| CHARNWOOD   COUNTRY 14B   Roomheater with Boiler   Operating   and   Installation Instructions   C H A R N W O O D B i s h o p s W a y , N e w p o r t , I s l e o f W i g h t P O 3 0 5 W S , U n i t e d K i n g d o m   T : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 9 9 F : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d @ a j w e l l s . c o . u k w w w . c h a r n w o o d . c o m   Download from Www.Somanuals.com. All Manuals Search And Download.   or fire lighters, and kindling on the   grate and cover with approximately 2   inches of fuel. Turn the control knob   to maximum, and open the airwash   control fully (see Fig. 1). Light the   paper or fire lighters. Close the doors   until the fuel is well ignited then load   with fuel and adjust the air controls to   the required setting.   firebox in two stages waiting between   each stage for the flames to appear   above the fire.   REFUELLING   Keep the firebox well filled but do not   overfill to prevent fuel from spilling   over the top of the front fire bars.   After a period of slumbering always   turn the air control up to maximum   and wait until flames appear above the   fuel bed before opening the doors.   Care should be taken especially when   burning wood that fuel does not   project over the front fire bars or   damage to the glass may be caused   when the doors are closed, it can also   cause the glass to black up.   Burning coal will produce more soot   deposits than other fuels, especially if   the fire is run at low levels for long   periods. It is therefore vital to clean   the throat plate regularly, weekly   cleaning is recommended.   On initial lighting, the stove may   smoke and give off an odour as the   silicon paint with which the firebox is   painted reacts to the heat. This is   normal and will cease after a short   time, but meanwhile the room should   be kept well ventilated.   Never fully close the Airwash control   when burning coal.   When relighting the stove, riddle (if   burning solid fuel), remove any   clinker from the firebed and then   empty the ashpan.   SPECIAL POINTS   WHEN BURNING   WOOD AND PEAT   CONTROLLING THE   FIRE   The rate of burning and hence the   output is controlled by the control   knob on the side of the fire and the   airwash control (see Fig.1).   The grate should be kept in the wood   burning position and should not be   riddled until the ash becomes so deep   that it begins to block the passage of   air into the firebox at the side of the   grate. When this is the case do not   remove all of the ash using the   Solid Fuel   Riddle   riddling mechanism but keep a layer   about half an inch thick as this enables   the wood to burn more effectively.   When burning wood or peat use the   airwash control in the same way as   described (see "CONTROLLING   THE FIRE" )   The control knob is linked to a   thermostat which senses the boiler   temperature. The number at the front   of the knob is the number at which it   is set.   Wood   The airwash control should be kept at   least slightly open most of the time to   keep the glass clean. It may be fully   opened when rapid heating is required   or to help clean any deposits from the   glass. It will not be possible to keep   the glass clean if this control is fully   closed, particularly immediately after   refuelling.   OVERNIGHT   BURNING   For overnight burning the fire doors   must be closed.   Fig 2. Grate Operation   ASH CLEARANCE   The ashpans should be emptied   When burning solid fuel the ashpans   should be emptied and the fire riddled.   If the fire is very low then it may be   necessary to add a little fuel and turn   the thermostat control up to maximum   for a brief period until the fire is   burning brightly before filling with   fuel. When the new fuel has ignited,   the thermostat control should be   turned down to the required setting   and the airwash control moved to a   low setting. If the central heating   pump is off overnight then the   regularly before it becomes too full.   Never allow the ash to accumulate in   the ashpans so that it comes in contact   with the underside of the grate as this   will seriously damage the grate bars.   The ashpans are handled using the tool   provided. Care should be taken to   ensure that ash is cool before   RIDDLING   When burning solid fuels riddling   twice a day is usually sufficient. When   burning wood or peat, ash should be   allowed to build up and generally   weekly riddling will be sufficient. The   fire should be riddled with the doors   shut (see Fig 2.) Place the tool onto   the riddling lever and rotate between   the 1 o'clock and 3 o'clock positions   several times. Too much riddling can   result in emptying unburnt fuel into   the ashpan and should therefore be   avoided. If any clinker forms it should   be removed from the firebed. After   riddling, the grate should be put back   into the solid fuel or wood position as   required (the tool should be in the 1   o'clock position for solid fuel or in the   5 o'clock position for wood).   emptying it into plastic liners or bins.   To make ash removal easier there is a   special Charnwood ash carrier   available. This may be purchased from   your supplier or, in case of difficulty,   from ourselves.   thermostat may be left at the same   setting for both day and night   operation. If the central heating pump   is on overnight then set the thermostat   control to give the required level of   heating. Some experimentation will be   necessary to find the settings most   suitable for the particular fuel used   and the draw on the chimney.   SPECIAL POINTS   WHEN BURNING   COAL   When loading the stove take care not   to smother the fire, instead fill the   To revive the fire, empty the ashpans,   Page 2   Country 14B 09/03   Download from Www.Somanuals.com. All Manuals Search And Download.   riddle, and open the air controls to   maximum. When the fire is burning   well load on more fuel as necessary   and move the air controls to the   desired setting.   retaining lugs.   that a suitable fuel is being used, d)   that there is an adequate air supply   into the room,   e) that an extractor fan is not fitted in   the same room as the stove.   f) there is sufficient draw in the   chimney, (once the chimney is warm a   draught reading of at least 0.10 inches   water gauge should be obtained).   CHIMNEY SWEEPING   The chimney should be swept at least   twice a year. Where a top outlet is   used it will generally be possible to   sweep the chimney through the   appliance.   When burning wood use large logs   rather than small ones. Proceed as   above, but do not riddle the fire either   when shutting down or reviving.   First remove the side fire plates, front   firebars and the throat plate. Then   sweep the chimney ensuring that soot   is removed from all horizontal   surfaces after sweeping.   Door Glass Blacks Up   CLEANINGAND   MAINTENANCE   The stove is finished with a high   temperature paint which will   Keeping the glass clean requires a   certain amount of experimentation due   to the differences in the draw of   different chimneys. The following   points should be noted and with a little   care should enable the glass to be kept   clean in most situations:   In situations where it is not possible to   sweep through the appliance the   installer will have provided alternative   means, such as a soot door. After   sweeping the chimney the appliance   flue outlet and the flue pipe   withstand the temperatures   encountered in normal use. This may   be cleaned with a damp lint-free cloth   when the stove is cold. Should re-   painting become necessary, high   temperature paints are available from   your supplier or from stove shops.   a) The airwash relies on a supply of   heated air to keep the glass clean,   therefore, when lighting the stove   allow the firebed to become well   established before closing the air   controls. This may also be necessary   when re-fuelling the stove.   connecting the stove to the chimney   must be cleaned with a flue brush.   The glass in the doors is a zero   expansion ceramic glass, capable of   withstanding the heat of the fire.   After clearing any soot from within   the stove, replace the throat plate (see   Fig. 3), the front firebars, and side   fireplates.   Before cleaning the glass open the   doors and allow them to cool. Clean   the glass using a damp cloth and then   wiping over with a dry cloth. Any   stubborn deposits on the glass may be   removed with a proprietary stove glass   cleaner or ceramic hob cleaner. Some   deposits on the glass may be burnt off   simply by running the fire at a fast rate   for a few minutes. Do not use abrasive   cleaners or pads as theses can scratch   the surface which will weaken the   glass and cause premature failure.   