		 UDS / UDH Series   
					Ultra Low NOx Direct Vent Water Heaters   
					SERVICE   
					MANUAL   
					Troubleshooting Guide   
					and Instructions for Service   
					(To be performed ONLY by   
					qualified service providers)   
					Models Covered   
					by This Manual:   
					ECO-Defender Safety System® Models   
					UDS140S*FRN   
					UDS150S*FRN   
					UDH1504T*FRN   
					UDH165T*FRN   
					UDH175S*FRN   
					UDH50T45FR*N   
					UDH65T45FR*N   
					UDH75T50FR*N   
					(*) Denotes Warranty Years   
					Manual 238-49640-00A   
					Save this manual for future reference   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				INTRODUCTION   
					The new Bradford White UDS and UDH water heaters are designed to   
					provide reliable performance with enhanced standard features. Design   
					features include reliable standing pilot ignition system, enhanced   
					diagnostics, simplified servicing, certified FVIR technology and Ultra   
					Low NOx emissions.   
					The UDS and UDH water heaters use a combustion system where   
					combustion air is drawn from the outside of the building. The gas control   
					maintains water temperature and maintains gas flow. If a situation outside   
					of normal operating parameters exists, the gas control diagnostic LED wll   
					flash a code to positively identify an operational issue.   
					This service manual is designed to facilitate problem diagnosis and   
					enhance service efficiency. To further promote quicker service times the   
					gas valve can be removed and replaced without draining the water heater.   
					Please read the service manual completely before attempting service on   
					this new series of direct vent water heaters.   
					How the Safety System Works   
					During normal operation, air for the combustion chamber is drawn into   
					the water heater through the vent pipe from outside your building. The air   
					travels into the closed combustion chamber. The air then mixes in a   
					normal manner with supplied gas and is efficiently combusted, producing   
					Ultra Low NOx emissions.   
					In the unlikely event trace amounts of flammable vapors are present in the   
					area surrounding the water heater, the sealed combustion system prevents   
					the flammable vapors from reaching the ignition source.   
					3 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Honeywell Gas Control Troubleshooting Chart   
					Flammable Vapor Ignition Resistant Water   
					Heaters   
					Observe green LED indicator on   
					Gas Control. Error flash codes are   
					displayed with a three second pause   
					before repeating. Check and repair   
					the system as noted in the   
					Green LED Indicator   
					troubleshooting table below.   
					Service   
					Procedure   
					LED Status   
					Control Status   
					Probable Cause   
					If the pilot will not stay   
					. 
					lit replace pilot   
					None (LED not on or   
					flashing   
					Pilot assembly is not lit   
					Gas Control is not powered. Light pilot. assembly. If problem   
					persists replace Gas   
					Control.   
					1. If set point knob is in “PILOT”   
					position then pilot flame is detected.   
					Turn set point knob to desired setting.   
					2. If the set point knob is already at   
					the desired setting, the water heater is   
					satisfied.   
					1. Gas Control is powered and waiting   
					for the set point knob to be turned to a   
					One flash and three   
					second pause   
					1. Adjust set point knob   
					water temperature setting.   
					to desired setting.   
					2. Water heater is satisfied and   
					operating normally.   
					Two quick flashes   
					and a three second   
					pause   
					Gas control is calling for heat (no   
					fault).   
					Tank temperature below set point of   
					Normal operation.   
					thermostat.   
					Set point knob has been recently   
					turned to the “OFF” position. Wait   
					until LED goes out before   
					attempting to relight   
					LED will go out and the   
					LED on continuously   
					(Solid)   
					Set point knob was turned to “OFF” control will function   
					position.   
					normally when the pilot   
					is lit.   
					1. See service   
					procedure II   
					2. See service   
					procedure III   
					3. See service   
					procedure III   
					1. Thermopile failure   
					Two flashes and   
					three second pause   
					Weak pilot signal detected. System will 2. Unstable pilot   
					reset when pilot flame is sufficient.   
					3. Pilot tube block or restricted.   
					1. See service   
					procedure V   
					2. See service   
					procedure V   
					1. Temperature sensor out of   
					calibration   
					2. Faulty Gas Control   
					Four flashes and   
					three second pause   
					Excessive tank temperature. System   
					must be reset.   
					4 
					4 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Honeywell Gas Control Troubleshooting Chart   
					Flammable Vapor Ignition Resistant Water   
					Heaters   
					Observe green LED indicator on   
					Gas Control. Error flash codes are   
					displayed with a three second pause   
					before repeating. Check and repair   
					the system as noted in the   
					Green LED Indicator   
					troubleshooting table below.   
