INSTALLATION OF THE
ADF ADAPTER PLUG
ELECTRICAL SHOCK HAZARD. Turn off power to the area where you
will install this unit at the circuit breaker or fuse box before beginning
installation. Failure to turn off the power before installation may result in
serious electrical shock, injury or death. Do not restore power until all
Smoke Alarms are completely installed.
•
Installation of this unit must conform to the electrical codes in your
area; Article 760 of NFPA 70 (NEC), NFPA 72, NFPA 101; SBC (SBCCI);
UBC (ICBO); NBC (BOCA); OTFDC (CABO), and any other local or
building codes that may apply. Wiring and installation must be per-
formed by a licensed electrician. Failure to follow these guidelines
may result in injury or property damage.
INSTALLATION INSTRUCTIONS
•
This unit must be powered by a 24-hour, 120VAC pure sine wave 60Hz
circuit. Be sure the circuit cannot be turned off by a switch, dimmer,
or ground fault circuit interrupter. Failure to connect this unit to a
24-hour circuit may prevent it from providing constant protection.
1. Verify which MODELS are installed in your system to determine if they are
compatible with the ADF Adapter Plug (see part C below).
2. Turn off AC power.
3. Remove unit. Remove old mounting bracket.
4. Install new mounting bracket (see part A below).
For all other Smoke Alarm information, instructions and warnings, refer
to the Smoke Alarm User’s Manual.
5. Connect the black end of the ADF Adapter Plug to the existing power
connector (connect part C to part D as shown below).
®
NOTE: There may not be enough room for the Adapter Plug and additional
wiring to fit in the junction box. If not, the old power connector must be
COMPATIBLE BRK MODELS
®
®
®
All of the listed BRK and First Alert Alarms are compatible with the listed
FIREX Alarms and will work with the enclosed Adapter Plugs.
removed and replaced with a First Alert Power Connector.
®
6. Connect the other end of the Adapter Plug to the appropriate Smoke Alarm
®
BRK Alarms
(connect part C to part B as shown below).
4120, 9120 Series – AC, AC/DC Ion, Silence
5919 – AC Photo
7. Check all connections. Make sure all plugs are completely connected and
snapped together. Ensure the Adapter Plug is securely connected to the
existing Power Connector.
2002RAC – AC/DC Photo
7010 Series – AC, AC/DC Photo, Silence
SC6120B, SC9120B – AC/DC Smoke/CO Combo
HD6135FB – Heat Alarm
8. Install the base of the Smoke Alarm to the mounting bracket.
9. Restore power to the junction box.
RM3 – Auxiliary Relay
10. Test each Smoke Alarm. Press and hold the test button until the unit alarms.
When testing a series of interconnected units you must test each unit
individually. Make sure all units alarm when each one is tested.
®
FIREX
406 (Model #G-6) – AC Ion
4518 (Model #ADC) – AC/DC Ion, Battery in Rear
4618 (Model #FADC) – AC/DC Ion
5000 (Model #FADC) – AC/DC Ion, Latching LED
484 (Model #PG-40) – AC Photo
4480 (Model #PAD) – AC/DC Photo
5700 (Model #ADH) – Heat Alarm
499 – Auxiliary Relay
The Parts of This Installation
D
A
• Maximum of only 12 units (except model G-6) may be interconnected.
A
B
Mounting Bracket
Check for model numbers above.
®
BRK 4120, 9120 Series
Smoke Alarm
®
Adapter Plug (ADF) Diagram for FIREX Models:
C
D
ADF Adapter
Plug Pin
View
Side View
Existing compatible
power connector
White
Orange
Electrical Rating:
120V AC, 100mA Maximum
Black
Not for Current Interruption
C
NOTE: Twist tie should not be removed.
®
NOTE: ADAPTER PLUG CANNOT BE USED TO CONNECT FIREX CARBON
MONOXIDE ALARMS.
®
B
THE ABOVE MODELS OF FIREX ARE THE ONLY MODELS THAT MAY BE
INTERCONNECTED USING ONE OF THE ADAPTER PLUGS INCLUDED.
IF THE MODEL IS NOT LISTED, IT MUST BE REMOVED FROM THE SYSTEM.
NOTE:
RECOGNIZED
COMPONENT
CONFORMS TO
UL STANDARD 1977
Independent evaluation of the
Adapter Plug and interconnect
compatibility was performed by
Intertek, a division of ETL SEMKO.
INCOMPATIBLE POWER CONNECTORS:
DO NOT ATTEMPT
INSTALLATION
3055574
© 2007 BRK Brands, Inc., a Jarden Corporation company (NYSE: JAH)
3901 Liberty Street Road, Aurora, IL 60504-8122
®
FIREX
All rights reserved.
US Patent No.: 6,641,433 B2
BRK® is a registered trademark of BRK Brands, Inc.
First Alert® is a registered trademark of the First Alert Trust.
Firex® is a registered trademark of Maple Chase Company.
®
NOTE: Adapter Plug can be used on FIREX Models manufactured on or
before January 1, 2004.
Printed in Mexico M08-0125-001
H
06/07
Download from Www.Somanuals.com. All Manuals Search And Download.
|