| INSTALLATION   INSTRUCTIONS   PRODUCT LITERATURE   Lennox Industries Inc.   Dallas, Texas   GWB8-262E-2   GWB8-245E-2   GWB8-299E-2   GWB8-280E-2   GAS FIRED BOILER   RETAIN THESE INSTRUCTIONS FOR   FUTURE REFERENCE   These instructions must be affixed on   or adjacent to the boiler.   ! WARNING   Improper installation, adjustment,   alteration, service, or maintenance   can cause injury or property damage.   Refer to this manual. For assistance   or additional information consult a   qualified installer, service agency, or   the gas supplier.   This boiler cannot be used with all types of   chimneys. Read these instructions carefully   before installing.   GAS-FIRED HOT WATER BOILERS   These Gas-Fired Water boilers are low pressure,   sectional cast iron boilers Design Certified by   CSA (Canadian Standards Association) for   use with Natural and Propane Gases. They   are constructed and hydrostatically tested for   maximum working pressure of 50 psi (pounds   per square inch) in accordance with A.S.M.E.   (American Society of Mechanical Engineers)   Boiler and Pressure Vessel Code Section IV   Standards for Cast Iron Heating Boilers.   Tested for 50 psi. ASME   Working Pressure   C.S.A. Certified for   Natural gas or Propane   P/N# 240009276, Rev. A [03/2012]   2 - BOILER RATINGS AND CAPACITIES   Table 2 - Ratings and Capacities   † NATURAL GAS   † PROPANE GAS   AFUE   (2)   (2)   HIGH   NET   HIGH   ALTITUDE   INPUT   (3) Mbh   BOILER MODEL   NUMBER(1)   NET AHRI   HEATING   CAPACITY   (3)Mbh   INTERMITTENT   IGNITION   WITH VENT   DAMPER   Input   (3) Mbh   Heating   Capacity   (3) Mbh   ALTITUDE INPUT   AHRI   RATING   Water,   (3) Mbh   RATING   Water,   (3) Mbh   (3)Mbh   INPUT   (3) Mbh   GWB8-262E-2   GWB8-299E-2   GWB8-245E-2   GWB8-280E-2   262.5   299   220   251   191   218   83.9   83.7   83.9   83.7   236   269   245   280   206   235   179   204   220   252   † Input rating for sea level to 2,000 ft. (610m) above sea level.   • United States, over 2000 ft (610m) above sea level. Reduce input rate 4% for every 1000 ft (304m)   above sea level.   • *Canada, 2000 ft (610m) to 4500 (1350m) above sea level, reduce input per table. Over 4500 ft   (1350m) above sea level. Contact Provincial authority having jurisdiction.   + Heating Capacity based on D.O.E. (Department of Energy) test procedure.   (2)   Net AHRI Water rating shown based on piping and pickup allowance of 1.15. Consult manufacturer before   selecting boiler for installations having unusual piping and pickup requirements, such as intermittent   system operation, extensive piping systems, etc.   Mbh = 1,000 Btuh = British Thermal Unit Per Hour   (3)   - Ratings marked “Net AHRI Ratings” indicate amount of remaining heat input used to heat radiation or   terminal units. Net AHRI Ratings shown are based on allowance of 1.15 in accordance with factors shown on   AHRI Standard as published by The Hydronics Institute.   - Selection of boiler size should be based upon “Net AHRI Rating” being equal to or greater than calculated   heat loss of the building.   - Consult manufacturer before selecting boiler for installations having unusual piping and pickup requirements.   BOILERS FOR USE AT HIGH ALTITUDE   Boiler is factory equipped for use at altitudes of 0-2,000 feet above sea level.   For use at altitudes above 2,000 feet above sea level, input ratings are reduced by change in main burner   orifice size.   For altitudes above 2,000 feet above sea level, input ratings should be reduced at rate of 4% for each 1,000   feet above sea level. Consult National Fuel Gas Code, ANSI Z223.1/NFPA 54, or manufacturer for correct   orifice sizing information.   In Canada, a high altitude conversion kit is available to convert to altitudes of 2,000 to 4,500 feet above sea   level. Please consult your dealer.   3 3 - TABLE OF CONTENTS   KEEP THIS MANUAL NEAR BOILER   1 - Dimensions....................................................2   2 - Ratings And Capacities....................................3   3 - Table of Contents............................................4   4 - Installation Procedure .....................................5   5 - Ventilation & Combustion Air............................6   6 - Connecting Supply And Return Piping................7   7 - Chimney And Vent Pipe Connection................. 11   8 - Vent Damper Operation................................. 14   9 - Gas Supply Piping......................................... 15   10 - Electrical Wiring.......................................... 15   11 - Wiring Diagrams......................................... 16   12 - General Instructions.................................... 19   13 - Lighting Instructions ................................... 20   14 - Operating Your Boiler .................................. 21   15 - Maintaining Your Boiler................................ 23   16 - Service Hints.............................................. 24   17 - Equipment And Optional Accessories ............ 25   Appendix A - Control Module............................... 27   RETAIN FOR FUTURE REFERENCE   IMPORTANT: Read the following instructions   COMPLETELY before installing!!   ! WARNING   Fire, explosion, asphyxiation and electrical shock   hazard. Improper installation could result in death   or serious injury. Read this manual and understand   all requirements before beginning installation.   WARNING   ! Keep boiler area clear and free from combustible   materials, gasoline and other flammable vapors   and liquids.   DO NOT obstruct air openings to the boiler room.   Modification, substitution or elimination of factory   equipped, supplied or specified components may   result in personal injury or loss of life.   TO THE OWNER - Installation and service of this   boiler must be performed by a qualified installer.   SAFETY SYMBOLS & WARNINGS   The following defined symbols are used throughout this   manual to notify the reader of potential hazards of varying   risk levels.   TO THE INSTALLER - Leave all instructions with   boiler for future reference.   When this product is installed in the   Commonwealth of Massachusetts the installation   must be performed by a Licensed Plumber or   Licensed Gas Fitter.   ! DANGER   Indicates a hazardous situation which, if not avoided,   WILL result in death or serious injury   ! WARNING   Indicates a hazardous situation which, if not avoided,   could result in death or serious injury.   ! CAUTION   Indicates a hazardous situation which, if not avoided,   could result in minor or moderate injury.   NOTICE   Used to address practices not related to personal   injury.   4 4 - INSTALLATION PROCEDURE   ! ! WARNING   WARNING   Improper installation, adjustment, alteration, service   or maintenance could result in death or serious   injury.   Fire hazard. Do not install boiler on combustible   flooring or carpeting. Failure to follow these   instructions could result in death or serious injury.   1. FOR INSTALLATION ON NON-COMBUSTIBLE   FLOORS ONLY - For installation on combustible   flooring special base must be used. (See Replacement   Parts Section.) Boiler can not be installed on   carpeting.   1. Installation must conform to the requirements of the   authority having jurisdiction or, in the absence of such   requirements, to the National Fuel Gas Code, ANSI   Z223.1/NFPA 54, and/or Natural Gas and Propane   Installation Code, CAN/CSA B149.1.   2. Where required by the authority having jurisdiction, the   installation must conform to the Standard for Controls   and Safety Devices for Automatically fired Boilers,   ANSI/ASME CSD-1.   Table 3 - MINIMUM CLEARANCE DIMENSIONS   Inches   (mm)   Top   6”   6”   (152mm)   (152mm)   (178mm)   (152mm)   (457mm)   (152mm)   (13mm)   3. Boiler series is classified as a Category I. Vent   installation shall be in accordance with "Venting of   Equipment ," of the National Fuel Gas Code, ANSI   Z223.1/NFPA 54, or "Venting Systems and Air Supply   for Appliances," of the Natural Gas and Propane   Installation Code, CAN/CSA B149.1, or applicable   provisions of the local building codes.   Rear   Control Side   Opposite Side   Front   7”   6”   18”   6”   Flue/Vent Connector   Near Boiler Piping   1/2”   4. Boiler has met safe lighting and other performance   criteria with the gas manifold and control assembly on   the boiler per the latest revision of ANSI Z21.13/CGA   4.9.   NOTE: Greater clearances for access should supersede fire   protection clearances.   5. Install boiler such that gas ignition system components   are protected from water (dripping, spraying, rain,   etc.) during appliance operation and service, (circulator   replacement, condensate trap, control replacement,   etc.).   * Definition of Alcove is three sided space with no wall in   front of boiler. ANSI standard for alcove is 18 inches from   front of appliance to leading edge of side walls as shown   below.   6. Locate boiler on level, solid base as near chimney as   possible and centrally located with respect to heat   distribution system as practical.   Minimum Clearances to Combustible   Construction (as seen from above)   7. Allow 24 inches (610mm ) at front and right side for   servicing and cleaning.   6"   8. When installed in utility room, door should be wide   enough to allow largest boiler part to enter, or to   permit replacement of another appliance such as water   heater.   6"   7"   Control   Side   BOILER   Front   18"   5 5 - VENTILATION & COMBUSTION AIR   Provide combustion air and ventilation air in accordance   • All Outdoor Air. Provide permanent opening(s)   communicating directly or by ducts with outdoors.   with the section “Air for Combustion and Ventilation,” of the   National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections   8.2, 8.3 or 8.4 of Natural Gas and Propane Installation   Code, CAN/CSA B149.1, or applicable provisions of local   building codes.   A. Two Permanent Opening Method. Provide opening   commencing within 12 inches of top and second   opening commencing within 12 inches of bottom of   enclosure.   Provide make-up air where exhaust fans, clothes dryers,   and kitchen ventilation equipment interfere with proper   operation.    Direct communication with outdoors or   communicating through vertical ducts. Provide   minimum free area of 1 in² per 4 Mbh of total   input rating of all appliances in enclosure.   National Fuel Gas Code recognizes several methods   of obtaining adequate ventilation and combustion air.   Requirements of the authority having jurisdiction may   override these methods.    Communicating through horizontal ducts.   Provide minimum free area of 1 in² per 2   Mbh of total input rating of all appliances in   enclosure.   • Engineered Installations. Must be approved by   authority having jurisdiction.   B. One Permanent Opening Method. Provide opening   commencing within 12 inches of top of enclosure.   Provide minimum clearance of 1 inch on sides/back   and 6 inches on front of boiler (does not supersede   clearance to combustible materials).   • Mechanical Air Supply. Provide minimum of 0.35   cfm per Mbh for all appliances located within space.   Additional requirements where exhaust fans installed.   Interlock each appliance to mechanical air supply   system to prevent main burner operation when   mechanical air supply system not operating.   • Refer to National Fuel Gas Code for additional   requirements for louvers, grilles, screens and air   ducts.   • All Indoor Air. Calculate minimum allowable room   volume for all appliances in space. Use a different   method if minimum volume not available.   • Combination Indoor and Outdoor Air. Refer to National   Fuel Gas Code for application information.   A. Standard Method. Cannot be used if known air   infiltration rate is less than 0.40 air changes per   hour. See Table 4 for space with boiler only. Use   equation for multiple appliances.   Canada   National Gas and Propane Installation Code Requires   providing air supply in accordance with:   Volume ≥ 50 ft3 x Total Input [Mbh]   • Section 8.2 and 8.3 when combination of appliances   has a total input of up to and including 400 Mbh (120   kW).   B. Known Air Infiltration Rate. See Table 4 for   space with boiler only. Use equation for multiple   appliances. Do not use an air infiltration rate   (ACH) greater than 0.60.   • Section 8.4 when combination of appliances has total   input exceeding 400 Mbh (120 kW).   • Refer to Natural Gas and Propane Installation Code   for specific air supply requirements for enclosure   or structure where boiler is installed, including air   supply openings and ducts.   Volume ≥ 21 ft3⁄ACH x Total Input [Mbh]   C. Refer to National Fuel Gas Code for opening   requirements between connected indoor spaces.   Table 4 - Minimum Room Volume, Indoor Air Only*   Room Cubic Feet Volume   Known Air Infiltration Rate Method (Air Changes Per Hour)   Standard   Method   Input Mbh   0.1   0.2   0.3   0.4   0.5   0.6   262.5   299   13125   14950   55125   62790   27563   31395   18375   20930   13781   15698   11025   12558   9188   10465   * Table values based on boiler only. Add volume for any additional appliances.   6 6 - CONNECTING SUPPLY AND RETURN PIPING   ! WARNING   Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns,   scalding, or water damage due to discharge of steam and/or hot water during operation.   Discharge line shall:   • connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum   distance from floor or allowable safe point of discharge;   • be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge   line;   • have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug or   place any obstruction in discharge line;   • terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing;   • allow complete drainage of the valve and the discharge line;   • be independently supported and securely anchored to avoid applied stress on the relief valve;   • be as short and straight as possible;   • terminate with plain end (not threaded);   • be constructed of material suitable for exposure to temperatures of 375°F (191°C); or greater.   Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation   requirements.   Figure 2 - Safety Relief Valve   RELIEF VALVE   DISCHARGE   LINE   Check local   codes for   maximum   distance   from floor   or allowable   safe point of   discharge.   7 6 - CONNECTING SUPPLY AND RETURN PIPING   Verify clean water supply is available to water inlet   ! WARNING   valve. Install sand strainer when water supply is from   a well or pump.   Burn and scald hazard. Safety relief valve could   discharge steam or hot water during operation. In-   stall discharge piping per these instructions.   Install hot water boiler above radiation level or as   required by Authority having jurisdiction install low   water cutoff device at time of installation. Periodic   inspection is necessary, as is flushing of float type   devices, per manufacturers specific instruction.   1. Boiler is shipped assembled. Install discharge piping   from safety relief valve. See Warning, Page 7.   2. Install temperature pressure gauge.   • Apply pipe sealant to threads on shaft of gauge.   FOR USE WITH COOLING UNITS   A. Boiler used in connection with refrigeration   system, must be installed so that chilled medium   is piped in parallel with heating boiler. Appropriate   valves must be used to prevent chilled medium   from entering heating boiler. See Figure 5 page 9.   B. Boiler connected to heating coils located in air   handling units where they may be exposed to   refrigerated air circulation, piping system shall   be equipped with flow control valves or other   automatic means to prevent gravity circulation of   boiler water during cooling cycle.   • Thread gauge into supply water tee. See Figure 3.   NOTICE   DO NOT TIGHTEN GAUGE BY HAND!! Gauge should   be tightened using crescent wrench or 9/16” open   end wrench. See Figure 3.   