| 	
		 IMI CORNELIUS REMCOR INC g 500 REGENCY DRIVE g GLENDALE HEIGHTS, IL 60139–2268   
					Telephone (800) 551–4423   
					Facsimile (800) 519–4423   
					CHILLER (“CH” SERIES)   
					Models: CH 250   
					CH 251   
					Operator’s Manual   
					Part No. 620914801   
					February 16, 1999   
					Revised: August 12, 2002   
					Revision C   
					THIS DOCUMENT CONTAINS IMPORTANT INFORMATION   
					This Manual must be read and understood before installing or operating this equipment   
					PRINTED IN U.S.A   
					IMI CORNELIUS INC; 1999–2002   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				GENERAL INFORMATION   
					INTRODUCTION   
					The REMCOR ”CH” Series Recirculating Water Chiller is designed to provide an accurate, reliable, and user–   
					friendly system for cooling a continuous flow of water and keep it at a constant temperature in various closed   
					loop or tank cooling applications.   
					The ”CH” Series Chiller consists of an air–cooled refrigeration system housed in a sturdy sheet metal frame and   
					cabinet. A standard pump and insulated water reservoir package provides a complete liquid cooling and circu-   
					lating system.   
					The ”CH” Series Chiller is designed to operate in a clean laboratory or industrial environment where ambient   
					temperatures range from 40 to100° F (5 to 38° C). With proper installation, operation, and maintenance, the   
					”CH” Series Chiller will provide years of trouble free service.   
					UNPACKING AND INSPECTION   
					This unit was thoroughly inspected before leaving the factory and the carrier has accepted and signed for it.   
					Any damage or irregularities should be noted at the time of delivery and immediately reported to the carrier. Re-   
					quest a written inspection report from the Claims Inspector to substantiate any necessary claims. In the event   
					that an immediate replacement is necessary, please contact REMCOR Chiller Sales at 1–800–551–4423.   
					DESIGN DATA   
					Table 1. Design Data   
					CH250   
					CH251   
					Cooling Capacity:   
					BTU/hr (W) at 80_ F(27_ C) and   
					70_ F (21_ C) Liquid Temperature.   
					3,000 (879)   
					3,000 (879)   
					Compressor Horsepower   
					.25 (.2 kW)   
					.25 (.2 kW)   
					Electrical Data:   
					Voltage/Phase/Hertz/Amperage   
					115/1/60   
					7.5 Amps   
					230/1/60   
					3.8 Amps   
					Refrigerant Type:   
					R134a   
					R134a   
					Physical Dimensions, Width X Depth   
					X Height   
					17.125” X 14.125” X 13.375”   
					(43.5 cm X 35.9 cm X 34cm)   
					17.125” X 14.125” X 13.375”   
					(43.5 cm X 35.9 cm X 34cm   
					Fittings:   
					Process Connections   
					Optimum Process Liquid Flow GPM   
					(Liters/Min)   
					1/2” FPT (S/S)   
					1/2I FPT (S/S)   
					0.6 (2.72)   
					0.6 (2.72)   
					Condenser Air Flow (CFM)   
					225   
					225   
					DATA PLATE INFORMATION   
					REMCOR PRODUCTS COMPANY   
					GLENDALE HEIGHTS, IL. 60139–2268   
					PART NO.   
					MODEL NO.   
					PH   
					SERIAL NO.   
					VOLTS   
					HZ   
					AMPS   
					R134A   
					BAR CODE   
					FIGURE 1. SAMPLE DATA PLATE   
					620914801   
					1 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				When servicing a REMCOR Chiller, it is important to note the information contained on the data plate located in   
					the upper rear of the Unit.   
					If technical assistance is needed, the phone technician will need the Serial Number of your Chiller. That informa-   
					tion is found on the Data Plate along with the model number, voltage requirement, and refrigerant information.   
					The serial Number is also needed when replacement parts are being ordered or for warranty claims. See   
					CHILLER WARRANTY PAGE.   
					Be sure to include the serial number on any documentation or billing information.   
