specification Sheets.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
GPH13[24-60]M41*
BLOWER PERFORMANCE DATA
Dry Coil Data
E.S.P (In. of H2O)
0.4 0.5
Model
Speed
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Volts
CFM
0.1
0.2
0.3
0.6
0.7
0.8
667
153
596
150
-------- -------- -------- -------- -------- --------
-------- -------- -------- -------- -------- --------
230
230
230
230
230
230
230
230
230
230
230
230
WATTS
CFM
897
841
784
224
713
217
610
207
982
333
901
305
1033
356
1194
446
915
300
1119
399
1230
477
915
300
1119
399
1230
477
-------- -------- --------
-------- -------- --------
WATTS
CFM
233
229
1242
373
1181
364
1122
354
1057
344
883
318
818
290
952
342
1106
427
804
283
1041
382
1144
461
804
283
1041
382
1144
461
719
298
648
271
777
313
1008
410
687
264
935
363
1055
442
687
264
935
363
1055
442
617
284
562
257
670
297
864
382
558
250
748
330
939
420
558
250
748
330
939
WATTS
CFM
1097
337
1059
330
1016
324
959
WATTS
CFM
315
1253
397
1204
388
1148
379
1097
369
WATTS
CFM
1448
499
1380
483
1323
472
1258
459
WATTS
CFM
1122
338
1078
330
1032
321
972
WATTS
CFM
310
1387
456
1331
440
1264
428
1209
412
WATTS
CFM
1521
534
1454
521
1388
510
1311
490
WATTS
CFM
1122
338
1078
330
1032
321
972
WATTS
CFM
310
1387
456
1331
440
1264
428
1209
412
WATTS
CFM
1521
534
1454
521
1388
510
1311
490
WATTS
CFM
420
1,130
1,440 1,395 1,360 1,310 1,265 1,235 1,190
275 285 295 315 325 335 345
1,795 1,765 1,715 1,695 1,650 1,600 1,500
475 490 505 520 530 535 510
1,860 1,820 1,785 1,745 1,700 1,625 1,515
515 530 545 565 570 550 535
1,755 1,720 1,685 1,645 1,615 1,570 1,530
420 435 455 460 475 490 500
1,850 1,820 1,775 1,735 1,705 1,675 1,610
480 500 515 525 535 555 545
2,180 2,125 2,050 1,975 1,875 1,800 1,655
770 755 725 700 675 640 575
T1 (G) 230
355
1,375
475
WATTS
CFM
T2 / T3
230
(W2)
WATTS
CFM
1,395
485
T4 / T5
230
(Y)
WATTS
CFM
1,465
500
T1 (G) 230
WATTS
CFM
1,495
520
T2 / T3
230
W2
WATTS
CFM
1,530
540
T4 / T5
230
Y
WATTS
NOTES:
•
Data shown is Dry Coil. Wet Coil Pressure Drop is approximate. 0.1" H2O, for 2 row indoor coil; 0.2” H2O, for 3 row indoor
coil; and 0.3” H2O, for 4 row indoor coil.
•
•
•
Data shown does not include filter pressure drop, approx. 0.08” H2O.
ALL MODELS SHOULD RUN NO LESS THAN 350 CFM / TON.
Reduce airflow by 2% for 208V operation.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
BLOWER PERFORMANCE DATA
S E R E I R U
M P T E E R A T
12
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPH1324M41*
13
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPH1324M41*
14
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPH1330M41*
15
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPH1330M41*
16
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPH1336M41*
17
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPH1336M41*
18
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPH1342M41*
19
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPH1342M41*
20
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPH1348M41*
21
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPH1348M41*
22
Download from Www.Somanuals.com. All Manuals Search And Download.
GPH1360M41*
COOLING PERFORMANCE DATA
23
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING PERFORMANCE DATA
GPH1360M41*
24
Download from Www.Somanuals.com. All Manuals Search And Download.
