| Dell™ Systems   Cabling Instructions for   the –48 VDC   w w w. d e l l . c o m | s u p p o r t . d e l l . c o m   This document describes the requirements and instructions for connecting the safety   ground wire for systems equipped with a –48 VDC power supply.   CAUTION: A qualified electrician must perform all connections to DC power and   safety grounds. The system must be safety grounded at the cabinet frame. All   electrical wiring must comply with applicable local or national codes and   practices.   CAUTION: The System Information document provides important safety and   regulatory information. Read and follow all safety instructions prior to setup,   operation, and service of your system.   CAUTION: The system chassis must be positively grounded to the rack cabinet   frame. Do not attempt to connect power to the system until grounding cables are   connected.   CAUTION: An energy hazard will exist if the safety ground cable is omitted or   disconnected.   CAUTION: Before connecting safety ground or power cables to the connector,   ensure that the power is removed from the DC circuit. To ensure that the power   is off, locate the circuit breaker on the DC source circuit. Switch the circuit   breaker to the off position and, if available, install an approved safety locking   device to the circuit breaker or switch to prevent against another person from   energizing the circuit.   Precaution Statements   This system is intended for restricted access locations (dedicated equipment rooms,   equipment closet, or the like) in accordance with Articles 110-5, 110-6, 110-11, 110-14, and   110-17 of the National Electrical Code, American National Standards Institute   (ANSI)/National Fire Protection Association (NFPA) 70.   Protect the system with a 7.2-ampere (A) minimum to 20-A maximum protective device or   a 25-A maximum protective device when used with 90ºC wire.   Connect the system to a –48 VDC supply source that is electrically isolated from the AC   source. Ensure that the –48 VDC source is efficiently secured to earth (ground).   CAUTION: When installing the unit, the ground connection must always be made   first and disconnected last to prevent an energy hazard.   CAUTION: Never defeat the ground conductor or operate the equipment in the   absence of a suitably installed ground conductor. Contact the appropriate   electrical inspection authority or an electrician if you are uncertain whether   suitable grounding is available.   Cabling Instructions for the –48 VDC   1-1   Input Requirements   • • Supply voltage: –(38–60) VDC   Current consumption: 7.5 A   Connecting the –48 VDC Power Cable and   Safety Ground   1 Remove the #6-32 nut equipped with a lock washer from the grounding post on the   back of the system.   2 Connect the safety ground (green/yellow wire) to the grounding post on the back of   the system using the #6-32 nut equipped with a lock washer that you removed in   step 1 (see Figure 1-1).   NOTE: If your system is equipped with redundant –48 VDC power supplies, you   must connect both safety ground wires to the grounding post on the back of the   system.   Figure 1-1. Safety Ground   grounding post   safety ground wire   #6-32 nut with   lock washer   1-2   Cabling Instructions for the –48 VDC   3 Plug the DC power cable into the system.   Figure 1-2 and Table 1-1 indicate the DC input power cable connector’s pin   orientation and descriptions.   See your Rack Installation Guide for information on routing cables.   Figure 1-2. DC Input Power Cable Connector ’s Pin Orientation   2 1 Table 1-1. Connector Housing Pin Assignments   Pin   1 Description   –48 VDC   Wire Color and Size   Black 14 AWG   2 –48 VDC return   Red 14 AWG   Cabling Instructions for the –48 VDC   1-3   1-4   Cabling Instructions for the –48 VDC   |