Faber Indoor Fireplace CADRA NOVA User Manual

SILENCE  
FEELING  
WHISPER  
SPECTRA NOVA  
CADRA NOVA  
MISTY  
room-sealed built-in gas-fireplace  
installation guide and user manual  
“Log Burner Technology”  
Saturnus 8  
NL-8448 CC Heerenveen  
NL-8440 AE Heerenveen  
Postbus 219  
T. +31(0)513 656500  
F. +31(0)513 656501  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
1. INTRODUCTION  
2. SAFETY AND GENERAL  
INFORMATION  
Note: these instructions should be read carefully and retained for  
future reference.  
Please leave these instructions with the user.  
Before installation, ensure that the local distribution conditions  
(identification of the type of gas and pressure) and the adjustment of  
the appliance are compatible.  
This guide is concerning the following types of appliances:  
Widescreen interior:  
Roundscreen interior:  
MV100 interior:  
Types Silence and Feeling  
Type Misty  
This gas appliance is factory set and shall not be adjusted by the  
installer.  
Type Whisper  
MV110 interior:  
Types Spectra Nova and Cadra Nova  
This appliance does not contain any component manufactured from  
asbestos or any asbestos related products.  
Special features:  
The pilot and flame sensing device fitted to this fire is also a safety  
device. If for any reason any part of the pilot assembly is to be  
replaced the entire assembly including the pilot burner, thermocouple,  
electrode and injector must be exchanged complete for a pilot assembly  
from the original manufacturer only.  
- Realistic flame and glow effect because of the "Log burner"  
technology.  
- Room sealed appliance, inlet and outlet are led to the outside  
using a natural draught concentric pipe system (100 mm/150 mm)  
(no power fan required). No additional ventilation required.  
Ventilation  
This appliance is room-sealed and doesn't require purpose provided  
ventilation.  
- Air supply and flue-gases go to outside atmosphere through wall or  
roof. A maximum horizontal extension of 6 meters is possible.  
- Remote Control option on all appliances.  
2.1 General safety  
- Meets the essential requirements of the European Gas Appliance  
Directive (GAD) and carries the CE mark.  
It is the law in the UK that all gas appliances, are installed by a  
competent person in accordance with the Gas Safety (Installation and  
Use) Regulations (as amended), the relevant British Standards for  
Installation work, Building Regulations, Codes of Practice and the  
manufacturers instructions.  
The installation should also be carried out in accordance with the  
following where relevant:  
BS5871 Part1  
BS5440 Parts 1 & 2  
BS1251.  
Building Regulations Document J (as applicable).  
2
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
3. INSTALLATION REQUIREMENTS  
Building Regulations and Standards issued as relevant by the  
Department of the Environment or the Scottish Development  
Department.  
Note:  
Since the appliance is a source of heat, circulation of air occurs.  
Therefore it is of importance that you do not use the appliance  
shortly after a renovation of the home. Because of the natural  
circulation of air, moist and volatile components from paint, building  
materials, carpet etc. will be attracted. These components can settle  
themselves down onto cold surfaces in the form of soot.  
In the Republic of Ireland installation should be carried out in  
accordance with IS813, ICP3, IS327, Building Regulations, Codes of  
Practice, the manufacturers instructions and any other rules in force.  
Failure to comply with the above could leave the installer liable to  
prosecution and invalidate the appliance warranty.  
As on all heat producing appliances, soft furnishings such as blown  
vinyl wallpaper placed too near to the appliance may become  
scorched or discoloured. This should be born in mind when installing  
the appliance.  
Safety instructions for the user: see chapter 9.  
3.1 Builders opening and surround  
The appliance can be installed in the following situations:  
In a non-combustible fireplace or builders opening. This could be either  
an existing builders opening or a new made prefab builders opening.  
For the measurements, see figure 1 and index.  
Although the appliance is tested for installation without a hearth, the  
appliance must not stand on combustible materials or carpets. If the  
appliance is placed on a combustible floor then a fibrelux or similar  
heatproof board of 12 mm thickness should be placed under it. Any  
under floor vents or openings within the builders opening should be  
sealed off.  
Do not place the lintel, surround or marble stone directly onto the  
appliance. If possible, apply a lintel made of cement or something  
similar.  
Isolate the appliance with a ceramic blanket (25 mm). See also  
chapter 4: Installation instructions.  
Preferred choice for insulation is unbound insulation wool (at  
1000 °C gives no smell).  
4
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
3.1 Builders opening and surround (continuing)  
If the builders' opening is constructed out of non-combustible  
F
composition board (Fibrelux) and you install the appliance without a  
mantel then:  
G
K
2
- Ventilate the space above the appliance (min. 1000 mm ).  
E
I
M
L
D
- Always fit the DC convection set.  
B
C
J
H
- The plaster of the outside has to be resistant to a high  
A
temperature. Use therefore the plaster materials especially made for  
this, to prevent discoloring (min. 100 °C temperature resistant).  
fig. 1  
If the appliance is to be fitted against a wall with combustible  
cladding, the cladding must be removed from the area covered by the  
surround.  
Builders opening (mm) Feeling  
Silence  
Whisper  
Spectra  
Nova  
780  
Cadra  
Nova  
680  
Misty  
A Opening width*  
B Opening height*  
C Opening depth*  
Shelf dimensions  
(combustible)  
960  
649  
385  
960  
649  
385  
780  
705  
430  
710  
890  
370  
698  
798  
The minimum height from the top surface of the fire to the underside  
of any shelf made from wood or other combustible materials is as  
follows:  
430  
430  
D Min. height shelf from  
top frame  
- For a shelf up to 150 mm deep – Minimum height = 350 mm  
(fig. 1).  
350  
150  
350  
150  
350  
150  
350  
150  
350  
150  
350  
150  
E Depth shelf max.  
Dimensions (mm)  
F Box width  
- If the shelf depth is greater than 150 mm add 50 mm to the upper-  
clearance height for every 25 mm increase in shelf depth.  
880  
366  
636  
1064  
678  
47  
880  
366  
636  
1064  
678  
20  
750  
397  
714  
815  
720  
16  
750  
375  
715  
794  
703  
30  
650  
375  
815  
694  
803  
30  
698  
338  
879  
740  
905  
144  
G Box depth  
H Box height  
- Side clearance = Minimum distance from the side of the fire frame  
to combustible material = 150 mm.  
I
J
Frame width  
Frame height  
K Frame thickness  
L Position flue  
(behind  
frame)255  
255  
257  
111  
235  
235  
196  
140  
M Position flue (from the  
back side  
box)111  
140  
140  
142  
*the points A until C applies a tolerance from:  
– 0 mm and + 5 mm.  
table 1  
6
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
3.2 Flue requirements  
Flue restrictor  
The appliance is of the type C11/C31. The appliance will need to be  
If applicable, in the table is also stated the size of a flue restrictor.  
This restrictor needs to be fitted in the combustion chamber when  
placing the appliance ( see chapter 4.2). Normally the smallest flue  
restrictor is fitted.  
supplied with the approved flue pipes and terminal, it is not possible to  
supply your own.  
The minimum effective height of the flue system must be 0.5 or 1 meter,  
depending on the appliance.  
Terminal locations, through the wall as well as through the roof. See  
figure 3.  
Flue routing;  
- a horizontal extension with elbows is allowed for a maximum of  
6 meters (depending on the type and situation).  
- vertical max. 12 meters.  
Determine on the base of the table 2 and 3, depending on the type  
and terminal position, if the desired situation is possible.  
To establish this you will need to calculate:  
- The effective height (this is the real difference in height between the  
upper side of the appliance and the terminal).  
- The total horizontal extension. This is the total horizontal flue length  
where:  
• each elbow, which is in the horizontal area, counts for 2 meters.  
• each 45-degree bend, which is in the horizontal area, counts for  
1 meter.  
• elbows and bends at the transition of horizontal to vertically are  
not to be counted.  
• the wall mounted terminal counts for 1 meter.  
8
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
Example calculation 1  
Table Silence and Feeling with interior Widescreen  
Determine according to the table 2 the right total horizontal- and vertical length.  
When meeting an X, and when the values are outside the table, the combination is  
not allowed. Normally the 30 mm flue restrictor is preinstalled.  
Calculati0n horizontal extension fig. 2a:  
Flue lenght C + E = 1m + 1m  
Elbows = 2m  
2 m  
2 m  
D
Total horizontal extension  
4 m  
Horizontal extension  
Measure or calculate effective height (Hvert)  
0
1
2
3
4
5
6
0
1
1,5  
2
3
4
5
6
7
8
Flue lenght A  
1 m  
1 m  
X
0
0
X
0
0
X
X
0
X
X
0
X
X
X
0
X
X
X
0
0
0
30  
30  
30  
X
X
X
X
X
X
X
X
0
0
0
0
0
X
X
X
X
X
X
Roof mounted terinal  
G
F
X
combination  
not allowed  
Total effective height  
2 m  
30  
45  
45  
50  
50  
60  
60  
65  
65  
65  
65  
30  
45  
45  
50  
50  
60  
60  
65  
65  
65  
0
0
When calculating on basis of the  
Widescreen table nr. 2:  
It is allowed.  
0 remove flue restrictor  
30  
30  
45  
45  
50  
60  
60  
65  
30  
30  
30  
30  
45  
50  
60  
0
E
Number is size in mm  
of the flue restrictor  
30  
30  
30  
45  
50  
C
B
Remove the flue restrictor!  
D
When calculating on basis of the  
MV100 table nr. 3:  
Allowed but without flue restrictor.  
Remove the flue restrictor!  
A
9
X
When calculating on basis of the  
MV150 table nr. 4:  
Allowed but without flue restrictor.  
Remove the flue restrictor!  
10  
11  
12  
X
X
X
X
X
X
X
X
table 2  
interior Widescreen  
X
When calculating on basis of the  
Roundscreen table nr. 5:  
Allowed but without flue restrictor.  
Remove the flue restrictor!  
Table Whisper and Spectra Nova with interior MV100  
fig. 2a  
Determine according to the table 3 the right total horizontal- and vertical length.  
When meeting an X, and when the values are outside the table, the combination is  
not allowed. Normally the 30 mm flue restrictor is preinstalled.  
Example calculation 2  
Calculati0n horizontal extension fig. 2b:  
Flue lenght J + L = 0,5 + 0,5  
1 m  
4 m  
1 m  
Elbows  
K + M = 2m + 2m  
Horizontal extension  
Terminal  
0
X
1
X
0
2
X
0
0
30  
30  
45  
45  
60  
60  
60  
65  
3
X
0
0
0
4
X
0
0
0
5
X
0
0
0
0
0
0
45  
X
X
X
X
X
6
Total horizontal extension  
6 m  
0
1
2
3
4
5
6
7
8
X
0/X*  
0
0
0
0
0
30  
30  
45  
45  
50  
50  
60  
60  
65  
65  
65  
65  
X
0
combination  
not allowed  
remove flue restrictor  
Vertical  
30  
45  
45  
50  
50  
60  
60  
65  
65  
65  
X
M
Flue lenght  
H
1 m  
L
N
0
0
I
J
K
When calculating on basis of the  
Widescreen table nr. 2:  
Combination not allowed.  
Number is size in mm  
of the flue restrictor  
45  
45  
50  
60  
60  
X
X
X
30  
30  
50  
50  
X
X
X
X
X
X
X
X
X
X
When calculating on basis of the MV100  
table nr. 3:  
Allowed but without flue restrictor.  
Remove the flue restrictor!  
H
9
10  
11  
12  
When calculating on basis of the MV150  
table nr. 4:  
Combination not allowed.  
X
X
table 3  
interior MV100  
When calculating on basis of the  
Roundscreen table nr. 5:  
Combination not allowed.  
* at propane not allowed  
fig. 2b  
10  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
Table Cadra Nova with interior MV150  
3.2 Flue requirements (continuing)  
3.2.1 Terminal position  
Determine according to the table 4 the right total horizontal- and vertical length.  
When meeting an X, and when the values are outside the table, the combination is not  
allowed. Normally the 30 mm flue restrictor is preinstalled.  
Verify if the required terminal position meets the local installation  
regulations regarding disturbance, good functioning and ventilation.  
(Also see: safety requirements).  
Horizontal extension  
0
X
X
1
X
0
2
X
X
0
3
X
X
0
0
4
X
X
0
0
0
0
30  
40  
40  
5
X
X
0
0
6
Note:  
0
0,5  
1
2
3
4
5
6
7
8
9
10  
11  
12  
X
X
X
0
0
0
0
0
X
X
X
X
X
X
The terminal must be located so that the outlet is not obstructed. If  
the flue terminal is located within 2 meters of a footway, path or  
where people could come into contact with it then a suitable  
terminal guard must be fitted.  
X
0
combination  
not allowed  
remove flue restrictor  
30  
30  
40  
40  
50  
50  
50  
60  
60  
60  
65  
X
40  
40  
50  
50  
50  
60  
60  
60  
65  
65  
65  
0
30  
40  
40  
50  
50  
50  
60  
60  
X
X
0
0
0
30  
40  
40  
40  
50  
Number is size in mm  
of the flue restrictor  
30  
30  
40  
X
X
X
X
X
Terminals located close to shared walkways, footpaths etc. could be  
subject to legal constraints and this should be pointed out to the  
customer before installation. If in any doubt about flue location  
advice should be sought from local building control, or if appliance-  
related, from the manufacturer including wherever possible a  
dimensioned sketch.  
50  
50  
X
X
X
X
X
X
X
table 4  
interior Cadra Nova  
X
Misty with roundscreen  
Avoid locating the terminal in close proximity to plastic materials  
such as gutters or other combustibles. If this is unavoidable then a  
suitable deflector should be made.  
Determine according to the table 5 the right total horizontal- and vertical length.  
When meeting an X, and when the values are outside the table, the combination is not  
allowed. Normally the 30 mm flue restrictor is preinstalled.  
Some important requirements for a good functioning are:  
Horizontal extension  
The wall-mounted terminal has to be at a distance of at least  
0
1
2
3
4
X
X
0
0
0
0
0
30  
40  
40  
50  
5
X
X
X
0
0
6
0.5 meters off:  
0
0,5  
1
X
X
X
X
0
X
X
X
X
X
X
X
0
0
0
0
0
0
X
X
X
X
X
X
- Corners of the building.  
X
0
combination  
not allowed  
remove flue restrictor  
30  
30  
30  
40  
40  
50  
50  
50  
60  
60  
60  
65  
0
0
- Below eaves.  
1,5  
2
3
4
5
6
7
8
9
40  
40  
40  
50  
50  
50  
60  
60  
60  
65  
65  
65  
0
0
0
0
0
30  
40  
40  
40  
50  
50  
- Balcony's etc. unless the duct is dragged to the front side of the  
overhanging part.  
30  
40  
40  
50  
50  
50  
60  
60  
0
0
Number is size in mm  
of the flue restrictor  
30  
30  
40  
X
X
X
X
X
The roof mounted terminal has to be at a distance of at least  
0.5 meters of the sides of the roof, excluded the ridge.  
X
10  
11  
12  
X
X
X
X
X
X
table 5  
interior Roundscreen  
X
X
X
12  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
Flue terminal positions  
Table 6  
Dimension Terminal position  
Balanced flue room sealed  
(kW  
input  
7.5  
kW  
expressed  
in  
A
B
C
Direct below an opening, airbrick,  
opening windows, etc.  
Above an opening, airbrick,  
opening window ect.  
300 mm  
300 mm  
300 mm  
Horizontally to an opening, airbrick,  
opening window etc.  
D
E
F
G
H
I
Below gutters, soil pipes or drain pipes  
Below eaves  
500 mm  
500 mm  
600 mm  
300 mm  
600 mm  
300 mm  
600 mm  
600 mm  
1200 mm  
Below balconies or car port roof  
From a vertical drain pipe or soil pipe  
From an internal or external corner  
Above ground roof or balcony level  
From a surface facing the terminal  
From a terminal facing the terminal  
From an opening in the carport (e.g.  
window) into the dwelling  
J
K
L
M
N
P
Vertically from a terminal on the same wall  
1500 mm  
fig. 3  
Horizontally from a terminal on the same wall 300 mm  
From a vertical structure on the roof  
Above intersection with roof  
600 mm  
500 mm  
Q
14  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
Example of how terminal position is measured  
4. INSTRUCTIONS FOR INSTALLATION  
4.1 Gas connection  
1. Installation pipes should be in accordance with BS 6891. Pipe work  
from the meter to the appliance must be of adequate size.  
2. The complete installation including the meter must be tested for  
soundness and purged as described in the above code.  
3. A means of isolation must be provide in the supply to facilitate  
servicing.  
4. The connection should be made in 8 mm copper or similar semi  
flexible tube. (max 1 meter). Ensure that the gas pipe does not  
interfere with the removal or replacement of the burner tray of the  
controls.  
5. The gas connection is nut and olive suitable for 8 mm pipe.  
A
C
&
=
B
=
Behind surround  
-
Sleeve pipe through surround  
Through wall  
-
Pipe must be sleeved and sealed to fire  
C
fig. 4  
outer wall  
cavity  
3.2.2 Using an existing chimney as air inlet  
inner wall  
You can connect the appliance onto an existing chimney. The existing  
chimney then functions as air supply, where a flexible stainless steel  
liner (to BS715) of 100 mm performs the flue function.  
A
B
surround  
marble  
Requirements:  
- Any existing chimney used as an air supply must only service this  
appliance.  
fig. 5  
gas supply routes when fire is fitted in a deep surround  
- A chimney that has previously been used for solid fuel must be swept  
before use.  
4.2 Preparing the appliances Widescreen and Whisper  
- The existing chimney needs to be airtight.  
- The existing chimney needs to have an opening of  
min. 150 x 150 mm.  
1. Open the ashtray door by pushing on the right side for the  
Silence/Feeling and on the left side for the Whisper. Remove the  
frame by loosening the screws A behind the door (see fig. 5).  
Lift and pull forward when you take it away.  
- The chimney needs to be intact and well looked after.  
- Use the adjustable roof-mounted-terminal especially made for this,  
and the chimney connection set.  
- The minimum distance between two terminals should be at least  
450 mm.  
16  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
4.2 Preparing the appliances Widescreen and Whisper (continuing)  
4.2 Preparing the appliances Widescreen and Whisper (continuing)  
C
C
C
2.  
C
C
C
C
C
C
C
A
fig. 8  
A
A
fig. 6  
4. Take the box with the log set out of the combustion chamber.  
Remove the back panel by loosening the screws B (see fig. 6).  
5. Place the right flue restrictor in the combustion chamber. To  
determine the right flue restrictor, see chapter 3.  