3. Connect supply and return lines to boiler. Connections   may require additional fittings and parts, as shown on   diagrams.   LOW WATER TEMPERATURE AND LARGE WATER   CONTENT SYSTEM (See Figures 6 and 7, Page 10.)   Significant condensation may form in boiler and/or   venting system if boiler is operated for long period of   time with return temperatures of less than 120° F.   Figure 3 - Temperature Pressure Gauge   Condensate is corrosive and can cause severe   damage to boiler and venting system. Minimum   design return water temperature to prevent   condensation in boiler and venting is 120°F.   Minimum high limit setting is 140°F.   1. Boiler used in heating system where design water   temperatures below 140°F are desired (e.g. radiant   floor heating), 4-way mixing valve or suitable   alternative is required to prevent low temperature   return water from entering boiler. Follow mixing valve   manufacturer’s instructions.   2. Boiler connected to system having large water content   (such as former gravity system), install system bypass.   See Figures 6 and 7, page 10.   3. If boiler water reset control is used to operate boiler,   minimum reset supply water temperature setpoint   must be at least 140°F, unless mixing valve is used as   in (1) above.   8 6 - CONNECTING SUPPLY AND RETURN PIPING   Figure 4 - Typical Hot Water Piping   Figure 5 - Chilled Water Piping   9 6 - CONNECTING SUPPLY AND RETURN PIPING   Bypass Piping Required For High Mass (Large Water Content) Systems   Figure 6 - BYPASS PIPING - CIRCULATOR ON SUPPLY   Figure 7 - BYPASS PIPING - CIRCULATOR ON RETURN   10   7 - CHIMNEY AND VENT PIPE CONNECTION   Connecting The Vent Damper And Vent   WARNING   ! Connector   Refer to Figure 1, page 2 for size and location of vent   (flue opening).   Boiler and venting installations shall be performed   by a qualified expert and in accordance with the   appropriate manual. Installing or venting boiler   or other gas appliance with improper methods or   materials may result in serious injury or death due   to fire or to asphyxiation from poisonous gases such   as carbon monoxide with is odorless and invisible.   NOTICE   Damper blade on furnished vent damper has 1/2   square inch hole (approximately 3/4” diameter).   Boilers equipped with intermittent ignition, hole   should be plugged by using plug supplied with vent   damper.   Boilers connecting to gas vents or chimneys, vent   installations shall be in accordance with “Venting of   Equipment”, of the National Fuel Gas Code, ANSI   Z223.1/NFPA 54 or “Venting Systems and Air Supply   for Appliances,” of the Natural Gas and Propane   Installation Code, CAN/CSA B149.1, or applicable   provisions of the local building codes.   1. Position furnished vent damper on top of flue outlet   collar. Fasten damper securely to flue outlet collar with   sheet metal screws. Verify damper blade has clearance   to operate inside of diverter. Do not modify either draft   diverter or vent damper during installation.   Check Your Chimney   It must be clean, right size, properly constructed and   in good condition.   As An Option   Damper may be installed in horizontal or vertical   position, closer to flue outlet collar preferred. See   Figures 8, 9 and 10 and enclosed vent damper   instructions.   Chimney Sizing   Chimney sizing, and vent installation must be in   accordance with The National Fuel Gas Code, ANSI   Z223.1/NFPA 54 or CAN/CSA B149.1, or applicable   provisions of local building codes.   2. Install vent damper to service only single boiler for   which it is intended. Damper position indicator shall be   in visible location following installation. Locate damper   so it is accessible for servicing. See Figure 9.   This is a high efficiency boiler with low stack   temperature. Following recommendations are in   addition to requirements of the National Fuel Gas   Code.   3. Damper must be in the open position when appliance   main burners are operating.   1. Type B double wall vent pipe is recommended for   vent connector. Single wall vent connectors should   not be used unless following conditions are true:   4. Boiler is equipped with factory wired harness that plugs   into vent damper.   a) Except for basement, boiler is not installed in   unheated space.   5. Slope pipe up from boiler to chimney not less than 1/4”   per foot.   b) Total horizontal portion of vent connector, not   including elbows is less than 5 feet in length.   6. Run pipe as directly as possible with as few elbows as   2. Outside chimneys (i.e. chimneys exposed to   outdoors below roof line) should not be used unless   they are:   possible.   7. Do not connect to fireplace flue.   8. End of vent pipe must be flush with inside face of   chimney flue. Use a sealed-in thimble for chimney   connection.   a) enclosed in a chase, or   b) lined with type B vent pipe, or listed flexible   vent liner, or other certified chimney lining system.   3. Where possible it is recommended to common vent   boiler and water heater.   Fasten sections of vent pipe with sheet metal screws   to make piping rigid. Support horizontal potions of   vent system to prevent sagging. Use stovepipe wires   every 5’ to support pipe from above. Use double wall   vent pipe if vent pipe must go through crawl space.   Where vent pipe passes through combustible wall   or partition, use ventilated metal thimble. Thimble   should be 4 inches larger in diameter than vent pipe.   4. For multiple boiler installations, consult boiler   manufacturer for venting recommendations.   11   7 - CHIMNEY AND VENT PIPE CONNECTION   5. Test for spillage at the draft hood relief opening after   WARNING   ! 5 minutes of main burner operation. Use the flame of   a match or candle, or smoke from a cigarette, cigar or   pipe.   Boiler and venting installations shall be performed   by a qualified expert and in accordance with the   appropriate manual. Installing or venting boiler   or other gas appliance with improper methods or   materials may result in serious injury or death due   to fire or to asphyxiation from poisonous gases such   as carbon monoxide with is odorless and invisible.   6. After it has been determined that each appliance   remaining connected to the common venting system   properly vents when tested as outlined above, return   doors, windows, exhaust fans, fireplace dampers and   any other gas-burning appliance to their previous   conditions of use.   ! WARNING   7. Any improper operation of the common venting system   should be corrected so the installation conforms with   the National Fuel gas Code, ANSI Z223.1/NFPA 54,   and/or the Natural Gas and Propane Installation Code,   CAN/CSA B149.1. When re-sizing any portion of the   common venting system, the common venting system   should be re-sized to approach the minimum size   determined using the appropriate tables in Chapter 13   of the National Fuel Gas Code, ANSI Z223.1/NFPA 54,   and/or the Natural Gas and Propane Installation Code,   CAN/CSA B149.1.   Do not connect boiler to any portion of mechanical   draft system operating under positive pressure.   Minimum Vent Pipe Clearance   Wood and other combustible materials must not be   closer than 6” from any surface of single wall metal   vent pipe. Listed Type B vent pipe or other listed   venting systems shall be installed in accordance with   their listing.   Removing Existing Boiler From Common   Venting System   When an existing boiler is removed from common   venting system, common venting system is likely to be   too large for proper venting of appliances remaining   connected to it.   At time of removal of existing boiler, following steps   shall be followed with each appliance remaining   connected to the common venting system placed   in operation, while other appliances remaining   connected to common venting system are not in   operation.   1. Seal any unused openings in the common venting   system.   