					Service   
					Procedure   
					LED Status   
					Control Status   
					Probable Cause   
					1. Damage to the temperature sensor.   
					2. Temperature sensor resistance out of   
					range.   
					Five flashes and   
					three second pause   
					1. See service   
					procedure V   
					Thermostat/well sensor fault.   
					1. Check T&P valve   
					2. Check all water   
					fittings.   
					3. Pressurize and leak   
					test tank.   
					Six flashes and   
					three second pause   
					Water leak detected by accessory   
					module.   
					Excessive amount of water in drain   
					pan/water dam.   
					1. Control needs to be reset.   
					Gas Control electronic fault detected. 2. Control is wet or physically   
					damaged.   
					1. Reset Gas Control   
					2. Replace Gas   
					Control.   
					Seven flashes and   
					three second pause   
					Eight flashes and   
					three second pause   
					Standing pilot remains on while set   
					Pilot valve stuck in open position.   
					point knob is in “OFF” position.   
					Replace Gas Control.   
					5 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SERVICE PROCEDURE I   
					Inner Door/Gasket Removal, Inspection   
					Replacement and Reinstallation   
					The Bradford White   
					Inner Door Removal Procedure   
					Step 1.   
					Step 2.   
					Step 3.   
					Step 4.   
					Rotate set point knob of the gas control to the “OFF” position.   
					Turn off the gas supply to the water heater   
					Remove the outer door.   
					Remove the four (4) ¼” hex drive screws holding the   
					right side inner door in place   
					Step 5.   
					Step 6.   
					Remove the three (3) ¼” hex drive screws holding the   
					left side burner door in place.   
					¼” Hex Drive Screws at Flange   
					Area of Inner Door   
					¼” Hex Drive Screws Right   
					Side Inner Door   
					¼” Hex Drive Screws on Left   
					Side Inner Door   
					Disconnect the pilot tube from the gas control using a   
					7/16" wrench. Remove the main burner feedline from   
					the gas control with a ¾” wrench.   
					Step 7.   
					Step 8.   
					Disconnect the spark igniter wire from   
					the gas control.   
					Remove the burner assembly from the combustion chamber.   
					Step 9. Fully inspect burner and inner door gaskets for the following:   
					>Tears   
					>Other imperfections that will inhibit proper seal   
					>Gasket adhesion to inner door   
					>Material left on combustion chamber (around opening)   
					>Missing Material   
					>Cracks   
					>Dirt or debris   
					If the gasket is not affected by any of the above, gasket replacement is not required. If replacement is   
					required, proceed to Inner Door Gasket Replacement Procedure.   
					6 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SERVICE PROCEDURE I   
					Inner Door/Gasket Removal, Inspection   
					Replacement and Reinstallation   
					The Bradford White   
					Inner Door Gasket Replacement   
					Procedure.   
					WARNING   
					If the information in these instructions is not   
					followed exactly, a fire or explosion may result causing   
					property damage, personal injury or death.   
					Step 10. After inspection of inner door as noted in step 9, completely remove gasket and adhesive residue from   
					burner and left side inner doors as needed.   
					Step 11. Use RTV sealant (recommended bead size 1/8") to secure the inner door gasket to the inner door sections   
					(right & burner). The burner door gasket must be sliced in the location shown on the illustration below in   
					order to slide the gasket over the burner venturi. Refer to illustration below for proper RTV sealant   
					application. Note the overlap configuration in the flange area of the inner door. Set the flange section first, this   
					will help to achieve the proper over lap position.   
					Installation of Inner Door With   
					Gasket.   
					Step 12. Clean any residual gasket residue or other   
					WARNING   
					debris from combustion chamber surface   
					before installing the inner door/gasket   
					assembly.   
					Stripped fastener connections may allow   
					for seal breach of inner door. A seal   
					breach may result in a fire or explosion   
					causing property damage, personal injury   
					or death. Do not over tighten screws in   
					steps 13, 15 and 16.   
					Step 13. Place the burner door into position first. Tighten   
					the pilot line nut to the gas control. Tighten the   
					main burner feedline to the gas control. Use the   
					¼” hex drive screw without the built-in washer   
					to secure the right side of the burner door to the   
					chamber. Use the ¼” hex drive screws with the   
					built-in washer to secure the left side of the   
					burner door in place. DO NOT OVER   
					If a fastener connection is stripped,   
					contact the manufacturer listed on the   
					water heater rating plate.   
					TIGHTEN SCREWS.   
					Step 14. Position the fiberglass sock containing the igniter   
					wire, the pilot tube and the armored thermopile   
					cable against the inner door flange.   
					Page 37   
					7 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SERVICE PROCEDURE I   
					Inner Door/Gasket Removal, Inspection   
					Replacement and Reinstallation   
					The Bradford White   
					Position fiberglass sock, pilot   
					tube and armored thermopile   
					cable against flange.   
					Step 15. Firmly place right side inner door flange against the burner door flange and secure with two ¼” drive   
					screws from step 5. DO NOT OVER TIGHTEN SCREWS.   
					Step 16. Align right side inner door to combustion chamber and verify the fastener holes of the combustion   
					chamber are aligned with the right side inner door slotted opening. Verify seal integrity around combustion   
					opening. Secure right side inner door using 1/4” hex drive screws from step 5. DO NOT OVER TIGHTEN   
					SCREWS. Verify both burner and right sides of the inner door are properly positioned and sealed against   
					the combustion chamber.   
					Secure flange with   
					¼" drive screws.   
					Verify threaded hole   
					alignment with slotted   
					openings in inner door.   
					Step 17. Reconnect the igniter wire to the gas control   
					Step 18. Replace outer jacket burner access door.   
					Step 19. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions   
					located in the installation and operation manual.   
					8 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The Bradford White   
					SERVICE PROCEDURE II   
					Thermopile Testing and Replacement   
					OPEN CIRCUIT THERMOPILE TESTING   
					The following test should be performed while the pilot flame is on.   
					Step 1.   
					Step 2.   
					Turn knob to pilot position and depress.   
					Continue pressing knob and remove red (+) thermopile wire from the red wire leading from the gas control.   
					Also remove white (-) thermopile wire from the gas control.   
					Step 3.   
					Using a multimeter capable of measuring millivolts, connect the positive side of the multimeter to the   
					red (+) thermopile wire connector. Connect the negative side of the multimeter to the white thermopile   
					connector.   
					White (-) thermopile wire   
					Red (+) thermopile wire   
					Red gas control wire   
					Red (+) thermopile wire   
					White (-) thermopile wire   
					Normal thermopile operation will be between 350mV - 850mV. If reading is less than 350mV, replacement of pilot   
					assembly is recommended following SERVICE PROCEDURE III.   
					Step 4.   
					Step 5.   
					If thermopile reading is between 350mV - 850mV, remove multimeter and reconnect red (+) thermopile wire   
					to red wire leading from the gas control. Reconnect white (-) thermopile wire negative (-) terminal on gas   
					control.   
					Release Gas Control knob and turn to desired setting to resume normal operation.   
					9 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The Bradford White   
					SERVICE PROCEDURE III   
					Pilot Assembly Inspection, Cleaning   
					and Replacement   
					For Honeywell Control, rotate knob   
					counter-clockwise to the “OFF”   
					position.   
					PILOT/ELECTRODE ASSEMBLY INSPECTION,   
					CLEANING AND REPLACEMENT   
					Step 1.   
					Turn off gas supply to water heater. Rotate knob   
					Thermopile   
					connections   
					of gas control/gas valve   
					to “OFF” position.   
					Pilot tube   
					Step 2.   
					Step 3.   
					Remove outer jacket door.   
					Remove burner and right side inner door per   
					SERVICE PROCEDURE I, steps 1 through 8.   
					Step 4   
					Disconnect thermopile, pilot tube,   
					and feedline from gas control.   
					Step 5   
					Step 6.   
					Disconnect igniter wire from gas control.   
					Remove pilot/electrode assembly from burner (¼”   
					drive tool).   
					Feedline nut   
					Igniter wire   
					Step 7.   
					Inspect pilot for the following:   
					a) Primary air openings for blockage. Must be free from any   
					debris (dirt, lint, etc).   
					b) Kinks or cracks in the pilot tube. If found,   
					the pilot must be replaced.   
					Primary air   
					opening   
					Step 8.   
					Inspect pilot orifice:   
					a) Remove ½" nut from bottom of pilot assembly.   
					b) Remove pilot tube and pilot orifice.   
					c) Inspect pilot orifice for blockage, must be cleaned or replaced.   
					(Honeywell pilot orifice not replaceable, replace pilot assembly)   
					Step 9.   
					Install pilot/electrode assembly to feedline, secure with screw from step 6.   
					Step 10. Re-Install burner assembly and right side inner door per SERVICE   
					PROCEDURE I, steps 9 through 19.   
					Pilot orifice   
					Step 11. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions   
					located in the installation and operation manual.   
					10   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The Bradford White   
					SERVICE PROCEDURE IV   
					Igniter, Electrode Testing   
					and Replacement   
					IGNITER, ELECTRODE TESTING AND REPLACEMENT   
					With the pilot not in operation (no pilot flame) you can check the igniter and electrode circuit by viewing pilot   
					thru the sight glass located on the inner door and observing the spark action.   
					Step 1.   
					Step 2.   
					Remove outer jacket door.   
					Repeatedly depress the igniter while viewing the pilot thru the sight glass. If a spark is   
					present, the circuit is OK. If there is no spark, proceed to step 3.   
					View spark   
					Action through   
					Sight glass   
					Repeatedly   
					Depress Piezo   
					Igniter   
					Step 3.   
					Remove white wire from igniter and install a jumper wire in its place. Hold the other end of the   
					jumper by the wire insulation or using an insulated tool, next to an unpainted surface such as the   
					feedline and depress the igniter. If there is a spark, the igniter is OK, the pilot is not functioning and   
					must be replaced, see SERVICE PROCEDURE III for pilot replacement. If no spark is present the   
					igniter is not functioning and must be replaced. See SERVICE PROCEDURE V for gas control   
					disassembly/reassembly.   
					Insulated jumper   
					wire   
					Feedline   
					11   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SERVICE PROCEDURE V   
					Gas Control   
					Testing, Disassembly & Replacement   
					The Bradford White   
					Honeywell Gas Control Testing, Disassembly, and Replacement   
					The Gas Control is made up of (5) major components; the control cover, the piezo igniter, the valve body, the temperature   
					sensor, and the back plate. The Gas Control is designed so that any of these components may be replaced without   
					replacing the entire Gas Control.   
					Valve Body   
					Backplate   
					Gas Control   
					Cover   
					Gas Control   
					Cover Screw   
					Temperature   
					Piezo Igniter   
					Sensor   
					Valve Body   
					Screw   
					Insertion Stick   
					LINE PRESSURE   
					The Gas Control is designed for a maximum line pressure of 14.0" w.c. and a minimum line pressure of 1.0" w.c. over the   
					water heater’s rated manifold pressure (check rating plate). Line pressure must be checked with the main burner on and   
					off to assure proper readings.   
					12   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The Bradford White   
					SERVICE PROCEDURE V   
					Gas Control   
					Testing, Disassembly & Replacement   
					MANIFOLD PRESSURE TESTING (this procedure presumes a maximum line pressure of 14.0" w.c.)   
					Step 1.   
					Step 2.   
					Set the Gas Control to the “OFF” position.   
					Remove pressure tap plug and install   
					1/8" NPT pipe, coupling, & pressure tap.   
					Gas Control shown in the “OFF” position   
					Step 3.   
					Step 4.   
					Connect manometer to pressure tap.   
					Follow instructions located on the lighting   
					instructions label and proceed to light the main   
					burner and observe manometer reading.   
					Step 5.   
					Step 6.   
					Proper operating range for natural gas is: 4.0" 0.5" w.c.   
					Proper operating range for LP gas is: 10.0" 0.5" w.c.   
					If pressure is within the range specified in the previous   
					step, set Gas Control knob to the “OFF” position,   
					remove manometer and pressure tap, and replace   
					pressure tap plug. Check for gas leaks prior to placing   
					water heater back into operation by following the   
					instructions located on the lighting instruction label or the   
					lighting instructions located in the installation and   
					operation manual.   
					Step 7.   
					If gas pressure is outside the specification noted above,   
					refer to “Honeywell Gas Control Testing, Disassembly,   
					and Replacement” to replace Gas Control or valve body.   
					Pressure Tap   
					Shown Installed   
					THERMOPILE TESTING   
					See SERVICE PROCEDURE II   
					ECO (Energy Cut Off) TESTING   
					The Honeywell Gas Control is designed with an ECO device that will reset.   
					To reset the Gas Control after an error code (4), turn the Gas Control knob to the “OFF” position and wait a minimum   
					of (5) minutes before relighting following the instructions located on the lighting instruction label or the lighting   
					instructions located in the installation and operation manual.   
					13   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The Bradford White   
					SERVICE PROCEDURE V   
					Gas Control   
					Testing, Disassembly & Replacement   
					TEMPERATURE SENSOR TESTING   
					CAUTION   
					DO NOT use standard multimeter probes for this test.   
					Doing so will damage connector. Use special pin type   
					electronic probes or small diameter wire pins inserted   
					into connector.   
