Friedrich Air Conditioner 920 159 01 10 03 User Manual

®
Vert-I-Pak  
Single Package Vertical Air Conditioning System  
A-Series  
24,000 BTU/h  
Installation & Operation Manual  
920-159-01 (10-03)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
Vert-I-Pak Installation Recommendations  
For proper unit performance and maximum operating life please refer to the minimum installation clearances below.  
Figure 1  
VERT-I-PAK® units must be installed on an outside wall. Confined spaces and/or covered areas should be  
avoided. Units should be installed no closer than 12" apart when two units are side by side. If three of more  
units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical  
clearance of 60" should be maintained between units. Units installed on the bottom floor should be mounted  
at least 6" off of the ground.  
B
6"  
A
60" 60"  
SMALL RECESS OK  
LARGER RECESS OK. IF A> 5xB  
60"  
60"  
60"  
60"  
60"  
60"  
60"  
60"  
60"  
6"  
6"  
12"  
Figure 2  
BUILDING  
Any time obstructions are present use  
the following guidelines for proper  
spacing from the VERT-I-PAK louver:  
60"  
24"  
VPAK  
VPAK  
VPAK  
12"  
• For minor obstructions such as lamp  
poles or small shrubbery a clearance  
of 24" from the outdoor louver should  
be maintained.  
24"  
72"  
• For major obstructions such as a solid  
fence, wall or other heat rejecting  
device like a condensing unit, a mini-  
mum distance of 72" should be kept.  
SHRUB  
POLE  
OUTDOOR  
CONDENSING  
UNIT  
FENCE  
MAJOR OBSTRUCTION  
Theabovesuggestionsareforreferenceonlyanddonotrepresentallpossibleinstallations. Pleasecontactthefactory  
for information regarding affects of other installation arrangements.  
By following these simple recommendations you can be confident that your Friedrich Vert-I-Pak® will provide years  
of worry-free operation.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
Section I. General Specifications  
®
VERT-I-PAK MODEL IDENTIFICATION GUIDE  
MODEL NUMBER  
V
E
A 24 K 50 RT A  
ENGINEERING CODE  
OPTIONS  
RT = Standard Remote Operation  
SP = Seacoast Protected  
SERIES  
V=Vertical Series  
E=Cooling with or without electric heat  
H=Heat Pump  
ELECTRIC HEATER SIZE  
A-Series  
00 = No electric heat  
25 = 2.5 KW  
34 = 3.4 KW  
50 = 5.0 KW  
DESIGN SERIES  
A = 32" and 47" Cabinet  
NOMINAL CAPACITY  
A-Series (Btu/h)  
09 = 9,000  
12 = 12,000  
18 = 18,000  
75 = 7.5 KW  
10 = 10 KW  
24 = 24,000  
VOLTAGE  
K = 208/230V-1Ph-60Hz  
Vert-I-Pak® Chassis Specifications  
MODEL:  
V(E,H)A24  
230/208  
R-22  
Voltage (V)  
Refrigerant  
Chassis Width  
23.125  
23.125  
47.25  
Chassis Depth  
Chassis Height **  
Supply Duct Collar ***  
Drain Connection  
Min. Circuit Amps  
10"  
3/4" FPT  
See Nameplate  
CFM Indoor  
See chart, pg. 11  
.4 in. water  
Max. Duct ESP  
NOTES:  
** Height includes 2" duct collar & isolators under unit.  
*** Factory collar accepts 10" flex duct.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
II. Installation  
1) Utility Closet Dimensions  
Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1. Three inches minimum clearance on  
three sides of the unit must be allowed for return airflow, installation access and service access. See Figures 1 & 2 for clearances and  
reference dimensions.  
Figure 3  
Typical Utility Closet  
Chassis Shown in Closet, on Optional Platform  
Rigid Ductwork  
Field-supplied  
Filter (25" x 20")  
58"  
Exterior Wall  
Flexible Ductwork  
VPAWP1-8/1-14 Wall Plenum  
Power  
Disconnect  
Plenum  
29"  
VPRG4 Access Panel &  
Return Air Filter Grille  
Optional Platform  
3" Clearance on all  
three sides  
minimum for  
VPDP1 drain pan  
beneath unit is  
required on all  
VEA/VHA24 units.  
Drain pan must be  
installed prior to  
chassis installation  
Chassis is  
shipped with  
vibration  
isolators  
installed  
Figure 4  
Top View  
Vert-I-Pak Chassis 2-ton dimensions:  
23" wide x 23" deep x 47 1/4" high.  
control box  
VPAWP1-8/1-14 Wall Plenum cut-out  
dimensions 24 5/8" wide x 30 7/8" high.  
electrical  
entrance  
VPRG4 Access Panel cutout dimensions:  
27" wide by 55 3/4" high.  
See Figure 8 (Page 10) for proper  
chassis installation.  
NOTE: Drain pan must be installed in closet prior to chassis  
insertion into plenum. See Figure 7 (page 8) for drain pan  
installation details.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
2) Wall Plenum and Architectural Louver Installation  
A. Install the wall plenum (VPAWP1-8/1-14) components in accordance with the installation instructions provided with each accessory.  
IMPORTANT REMINDER: FRIEDRICH WALL PLENUM IS NOT DESIGNED TO CARRY STRUCTURAL  
LOADS. PROPER WALL HEADER CONSTRUCTION IS REQUIRED. THE PLENUM REQUIRES  
PROPER FLASHING, SHIM AND CAULK FOR A WEATHER RESISTANT INSTALLATION.  
B. Ensure that the divider is adjusted properly for the depth of the wall in accordance with the accessory installation manual  
Figure 5  
Wall Plenum & Outdoor Louver Installation  
Proper Header  
Caulk all 8  
flange corners  
Proper Flashing  
Proper Caulking  
Inside Wall Plenum  
(Part B)  
Outside Wall  
Proper Caulking  
Architectural louver VPAL2 mounted  
on the outside wall plenum (Part A)  
Proper Flashing  
Rough opening dimension 24 5/8" wide x 30 7/8" high.  
Ensure that the bottom of the plenum is 1 1/2" from the floor of the closet. Note: 9,000 / 12,000 / 18,000 installation  
height may be different. Refer to specific installation manual for clarification.  
For proper airflow, maintain a minimum distance of 12" between Vert-I-Pak units. Consult the factory for any  
installation or application questions.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
3) Electrical Information  
Electrical Data  
MODEL  
Voltage ( V)  
LRA - Comp. (A)  
230/208  
68  
230/208 230/208 230/208 230/208 230/208  
68 68 68 68 68  
Cooling Current (A) 13.7/12.4 13.7/12.4 13.7/12.4 13.7/12.4 13.7/12.4 13.7/12.4  
MIN. Ckt. Amps (A) 17.2/15.9 22.1/20.3 30.7/28.1 44.3/40.3 57.9/52.7 15.6/15.6  
Max Branch Circuit Fust (Amps)  
Power Connection  
25/25  
14/14  
25/25  
12/12  
35/30  
HARD WIRED  
45/45  
60/60  
4/6  
20/20  
14/14  
Recommended Branch  
Circuit Wire Sizes*  
8/10  
6/6  
AWG - American Wire Gauge  
* Single circuit from main box. Based on copper wire, single insulated conductor at 60°C.  
NOTE: Use copper conductors ONLY. Wire sizes are per NEC. Check local codes for overseas applications.  
Sample Nameplate (see your chassis nameplate)  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
IMPORTANT: ALL 208/230V CHASSIS MUST BE HARD WIRED WITH PROPERLY SIZED  
BREAKER. SEE NAMEPLATE FOR SPECIFIC CHASSIS ELECTRICAL REQUIREMENTS.  
SEE PAGE 9 - FIGURE 8 FOR UNIT WIRING AND WALL THERMOSTAT WIRING. SEE PAGE  
7 FOR WIRE SIZE. USE HACR TYPE BREAKERS TO AVOID NUISANCE TRIPS. ALL FIELD  
WIRING MUST BE DONE IN ACCORDANCE WITH NEC AND LOCAL CODES.  
3) Electrical Information (continued)  
Figure 6  
Electrical Requirements  
Note:AlleldwiringmustcomplywithNECandlocalcodes. It  
is the responsibility of the installer to insure that the electrical  
codes are met.  
CAUTION  
Electric shock hazard.  
Use ONLY wiring size recommended for single  
outlet branch circuit.  
Turn OFF electric power before service  
or installation.  
Wire Size  
AllelectricalconnectionsandwiringMUST  
be installed by a qualified electrician and  
conformtotheNationalElectricalCodeand  
all local codes which have jurisdiction.  
Use ONLY type and size fuse or HACR circuit  
breakerindicatedonunit'sratingplate(Seesample  
on page 6). Proper current protection to the unit is  
the responsibility of the owner.  
Fuse/Circuit  
Breaker  
Failure to do so can result in property  
damage, personal injury and/or death.  
Unit MUST be grounded from branch circuit to  
unit, or through separate ground wire provided on  
permanently connected units. Be sure that branch  
circuit or general purpose outlet is grounded.  
Grounding  
Wire Sizing  
Use recommended wire size given in tables and  
installasinglebranchcircuit. Allwiringmustcomply  
with local and national codes. NOTE: Use copper  
conductors only.  
CAUTION  
Figure 7  
THE ACCESSORY DRAIN PAN  
(VPDP1) MUST BE INSTALLED  
BEFORE INSTALLING THE UNIT.  
Drain Connection  
and Location  
1. The accessory drain pan has two (2)  
provisions (left & right) for connecting  
an external condensate drain.  
2. A field supplied condensate drain  
system must be connected to one of  
the two 3/4" FPT connections.  
3. The remaining connection must be  
plugged using the 3/4" pipe plug  
(provided) and field suppled teflon  
tape or pipe joint compound.  
4. Failure to follow these procedures  
may result in serious property  
damage.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
3) Electrical Data (continued)  
Figure 8  
Electrical & Thermostat Wiring Diagrams  
FOR 208 VOLT MODELS ONLY  
MOVE THE WHITE WIRE AS  
SHOWN BELOW  
RT2  
THERMOSTAT  
(FRONT)  
COM. 208V 240V  
TRANSFORMER  
24V  
THERMOSTAT CONNECTIONS  
(EAR)  
UP  
G
R
R
BLACK  
W
Y
B
C
RED  
HEATER  
HEATER  
7.5 KW 10 KW  
2.5 KW  
&
3.4 KW  
&
5
KW  
COIL, SOLENOID  
RED  
BROWN  
QUICK DISCONNECT  
L1  
L2  
RED  
BLACK  
BLACK  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
BLUE  
RED  
WHITE  
PRESSURE  
SWITCH  
HEAT  
RELAY  
HEAT  
RELAY  
HEAT  
RELAY  
(7.5KW/10KW)  
REV VALVE  
RELAY  
HEAT  
RELAY  
FAN  
COMP WIRE HARNESS  
COMPR RELAY  
RELAY  
(7.5KW/10KW)  
(2.5KW/3.4KW  
KW)  
(2.5KW/3.4KW  
5
5
KW)  
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
COMPRESSOR  
c
COM. 208V  
TRANSFORMER  
240V  
LOW AMBIENT  
CONTROL  
BLACK  
BLACK  
BLACK  
BLACK  
BLACK  
BLACK  
24V  
RED  
RED  
BLACK  
C
W
Y
R
G
B
TERM BOARD  
CAPACITOR  
WIRE NUT (RED)  
GREEN  
SEE NOTE #6  
BLACK  
BLACK  
BLUE  
GREEN  
RED  
T-STAT  
C
H
DEFROST  
INSULATOR  
2-REQ'D  
YELLOW  
WHITE  
BLACK  
L
GREEN  
WHITE  
TO MOTOR  
MOUNT  
CAPACITOR  
c
BLUE  
WHITE  
WIRE NUT (RED)  
WHITE  
BROWN  
GREEN  
BLOWER  
MOTOR  
CONDENSER  
MOTOR  
SEE NOTE #4  
BLACK  
TO MOTOR  
MOUNT  
BROWN  
NOTE: THE DIAGRAM ABOVE ILLUSTRATES THE TYPICAL THERMOSTAT WIRING AND 208  
VOLT TRANSFORMER WIRING. SEE THE UNIT CONTROL PANEL FOR THE ACTUAL  
UNIT WIRING DIAGRAM AND SCHEMATIC.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
4) Indoor Return Air Grille Installation  
There are three Indoor Return Air Grille options as shown in Figure 9. Choose the option that best suits your needs. Use the installation  
instructions provided with accessories for installation details.  
Figure 9  
Return Air Grille Options  
Option 1  
VPRG4  
Return Air Grille with Access Panel  
A field-supplied (25" x 20") filter is  
mounted inside the hinged access door.  
Option 2  
All Vert-I-Pak chassis are shipped with a 20" x 14"  
filter installed. If an accessory filter holder is to be  
used, you MUST remove the factory shipped filter  
from the chassis. Do NOT use two filters  
VPRG2  
Return Air Grille  
Unit requires a field-supplied  
access door or panel and a  
16" x 20" filter.  
Notes:  
A. These are the Friedrich recommended return air grille / filter / access panel arrangements. Consult the factory on other  
arrangements. Improper return air arrangements will cause performance problems.  
B. Return air arrangements are shown from the front, but can also be installed from the right or left side of the unit.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
5) Indoor Airflow Data  
6) Chassis Installation  
The Vert-I-Pak A series units must be installed with a free return air  
configuration. Thetablebelowliststheindoorairflowatcorresponding  
static pressures. All units are shipped from the factory and are rated  
at low speed.  
NOTE: Priortoinstallingthechassis, ensurethatthedrainpanand  
line are free from debris.  
A. Ensure that the wall plenum is installed in accordance with  
the VPAWP1-8/1-14 Installation Manual.  
To change to high speed replace the low speed lead (blue) with the  
high speed lead (black) on the blower relay.  
B. Ensure that the VPDP1 drain pan is installed correctly (see  
page 8). Using the 3/4" plugs supplied with the pan, plug  
the unused condensate drain hole. Connect a drain to the  
condensate exit location. Be sure to use teflon tape or  
approved pipe sealant on all drain connections and plugs  
(see page 8).  
VEA/VHA24K  
Low  
750  
725  
700  
675  
High  
815  
780  
745  
700  
.1” ESP  
.2” ESP  
.3” ESP  
.4” ESP  
All values listed are inches  
W.C. with a wet indoor coil  
with filter installed.  
C. Place the chassis into the closet with the outdoor side  
facing the wall plenum opening.  
D. Slide the chassis into the wall plenum until the plenum  
divider seal is established and the factory-installed chassis  
to plenum gasket has sealed to the top flange of the  
plenum. (See Figure 10)  
Figure 10  
Chassis to  
plenum gasket  
Slide-in View / Chassis Installation  
TheVert-I-Pakchassismustbeinsertedinto  
the wall plenum so that the plenum divider  
gasket makes contact with the condenser  
baffle in the unit. The chassis will fit  
3
8
approximately 2 / " into the wall plenum.  
NOTE: Prior to installing the chassis,  
ensure that the drain pan and line are free  
from debris.  
23/8  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
7) Chassis Final Connections  
With the chassis in place, you are now ready to begin chassis  
connections:  
A. Move the thermostat switches to "OFF" and "AUTO." This  
will keep the thermostat from cycling the chassis until final  
connections are complete.  
RT2 Digital Thermostat  
B. Connecttheductworkontothe10"collar. Plasticwireties(field  
supplied)aresuggestedtosecuretheductworkinplace. Use  
2 wire ties, one for each inner and outer flex duct sleeve.  
D. For208Voltpoweronly: youmustmovethetransformerwire  
as shown in Figure 8, Page 9.  
III. Chassis Operation  
E. Review the Final Installation Checklist on Page 12 before  
replacing the power quick disconnect, reconnecting power  
to the chassis, plugging in the remote thermostat harness, or  
operating the chassis.  
9) Remote Thermostat Control  
Thechassisrequiresasimplesinglestageheat-coolwallthermostat.  
Each chassis comes with a terminal strip located in the electrical  
controlbox. Allinternalchassiswiring(low&highvoltage)isfactory  
ready for 230 Volt operation. For 208 Volt operation a single wire  
MUSTBECHANGEDONTHETRANSFORMER. RefertoFigure  
8 on page 9.  
Electricalshockandmovingpartshazardcancauseinjury  
or death. If you have not done so, pull out the disconnect  
headfoundonthefrontofchassisbeforecontinuinginstal-  
lation! Disconnect external power at the breaker.  
10) Low Ambient Protection  
EachchassisisequippedwithLowAmbientProtectionintheformof  
a suction line thermostat. This thermostat will prevent compressor  
operation at low suction line temperatures. Each chassis is also  
equipped with a factory installed bellows that will drain water from  
the base pan to prevent the fan slinger from freezing during winter  
weather.  
8) Final Installation Checklist  
Correct line voltage?  
o
11) Heating Defrost (Heat Pump Models Only)  
All Heat Pumps have a passive heating defrost system. Defrost  
occursasneededandautomaticallyswitchestoelectricheatduring  
defrost.Whentheoutdoorambienttemperaturedropsbelowa45°F  
factory setting, the chassis automatically switches to electric heat.  
As outdoor ambient temperatures rise above 45°F, the chassis  
returns to the heat pump mode. The changeover temperature  
is user adjustable from approximately 32°F - 55°F. The defrost  
thermostat may also be used to lock out the compressor in an  
emergency heat situation.  
Chassis deck level?  
o
Plenum divider baffle installed?  
o
Wall plenum caulked? Level? Flashing?  
o
HACR type breaker/fuse?  
o
Single circuit only?  
o
Ductwork connected?  
o
Chassis weather seal in place?  
o
Wall thermostat wired correctly?  
o
Chassis inserted into plenum?  
o
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
12) Fresh Air Door  
15) Routine Maintenance  
The Fresh Air Door is an "intake" system. The fresh air door is  
opened via a slide on the front of the chassis located just above  
the indoor coil. Move the slide left to open and right to close the  
fresh air door. The system is capable of up to 60 CFM of fresh air  
@ ~.3" H20 internal static pressure.  
Performing Routine Maintenance  
With the proper maintenance and care, your system will operate  
economically and dependably. Maintenance can be accomplished  
easily by referring to the following directions. However, before  
performing any maintenance, consider these important safety  
precautions:  
13) Condensate Disposal System  
The VPDP1 drain pan features two ꢀ female PVC fittings to  
attach a drain connection to on the left or right side of the drain  
pan. Condensate piping can be routed to the left, right or beneath  
the unit platform.  
WARNING:ElectricalShockHazard.Beforeattemptinganyservice  
work or routine maintenance, turn off all electrical connections to  
the unit. Failure to do so may result in property damage, personal  
injury and/or death.  
CAUTION: Although great care has been taken to minimize sharp  
edges in the construction of your unit, be extremely careful when  
handling parts or reaching into the unit.  
See page 8 or the drain pan installation manual for more  
information.  
Part 1: The system’s first stage increases energy  
efficiency utilizing a factory installed fan that slings  
the cold condensate onto the hot outdoor coil.  
Replace Air Filter  
A dirty air filter reduces the efficiency of your Vert-I-Pak and  
allows lint and dirt to accumulate on the indoor-air coil. Lint and  
dirt on the indoor-air coil can damage your unit and void the  
warranty. The air filter should be replaced as it becomes dirty.  
Part 2: When high outdoor humidity prevents the slinger  
from disposing of all the condensate, the excess  
condensate overflows into the condensate drain  
pan and out of the ꢀ" internal drain connections.  
To replace the filter (chassis mounted return air filter):  
1. Slide the filter clear of the filter rails.  
2. Remove the filter.  
Part 3: If Parts 1 & 2 fail for any reason, excess  
condensate overflows from a spillway directly into  
the wall plenum to the outside of the building. IF  
THIS OCCURS, THIS IS YOUR WARNING THAT  
THE CHASSIS OR DRAIN NEEDS SERVICING.  
3. Install new disposable filter.  
CAUTION: Do not operate your system without a filter in place,  
nor block the front of the unit return air opening.  
Inspect and Clean Indoor-air Coil  
IV. Service & Warranty  
14) Servicing / Chassis Quick Changeouts  
The chassis is designed for quick disconnect and change out. For  
minor electrical service, the control box cover lifts straight up after  
the screws & disconnect head are removed. For major electrical,  
refrigeration and fan service the chassis may be removed from  
utility closet.  
Eventually, minor amounts of lint and dirt may pass through the  
filter and collect on the indoor-air coil. These minor accumulations  
can be carefully vacuumed away with a brush attachment on  
a vacuum cleaner. Care must be taken to avoid bending the  
aluminum fins on the coil. Bent fins should be straightened using  
a special fin tool available from most HVAC service technicians.  
Inspect Outdoor-air Intake and Exhaust  
The unit’s outdoor-air intake and outdoor-air exhaust paths must  
remain clear. Check the OA exhaust frequently. Keep it free of all  
debris, snow, or ice. The OA intake should also be kept free of  
obstructions. Blocking the OA exhaust or OA intake opening will  
reduce the efficiency of your unit, could damage it, and may void  
your warranty.  
To Remove the Chassis from the Closet:  
A. Switch the wall Thermostat off.  
B. Pull the Power Disconnect located in the front of the chassis.  
C. Disconnect the thermostat wiring harness.  
D. Disconnect the electrical connection.  
E. Disconnect the ductwork.  
Inspect and Clean Condensate Drain  
The condensate drain must be routed to a suitable drainage  
area. Check the unit condensate drain periodically. Keep it free of  
anything that may block or impede the flow of condensate water.  
If there is any accumulation of foreign matter in the drain pipe, it  
should be removed and cleaned. The entire drain line must be  
protected from freezing.  
F. Slide the chassis out of the wall plenum.  
G. Lift the chassis out of the utility closet.  
16) Warranty  
Allserviceworkmustbedonebyaqualifiedservicer. SeeWarranty  
on the next page, and consult your dealer or contractor for details  
Electricalshockandmovingpartshazardcancauseinjury  
or death. Pull out the disconnect head found on the front  
of the chassis before servicing.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
FRIEDRICH AIR CONDITIONING CO.  
Post Office Box 1540 · San Antonio, Texas 78295-1540  
(210) 357-4400 · FAX (210) 357-4480  
VERT- I-PAK® A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONERS  
LIMITED WARRANTY  
SAVE THIS CERTIFICATE. It gives you specific rights, you may also have other rights which may vary from state to state and province  
to province.  
In the event that your unit needs servicing, contact your nearest authorized service center. If you do not know the nearest service center,  
ask the company that installed your unit or contact us - see address and telephone number below. To obtain service and/or warranty parts  
replacement, you must notify an authorized FRIEDRICH Air Conditioning Co. service center, distributor, dealer, or contractor of any defect  
within the applicable warranty period.  
When requesting service: please have the model and serial number from your unit readily available.  
Unless specified otherwise herein, the following applies:  
FRIEDRICH VERT-I-PAK A SERIES VERTICAL AIR CONDITIONERS AND HEAT PUMPS  
LIMITED WARRANTY - FIRST YEAR (Twelve (12) months from the date of installation). Any part found to be defective in the material  
or workmanship will be repaired or replaced free of charge by our authorized service center during the normal working hours; and  
LIMITED WARRANTY - SECOND THROUGH FIFTH YEAR (Sixty (60) months from the date of installation). ON THE SEALED  
REFRIGERATION SYSTEM. Any part of the sealed refrigeration system that is defective in material or workmanship will be repaired or  
replaced free of charge (excluding freight charges) by our authorized service center during normal working hours. The sealed refrigeration  
system consists of the compressor, metering device, evaporator, condenser, reversing valve, check valve, and the interconnecting tubing.  
These warranties apply only while the unit remains at the original site and only to units installed inside the continental United  
States,Alaska, Hawaii, Puerto Rico and Canada. The warranty applies only if the unit is installed and operated in accordance with  
the printed instructions and in compliance with applicable local installation and building codes and good trade practices.  
For international warranty information, contact the Friedrich Air Conditioning Company - International Division.  
Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part. Reasonable proof must  
be presented to establish the date of install, otherwise the beginning date of this certificate will be considered to be our shipment date plus  
sixty days. Replacement parts can be new or remanufactured. Replacement parts and labor are only warranted for any unused portion  
of the unit’s warranty.  
We will not be responsible for and the user will pay for:  
1. Service calls to:  
A) Instruct on unit operation. B) Replace house fuses or correct house wiring. C) Clean or replace air filters. D) Remove the unit  
from its installed location when not accessible for service required. E) Correct improper installations.  
2. Parts or labor provided by anyone other than an authorized service center.  
3. Damage caused by:  
A)Accident, abuse, negligence, misuse, riot, fire, flood, or acts of God. B) Operating the unit where there is a corrosive atmosphere  
containing chlorine, fluorine, or any damaging chemicals (other than in a normal residential environment). C) Unauthorized altera-  
tion or repair of the unit, which in turn affects its stability or performance. D) Failing to provide proper maintenance and service. E)  
Using other than a “Seacoast Protected” unit in a coastal environment. F) Using an incorrect power source. G) Faulty installation  
or application of the unit.  
We shall not be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure  
of this unit. We have not made and do not make any representation or warranty of fitness for a particular use or purpose and  
there is no implied condition of fitness for a particular use or purpose. We make no expressed warranties except as stated in  
this certificate. No one is authorized to change this certificate or to create for us any other obligation or liability in connection  
with this unit. Any implied warranties shall last for one year after the original purchase date. Some states and provinces do not  
allow limitations on how long an implied warranty or condition lasts, so the above limitations or exclusions may not apply to you. The provi-  
sions of this warranty are in addition to and not a modification of or subtraction from the statutory warranties and other rights and remedies  
provided by law.  
In case of any questions regarding the provisions of this warranty, the English version will govern.  
Rev 9-03  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
920-159-01 (10-03)  
IV. Vert-I-Pak Accessories  
MODEL  
DESCRIPTION  
PHOTO  
WALL PLENUM Two-part sleeve that telescopes in and  
out from 51/2" to 8" in depth. The wall plenum sits inside  
the exterior wall penetration.  
VPAWP1-8  
DIMENSIONS: 303/8" high x 241/8" wide.  
CUTOUT DIMENSIONS: 307/8" high x 245/8" wide.  
Same as VPAWP1-8, but telescopes 8" to 14" as required.  
VPAWP1-14  
ARCHITECTURAL LOUVER Extruded aluminum louver  
that attaches to the outdoor section of the wall plenum.  
DIMENSIONS: 311/16" high x 259/16" wide.  
VPAL2  
VPSC2  
Same as VPAL2 but can be ordered in a special color to  
match the exterior wall.  
DIGITAL THERMOSTAT Digital electronic thermostat with  
"one touch" adjustment. Mounts to wall for control of unit.  
RT2  
ACCESS PANEL / RETURN AIR GRILLE – Serves as  
an access panel to chassis and interior return air grille.  
A Þeld-supplied (25" x 20") Þlter is mounted inside the  
hinged access door.  
VPRG4  
DIMENSIONS: 58" high x 29" wide.  
CUTOUT DIMENSIONS: 553/4" high x 27" wide.  
RETURN AIR GRILLE – Interior return air grille that  
hinges to allow a Þeld supplied (16" x 20") Þlter to slip  
inside. Must be used when an access door / panel  
already exists in closet.  
VPRG2  
VPDP1  
DIMENSIONS: 187/16" high x 223/8" wide.  
DRAIN PAN for VEA/VHA24 models. Drain pan may be  
installed prior to chassis for easy installation/removal.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Use Factory Certified Parts.  
FRIEDRICH AIR CONDITIONING CO.  
Post Office Box 1540 · San Antonio, Texas 78295-1540  
4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212  
(210) 357-4400 · Fax (210) 357-4480  
920-159-01 (10-03)  
Printed in the U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Electro Voice Microphone HM1x User Manual
Evo Fitness Cooktop Affinity 30G User Manual
Fisher Price Offroad Vehicle M9780 User Manual
Fisher Price Riding Toy R8637 User Manual
Frigidaire Microwave Oven CPLMV169 User Manual
FujiFilm Digital Camera 16243252 User Manual
GE Air Conditioner AZ75E12DAC User Manual
GE Double Oven JKP90SP User Manual
Gefen Switch 3x1 HDMI Switcher User Manual
GE Heat Pump AZ85H18EAC User Manual