					CHILLER INSTALLATION   
					Location of Chiller   
					THE CHILLER MUST BE LOCATED NEAR A PROPERLY GROUNDED ELECTRICAL OUTLET. THE CIR-   
					CUIT SHOULD BE FUSED AND NO OTHER ELECTRICAL APPLIANCE SHOULD BE CONNECTED TO THE   
					CIRCUIT. ALL ELECTRICAL WIRING MUST CONFORM TO NATIONAL AND LOCAL ELECTRICAL   
					CODES.   
					The Chiller must be located in a well ventilated, indoor area where ambient temperatures will remain above   
					40_ F (5_ C) and will never increase above 100_ F (38_ C). To obtain optimum cooling capacity, the ambient   
					temperature should be at or below 80_ F (27_ C).   
					It is very important that the air intake and discharge sides of the chiller are not obstructed by other free standing   
					objects. A minimum of two feet of space on all four sides of the chiller will be sufficient to prevent air flow ob-   
					structions.   
					It is also important to direct any hot air discharge from other equipment away from the air intake side of the chill-   
					er. Condenser air entering the “CH” unit should be below 100_ F (38_ C) .Condenser air temperatures above   
					100_ F (38_ C) can cause the high pressure safety control to shut down the unit.   
					Electrical Connections   
					(see Figure 3)   
					All wiring must conform to the National Electric Code and any applicable local codes. The Chiller must be   
					permanently wired by means of electrical conduit to a properly fused disconnect of proper amperage or wired to   
					a properly rated power cord and plugged into an outlet with the appropriate disconnect and amperage rating.   
					The electrical junction box, located on the back panel of the Chiller, includes a four terminal strip for power   
					supply connection.   
					The data plate, located next to the junction box, includes the actual voltage, phase, and amperage of the Chiller.   
					START UP   
					WARNING: Never operate the Chiller with it’s panels removed.   
					Always use the power switch to turn off the Chiller when it is not being used.   
					Always ensure that all air inlets and outlets are free from obstruction.   
					Be sure that the reservoir is filled with fluid prior to powering up the unit (see Fluid   
					Recommendations page).   
					Process Water Flow, Units with Pump and Tank (Standard)   
					Follow standard plumbing practices and local codes in making water connections. The Chiller inlet and outlet   
					connections are 3/4”. Flexible hose and fittings are recommended for plumbing the system. A No. 20 mesh   
					strainer should be installed on the Chiller inlet to prevent foreign particles from entering the system and should   
					be cleaned monthly. Lines should be routed with as few bends as possible. Prevent lines from running near   
					620914801   
					2 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				radiators, hot water pipes, etc. Any lengths of tubing that are exposed to high ambient temperatures should be   
					insulated to prevent condensation and/or significant liquid heat loss.   
					After ensuring that the system is free from the obstruction, that all valves are open, and the reservoir when avail-   
					able is full, push the CONTROL POWER switch to the “ON” position. The pump should now be operating.   
					Process Water Flow, Units Without Reservoir (Optional)   
					Follow standard plumbing practices and local codes in making water connections. The Chiller inlet and outlet   
					connections are 3/4”. Flexible hose and fittings are recommended for plumbing the system. A No. 20 mesh   
					strainer should be installed on the Chiller inlet to prevent foreign particles from entering the system and should   
					be cleaned monthly. Lines should be routed with as few bends as possible. Prevent lines from running near   
					radiators, hot water pipes, etc. Any lengths of tubing that are exposed to high ambient temperatures should be   
					insulated to prevent condensation and/or significant water heat loss.   
					Proper priming of the water lines is essential to prevent pump cavitation. Be certain all air has been purged from   
					the lines before operating the pump for an extended period of time. Be sure to remove any loops in the lines that   
					may trap air. The pump must have a supply of water with the level of the water above the inlet of the Chiller.   
					The supply tank must feed the Chiller from the side of the tank below the water level (see Figure 2).   
					CHILLER   
					INLET   
					WATER   
					LINE   
					LEVEL   
					EXTERNAL   
					RESERVOIR   
					CHILLER   
					W/O TANK   
					CORRECT   
					CHILLER   
					INLET   
					LINE   
					CHILLER   
					INLET   
					LINE   
					CHILLER   
					INLET   
					LINE   
					WATER   
					LEVEL   
					WATER   
					LEVEL   
					EXTERNAL   
					RESERVOIR   
					EXTERNAL   
					RESERVOIR   
					WATER   
					LEVEL   
					CHILLER   
					W/O TANK   
					CHILLER   
					W/O TANK   
					CHILLER   
					W/O TANK   
					EXTERNAL   
					RESERVOIR   
					WATER LEVEL IS   
					AIR CAN BE TRAPPED IN   
					WATER FEEDING FROM   
					BELOW CHILLER INLET   
					CHILLER INLET   
					TOP OF TANK   
					INCORRECT   
					INCORRECT   
					INCORRECT   
					FIGURE 2. EXTERNAL RESERVOIR WATER LEVEL   
					THERMOSTAT ADJUSTMENT   
					Standard Thermostat   
					The following procedure should be followed to adjust the standard thermostat:   
					620914801   
					3 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				1. Push the “SET” button located to the right of the digital display. The current set-point will be displayed.   
					2. Push the “UP” or “DOWN” button until the desired set-point is displayed.   
					3. After approximately 3 seconds, the display will show the system water temperature. The set-point can be   
					viewed at any time by pressing the “SET” button.   
					The thermostat has a range that has been pre-set at the factory. The range is 40° F (5° C) to 100° F (38° C). If   
					operation outside of this range is required, please contact the Remcor Technical Service Department.   
					UP   
					5 
					F 
					DOWN   
					SET   
					CHILLER MAINTENANCE   
					WARNING: Disconnect electrical power to the Chiller to prevent personal injury before   
					attempting any internal maintenance. Only qualified personnel should service the internal   
					components or electrical wiring.   
					Condenser   
					On air–cooled Chillers, the CONDENSER FINS should be cleaned by blowing compressed air through the con-   
					denser from the fan side. Dirt and debris accumulate on the condenser fins over time, and this build up can se-   
					verely reduce the performance of the Chiller. Cleaning of the CONDENSER COIL FINS should be done   
					approximately every three months, depending upon cleanliness of your application.   
					Fan Motor   
					On air–cooled Chillers, the condenser FAN MOTOR should be lubricated every 6 months with a few drops of   
					SAE 10 oil.   
					Pump Motor   
					The PUMP MOTOR should be lubricated with thirty drops of SAE 20 oil once a year.   
					Circulation System   
					The CIRCULATION SYSTEM should be drained and flushed periodically to avoid build up and a possible flow   
					restriction caused by contaminants.   
					Filters/Strainers   
					The STRAINER at the Chiller inlet should be removed and cleaned monthly.   
					The “Y” STRAINER, located inside the unit at the inlet of the pump, should be cleaned periodically depending on   
					applications. If a reduction in flow or cavitation of the pump occurs, remove the strainer, flush it out with water,   
					then replace.   
					620914801   
					4 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				FLUID RECOMMENDATION   
					Remcor Chillers are designed to operate with water to provide maximum performance for   
					temperatures of 40_F–100_F.   
					Distilled Water   
					Acceptable   
					Acceptable   
					De–Ionized Water   
					(1–5 MEG/OHMS)   
					De–Ionized Water   
					(5+MEG/OHMS)   
					Acceptable with Stainless Steel & PVC only   
					*No Copper or Brass   
					Propylene Glycol   
					(Lab & Industrial Grade)   
					Acceptable – 30% Glycol/70% Water   
					*For Applications with Temperatures below 40_F   
					Acceptable – 30% Glycol/70% Water   
					*For Applications with Temperatures below 40_F   
					Acceptable   
					Lab & Industrial Grade Ethylene Glycol   
					Mineral/Hydraulic Oils   
					(Viscosity<50 Centistrokes)   
					Ethylene Glycol   
					NOT Acceptable   
					(Commercial/Automotive Antifreeze)   
					*Silicate Rust Inhibitors in Automotive/Commer-   
					cial Antifreeze will damage pump seals and   
					housing which lead to failure.   
					Acidic/Basic Solutions   
					(Above 8/Below 6 PH)   
					Not Acceptable   
					Mineral/Hydraulic Oils   
					Not Acceptable   
					(Viscosity>50 Centistrokes)   
					For questions regarding special or other fluids contact IMI Cornelius Remcor at   
					800–551–4423.   
					To Purchase Lab or Industrial Glycol contact:   
					Hubbard Hall   
					IMI Cornelius   
					(800) 648–3412 – Dow Therm SR1 available in 5 gallon   
					(800) 551–4423 – Part# 111521000 5 gallons   
					620914801   
					5 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TROUBLESHOOTING   
					WARNING: Disconnect electrical power to the Chiller to prevent personal injury before   
					attempting any internal maintenance. Only qualified personnel should service internal   
					components or electrical wiring.   
					If repairs to the Chiller must be made, disconnect electrical power to the unit, then shut off the   
					water source.   
					TROUBLE   
					PROBABLE CAUSE   
					A. No Power To Unit.   
					REMEDY   
					CHILLER DOES NOT   
					OPERATE, CONTROL   
					POWER LIGHT “OFF”   
					A. Check Main disconnect fuses,   
					wiring, and power lead to unit.   
					B. Defective Control Power   
					Switch.   
					B. Replace Switch   
					C. Defective Control Transformer. C. Replace Transformer   
					D. Wrong Voltage Supplied to   
					Unit.   
					D. Supplied Voltage Must be within   
					± 10% of nameplate rating.   
					PUMP DOES NOT OPERATE, A. Line to or from Chiller is   
					A. Inspect lines and remove any   
					obstructions.   
					BUT POWER LIGHT IS “ON”.   
					restricted.   
					B. Internal or external filter is   
					blocked with debris.   
					B. Remove and clean strainer, then   
					replace.   
					C. Pump Contactor is   
					defective.   
					C. Replace Contactor.   
					D. Damaged pump motor or   
					impeller.   
					D. Replace pump motor or impeller.   
					A. Clean condenser.   
					UNIT RUNS CONTINUOUSLY, A. Condenser is restricted.   
					BUT IS NOT COOLING   
					PROCESS WATER ENOUGH.   
					B. Unit low on refrigerant.   
					C. Inefficient compressor.   
					B. Call Service.   
					C. Call Service.   
					D. Unit is undersized for   
					application.   
					D. Call REMCOR Chiller Sales Rep.   
					NOTE: When servicing a REMCOR Chiller, it is important to note all information provided on the DATA   
					PLATE located in the upper rear of the unit. If technical assistance is needed, the REMCOR Service   
					Technician will need this information along with any description of the problem(s) you are   
					encountering. The serial number and other information will also be required when ordering   
					replacement parts and any other Warranty Claims.   
					6 
					620914801   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				COMPRESSOR   
					1 
					C 
					3 
					M 
					OVERLOAD   
					115/1/60   
					5 
					8 
					1 
					9 
					M 
					6 
					115V   
					24V   
					PUMP   
					FAN   
					7 
					M 
					4 
					S 
					R 
					M 
					COMPRESSOR   
					START   
					CAPACITOR   
					START RELAY   
					ELECTRICAL WIRING DIAGRAM   
					LIGHT, POWER ON   
					FIGURE 3. WIRING DIAGRAM (115V)   
					620914801   
					7 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				COMPRESSOR   
					1 
					2 
					3 
					C 
					M 
					OVERLOAD   
					230/1/60   
					1 
					5 
					8 
					9 
					M 
					6 
					PUMP   
					FAN   
					230V   
					24V   
					7 
					M 
					4 
					S 
					R 
					M 
					COMPRESSOR   
					START   
					CAPACITOR   
					START RELAY   
					LIGHT, POWER ON   
					ELECTRICAL WIRING DIAGRAM   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				4 
					17   
					2 
					16   
					1 
					6 
					3 
					14   
					15   
					7 
					5 
					8 
					10   
					18   
					11   
					12   
					13   
					9 
					FIGURE 5. CABINET SECTION EXPLODED VIEW   
					Item   
					Item   
					No.   
					Part No.   
					Name   
					No.   
					10   
					11   
					Part No.   
					Name   
					1 
					2 
					3 
					4 
					5 
					6 
					7 
					8 
					9 
					32386   
					TemperatureController   
					Power Switch   
					Evaporator   
					31962   
					Fan Motor   
					Fan Blade   
					31934   
					31488   
					61014   
					12   
					13   
					14   
					15   
					16   
					17   
					18   
					620023503   
					60576   
					Panel, Right Side   
					Condenser   
					620023502   
					51882   
					Wrapper Panel   
					Priming Reservoir Ass’y   
					Panel, Left Side   
					Compressor   
					33082   
					Relay   
					24388   
					32378   
					Transformer   
					60992   
					32588   
					Temperature Probe   
					Panel, Front   
					31955   
					Pump   
					620023504   
					24389   
					24390R   
					Base Ass’y   
					Shroud, Condenser   
					620914801   
					9 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Download from Www.Somanuals.com. All Manuals Search And Download.   
				WARRANTY   
					IMI Cornelius Inc. warrants that all equipment and parts are free from defects in material and workmanship un-   
					der normal use and service. For a copy of the warranty applicable to your Cornelius, Remcor or Wilshire prod-   
					uct, in your country, please write, fax or telephone the IMI Cornelius office nearest you. Please provide the   
					equipment model number, serial number and the date of purchase.   
					IMI Cornelius Offices   
					AUSTRALIA D P.O. 210, D RIVERWOOD, D NSW 2210, AUSTRALIA D (61) 2 533 3122 D FAX (61) 2 534 2166   
					AUSTRIA D AM LANGEN FELDE 32 D A-1222 D VIENNA, AUSTRIA D (43) 1 233 520 D FAX (43) 1-2335-2930   
					BELGIUM D BOSKAPELLEI 122 D B-2930 BRAASCHAAT, BELGIUM D (32) 3 664 0552   
					D 
					FAX (32) 3 665 2307   
					BRAZIL D RUA ITAOCARA 97 D TOMAS COELHO D RIO DE JANEIRO, BRAZIL D (55) 21 591 7150 D FAX (55) 21 593 1829   
					ENGLAND D TYTHING ROAD ALCESTER D WARWICKSHIRE, B49 6 EU, ENGLAND D (44) 789 763 101 D FAX (44) 789 763 644   
					FRANCE D 71 ROUTE DE ST. DENIS D F-95170 DEUIL LA BARRE D PARIS, FRANCE D (33) 1 34 28 6200 D FAX (33) 1 34 28 6201   
					GERMANY D CARL LEVERKUS STRASSE 15 D D-4018 LANGENFELD, GERMANY D (49) 2173 7930 D FAX (49) 2173 77 438   
					GREECE D 488 MESSOGION AVENUE D AGIA PARASKEVI D 153 42 D ATHENS, GREECE D (30) 1 600 1073 D FAX (30) 1 601 2491   
					HONG KONG D 1104 TAIKOTSUI CENTRE D 11-15 KOK CHEUNG ST D TAIKOKTSUE, HONG KONG D (852) 789 9882 D FAX (852) 391 6222   
					ITALY D VIA PELLIZZARI 11 D 1-20059 D VIMARCATE, ITALY D (39) 39 608 0817 D FAX (39) 39 608 0814   
					NEW ZEALAND D 20 LANSFORD CRES. D P.O. BOX 19-044 AVONDALE D AUCKLAND 7, NEW ZEALAND D (64) 9 8200 357 D FAX (64) 9 8200 361   
					SINGAPORE D 16 TUAS STREET D SINGAPORE 2263 D (65) 862 5542 D FAX (65) 862 5604   
					SPAIN D POLIGONO INDUSTRAIL D RIERA DEL FONOLLAR D E-08830 SANT BOI DE LLOBREGAT D BARCELONA, SPAIN D (34) 3 640 2839 D FAX (34) 3 654 3379   
					USA D ONE CORNELIUS PLACE D ANOKA, MINNESOTA D (763) 421-6120 D FAX (763) 422-3255   
					LD004   
					4/21/98   
					620914801   
					10   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				IMI CORNELIUS INC.   
					CORPORATE HEADQUARTERS:   
					One Cornelius Place   
					Anoka, Minnesota 55303-6234   
					(763) 421-6120   
					(800) 238-3600   
					620914801   
					9 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |