					Chromalox   
					SERVICE REFERENCE   
					Installation   
					DIVISION   
					SALES   
					4 
					SECTION NHWO   
					(Supersedes PE406-4)   
					and   
					REFERENCE   
					PE406-5   
					RENEWAL PARTS IDENTIFICATION   
					161-048710-001   
					DATE   
					FEBRUARY, 1999   
					1-3/8” Conduit   
					Openings   
					12-5/16”   
					Type NWHO-3 Series Circulation Heaters   
					(for Regular and Fuel Oil Heating)   
					8-1/32”   
					1” Pipe   
					Outlet   
					Specifications — Table A   
					Thermostat   
					Type AR   
					Regular Oil Heaters   
					Dimensions (In.)   
					A 
					Mounting Lugs   
					B 
					C 
					3/8” - 16   
					Model   
					Volts   
					Phase   
					kW   
					W/In2   
					A 
					B 
					C 
					Threaded Holes -   
					1-1/2” Deep   
					1-1/4” Centers   
					NWHO-33015   
					NWHO-34515   
					NWHO-36015   
					NWHO-37515   
					NWHO-39015   
					3 
					4.5   
					6 
					7.5   
					9 
					32-15/16   
					32-15/16   
					42-15/16   
					55-7/16   
					55-7/16   
					22-1/2   
					22-1/2   
					32-1/2   
					45   
					16-1/2   
					16-1/2   
					26-1/2   
					39   
					240 or 480   
					1 or 3 s   
					23   
					45   
					39   
					Fuel Oil Heaters   
					1” Pipe   
					Inlet   
					NWHO-30315   
					NWHO-30415   
					NWHO-30615   
					3 
					4 
					6 
					32-15/16   
					42-15/16   
					55-7/16   
					22-1/2   
					32-1/2   
					45   
					16-1/2   
					26-1/2   
					39   
					240 or 480   
					1 or 3 s   
					15   
					6-1/8”   
					GENERAL   
					Depending upon the order specifications, the NWHO-3 may or   
					may not be factory equipped with AR or other Chromalox thermostat.   
					Such thermostats function to control outlet temperatures and to limit   
					internal temperatures under abnormal flow conditions. These controls   
					do not fail safe.   
					WARNING: This heater is not intended for use in haz-   
					ardous atmospheres where flammable vapors, gases,   
					liquids or other combustible atmospheres are present   
					as defined in the National Electrical Code. Failure to   
					comply can result in explosion or fire.   
					The NWHO-3 series is a general-purpose regular and fuel oil solu-   
					tion circulation heater intended for use indoors. It is designed for 150   
					psig at 550˚F per ANSI standards.   
					CAUTION: Users should install adequate back-up controls   
					and safety devices with their electric heating equipment.   
					Where the consequences of failure may be severe, back-   
					up controls are essential. Although the safety of installa-   
					tion is the responsibility of the user, Chromalox will be   
					glad to make equipment recommendations.   
					The 3 steel-sheathed tubular elements are centered in a 3” diame-   
					ter steel heating chamber and welded to a removable steel flange. The   
					assembly is surrounded by 1-1/2” insulation and sheet metal jacket.   
					INSTALLATION   
					Note: A drain pipe located at the bottom of the heater should be   
					provided and enough room left, when mounting heater, to allow   
					draining the heater.   
					WARNING: Hazard of Shock. Disconnect all power   
					before installing heater.   
					1. Vertical mounting (Preferred) —   
					When the heater is vertically mounted, the terminal housing will be   
					at the top of the heater. The inlet pipe will be located on the side   
					near the bottom of the heater and the outlet pipe at the top.   
					The axis of the chamber will be in a vertical position as in the   
					photo above and as in Figure A.   
					2. Horizontal Mounting (Optional) —   
					When mounting heater horizontally, inlet and outlet pipes must be   
					up. In any other position, heater cannot be purged of air, and ele-   
					ments may be seriously damaged. (See Figure B.)   
					Correct   
					Incorrect   
					Correct   
					Incorrect   
					Figure A — Vertical Mounting   
					Figure B — Horizontal Mounting   
					© 2010 Chromalox, Inc.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				RENEWAL PARTS IDENTIFICATION   
					Regular Oil Heater   
					Phase   
					Fuel Oil Heater   
					Phase   
					Heating   
					Elements   
					Heating   
					Elements   
					Model   
					Volts   
					kW   
					Model   
					Volts   
					kW   
					NWHO-33015   
					NWHO-33015   
					NWHO-33015   
					NWHO-33015   
					240   
					240   
					480   
					480   
					1 
					3 
					3 
					3 
					3 
					155-024796-031   
					155-024796-032   
					155-024796-033   
					155-024796-034   
					NWHO-30315   
					NWHO-30315   
					NWHO-30315   
					NWHO-30315   
					240   
					240   
					480   
					480   
					1 
					3 
					3 
					3 
					3 
					155-024796-066   
					155-024796-067   
					155-024796-068   
					155-024796-069   
					3 s   
					1 
					3 s   
					1 
					3 s   
					3 s   
					NWHO-34515   
					NWHO-34515   
					NWHO-34515   
					NWHO-34515   
					240   
					240   
					480   
					480   
					1 
					4.5   
					4.5   
					4.5   
					4.5   
					155-024796-036   
					155-024796-037   
					155-024796-038   
					155-024796-039   
					NWHO-30415   
					NWHO-30415   
					NWHO-30415   
					NWHO-30415   
					240   
					240   
					480   
					480   
					1 
					4 
					4 
					4 
					4 
					155-024796-071   
					155-024796-072   
					155-024796-073   
					155-024796-074   
					3 s   
					1 
					3 s   
					1 
					3 s   
					3 s   
					NWHO-36015   
					NWHO-36015   
					NWHO-36015   
					NWHO-36015   
					240   
					240   
					480   
					480   
					1 
					6 
					6 
					6 
					6 
					155-024796-041   
					155-024796-042   
					155-024796-043   
					155-024796-044   
					NWHO-30615   
					NWHO-30615   
					NWHO-30615   
					NWHO-30615   
					240   
					240   
					480   
					480   
					1 
					6 
					6 
					6 
					6 
					155-024796-081   
					155-024796-082   
					155-024796-083   
					155-024796-084   
					3 s   
					1 
					3 s   
					1 
					3 s   
					3 s   
					NWHO-37515   
					NWHO-37515   
					NWHO-37515   
					NWHO-37515   
					240   
					240   
					480   
					480   
					1 
					7.5   
					7.5   
					7.5   
					7.5   
					155-024796-046   
					155-024796-047   
					155-024796-048   
					155-024796-049   
					3 s   
					1 
					Parts Common To All Heaters   
					3 s   
					Standard Gasket . . . . . . . . . . . . . . . . . . . . . . . . . .132-017222-015   
					Spiral Wound Gasket . . . . . . . . . . . . . . . . . . . . . . .132-073008-009   
					Thermostat (Regular Oil) . . . . . . . . . . . . . . . . . . . .300-057502-015   
					Thermostat (Fuel Oil) . . . . . . . . . . . . . . . . . . . . . .300-057502-016   
					NWHO-39015   
					NWHO-39015   
					NWHO-39015   
					NWHO-39015   
					240   
					240   
					480   
					480   
					1 
					9 
					9 
					9 
					9 
					155-024796-051   
					155-024796-052   
					155-024796-053   
					155-024796-054   
					3 s   
					1 
					3 s   
					Note: When ordering parts for Model Numbers suffixed by “XX” or any other letters not specifically identified on this instruction sheet, order Renewal Parts on special order basis, giving   
					name of part, part number, model number and description.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Limited Warranty:   
					Please refer to the Chromalox limited warranty applicable to this product at   
					
					2150 N. RULON WHITE BLVD., OGDEN, UT 84404   
					Phone: 1-800-368-2493   
					
					99 - 050   
					TA - P9 - EF   
					Litho in U.S.A.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |