Room Air Conditioner
Service and Parts
Manual
Timer
0n/0ff
0F
hr
Mode
Fan Only Cool
Dry Money Saver®
Auto
Swing
Fan
Speed
Power
Temp
115Volts
CP10F10 CP12F10
CP10 - CP12 Svc Parts 2010 (05/10)
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions
must be followed.
Incorrect operation due to ignoring instructions will cause harm or damage. The seriousness
is classified by the following indications.
This symbol indicates the possibility of death or serious injury.
WARNING
This symbol indicates the possibility of injury or damage to property only.
CAUTION
Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Always install the expansion panel(s).
Do not place the power cord near a heater.
• Improper assembly or installation may cause
incorrect operation, including injury, fire, and
electric shock hazards.
• It may cause fire and electric shock.
Do not use the power cord near flammable
gas or combustibles such as gasoline,
benzene, thinner, etc.
Do not disassemble or modify products.
• It may cause explosion or fire.
• It may cause failure and electric shock.
Service Manual 3
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Plug in the power plug
properly.
Do not operate or stop the
unit by inserting or pulling
out the power plug.
Do not damage or use an
unspecified power cord.
• Otherwise, it will cause
electric shock or fire.
• It will cause electric shock or
fire.
• It will cause electric shock or
fire.
Do not modify power cord
length.
Use the air conditioner on a
single outlet circuit.(see page 7.)
Do not share the outlet with
other appliances.
Always plug into a
grounded outlet.
• It will cause electric shock or
fire.
•
It will cause electric shock or
fire.
• No grounding may cause
electric shock.
Ventilate before operating air Do not use the socket if it is
Do not operate with wet
hands or in damp
environment.
conditionerwhen gas goes
out.
loose or damaged.
It may cause explosion, fire,
and burn.
•
• It may cause fire and electric
shock.
• It will cause electric shock.
4 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
If water enters the product, turn off the the
power switch of the main body of appliance.
Contact service center after taking the power-
plug out from the socket.
Do not clean the air conditioner with water.
• It will cause electric shock or failure of
machine.
• Water may enter the unit and degrade the
insulation. It may cause an electric shock.
CAUTION
Never touch the metal parts of the unit
when removing the filter.
Do not block the inlet or outlet.
• They are sharp and may cause injury.
It may cause failure of appliance or
performance deteriorate.
•
Ensure that the outer caseis not damaged
by age orwear.
Be cautious not to touch the sharp edges
when installing.
• Leaving it damaged couldresult in the air
conditioner falling out of the window, creating
a safety hazard.
It may cause injury.
•
Sharp
edges
Service Manual 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
Dimensions
Symbols Used in this Manual
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the
air conditioner.
NOTICE
This symbol indicates special notes.
Outside Dimensions
11
1
525(20 /16")
470(18 /2")
6 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Specfications
rduct Specifications
MODELS
CP10F10
CP12F10
ITEMS
1Ø , 115, 60Hz
POWER SUPPLY
COOLING CAPACITY
INPUT
10,000
12,000
1,110
10.2
(Btu/h)
(W)
920
8.5
RUNNING CURRENT
(A)
.
10.8
E.E.R
(BTU/W h)
OPERATING
80 (DB)* 67(WB)**
95 (DB)* 75(WB)**
INDOOR ( F)
OUTDOOR ( F)
CONDITION
530g(18.7oz)
540g(19.0oz)
REFRIGERANT (R410) CHARGE
EVAPORATOR
Ø9.52, 2ROW 13STACKS
Ø5.0 , 3ROW 18STACKS
TURBO FAN
CONDENSER
FAN, INDOOR
PROPELLER TYPE FAN WITH SLINGER RING
3/3
FAN, OUTDOOR
FAN SPEEDS, FAN/COOLING
FAN MOTOR
6 POLES
REMOTE CONTROLLER
OPERATION CONTROL
ROOM TEMP. CONTROL
AIR DIRECTION CONTROL
CONSTRUCTION
THERMISTOR
HORIZONTAL LOUVER (UP & DOWN), VERTICAL LOUVER (RIGHT&LEFT)
SLIDE IN-OUT CHASSIS
OVERLOAD PROTECTOR
COMPRESSOR
FAN MOTOR
PROTECTOR
INTERNAL THERMAL PROTECTOR
3 WIRE WITH GROUNDING
POWER CORD
DRAIN SYSTEM
ATTACHMENT PLUG (CORD-CONNECTED TYPE)
DRAIN PIPE OR SPLASHED BY FAN SLINGER
235/8x1431/32x225/16
OUTSIDE DIMENSION
(W x H x D)
(inch)
(mm)
380 x 600 x 555
* DB:Dry Bulb
**WB:Wet Bulb
Operation
• DESIGNED FOR COOLING ONLY
• POWERFUL AND INCREDIBLE COOLING
• TOP-DOWN CHASSIS FOR THE SIMPLE INSTALLATION AND SERVICE
• BUILT-IN ADJUSTABLE THERMOSTAT
• WASHABLE ONE-TOUCH FILTER
• COMPACT SIZE
Serrvice Manual 7
Download from Www.Somanuals.com. All Manuals Search And Download.
7
5
3
Power
1
Timer
0n/0ff
0F
hr
Mode
Temp
Fan Only Cool
2
Dry Money Saver®
Fan S peed
4
Auto
Swing
Fan
ower
Speed
Mode
Timer
Temp
5
6
3
Auto
Swing
A
S wing
4
6
2
1
6. AUTO SWING
This button can automatically control the air flow
direction.
7
Service Manual 8
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
Disassembly
Before the following disassembly, POWER SWITCH set to OFF and disconnect the power cord.
Mechanical Parts
1. FRONT GRILLE
1. Open the lnlet grille upward or downward.
2. Remove the screw which fastens the front grille.
3. Pull the front grille from the right side.
4. Remove the front grille.
5. Re-install the component by referring to the
removal procedure, above.(See Figure 1)
Figure 1
2. CABINET
1. After disassembling the FRONT GRILLE, remove
the 2 screws which fasten the cabinet at both
sides.
2. Remove the 2 screws which fasten the cabinet at
back.
3. Pull the base pan forward. (See Figure 2)
4. Remove the cabinet.
5. Re-install the component by referring to the
removal procedure, above.
Figure 2
3. CONTROL BOX
1. Disconnect the unit from the power source.
2. Remove the front grille.
3. Remove the cabinet.
4. Remove the screw which fastens the control box
cover.
5. Remove the housing which connects motor wire
in the control box.
6. Remove the 3 leads from the compressor.
7.Discharge the capacitor by placing a 20,000
ohmresistor across the capacitor terminals.
8. Remove the 2 screws which fasten the control
box.(See Figure 19)
9. Pull the control box forward completely.
10. Re-install the components by referring to the
removal procedure, above. (See Figure 3)
Figure 3
Service Manual 9
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
Air Handling Parts
1. AIR GUIDE AND BLOWER
1. Remove the front grille.
2. Remove the cabinet.
3. Remove the control box.
4. Remove the 3 screws which fasten the brace.
5. Remove the brace.
6. Remove the 2 screws which fasten the evaporator.
7. Move the evaporator forward and pulling it upward
slightly. (See Figure 4)
8. Move the evaporator to the left carefully.
9. Pull out the hook of orifice by pushing the tabs and
remove it. (See Figure 5)
Figure 4
10. Remove the clamp with a hand plier which
secures the blower.
11. Remove the blower.
12. Remove the 4 screws which fasten the air guide
from the barrier.
13. Move the air guide backward, pulling out from the
base pan.
14. Re-install the components by referring to the
removal procedure, above.
Figure 5
2. FAN AND SHROUD
1. Remove the cabinet.
2. Remove the brace.
3. Remove the 3 screws which fasten the condenser.
4. Move the condenser to the left carefully.
5. Remove the clamp which secures the fan.
6. Remove the fan and then pull out the shroud.
(See Figure 6)
7. Re-install by referring to the removal procedure.
Figure
6
10 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
3. MOTOR
1. Remove the cabinet.
2. Remove the evaporator.
3. Remove the orifice.
4. Remove the blower.
5. Remove the fan.
6. Remove the control box cover and housing of the
motor in the control box.
7. Remove the 2 screws which fasten the motor from
the mount motor. (See Figure 7)
8. Remove the motor.
9. Re-install the components by referring to the
removal procedure, above.(See Figure 7)
Figure 7
Electrical Parts
1. OVERLOAD PROTECTOR
1. Remove the cabinet.
2. Remove the nut which fastens the terminal cover.
3. Remove the terminal cover. (See Figure 8)
4. Remove all the leads from the overload protector.
5. Remove the overload protector.
6. Re-install the component by referring to the
removal procedure, above.
Figure 8
2. COMPRESSOR
1. Remove the cabinet.
2. Discharge the refrigerant system using a FreonTM
Recovery System.
If there is no valve to attach the recovery system,
install one (such as a WATCO A-1) before venting
the FreonTM. Leave the valve in place after
servicing the system.
3. Remove the overload protector.
4. After purging the unit completely, unbraze the
suction and discharge tubes at the compressor
connections.
5. Remove the 3 nuts and the 3 washers which
fasten the compressor.
6. Remove the compressor. (See Figure 9)
7. Re-install the components by referring to the
removal procedure, above.
Figure 9
Service Manual 11
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
3. CAPACITOR
MODEL : TOUCH & REMOTE CONTROL TYPE MODEL
1. Remove the control box.
2. Remove the screw which fasten control panel from
control box.
3. Remove the screw which located in the front.
4. Open the bottom side of control box.
5. Remove the screw and the clamp which fastens
the capacitor.
6. Disconnect all the leads of capacitor terminals.
7. Re-install the components by referring to the
Figure 10
removal procedure, above. (See Figure 10)
4. POWER CORD
1. Remove the control box.
2. Open the control box.
3. Disconnect the grounding screw from the control
box.
4. Disconnect the 2 receptacles.
5. Remove a screw which fastens the clip cord.
(See Figure 11)
6. Remove the power cord.
7. Re-install the component by referring to the above
removal procedure, above.
(Use only one ground-marked hole
connection.)
for ground
Figure 11
8. If the supply cord of this appliance is damaged, it
must be replaced by the special cord. (The
special cord means the cord which has the same
specification marked on the supply cord attached at
the unit.)
Refrigerating Cycle
TM
CAUTION: Discharge the refrigerant system using a Freon Recovery System. If there is no valve
to attach the recovery system, install one (such as a WATCO A-1) before venting the Freon . Leave
TM
the valve in place after servicing the system.
1. CONDENSER
1. Remove the cabinet.
2. Remove the 3 screws which fasten the
brace.
3. Remove the 3 screws which fasten the condenser
and shroud.
4. After discharging the refrigerant completely,
unbraze the interconnecting tube at the condenser
connections.
5. Remove the condenser carefully.
6. Re-install the component by referring to notes.
(See Figure 12)
Figure 12
12 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
2. EVAPORATOR
1. Remove the cabinet.
2. Remove the 2 screws which fasten the evaporator.
3. Move the evaporator sideways carefully.
4. After discharging the refrigerant completely,
unbraze the interconnecting tube at the evaporator
connections.
5. Remove the evaporator carefully.
6. Re-install the component by referring to notes.
(See Figure 1)
3. CAPILLARY TUBE
1. Remove the cabinet.
2. After discharging the refrigerant completely,
unbraze the interconnecting tube at the capillary
tube.
3. Remove the capillary tube.
4. Re-install the component by referring to notes.
Figure 13
NOTICE
remaining in the system. With valves A and B
closed, stop the vacuum pump.
4) Remove the hose from the vacuum pump and
place it on the charging cylinder. See figure
14B. Open valve C.
Discharge the line at the manifold connection.
5) The system is now ready for final charging.
— Replacement of the refrigeration cycle.
1. When replacing the refrigeration cycle, be sure to
TM
Discharge the refrigerant system using a Freon
recovery System.
If there is no valve to attach the recovery system,
install one (such as a WATCO A-1) before venting
the Freon . Leave the valve in place after
TM
6. Recharge as follows :
servicing the system.
1) Refrigeration cycle systems are charged from
the High-side. If the total charge cannot be put
in the High-side, the balance will be put in the
suction line through the access valve which you
installed as the system was opened.
2) Connect the charging cylinder as shown in figure
33B.
With valve C open, discharge the hose at the
manifold connection.
3) Open valve A and allow the proper charge to
enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not
take it. Close valve A.
2. After discharging the unit completely, remove the
desired component, and unbraze the pinch-off
tubes.
3. Solder service valves into the pinch-off tube ports,
leaving the valves open.
4. Solder the pinch-off tubes with Service valves.
5. Evacuate as follows.
1) Connect the vacuum pump, as illustrated figure
14A.
2) Start the vacuum pump, slowly open manifold
valves A and B with two full turns counterclock-
wise and leave the valves open.
The vacuum pump is now pulling through valves
A and B up to valve C by means of the manifold
and entire system.
5) With the unit running, open valve B and add the
balance of the charge.
a. Do not add the liquid refrigerant to the Low-side.
b. Watch the Low-side gauge; allow pressure to
rise to 39 lbs.
c. Turn off valve B and allow pressure to drop.
d. Repeat steps b. and c. until the balance of the
charge is in the system.
CAUTION: If high vacuum equip-
ment is used, just crack valves A
and B for a few minutes, then open
slowly with the two full turns counter-
clockwise. This will keep oil from foaming
and being drawn into the vacuum pump.
6) When satisfied the unit is operating correctly,
use the pinch-off tool with the unit still running
and clamp on to the pinch-off tube. Using a tube
cutter, cut the pinch-off tube about 2 inches from
the pinch-off tool. Use sil-fos braze and braze
pinch-off tube closed. Turn off the unit, allow it to
set for a while, and then test the leakage of the
pinch-off connection.
3) Operate the vacuum pump vaccum for 20 to 30
minutes, until 600 microns of vaccum is
obtained. Close valves A and B, and observe
vacuum gauge for a few minutes. A rise in pres-
sure would indicate a possible leak or moisture
13 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pin-off tool capable
of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
COMPOUND GAUGE
CONDENSER
(HIGH PRESSURE SIDE)
MANIFOLD
GAUGE
A
B
CAPILLARY TUBE
SEE INSETS
BELOW
EVAPORATOR
(LOW PRESSURE SIDE)
COMPRESSOR
HI
LOW
A
A
B
B
EXTERNAL
VACUUM PUMP
CHARGING
CYLINDER
C
Figure 14B-Charging
Figure 14A-Pulling Vacuum
Service Manual 14
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
Circuit Diagram
MODEL : TOUCH & REMOTE CONTROL TYPE MODEL
WH
(BL)
(SMPS)
250V/T2A
(250V/T3.15A)
MEZ62420717
LOCATION
Q'TY
DESCRIPTION
NO.
PER SET
1
2
3
4
5
6
7
8
POWER CORD ASSEMBLY
FAN MOTOR
1
1
1
1
1
1
1
1
COMPRESSOR
DISPLAY P.W.B ASSEMBLY
MAIN P.W.B ASSEMBLY
THERMISTOR
CAPACITOR
OWERLOAD PROTECTOR
Service Manual 15
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
Electronic Control Device
16 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Troubleshooting Guide
Piping System
CONDENSER COIL
FAN
CAPILLARY TUBE
COMPRESSOR
MOTOR
BLOWER
EVAPORATOR COIL
Figure 15 is a brief description of the important components and their function in what is called the refrigeration
system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.