2. Visually inspect the venting system for proper size and   horizontal pitch and determine there is no blockage or   restriction, leakage, corrosion and other deficiencies   which could cause an unsafe condition.   3. Insofar as is practical, close all building doors and   windows and all doors between the space in which the   appliances remaining connected to the common venting   system are located and other spaces of the building.   Turn on clothes dryers and any appliance not connected   to the common venting system. Turn on any exhaust   fans, such as range hoods and bathroom exhausts, so   they will operate at maximum speed. Do not operate a   summer exhaust fan. Close fireplace dampers.   4. Place in operation the appliance being inspected. Follow   the lighting instructions. Adjust thermostat so appliance   will operate continuously.   12   8 - VENT DAMPER OPERATION   Figure 8 - Vent Damper Installation   Figure 9 - Vent Damper Placement   Annually check vent damper and all flue product   carrying areas of appliance, with particular attention   given to deterioration from corrosion or other   sources. If you see corrosion or other deterioration,   contact your heating contractor for repairs. Check   vent damper operation as follows:   For further information, and vent damper   troubleshooting guide, refer to manual packaged with   vent damper.   Inspect vent damper at least once a year by a   qualified service technician.   • When boiler is off, check vent damper positions   indicator points to closed position, Figure 10.   • Turn thermostat or controller up to call for heat and   check vent damper indicator points to open position.   Figure 10 - Vent Damper Position Indicator   • Turn thermostat or controller down again and check   damper position indicator returns to closed position.   Vent Damper Manual Operation   Vent damper may be placed in open position to   permit burner operation by using “HOLD DAMPER   OPEN” switch, located on damper controller.   Thermostat will control burner firing as before, while   damper will remain open. DO NOT turn damper   open manually or motor damage will result. Set   switch to “AUTOMATIC OPERATION” to close vent   damper during burner off cycle.   13   9 - GAS SUPPLY PIPING   • • • Pressure test over 1/2 psig (3.5 kPa). Disconnect   boiler and its individual gas shutoff valve from gas   supply system.   ! CAUTION   WHAT TO DO IF YOU SMELL GAS   • Do not try to light any appliance.   Pressure test at 1/2 psig (3.5 kPa) or less. Isolate   boiler from gas supply system by closing manual gas   shutoff valve.   • Do not touch any electrical switch; do not use   any phone in your building.   Locate leakage using gas detector, noncorrosive   detection fluid, or other leak detection method   acceptable to authority having jurisdiction. Do   not use matches, candles, open flames, or other   methods providing ignition source.   • Immediately call your gas supplier from a   neighbor’s phone. Follow gas supplier’s   instructions.   • If you cannot reach your gas supplier, call the fire   department.   • Correct leaks immediately and retest.   CHECK GAS SUPPLY   Table 5 - Gas Pipe Sizes   NATURAL GAS   Gas pipe to your boiler must be correct size for   length of run and for total BTU per hour input of all   gas utilization equipment connected to it. See Table   5 for proper size. Be sure your gas line complies with   local codes and gas company requirements.   Pipe Capacity - BTU Per Hour Input   Includes Fittings   Length of   Pipe - FT   ½”   ¾”   1”   1¼”   CONNECTING THE GAS PIPING See Figure 11.   Gas line enters boiler from right side.   20   40   60   92,000   63,000   50,000   190,000   130,000   105,000   350,000   245,000   195,000   625,000   445,000   365,000   • Use piping materials and joining methods acceptable   to authority having jurisdiction. In absence of such   requirements:   • USA - National Fuel gas Code, ANSI Z223.1/NFPA 54   PROPANE GAS   • Canada - Natural Gas and Propane Installation Code,   CAN/CSA B149.1   Pipe Capacity - BTU Per Hour Input   Includes Fittings   • Use pipe joint compound suitable for LP gas on male   threads only.   Copper Tubing *   Iron Pipe   Length of   Pipe - FT   ⅝”   ¾”   ½”   ¾”   • Use ground joint unions.   20   40   60   131,000   90,000   72,000   216,000   145,000   121,000   189,000   129,000   103,000   393,000   267,000   217,000   • Install sediment trap upstream of gas controls.   • Use two pipe wrenches when making connection to gas   valve to keep it from turning.   * Outside diameter   Measure length of pipe or tubing from gas meter or   propane second stage regulator.   • Install manual shut-off valve in vertical pipe about 5   feet above floor.   Figure 11 - Gas Piping   • Tighten all joints securely.   • Propane gas connections should only be made by   licensed propane installer.   • Two-stage regulation should be used by propane   installer.   • Propane gas piping should be checked out by propane   installer.   CHECKING GAS PIPING   ! DANGER   Fire Hazard. Do not use matches, candles, open   flames, or other methods providing ignition source.   Failure to comply will result in death or serious   injury.   Pressure test boiler and gas connection before placing   boiler in operation.   14   10 - ELECTRICAL WIRING   VENT DAMPER WIRING   ! WARNING   Boiler is equipped with factory wired harness with 4 pin   molex plug, that plugs into 4 pin molex receptacle inside   vent damper operator.   Electrical shock hazard. Turn OFF electrical power   supply at service panel before making electrical   connections. Failure to do so could result in death   or serious injury.   Vent damper must be connected for boiler to operate.   If any of the original wire as supplied with this   appliance must be replaced,   It must be replaced with type 105°C thermoplastic   wire or its equivalent.   NOTICE   Label all wires prior to disconnection when servicing   controls. Wiring errors can cause improper and   dangerous operation. Verify proper operation after   servicing.   Electrically bond boiler to ground in accordance with   requirements of authority having jurisdiction. Refer to:   • USA- National Electrical Code, ANSI/NFPA 70.   • Canada - Canadian Electrical Code, Part I, CSA C22.1:   Safety Standard for Electrical Installations.   ELECTRIC POWER SUPPLY   Run separate 120 volt circuit from separate over   current protective device in electrical service entrance   panel. This should be a 15 ampere circuit. Locate   shut-off switch at boiler. It must be turned off during   any maintenance. Connect 120 volt power supply to   control leads L1 (HOT) and L2.   Run a 14 gauge or heavier copper wire from boiler   to grounded connection in service panel or properly   driven and electrically grounded ground rod.   THERMOSTAT INSTALLATION   1. Thermostat should be installed on an inside wall about   four feet above the floor.   2. NEVER install thermostat on outside wall.   3. Do not install a thermostat where it will be affected   by drafts, hot or cold pipes, sunlight, lighting fixtures,   televisions, a fireplace, or a chimney.   4. Check thermostat operation by raising and lowering   thermostat setting as required to start and stop the   burners.   5. Instructions for the final adjustment of the thermostat   are packaged with the thermostat (adjusting heating   anticipator, calibration, etc.)   Set heat anticipator at .2 amps. 24 volt thermostat   connects to aquastat terminals T and TV.   15   11 - WIRING DIAGRAMS   Figure 12 - Integrated High Limit Electronic Ignition Control (240008781)   ! WARNING   Modification, substitution or elimination of factory   equipped, supplied or specified components may   result in personal injury or loss of life.   I Inducer is not an option.   16   11 - WIRING DIAGRAMS   Figure 13 - Integrated High Limit Electronic Ignition Control (240008781)   17   11 - WIRING DIAGRAMS   Figure 14 - Integrated High Limit Electronic Ignition Control (240008781)   18   12 -GENERAL INSTRUCTIONS   FILLING SYSTEM WITH WATER   NOTICE   Never run water in a hot empty boiler.   • Close air vents on all radiation units. Open valves to   these units.   • Verify boiler and expansion tank drain valves are closed.   • Air bleed screw on tank drain fitting should be closed.   • Open valve in line from boiler to expansion tank. Open   water inlet to your boiler and leave it open. Start with   lowest radiation unit. Open air vent on this unit. When   all air has escaped and water starts to flow from vent,   close it.   • Go to next radiation unit, and repeat this process.   Repeat until you have covered every radiation units in   the system (ending up at highest unit in system).   • If your units have automatic vents, manual venting is   unnecessary but it will speed up the proper filling of   your system.   • If your system is closed expansion tank system, you   may leave it open to refill system automatically as   needed.   • Check temperature pressure gauge. Not position of hand   indicating pressure. This should be between 10 and 15   psi. Any lowering of this movable hand below 10 psi.   Will indicate loss of water due to leakage. Automatic   fill valve should compensate for this. Instructions are   packaged with the valve.   19   13 - LIGHTING INSTRUCTIONS   5. Remove lower front panel.   ! WARNING   6. Rotate the gas control knob clockwise   “OFF”.   to   If you do not follow these instructions   exactly, a fire or explosion may result   causing property damage, personal injury   or loss of life.   • This appliance is equipped with an ignition device   which automatically lights burner. Do NOT try to   light this burner by hand.   Figure 15 - Automatic Gas Valve   WIRING   PRESSURE REGULATOR ADJUSTMENT   (UNDER CAP SCREW)   TERMINALS (2)   OUTLET   PRESSURE   TAP   INLET   PRESSURE   TAP   GROUND   TERMINALS   (2)   • Before operating smell all around appliance area   for gas. Be sure to smell next to floor because   some gas is heavier than air and will settle to the   floor.   OUTLET   INLET   ON   PILOT   OFF   OUTLET   •Use only your hand to turn the gas shutoff   valve. Never use tools. If valve will not turn   by hand, do not try to repair it, call a qualified   service technician. Force or attempted repair may   result in fire or explosion.   PILOT ADJUSTMENT   (UNDER CAP SCREW)   GAS CONTROL KNOB   7. Wait five (5) minutes to clear out any gas. Then   smell for gas, including near the floor. If you smell   gas, STOP! Immediately call your gas supplier from a   neighbor’s phone. Follow the gas supplier’s instructions.   If you don’t smell gas, go to next step.   •Do not use this appliance if any part has   been under water. Immediately call a qualified   service technician to inspect appliance and to   replace any part of control system and any gas   control which has been under water.   8. Rotate gas control knob counterclockwise   “ON”.   to   LIGHTING PROCEDURE FOR BOILER WITH   INTERMITTENT PILOT SYSTEM   9. Replace lower front panel.   10. Turn on all electric power to the appliance.   11. Set thermostat to desired setting.   For Your Safety, Read Before Operating!!   A. This appliance is equipped with an ignition device   which automatically lights the pilot. Do not try to light   appliance by hand.   12. If the appliance will not operate, follow the   instructions “To Turn Off Gas To Appliance” and call   your service technician or gas supplier.   ! CAUTION   TO TURN OFF GAS TO APPLIANCE   WHAT TO DO IF YOU SMELL GAS   1. Set the thermostat to lowest setting.   • Do not try to light any appliance.   2. Turn off all electric power to the appliance if   service is to be performed.   • Do not touch any electrical switches; do not use   any phone in your building.   3. Push in gas control knob slightly and turn   • Immediately call your gas supplier from a   neighbor’s phone. Follow the gas supplier’s   instructions.   clockwise   to “OFF” Do not force.   • If you cannot reach your gas supplier, call the fire   department.   1. STOP! Read the safety information above.   2. Set the thermostat to lowest setting.   3. Turn off all electric power to the appliance.   4. This appliance is equipped with an ignition device   which automatically lights the pilot. Do not try to   light the pilot by hand.   20   14 - OPERATING YOUR BOILER   Figure 16 - Pilot Flame   AUTOMATIC GAS VALVE   Automatic Gas Valve opens or closes according to   heat requirements of thermostat and temperature   limit control. It closes if pilot goes out. Each   individual control must be operating correctly before   any gas can pass to burners. Any one control can   hold gas supply from burner regardless of demand of   any other control.   SAFETY PILOT   Safety Pilot prevents flow of gas to burner if pilot   goes out, or will not ignite.   GAS VALVE SAFETY SHUTDOWN TEST   Ignition system safety shutoff device must be tested after   placing boiler in operation.   RELIGHT   Electric and gas shall be off for 5 minutes before   relighting.   MAIN BURNER(S)   • Main burners do not require primary air adjustment and   are not equipped with primary air shutters.   THERMOSTAT   • Main burner flames form sharp blue inner cones in softer   blue outer mantel, with no yellow.   Keep it set at desired room temperature. If windows   are to be opened or heat is not needed, move   thermostat pointer to lower setting.   • Puffs of air from blowing on flame or stamping on floor   will cause flames to turn orange momentarily. This is   not unusual. Remain still when observing main burner   flames.   NOTICE   In event of failure of any component, system   will not operate or will go into safety lockout.   System is completely self-checking. On   every call for heat, each component must   be functioning properly to permit operation.   Safety lockout system has to be reset by   turning thermostat to lowest setting for one   minute, then back to normal setting.   • If flame appearance is not correct, check main burner   orifices, burner throat and flame ports for dust and   lint obstruction. It may be necessary to remove rollout   shield to observe main burner flames. Replace rollout   shield after observation. Refer to Figure 17.   Figure 17 - Burner   ADJUST PILOT BURNER   Pilot flame should surround 3/8” to 1/2” of the pilot   sensor. See Figure 16. If flame needs adjusting, do it   as follows:   1. Remove screw cover over pilot adjusting screw.   2. Insert small screwdriver and adjust flame as needed.   Turn screw counterclockwise to increase flame, clockwise   to decrease.   ADJUST LIMIT CONTROLS   3. Replace screw cover over pilot adjusting screw.   Instructions for each control are included with   controls. Settings can be changed. Refer to   Appendix A page 27 for information.   21   14 - OPERATING YOUR BOILER   CHECK THERMOSTAT OPERATION   A. When set above temperature indicated on   thermostat, boiler should ignite.   B. Verify thermostat turns boiler off when room   temperature reaches selected setting and starts   boiler operating when room temperature falls a   few degrees.   C. After setting limit control to limit setting, check to   see if it shuts off gas supply to burners. Turn your   thermostat up to call for heat and let boiler run   until temperature of water reaches limit setting.   Gas valve should shut off and circulator running   until thermostat is satisfied, or water cools enough   to restart burners through limit control.   D. Set thermostat for desired temperature. Conditions   in your home and location of thermostat will govern   this setting.   22   15 - MAINTAINING YOUR BOILER   BURNERS   CLEANING YOUR BOILER AND BURNERS   Beginning of heating season visually check pilot and main   burner flames. See Figure 16.   Flue passages between sections should be examined yearly   and cleaned if necessary.   To clean:   SAFETY RELIEF VALVE   • Remove burners, pilot, and vent pipe.   Refer to page 7 for important information. To test safety   relief valve refer to valve manufacturer’s instructions   packaged with relief valve. Call Technical Support if   • Remove top and front jacket panels.   • Remove two screws attaching intermediate front panel   to left and right side jacket panels.   manufacturer’s instruction are not located.   • Remove draft diverter and intermediate front panel   together.   EXPANSION TANK   • Carefully remove cerafelt gasket strips.   Tank may become waterlogged, or may receive excess   of air. Frequent automatic opening of safety relief   valve indicates water logging. High boiler temperature   accompanied by unusually low radiation unit temperature   (and “knocking”) indicates excess air in tank.   • Clean passageways between sections with flexible   handle wire brush. Remove dirt from bottom of boiler   and from between sections by vacuuming.   • Verify all flame ports in burners are open and clear.   Shake out or blow out all loose dirt in burners.   To correct:   1. Close valve between boiler and tank. Drain tank until   • Reseal seams between adjacent sections as necessary   with 400° F RTV silicone sealant.   empty.   2. Check all tank plugs and fittings. Tighten as necessary.   • Reassemble all parts.   3. Open valve between boiler and tank. Water will rise to   normal height in tank if you have automatic fill valve   (otherwise, manually refill system).   • Verify tightness of pilot connections and condition of   burner flames after reassembly. See Figures 16 and 17,   pages 21.   • Verify vent pipe connections to chimney are secure and   no obstructions are present.   BOILER FLUE PASSAGES   Recommend following checked annually by qualified service   agent.   HOUSEKEEPING   • flue passages   • Keep boiler area clear and free from combustible   materials, gasoline and other flammable vapors and   liquids.   • burner adjustment   • operation of controls   • Keep boiler area clear of debris and other materials   obstructing flow of combustion and ventilation air.   Before start of each season (or whenever system has been   shut down for some time) recheck whole system for leaks   and recheck boiler and vent pipe for leaks. Replace or patch   any boiler seals that are faulty.   VENT PIPE   Venting and piping should be checked at least once a   season. If vent piping shows any sign of leaking, replace   immediately.   WATER SYSTEM   If system is to remain out of service during freezing weath-   er, always drain it completely (water left in to freeze will   crack pipes and/or boiler).   23   16 - SERVICE HINTS   EQUIPMENT AND OPTIONAL ACCESSORIES - WHAT THEY DO   ! CAUTION   WHAT TO DO IF YOU SMELL GAS   • Do not try to light any appliance.   • Do not touch any electrical switch; do not use any   phone in your building.   • Immediately call your gas supplier from a neighbor’s   phone. Follow the gas supplier’s instructions.   • If you cannot reach your gas supplier, call the fire   department.   IF YOUR SYSTEM IS NOT HEATING OR NOT GIVING ENOUGH HEAT . . .   You may avoid inconvenience and service calls by checking these points before you call for service.   Possible Cause   What to do   Thermostat is not set correctly Reset thermostat above room temperature   Burner is not operating properlyCheck flame. If it is yellow, burner is not getting enough air.   Or, if flame is blue and noisy and seems to lift off burner,   burner is getting too much air. Contact your service technician.   No electric power to boiler   Check over current protection. Verify electric power supply circuit is   “ON”.   Controls out of adjustment   Radiators not heating   Reset according to instructions.   Open radiator vents to expel air. Check flow control valve (if   used). It may be in closed position.   Circulating pump not running Check over current protection. Check relay operation.   Poor electrical contact   Rollout switch blown   Check all control terminals and wire joints.   Have your service agent check heat exchanged for blockage.   Replace rollout switch with exact replacement.   Blocked vent blown   Have your service agent check venting system and chimney   for blockage, or down draft condition. Reset blocked vent.   Vent damper not operating   Consult troubleshooting guide in Effikal manual, packaged with   vent damper.   IF BURNER IS NOISY . . .   Possible Cause   What to do   Gas input amount is incorrect Contact your service agent.   RELIEF VALVE LEAKING . . .   Possible Cause   Dirt on seat   What to do   Open valve manually. Allow water to run and clear valve seat.   Water logged expansion tank Drain tank, see instructions.   HAVE YOUR SERVICE AGENT CHECK ANY PROBLEM YOU ARE UNABLE TO CORRECT.   24   17 - EQUIPMENT AND OPTIONAL ACCESSORIES   AUTOMATIC FILL VALVE   EXPANSION TANK   Expanding water flows into expansion tank. Tank should   be correct size. Tank is filled with air. As water expands it   compresses air in the tank to form air pressure cushion.   This “spring-like” cushion serves to maintain correct   operating water pressure regardless of water temperature.   This assures “full measure” of water, even in highest   radiation unit of system. It also prevents blowing off of   safety relief valve. Air in tank in beginning (with system   filled with cold water) is sufficient for proper operation.   Tank also serves as trap for excess air in system. Air   would cause gurgling in pipes and in efficient circulation in   radiators if left in system.   For a safe, efficient operation, hot water system must be   completely filled with water. Adding new water, when   needed can be done manually (by use of hand valve in   water supply line). Requires regular attention to system’s   needs. Automatic fill valve accomplishes this without atten-   tion. Install in supply line on hot water boilers only. Valve   operates through water pressure differentials. It does not   require electrical connection.   DRAIN VALVE   Manual valve provides means of draining all water from   boiler and system. It is often installed in 3/4” tapping at   bottom of end boiler section. Or it can be installed in tee   where return line enters boiler.   It is possible for tank to become “waterlogged” (filled with   water). It can also become overfilled with air. This can hap-   pen after filling system with new water. Fittings provided on   tank and in line to tank are for bleeding off excess water or   air.   WATER TEMPERATURE CONTROL   Water temperature limit control in relay is adjustable   When installing this tank, it is important:   and may be set as necessary. It may be set as low as   104°F (40°C), or as high as 220°F (104°C). This depends   on type and amount of radiation involved and weather   conditions.   1. Tank be higher than boiler top.   2. Pipe to tank continuously rises up to tank (so air   can “bubble” up to it).   DIAPHRAGM TYPE EXPANSION TANK   CIRCULATING PUMP   Diaphragm type expansion tank takes place of conventional   expansion tank. Carefully read instructions packed with   your tank assembly.   Every forced hot-water system requires circulating pump.   Separate pump or zone valve is required for each zone,   if you have a two or more zone system. Pump must have   capacity to provide circulation required by your system.   Pump is connected into main just ahead of boiler. It is also   wired to electrical system.   Tank comes with 10-12 pounds per square inch air charge.   This is the same as pressure produced in system by   automatic fill valve. When system is first filled, tank will   contain little or no water.   As water is heated its pressure increases. It expands into   tank, compressing air in tank. Compressed air cushion   permits water in system to expand as temperature   changes. Diaphragm type tank can be mounted on air   purger fitting or at any convenient place in supply or return   line.   VENT DAMPER   This product is automatic, motorized stack damper   developed to increase efficiency of heating system by   reducing standby losses from heating apparatus and   conditioned air space. Damper closes chimney vent   when burner is off and fully opens it when combustion is   required.   AIR ELIMINATING FITTING (AIR PURGER)   Air purger is used to remove excess air from system. It   is installed in supply line. It will eliminate air from water   before it reaches radiators and bleed off this air.   MAIN AIR VENT FOR DOWN FLOW SYSTEMS OR   DIAPHRAGM TYPE EXPANSION TANK   Before system is filled with water, there is air in pipes and   radiation units. Some of it will be trapped as system is   filled . It is possible to eliminate most of this air through   air vent on radiation units. Main air vent will speed and   simplify this. Install on highest point in supply main when   all radiation is below top of boiler.   25   17 - EQUIPMENT AND OPTIONAL ACCESSORIES   BLOCKED VENT SAFETY SWITCH   ROLLOUT SWITCH   (FLAME ROLLOUT SAFETY SHUTOFF)   (BLOCKED VENT SAFETY SHUTOFF)   Rollout switch is temperature-sensitive fuse link device.   Located on boiler base just outside fire box. In event of   heat exchanger flueway blockage causing flame to roll   out of fire box, fuse does not change in appearance when   blown.   Blocked vent safety switch is manual reset disc thermostat   with fixed setpoint (340°F (171°C)), and normally closed   contacts. It is located at relief opening of integral draft diverter.   In event of chimney or venting system blockage causing   products of combustion to spill out of relief opening, blocked   vent disc heats up and blocked vent contacts open, shutting   down flow of gas to main burners by removing power to gas   valve.   If rollout switch blows, it must be replaced with exact   replacement. Check heat exchanger flueways for blockage   when restoring system to operating condition. DO NOT   operate system without rollout switch.   In event blocked vent contacts open, reset button on back   of switch will pop up. Blocked vent safety switch must be   reset manually, after switch has cooled off, by pushing   reset button down. Check venting system and chimney for   blockage when restoring system to operating condition. DO   NOT operate boiler without Blocked vent safety switch.   26   APPENDIX A - CONTROL MODULE   A.1 Installation Environment Considerations A.3 Adjusting Settings   To discourage unauthorized changing of settings, procedure   to enter adjustment mode is required.   ! WARNING   If you do not follow these instructions   exactly, a fire or explosion may result   causing property damage, personal injury   or loss of life.   To enter adjustment mode, press UP, DOWN, and I buttons   simultaneously for three seconds. Press and release I   button until parameter requiring adjustment is displayed.   See Figure 12, page 16.   о “SP_” Setpoint (180 °F default setting; adjustable   •Do not use this appliance if any part has   been under water. Immediately call a qualified   service technician to inspect appliance and to   replace any part of control system and any gas   control which has been under water.   between 130 and 220 °F)   о “Df_” Setpoint Differential (15 °F default setting;   adjustable between 10 and 30 °F)   о “°F_” Degrees Fahrenheit   • Do not allow water to drip on controls. Prevent   condensation by allowing air circulation around   module and gas control.   Press UP or DOWN button until parameter has reached   desired value. After 60 seconds without any button inputs,   control automatically returns to READ mode.   • Do not use corrosive chemicals around or on   module or gas control.   A.4 Display   In RUN mode, status items and parameters are viewable.   • Controls can be damaged by excessively high   temperatures. Verify adequate air circulation around   control is maintained when installing boiler.   Example, to display setpoint, control flashs “sp” (setpoint)   followed by temperature (i.e., 135), followed by °F or °C.   To read settings, press and release I key to find parameter   of interest.   A.2 Electrical Connections   Example, press and release I until setpoint (sp) is   displayed, followed by three-digit number, i.e., 190,   followed by °F or °C. Press I button again will display (S1T)   Sensor 1 Temperature followed by three-digit number and   corresponding degree designator.   Connect Module Connectors Figure 14, Page 18   • L1& L2 leads inside J-box using wire nuts. Secure J-   box cover.   • Circulator harness to circulator. Harness comes   plugged into module with Molex® plug.   See Display Readout.   • Thermostat connection to yellow wires marked TT   using wire nuts.   Figure 18 - Display Readout   • Ensure remaining Molex® plug connectors have not   worked loose during transit.   • Check sensing bulb is fully inserted in well and is not   loose.   • Refer to enclosed addendum for wiring instructions   when using indirect hot water heater.   27   APPENDIX A - CONTROL MODULE   module proceeds to start burner (see state codes list)   A.5 Operation   and heats water in boiler until setpoint temperature is   achieved or thermostat is satisfied. .   Module continuously monitors boiler water temperature and   fires or shuts off burner based on this temperature data.   3. Burner is de-activated, ignition module completes heat-   ing cycle, returns to idle and waits for temperature to   drop again.   1. When “Call for Heat” occurs, control enables circulator   and monitors boiler water temperature to determine   whether thermostat can be satisfied without firing   burners.   4. Circulator is turned on throughout “Call for Heat.”   2. Control determines burner operation is required,   Table 6 - Operation State Codes   State   Code   Definition   Explanation   Number   Idle   Standby - no call for heat   1 Heat request present. Boiler temperature sufficiently high to run circulator   pump only.   Circulator   4 6 Pre-purge   Spark   System is purging before ignition trial; includes Pilot Valve circuit diagnostics.   System sparking. Flame is not present up to 13 seconds   Flame signal is being established. Variation in signal is allowed during this   state, flame must be stable at end of period   7 Flame stabilization   8 9 Running   System is running. Flame signal must be present.   System is purging at end of call for heat   Post-Purge   Successful ignition was not detected, and delay is called before retry.   Retry Recycle Delay   10   Flame signal was lost during state 7 or 8, and delay is called before retry (32   second delay)   13   14   15   Soft lock-out   Hard lock-out   Soft lockout duration is one hour, may override with manual reset.   Manual reset is required for hard lockout   Wait for limit to close   Possible thermostat call for heat; limit switch is open.   Flame signal sensed before trial for ignition. Appropriate alarm is sent.   OR   16   17   Flame out of sequence   Flame signal sensed out of sequence during post purge. Appropriate alarm is s   ent.   OR   Flame signal present when not expected. Appropriate alarm is sent.   Pilot valve circuitry diagnostics during pre-purge.   Pilot valve diagnostics   Self check performed at start up, again at beginning of heat cycle, and during   “Wait for Recovery “ State.   Current leakage detection   Self check performed at start up, again at beginning of heat cycle, and during   “Wait for Recovery “ State   Wait for recovery   Control has signaled damper/pressure switch   to close, and is waiting for completion.   If damper/pressure switch does not close within 60 seconds, control goes to   State 20.   18   19   Wait for damper to open   Damper is closed and control waits for damper to open.   Checked at beginning of heat cycle before opening damper.   If damper does not open in 60 seconds, control goes to State 21.   Wait for damper to close   Wait for damper to open   (Failed close)   Damper has not opened (end swich not closed) at beginning of heat cycle.   Alarm message is sent, control is NOT in lockout.   20   21   Wait for damper to close   (Failed open)   Damper has not closed despite actuator de-energized.   Alarm message is sent, control is NOT in lockout.   28   APPENDIX A - CONTROL MODULE   A.6 Boiler High Limit Temperature Controller   A.7 Troubleshooting   • When water temperature reaches setpoint, controller   ends heating cycle.   • Following service procedures are provided as general   guide.   • When water temperature drops below setpoint minus   differential, controller restarts heat cycle to re-heat   boiler water.   • On lockout and retry models, meter readings between   gas control and ignition module must be taken within   trial for ignition period. Once ignition module shuts   off, lockout models must be reset through key buttons   and display. On retry models, wait for retry or reset at   thermostat.   • If water temperature exceeds maximum allowed   temperature (220°F or 104°C), controller enters manual   reset lockout state.   • Check for correct installation and wiring before replacing   any component.   • For models having reset capability, press any onboard   button or cycle power to reset.   • Control module cannot be repaired. If it malfunctions, it   must be replaced.   Figure 20 - Basic Control Algorithm Example   • Use only qualified service agent to service ignition   systems.   1. Perform checkout as first step in troubleshooting.   Check troubleshooting guide to pinpoint cause of problem.   See Table 7 , page 30.   2. If troubleshooting indicates ignition problem, see   Ignition System Checks to isolate and correct the   problem.   3. Perform checkout procedure following troubleshooting   guide again to verify system is operating normally.   A.8 Troubleshooting Error Codes   Integrated boiler control uses advanced diagnostic   capability to assist in troubleshooting error conditions.   Table 6 page 28 shows codes that could arise on integrated   display during fault.   Suggestions are provided in Table 6 for servicing these   potential errors.   29   APPENDIX A - CONTROL MODULE   Table 7 - Troubleshooting Error Codes   Error   Code   Definition   Consequence   Number   4 6 Flame current too low. Check for flame.   Non critical alarm   Soft lockout   Flame sensed out of normal sequence (before opening or after closing gas valve).   Gas valve relays welded. Five consecutive soft lockouts.   18   23   Hard lockout   Soft lockout   Flame sensed during prepurge ( before gas valve signaled opened).   Sensor 1 error. Temperature sensor in well is not reading correctly.   Verify it is connected to board. Replace if necessary.   32   Wait for recovery   55   56   57   58   59   Atmospheric damper end switch failed to close (end switch contacts stuck open).   Atmospheric damper end switch failed to open (end switch contacts stuck close).   Igniter flame rod shorted to burner ground   Wait for recovery   Wait for recovery   Wait for recovery   Wait for recovery   Wait for recovery   Igniter flame rod shorted to burner ground. Repair or replace igniter.   Line Voltage error - voltage out of specification high or low (15-37V (44-66Hz))   Applies only to thermostats having on-board transformer.   Polarity is wrong in this case.   60   Wait for recovery   Thermostat input higher than threshold.   Line voltage unstable - possibly too may heavy loads switching on and off causing   erratic supply voltage.   61   62   Wait for recovery   Soft lockout   Soft lockout: maximum number of retries exceeded.   Soft lockout is reset after one hour if alarm reason disappears.   Soft lockout: maximum number of recycles exceeded.   63   64   Soft lockout   Soft lockout   Soft Lockout - electronics failure. On-board self diagnostics detected error.   Over temperature error. Sensor measured temperature in excess of maximum   allowable limit.   65   Soft lockout   Note: Soft lockout time is 1 hour or manual reset. Hard lockout requires manual reset.   STEP 2:   A.9 Intermittent Pilot   Verify ignition system grounding. Nuisance shutdowns are   often caused poor or erratic grounding.   Ignition System Checks   Common ground is required for module and pilot burner/   igniter sensor.   STEP 1: Check ignition cable.   • Verify ignition cable does not touch metal surfaces.   — Check for good metal-to-metal contact between   pilot burner bracket and the main burner.   • Verify only factory supplied Ignition cable (or approved   replacement) is used.   — Check ground lead from GND (BURNER) terminal   on module to pilot burner. Verify connections are   clean and tight. If wire is damaged or deteriorated,   replace with No. 14-18 gauge, moisture-resistant,   thermoplastic insulated wire with 105°C [221°F]   minimum rating.   • Verify connections to ignition module and igniter or   igniter-sensor are clean and tight.   • Verify ignition cable provides good electrical continuity.   — Check ceramic flame rod insulator for cracks or   evidence of exposure to extreme heat, which can   permit leakage to ground. Replace pilot burner/igniter   sensor and provide shield if necessary.   30   APPENDIX A - CONTROL MODULE   — If flame rod or bracket is bent out of position, restore   • Recheck ignition sequence as follows.   to correct position.   — Reconnect main valve wire.   STEP 3: Check spark ignition circuit.   Disconnect ignition cable at SPARK terminal on module.   — Adjust thermostat above room temperature.   — Verify ignition sequence at burner.   ! WARNING   — If spark does not stop after pilot lights, replace   module.   Electrical shock hazard. Ignition circuit generates   over 10,000 volts. Turn OFF electrical power   supply at service panel before making electrical   connections. Failure to do so could result in death   or serious injury.   — If main burner does not light or if main burner lights   and system locks out, check module, ground wire and   gas control as described in troubleshooting table. See   Table 7, Page 30.   Figure 19 - Troubleshooting Pilot Flame   Energize module and listen for audible sparking noise.   When operating normally, there should be buzzing noise   turns on and off twice per second for duration of 1–7   seconds, depending on model.   STEP 4: Verify pilot and main burner light-off.   • Initiate call for heat. Turn thermostat above room   temperature. Ignition sequence may be delayed by   thermal purge until boiler water temperature is below   140°F (60°C)   • Watch pilot burner during ignition sequence.   — Verify ignition spark continues after pilot is lit.   — Verify pilot lights and spark stops, verify main   burner does not light.   • If so, ensure adequate flame current as follows.   — Turn off boiler at circuit breaker or fuse box.   — Clean flame rod with emery cloth.   — Verify electrical connections are clean and tight.   Replace damaged wire..   — Check for cracked ceramic insulator, which can   cause short to ground, and replace igniter-sensor if   necessary.   — At gas valve, disconnect main valve wire from MV   terminal.   — Turn on power and set thermostat to call for heat. Pilot   should light, main burner will remain off because main   valve actuator is disconnected.   — Check pilot flame. Verify it is blue, steady and   envelops 3/8 to 1/2 in. [10 to 13 mm] of flame rod.   See Figure 19 for possible flame problems and causes.   — If necessary, adjust pilot flame by turning pilot   adjustment screw on gas control clockwise to decrease   or counterclockwise to increase pilot flame. Following   adjustment, always replace pilot adjustment cover   screw and tighten firmly to assure proper gas control   operation. Figure 16, page 20.   — Set temperature below room set-point to end call for   heat.   Correct Pilot Flame: 3/8 to 1/2 inch in flame.   See Figure 16, Page 21.   31   PRODUCT LITERATURE   Lennox Industries Inc.   Dallas, Texas   Manufactured by:   ECR International, Inc.   2201 Dwyer Avenue, Utica NY 13501   |