HEATING PERFORMANCE DATA
GPH13[24-42]M41*
EXPANDED PERFORMANCE DATA
MODEL: GPH1324M41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
22.3
25.0
1.97
8.4
3.30
11.3
320
98
40
20.7
23.2
1.94
8.0
3.13
10.7
308
90
35
30
16.7
18.8
2.32
7.4
2.11
7.2
283
73
25
15.4
17.3
2.26
7.1
1.99
6.8
270
65
20
14.2
15.9
2.21
6.9
1.88
6.4
260
57
17
13.4
15.1
2.18
6.7
1.80
6.2
253
53
15
12.9
14.5
2.16
6.7
1.75
6.0
249
51
10
11.6
13.0
2.10
6.4
1.61
5.5
239
43
5
0
9.0
-5
7.6
8.6
-10
6.3
7.0
MBh
Delta T
KW
AMPS
COP
EER
HI PR
LO PR
28.9
32.4
2.14
10.4
3.96
13.5
379
135
27.4
30.7
2.10
9.8
3.82
13.1
364
126
25.8
28.9
2.06
9.2
3.67
12.5
350
24.1
27.0
2.01
8.8
3.50
12.0
334
23.0
25.8
1.99
8.5
3.38
11.5
326
19.1
21.4
1.89
7.7
2.95
10.1
295
80
10.3
11.5
2.05
6.1
1.47
5.0
10.1
2.00
5.8
1.31
4.5
1.95
5.5
1.15
3.9
213
27
1.89
5.1
0.97
3.3
205
22
230
37
221
31
118
108
102
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: GPH1330M41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
21.2
18.7
2.29
9.6
2.71
9.2
280
70
25
19.6
17.3
2.24
9.2
2.55
8.7
267
63
20
18.0
15.9
2.19
8.9
2.40
8.2
256
55
17
17.0
15.0
2.17
8.7
2.30
7.9
250
51
15
16.4
14.4
2.15
8.6
2.23
7.6
246
49
10
14.7
13.0
2.10
8.2
2.05
7.0
236
42
5
0
-5
9.7
-10
7.9
MBh
Delta T
KW
AMPS
COP
EER
HI PR
LO PR
36.2
31.9
2.74
13.6
3.87
13.2
375
131
34.3
30.2
2.68
12.7
3.74
12.8
359
32.3
28.4
2.63
12.0
3.59
12.3
346
30.2
26.6
2.58
11.4
3.42
11.7
330
28.8
25.4
2.55
11.1
3.30
11.3
323
27.9
24.6
2.53
10.9
3.23
11.0
316
25.9
22.9
2.48
10.4
3.06
10.5
304
23.9
21.1
2.43
9.9
2.88
9.8
13.0
11.5
2.05
7.8
1.86
6.4
11.4
10.0
2.00
7.5
1.66
5.7
8.6
1.95
7.0
1.46
5.0
210
27
7.0
1.90
6.5
1.22
4.2
203
21
292
78
227
36
218
30
122
114
105
99
95
88
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: GPH1336M41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
20.8
16.7
2.26
9.9
17
19.6
15.8
2.24
9.7
15
18.9
15.2
2.22
9.6
10
17.0
13.6
2.17
9.2
5
0
-5
11.2
9.0
2.02
7.8
-10
9.2
7.4
1.97
7.2
MBh
Delta T
KW
AMPS
COP
EER
HI PR
LO PR
43.0
34.6
3.10
15.4
4.06
13.9
403
137
40.7
32.8
3.04
14.4
3.92
13.4
386
38.3
30.8
2.98
13.6
3.76
12.8
371
35.8
28.8
2.92
12.9
3.58
12.2
355
34.2
27.5
2.89
12.5
3.46
11.8
347
33.1
26.7
2.86
12.3
3.39
11.6
340
30.8
24.8
2.81
11.7
3.21
11.0
327
28.4
22.9
2.75
11.1
3.02
10.3
314
24.4
19.7
2.36
10.7
3.03
10.4
300
73
22.6
18.2
2.31
10.3
2.86
9.8
15.0
12.1
2.12
8.7
13.1
10.6
2.07
8.3
2.69
9.2
276
58
2.57
8.8
269
54
2.50
8.5
264
52
2.29
7.8
254
44
2.08
7.1
244
38
1.85
6.3
234
32
1.62
5.5
226
28
1.36
4.6
218
22
287
66
127
119
109
103
99
91
81
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: GPH1342M41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
19.1
13.6
2.14
10.6
2.61
8.9
5
-5
12.6
9.0
2.01
9.0
1.84
6.3
181
29
-10
10.3
7.3
1.96
8.3
1.54
5.3
175
22
MBh
Delta T
KW
AMPS
COP
EER
HI PR
LO PR
50.3
35.8
3.58
17.6
4.11
14.0
323
141
47.6
33.9
3.52
16.5
3.96
13.5
310
44.8
31.9
3.45
15.6
3.80
13.0
298
41.9
29.8
3.38
14.8
3.62
12.4
285
40.0
28.5
3.34
14.3
3.50
12.0
278
38.8
27.6
3.31
14.1
3.42
11.7
273
36.0
25.6
3.25
13.4
3.24
11.1
262
33.2
23.6
3.18
12.8
3.05
10.4
252
27.5
19.6
2.31
12.3
3.48
11.9
241
75
25.4
18.1
2.27
11.9
3.27
11.2
230
67
23.4
16.7
2.23
11.4
3.07
10.5
221
59
22.1
15.7
2.20
11.2
2.94
10.0
216
55
21.3
15.1
2.18
11.1
2.85
9.7
16.9
12.0
2.09
10.0
2.36
8.1
14.8
10.5
2.05
9.6
2.11
7.2
212
53
204
45
196
39
188
33
131
122
112
106
102
94
84
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low
and high side pressures and power will not change.
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
HEATING PERFORMANCE DATA
GPH13[48-60]M41*
EXPANDED PERFORMANCE DATA
MODEL: GPH1348M41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
22.7
12.2
2.29
11.2
2.91
9.9
5
-5
15.0
8.1
2.14
9.5
2.05
7.0
209
26
-10
12.3
6.6
2.09
8.7
1.72
5.9
202
21
MBh
Delta T
KW
AMPS
COP
EER
HI PR
LO PR
57.2
30.8
3.90
19.0
4.29
14.7
372
130
54.1
29.1
3.83
17.7
4.14
14.1
357
121
51.0
27.4
3.75
16.7
3.97
13.6
343
47.6
25.6
3.68
15.8
3.79
13.0
328
45.5
24.5
3.63
15.3
3.66
12.5
320
44.1
23.7
3.60
15.0
3.58
12.2
314
41.0
22.0
3.53
14.3
3.39
11.6
302
37.8
20.3
3.46
13.7
3.20
10.9
290
32.8
17.6
2.48
13.1
3.86
13.2
278
70
30.2
16.3
2.43
12.6
3.64
12.4
265
62
27.8
15.0
2.38
12.1
3.42
11.7
255
55
26.3
14.2
2.36
11.9
3.27
11.2
249
51
25.3
13.6
2.34
11.8
3.17
10.8
244
49
20.1
10.8
2.24
10.6
2.63
9.0
17.6
9.5
2.19
10.1
2.35
8.0
235
42
226
36
217
30
113
104
98
95
87
77
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: GPH1360M41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
-5
17.9
9.2
2.12
12.0
2.47
8.4
216
27
-10
14.7
7.5
2.08
11.0
2.06
7.1
MBh
Delta T
KW
AMPS
COP
EER
HI PR
LO PR
69.8
35.9
4.80
24.1
4.25
14.5
385
134
66.0
34.0
4.71
22.5
4.10
14.0
369
124
62.2
32.0
4.62
21.2
3.94
13.5
354
58.1
29.9
4.53
20.1
3.76
12.8
339
55.5
28.5
4.47
19.4
3.63
12.4
331
53.8
27.7
4.44
19.1
3.55
12.1
325
50.0
25.7
4.35
18.1
3.36
11.5
312
46.1
23.7
4.26
17.3
3.17
10.8
300
39.1
20.1
2.41
16.7
4.76
16.3
287
72
36.1
18.6
2.36
16.0
4.47
15.3
274
64
33.3
17.1
2.32
15.4
4.19
14.3
263
56
31.4
16.2
2.30
15.0
4.00
13.7
257
52
30.3
15.6
2.28
14.9
3.88
13.2
252
50
27.1
14.0
2.24
14.2
3.54
12.1
243
24.1
12.4
2.20
13.4
3.20
10.9
233
37
21.0
10.8
2.16
12.8
2.84
9.7
224
31
208
21
116
107
101
97
89
80
43
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low
and high side pressures and power will not change.
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
WIRING DIAGRAMS
GPH13[24-42]M41AB
LPS
SEE NOTE #8
SEE NOTE #7
YL/PK
YL/PK
PU
SEE NOTE 4
PU
PU
BK
BK
2
RD
GR
1
C
3
240
BL
PU
208
RD
BK
2
0
8
-
2
4
0
/
G
BL
YL
L2
T2
T1
EBTDR
RD
24V
BL
BK
RD
NO
R
K1
SEE NOTE
#6
1
3
4
C
BL
XFMR-R
YL
L1
BK
COM
NC
BL
2
K1
RD
RD
BK
PU
C
PU
BR
SPEED
UP
RD
M1 M2
BL
BK
BK
1
/
GND
PU
6
0
OR
PU
BK
BK
C
C
Y
Y
C
OR
RD
C-RV
BL/PK
PU
YL
BL/PK
LVJB
PU
BK
CNT
O
DC
R-PS1
PS2
RD
BK
YL
H
BR
O-RV
W
PU
CCR
LVDR
HPS
T
WH
PU
RD
WH
PLF
3
2
1
H
E
R
M
O
S
T
YL
RD
GR
WH
OR
BR
BL
Y
RD
YL
R
R
R
G
W1
O
W2
C
6
5
4
9
8
C
F
HVDR
DF1
R-DFT
DFT
DF2
BR
RD
RCCF
SA
A
T
7
RD
++
PU
BR
BL
CONTROL
BOX
BK
BK
SEE NOTE #5
PU
PU
RD
SEE NOTE #3
BK
RD
RD
C
(TRANS240V)
CH
GR
BK
RD
BK
BR
RD
PU (M1)
LOW
RD
YL
BL
PU
BK
BR
CM
S
R
(COM)BK
HIGH
BR
PU
EM
RD
EM
3 SPEED
BR
DFT
2 SPEED
OPTIONAL
BK
COMP
FC
CHS
FC
BK
BK
RVC
SEE NOTE #3
L1
L2
SUPPLY VOLTAGE
208-240/1/60
SEE NOTE 3
CHS
COMPONENT LEGEND
FACTORY WIRING
LINE VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH
VOLTAGE
CH
BR
C
BLOWER INTERLOCK RELAY
CONTACTOR
T2
C
C
R
C
CCR
CH
CHS
CM
COMPRESSOR CONTACTOR RELAY
CRANKCASE HEATER
CRANKCASE HEATER SWITCH
CONDENSER MOTOR
T1
COMP
C
RCCF
S
H
HVDR
CM
BR
2 POLE ONLY
SEE NOTE 7
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
F
COMP COMPRESSOR
S.A.
DC
DEFROST CONTROL
DEFROST THERMOSTAT
DFT
EBTDR ELECTRONIC BLOWER TIME DELAY RELAY
SEE NOTE 5
P
L
F
3
1
EM
FC
EVAPORATOR MOTOR
FAN CAPACITOR
1
3
4
GND
HPS
EQUIPMENT GROUND
HIGH PRESSURE SWITCH
HVDR HIGH VOLTAGE DEFROST RELAY
WIRE CODE
BK BLACK
BL BLUE
BR BROWN
GR GREEN
OR ORANGE
PU PURPLE
RD RED
WH WHITE
YL YELLOW
2
LOW PRESSURE SWITCH
LPS
LVDR
LVJB
PLF
LOW VOLTAGE DEFROST RELAY
LOW VOLTAGE JUNCTION BOX
FEMALE PLUG / CONNECTOR
REVERSING VALVE COIL
EBTDRM1
M2
SEE
NOTE 2
EBTDR
NC
COM
EM
RVC
RCCF RUN CAPACITOR FOR
FC
COMPRESSOR AND FAN
START ASSIST
TRANSFORMER
208-240
2
SA
TR
SEE NOTE 4
1
3
TR
24V
G
EBTDR
R
NOTES:
C
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS
ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED REPLACE LEAD ON EBTDR
"COM" WITH LEAD ON EBTDR "M1" OR "M2".
DFT
3. CRANKCASE HEATER AND CRANKCASE HEATER SWITCH FACTORY
EQUIPPED WHEN REQUIRED.
4. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES
FROM TERMINAL 3 TERMINAL 2 ON TRANSFORMER.
5. START ASSIST FACTORY EQUIPPED WHEN REQUIRED.
6. USE COPPER CONDUCTORS ONLY ++ USE N.E.C. CLASS 2 WIRE.
7. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR
COULD BE FACTORY EQUIPPEDAS AN ALTERNATE CONFIGURATION.
8. COMMON SIDE OF CONTACTOR CAN NOT BE GROUNDED OR
CONNECTED TO ANY OTHER COMMON (24V).