					If Control has gone into lockout due to excessive tank   
					temperature (four flash, three second pause) reset   
					control by rotating gas control knob to “OFF” position   
					and wait a minimum of (5) minutes. Then follow lighting   
					instructions and return gas control knob to desired   
					setpoint.   
					Observe Green LED indicator.   
					N 
					Does error code 4 (four flash, three   
					second pause) continue?   
					Y 
					Using a multi-meter set to the ohms setting, insert one meter probe (see caution)   
					into center wire position of thermal well connector, insert the second probe (see   
					caution) into either of the outside wire positions (see photo on left).   
					Temperature Sensor Testing   
					Following “Gas Control   
					Disassembly/Reassembly”   
					instructions, disassemble Gas   
					Control to access temperature   
					sensor.   
					Alternate the probe on the outside position to the opposite outside wire position   
					(see photo on right).   
					With the temperature sensor still   
					in the back plate, use a multi-   
					meter set to the Ohms setting,   
					determine the resistance of   
					temperature sensor   
					Resume normal operation.   
					(see caution and photos above)   
					Once the temperature sensor resistance values are known, the   
					water temperature must also be known to determine if the   
					resistance values are correct. See next page to obtain water   
					temperature.   
					N 
					Replace temperature   
					sensor   
					Are temperature sensor resistance values correct?   
					Y 
					Replace Gas Control   
					14   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SERVICE PROCEDURE V   
					Gas Control   
					Testing, Disassembly & Replacement   
					The Bradford White   
					WARNING   
					Stored water may be HOT when performing the following steps in this procedure.   
					Take necessary precaution to prevent personal injury.   
					DETERMINE WATER TEMPERATURE INSIDE TANK   
					Note:   
					It is important to understand once the resistance for the temperature sensor is determined from the   
					previous page, water flow through the water heater should not occur. Prior to drawing water from drain   
					valve, turn off the cold water supply to the water heater. This will prevent cold water flow into the tank   
					affecting the resistance value of the temperature sensor.   
					Step 1.   
					Step 2.   
					Step 3.   
					Set the Gas Control knob to the “OFF” position.   
					Turn off inlet water supply to water heater.   
					Draw approximately 4 gallons of water from drain valve into a container, or suitable drain, and discard.   
					Draw an additional gallon and immediately measure water temperature using an accurate thermometer.   
					It may be necessary to open a hot water faucet to allow water heater to drain.   
					Step 4.   
					Using the chart below, determine correct resistance value for the water temperature from step 3.   
					Example:   
					If temperature of water is 84°F, then the resistance through the sensor would be   
					8449 (see shaded area). NOTE: Sensor resistance increases as the temperature   
					decreases.   
					Sensor Resistance at Various Temperatures   
					In Degrees F   
					°F   
					40   
					50   
					60   
					70   
					80   
					90   
					100   
					110   
					120   
					130   
					140   
					150   
					160   
					170   
					180   
					190   
					200   
					0 
					1 
					2 
					3 
					4 
					5 
					6 
					7 
					8 
					9 
					26109   
					19906   
					15314   
					11884   
					9299   
					7333   
					5827   
					4663   
					3758   
					3048   
					2488   
					2043   
					1688   
					1402   
					1170   
					982   
					25400   
					19383   
					14925   
					11592   
					9078   
					7165   
					5697   
					4562   
					3679   
					2986   
					2439   
					2004   
					1656   
					1376   
					1150   
					965   
					24712   
					18876   
					14548   
					11308   
					8862   
					7000   
					5570   
					4464   
					3602   
					2925   
					2391   
					1966   
					1625   
					1351   
					1129   
					949   
					24045   
					18383   
					14180   
					11032   
					8653   
					6839   
					5446   
					4368   
					3527   
					2866   
					2344   
					1928   
					1595   
					1327   
					1110   
					933   
					23399   
					17905   
					13823   
					10763   
					8449   
					6683   
					5326   
					4274   
					3453   
					2808   
					2298   
					1891   
					1566   
					1303   
					1090   
					917   
					22771   
					17440   
					13477   
					10502   
					8250   
					6531   
					5208   
					4183   
					3382   
					2752   
					2253   
					1856   
					1537   
					1280   
					1071   
					901   
					22163   
					16990   
					13140   
					10248   
					8057   
					6383   
					5094   
					4094   
					3312   
					2697   
					2209   
					1820   
					1509   
					1257   
					1953   
					886   
					21573   
					16553   
					12812   
					10000   
					7869   
					6238   
					4982   
					4006   
					3244   
					2643   
					2166   
					1786   
					1481   
					1235   
					1035   
					871   
					21000   
					16128   
					12494   
					9760   
					7685   
					6098   
					4873   
					3922   
					3177   
					2590   
					2124   
					1753   
					1454   
					1213   
					1017   
					857   
					20445   
					15715   
					12185   
					9526   
					7507   
					5961   
					4767   
					3839   
					3112   
					2538   
					2083   
					1720   
					1427   
					1191   
					999   
					842   
					713   
					828   
					814   
					801   
					788   
					775   
					762   
					749   
					737   
					725   
					15   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The Bradford White   
					SERVICE PROCEDURE V   
					Gas Control   
					Testing, Disassembly & Replacement   
					GAS CONTROL DISASSEMBLY/REASSEMBLY   
					Step 1. Rotate knob of the Gas Control to the “OFF” position.   
					Step 2. Turn off gas supply to water heater.   
					Step 3. Disconnect gas supply line from Gas Control.   
					Step 4. Disconnect igniter wire.   
					Rotate knob counter-clockwise to   
					the “OFF” posistion.   
					Step 5. Disconnect main burner feedline, pilot tube and thermopile wires from gas control.   
					Step 6. Remove Gas Control cover screw.   
					Gas Control cover   
					screw   
					Step 7. Depress both tabs on the top of the Gas Control cover and pull to remove.   
					CAUTION   
					Use caution not to bend or damage valve body pins   
					when removing or installing Gas Control cover.   
					Valve body pins   
					16   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SERVICE PROCEDURE V   
					Gas Control   
					Testing, Disassembly & Replacement   
					The Bradford White   
					GAS CONTROL DISASSEMBLY/REASSEMBLY   
					Step 8. Disconnect temperature sensor from control board and remove wire from the temperature sensor wire routing clip.   
					Temperature sensor   
					wire routing clip   
					Disconnect   
					temperature sensor   
					Step 9. Remove the piezo igniter from the control cover by releasing the lock tab on the control cover.   
					Release lock tab   
					17   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The Bradford White   
					SERVICE PROCEDURE V   
					Gas Control   
					Testing, Disassembly & Replacement   
					GAS CONTROL DISASSEMBLY/REASSEMBLY   
					Step 10. Remove the valve body by removing screw located at the lower left corner then unclipping the lower right side   
					from the backplate first followed by the lower left side using a flat head screwdriver.   
					CAUTION   
					Use caution not to bend or   
					damage valve body pins.   
					Unclip lower right   
					side first   
					Unclip lower left side   
					second   
					Valve body screw   
					Step 11. Remove temperature sensor and insertion stick from backplate by first removing wire from the temperature sensor   
					wire routing clips located on the backplate. Note the orientation of insertion stick, insertion stick can only be   
					installed in one way.   
					Temperature sensor   
					wire routing clips   
					CAUTION   
					When reinstalling temperature sensor and insertion stick,   
					make sure the assembly is inserted FULLY into the   
					backplate and the wires are routed through the wire   
					routing clips. Failure to do so will not allow valve body to   
					be reinstalled properly and may damage temperature   
					Insertion stick fully   
					inserted into backplate   
					sensor wires.   
					18   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The Bradford White   
					SERVICE PROCEDURE V   
					Gas Control   
					Testing, Disassembly & Replacement   
					GAS CONTROL DISASSEMBLY/REASSEMBLY   
					Step 12. Remove temperature sensor from insertion stick by pulling apart as illustrated below.   
					Temperature sensor   
					Pull in this direction   
					Insertion stick   
					Pull in this direction   
					Step 13. To reassemble Gas Control, follow the previous steps in reverse order. Once Gas Control is reassembled, burner   
					assembly is reinstalled, and the gas supply line is reconnected, resume water supply to water heater. Be sure tank   
					is full of water before relighting.   
					Step 14. To resume operation, follow the instructions located on the lighting instruction label or the lighting instructions   
					located in the installation and operation manual.   
					19   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SERVICE PROCEDURE V   
					Gas Control   
					Testing, Disassembly & Replacement   
					The Bradford White   
					GAS CONTROL REPLACEMENT   
					Step 1. Rotate knob of the gas control   
					to the “OFF” position.   
					Rotate knob counter-clockwise to   
					the “OFF” position.   
					Step 2. Turn off gas supply to water heater.   
					Step 3. Disconnect gas supply line from gas control.   
					Step 4. Turn off water supply and drain water heater completely.   
					Step 5. Remove the wire clip from the feedline.   
					Step 6. Disconnect main burner feedline, pilot tube, white thermopile wire and igniter wire from gas control and bend   
					the main burner feedline and pilot tube out of the way. Also disconnect the red wire leading from the thermopile   
					from the red wire leading from the gas control.   
					Step 7. Remove the gas control from the water heater by rotating counter-clockwise. It may be necessary to use a length   
					of ½” NPT pipe threaded into the inlet of the gas control.   
					White thermopile   
					Pilot tube   
					wire   
					Red gas control   
					Red thermopile   
					Igniter wire   
					wire   
					wire   
					Main burner   
					feedline   
					Step 8. Install new gas control into the water heater.   
					a) Install gas control into water heater by rotating clockwise. DO NOT use a wrench on the gas control   
					body or damage to the gas control may occur. If necessary, use a length of ½” NPT pipe threaded into   
					gas inlet of gas control.   
					b) Bend the main burner feedline and pilot tube back to the gas control and attach to the gas control.   
					Connect the igniter wire and the white thermopile wire to the gas control. Connect the red wire from   
					the gas control to the red wire from the thermopile.   
					c) Gather the igniter wire, white thermopile wire and red thermopile wire near the side of the feedline.   
					Use the clip that was removed in Step 5 to secure the wires to the feedline.   
					d) Connect gas supply to inlet of gas control.   
					Step 9. Resume the water supply to the water heater. Be sure that the tank is full before operation is resumed.   
					Step 10. To resume operation follow the instructions located on the lighting instruction label or the lighting   
					instructions located in the installation and operation manual.   
					20   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SERVICE PROCEDURE VI   
					Burner Operation Inspection, Adjustment   
					Cleaning and Replacement   
					The Bradford White   
					MAIN BURNER: Inspection,   
					Cleaning and Replacement   
					At periodic intervals (not more then 6 months) a visual inspection should be made of the main burner for proper operation   
					and to insure no debris is accumulating.   
					Main burner should light smoothly from pilot and burn with a blue flame with a minimum of yellow tips. After 5 minutes   
					of operation the burner screen will become radiant and the flame will soften and turn orange. If the burner screen does not   
					become radiant after 5 minutes of operation it must be cleaned (see burner cleaning procedure below).   
					Main burner must be free from any debris accumulation that may effect burner operation (see burner cleaning procedure   
					below).   
					DANGER   
					Under no circumstances shall flammable materials be used or stored in the vicinity of the water heater. With   
					the inner door removed the Bradford White Defender Safety System will be inactivated. If flammable vapors   
					are present, a fire or explosion may result causing property damage, personal injury or death.   
					WARNING   
					Inner door and burner components may be HOT when performing this operation. Take   
					necessary precaution to prevent personal injury.   
					BURNER CLEANING   
					Step 1.   
					Step 2.   
					Remove burner and inner door assembly per SERVICE PROCEDURE I, steps 1 through 9.   
					Thoroughly inspect burner screen and burner venturi and remove any loose debris accumulation. Inspect   
					burner screen for any openings larger than the normal screen openings.   
					Step 3.   
					Use compressed air and/or a vacuum to remove any scale or other debris accumulation from the burner screen   
					and venturi.   
					Burner Venturi   
					Burner Screen   
					21   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SERVICE PROCEDURE VI   
					Burner Operation Inspection, Adjustment   
					Cleaning and Replacement   
					The Bradford White   
					Step 4.   
					Step 5.   
					Disconnect (unscrew) feedline from the main burner door.   
					Feedline   
					Remove main burner orifice from feed line (3/8" wrench). Inspect and   
					clean if necessary   
					Main Burner Orifice   
					Step 6.   
					Remove pilot assembly, refer to SERVICE PROCEDURE III   
					for cleaning and inspection.   
					Step 7.   
					Step 8.   
					Reassemble burner.   
					Reinstall burner and inner door per SERVICE PROCEDURE I,   
					steps 9 through 19.   
					Step 9.   
					To resume operation, follow the instructions located on the lighting instruction label or the lighting   
					instructions located in the installation and operation manual.   
					22   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The Bradford White   
					SERVICE PROCEDURE VII   
					Dip Tube and Anode   
					Inspection and Replacement   
					DIP TUBE INSPECTION AND REPLACEMENT   
					WARNING   
					Heater components and stored water may be HOT when performing the following steps in   
					this procedure. Take necessary precaution to prevent personal injury.   
					Step 1.   
					Rotate knob of gas control to “OFF” position.   
					For Honeywell Control, rotate knob   
					counter-clockwise to the “OFF”   
					position.   