B
B
B
B
B
fig. 7  
3. Remove the glass by removing the glass clamps C (see fig. 7) for  
instance with a screwdriver. Careful when removing the glass! Wear  
gloves! Before placing the glass back, be sure that there are no  
fingerprints on the glass, it is not possible to remove those prints  
after you burn the appliance or a while (they will be burnt in).  
fig. 9  
18  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
4.3 Preparing the appliance Misty  
4.3 Preparing the appliance Misty (continuing)  
4. Take the box with the log set out of the combustion chamber.  
5. Place the right flue restrictor in the combustion chamber. To  
determine the right flue restrictor, see chapter 3.  
fig. 10  
1. Remove the door frame. Lift and pull forward (see fig. 10).  
2. Open the ashtray door by pulling down (bottom handle).  
C
fig. 12  
C
fig. 11  
3. To open the door, remove the screws C (see fig. 11). The door  
opening is limited; if you need more space then remove the door (lift  
and pull forward). Be sure that there are no fingerprints on the glass.  
It is not possible to remove those prints after you burn the appliance  
for a while (they are burnt in).  
20  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
4.4 Preparing the appliances Spectra Nova/Cadra Nova  
4.4 Preparing the appliances Spectra Nova/Cadra Nova (continuing)  
4. Take the box with the log set out of the combustion chamber.  
5. Place the right flue restrictor in the combustion chamber. To  
determine the right flue restrictor, see chapter 3.  
fig. 13  
1. To open the door, remove the screws A (see fig. 13). Open and  
remove the door; lift and pull forward. Be sure that there are no  
fingerprints on the glass. It is not possible to remove those prints  
after you burn the appliance for a while (they are burnt in).  
fig. 15  
fig. 14  
2. Remove the back panel by loosening the 4 screws B (see fig. 14).  
22  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
4.5 Fitting the firebox  
4.5 Fitting the firebox (continuing)  
Points of attention for placement:  
ceramic  
blanket  
ceramic  
blanket  
- If possible, first locate the appliance before assembling the flue.  
- If this is not possible then always use an extendible pipe before  
connection onto the appliance.  
ceramic blanket  
1. Position the firebox in the fireplace opening. You can adjust the  
height with the 4 adjustable feet.  
ceramic  
blanket  
ceramic  
blanket  
2
Make the gas connection according to the instructions (also see gas  
connection, chapter 4.1).  
3. Assemble the flue system onto the firebox (see chapter 5).  
fig. 17  
4. Check if applicable that the safety hatch seals the combustion  
chamber properly.  
8. Spread, the bags of embers (imitation ashes) provide with the  
appliance over the burner tray.  
Attention! No embers on the grid end between the logs and the  
burner tray.  
9. Before placing the glass; check the glass sealing rope is in good  
condition and makes an effective seal. Be sure that there are no  
fingerprints on the glass. It is not possible to remove those prints  
after you burn the appliance for a while (they are burnt in).  
safety hatch  
- Widescreen and Whisper; Place the glass in front of the appliance  
and fix it with the glass clamps. Replace the frame.  
- Misty, Cadra Nova and Spectra Nova:  
fig. 16  
Place the door and fix it. Check on visual leakages around the  
door sealing.  
5. If necessary, place the DC convection system (also consult the  
instruction belonging to the DC construction set).  
10. Misty and widescreen: Fix the back and top or door frame (the back  
frame first).  
6. Isolate the firebox with a ceramic blanket (25 mm). Preferred choice  
for insulation is unbound insulation wool (at 1000 °C gives no  
smell).  
7. Place the log set (see placing log set, chapter 4.4).  
24  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
4.6 Placing the log set  
5. INSTALLATION OF THE FLUE  
Never place extra elements of any kind into the combustion chamber.  
5.1 Connections with use of concentric duct material  
To guarantee good combustion, the log set may only be installed in  
the way specified by Faber International. Any other arrangement can  
lead to soot on logs or window. Do not use the fire with broken or  
missing logs.  
- Build the system starting from the appliance on.  
- Make a hole of ø 153 mm for the wall or roof mounted terminal.  
4.6.1 Placing the log set Widescreen, Whisper, Spectra Nova, Misty and Cadra Nova  
- Make sure you place the pipes in the right direction, the narrow  
end towards the appliance.  
- Make sure the pipes are fixed sufficiently, a wall clamp every 2m, so  
the weight of the pipes is not resting onto the appliance.  
- The outside of the pipe can become hot (140 degrees). Stay 50 mm  
away from wall surface or sealing. Make sure to provide sufficiently  
heat resistant isolation when going through the wall or roof.  
fig. 18  
- Because of expansion or cooling down the concentric pipes can turn  
loose. It is recommended to fix the spring clip with a self tapping  
screw at inaccessible places.  
- To get the exact measure flue length you can use cut down-  
concentric pipe, wall mounted terminal or roof mounted terminal. To  
obtain a smoke sealed connection, the inner pipe must be 20 mm  
longer then the outside pipe.  
fig. 19  
On the bottom of the logs is a identification:  
- The horizontal pipes need to rise away from the appliance at a rate  
of 3 degrees per metre.  
• L  
• R  
location on the left side resting on the rear log.  
location on the right side resting on the rear log.  
• 1 dimple first log left placed over the burner and resting on the  
burner tray.  
• 2 dimples placed in the middle over he burner and resting on the  
burner tray.  
• 3 dimples the right side log placed over the burner and resting on the  
burner tray.  
Attention! Beware that there are no embers between the logs and the  
burner tray.  
26  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
5.2 Connection onto an existing chimney  
5.2 Connection onto an existing chimney (continuing)  
You can connect the appliance onto an existing chimney. The existing chimney then  
functions as air supply, where a flexible stainless steel liner (to BS715) of 100 mm  
performs the flue function. Any existing chimney used as an air supply must only  
service this appliance.  
5. Fixing the chimney sealing plate (D) and place the 150 mm  
grommet into the hole of the sealing plate.  
6. Fix the sealing plate air tight into the builders opening (use the  
isolation rope from the chimney connection set to make the plate  
air tight).  
Requirements:  
- 300 mm of free space above the appliance;  
- The chimney only supply’s air to this appliance;  
- The existing chimney needs to be clean and very well swept;  
- The existing chimney needs to be airtight;  
- The existing chimney needs to have an opening of  
min. 150 x 150 mm.  
7. Slide the pipe (E) 150mm length 500mm into the sealing plate.  
Slide this pipe so far that you will have enough space later on  
for assembling the liner.  
8. Install the appliance.  
Parts needed for this kind of installation:  
- Chimney connection set  
9. Connect the flexible stainless steel liner onto the appliance using  
the 100mm pipe (F) as adapter.  
part number A9225000  
- Short roof terminal  
Fig 20 part D  
Fig 19 part B  
Fig 19 part A  
B
A
part number A9266100  
- Chimney closure plate  
part number A 9240000  
10. If the distance from the flue outlet to the sealing plate is bigger  
then 300 mm, you have to use a concentric pipe first.  
C
- Two stainless steel tubes one 100 mm -  
length 500 mm and one 150 mm -  
length 500 mm  
11. Slide the outside pipe onto the appliance or concentric extension  
so that you have a air tight connection.  
part number A 9273900  
Fig 19 part E and F  
1. Place the aluminium closure plate (A) onto the  
chimney. Permanently attach and make airtight.  
D
2. Pull the liner (C) through the chimney.  
F
E
3. Connect the liner onto the roof terminal and fix  
this with the clamp provided with the chimney  
connection set.  
4. Place the roof terminal onto the closure plate.  
fig. 20  
28  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
5.3 Remote control (if applicable)  
The remote control is only meant to regulate the flames, it functions  
only when the pilot burner is ignited. It is therefore not possible to  
ignited the appliance with the remote control or to shut-off the pilot-  
flame.  
fig. 22  
The radio-frequency remote control is intended for fireplaces installed  
in a domestic setting in all EU countries except Austria, Denmark,  
Finland and Greece.  
3. Connect the wires to the gas valve (see fig. 22).  
Features:  
4. Check that there are batteries in the transmitter.  
See "Replacing batteries", see chapter 10.4.4.  
- Manual control will always remain possible.  
- The remote control is a radio frequency type and has been approved  
internationally.  
5. Set the on/off switch on the receiver to "on".  
- The remote control generates a unique safety code every time you  
activate the transmitter, its similar to those used in a car.  
- The remote control is easy to install retrospectively.  
Setting the right transmission code  
The receiver has to learn the code from the transmitter, which is already  
done at the factory. However the code disappears if the receiver is  
disconnected from the mains for a longer period.  
5.3.1 Installation remote control  
1. Connect the mains adapter to the receiver box. The adapter is set  
to the correct voltage in the factory 4.5V.  
1. Push the "mod" button on the receiver and hold it for 3 seconds.  
2. The green control lamp will light up and stay on. Repeat this step  
if it doesn't.  
3. Push a button on the remote control. The control lamp on the  
receiver should now go out.  
4. Again push a button on the remote control. The lamp starts  
flashing and will switch off eventually.  
fig. 21  
2. Slide the receiver box into the holder.  
5. The receiver now recognizes the remote control. The remote  
control now functions.  
6. Check if you can hear a sound and the motor runs when you  
push a button on the remote control.  
30  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
6. COMMISSIONING (functional checks)  
6.3 Functional balanced flue check  
1. Set the appliance on max. input.  
6.1. Check pilot ignition  
2. Verify the flame picture, this means no flames against the  
window, the flame have to come besides the logs, if not check  
the log layout.  
1. Push in and turn the control knob (A) from { anticlockwise to the  
setting (small flame). You will hear a tick meaning there is  
3. Check if the flames are yellow after 10 minutes of operation. If  
you still have a blue flame or the appliance goes out check:  
- If the flue pipes are fitted correctly (no leakage).  
- If the wall mounted terminal is placed with the correct side up.  
- If the correct flue restrictor is installed.  
ignition. Hold the knob in and wait for a few seconds while the air  
is purged.  
2. Bring the knob back in the start position and turn the knob several  
times to the  
position. Check that the pilot has lit.  
3. Continue to hold in the control knob for a further ten seconds to  
ensure that the pilot flame is stable.  
4. Release the knob. The pilot should remain alight.  
A
B
D
C
C
A
B
B
A
fig. 24  
6.4 Check reference pressure  
The appliance is preset to give the correct heat input.  
fig. 23  
No further adjustment is necessary. Fit a pressure gauge at the test  
point D to check the burner pressure.  
6.2 Functional burner check  
The pressure should be checked with the appliance alight and at max  
1. Turn knob (B) to max. clockwise.  
2. Turn the knob (A) more anticlockwise to the  
input.  
position (large  
The setting pressure should be as shown at the technical data  
page 41.  
flame). Now it is possible to light the main burner.  
3. Turn knob B anticlockwise to max. The main burner should light.  
Check for gas soundness at all joints with leak detection floud!  
4. Check the ignition of the main burner on low and high setting.  
5. Turn knob B clockwise till {. The main burner is off.  
6. Turn the knob A to {. The pilot should go out.  
After checking the pressure, turn off the appliance. Remove the  
pressure gauge and close the sealing screw. Re-light the appliance.  
Turn to max. input and test around the test point D for gas  
soundness using a suitable leak detection fluid.  
32  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
7. HANDING OVER  
8. SERVICING  
(final check and customer briefing)  
To ensure safe, efficient operation of the appliance, it is necessary to  
carry out routine servicing at regular intervals.  
7.1  
Instruct the customer on the full operation of the appliance.  
7.2.1 Advise the customer how to clean the appliance including the  
It is recommended, that the fire is inspected/serviced by a competent  
person at least once a year.  
glass.  
7.2.2 Instruct the customer on the operation of the remote control,  
including replacement of batteries and how to set the right  
transmissions code.  
Important  
Turn off the gas supply before commencing any servicing. Always  
test for gas soundness after refitting the appliance.  
7.2.3 Hand over these instructions including the user guide to the  
consumer.  
8.1 Routine annual servicing  
7.2.4 Recommend that the appliance should be serviced by a  
1. Clean (if necessary):  
competent person at least once a year.  
- the pilot system;  
- the burner;  
- the combustion chamber;  
- the glass.  
2. Check the log lay and replace the embers (if applicable).  
3. Do the functional test as described at page 34.  
4. Check the flue system and terminal on damage and soundness  
(visual inspection).  
34  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
8.1.1 Cleaning the glass  
8.1.4 Burner tray assembly  
Depending on the intensity of use, you can get a deposit on the  
1. Remove the front, glass, log set, grid and burner tray cover.  
2. Break the gas supply at the control valve.  
3. Unscrew the burner assembly and take them out of the combustion  
chamber.  
glass. This can be removed with a special ceramic glass cleaner  
(ceramic cook-top cleaner) as follows:  
1. Remove the front and the back.  
2. Clean the glass. Handle the glass with clean hands, wear gloves if  
possible.  
B
3. To fit the glass, proceed in reverse order. Make sure that the log  
set has been installed correctly before fixing the glass.  
A
D
C
Attention:  
Before placing the glass: check the glass sealing rope is in good  
condition and makes an effective seal. Be sure that there are no  
fingerprints on the glass. It is not possible to remove those prints  
after you burn the appliance for a while (they are burnt in). Place  
the glass in front of the appliance and fix the glass frame or use the  
glass clamps.  
E
F
8.1.2 Cleaning the combustion chamber and burner  
fig. 25  
You can clean the combustion chamber with a vacuum cleaner.  
A. Pilot assembly  
B. Burner  
If the burner is visibly damaged, this can affect the distribution of  
the flame, if so then replace the burner.  
C. Fixation plate  
D. Injector  
8.1.3 Propane conversion  
E. Gas control  
F. Receiver  
For conversion from propane to natural gas, order for a propane  
burner unit.  
Please give the serial number from the data plate when you order.  
8.1.5 Pilot/thermocouple assembly  
Remove the burner tray as described above.  
Now you have access to all the pilot and thermocouple parts.  
36  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
8.1.7 Combustion test  
8.1.6 Gas control block  
A BS7967 combustion analysis check should be carried out using an  
analyser to BS7927 positioned in the flue outlet.  
A Ratio of CO/CO2 should be less than 0.01 within 30 minutes.  
(100ppm CO per 1% CO2).  
A reading of CO in the room centre should give a rise of less than  
9ppm over ambient, peak reading.  
A
B
A
B
D D  
C
C
A
B
C
D
Governor  
fig. 26  
Adjusting screw pilot flame  
Inlet pressure test point  
Burner pressure test point  
38  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
8.2 LIST OF SPARE PARTS  
8.3 TECHNICAL DATA  
Widescreen Silence en Feeling C11/C31  
Country  
UK/IRL  
UK/IRL  
II2H3+  
Category  
II2H3+  
Whisper Feeling  
Silence  
Misty  
Spectra Cadra  
Nova Nova  
Company Company Company Company Company Company  
part part part part part part  
Model type  
C11 0f C31  
C11 0f C31  
Description  
Heat input Hi  
Efficiency class  
NOX class  
kW  
7,5  
2
7,2  
2
Surround antracite  
Glass  
A9271453 A9270053 A9267753 AA9272853 A9274149 A9274249  
04508200 04508300 04508300 04509000 4509500 04509300  
04509600 04509400  
4
4
Type of gas  
Inlet pressure  
G20  
G30  
30 / 37  
mbar 20  
Glass below  
Burner NG  
Burner propane  
Log set  
x
x
x
x
20521808 20521808 20521808 20521808 20521808 20900166  
20521835 20521835 20521835 20521835 20521835 20900167  
20773200 20774500 20772500 20786130 20773700 20773700  
06017300 06017300 06017300 06017300 06017300 06017300  
20604000 20604000 20604000 20604000 20604000 20604000  
20603900 20603900 20603900 20603900 20603900 20603900  
20900142 20900142 20900142 20900142 20900142 20900142  
37003089 37003089 37003089 37003089 37003089 37003089  
control)37003086 37003086 37003086 37003086 37003086 37003086  
Gas rate 15 °C / 1013 mbar  
m3/h 740  
kg/h  
231  
540 g  
Reference burner pressure  
Injector size  
mbar 17  
22  
Spark wire  
Receiver  
mm  
mm  
3x 1,45  
3x 1,00  
1,1  
Remote control  
Adapter  
1x 1,30  
1,8  
Reduced input restrictor  
Gas control  
Pilot assembly  
Type  
Motor  
(remote  
SIT 160  
Nr 51  
SIT 160  
Nr 30  
Pilot burner assemb. NG 20900145 20900145 20900145 20900145 20900145 20900145  
Pilot burner assemb.  
Code  
propane  
20900154 20900154 20900154 20900154 20900154 20900154  
37002033 37002033 37002033 37002033 37002033 37002033  
06006600 06006600 06006600 06006600 06006600 06006600  
20900019 20900019 20900019 20900019 20900019 20900019  
Flue system  
Thermocouple  
Spark electrode  
Embers  
MV size  
100-150  
30  
100-150  
30  
Preinstalled flue restrictor  
mm  
Gas control  
GV36 with  
GV36 without  
pressure reg.  
Heat resisting paint  
pressure reg.  
spray for comb. chamb. 09000008 09000008 09000008 09000008 09000008 09000008  
Set of glass clips  
20900008 20900008 20900008  
28103900 28103900 28103900  
x
x
x
x
x
x
Remote control  
Adapter  
V
4,5  
Touch Latch assembly  
Batteries remote control  
2x LR03 1,5 V Alkaline  
Gas connection  
mm  
8 mm nut  
and olive.  
18 mm nut  
and olive  
Dimensions: see table 1  
40  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
8.3 TECHNICAL DATA  
8.3 TECHNICAL DATA  
MV100 Whisper and Spectra Nova  
MV150 Cadra Nova  
Country  
UK/IRL  
II2H3+  
UK/IRL  
II2H3+  
Country  
UK/IRL  
II2H3+  
UK/IRL  
II2H3+  
Category  
Category  
Model type  
C11 0f C31  
C11 0f C31  
Model type  
C11 0f C31  
C11 0f C31  
Heat input Hi  
Efficiency class  
NOX class  
kW  
7.5  
2
7.5  
2
Heat input Hi  
Efficiency class  
NOX class  
kW  
7,5  
2
7,5  
2
4
4
4
4
Type of gas  
Inlet pressure  
G20  
20  
G30  
30/37  
Type of gas  
Inlet pressure  
G20  
20  
G30  
30/37  
mbar  
mbar  
Gas rate 15 °C / 1013 mbar  
m3/h  
kg/h  
800  
231  
Gas rate 15 °C / 1013 mba  
m3/h  
kg/h  
790  
17  
231  
540 g  
540 g  
Reference burner pressure  
Injector size  
mbar  
mm  
13  
25  
Reference burner pressure  
Injector size  
mbar  
mm  
22  
3x 1.50  
1.8  
3x 0.90  
1.1  
2x 1,40  
1x 1,30  
1,8  
3x 1,00  
1,1  
Reduced input restrictor  
mm  
Reduced input restrictor  
mm  
Pilot assembly  
Type  
Pilot assembly  
Type  
SIT 160  
Nr 51  
SIT 160  
Nr 30  
SIT 160  
Nr 51  
SIT 160  
Nr 30  
Code  
Code  
Flue system  
Flue system  
MV size  
100-150  
30  
100-150  
30  
MV size  
100-150  
30  
100-150  
30  
Preinstalled flue restrictor  
mm  
Preinstalled flue restrictor  
mm  
Gas control  
GV36 with  
GV36 without  
Gas control  
GV36 with  
GV36 without  
pressure reg. pressure reg  
pressure reg. pressure reg.  
Remote control  
Voltage adapter  
Batteries  
V
4,5  
Remote control  
Voltage adapter  
Batteries  
2x LR03 1,5 V Alkaline  
V
4,5  
2x LR03 1,5 V Alkaline  
Gas connection  
mm  
kg  
8 mm nut  
and olive  
8 mm nut  
and olive  
Gas connection  
mm  
kg  
8 mm nut  
and olive  
8 mm nut  
and olive  
Weight incl. packing material  
Dimensions: see table 1  
75  
75  
Weight incl packing material  
Dimensions: see table 1  
75  
75  
42  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
8.3 TECHNICAL DATA  
Roundscreen Misty  
Country  
UK/IRL  
II2H3+  
UK/IRL  
II2H3+  
Category  
Model type  
C11 0f C31  
C11 0f C31  
Heat input Hi  
Efficiency class  
NOX class  
kW  
8,5  
2
8,5  
2
4
4
Type of gas  
Inlet pressure  
G20  
20  
G30  
30 / 37  
USER GUIDE  
mbar  
Gas rate 15 °C / 1013 mbar  
m3/h  
kg/h  
900  
231  
540 g  
Reference burner pressure  
Injector size  
mbar  
mm  
16  
25  
3x 1,50  
1,8  
3x 0,95  
1,1  
Reduced input restrictor  
mm  
Pilot assembly  
Type  
SIT 160  
Nr 51  
SIT 160  
Nr 30  
Code  
Flue system  
MV size  
100-150  
30  
100-150  
30  
Preinstalled flue restrictor  
mm  
Gas control  
GV36 with  
GV36 without  
pressure reg. pressure reg.  
Remote control  
Voltage adapter  
Batteries  
V
4,5  
2x LR03 1,5 V Alkaline  
Gas connection  
mm  
8 mm nut  
and olive  
8 mm nut  
and olive  
Dimensions: see table 1  
44  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
9. SAFETY INSTRUCTIONS FOR THE  
USER  
IMPORTANT  
A suitable Fireguard conforming to BS6539 and BS6778 should be used  
with this appliance to protect children, the elderly or infirm. Care  
should also be taken with pets.  
9.1 General safety instructions  
In your own interest and that of safety, all gas appliances must be  
installed by competent persons. Installation must be in accordance with  
National Regulations. CORGI registered installers are required to work to  
recognised standards.  
If a gas leak is found or suspected, turn off the gas supply at the  
meter and contact your installer or gas emergency service.  
These instructions should be read carefully and retained for future  
reference.  
Note:  
Since the appliance is a source of heat, circulation of air occurs.  
Therefore it is of importance that you do not use the appliance shortly  
after a renovation of the home. Because of the natural circulation of air,  
moist and volatile components from paint, building materials, carpet etc.  
will be attracted. These components can settle themselves down onto  
cold surfaces in the form of soot. As on all heat producing appliances,  
soft furnishings such as blown vinyl wallpaper placed too near to the  
appliance may become scorched or discoloured. This should be born in  
mind when installing the appliance.  
Do not use the fire with a broken or damaged glass.  
The fire has a safety device which turns off the gas supply if there is a  
build up from flue gasses in the combustion room or a temporary gas  
cut-off. Wait at least 5 minutes before turning the appliance on again.  
Contact a qualified installer when the appliance goes off regularly.  
The appliance has been designed for heating purposes. This means that  
all surfaces, including the glass, can become very warm (over  
100 degrees). An exception to this is the lower side of the door and the  
control buttons.  
Due to the newness of materials, they may give off a slight smell for a  
period after initial lighting. This is normal, odours will disperse after a  
few hours use.  
Do not place curtains, clothing, laundry, furniture or other flammable  
materials nearby the appliance. The required minimum distance is  
100 cm.  
Switch off the receiver of the remote control if you don’t use the fire for  
a long time. Do not let children use the remote control without  
supervision.  
46  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
10. CONTROLLING THE APPLIANCE  
Knob A  
The { is the OFF position preventing any gas from passing through the  
control valve to either the pilot burner or to the main burner. By pressing  
the knob in it is possible to turn it anticlockwise. The first function is to  
turn on the gas to the pilot- this occurs just before reaching the  
|position (if the fire has not been lit for some time it may be necessary  
to hold the knob in this position for some seconds to clear the air from  
the pipe and allow gas to reach the pilot burner). Once gas is available  
at the pilot, continued rotation anti-clockwise will cause the piezo igniter  
to spark. This is accompanied by a click at the valve and should result in  
the pilot burner igniting. Once the pilot is lit, the control knob should be  
held pressed in for 10 seconds. In this time the pilot flame will have  
heated the flame supervision thermocouple sufficiently to operate a hold-  
on magnet within the valve. Now turn the control knob A to the  
position. This allows gas to enter control knob B.  
10.1 Lighting the fire  
If the main burner or pilot light are extinguished for any reason, do  
not attempt to relight the pilot within 5 minutes. Contact a qualified  
installer when the appliance goes off regularly.  
The control valve is behind the ashtray door.  
Silence /Feeling /Whisper  
Open the ashtray door by pushing on the right side for the  
Silence/Feeling and on the left side for the Whisper.  
Misty  
Open the ashtray door by pulling down (bottom handle with gas  
damper).  
Knob B  
The { is the OFF position preventing gas entering the main burner if  
the pilot is lit. The knob should be turned slowly anticlockwise. This  
allows gas to enter the burner and be ignited by the pilot flame. Once  
ignition has taken place, the fire may be set to any level between min.  
and max. by adjusting the control knob B.  
Cadra Nova and Spectra Nova  
Open by pushing the lip located on the right side in the gap between  
the ashtray door and the frame (door flaps open).  
A
B
10.2 To light  
1. Push in and turn the control knob (A) from { anticlockwise to  
the setting  
(small flame). You will hear a ignition click. Check  
that the pilot is lit (if not repeat).  
2. Continue to hold in the control knob for a further ten seconds to  
ensure that the pilot flame is stable.  
3. Release the knob. The pilot should remain alight.  
fig. 27 control unit  
4. Turn the control knob A to the  
position.  
With control button A you can light the pilot. With the control button  
B you can adjust the height of the flames (see fig. 27).  
5. Turn knob B slowly anticlockwise, the fire should then ignite.  
6. Adjust flames to the required level.  
48  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
10.3 To extinguish  
10.4.1 To light  
1. Push in and turn the control knob (A) from { anticlockwise to  
1. For the main burner turn the control knob B clockwise to  
the setting (small flame). You will hear a ignition click. Check  
that the pilot is lit (if not repeat).  
position {.  
2. To disable knob B turn knob A to the  
position.  
2. Continue to hold in the control knob for a further ten seconds to  
ensure that the pilot flame is stable.  
3. To extinguish the pilot turn control knob A to position { ,  
although it is in order lo leave the pilot permanently lit.  
3. Release the knob. The pilot should remain alight.  
10.3.1 When the pilot extinguishes  
Warning! When the pilot extinguishes, for whatever reason, you should  
4. Turn the control knob A to the  
position.  
wait at least 5 minutes before trying to turn it on again.  
5. Set the on/off switch on the receiver to "on”.  
Possible causes of pilot extinguish are:  
- Operating error.  
low flame  
high flame  
- Interference of the safety device.  
- Failure in the pilot flame system.  
6. Use  
(high) and  
(low) to achieve the desired heating and  
Contact a qualified installer when the appliance goes off regularly.  
flame effect.  
fig. 28  
remote control 7. You will hear a beep every time the receiver recognises a good  
signal. (If not, so see 10.4.3, setting the right transmission code).  
10.4 Remote control version  
The remote control is only meant to regulate the flames from off till  
max., it functions only when the pilot burner is ignited and knob A in  
(big flame) position. It is therefore not possible to ignite the pilot  
flame with the remote control or to extinguish the pilot flame. The  
radio-frequency remote control is intended for fireplaces installed in a  
domestic setting in all EU countries except Austria, Denmark, Finland,  
and Greece.  
8. When the fire is not be used for a prolonged period, turn off the  
pilot (see 10.4.2).  
10.4.2 To extinguish  
1. Push  
clicking.  
(low) till the burner goes out and you can hear the motor  
2. To enable the remote control turn knob A to the  
position.  
Features:  
- Manual control will always remain possible.  
- The remote control is a radio frequency type and had been approved  
internationally.  
3. To extinguish the pilot turn control knob A to position {, although  
it is in order to leave the pilot permanently lit.  
- The remote control generates a unique safety code every time you  
activate the transmitter, its similar to those used in a car.  
- The remote control is easy to install retrospectively.  
50  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
10.4.3 Setting the right transmission code  
10.4.4 Changing the batteries  
he receiver has to learn the code from the transmitter, which is already  
There is no risk of electric shock as the low voltage supply is similar  
to that used in torches. Always turn off the appliance before changing  
batteries.  
done at the factory. However the code disappears if the receiver is  
disconnected from the mains for a longer period,  
1. Set the on/off switch on the receiver to "on".  
Remote control  
2. Push the "mod" button on the receiver and hold it for 3 seconds.  
1. Remove the cover on the back of the remote control.  
3. The green control lamp will light up and stay on. Repeat this step  
if it doesn't.  
2. Carefully remove the battery clip along the side. Pay attention not  
to pull the wires.  
4. Push a button on the remote control. The control lamp on the  
receiver should now go out.  
3. If necessary, remove the old batteries and place the new ones:  
2 x LR03 Alkaline long life 1.5 V.  
+
5. Again push a button on the remote control. The lamp starts  
flashing and will switch off eventually.  
4. Click the battery clip into the remote control and close the cover.  
5. It might be possible that you have to set the transmission code  
after changing the batteries (see 10.4.3).  
6. The receiver now recognizes the remote control. The remote  
control now functions.  
+
Note  
7. Check if you can hear a sound and the motor runs when you  
push a button on the remote control.  
Batteries are chemical waste and should be disposed in accordance  
with local regulations.  
fig. 29  
changing batteries  
52  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UK/IRL  
UK/IRL  
12. DISPOSAL OF THE PACKAGING  
11. CLEANING AND SERVICE  
INSTRUCTIONS  
AND THE APPLIANCE  
The appliance packaging is recyclable. The packaging could include  
Important:  
the following materials:  
- cardboard;  
Turn off the fire and allow it to cool down before  
commencing cleaning.  
- CFC-free foam (soft);  
- wood;  
It is recommended that the fire is inspected/serviced, by a competent  
person at least once a year.  
- plastic;  
- paper.  
To maintain the finish on the trim wipe with soft damp cloth only. Do  
not use abrasive cleaners, polish or solvents as these can damage  
the surface finish.  
These materials should be disposed responsibly and in conformity  
with government regulations.  
Batteries are considered chemical waste. The batteries should be  
disposed of responsibly and in conformity with government  
regulations. Remove the batteries before disposing of the remote  
control.  
Information on how to responsibly dispose of discarded appliances  
can be obtained from the local authorities.  
54  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Fisher Paykel Ventilation Hood HC120DCXB1 User Manual
Fisher Price Baby Monitor C7051 User Manual
Fisher Price Baby Toy 90197 User Manual
FMI Indoor Fireplace CDCFNRB User Manual
Frigidaire Air Conditioner FRA123KT1 User Manual
Frigidaire Washer Dryer 134889200 User Manual
Fujitsu Scanner fi 5120C User Manual
GE Convection Oven EER2000 User Manual
Gemini Stereo Amplifier X 01 User Manual
Gillette Electric Shaver 5693 User Manual