b) When re-fuelling keep the fuel as   far back from the front firebars as   possible, do not try to fit too much   fuel into the firebox.   Different types of sweep's brushes are   available to suit different flueways.   For standard brick chimneys a wire   centre sweep's brush fitted with a   guide wheel is recommended. For   prefabricated insulated chimneys the   manufacturers instructions with regard   to sweeping should be consulted.   c) Never completely close the airwash   control - as a guide it should be at   least a quarter open.   d) Wet wood or logs overhanging the   front firebars will cause the glass to   blacken.   It is always more difficult to keep the   glass clean when running the stove   very slowly for long periods.   THROAT PLATE AND   FLUEWAY CLEANING   It is important that the throat plate and   all the stove flueways are kept clean.   When burning smokeless fuels they   should be cleaned monthly. When   burning other fuels they should be   cleaned at least once a week, and more   frequently if necessary. It is not   If blackening of the glass still occurs   check that all flue connections and the   blanking plate are well sealed. It is   also important that the chimney draw   is sufficient, (when the chimney is   warm a draught reading of at least   2.54 mm, or 0.10 inches, water gauge   should be obtained), and that it is not   affected by down-draught.   Tool   Pull Forward   Swing Down   necessary to let the fire out completely   to carry out these operations.   When burning coal some blackening   of the glass may occur below the level   of the front firebars. This will not   obscure the view of the fire or affect   its performance.   The throat plate is lowered using the   door opening tool. Slide the tool into   the bracket from the side, pull the   throat plate forward, and then lower it   as shown in Fig. 3. Any sooty deposits   should then be swept from the plate   and into the fire.   Fig.3 Throat Plate Location   Fume Emission.   TROUBLE SHOOTING   Fire Will Not Burn.   Check that:   a) the air inlet is not obstructed in any   way,   Warning Note: Properly installed   and operated this appliance will not   emit fumes. Occasional fume from   de-ashing and re-fuelling may occur.   Persistent fume emission is   potentially dangerous and must not   be tolerated. If fume emission does   persist, then the following   While the throat plate is lowered clean   any sooty deposits from the boiler   faces and the airwash tubes.   Return the throat plate to its correct   position - raise the front of the plate,   push it back and then lower it onto the   b) chimneys and flueways are clear, c)   Page 3   Country 14B 09/03   Download from Www.Somanuals.com. All Manuals Search And Download.   immediate actions should be taken:   f) Door seals and airwash slide are   intact.   b) the throat plate is fitted correctly   (see Fig. 3.) and that it is not distorted.   c) the door seals are in good condition.   d) If the hot water goes cold when the   pump is turned on, or if some radiators   are hotter than others, then the system   may need balancing, the pump may be   pumping the water too quickly around   the system, or the radiators may need   bleeding. Please ask your installer to   check these points.   a) Open doors and windows to   ventilate the room.   b) Let the fire out and safely dispose   of the fuel from the appliance.   c) Check for flue or chimney   blockage, and clean if required.   d) Do not attempt to re-light the fire   until cause of fume has been   identified, if necessary seek   professional advice.   Over-Firing   If the fire is over-fired it will cause   premature failure of the internal fire   parts. Overfiring is occurring when   any parts of the fire begin to glow red.   To prevent over-firing ensure that:   a) the door seals are kept in good   condition, and that the doors are   sealing correctly,   b) the thermostat on the fire is   working correctly,   c) a suitable fuel is being used,   d) the fire is not fitted onto a heating   system which is too large.   The most common cause of fume   emission is flueway or chimney   blockage. For your own safety these   must be kept clean.   Chimney Fires.   