					Step 2.   
					Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain.   
					Open a nearby hot water faucet to vent heater for draining. Open drain spigot of hot water heater and allow   
					heater to drain to a point below the inlet connection nipple.   
					Step 3.   
					Step 4   
					Disconnect inlet nipple from plumbing system.   
					With an appropriate wrench, remove inlet nipple/dip tube from the water heater. Use caution not to damage   
					pipe threads.   
					Step 5.   
					Visually Inspect inlet nipple/dip tube. Inlet nipple/dip tube should be free of cracks and any blockage.   
					Hydro-jets located near the bottom of the dip tube should be open and free of any blockage.   
					Anti-siphon hole located approximately 6" from the bottom of nipple, should be free of any blockage.   
					Any damage such as cracks, restriction due to deformation or unintentional holes are not field repairable   
					and the inlet nipple/dip tube must be replaced.   
					Step 6.   
					Step 7.   
					Upon completion of inspection or subsequent replacement, reinstall inlet nipple/dip tube into heater. Connect   
					nipple to plumbing system, resume water supply and refill heater with water.   
					To resume operation follow the instructions located on the lighting instruction label or the lighting instructions   
					located in the installation and operation manual.   
					23   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SERVICE PROCEDURE VII   
					Dip Tube and Anode   
					Inspection and Replacement   
					The Bradford White   
					ANODE INSPECTION AND REPLACEMENT   
					WARNING   
					Heater components and stored water may be HOT when performing the following steps in   
					this procedure. Take necessary precaution to prevent personal injury.   
					Step 1.   
					Turn off water supply to water heater. Rotate knob of gas control to “OFF” position.   
					For Honeywell Control, rotate knob   
					counter-clockwise to the “OFF”   
					position.   
					Step 2.   
					Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain.   
					Open a nearby hot water faucet to vent heater for draining. Open drain spigot of hot water heater and allow   
					heater to drain to a point below the outlet connection nipple.   
					Step 3.   
					Step 4   
					Disconnect outlet nipple from plumbing system.   
					With an appropriate wrench, remove outlet nipple/anode from the water heater. Use caution not to damage   
					pipe threads.   
					Step 5.   
					Visually Inspect outlet nipple/anode. Outlet nipple/anode should show signs of depletion, this is normal.   
					If depletion is ½ of the original anode diameter (approximately 5/8” diameter), replacement is recommended.   
					If any of thesteel core of the anode is exposed, replacement is recommended.   
					Step 6.   
					Step 7.   
					Upon completion of inspection or subsequent replacement, reinstall outlet nipple/anode into heater. Connect   
					nipple to plumbing system, resume water supply and refill heater with water.   
					To resume operation, follow the instructions located on the lighting instruction label or the lighting   
					instructions located in the installation and operation manual.   
					24   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The Bradford White   
					Generic Parts List   
					1 
					2 
					3 
					4 
					5 
					6 
					7 
					8 
					9 
					Vent Package   
					19 T&P Relief Valve   
					Air Intake Terminal   
					Outer Wall Mounting Plate   
					Backing Plate   
					20 ¾” NPT Tank Plug (UDH Models)   
					21 Feedline Spring Clip   
					22 Air Intake Boot   
					Telescopic Air Intake Tube   
					Telescopic Vent Tube   
					Intake Elbow   
					23 Air Intake Boot Gasket   
					24 Complete Right Side Inner Door   
					25 Screw-#10-12 x ¾ Hex Washer Head   
					26 Screw-#8-18 x ¾ Hex Washer Head   
					27 Brass Drain Valve   
					Exhaust Elbow   
					Plenum   
					10 Flue Reducer   
					28 Outer Door   
					11 Plenum Gasket   
					29 Gas Control   
					12 Air Intake Tube   
					30 Inner Door Gasket Kit   
					31 Heat Trap Kit   
					13 Air Intake Terminal Guard (Optional)   
					14 Flue Baffle   
					32 ASSE Approved Mixing Valve (Optional)   
					33 Ultra Low NOx Burner Assembly   
					34 Pilot Assembly   
					15 Heat Trap (Inlet)   
					16 Cold Water Inlet Tube   
					17 Hot Water Outlet/Anode   
					18 Heat Trap (Outlet)   
					35 Ultra Low NOx Burner   
					36 Main Burner Feedline   
					37 Main Burner Orifice   
					25   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Download from Www.Somanuals.com. All Manuals Search And Download.   
				Download from Www.Somanuals.com. All Manuals Search And Download.   
				Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |