| 1. Brief introduction   1.1 System and model description   This Online Series is an uninterruptible power supply incorporating   double-conversion technology. It provides perfect protection   specifically for computer equipment, Communication Systems to   computerized instruments.   Its true online double-conversion design eliminates all mains power   disturbances. A rectifier converts the alternating current from the   utility power to direct current. This direct current charges the   batteries and powers the inverter. On the basis of this DC voltage,   the inverter generates a pure sinusoidal AC voltage, which is   modulated by an isolation transformer and then power the loads.   Computers and Peripherals are thus powered entirely by the UPS. In   the event of power failure, the maintenance-free batteries power the   inverter. This manual is applicable to the following models:   1) The DX 6000L is a standard model with inbuilt battery,   hereinafter called 6000L;   2) The DX 6000LXL is a long backup time model, which is able to   connect with the external battery bank, hereinafter called   6000LXL;   3) The DX 10000L is a standard model with inbuilt battery, hereinafter   called 10000L;   4) The DX 10000LXL is a long backup time model, which is able to   connect with the external battery bank, hereinafter called   10000LXL;   1.2 Description of commonly used symbols   The following symbols will be used in this manual and may appear   during the course of your practical applications. Therefore, all   users should be familiar with them and understand their meanings.   1 Download from Www.Somanuals.com. All Manuals Search And Download.   Nation and Explanation   Nation   Explanation   Nation   Explanation   Alert you to pay special   attention   Protective ground   Caution of high voltage   Turn on the UPS   Alarm silence   Overload indication   Idle or shut down the   UPS   Battery check   Recycle   Alternating current   source (AC)   Keep UPS in a clear   area   Direct current source   1.3 Appearance   Back View Of 6000L(XL)   2 Download from Www.Somanuals.com. All Manuals Search And Download.   Download from Www.Somanuals.com. All Manuals Search And Download.   ● Electrical performance   Input   Model   Voltage   Frequency   (46~54)/(56~64)Hz   Output   Power Factor   6000L(XL)/   10000L(XL)   Single-phase   >0.98 (Full load)   Voltage Power   regulation factor   Frequency   tolerance   Current   crest ratio   Distortion Overload capacity   105%~130% load   transfers to bypass   mode after 10   Synchronized   (46~54)/(56~64)Hz   in Line mode(AC   mode)   THD<3%   Full load   (linear   minutes.   3:1   maximum   ±4%   0.7lag   >130% load transfers   to bypass mode after   1 second and   ±0.1% of normal   frequency in   load)   shutdown the output   after 1 minutes   Battery mode.   ● Operating environment   Temperature   Humidity   <95%   Altitude   <1000m   Storage temperature   -15℃~40℃   0℃~40℃   Note: if the UPS is installed or used in a place where the altitude is   above than 1000m, the output power must be derated in use, please   refer to the following :   Altitude (M)   1000 1500 2000 2500 3000 3500 4000 4500 5000   Deratingpower 100% 95% 91% 86% 82% 78% 74% 70% 67%   4 Download from Www.Somanuals.com. All Manuals Search And Download.   2. Installation   2.1 Unpacking and inspection   1) Unpack the packaging and check the package contents. The   shipping package contains:   ● A UPS   ● A User Manual   ● A Communication Cable   ● A Battery Cable (for 6000LXL /10000LXL only)   2) Inspect the appearance of the UPS to see if there is any   damage during transportation. Do not turn on the unit and notify   the carrier and dealer immediately if there is any damage or   lacking of some parts.   2.2 Input and output power cords and protective earth   ground installation   1. Notes for installation   1) The UPS must be installed in a location with good ventilation,   far away from water, inflammable gas and corrosive agents.   2) Ensure the air vents on the front and rear of the UPS are not   blocked. Allow at least 0.5m of space on each side.   3) Condensation to water drops may occur if the UPS is   unpacked in a very low temperature environment. In this   case it is necessary to wait until the UPS is fully dried inside   out before proceeding installation and use. Otherwise there   are hazards of electric shock.   Installation and wiring must be performed in accordance with the   local electric code and the following instructions by professional   personnel.   For safety, please cut off the mains power switch before   5 Download from Www.Somanuals.com. All Manuals Search And Download.   