| FH085D36E   FLF085D36E   FLR085D36E   FLR140D60E   FH110D48E   FLF110D48E   FLR110D48E   FC085D36E   FH110D60E   FLF110D60E   FLR110D60E   WARNING   READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE   INSTALLATION.   THIS INSTALLATION MUST COMPLY WITH THESE INSTRUCTIONS AND   THE REQUIREMENTS OF ALL GOVERNING CODES AND ORDINANCES FOR   THE INSTALLATION LOCATION.   IT IS THE RESPONSIBILITY OF INSTALLER TO KNOW AND UNDERSTAND   ALL OF THESE REQUIREMENTS.   FAILURE TO DO SO COULD CREATE A HAZARD RESULTING IN PROPERTY   DAMAGE, BODILY INJURY OR DEATH.   FOR YOUR SAFETY   DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR   LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.   IMPORTANT NOTICE   THIS FURNACE IS NOT INTENDED FOR USE AS A CONSTRUCTION   HEATER. USE OF THIS FURNACE DURING CONSTRUCTION AND FINISHING   GETTING OTHER INFORMATION and PUBLICATIONS   These publications can help you install the furnace. You   can usually find these at your local library or purchase   them directly from the publisher. Be sure to consult   current edition of each standard.   FOR MORE INFORMATION, CONTACT   THESE PUBLISHERS:   ACCA   Air Conditioning Contractors of America   1712 New Hampshire Ave. N.W.   Washington, DC 20009   National Fuel Gas Code ........... ANSIZ223.1/NFPA54   National Electrical Code ...................... ANSI/NFPA70   Telephone: (202) 483-9370   Fax: (202) 234-4721   ANSI   American National Standards Institute   11 West Street, 13th Floor   New York, NY 10036   Standard for the Installation .............. ANSI/NFPA90A   of Air Conditioning and Ventilating Systems   Telephone: (212) 642-4900   Fax: (212) 302-1286   Standard for Warm Air...................... ANSI/NFPA90B   Heating and Air Conditioning Systems   ASHRAE American Society of Heating Refrigerating,   and Air Conditioning Engineers, Inc.   1791 Tullie Circle, N.E.   Standard for Chimneys, Fireplaces, Vents ... NFPA 211   and Solid Fuel Burning Appliances   Atlanta, GA 30329-2305   Telephone: (404) 636-8400   Fax: (404) 321-5478   Load Calculation for .......................... ACCA Manual J   Residential Winter and Summer Air Conditioning   NFPA   National Fire Protection Association   Batterymarch Park   P.O. Box 9101   Quincy, MA 02269-9901   Telephone: (800) 344-3555   Fax: (617) 984-7057   Duct Design for Residential .............. ACCA Manual D   Winter and Summer Air Conditioning   and Equipment Selection   Manual 2100-422   Page   1 INSTALLATION and OPERATING INSTRUCTIONS   LOCATING THE FURNACE   EQUIPMENT SELECTION   When installing the furnace be sure to provide adequate   space for easy service and maintenance. Locate the   furnace as close to the chimney as practical, giving   consideration to the accessibility of the oil burner,   controls, and blower for service. Allow a minimum of   24 inches at front of furnace for servicing oil burner.   Allow adequate room for filter and blower   maintenance. Clearance from combustible material as   stated on the furnace and repeated in Table 1 must be   maintained. For damp basement installations, a raised   concrete pad is recommended. This will help keep the   bottom of the furnace dry and reduce the risk of rusting.   An accurate heating load calculation must be conducted   using American Society of Heating, Refrigeration and   Air Conditioning Engineers (ASHRAE) or Air   Conditioning Contractors of America (ACCA) manuals.   Do not add a large safety factor above the calculated   value. If the calculated heating load requirement   exceeds the heating capacity rating of a given model,   use only the next larger size available. Never increase   by any more than absolutely necessary based upon   available equipment heating capacities. Always select   based upon heat capacity (output), never use input   capacities.   An oil burner must have a generous supply of   combustion air to operate properly. The flow of   combustion and ventilating air must not be obstructed   from reaching the furnace. See “Combustion Air   Requirements”section.   NOTE: It is the personal responsibility and   obligation of the purchaser to contract a   qualified installer to assure that installation   is adequate and is in conformance with   governing codes and ordinances.   The furnace area must be kept clear and free of   combustible materials, gasoline and other flammable   vapors and liquids.   This unit is not designed for mobile home or trailer   installations. Always install furnace in a level position.   TABLE 1   MINIMUM CLEARANCES   Minimum Installation Clearnaces — Inches   Minimum Service   Clearances   Furnace   Front Back Sides   Plenum   1 Flue   Pipe   Model   Top   Sides Duct   Floor Front Back Sides   FH085D36E   FH110D48E   FH110D60E   4 4 4 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 9 9 9 C C C 24   24   24   — — — — — — FLF085D36E   FLR085D36E   FLF110D48E   FLF110D60E   6 6 6 6 0 18   0 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 9 9 9 9 NC   NC   NC   NC   24   24   24   24   24   24   24   24   18 *   18 *   18 *   18 *   0 FLR110D48E   FLR110D60E   FLR140D60E   FC085D36E   6 6 6 6 18   18   18   1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 9 9 9 9 NC   NC   NC   24   24   24   24   24   24   24   — 18 *   18 *   18 *   — NC **   j For the first three (3) feet from plenum. After three (3) feet, no clearance required.   Combustible flooring   C NC Noncombustible floor   Maintained on one side or the other to achieve filter access and/or blower service.   * ** Floor must be noncombustible. For furnace only installation can be installed on combustible   flooring only when installed on special base part no. CFB7 available from factory. When air   conditioning coil cabinet DCB23-22 is used then use special base part no. CFB23.   Manual 2100-422   Page   2 FIGURE 1   FLF/R MODELS DIMENSIONS   TABLE 2   FLF/R MODELS DIMENSIONS (INCHES)   FLF/FLR 085, 110 AND 140   SPECIFICATION SHEET   Plenum   Cabinet   B Openings   Flue Conection   G Air Filters   Size   1 Model   Number   A C D x E D x F   No.   Used   J TOP VIEW   Width Depth Height Supply Return Location Dia.   H J RETURN   DUCT   SUPPLY   DUCT   FLF085D36E   FLR085D36E   23 48.125 36.625 22x20 22x14   23 48.125 36.625 22x20 22x14   Front   Rear   6 6 31.625 5.125 16 x 20 x 1   31.625 5.125 16 x 20 x 1   1 1 FLF110D48E   FLF110D60E   FLR110D48E   FLR110D60E   23 48.125 40.625 22x20 22x14   23 48.125 40.625 22x20 22x14   23 48.125 40.625 22x20 22x14   23 48.125 40.625 22x20 22x14   Front   Front   Rear   Rear   6 6 6 6 35.625 5.125 20 x 20 x 1   35.625 5.125 20 x 20 x 1   35.625 5.125 20 x 20 x 1   35.625 5.125 20 x 20 x 1   1 1 1 1 D FLR140D60E   26 50.250 47.625 25x20 25x16   Rear   6 42.125 - - - 20 x 25 x 1   1 j Washable type filter 1” nom. thickness   "FLF" FLUE   KNOCKOUT   G F B E A "FLF" FLUE   KNOCKOUT   REAR FLUE   ON "FLR" MODELS   "FLF" FLUE   KNOCKOUT   OPTIONAL   HIGH VOLTAGE   ENTRANCE   LOW VOLTAGE   ENTRANCE   OPTIONAL   LOW VOLTAGE   ENTRANCE   HIGH VOLTAGE   ENTRANCE   C H OIL   ENTRANCE   OPTIONAL   OIL   ENTRANCE   OPTIONAL   OIL ENTRANCE   FILTER   DOOR   FRESH AIR   KNOCKOUT   LEFT SIDE VIEW   FRONT VIEW   RIGHT SIDE VIEW   MIS-1815 A   FIGURE 2   FH MODELS DIMENSIONS   21 7/8"   TOP VIEW   FH085 AND FH110   SPECIFICATION SHEET   SUPPLY   OPENING   19 7/8"   30 1/2"   FLUE   KNOCKOUT   23"   FLUE   KNOCKOUT   FLUE   KNOCKOUT   OPTIONAL   HIGH VOLTAGE   ENTRANCE   REAR CLEANOUT   DOOR   OPTIONAL   LOW VOLTAGE   ENTRANCE   HIGH   VOLTAGE   ENTRANCE   OPTIONAL   OIL   ENTRANCE   53" (FH085)   59" (FH110)   OIL   ENTRANCE   LOW VOLTAGE   ENTRANCE   19 1/4"   FRESH AIR   KNOCKOUT   OPTIONAL   OIL   ENTRANCE   RETURN   OPENING   (CUT OUT)   RETURN   OPENING   (CUT OUT)   16"   VESTIBULE   DOOR   LEFT SIDE VIEW   RIGHT SIDE VIEW   FRONT VIEW   MIS-1814 A   FIGURE 3   FC085 MODEL DIMENSIONS   21 7/8"   SUPPLY   OPENING   FC085   SPECIFICATION   SHEET   19 7/8"   30 1/2"   TOP VIEW   FLUE   KNOCKOUT   23"   FLUE   KNOCKOUT   FLUE   KNOCKOUT   OPTIONAL   HIGH VOLTAGE   ENTRANCE   54 1/4"   REAR   CLEANOUT   DOOR   OPTIONAL   LOW VOLTAGE   ENTRANCE   LOW VOLTAGE   ENTRANCE   OIL ENTRANCE   HIGH VOLTAGE   ENTRANCE   OPTIONAL   OIL ENTRANCE   FRESH AIR   KNOCKOUT   OPTIONAL   OIL ENTRANCE   FRONT VIEW   LEFT SIDE VIEW   RIGHT SIDE VIEW   RETURN   OPENING   18 1/8"   BOTTOM VIEW   MIS-1826   19 1/8"   Manual 2100-422   Page   5 DUCT WORK   INSTALLING THE FURNACE   The air distribution system should be designed and   installed in conformance with manuals published by Air   Conditioning Contractors of America (ACCA) as set   forth in Manual D, or ASHRAE publications.   