ROOM AIR CONITIONER
CYCLE OF REFRIGERATION
EVAPORATOR COILS
CONDENSER COILS
VAPOR INLET
SUCTION LINE
COOL LOW PRESSURE VAPOR
HOT
DISCHARGED
AIR
COMPLETE LIQUID
BOIL OFF POINT
COOLED
AIR
ROOM AIR HEAT LOAD
OUTSIDE COOLING
AIR FOR REFRIGERANT
PASS THROUGH
MOTOR
COMPRESSOR
OIL
LIQUID
PRESSURE
DROP
LIQUID OUTLET
HIGH PRESSURE VAPOR
(LIQUID REFRIGERANT)
LIQUID REFRIGERANT
LOW PRESSURE VAPOR
CAPILLARY TUBE
Figure 15
17 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Troubleshooting Guide
In general, possible trouble is classified in two kinds.
The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling.
Ineffective Cooling
Check cold air
circulation for smooth
flow.
Check outdoor coil
(heat exchanger) and
fan operation.
Check heat load
increase.
Clean condenser.
Dirty indoor coil
(heat exchanger)
Check gas leakage.
Repair gas leak.
Not on separate circuit
Malfunction of fan.
Check inside gas
pressure.
Replacement of unit if
the unit is beyond repair.
Clogging of air filter.
Obstruction at air outlet.
Remove obstruction.
Adjust refrigerant
charge.
Malfunction of
compressor.
Check clogging in refrigera-
tion circuit.
Replacement of
compressor.
Satisfactory operation
with temperature
Repair clogging in
refrigeration circuit.
difference of inlet & outlet
air; 44~50°F (7~10°C)
Service Manual 18
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Fails to Start
Check of circuit breaker
and fuse.
Check of power source.
Check of control panel
setting.
Check control panel.
Compressor fails only to
start.
Fan only fails to start.
Improper wiring.
Improper thermistor
setting
Drop of power voltage.
Defect of fan motor
capacitor.
Defect of compressor
capacitor.
Loose terminal
connection
Irregular motor
resistance (Ω)
Irregular motor
insulation (Ω)
Capacitor check.
Replacement.
Improper wiring
Replacement of fan motor.
Regular but fails to start.
Irregular motor resistance (Ω)
Irregular motor insulation (Ω)
Replacement of compressor.
(Locking of piston, metal.)
Replacement of compressor
(Motor damaged).
19 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
I MODEL : BG8000ER, WG8000RY4, WG1000RY4
ELECTRIC PARTS TROUBLESHOOTING GUIDE:
• The unit does not operate.
Possible Trouble 1
NO
•
•
Check the Fuse.
Check the wiring diagram.
Is the Trans input power
AC 115V?
YES
NO
NO
•
Check the Main
P.W.B pattern.
Is the Trans output power
about AC 14V?
Is shorted the Trans. output?
YES
YES
• Exchange the Trans.
Exchange D02D~D05D.
•
NO
NO
Is output Voltage of IC01D
DC 12V?
• Exchange IC01D.
YES
• Exchange IC02D.
Is output Voltage of IC02D
DC 5V?
YES
NO
NO
NO
Is the reset circuit all right?
(The No.14 of Micom
is 5V.)
• Exchange IC01A.
YES
Is the
• Connect connector
exactly.
connection between
Main and Display
all right?
YES
• Check the P.W.B
pattern.
Is the voltage No.18 of Micom
DC 5V?
YES
Exchange Main P.W.B Ass'y.
Service Manual 20
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
• The compressor does not operate.
• Set the Temp. setting to lower Temp.
Possible Trouble 2
Is Temp.
setting set lower than Room
Temp.-0.5°C?
NO
NO
YES
NO
NO
Is the voltage No.10
of IC01M 0V?
Is the voltage N0.7 of
Is the Unit for 3 minutes
delay?
IC01M DC 5V?
YES
YES
YES
• Check the RY-COMP.
• Check the wiring
Diagram.
• Exchange IC01M.
• Wait 3 Minutes
• Exchange MAIN
P.W.B Ass'y.
• The compressor always operate.
Possible Trouble 3
• Connect LEAD Wire to
RY-COMP again.
NO
Is the wire connection of
RY-COMP all right?
YES
• Check the RY-COMP.
• Fan does not operate.
Possible Trouble 4
NO
Is the voltage NO.1 or 4
of IC01M DC 5V?
• Exchange IC01M.
• Exchange IC01M.
YES
NO
Is the voltage NO.13 or 16
of IC01M 0V?
YES
• Check the RY-Hi or
RY-Lo.
•
Check the wiring diagram.
21 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
• Romote controller does not operate.
Possible Trouble 5
NO
NO
Is the voltage of Battery
about over 2.3V?
• Exchange the battery.
YES
Is the voltage No.16
of CN-DISP1 on Main P.W.B
Ass'y DC 5V?
•
Check the P.W.B pattern.
YES
• Connect connector to
CN-DISP1 exactly.
NO
Is the connection of
CN-DISP1 all right?
YES
•
Exchange Receiver Ass'y.
• It displays abnormally on Display P.W.B Ass'y.
Possible Trouble 6
NO
NO
NO
• Exchange IC01G.
Is the IC01G all right?
YES
NO
• Connect connector
to CN-DISP1 exactly.
Is the connection of
CN-DISP1 all right?
YES
Does the Q01G,
Q02G, Q03G Q04G operate normally
on main P.W.B Ass'y?
• Exchange Q01G,
Q02G, Q03G, Q04G
YES
• Exchange the display
P.W.B Ass'y.
Service Manual 22
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
ROOM AIR CONDITIONER VOLTAGE LIMITS
NAME PLATE RATING
115V ± 10%
MINIMUM
103.5V
MAXIMUM
126.5V
COMPLAINT
CAUSE
REMEDY
Fan motor will not run.
No power
Check voltage at outlet. Correct if none.
Wire disconnected or
connection loose
Connect wire. Refer to wiring diagram for
terminal identification. Repair or replace loose
terminal.
Capacitor (Discharge
Test capacitor.
capacitor before testing.)
Replace if not within ±10% of manufacturer's
rating. Replace if shorted, open, or damaged.
Will not rotate
Fan blade hitting shroud or blower wheel hitting
scroll. Re-align assembly.
Units using slinger ring condenser fans must
have 0.22~0.25 inch clearance to the base.
If necessary, shim up the bottom of the fan motor
with mounting screw(s).
Check fan motor bearings; if motor shaft will not
rotate, replace the motor.
Fan motor runs.
Revolves on overload
Check voltage. See limits on this page.
If not within limits, call an electrician.
Test capacitor.
Check bearings. Does the fan blade rotate
freely?
If not, replace fan motor.
Pay attention to any change from high speed to
low speed. If the speed does not change,
replace the motor.
23 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
REMEDY
COMPLAINT
CAUSE
Fan motor noise.
Fan
If cracked, out of balance, or partially missing,
replace it.
Blower
If cracked, out of balance, or partially missing,
replace it.
Loose set screw
Worn bearings
Tighten it.
If knocking sounds continue when running or
loose, replace the motor. If the motor hums or
noise appears to be internal while running,
replace motor.
Compressor will not run,
fan motor runs.
Voltage
Wiring
Check voltage. See the limits on the preceding
page. If not within limits, call an electrician.
Check the wire connections; if loose, repair or
replace the terminal. If the wires are discon-
nected, refer to wiring diagram for identification,
and replace the wires. Check the wire connections;
If not according to the wiring diagram, correct
the connections.
Thermistor
Check the TEMP control. If not at the lowest
number, set TEMP control to this setting and
restart the unit.
Check the continuity of the thermistor. Replace
the thermistor if the circuit is open.
Rotary
Check for continuity, refer to the wiring diagram
for terminal identification. Replace the switch if
the circuit is open.
Capacitor (discharge
capacitor before
servicing.)
Check the capacitor.
’s
Replace if not within ±10% of manufacturer
rating, replace if shorted, open, or damaged.
Compressor
Overload
Check the compressor for open circuit or
ground. If open or grounded, replace the
compressor.