installation. The battery breaker also needs to be cut off if it is a   long backup time model (“XL” model).   ● Open the terminal block cover located on the rear panel of   the UPS, please refer to the appearance diagram.   ● For 6000L(XL) UPS, it is recommended to select the   UL101510AWG(6mm2) wire or other insulated wire which   complies with AWG Standard for the UPS input and output   wirings.   ● For 10000L(XL) UPS, it is recommended to select the   UL1015 8AWG(10mm2) wire or other insulated wire which   complies with AWG Standard for the UPS input and output   wirings.   Note: Do not use the wall receptacle as the input power source   for the UPS, as its rated current is less than the UPS’s   maximum input current. Otherwise the receptacle may be   burned and destroyed.   ● Connect the input and output wires to the corresponding   input and output terminals according to the following   diagram.   Note: you must make sure that the input and output wires and the   input and output terminals are connected tightly   ● The protective earth ground wire refers to the wire   connection between the equipment which consumes electric   equipment and the ground wire. The wire diameter of   protective earth ground wire should be at least as above   mentioned for each model and green wire or green wire with   yellow ribbon wire is used.   ● After having completed the installation, make sure the   wiring is correct.   ● Please install the leak current protective breaker at the output   power distribution panel of the UPS if necessary.   6 Download from Www.Somanuals.com. All Manuals Search And Download.   ● To connect the load with the UPS, please turn off all the loads   first, then perform the connection and finally turn on the loads   one by one.   ● No matter the UPS is connected to the utility power or not,   the output of the UPS may have electricity. The parts inside   the unit may still have hazardous voltage after turning off the   UPS. To make the UPS have no output, power off the UPS,   and then disconnect the utility power supply.   ● Suggest charging the batteries for 8 hours before use. After   connection, turn the bypass breaker in the “ON” position, the   UPS will charge the batteries automatically. You can also use   the UPS immediately without charging the batteries first, but   the backup time may be less than the standard value.   ● If it is necessary to connect the inductance load such as a   monitor or a laser printer to the UPS, the start-up power   should be used for calculating the capacity of the UPS, as its   start-up power consumption is too big when it is started.   Input and output Terminal Block wiring diagram of 6000L(XL)/10000L(XL)   Important notes: If the UPS is used in single mode, JPI and JP2   must be connected by 10AWG(6mm2). If the UPS is used in   parallel mode, the Jumper between JP1 and JP2 must be removed   7 Download from Www.Somanuals.com. All Manuals Search And Download.   Connection Details of Output Terminals   Important Note: If the UPS is used in Single Mode, JP1 and JP2   must be connected by 10AWG (6mm2). If the UPS is used in Parallel   Mode, the Jumper between JP1 and JP2 must be removed.   ● Option: 1   Connection Details of Output Terminals.   Connection Details of Output Terminals.   Connect Output Line 1 and Output Neutral 1 for 120V / 3KVA Load or connect by   10AWG (6mm2). Output Line 2 and Output Neutral 2 for 120V / 3KVA Load.   8 Download from Www.Somanuals.com. All Manuals Search And Download.   Important Note: If the UPS is used in Single Mode, JP1 and JP2 must be   connected by 10AWG (6mm2). If the UPS is used in Parallel Mode, the Jumper   between JP1 and JP2 must be removed.   ● Option: 2   Connection Details of Output Terminals.   Connect Output Line 1 and Neutral2 by 10AWG (6mm2) for 240V / 6KVA Load.   Important Note: If the UPS is used in Single Mode, JP1 and JP2 must be   connected by 10AWG (6mm2). If the UPS is used in Parallel Mode, the Jumper   between JP1 and JP2 must be removed.   2.3 Operating procedure for connecting the long backup   time model UPS with the external battery   1. The nominal DC voltage of external battery pack is 240VDC.   Each battery pack consists of 20 pieces of 12V maintenance free   batteries in series. To achieve longer back time, it is possible to   connect multi-battery packs, but the principle of “same voltage,   same type” should be strictly followed.   2. The connector of the external battery cable is used to plug into   the external battery socket of the UPS, the other end of the   external battery cable is made of three open wires with ring   terminals to connect with the external battery pack(s). The   procedure of installing battery bank should be complied with   strictly. Otherwise you may encounter the hazardous of electric   shock.   9 Download from Www.Somanuals.com. All Manuals Search And Download.   1) DC breaker must be connected between the battery pack and   the UPS. The capacity of breaker must be not less than the data   specified in the general specification.   2) Set the battery pack breaker in ”OFF” position and connect the   20 pieces of batteries in series   3) You must connect the external battery cable to the battery first,   if you connect the cable to the UPS first, you may encounter the   hazardous of electric shock. The positive pole of the battery is   connected to the10000LXL in parallel with blue and brown wires;   the negative pole of the battery is connected to the 10000LXL in   parallel with black and white wires; the green and yellow ribbon   wire is connected to the ground of the battery cabinet.   3. To complete the connection by plugging the connector of the   external battery cable into the external battery socket of the UPS.   Do not attempt to connect any loads to the UPS now. You should   connect the input power wire to the right position first. And then   set the breaker of the battery pack in the ON position. After that   set the bypass breaker in the ON position. The UPS begins to   charge the battery packs at the time.   The blue & brown wires for connection to the positive   terminal of the battery pack output   The black & white wires for   connection to the negative   terminal of the battery pack   The receptacle for   The green and yellow ribbon wire for   connecting the UPS   connection to the ground of the battery   The External Battery Cable Diagram For 6000L(XL)/10000L(XL)   (The cable may vary from different “XL” models)   10   Download from Www.Somanuals.com. All Manuals Search And Download.   2.4 Parallel operation   1. Brief introduction of the redundancy   N+X is currently the most reliable power supply structure. N   represents the minimum UPS number that the total load needs; X   represents the redundant UPS number, i.e. the fault UPS number   that the system can handle simultaneously. The bigger the X is, the   higher reliability of the power system is. For occasions where   reliability is highly depended on, N+X is the optimal mode.   As long as the UPS is equipped with parallel cables, up to 3 UPSs   can be connected in parallel to realize output power sharing and   power redundancy.   2. Parallel installation   1) Users need to opt a standard 25-pin communication cable,   which should have 25 cores, corresponding stitches and shield,   as the UPS parallel cable. The length of the parallel cable is   appropriate to be less than 3 m.   2) Strictly follow the stand-alone wiring requirement to perform the   input wiring of each UPS.   3) Connect the output wires of each UPS to an output breaker   panel.   4) Disconnect the Jumper on JP1 and JP2 of the terminal block   first, and connect each output breaker to a main output breaker   and then to the loads.   Note: The requirement of the output wiring is as follows:   ● When the distance between the UPSs in parallel and the breaker   panel is less than 20 meters, the difference between the wires of   input & output of the UPSs is required to be less than 20%;   ● When the distance between the UPSs in parallel and the breaker   panel is greater than 20 meters, the difference between the wires   of input & output of the UPSs is required to be less than 10%.   11   Download from Www.Somanuals.com. All Manuals Search And Download.   3. Parallel operation   To perform the general operation, follow the stand-alone operating   requirement:   1) Startup: The units transfer to INV mode simultaneously as they   start up sequentially in utility power mode;   2) Shutdown: the units shut down sequentially in INV mode. When   the l ast one completes the shutdown action, each unit will shut   down the inverter simultaneously and transfer to bypass mode.   It is easy to operate the equipment, with no previous training. You   just need to read through this manual and operate according to the   instructions in it. The meaning of the LED indicators, please refer to   the appendix 1 “Display panel”   3. Operation and Operating mode   3.1 Operation   1. Turn on the UPS with utility power supplied (in Line mode/AC   mode)   1) After you make sure that the power supply connection is correct,   set the bypass breaker and the input breaker in the “ON”   position first. At this time the fan rotates and the UPS   supplies power to the load via the bypass. The UPS operates   in Bypass mode.   12   Download from Www.Somanuals.com. All Manuals Search And Download.   2) To power on the UPS by simply pressing the “ON” button   continuously for more than 1 second.   3) When being powered on, the UPS will perform self-diagnosis,   with the load/battery level LEDs turned on and then off one   after another in ascending order. A few seconds later, the INV   LED is turned on, the UPS is already running in Utility Power   mode. If the utility power is abnormal, the UPS will operate in   battery mode without output interruption of the UPS.   2. Turn on the UPS with no utility power supplied (in Battery mode)   1) Press the “ON” button continuously for more than 1 second to   power on the UPS. For long back up time model (“XL” model),   please make sure that the battery breaker is in “ON” position.   2) During the course of starting up, the UPS has the same action   as if it is connected to utility power except that the utility power   LED is not turned on and the battery LED is turned on instead.   3. Turn off the UPS with utility power supplied (in Line mode/AC mode)   1) Press the “OFF” button continuously for more than 1 second   to turn off the inverter of the UPS immediately.   2) When being powered off, the UPS will perform self-diagnosis,   the Load/Battery level LEDs will be turned on and then off one   after another in ascending order, then the INV LED will be   turned off and Bypass LED will be turned on. The UPS is   working in Bypass mode.   3) Upon completion of the above to turn it off, output of electric   current of the UPS is still present. In order to cut off the output   from the UPS, simply cut off the utility power supply and the   UPS will perform self-diagnosis, finally not any display is   shown on the display panel and no voltage output is available   from the UPS output.   4. Turn off the UPS with no utility power supplied (in Battery mode)   1) Press the “OFF” button continuously for more than 1 second   13   Download from Www.Somanuals.com. All Manuals Search And Download.   to power off the UPS.   2) When being powered off, the UPS will perform self-diagnosis,   the Load/Battery level LEDs will be turned on and then off one   after another in ascending order. Finally not any display is   shown on the display panel and no voltage is available from   the UPS output.   Suggestions: Please turn off the connected loads before turning on   the UPS and turn on the loads one by one after the UPS is working   in INV mode. Turn off all of the connected loads before turning off   the UPS.   3.2 Operating mode   1. Utility power mode   The display panel in utility power   mode is shown in the following   diagram. The utility power LED and   the INV LED are turned on. The   load level LEDs will be turnd on in   accordance with the load capacity   connected.   1) If the battery LED is turned on   and the utility power LED   The Utility Power Mode   flashes, it indicates the voltage   or frequency of the utility power   has exceeded the normal range, the UPS operates in battery   mode.   2) If output overloaded, the load level LEDs will be turned on and   alarm will keep twice every second. You should get rid of some   unnecessary loads one by one to decrease the loads connected   to the UPS less than 90% of its nominal power capacity.   Note: Please follow the following steps to connect the generator:   ● Activate the generator and wait until the operation is stable   14   Download from Www.Somanuals.com. All Manuals Search And Download.   before supplying power of the generator to the UPS (be sure   that the UPS is in idle mode). Then turn on the UPS according to   the start-up procedure. After the UPS is turned on, then the   loads can be connected to the UPS one by one.   ● The power capacity of the AC generator should be at least twice   of the UPS capacity.   2. Battery mode   The display panel in battery mode is shown in the following diagram.   The battery LED and the INV LED are turned on. The displayed   number of the battery level LEDs will be turned on in accordance   with the battery capacity. Note that the load level LEDs in utility   power mode will indicate the level of   the battery capacity in battery mode.   1) When the UPS in battery mode,   the buzzer beeps once every 4   seconds. If the “ON” button is   pressed for more than   1 seconds, the buzzer will stop   beeping. Press the “ON” button   once again for more than 1   second to resume the alarm   function.   Battery mode diagram   2) When the battery capacity   decreases, the number of the battery capacity LEDs turned on   will be reduced. If the battery voltage descends to the alarm   level, the buzzer will beep once every second to remind the   users of in sufficient battery capacity and the UPS is soon   going to shut down automatically. Then the load operations   should be carried out promptly and the loads should be   eliminated one by one.   3. Bypass mode   15   Download from Www.Somanuals.com. All Manuals Search And Download.   The display panel in bypass mode is   shown in the following diagram. The   utility power LED and the bypass   LED are lit. The displayed number   of the load LEDs will be turned on in   accordance with the load capacity   connected. The UPS will beep once   every 2 minutes in bypass mode.   1) The utility power LED flashes, it   shows that the voltage or   frequency of the utility power   has exceeded the normal range   of the UPS.   Bypass Mode Diagram   2) Other indications on the display panel are the same in utility   mode.   3) The UPS does not have the backup function when it is in   bypass mode. The power used by the load is supplied from the   utility power via internal filter and the transformer.   4. Abnormality mode   In case the fault LED is turned on when the UPS is in use, it shows   that the UPS is operating in abnormal mode. Please refer to the   troubleshooting in section 6 for detail.   5. Backup time for the standard model   The backup time of the long backup time model is dependent on the   external battery pack capacity and the load level as well as other   factors. The backup time of standard model may vary from different   models and load level. Please refer to the following:   16   Download from Www.Somanuals.com. All Manuals Search And Download.   Load Level   Load level   Backup Time Of 6000L(XL)   Backup Time Of 10000L(XL)   6. Communication Port   Intelligent slot   This series is equipped with an intelligent slot for Webpower   (optional accessory) or other optional card to achieve remote   management of the UPS through internet / intranet. Please contact   your local distributor for further information.   RS232 interface   The following are the descriptions and pin assignment of RS232   DB-9 port:   Baud rate: 2400bps   Ending bit:1bit   Data bit: 8 bit   Parity bit: None   17   Download from Www.Somanuals.com. All Manuals Search And Download.   Pin   Function   I/O   number   description   3 2 5 Rx   Tx   input   output   GND   Ground   DB-9 pin assignment:   RS232 Interface   Optional AS400 interface   This optional AS400 card provides dry contact closure signal   “OPEN” or “CLOSE”. Following are the pin assignment and the   descriptions of AS400 card:   PIN1: UPS failure (normally open, active close)   PIN2: summary alarm   PIN3: ground   PIN4: Remote shutdown   PIN5: Common   PIN6: Bypass active (relay close)   PIN7: Battery low   PIN8: UPS On (relay close)   PIN9: Utility Power failure (normally open, active close)   AS400 Interface   18   Download from Www.Somanuals.com. All Manuals Search And Download.   Data-Line Surge Protection   The built-in data-line surge   suppression on the rear panel   completes your system protection. It   provides an easy way to protect a   network (RJ45) or modem (single line   phone) connection from hazardous   spikes.   RJ45   4. Battery maintenance   ● This series UPS only requires minimal maintenance. The battery   used for standard models are value regulated sealed lead-acid   maintenance free battery. These models require minimal repairs.   The only requirement is to charge the UPS regularly in order to   maximize the expected life of the battery. When being connected to   the utility power, whether the UPS is turned on or not, the UPS keeps   charging the batteries and also offers the protective function of   overcharging and overdischarging.   ● The UPS should be charged once every 4 to 6 months if it has not   been used for a long time.   ● In the regions of hot climates, the battery should be charged and   discharged every 2 months. The standard charging time should be at   least 12 hours.   ● Under normal conditions, the battery life lasts 3 to 5 years. In case if   the battery is found not in good condition, earlier replacement should   be made. Battery replacement should be performed by qualified   personnel.   19   Download from Www.Somanuals.com. All Manuals Search And Download.   ● Replace batteries with the same number and same type of batteries.   ● Do not replace the battery individually. All the batteries should be   replaced at the same time following the instructions of the battery   supplier.   ● Normally, the batteries should be charged and discharged once   every 4 to 6 months. Charging should begin after the UPS shuts   down automatically in the course of discharging, the standard   charging time for the standard UPS should be at least 12 hours.   5. Notes for battery disposal and battery   replacement   1) Before disposing of batteries, remove conductive jewelry   such as necklace, wrist watches and rings.   2) If it is necessary to replace any connection cables, please   purchase the original materials from the authorized   distributors or service centers, so as to avoid overheat or   spark resulting in fire due to insufficient capacity.   3) Do not dispose of batteries or battery packs in a fire, or they   may explode.   4) Do not open or mutilate batteries, released electrolyte is   highly poisonous and harmful to the skin and eyes.   5) Do not short the positive and negative of the battery   electrode, otherwise, it may result in electric shock or fire.   6) Make sure that there is no voltage before touching the   batteries. The battery circuit is not isolated from the input   potential circuit. There may be hazardous voltage between   the battery terminals and the ground.   7) Even though the input breaker is disconnected, the   components inside the UPS are still connected with the   batteries, and there are potential hazardous voltages.   20   Download from Www.Somanuals.com. All Manuals Search And Download.   Therefore, before any maintenance and repairs work is   carried out, switch off the breaker of the battery pack or   disconnect the jumper wire of connecting between the   batteries.   8) Batteries contain hazardous voltage and current. Battery   maintenance such as the battery replacement must be   carried out by qualified personnel who are knowledgeable   about batteries. No other persons should handle the   batteries.   6. Troubleshooting   Problem   Possible cause   Solution   Make sure the UPS is not overloaded;   the air vents are not blocked and the   ambient temperature is not too high.   Wait for 10 minutes for the UPS to cool   down before turning on again. If failed,   please contact the distributor or service   center.   The #1 Fault LED   and the #6 LED are The UPS   turned on, the   buzzer beeps   continuously   shutdown due to   internal overheat   The #1 Fault LED   and the #2 and #5   LED are turned on,   and the buzzer   Turn off the UPS. Remove all the loads.   Ensure that the load is not failed or the   UPS has no internal faults before   turning it on again. If failed, please   contact the distributor or service center.   The UPS output   is short circuited.   beeps continuously   The #1 Fault LED   and the #4 LED are   turned on, the UPS   beeps continuously   The #1 Fault LED   and the #5 LED are   turned on, the UPS   beeps continuously   The #1 Fault LED   The UPS shuts   down due to its   internal fault.   Please contact the distributor or service   center.   The UPS shuts   down due to its   internal fault.   Please contact the distributor or service   center.   and the #3 LED are Overcharging   The charger of the UPS is failed. Please   contact the distributor or service center.   protection   turned on, the UPS   beeps continuously   21   Download from Www.Somanuals.com. All Manuals Search And Download.   The voltage or   frequency of the   utility power is   out of the input   range of the   UPS.   The UPS is running in battery mode. To   save your data and close the application   program. Make sure the utility power is   within the input voltage or frequency   range permitted by the UPS.   The utility power   LED flashes   Check the loads and remove all   no-critical equipment. Recalculate the   load power and reduce the number of   loads connected to the UPS. Check that   the loads are not failed.   The #1 Fault LED   The UPS is   and the #2 LED are overloaded or the   turned on, the UPS load equipment   beeps continuously is faulty   22   Download from Www.Somanuals.com. All Manuals Search And Download.   The #1 Fault LED   and the battery LED   are turned on, the   buzzer beeps every   second   The charger of   the UPS is   defective.   Please contact the distributor or service   center.   Check the battery. If the battery is   damaged, replace the battery   Battery low or   battery not   connected   Battery LED flashes   immediately and ensure that the battery   breaker is in “ON” position.   The utility power is   normal, but the UPS   can not turn in line   mode   Bypass breaker   Set the bypass breaker in “ON” position.   in “OFF” position   Battery not yet   been fully   Keep UPS connected to utility power   persistently for more than 10 hours to   recharge the batteries again.   charged   Battery discharging   time diminishes   Check the loads and remove the   non-critical equipment.   UPS overloaded   Replace the batteries. Please contact   the distributor to obtain the parts and   replacement service.   Battery aged   The “ON” button   is pressed too   briefly   Press the “ON” button for more than 1   second.   The UPS is not   connected to the   battery or the   battery pack   voltage is too   low.   The UPS cannot   power on after   pressing the ON   button   Check the battery or recharge the   battery.   Please contact the distributor or service   center.   UPS fault   When you contact the service center, please provide the following information:   ● Model No. and the serial No. of the UPS;   ● The date when the problem arose;   ● Complete description of the problem, including the LED display, alarm warning,   and power condition and load capacity. If your UPS is a long backup time model,   you may also provide the battery information.   23   Download from Www.Somanuals.com. All Manuals Search And Download.   Appendix 1: display panel   n Power ON/OFF: To turn on the UPS simply by pressing the “ON” button on the   front panel continuously for 1 second. Press the “OFF” button on the front panel   continuously for 1 second to turn off the UPS.   n n n n n n Bypass LED (orange LED): Whenever the bypass LED is turned on, it shows   that the loading current is supplied directly from the utility power.   Utility power LED (green LED): Whenever the utility power LED is turned on, it   shows that the utility power is normal.   Inv LED (green LED): Whenever the INV LED is turned on, it shows that the   loading current is supplied from utility power or battery via the inverter.   Battery LED (orange LED): Whenever the battery LED is turned on, it shows   that the loading current is supplied from battery via the inverter.   Fault LED (red LED): Whenever the fault LED is turned on, it shows that the   UPS is in abnormal condition.   #2-#6 LEDs (the #2 LED is orange and the #3-#6 LEDs are green): These   LEDs indicate the percentage of the load capacity in utility power mode or   battery capacity level in battery mode.   24   Download from Www.Somanuals.com. All Manuals Search And Download.   Appendix 2: The corresponding form of the LED   display   LED display   Alarm   warning   No.   Operating state   1# 2# 3# 4# 5# 6# 7# 8# 9# 10#   0~35%   Load capacity   1 2 3 4 5 ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● none   none   none   none   none   36%~55%   Load capacity   ● ● ● ● Utility   Power   Mode   56%~75%   Load capacity   ● ● ● 76%~95%   Load capacity   ● ● 96%~105%   Load capacity   ● ● 0~20%   Battery   capacity   Beep once   every sec   6 7 ● ● ● ● ● ● ● ● ● ● 21%~40%   Battery   capacity   Beep once   every 4 sec   ● ● ● ● ● ● 41%~60%   Battery   capacity   Battery   Mode   Beep once   every 4 sec   8 ● ● 61%~80%   Battery   capacity   Beep once   every 4 sec   9 ● 81%~100%   Battery   capacity   Beep once   every 4 sec   10   ● ↑ ● ● ↑ ● ● ↑ ● ● ↑ ● ● ● ● Beep once   every 2 min.   11 Bypass mode   Overloaded in utility   12 mode and UPS still in   INV mode   ● ● ● ● Beep twice   every sec.   ● ● ● Overloaded in utility   mode and UPS in   bypass mode   Continuously   beep   13   ● ● 25   Download from Www.Somanuals.com. All Manuals Search And Download.   14 Utility power abnormal   Overloaded in battery   ↑ ● ↑ ↑ ↑ ↑ ↑ ↑ ● ↑ ★ ↑ ↑ ● ↑ ● ↑ Beep twice   every sec.   mode,   15   ● ● Early-warning   Overloaded in battery   mode,   Continuously   beep   16   ● Cut off the output   Continuously   beep   17 Over temperature   18 Inv abnormal   ● ● ● ● ● ↑ ● ● ● ● ● ● ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ● Continuously   beep   ● ● Continuously   beep   19 Output short circuited   20 BUS voltage abnormal   21 Charger or battery failed   ● Continuously   beep   ● ↑ Continuously   beep   ● ↑ ● ● ↑ ★ ★ Battery voltage   abnormal   22   ↑ ● ● ● ● ● ● ↑ Continuously   beep   23 BAT SCR failed   24 Fan abnormal   25 Bypass STS failed   26 INV RLY failed   Continuously   beep   ● ● ● ↑ ● ● ● ↑ Continuously   beep   ● Continuously   beep   ● ● Communication   abnormal   Continuously   beep   27   ● ●: Solid ON   ★: Flash   ↑: LED display and alarm warning are dependent on other conditions.   26   Download from Www.Somanuals.com. All Manuals Search And Download.   614-03753-01   Download from Www.Somanuals.com. All Manuals Search And Download.   |