RVC
C-RV
O-RV
R
R-DFT
DFT
R
C
DC
Y
O
W
R-PS1
LPS
PS2
CNT
4
5
6
P
L
F
C
HPS
SEE UNIT RATING PLATE FORTYPE AND SIZE
OF OVER CURRENT PROTECTION
R
W2
O
W1
Y
G
C
208-240/1/60 0140G01745-A
THERMOSTAT
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
WIRING DIAGRAMS
GPH13[48-60]M41AB
SEE NOTE 8
SEE NOTE 3
SEE NOTE 7
PU
LPS
BK
2
PU
PU
BK
1
C
BL
3
208
240
YL/PK
YL/PK
PU
2
BL
BL
0
8
-
2
4
0
/
T2
T1
L2
C
RD
24V
RD
YL
BL
SEE NOTE 5
BL
L1
BK
BK
PU
YL
BK
BL
PU
1
/
RD
BK
PU
GND
GR
GR
60
C
Y
Y
C
C
OR
RD
C-RV
RD
PU
OR
PU
BK
CNT
O
DC
R-PS1
PS2
PU
RD
RD
RD
YL
BR
O-RV
W
PU
WH
CCR
LVDR
LVJB
GR
T
H
E
R
M
O
S
T
WH
PLF
WH
YL
RD
GR
WH
OR
BR
BL
R
R
BL
R
G
W1
O
W2
C
YL
BL
BK
WH
3
6
5
4
9
8
7
H
C
F
HVDR
DF1
GR
R-DFT
DFT
DF2
2
1
BR
RCCF
RD
RD
A
T
YL
RD
YL
++
PU
BR
BK
BK
BK
PU
PU
SA
RD
SEE NOTE 4
PU
YL
SEE
NOTE 6
WH
PU
RD
BL/PK
BL/PK
BK
CH
GR
CONTROL
BOX
BR
CM
YL
RD RD
RD
BK
RD
GR
CHS
C
1
L
2
G
3
N
S
C
R
4
5
DFT
RVC
BKBK
HPS
BK
SEE NOTE 6
BK
EM
COMP
SEE NOTE 2
L1
L2
SUPPLY VOLTAGE
208-240/1/60
COMPONENT LEGEND
CONTACTOR
FACTORY WIRING
LINE VOLTAGE
LOW VOLTAGE
OPTINAL HIGH
VOLTAGE
C
T2
C
CCR
COMPRESSOR CONTACTOR RELAY
R
COMP
C
T1
CH
CRANKCASE HEATER
C
C
CHS
CM
CRANKCASE HEATER SWITCH
CONDENSER MOTOR
RCCF
S
H
HVDR
CM
COMP
COMPRESSOR
2 POLE ONLY
SEE NOTE 7
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
F
DC
DEFROST CONTROL
S.A.
SEE NOTE 4
DFT
EM
DEFROST THERMOSTAT
EVAPORATOR MOTOR
GND
HVDR
LPS
LVDR
LVJB
PLF
EQUIPMENT GROUND
HIGH VOLTAGE DEFROST RELAY
LOW PRESSURE SWITCH
LOW VOLTAGE DEFROST RELAY
LOW VOLTAGE JUNCTION BOX
FEMALE PLUG / CONNECTOR
REVERSING VAVLE COIL
RUN CAPACITOR FOR
WIRE CODE
BK BLACK
BL BLUE
BR BROWN
GR GREEN
OR ORANGE
PU PURPLE
RD RED
SEE NOTE 6
CHS
RVC
RCCF
CH
SEE NOTE 2
EM
L
N
COMPRESSOR AND FAN
START ASSIST
3
2
SA
WH WHITE
YL YELLOW
TR
TRANSFORMER
G
1
HPS
HIGH PRESSURE SWITCH
208-240
2
SEE NOTE 3
1
3
NOTES:
TR
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS
ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTO R SPEED MOVE WHITE AND YELLOW
LEADS FROM EM"2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE
ENERGIZED, THE HIGHER SPEED SETTING IS USED.
24V
DFT
RVC
O-RV
R
C-RV
R-DFT
R-PS1
DFT
R
C
3
FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES FROM
DC
Y
TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED
5. USE COPPER CONDUCTORS ONLY
++ USE N.E.C. CLASS 2 WIRE
6. CRANKCASE HEATER AND CRANKCASE HEATER SWITCH FACTORY
EQUIPPED WHEN REQUIRED.
7. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR
COULD BE FACTORY EQUIPPED AS AN ALTERNATE CONFIGURATION.
8. COMMON SIDE OF CONTACTOR CAN NOT BE GROUNDED OR
CONNECTED TO ANY OTHER COMMON (24V).
O
W
PS2
CNT
LPS
HPS
2
3
C
EM
1
4
5
6
SEE NOTE 2
PLF
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
C
R
O
W1
Y
G
C
W2
THERMOSTAT
208-240/1/60 0140G01640-A
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Everpure Water System EV9325 04 User Manual
Fisher Price Baby Toy x3189 User Manual
Foundations Baby Furniture 100 SSE User Manual
Fundex Games Games Billionaire User Manual
Gefen TV Cables EXT DVIRS232 1FO User Manual
Gemini CD Player CD 9500 User Manual
Genesis ICE Cordless Drill GCD18BK User Manual
GE Range 10 95 CG User Manual
Gianni Industries Door DG 15LD User Manual
Goodman Mfg Air Conditioner goodman High Efficiency 2 to 5 Ton Split System Air Conditioner User Manual