Check the compressor overload if externally mounted.
Replace if open. (If the compressor temperature is
high, remove the overload, cool, and retest.)
Service Manual 24
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
COMPLAINT
CAUSE
REMEDY
Compressor cycles on
overload.
Voltage
Check the voltage. See the limits on the
preceding page. If voltage is not within these limits,
call an electrician.
Overload
Check overload, if externally mounted.
Replace if open. (If the compressor temperature
is high, remove the overload, cool, and retest.)
Compressor cycles on
overload.
Fan motor
If not running, determine the cause. Replace if
required.
Condenser air flow
restriction
Remove the cabinet, inspect the interior surface
of the condenser. If restricted, clean carefully
with a vacuum cleaner (do not damage fins) or
brush. Clean the interior base before
re-assembling.
Condenser fins
(damaged)
If the condenser fins are closed over a large
area on the coil surface, head pressures will
increase, causing the compressor to cycle.
Straighten the fins or replace the coil.
Capacitor
Test the capacitor.
Wiring
Check the terminals. If loose, repair or replace.
Check the system for a restriction.
If restricted, clean or replace.
Refrigeration system
Air filter
Insufficient cooling
Excessive noise
Unit undersized
Blower or fan
Determine if the unit is properly sized for the
area to be cooled.
Check the set screw, or clamp. If loose or miss-
ing, correct. If the blower or fan is hitting scroll
or barrier, rearrange the air handling parts.
Copper tubing
Remove the cabinet and carefully rearrange the
tubing not to contact the cabinet,
compressor, shroud, and barrier.
25 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Exploded View
Exploded View
130910
749740
731273
148000
359011
346811
352380
W48602
349600
149980
359012
267110
W48602
349001
349480
567502
152302
135303
147582
130410
550140
135312
147581
249950
W0CZZ
567480
268711-1
238310
146812
264110
268711-2
237200
135500
Service Manual 26
Download from Www.Somanuals.com. All Manuals Search And Download.
ReplacementParts list
LocNo
DESCRIPTION
Base Assembly,Single
Cabinet Assembly,Single
Grille,Inlet
CP10F10
67305518
67303716
67306112
67306019
67304701
67300902
67306209
67306265
67303910
67305519
67304308
67305514
67500143
67500146
67300022
67302232
67303039
67303508
67303413
67303607
67302737
67302614
67302616
67305000
67307806
67301904
67306313
67304009
67307623
67307622
67300709
67302500
CP12F10
67305518
67303716
67306112
67306019
67304701
67300902
67306209
67306265
67303910
67305519
67304308
67305514
67500143
67500147
67300028
67302232
67303040
67303508
67303413
67303607
67302737
67302614
67302616
67305000
67307806
67301905
67306313
67304009
67307623
67307625
67300728
67302500
130410
130910
135303
135312
135500
146812
147581
147582
148000
149980
152302
237200
238310
249950
264110
267110
346811
349001
349480
349600
352380
359011
359012
550140
567480
567502
731273
749740
268711-1
268711-2
W0CZZ
W48602
Grille Assembly,Front(Indoor)
Cover
Motor,AC
Louver,Horizontal
Louver,Vertical
Supporter
Shroud
Filter,Air
Panel,Control
Escutcheon
Case Assembly,Control
Power Cord Assembly
Remote Controller Assembly
AC Motor Assembly
Damper,Vent
Orifice
Bracket,Motor
Guide Assembly,Air
Fan,Axial
Fan,Turbo
Damper,Compressor
Thermistor,NTC
Overload Protect
Install Part Assembly,Single
Guide
PCB Assembly,Display
PCB Assembly,Main
Capacitor,Film,Box
Clamp,Spring
27 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Use Factory Certified Parts...
FRIEDRICH AIR CONDITIONING CO.
Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540
• (210) 357-4400 • FAX (210) 357-4490
CP10 - CP12 Svc Parts 2010 (05/10)
Download from Www.Somanuals.com. All Manuals Search And Download.
|