If the chimney is thoroughly and   regularly swept, chimney fires should   not occur. However, if a chimney fire   does occur turn the controls to the   minimum setting, and tightly close the   doors of the appliance. This should   cause the chimney fire to go out in   which case the controls should be kept   at the minimum setting until the stove   has gone out. The chimney and   flueways should then be cleaned. If   the chimney fire does not go out when   the above action is taken then the fire   brigade should be called immediately.   Fire blazing out of control   Check that :   Freezing   Do not light the fire if there is any   possibility that any parts of the system   may be frozen.   a) The doors are tightly closed.   b) The aircontrols are set at the   minimum setting.   c) the thermostat flap is closed (at the   bottom of the left hand side of the   appliance, see Fig. 1.) and that it is not   prevented from closing completely by   a piece of ash,   Lack of Heat To   Radiators / Hot Water   After a chimney fire the chimney   should be carefully examined for any   damage. Expert advice should be   sought if necessary.   d) The airwash control is closed.   e) A suitable fuel is being used.   Check that:   a) the fire is burning properly - if not   then carry out the checks under "Fire   Will Not Burn".   Page 4   Country 14B 09/03   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION INSTRUCTIONS FOR THE   CHARNWOOD COUNTRY 14B   complete chimney.   HEALTH AND SAFETY   CHIMNEY   If it is found that there is excessive   draw in the chimney then a draught   stabilizer should be fitted.   PRECAUTIONS   In order for the appliance to perform   satisfactorily the chimney height must   not be less than 4 metres measured   vertically from the outlet of the stove   to the top of the chimney. The internal   dimensions of the chimney should   preferably be 175 mm (7 inches) or   200mm (8 inches) either square or   round and MUST NOT BE LESS   THAN 150 mm (6 INCHES).   Please take care when installing the   stove that the requirements of the   Health and Safety at Work Act 1974   are met.   It is important that there is sufficient   draw in the chimney and that the   chimney does not suffer from down-   draught. When the chimney is warm   the draw should be not less than 2.54   mm (0.10 inches) water gauge. If in   doubt about the chimney seek expert   advice.   Some types of fire cement are caustic   and should not be allowed to come   into contact with the skin. In case of   contact wash with plenty of water.   If an existing chimney is to be used it   must be swept and checked, it must be   in good condition, free from cracks   and blockages, and should not have an   excessive cross sectional area (e.g.   greater than 250mm x 250mm). If you   find that the chimney is in poor   condition then expert advice should be   sought regarding the necessity of   having the chimney lined. If it is   If there is a possibility of disturbing   any asbestos in the course of   installation then please use appropriate   protective equipment.   HEARTH AND FIRE   SURROUND   The stove must stand on a fireproof   hearth and must be situated at least   300mm (12 inches) from any   combustible material. The positioning   of the stove and the size of the hearth   are governed by building regulations   for Class 1 appliances. These building   regulations state that the hearth must   extend in front of the stove by at least   300mm (12 inches) and to the sides of   the stove by at least 150mm (6   inches). If in doubt as to the   There must not be an extractor fan   fitted in the same room as the stove as   this can cause the appliance to emit   fumes into the room.   There must be an adequate air supply   into the room in which the appliance is   installed totalling at least 100 square   cm. (16 square inches) to provide   combustion air. This is particularly   necessary if the room is double glazed.   found necessary to line the chimney   Boiler   Output   (kW)   Do not light the fire before the boiler   has been connected to the system and   filled with water, as this can cause   serious damage to the boiler.   12.0   10.0   8.0   6.0   4.0   2.0   0 positioning of the stove expert advice   should be sought either from the   supplier or the local building   inspector.   In addition to these instructions the   requirements of BS.8303 and BS.6461   Pt 1&2; 1984 must be fulfilled. Local   Authority Bylaws and Building   Regulations regarding the installation   of Solid Fuel burning appliances, flues   and chimneys must also be observed.   The fireplace must allow good   circulation of air around the appliance   to ensure that maximum heat is   transferred to the room and also to   prevent the fireplace from   overheating. A gap of 150mm (6   inches) each side and 300mm (12   inches) above the appliance should   give sufficient air circulation. If a   wooden mantelpiece or beam is used   in the fireplace it should be a   minimum of 460mm (18 inches), and   preferably 600mm (24 inches) from   the appliance. In some situations it   may be necessary to shield the beam   or mantelpiece to protect it.   0 1.0 2.0 3.0 4.0   Space Output   PERFORMANCE   (kW)   The output of the Country 14B is 10.5   kW (35,800 Btu/h) to water and 3.7   kW (12,600 Btu/h) to the room. The   outputs were obtained burning   smokeless fuel over a four hourly re-   fuelling cycle with the doors closed.   Fig. 4. Performance Chart   then a lining suitable for Solid Fuel   must be used.   If there is no existing chimney then a   prefabricated block chimney or a twin   walled insulated stainless steel flue to   BS.4543 can be used either internally   or externally. These chimneys must be   fitted in accordance with the   The heat output to the room is directly   proportional to the heat output to   water as shown in Fig. 4. This means   that if the water heating load is less   than the rated output then the room   heating will be reduced by the same   proportion. This must be borne in   mind when calculating the heating   requirements.   CENTRAL HEATING   SYSTEM   The central heating system must   comply with BS:5449 part 1.   manufacturers instructions and   Building Regulations.   Single wall flue pipe is suitable for   connecting the stove to the chimney   but is not suitable for using for the   If the system is to be a combined   heating and domestic hot water system   then a double feed indirect hot water   storage cylinder to BS:1556 part 1   Page 5   Country 14B 09/03   Download from Www.Somanuals.com. All Manuals Search And Download.   should be used. In order to prevent the   build up of scale and corrosion a   suitable inhibitor should be used. The   system must be correctly vented as   shown in Figs. 5 and 6. The height   differential between the header tank   and the appliance must not exceed   15.2 metres (50 feet).   22mm Open Vents   Feed and Expansion Tank   Overflow   Cold Water Tank   Overflow   Domestic Hot Water Draw Off   If all four boiler tappings are used   then, if possible, diagonal pairs should   be connected for domestic hot water   and central heating. Where a common   return is used an injector tee must be   incorporated into the system as shown   in Fig. 7. This will ensure that a good   domestic hot water supply is   Gravity Radiator   Drain Cock   Indirect Hot Water Cylinder   maintained when the central heating   pump is operating.   Central Heating Flow   Circulating Pump   Central Heating Return   Minimum Return   Thermostat   The system must incorporate a gravity   circuit which will normally heat the   domestic hot water and an unvalved   radiator with an output of at least 1   kW. When the appliance is not   connected to a domestic hot water   system the unvalved radiator(s) on the   gravity circuit must have an output of   at least 1.25 kW. This is to prevent   boiling in case of pump failure. All   pipework in the primary circuit must   be 28 mm diameter and the gravity   flow pipe must rise continuously from   the boiler to the open vent. Two   typical systems are shown in Figures   5. and 6.   Drain Cock at Lowest Point   Fig. 5. Typical Central Heating & Hot Water System   Using 4 Boiler Tappings   22mm Open Vents   Feed and Expansion Tank   Overflow   Cold Water Tank   Overflow   Domestic Hot Water Draw Off   If the appliance is used to heat a small   central heating system then the heat   output to the room from the fire will   be reduced. Fig. 4. shows the ratio of   space heating to water heating which   can be expected.   Gravity Radiator   Drain Cock   Indirect Hot Water Cylinder   Fitting a radiator in the same room as   the fire is recommended as it will   allow greater flexibility in the way   that the system is operated as well as   ensuring that there is sufficient heat.   Minimum Return Thermostat   Circulating Pump   Central Heating Flow   Connect the heating system to the   boiler ensuring that the primary flow   pipe rises continuously from the   appliance to the vent. Fill the system   with water and check for leaks.   Central Heating Return   Drain Cock at Lowest Point   Injector Tee   Fig. 6. Typical Central Heating & Hot Water System   Using 3 Tappings   SYSTEM CONTROLS   The circulating pump may be   controlled by means of time switches,   room thermostats or outdoor   thermostats. Radiators may be either   manually or thermostatically   Gravity Return   (28mm Pipe)   controlled. These controls will all   work in conjunction with the   thermostat on the appliance and the   low limit pipe thermostat.   Common Return to Boiler   (28mm Pipe)   Central Heating Return   We recommend fitting a pipe   thermostat onto the gravity return to   Fig. 7. Injector Tee.   Page 6   Country 14B 09/03   Download from Www.Somanuals.com. All Manuals Search And Download.   Back of the Stove   Blanking Plate   Alternative   Soot Door   Positions   Soot Door   In Side or Rear   Of Chimney   Register Plate   With Soot Door   Clamping Plate   with fold horizontal   Blanking Plate   Clamping plate finishes   flush with inside face of   firebox top and bottom.   Fig 8. Vertical Register Plate   With Bricked Up Fireplace   Seal Blanking Plate   with fire cement   Fig 11. Horizontal Register Plate   With Optional Vertical   Alternative   Soot Door   Positions   Rear Flue Connector   Fig. 12. Flue Blanking Plate.   chimney or in the register   plate. Various types and positions of   soot doors are shown in figures 8 to   10.   on the boiler faces and will thereby   increase the life of the boiler. It will   also ensure that priority is given to the   domestic hot water. These thermostats   are available from ourselves if you are   unable to obtain them locally.   Register Plate   With Soot Door   THERMOSTAT   Before lighting the fire check the cold   setting distance of the thermostat.   CONNECTIONS TO   FLUES   There are several ways of connecting   the stove to the flue. These are   illustrated in figures 8 to 10.   Remove the cover plate on the left   hand side of the stove to give access to   the thermostat. With the control knob   at the maximum setting the flap   Fig 9. Horizontal Register Plate   With Rear Flue Connection   should be 18 mm from the air inlet as   shown in Fig. 13. To adjust the   distance slacken the locking nut and   adjust as necessary. When set correctly   If the optional vertical rear flue   connector is used then the chimney   may be swept through the appliance.   Alternative   Soot Door   Positions   Horizontal lengths of flue must be   kept to a minimum and should not be   more than 150mm (6 inches) long.   The sealing face of the flue collar   must be coated with fire cement   before fixing to the body of the stove   using the two screws provided. The   blanking plate must be removed,   sealed with fire cement and refitted,   care being taken to ensure that the fold   on the clamping plate is in line with   the lugs on the firebox as shown in   Fig. 12. Ensure the clamping plate   does not prevent the throat plate from   seating correctly. All flue connections   must be well sealed.   18mm   Register Plate   With Soot Door   Fig 10. Horizontal Register Plate   With Top Flue Connection   SOOT DOORS   Locking Nut   It is possible to pass a 16 inch   Thermostat Flap   act as a low limit thermostat This   should be wired into the mains supply   to the pump so that if the gravity   return temperature drops below 45º C   then the pump will cut out. This will   help to prevent condensation forming   diameter sweeps brush through the   appliance but in most back outlet   installations it will be necessary to   have a soot door to enable the   chimney to be swept. This may either   be in the actual brickwork of the   Fig. 13. Thermostat Setting   Page 7   Country 14B 09/03   Download from Www.Somanuals.com. All Manuals Search And Download.   re-tighten the locking nut. Ensure that   the flap opens and closes freely as the   knob is turned.   3. The throat plate must be fitted in the   roof of the appliance and should be   checked to ensure that it has not   become dislodged in transit. The   method of location and positioning of   the throat plate is shown in Fig. 3.   The central heating pump should be   adjusted to give the correct water flow   against the circuit resistance and the   system should be correctly balanced.   On completion of the installation and   commissioning please leave the   operating instructions with the   customer and advise on the use of the   appliance and any controls on the   system.   PRE LIGHTING   CHECK   Before initial lighting the following   points should be checked :-   COMMISSIONING   On completion of the installation and   after allowing a suitable period of time   for the fire cement and mortar to dry   out, the stove should be lit and   checked to ensure that smoke and   fumes are taken from the appliance up   the chimney and emitted safely. Also   check all joints and seals.   1. The bottom grate bars must all be   fitted and should move freely and   easily when the riddling mechanism is   operated.   2. The plates round the sides and back   of the grate must be in position and   sitting correctly.   Flue connection may   be Top or Rear   Boiler tappings are 1" BSP Female   136   601   ø154   136   357   340   451   608   789   731   683   570   616   389   136   344   Country 14B Dimensions   (All dimensions are in mm)   Page 8   Country 14B 09/03   Download from Www.Somanuals.com. All Manuals Search And Download.   Issue C   CHARNWOOD COUNTRY 14B PARTS LIST   35   46   45   9 23   Item 24 has been replaced by items 51 & 52   but they are not interchangeable.   36   42   26   14   7 6 52   13   10   15   11   21   12   31   39   41   40   37   38   43   16   30   32   27   28   15   21   29   17 31 19   20   8 7 6 23 22 33   25   24 34   24 26   51   Item Part No.   Description   Item Part No.   Description   1*   2*   3*   4*   5*   6 7 8 9 008/FV35L   008/FV35R   008/FV35/S   008/FW29   008/TW44S   006/LW30   004/EW23   002/FV07   010/NV31   012/NV14/1   012/FV14/2   012/FV14/3   012/FV14/4   004/FV15   Left Hand Door Seal   Right Hand Door Seal   Door Seal Set Incl. Adhesive   Door Seal Adhesive   Glass Channel (set of 8)   Glass (Inc Channel)   Glazing Bar   36   37   38   39   40   41   42   43   45   46   009/CO14B/A   002/TW34   008/FW48   008/FV49   008/BW50   012/FV10B/19   012/FV11   012/FW34   010/TW33   012/TW09   Firebox / Boiler Assy (Country 14B)   Riddler Knob & Lever   Thermostat   Thermostat Flap   Thermostat Knob   Thermostat Cover   Serial No. Label   Scraper Tool   Vert. Rear Flue Connector (Opt'l Extra)   Blanking Plate   Front Firebars   Throat Plate   10   11   12   13   14   15   16   17   18   19   20   21   22   23   24   25   26   27   28   29   30   31   32   33   34   35   Secondary Air Slide   Secondary Air Slide Guide   Secondary Air Slide Retainer   Secondary Air Cover   Secondary Air Rod   Side Fire Plate   47* 012/TW14   48* 004/FV18   49* 010/BW51   50* 008/TH02/L   51   52   Primary Air Slide   Primary Air Slide Guide   Ash Carrier (Optional Extra)   Low Level Pipe Stat (Opt'l Extra)   R.H. Door Knob & Spindle   Door Catch Cam   002/EW15   002/BV16   002/DY18   002/KV14   Back Fire Plate   Bottom Grate Bar   002/CG01   002/CG01S14   004/FV17L   004/FV17R   004/BV19   008/BW39/S   008/FW27   008/FV03/A   002/BV12   002/TW13   012/BV20/A   012/BV22/A   002/BV30   Set of Grate Bars (14 per set)   Left Hand Ashpan   Right Hand Ashpan   Ash Shedding Plate   Hinge Pin Set (4 per set)   Hinge Post   Door Catch Assembly   Left Hand Door Knob   Air Control Knob   Ashpan / Door Opening Tool   Riddling Tool   Carrier Bar   Mover Bar   012/BV33   012/BV23   012/CG05   002/FV01   002/FV02   Riddler Rod   Idler Rod   Left Hand Door   Right Hand Door   Flue Collar   002/CH12B   * These items are not shown on the drawing.   To obtain spare parts please contact your local stockist   giving Model, Part No. and Description. In case of   difficulty contact the manufacturer at the address shown.   This drawing is for identification purposes only.   C H A R N W O O D B i s h o p s W a y , N e w p o r t , I s l e o f W i g h t P O 3 0 5 W S , U n i t e d K i n g d o m   T : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 9 9 F : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d @ a j w e l l s . c o . u k w w w . c h a r n w o o d . c o m   Download from Www.Somanuals.com. All Manuals Search And Download.   Your Local Charnwood Dealer   C H A R N W O O D B i s h o p s W a y , N e w p o r t , I s l e o f W i g h t P O 3 0 5 W S , U n i t e d K i n g d o m   T : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 9 9 F : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d @ a j w e l l s . c o . u k w w w . c h a r n w o o d . c o m   Download from Www.Somanuals.com. All Manuals Search And Download.   |