INSTRUMENTSREQUIREDFORPROPER   SETUP OF THE FURNACE   It is important that a set of instruments capable of the   following requirements be used for the setup of this   furnace to ensure proper and safe operation:   IMPORTANT   1. Oil pump pressure gauge that measures up to   150 PSI.   When a furnace is installed so that supply   ducts carry air circulated by the furnace to   areas outside the space containing the   furnace, the return air must also be handled   by a duct(s) sealed to the furnace casing and   terminating outside the space containing the   furnace This is to prevent drawing possible   hazardous combustion products into the   circulated air.   2. Smoke gun to pull smoke samples from flue.   3. Draft gauge that will measure -.02” water column   (W.C.)   4. Duct static pressure gauge 0-1.0” W.C. range.   5. Temperature gauge that can read from 50° F up to   700° F.   6. A gauge to measure CO2 or O2.   INSTALLING A COOLING UNIT   INSTALLATION   When the furnace is used in connection with a cooling   unit*, the furnace shall be installed parallel with or on   the upstream side of the cooling unit to avoid   condensation in the heating element. With a parallel   flow arrangement, the dampers or other means used to   control flow of air shall be adequate to prevent chilled   air from entering the furnace, and if manually operated,   must be equipped with means to prevent operation of   either unit, unless the damper is in the full heat or cool   position.   A typical installation is shown in Figures 4 and 5. All   parts of the furnace installation (furnace, oil tank and   piping systems, combustion and ventilation air, venting,   etc.) must comply with NFPA31, Installation of Oil   Burning Equipment -- latest edition. This drawing   shows the typical connecting parts needed to correctly   install this furnace. Make sure that all parts of the   heating system comply with the local codes.   Check the furnace and your load calculation to verify   that the unit is properly sized. (Refer to Equipment   Selection” section on Page 2.)   * A cooling unit is an air conditioning coil, heat   pump coil or chilled water coil.   The correct size of unit needed may be substantially   smaller than the unit being replaced due to home   improvements and technology advancements since the   initial installation.   When installing a cooling unit above an FH or FL   (below on an FC) series furnace, the coil must be   spaced far enough from the furnace outlet to assure   proper operation of the furnace. Bard supplied coils,   when used with Bard supplied coil cabinets, are   automatically positioned.   INADEQUATE SUPPLY AIR and/or RETURN   AIR DUCT SYSTEMS   For top discharge FH and FL models, when coils are   installed without using Bard coil cabinets or coils of   another brand are used, the coil drain pan should be   located a minimum of two (2) inches above the top of   the furnace cabinet. If a greater clearance is specified   by the coil manufacturer then it would apply.   Short cycling because of limit control operation can be   created by incorrectly designed or installed supply and/   or return air duct systems.   The duct systems must be designed using ASHRAE or   ACCA design manuals and the equipment CFM and   external static pressure ratings to insure proper air   deliverycapabilities.   NOTE: IF DRAIN PAN IS ANYTHING OTHER   THAN A STEEL PAN PARTICULAR   ATTENTION MUST BE GIVEN TO THE   INSTALLATION INSTRUCTIONS FOR   THE COIL TO MAKE SURE IT IS   On replacement installations, particularly if equipment   is oversized, the duct systems can easily be undersized.   Modifications may be required to assure that the   equipment is operating within the approved   temperature rise range when under full rated input   conditions, and that no short cycling on limit controls is   occurring.   ACCEPTABLE FOR USE WITH THESE   OIL FURNACES HAVING MAXIMUM   OUTLET AIR TEMPERATURE OF 200° F.   See CFM versus static pressure curves on pages 33-36   for additional information.   Manual 2100-422   Page   6 FIELD WIRING   WIRING   All wiring must conform to the National Electrical   Code and all local codes. A separate fuse or breaker   should be used for the furnace.   FACTORY WIRING   All units are fully factory wired. Multispeed blowers   are factory wired on high speed for cooling/manual fan   operation. Heating speeds are wired for the largest   input and may need lower speed for field installed low   input nozzle. If replacement wire is necessary, use 105   degrees C minimum. See electrical data, Table 3.   TABLE 3   ELECTRICALDATA   Max. Time   Delay Fuse   or HACR   Blower Motor   Burner Motor   Minimum   Circuit   Total   Amps   HP   FLA   HP   FLA   Model   Volts-HZ-PH   115-60-1   115-60-1   115-60-1   115-60-1   115-60-1   115-60-1   115-60-1   115-60-1   115-60-1   115-60-1   115-60-1   Ampacity Circuit Breaker   FH085D36E   FH110D48E   FH110D60E   FLF085D36E   FLR085D36E   FLF110D48E   FLR110D48E   FLF100D60E   FLR100D60E   FLR140D60E   FC085D36E   9.2   1/3   1/2   3/4   1/3   1/3   1/2   1/2   3/4   3/4   3/4   1/3   7.5   10.5   12.5   5.6   1/7   1/7   1/7   1/7   1/7   1/7   1/7   1/7   1/7   1/7   1/7   1.7   1.7   1.7   1.7   1.7   1.7   1.7   1.7   1.7   1.7   1.7   15   16   19   15   15   16   16   19   19   19   15   15   20   20   15   15   20   20   20   20   20   15   12.2   14.2   17.3   17.3   12.2   12.2   14.2   14.2   14.2   7.3   5.6   10.5   10.5   12.5   12.5   12.5   5.6   Manual 2100-422   Page   7 FIGURE 4   TYPICAL UNIT SETUP   FLF UNIT SHOWN   WARNING   ALL WIRING MUST   CONFORM TO THE   NATIONAL ELECTRIC   CODE AND ALL LOCAL   CODES.   ! Left side   high voltage   (unit power)   entrance   Inspection   door   Left side   low voltage   (thermostat)   entrance   Right side   low voltage   (thermostat)   entrance   Left side oil   line entrance   for opt. air boot   To thermostat   and optional   A/C unit   Left side   oil line   entrance   To power   source   Oil line   (see burner   pump inst. for   hookup info.)   Shut off switch   (if not fused,   power line must   include fuse or   circuit breaker)   Air Boot   knockout   (optional)   Control panel   (junction box   in FH units)   Power Wires:   Black (HOT)   White (NEUTRAL)   Green (GROUND)   Right side   high voltage   (unit power)   entrance   Right side   oil line   MIS-1836   entrance   Manual 2100-422   Page   8 FIGURE 5   TYPICAL FLUE INSTALLATION REQUIREMENTS   FRONT FLUE LOWBOY MODEL SHOWN   (REPRESENTS ALL MODELS)   INSTALLER NOTE:   Thimble   Follow all appropriate   standards for installing   needed venting system.   Draft Regulator   (Be sure to follow   installation inst.   supplied with   regulator).   1/4 inch per   1 foot rise   L i n e d 90° Rotatable   Flue Box on front   flue models   (remove appropriate   cabinet knockout).   Mounting screws   located under flue   box cover.   Flue Box   Cover   C h i m n e y Optional   Flue   Locations   Oil Burner   Clean-out Door   (keep closed)   Optional Fresh   Air Boot (remove   rect. knockout).   MIS-1825   Manual 2100-422   Page   9 OIL LINE PIPING   BECKETT AFG OIL BURNER   First determine whether the pipe system is to be a single   line system or a two line system. All connections must   be absolutely air tight or you will have a malfunction of   the burner. When installing the piping, a good oil filter   should be installed close to the burner. A single line   system is recommended for gravity feed.   This furnace is equipped with a high static Beckett AFG   oil burner which is designed to produce adequate draft in   nearly any vertically vented application. The burner   employs the latest time tested controls of the highest   quality. The controls consist of a high voltage Beckett   solid state igniter, a Beckett “CleanCut” oil pump with   an integral solenoid valve, and a Beckett R7184B   primary control.   A typical single inside tank installations shown in   Figure 6. For installation details for this and other tank   configurations, refer to NFPA31 -- latest edition. All   tank and pipe setups must comply with NFPA31.   FIGURE 6   TYPICAL SINGLE INSIDE TANK INSTALLATION   Vent Cap   2" Cap   2" Fill Pipe   1-1/4"   Vent Pipe   Return Line   Guage   Bushing,   2" x 1-1/2" or   1-1/4"   Oil   Tank   Gate Valve   3/8" x 4"   nipple   6"   3/8" x 3/8"   Adapter   3/8" O.D. Copper   Fuel Tubing   Legs (either 1-1/4"x10"   or 1-1/2"x10" nipples)   MIS-1823   Bushing   Oil Filter   Manual 2100-422   Page 10   These controls were selected for their proven high   quality, dependability, and serviceability. With proper   maintenance this burner assembly will provide many   years of reliable service.   BECKETT SOLID STATE IGNITER   This igniter differs from the traditional iron core   transformer in that it produces a 14,000 volt spark   instead of a 10,000 volt spark of the iron core   transformer. This hotter spark provides for cleaner,   faster ignitions. Being solid state technology this   igniter is less susceptible to problems caused by voltage   variations. It also has a greater ability to ignite cold   and/or inconsistent oil. The solid state igniter is wired   to the primary control the same as an iron core   transformer.   All units are shipped with the oil burner installed, and   with high rate oil nozzle installed designed for use with   No. 1 or No. 2 fuel oil. Inspect firepot refractory   before firing to be sure it has not been jarred out of   position in shipment. Burner air tube must not   extend beyond inside surface of firepot. Burner   head should be centered on the combustion chamber   opening. See Figures 19 and 20.   BECKETT R7184B PRIMARY CONTROL   The R7184B Interrupted Electronic Oil Primary is a   line voltage, safety rated, interrupted ignition oil   primary control for residential oil burners. The R7184B   used with a cad cell flame sensor, operates the oil   burner and oil valve. The primary controls fuel oil,   senses flame, controls ignition spark and is designed to   notify a remote alarm circuit before going into lockout   when equipped with a flame monitoring system.   WARNING   Never attempt to use gasoline in your furnace.   Gasoline is more combustible than fuel oil and   could result in a serious explosion causing   damage, injury or death.   This primary control possesses the latest technology, is   a very simple control to operate and provides additional   troubleshooting features to ease service and reduce   down time. The operational guide for the R7184B   primary control is provided following on   Page 12.   The following is a detailed explanation of each control   included in the Becket AFG Oil Burner, how each   operates, how to set up the burner, and how to   troubleshoot problems should they occur.   BECKETT “CLEANCUT” OIL PUMP   This oil pump is equipped with an oil solenoid valve   installed in the pump housing. This feature provides   quick cutoffs resulting in reduction in smoke after the   burner shuts down. This is a time proven pump design   and is capable of both one and two pipe systems. This   pump requires a pre-purge style primary control such as   the R7184B primary. All installation and set up   instructions are outlined in the “Oil Pump   Specification” section of the installation instructions   manual.   Manual 2100-422   Page   11   BECKETT R7184B PRIMARY   OPERATIONAL GUIDE   Pre-Purge Delay – 15 seconds on delay   LED Codes – Flashing 1/2 second on / 1/2 second off – system is locked out or in restricted mode   (hard lockout).   – Flashing 2 seconds on / 2 seconds off – control is in recycle mode (soft lockout).   – ON – CAD cell is sensing flame   – OFF – CAD cell is not sensing flame.   Ignition Trials – On any given call for heat the   control will allow three ignition trials. After the three   trials the control will go into a soft lockout mode. The   LED will flash 2 seconds on and 2 seconds off when   in this recycle mode. The control may then be reset   by pressing the RED reset button on the control. If   within the same original call for heat the control will   again allow three ignition trials followed by another   soft lockout and a 2 second on / 2 second off LED   code. The control my be reset one additional time by   pressing the red reset button. This will allow three   final ignition trials. If all three of the final ignition trials   fail then the control goes into a hard lockout or   Restricted Mode. This series of ignition failures must   all occur with the original call for heat in order to   reach the Restricted Mode. The LED will now flash   1/2 second on / 1/2 second off indicating the   restricted mode. The control can be resurrected from   the restricted mode only by pressing and holding the   red reset button for approximately 30 seconds until   the LED flashes twice. Removing unit power or   resetting the thermostat will not reset the control   Checking CAD Cell – With a call for heat and the burner ignited, press and release the red reset button. The   LED will go out and then flash 1, 2, 3, or 4 times before returning to the run mode. The CAD cell resistance   must be below 1600 ohms for proper operation.   – 1 flash   – – – – Less than 400 ohms   – 2 flashes   – 3 flashes   – 4 flashes   More than 400 and less than 800 ohms   More than 800 and less than 1600 ohms   More than 1600 and less than 5000 ohms   Burner Option – Flame Quality Monitor   alarm, the security agency will notify the dealer of   choice based upon information supplied by the home   owner. The system will also be capable of being   connected to a phone line that will contact the dealer   directly with the alarm. This alarm will typical sound   3 to 5 days prior to the primary control going into   lockout giving the service agency a prior notice   before a sooting condition or other failure can occur   resulting in untold savings. This monitor system is   available through your local distributor under the   Honeywell part no. QS7100F.   This control is trained to recognize and remember a   good flame based on initial burner set up. Control   then monitors the flame via the CAD cell signal for   deviation in the combustion characteristics of the   burner. If the control senses a deviation on the high   side or on the low side from the original set up   condition for three consecutive cycles, it will trigger   an alarm circuit which can be tied to an audible local   device to signal the home owner or into the home   security system. Upon being notified of the of the   Electronic Blower Control Board (EBC)   blower on and off timings for both heating and   cooling speeds are timed automatically. The heating   blower off delay can be selected from four different   timings by moving the selection jumper. The timings   are as follows:   This furnace is equipped with an Electronic Blower   Control (EBC) which controls all comfort air blower   operations. This EBC has three relays; one for   heating speed, one for cooling speed, and one which   isolates the T–T signal from the oil primary control.   Heating Blower ON delay – 75 seconds from a call   for heat.   This EBC is designed to be very simple and   dependable. This basic control allows for easy   troubleshooting and maintenance. As illustrated in   Figure 7 all connections are well marked. The   Heating Blower OFF delay – Selectable in seconds:   150, 180. 210 or 240. Factory shipped at 240.   Cooling Blower ON delay – 6 seconds from a call for   cooling.   Cooling Blower OFF delay – 60 seconds.   Manual 2100-422   Page   12   FIGURE 7   ELECTRONIC BLOWER CONTROL   TRANSFORMER 24V   SECONDARY   CONNECTIONS   THERMOSTAT   CONNECTIONS   3 AMP FUSE   HEATING BLOWER   OFF DELAY   ADJUSTMENT   IN SECONDS.   OIL PRIMARY T-T   CONNECTIONS   LINE VOLTAGE   CONNECTION (HOT)   HUMIDIFIER   CONNECTION   UNUSED BLOWER MOTOR   SPEED CONNECTIONS   HEATING BLOWER   SPEED CONNECTION   LINE VOLTAGE   CONNECTION (COM, L2)   MIS-1819   ELECTRIC AIR   CLEANER CONNECTION   COOLING BLOWER   SPEED CONNECTION   Manual 2100-422   Page   13   TABLE 4   FURNACE DATA   Furnace Installed Standard   Field Installed Options   2 2 2 1 Nozzle   Size   Heating   1 Heating   1 Heating   Capacity   BTUH   Input   BTUH   Capacity Nozzle   BTUH   Input   BTUH   Capacity Nozzle   Input   Model Number   FLF085D36E   FLR085D36E   FLF110D48E   FLR110D48E   FLF110D60E   FLR110D60E   FLR140D60E   FC085D36E   FH085D36E   FH110D48E   FH110D60E   Size   .65   .65   .85   .85   .85   .85   1.10   .65   .65   .85   .85   BTUH   74,000   74,000   96,000   96,000   96,000   96,000   125,000   74,000   74,000   96,000   96,000   Size   .55   .55   NA   NA   NA   NA   NA   .55   .55   NA   NA   BTUH   77,000   77,000   NA   .75   .75   105,000   105,000   140,000   140,000   140,000   140,000   175,000   105,000   105,000   140,000   140,000   85,000   91,000   91,000   63,000   63,000   NA   85,000   1.00   1.00   1.00   1.00   1.25   .75   113,000   113,000   113,000   113,000   142,000   85,000   119,000   119,000   119,000   119,000   154,000   91,000   NA   NA   NA   NA   NA   NA   NA   NA   77,000   77,000   NA   63,000   63,000   NA   .75   85,000   91,000   1.00   1.00   113,000   113,000   119,000   119,000   NA   NA   j 70 degree hollow cone spray pattern, 100 PSIG pump pressure   k Annual fuel utilization efficiency and heating capacity based upon U.S. Government standard   test using D.O.E. isolated combustion rating procedure.   1. PREPARATION STEPS   BURNER SETUP AND ADJUSTMENT   PROCEDURES   A. Calibrate and Check Operation of   All oil burner installations should be performed by a   qualified installer in accordance with regulations of the   National Fire Protection Standard for Oil-Burning   Equipment, NFPA31 -- latest edition, and in complete   compliance with all local codes and authorities having   jurisdiction. A qualified installer is an individual or   agency who is responsible for the installation and   adjustments of the heating equipment and who is   properly licensed and experienced to install oil-burning   equipment in accordance with all codes and ordinances.   Measuring Equipment Follow   manufacturer’s recommended procedures for   calibration and equipment check out.   B. Prepare Heating Unit for Testing Drill two   1/4 inch holes in the flue between the heating   plant and the barometric draft regulator. If   space permits, the holes should be located in a   straight section of the flue, at least two flue   diameters from the elbow in the flue pipe and at   least one diameter from the draft regulator. The   purpose of the two holes in the flue pipe is to   speed up testing and reduce instrument   handling.   The proper installation and adjustment of any oil burner   requires technical knowledge and the use of combustion   test instruments. The following procedure must be   followed to correctly adjust the burner to match the   specific characteristics of the installation.   C. Clean and Seal Heating Plant Make sure the   burner blast tube, fan housing, and blower   wheel are clear of dirt and lint. Seal any air   leaks into the combustion chamber.   IMPORTANT   D. Nozzle Inspection Annual replacement of   nozzle is recommended. The nozzle size   should match the design load . DO NOT   Always use combustion test instruments when   making burner adjustments and draft gauge   when setting the barometric damper. It is   virtually impossible to make accurate and   reliable adjustments using the “eyeball”   method.   OVERSIZE. (Determination of oversizing can   be determined prior to your adjustment. If the   firing rate should be reduced refer to Table 4.)   Short cycles and low percent :on: time result in   higher overall pollutant emissions and lower   thermal efficiency. An in-line oil filter will   reduce service problems due to nozzle clogging.   Check all oil lines and connections for leaks.   Connect pressure gauge by removing bleed fitting and   screwing in pressure gauge. See Figure 9.   Manual 2100-422   Page   14   K. Adjust Air Setting Examine the smoke - CO2   plot and, keeping in mind the curve of   Figure 6, note the location of the “knee” where   the smoke number begins to rise sharply.   Noting the air gate position marks, adjust the   air setting to a CO2 level 1/2 to 1 percent lower   than the CO2 level at the “knee”. (This   provides a tolerance against possible shifts in   the setting over a period of time.) Do not   increase the air setting any more than necessary   on the lower portion of the curve below the   “knee”   It should be located as close as possible to the   oil burner. Care should be taken to prevent air   leakage in the oil suction line. Use continuous   runs of copper tubing and use minimum   number of joints and fittings. Always use flare   fittings.   E. Adjustment of Electrodes Adjust ignition   electrodes as specified in Figure 10.   F. Operate Burner Operate burner, adjust air   setting for good flame by visual observation,   and run for at least 10 minutes or until   operation has stabilized.   The characteristic curve for some burners may   not yield a distinct “knee” in the curve. In such   cases, the setting should be made near the   minimum smoke, (using judgement).   G. Check Burner Pressure Bleed air from   pump and nozzle piping. Check pump pressure   and adjust to 100 psi, if necessary.   Lock the air adjustment and repeat draft,   CO2 and smoke measurements to make sure   the setting has not shifted.   2. COMBUSTION ADJUSTMENT STEPS   H. Set Draft Check the draft reading over the   fire with a draft gauge through a hole in the   inspection door. The hole is above the flame   level. Adjust the barometric draft regulator on   the flue to give the over fire of -.02” W.C.   3. COMBUSTION DIAGNOSIS   L. Check Performance A well-matched and   well-tuned burner should be capable of   operation with smoke not greater than No. 2   and at a CO2 level not less than 10%.   I. Check Smoke Readings After burner has   been operating 5 or 10 minutes, make a smoke   measurement in the flue, following the smoke   tester instructions. Oily or yellow smoke spots   on the filter paper are usually a sign of   If this cannot be reached, check the following:   1. Air leaks into the combustion chamber or   heat exchanger can dilute the combustion   gases and prevent normal CO2 readings.   Such leaks should be sealed with furnace   cement or other high-temperature sealant.   unburned fuel, indicating very poor   combustion (and likely high emissions of   carbon monoxide and unburned hydrocarbons.)   This condition can sometimes be caused by too   much air, or by other factors. If this condition   cannot be corrected, major renovation or even   burner replacement may be necessary.   To check for dilution by leakage, measure   the CO2 at as high a point as possible over   the fire, using a stainless steel tube   inserted through the fire door sample hole   (as described earlier for overfire draft   measurements), and compare this with the   CO2 measured in the flue. A difference of   more than 1 percent CO2 between the flue   and overfire reading usually indicates air   entry through leaks that have not been   properlysealed.   J. Develop Smoke - CO2 Curve Record   measurements of smoke and CO2 from the   flue. Then establish the smoke - CO2 curve by   taking readings over a range of air settings, as   shown in Figure 8.   To do this, start with the air gate set at nearly   full open and then take smoke and CO2   readings at progressively lower air settings, as   necessary to visualize the general shape of the   curve. (The CO2 readings will increase as the   air setting is decreased, unless combustion is   incomplete.) Do not set the air gate to give a   smoke reading above No. 4 or No. 5. Plot the   points on graph paper, as in Figure 8. Usually   3 or 4 readings are enough to establish the   curve.   Seal between the probe and inspection door   sample hole during test. The inspection   door hole should be sealed when not being   used to avoid leakage of air through it.   (See Step H.)   2. If the CO2 level of 10% cannot be reached   without exceeding No. 2 smoke, poor   mixing of air and fuel is likely.   In adjusting each air setting, it is helpful to   note the various positions of air gate at which   measurements are made so that the final setting   can be located quickly.   It may be necessary to replace the   combustion head or try different settings.   Manual 2100-422   Page   15   4. FINAL CHECKS   SHORT FORM ADJUSTMENT   PROCEDURE   M. Measure Stack Temperature Operating the   unit at an excessive firing rate will generate   more heat than the heat exchanger can utilize   and result in unnecessary heat loss up the   chimney. Other causes of excessive heat loss   are badlysooted heat exchanger surfaces and   excessive draft. The temperature of the flue gas   provides an indication of these heat losses.   Some burner service organizations may wish to   perform a shorter procedure for the adjustment of oil   burners. The following is an example of such a short   form prepared by the National Association of Oil Heat   ServiceManagers.   1. SERVICE AND CLEAN BURNER   Follow company procedure to complete the   cleaning and servicing. Operate burner for ten   minutes while tools are gathered and are cleaned.   Measure flue temperature by subtracting the   room air temperature from the thermometer   reading. Excessive stack loss is indicated of the   net stack temperature during steady operation   exceeds 600° F.   2, CHECK DRAFT   Set draft regulator, if necessary. Regulator should   be adjusted to achieve a -.02” W.C. over fire   condition. The more restricted and lengthy the   flue, the higher the draft necessary to obtain the   accepted over fire conditions.   N. Check Ignition Check operation over repeated   cycles to insure prompt ignition on starting.   O. Check Pump Cutoff Slow pump cutoff at the   end of a firing cycle can cause smoke and other   pollutant emissions. Check for prompt pump   cutoff by observing flame or by testing smoke at   shutdown. If poor cutoff is observed, make sure   air is purged from the pump and nozzle line.   Air trapped in the pump or nozzle line will   expand when heated, thus causing oil to drip   into the combustion chamber after shutdown. If   poor cutoff persists, repair or replace pump.   Also make sure the pump solenoid is working.   If not replace.   3. SMOKE TEST   Follow the instructions of the manufacturer of the   smoke tester and take a smoke sample. Adjust the   air to obtain a preliminary reading of about No. 3   spot. Then readjust the air to obtain the lowest   possible reading, but do not open the air   adjustment more than absolutely necessary to   obtain a trace or No. 0 spot.   4. CO2 TEST   Check CO2 levels. This level should be between   10% and 12%.   Manual 2100-422   Page   16   FIGURE 8   TYPICAL SMOKE – CO2 CHART WITH ADJUSTMENT RANGE   High   Air Settings   Low   8 6 4 2 0 CO2 Curve   from plotted   points   Plotted point   Normal   adjustment   range   Tolerance   to "knee"   "Best" air   setting   Plotted point   Plotted point   "Knee"   6 8 12   Percent CO in Flue Gas   10   14   2 Technician's   plotting area   8 6 4 2 0 12   Percent CO in Flue Gas   6 8 10   14   MIS-1827   2 Manual 2100-422   Page 17   FIGURE 9   PRESSURE GAUGE CONNECTION TO BLEED PORT   Remove Bleed   Port to attach   pressure guage.   Pressure Gauge   MIS-1660   Manual 2100-422   Page 18   TABLE 5   CORRELATION OF PERCENT OF CO2, O2   AND RESERVE AIR   Carbon   Dioxide   Reserve Air   (Approx.)   Oxygen   15.4   15.0   14.5   0.0   0.6   1.2   0.0   3.0   6.0   14.0   13.5   13.0   2.0   2.6   3.3   10.0   15.0   20.0   12.5   12.0   11.5   4.0   4.6   5.3   25.0   30.0   35.0   11.0   10.5   10.0   6.0   6.7   7.4   40.0   45.0   50.0   TABLE 6   NO. 2 FUEL OIL EFFICIENCY CHART   (NET STACK TEMP. DEGREES F)   % O2 200   250   88.4   88.2   87.9   87.7   87.3   87.0   86.5   300   87.3   87.0   86.7   86.4   86.0   85.5   85.0   350   86.2   85.9   85.5   400   450   500   82.9   82.4   550   81.7   81.2   80.7   80.0   79.3   78.5   77.5   600   650   700   78.4   77.7   77.0   76.2   75.3   74.2   73.0   750   77.3   76.6   75.8   74.9   73.9   72.8   71.5   800 % O2   1 2 3 4 5 6 7 89.6   89.4   89.2   88.9   88.7   88.4   88.0   85.1 84.0   80.6   79.5   76.2   75.4   74.6   73.6   72.6   71.4   70.0   14.7   14.0   13.2   12.5   11.7   11.0   10.3   84.7   84.3   83.6   80.1 78.9   83.1 81.9   79.4   78.7   77.9   77.0   76.0   78.2   77.5   76.6   75.6   74.5   85.1 83.8   84.6 83.3   84.1 82.7   83.5 82.0   82.6   82.0   81.3   80.5   81.3   80.6   79.9   79.0   TABLE 7   RECOMMENDED START-UP SETTINGS   Factory Installed   Field Installed Option   Air   Air   Air   Air   Air   Air   Furnace   Model No.   Burner Style   Part No.   1 Band Shutter   1 Band Shutter   1 Band Shutter   Nozzle Setting Setting Nozzle Setting Setting Nozzle Setting Setting   FH085D36E AFG/9020-026   FH110D48E AFG/9020-027   FH110D60E AFG/9020-027   FLF085D36E AFG/9020-026   .75   1.00   1.00   .75   0 2 2 0 6 .65   .85   .85   .65   0 0 0 0 5 8 8 5 .55   NA   NA   .55   0 NA   NA   0 5 NA   NA   5 10   10   6 FLF110D48E   AFG/9020-027   FLF110D60E   1.00   .75   2 0 2 10   6 .85   .65   .85   0 0 0 8 5 8 NA   .55   NA   NA   0 NA   5 FLR085D36E AFG/9020-031   FLR110D48E   AFG/9020-032   FLR110D60E   1.00   10   NA   NA   FLR140D60E AFG/9020-033   FC085D36E AFG/9020-026   1.25   .75   0 0 8 6 1.10   .65   0 0 6 5 NA   .55   NA   0 NA   5 j 70 degree hollow cone spray pattern, 100 PSIG pump pressure   Manual 2100-422   Page 19   SPACINGOFELECTRODES   COMBUSTION AIR REQUIREMENTS   The electrodes should be spaced 5/32” apart. They   should extend 1/16” beyond the end and 5/16” above   the center of the nozzle tip as shown in Figure 10.   This furnace must be installed in a location where a   sufficient supply of combustion air is available for the   complete combustion of the fuel oil. Keep in mind that   a certain amount of excess air is required as well to   ensure complete combustion of the fuel oil.   GUNASSEMBLYADJUSTMENT   The gun assembly can be adjusted in the slot inside of   fan housing by loosening screw holding slot cover in   position. Nozzle tip should ordinarily be located 1-1/8”   behind the front face of the cone.   When structures are constructed too tightly to supply   sufficient combustion air, air from outside the structure   is required to be brought in directly to the furnace. This   furnace has been conveniently designed to accept a   combustion air boot which is attached directly to the   outdoors by means of a 4” pipe. This pipe can be rigid   or flexible, but it is recommended that a metallic   material be used. Refer to Figure 11. The air boot used   for this design is a Field Controls model number   CAS-2B-90E that can be purchased through your local   distributor. Follow all installation procedures as   specified in the instructions packaged with the air boot   kit.   REMOVINGGUNASSEMBLY   Disconnect the oil line at the fan housing and remove   lock nuts on copper tube fitting. Loosen igniter hold   down clamps, then swing igniter up and backward. Gun   assembly can now be removed through this opening.   FIGURE 10   ELECTRODE ADJUSTMENTS   1-1/8   5/32 GAP   5/16   1/16   NOZZLE   MIS-160   Manual 2100-422   Page 20   FIGURE 11   COMBINATION AIR BOOT ASSEMBLY   COMBUSTION   AIR BOOT   ASSEMBLY   USE THIS   KNOCKOUT   FOR OIL LINE   INTAKE   AIR   TUBE   BURNER   ASSEMBLY   REMOVE PUMP TO   ASSEMBLE INNER   AIR BOOT   REMOVE KNOCKOUT   IN LEFT SIDE   INSERT OUTER AIR   BOOT AND SECURE   FLANGE TO UNIT   MIS-1833   MAKE ALL SETTINGS   ACCORDING TO MANUAL   FOR AIR BOOT.   Manual 2100-422   Page 21   APPLIANCES LOCATED IN CONFINED   SPACES   TABLE 8   SQUARE FEET REQUIRED TO   QUALIFY AS UNCONFINED SPACE   In unconfined spaces in buildings, infiltration may be   adequate to provide air for combustion, ventilation, and   dilution of flue gases. However, in buildings of   unusually tight construction, additional air shall be   provided using the method described under “All Air   From Outdoors” in Figure 13.   Unconfined Space   Total   Minimum Area In   BTUH   Square Feet   Input   8' Ceiling Height   60,000   80,000   375   500   An unconfined space (such as an open basement) must   have a minimum volume of 50 cubic feet per 1,000   BTUH of total of all appliances in area. Adjoining   rooms may be counted as one area only if there are not   doors between the rooms.   85,000   105,000   531   656   115,000   120,000   719   750   Shown in Table 8 are the required minimum areas in   square feet to qualify as an unconfined space for   various total BTUH input ratings. The table is based on   a room(s) with 8 foot ceiling heights.   140,000   145,000   875   906   160,000   200,000   1000   1250   If the unconfined space is within a building having   insufficient air because of tight construction, the air for   combustion and ventilation shall be obtained from   outdoors or from spaces freely communicating with the   outdoors. Under these conditions a permanent opening   or openings have a total free area of not less than one   square inch per 5,000 BTU per hour (28 square inches   per hour ) of total input rating of all appliances shall be   provided. For combustion air options see Page 20,   “Combustion Air Requirements”.   ALL AIR FROM INSIDE BUILDING   The confined space shall be provided with two   permanent openings, one near the top of the enclosure   and one near the bottom. Each opening shall have a   free area of not less than one square inch per 1,000   BTU per hour (140 square inches per gallon per hour)   of the total input rating of all appliances in the   enclosure freely communicating with interior areas   having in turn adequate infiltration from the outside.   (See Figure 12.) Also see Table 9 on the following   page for specific ventilation opening requirements for   the furnace only.   FIGURE 12   APPLIANCES LOCATED   IN CONFINED SPACES   ALL AIR FROM INSIDE THE BUILDING   The flow of combustion and ventilating air must not   be obstructed from reaching the furnace.   NOTE: Each opening shall have a free area of   not less than one square inch per 1,000   BTU per hour (140 square inches per   gallon per hour) of the total input   rating of all appliances in the   enclosure.   MIS-1336   Manual 2100-422   Page   22   ALLVENTILATIONAIRFROMOUTDOORS   TABLE 9   MINIMUM VENTILATION OPENINGS   A. The confined space shall be provided with two   permanent openings, one in or near the top of the   enclosure and one in or near the bottom. The   openings shall communicate directly, or by means   of ducts with outdoors or to such spaces (crawl or   attic) that freely communicate with outdoors. (See   Figures 13, 14, & 15.)   Recommended   Opening   (2 Required)   Min. Ventilation   Opening   Model   Square Inch   Size   Sq. In.   FH085D36E   FH110D48E   FH110D60E   FLF085D36E   FLR085D36E   240   280   280   290   290   8 x 16   9 x 18   9 x 18   8 x 19   8 x 19   128   162   162   152   152   B. When directly communicating with outdoors or by   means of vertical ducts, each opening shall have a   free area of not less than one square inch per 4,000   BTU per hour (35 square inches per gallon per   hour) of total input rating of all appliances in the   enclosures. If horizontal ducts are used, each   opening shall have a free area of not less than one   square inch per 2,000 BTU per hour (70 square   inches per gallon per hour) of total input of all   appliances in the enclosure.   FLF110D48E   FLF110D60E   340   340   9 x 19   9 x 19   171   171   FLR110D48E   FLR110D60E   FLR140D60E   FC085D36E   360   240   9.5 x 19   8 x 16   180   128   FIGURE 13   APPLIANCES LOCATED IN CONFINED SPACES   ALL AIR FROM OUTDOORS   NOTE: Each air duct opening shall have a   free area of not less than one square   inch per 2,000 BTU per hour (70   square inches per gallon per hour) of   the total input rating of all appliances   in the enclosure.   MIS-1337   Manual 2100-422   Page   23   FIGURE 14   APPLIANCES LOCATED IN CONFINED SPACES   ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC   NOTE: The inlet and outlet air openings   shall each have a free area of not   less than one square inch per   4,000 BTU per hour (35 square   inches per gallon per hour) of the   total input rating of all   appliances in the enclosure.   MIS-1338   FIGURE 15   APPLIANCES LOCATED IN CONFINED SPACES   ALL AIR FROM OUTDOORS   INLET AIR FROM VENTILATED CRAWL SPACE AND OUTLET AIR TO VENTILATED ATTIC   NOTE: The inlet and outlet air openings   shall each have a free area of not   less than one square inch per 4,000   BTU per hour (35 square inches   per gallon per hour) of the total   input rating of appliances in the   enclosure.   MIS-1339   Manual 2100-422   Page 24   A barometric damper is supplied with the furnace and   must be installed in the flue pipe observing the   LOUVERS AND GRILLES   In calculating free area for ventilation and combustion   air requirements, consideration shall be given to the   blocking effect of louvers, grilles, or screens protecting   openings. Screens used shall not be smaller than 1/4   inch (6.3 mm) mesh and shall be readily accessible for   cleaning. If the free area through a design of louver or   grille is known, it shall be used in calculating the size   opening required to provide the free area specified. If   the design and free area is not known, it may be   assumed that wood louvers will have 30-35 percent free   area and metal louvers and grilles will have 60-75   percent free area.   instructions packaged with the damper control. The   barometric damper opening must be located in the same   atmospheric pressure zone as the combustion air inlet to   the furnace. The furnace must not be vented into the   same chimney with any solid fuel burning appliance   such as a wood burner or pellet burner. Masonry   chimneys must be lined with a listed system or other   approved material that will resist corrosion, softening or   cracking from flue gas temperatures up to 1800° F. See   Standard for Installation of Oil Burning Equipment   NFPA31 latest edition and Standard for Chimneys   NFPA211 latest edition for additional information.   VENTING OPTIONS   HORIZONTALVENTING   This furnace is designed to be vented conventionally   into a vertical chimney or horizontally through a side   wall with an optional Field Controls side wall power   ventingsystem.   This furnace is designed to be horizontally vented   through a side wall with an optional side wall power   vent. The recommended side wall venter is the Field   Controls model number SWG-4HDS for 085 and 110   models, and SWG-5S for 140 models only. This venter   can be purchased through your local distributor. Follow   all installation instructions packaged with the venter   system.   Note that the FH, FC and FLF series furnaces have been   designed to allow for bringing the vent system through   the cabinet side for increased venting flexibility. To   take advantage of this feature, simply remove the   desired knockout from either side or top of unit and   rotate flue box accordingly by removing four (4) screws   under cleanout plate as shown in Figure 4. Make sure   smoke pipe gasket is in place before reinstalling flue   box screws.   THERMOSTAT   These furnaces are designed to be controlled with any   24V heating or heating/cooling thermostat. The   heat/cool thermostats must be designed for independent   heat/cool transformer circuits to assure that the 24V   transformer built into the oil primary control does not   conflict with the main furnace 24V transformer. The   heat anticipator should be set at 0.20A. This is a   nominal setting. The thermostat circuit should be   checked to verify setting.   VERTICALVENTING   If the unit is to be vertically vented make sure the flue   pipe from the furnace to the chimney is the same size   diameter as the flue outlet of the furnace which is 6”.   The flue pipe must have no reductions in diameter, be   made of a corrosion-resistant material having an   upward pitch of 1/4” for every foot of horizontal run,   and be made of material capable of handling   temperatures up to 1800° F.   Manual 2100-422   Page   25   TABLE 10   TEMPERATURE RISE RANGES, LIMIT CONTROL SETTINGS,   AND HEATING BLOWER SPEEDS   Maximum   1 Nozzle   Outlet Air   Temp.   Heating Blower   Speed   Model   Rise Ranges   .55   .65   .75   70 - 100   70 - 100   60 - 90   200   200   200   Low   Low   Med   FH085D36E   .85   1.00   70 - 100   60 - 90   200   200   Low   Med Low   FH110D48E   FH110D60E   .85   1.00   60 - 90   60 - 90   200   200   Low   Med Low   .55   .65   .75   60 - 90   60 - 90   60 - 90   200   200   200   Low   Low   Med   FLF085D36E   .85   1.00   60 - 90   60 - 90   200   200   Med Low   Med High   FLF110D48E   FLF110D60E   .85   1.00   60 - 90   60 - 90   200   200   Med Low   Med High   .55   .65   .75   60 - 90   60 - 90   60 - 90   200   200   200   Low   Low   Med   FLR085D36E   .85   1.00   60 - 90   60 - 90   200   200   Med Low   Med High   FLR110D48E   FLR110D60E   FLR140D60E   .85   1.00   60 - 90   60 - 90   200   200   Med Low   Med High   1.10   1.25   60 - 90   60 - 90   200   200   Med Low   Med High   .55   .65   .75   70 - 100   70 - 100   60 - 90   200   200   200   Low   Low   Med   FC085D36E   j 70 degree hollow cone spray pattern, 100 PSIG pump pressure   Manual 2100-422   Page 26   AIR FILTERS   Only Lo-Boy models are shipped with air filters. Filter   kits are available from your local distributor for Upflow   and Counterflow models. Knockouts are provided in   the sides of the FH series models to facilitate the   cutting of the return openings.   TABLE 11   FILTER SIZES FOR OIL FURNACES   Model   Size   FH085D36E   Hi-Boy   (1)   (1)   (1)   16 x 25 x 1   The upflow filter kit part numbers are FR23 for a   16x25x1 filter size and FR24 for a 20x25x1 filter size.   These filter kits come complete with the filter and all   necessary brackets for installing on the furnace. Each   comes with a washable aluminum mesh filter. When   installing a five ton AC unit on the furnace, one FR24   or Two FR23 must be used due to the high airflow   requirements. It is important to note that a minimum of   one inch spacing is required between the filter and the   unit side. Do not exceed 400 fpm for fiberglass   (disposable) type filters and 575 fpm for washable type   filters. See Figure 16.   FH110D48E   Hi-Boy   16 x 25 x 1   20 x 25 x 1   FH110D60E   Hi-Boy   FLF085D36E   FLR085D36E (1)   Lo-Boys   16 x 20 x 1   20 x 20 x 1   FLF110D48E   FLR110D48E   FLF110D60E (1)   FLR110D60E   Lo-Boys   The counterflow filter kit part number FR25 comes   with two washable filters. If not installing the FR25 kit   remember not to exceed 400 fpm for fiberglass   (disposable) type filters and 575 for washable type   filters. See Figure 17.   FLR140D60E   (1)   20 x 25 x 1   16 x 20 x 1   Lo-Boy   FC085D36E   (2)   Counterflow   See Table 11 for filter sizes and quantities.   FIGURE 17   FIGURE 16   TYPICAL INSTALLATION OF FR25   FILTER KIT   TYPICAL INSTALLATION OF FR26 AND   FR27 FILTER RACKS   Optional   Filter   Box   "FC"   Unit   19 1/4"   16"   70 5/16"   Filter   Frame   (2) screws   Filter   Filter   Door   MIS-1839 A   MIS-1841   Manual 2100-422   Page 27   LO-BOY MODELS – FILTER LOCATIONS   Lo-boy models have the filter installed in the return air cabinet section of the furnace. It is accessible from the rear of   the furnace by removing the blower/filter access door. The electrical switch should be turned “off” prior to removing   the access door. Refer to Figure 18 below.   FIGURE 18   FILTER INSTALLATION – LO-BOY MODELS   UNIT   FILTER SIZE   FLF/FLR085 16 x 20 x1   FLF/FLR110 20 x 20 x1   FLR140   20 x 25 x 1   STEP 3:   SLIDE FILTER OUT   TOWARDS BLOWER   DOOR   STEP 2:   STEP 1:   REMOVE BLOWER DOOR   BY PULLING OUT ON   SWELL LATCHES AND   TILTING OUTWARDS   UNFASTEN SWELL   LATCHES BY PULLING   HANDLES OUTWARD   MIS-1835   Manual 2100-422   Page 28   MAINTENANCE   B. Ignition Failure – Test by closing oil supply   while burner is off. Run through starting   procedure. The primary control will attempt   three trials for ignition. After three attempts,   the control will lockout.   LUBRICATION   No lubrication is required for either the burner or the   blower motor. Both are permanently lubricated.   INSPECT AIR FILTER   C. Power Failure – Turn off power supply   while burner is on. When burner goes out,   restore power and burner will restart.   Replace filters before each heating season begins. It is   recommended that filters also be replaced at least twice   during the heating season.   D. If operation is not as described, check wiring   and installation first. If trouble appears to be   in the control circuit, replace the flame   detector. If trouble still persists, refer to   “Common Causes of Trouble” section on   page 28.   Be sure the new filters are set securely in the filter rack   so there can be minimal leakage around them.   FINAL INSPECTION AND TEST   Final inspection and test of an installation shall be   made to determine that the work has been done in full   accordance with regulations and according to the   highest standards for safety, performance and   appearance. Such an inspection and test should   indicate the following as a minimum:   SERVICE HINTS   Preventive maintenance is the best way to avoid   unnecessary expense, inconvenience, and retain   operating efficiency of your furnace. It is advisable to   have your heating system and burner inspected at   periodic intervals by a qualified serviceman. If trouble   develops, follow these simple checks before calling the   serviceman.   1. Determine that all parts of the oil storage and   circulating system, including tank, piping and   burner, are free from oil leaks. Be sure that no oil   discharges from the nozzle when burner is not   operating.   1. Make sure there is oil in tank and valve is open.   2. Make sure thermostat is set above room   temperature.   2. Be sure that the suction line and pump have been   entirely vented of air so that the burner has   instantaneous oil shutoff at the nozzle and so that   the pump operates without an air noise.   3. Make sure electrical supply to furnace is on and   fuses are not blown or circuit breakers tripped.   4. Reset safety switch of burner primary control.   3. Check the flame adjustment to determine that the   flame is clear, quiet, free of odor and oil nozzle is   of proper size for the furnace.   4. Test operation of burner by operating the   thermostat. First, set the thermostat above room   temperature. Burner should start. Second, set   thermostat below room temperature. Burner will   stop.   CAUTION   Reset three (3) times only. More than three   resets can cause excessive oil to be pumped   into combustion chamber which could result in   explosion upon ignition.   5. Check operation of burner primary control in   accordance with manufacturer’s instructions   included with the control. Following is the method   we recommend in checking the safety switch in   this primary control.   5. Press thermal protector button of burner motor.   6. Make sure air filters are in place and are clean.   7. Make sure all air openings in furnace, all   ventilation and combustion air openings, all return   air grilles, and all warm air registers are   unobstructed and open.   A. Flame Failure – Simulate by shutting off oil   supply manual valve while burner is on.   Within 9 seconds the control will shut the   burner down and flash a diagnostic code of   1/2 second on / 1/2 second off. Ignition and   motor stop and oil valve closes   Manual 2100-422   Page   29   COMBINATION COMBUSTION   CHAMBER/BURNER MOUNTING   SYSTEM   WARNING   The furnace has been designed with a combustion   chamber mounting system that enables service   personnel to remove the combustion chamber, its   mounting system, and burner assembly as one unit for   inspection and/or service on the bench. It has also been   designed to remove the burner assembly independently   from the mounting system to perform basic annual   service and inspection. The mounting system is   completely adjustable so exact alignment between the   burner tube and combustion chamber may be assured   prior to installation into the furnace. See Figure 19   and 20.   The procedures described in Figures 19 and   20 should be conducted only by a qualified   service technician.   Improper servicing could cause electric shock   hazard, fires or explosion resulting in damage,   injury or death.   FIGURE 19   REMOVAL OF BURNER ONLY   DANGER   *ELECTRICAL SHOCK HAZARD   *DISCONNECT POWER BEFORE   SERVICING.   ! STEP 2:   LOOSEN (3) BOLTS   ENOUGH TO ROTATE   BURNER ASSEMBLY.   STEP 3:   ROTATE BURNER   COUNTER-CLOCKWISE   STEP 4:   STEP 1:   PULL BURNER STRAIGHT   DISCONNECT "T-T" WIRES,   POWER CONNECTIONS, AIR   BOOT (OPTIONAL) AND OIL   LINES TO BURNER.   OUT TO PREVENT DAMAGE   TO CHAMBER DURING   REMOVAL.   MIS-1834   Manual 2100-422   Page 30   TO REMOVE THE ENTIRE COMBUSTION   CHAMBER MOUNTING SYSTEM   TO REMOVE BURNER ONLY   Disconnect fuel line, power cord and wires from T, T   on primary control. Loosen (3) 1/4 inch bolts securing   burner mounting flange. Twist burner counterclockwise   and pull straight back away from the furnace. (See   Figure 19.)   Disconnect fuel line, power cord and wires from T, T   on primary control. Remove (6) 5/16 inch bolts from   around front plate. Next remove (2) 5/16 inch nuts   from upper right and left hand corners of the front plate.   Pull entire assembly straight back away from furnace.   BE CAREFUL NOT TO TIP ASSEMBLY UP OR   DOWN AS IT MAY DAMAGE THE COMBUSTION   CHAMBER. (See Figure 20.)   FIGURE 20   REMOVAL OF ENTIRE COMBUSTION CHAMBER MOUNTING SYSTEM   DANGER   ! *ELECTRICAL SHOCK HAZARD   *DISCONNECT POWER BEFORE   SERVICING.   STEP 3:   REMOVE (2) NUTS   IN THE TOP LEFT   AND RIGHT CORNERS   OF BURNER PLATE.   CHAMBER   BURNER   PLATE   STEP 2:   REMOVE (6) BOLTS   AROUND PERIMETER   OF BURNER PLATE   STEP 4:   PULL BURNER ASSEMBLY   STRAIGHT OUT TO PREVENT   DAMAGE TO CHAMBER   DURING REMOVAL.   STEP 1:   DISCONNECT "T-T" WIRES,   POWER CONNECTIONS, AIR   BOOT (OPTIONAL) AND OIL   LINES TO BURNER.   MIS-1837   Manual 2100-422   Page 31   PUMPSQUEALSORCHATTERS   COMMON CAUSES OF TROUBLE   This may be caused by air in pipes. Check all joints in   the oil supply pipe for leaks. Check strainer in pump; if   dirty, clean.   CAUTION   To avoid accidents, always open main switch   (OFF position) when servicing the burner.   INSUFFICIENTHEAT   Check limit control setting. It may be that flame is not   allowed to stay on long enough to generate sufficient   heat in furnace to heat the house properly. If the proper   size furnace has been selected according to house   requirements and satisfactory heat is not obtained,   recheck the heating plant for size and capacity in   relation to house. Check for clogged filters.   BURNER WILL NOT PRODUCE FLAME   Check oil level gauge to see that there is sufficient oil in   tank or tanks. Check the burner mounted relay control.   Do not adjust this control.   Check position of electrodes – incorrect position will   cause slow or delayed ignition. Clean electrodes and   nozzle. Check and clean strainer in pump. If oil line   filter is used, check filter condition.   Check and make sure the heat anticipator on the   thermostat is set correctly.   CARE OF FINISH   If burner runs but there is no flame the fuel pump may   be air bound. Follow instructions for bleeding fuel   pump.   This furnace cabinet is made with a very durable and   corrosion resistant finish. With normal cleaning it will   last for many years.   Check and make sure the solenoid valve on the oil   pump is being energized and opening.   BURNER STARTS OR STOPS TOO OFTEN   WARNING   Check heat anticipator setting on thermostat.   Under no circumstance should a soot   deterioration device be used in the   combustion chamber. These products known   as “soot busters” or “soot sticks” are   comprised of chemicals that burn at very high   temperatures which may exceed the   temperature rating of the combustion chamber   material.   NOZZLEPRODUCESASTRINGYFLAME   Worn tangential grooves in nozzle. Replace nozzle.   BASEMENTTANKHUM   Occasionally with a two-pipe installation there may be   a low return line hum. Eliminate hum by installing a   special anti-hum valve in the return line near pump.   Use of these products are detrimental to the   life expectancy of the combustion chamber   and will destroy the chamber. Refer to the   “Cleaning of Furnace” section for proper   cleaning methods.   HEAVYFIREORPULSATINGFLAME.   These may occur after burner starts. It may be caused   by a slight oil leak in the fuel pump and cannot be   corrected except by replacing the pump. This happens   only when the burner is started.   CLEANING OF THE HEAT EXCHANGER   All of these units have four clean out plugs for easy   cleaning of the heat exchanger. They are accessible   from the front and back of these units by removing the   clean out access cover in the burner compartment and at   the back of unit. The furnace should be checked   annually by a qualified service technician.   CHATTERING SOUND OR HIGH PITCH NOISE   This noise from motor can usually be traced to where a   conduit or BX cable is fixed rigidly or attached to some   part of the building. Relieving this strain may eliminate   noise.   Manual 2100-422   Page   32   BLOWER SYSTEM RESISTANCE CHARTS   CHART 1   CHART 4   FH085D36E DATA   FLF/FLR085D36E DATA   Blower Speed   Low   Blower Static   Blower Speed   Blower Static   .07   .15   .20   .13   .24   .30   .19   .33   .40   .25   .41   .50   Low   Medium   High   .10   .16   .20   .15   .24   .30   .23   .34   .40   .30   .43   .50   Medium   High   CHART 5   FLF/FLR110D48E DATA   CHART 2   FH110D48E DATA   Blower Speed   Low   Blower Static   Blower Speed   Blower Static   Low   .03   .09   .16   .20   .08   .16   .25   .30   .13   .23   .34   .40   .18   .32   .44   .50   .05   .09   .15   .20   .09   .16   .24   .30   .15   .23   .34   .40   .20   .31   .42   .50   Medium Low   Medium High   High   Medium Low   Medium High   High   CHART 3   FH110D60E DATA   CHART 6   FLF/FLR110D60E DATA   Blower Speed   Low   Blower Static   Blower Speed   Blower Static   .06   .10   .14   .20   .12   .17   .21   .30   .17   .23   .31   .40   .21   .30   .38   .50   Low   .08   .10   .13   .20   .12   .16   .21   .30   .17   .22   .29   .40   .21   .28   .36   .50   Medium Low   Medium High   High   Medium Low   Medium High   High   Manual 2100-422   Page 33   CHART 8   CHART 7   FC085D36E DATA   FLR140D60E DATA   Blower Speed   Blower Static   Blower Speed   Blower Static   Low   Low   Medium   High   .05   .08   .11   .20   .14   .17   .20   .30   .17   .22   .27   .40   .24   .30   .35   .50   .08   .16   .20   .14   .24   .30   .20   .36   .40   .26   .42   .50   Medium Low   Medium High   High   Manual 2100-422   Page   34   FH SERIES   WIRING DIAGRAM   UNIT   NOTES   PURPLE   PURPLE   PRIMARY   IF PRIMARY LIMIT WIRES   ARE TO BE REPLACED,   USE WIRE WITH INSUL.   TEMP. RATING OF 200°C.   LIMIT   BACKUP   LIMIT   1 CONTROL   BURNER ASS'Y   HEATING SPEED   CONNECTION POINT.   2 3 L1   L2   T T   COOLING SPEED   CONNECTION POINT.   VALVE   OIL VALVE   ONLY ONE HEATING   AND COOLING SPEED   CAN BE CONNECTED.   ALL OTHER TAPS   BURNER   MOTOR   BURNER   MOTOR   4 5 CONNECT TO "SPARE"   TERMINALS.   IGNITOR IGNITOR   CAD CELL   DASHED LINES   REPRESENT FIELD WIRING.   CAD CELL   DANGER   1 ! *ELECTRICAL SHOCK HAZARD   *DISCONNECT POWER BEFORE   SERVICING.   BLACK   WHITE   GREEN   HOT   NEUTRAL   GROUND   PLUG   #1   PLUG #2   1 2 3 4 5 6 7   8 9 1 2   WARNING   ! IF ANY OF THE ORIGINAL WIRE AS   SUPPLIED WITH THIS APPLIANCE   MUST BE REPLACED, IT MUST BE   REPLACED WITH WIRING MATERIAL   HAVING A TEMP. RATING OF AT   LEAST 105°C EXCEPT PRIMARY   LIMIT WIRES. SEE NOTE "1".   BLACK   BLACK   GREEN   DOOR   SWITCH   WHITE   5 GREEN   C Rc   Y G W Rh   Y BLUE   R W G Y C COND.   150   180   210   240   THERMOSTAT   UNIT   24V   BLOWER CONTROL   3 T T T87F/Q539A1220   OR EQUIVELANT   24V.   CONN.   TRANSFORMER   120V COM   OPTIONAL AIR COND. SETTINGS   NOM.   L1   4 COOLING BLOWER CFM @   UNIT   A/C   TONS   2 2 1/2   3 2 1/2   3 3 1/2   4 SPEED (COLOR)   .50 WC   LOW (RED)   MED (BLUE)   730   900   FH085D36E   HIGH (BLACK)   LOW (RED)   MED-LOW (ORANGE)   MED-HIGH (BLUE)   HIGH (BLACK)   1160   1020   1280   1495   1640   1300   1460   1660   1970   BLACK   WHITE   2 WHITE   FH110D48E   FH110D60E   SEE CHART FOR   HEATING AND COOLING   WIRE COLORS   WHITE   3 LOW (RED)   PLUG #3   3 1/2   4 5 MED-LOW (ORANGE)   MID-HIGH (BLUE)   HIGH (BLACK)   1 2 3 4 5   BLOWER   CAPACITOR   FACTORY SETTINGS   INPUT   RATE   GPH   0.55   0.65   0.75   0.85   1 TEMP.   RISE   HEATING BLOWER COOLING BLOWER   SPEED (COLOR)   LOW   VOLTAGE   UNIT   SPEED (COLOR)   HIGH (BLACK)   RANGE   70°-100°   70°-100°   60°-90°   70°-100°   60°-90°   60°-90°   60°-90°   LOW (RED)   LOW (RED)   MED (BLUE)   FH085D36E   HIGH   VOLTAGE   LOW (RED)   MED-LOW (ORANGE)   LOW (RED)   FH110D48E   FH110D60E   0.85   1 MED-LOW (ORANGE)   FIELD   WIRING   BLOWER CAPACITOR RATING   UNIT MOTOR CAPACITOR   FH085D36E   FH110D48E   FH110D60E   1/3   1/2   3/4   5/370   7.5/370   15/370   4047-118 B   BLOWER ASSEMBLY   Manual 2100-422   Page   35   FLF/R SERIES   WIRING DIAGRAM   FACTORY SETTINGS   PRIMARY LIMIT   BACKUP LIMIT   HTG. BLWR SPD. TEMP. COLING BLWR.   UNIT   GPH INPUT   1 (COLOR)   LOW (RED)   LOW (RED)   MED (BLUE)   RISE   SPEED   0.55   0.65   0.75   0.85   1 60°-90° HIGH (BLACK)   60°-90° HIGH (BLACK)   60°-90° HIGH (BLACK)   FLF/R085D36E   BLACK   BLACK   BLACK   BLACK   FLF/R110D48E   FLF/R110D60E   MED. HIGH (BLUE)60°-90° HIGH (BLACK)   MED. HIGH (BLUE)60°-90° HIGH (BLACK)   MED. HIGH (BLUE)60°-90° HIGH (BLACK)   MED. HIGH (BLUE)60°-90° HIGH (BLACK)   1.1   1.25   FLR140D60E   PURPLE   PURPLE   5 BURNER ASS'Y   1 2 L1   L2   T T   THERMOSTAT   VALVE   OIL VALVE   C Y Rc   Y G W Rh   T87F/Q539A1220   OR EQUIVELANT   BURNER   MOTOR   BURNER   MOTOR   R W G Y C COND.   150   COOLING BLOWER SPEEDS   180   210   240   UNIT   IGNITOR   IGNITOR   NOM. A/C   CFM@   .50" WC   775   BLOWER CONTROL   3 24V.   T T UNIT   SPEED (COLOR)   (TONS)   CONN.   2 2.5   3 2.5   3 3.5   4 3 LOW (RED)   MED (BLUE)   HIGH (BLACK)   CAD CELL   CAD CELL   FLF/R085D36E   FLF/R110D48E   1070   1275   1065   1235   1415   1525   1190   1400   1640   2250   L1   4 LOW (RED)   MED LOW (ORANGE)   MED HIGH (BLUE)   HIGH (BLACK)   2 LOW (RED)   FLF/R110D60E   FLR140D60E   3.5   4 5 MED LOW (ORANGE)   MED HIGH (BLUE)   HIGH (BLACK)   BLACK   BLACK   NOTES   IF PRIMARY LIMIT WIRES   ARE TO BE REPLACED,   USE WIRE WITH INSUL.   TEMP. RATING OF 200°C.   BLOWER CAPACITOR   BLOWER CAPACITOR RATING   1 BROWN   UNIT   MOTOR CAPACITOR   FLF/R085D36E   FLF/R110D48E   FLF/R110D60E   FLR140D60E   1/3   1/2   5/370   7.5/370   HEATING SPEED   2 3 CONNECTION POINT.   BROWN   COOLING SPEED   CONNECTION POINT.   3/4   15/370   COM 120V   1 2 3 4 ONLY ONE HEATING   AND COOLING SPEED   CAN BE CONNECTED.   ALL OTHER TAPS   CONNECT TO "SPARE"   TERMINALS.   BLACK   TRANSFORMER   24V   BLUE   4 5 DANGER   ! ORANGE   WHITE   GREEN   BLACK   NEUTRAL   GROUND   HOT   *ELECTRICAL SHOCK HAZARD   *DISCONNECT POWER BEFORE   SERVICING.   RED   DASHED LINES   REPRESENT FIELD WIRING.   5 SEE CHART FOR   "HEAT" AND "COOL"   WIRE COLORS.   WHITE   BLOWER ASSEMBLY   4047-119 C   CONTROL PANEL   FC SERIES   WIRING DIAGRAM   FACTORY SETTINGS   PRIMARY LIMIT   HTG. BLWR SPD. TEMP. COLING BLWR.   UNIT   GPH INPUT   1 (COLOR)   LOW (RED)   LOW (RED)   MED (BLUE)   RISE   SPEED   0.55   0.65   0.75   60°-90° HIGH (BLACK)   70°-100° HIGH (BLACK)   60°-90° HIGH (BLACK)   BLACK   BLACK   FC085D36E   PURPLE   PURPLE   5 BURNER ASS'Y   1 2 L1   L2   T T   THERMOSTAT   T87F/Q539A1220   VALVE   OIL VALVE   C Y Rc   Y G W Rh   OR EQUIVELANT   BURNER   MOTOR   BURNER   MOTOR   R W G Y C COND.   150   180   210   240   UNIT   IGNITOR   IGNITOR   BLOWER CONTROL   3 24V.   T T CONN.   CAD CELL   CAD CELL   L1   BACKUP LIMIT   COOLING BLOWER SPEEDS   NOM. A/C   CFM@   .50" WC   775   1070   1230   UNIT   SPEED (COLOR)   (TONS)   4 2 2.5   3 LOW (RED)   MED (BLUE)   HIGH (BLACK)   2 FC085D36E   1 DOOR   SWITCH   BLACK   BLACK   2 3 4 BLACK   BLACK   NOTES   IF PRIMARY LIMIT WIRES   ARE TO BE REPLACED,   USE WIRE WITH INSUL.   TEMP. RATING OF 200°C.   BLOWER CAPACITOR   (5/370)   1 BROWN   HEATING SPEED   CONNECTION POINT.   2 3 DANGER   *ELECTRICAL SHOCK HAZARD   *DISCONNECT POWER BEFORE   SERVICING.   WHITE   ! COOLING SPEED   CONNECTION POINT.   BROWN   BLACK   BLUE   COM 120V   1 2 3 4 5 ONLY ONE HEATING   AND COOLING SPEED   CAN BE CONNECTED.   ALL OTHER TAPS   CONNECT TO "SPARE"   TERMINALS.   TRANSFORMER   24V   4 5 WHITE   GREEN   BLACK   NEUTRAL   GROUND   HOT   RED   DASHED LINES   REPRESENT FIELD WIRING.   SEE CHART FOR   "HEAT" AND "COOL"   WIRE COLORS.   WHITE   BLOWER ASSEMBLY (1/3 HP)   4047-120 B   CONTROL PANEL   |