| VR8104, VR8204, and VR8304   Intermittent Pilot Combination   Gas Controls   INSTALLATION INSTRUCTIONS   These gas controls are available in a range of valve   capacities, see Table 1. (Table 2 provides gas capacity   conversion factors.) The suffix letter indicates   APPLICATION   These intermittent pilot gas controls are used in gas-fired   appliances with up to 415 ft3/hr capacity at 1 in. wc   pressure drop (8.5 m3/hr at 0.25 kPa) on natural gas.   They include safety shutoff, a manual valve, two   automatic operators, a pressure regulator and a pilot   adjustment.   temperature range and regulator type, see Table 3.   For CE-approved models, the relevant sections of these   instructions and Table 4 are applicable.   a Table 1. Valve Capacity   AGA Certified Maximum   Regulation for   AGA Certified Capacity for   AGA Certified Minimum   Regulation for Natural Gas   Size   Inlet-Outlet   Natural Gas   Natural Gas   3 3 3 3 3 3 Model   VR8104   (in.)   ft /hr   m /hr   ft /hr   m /hr   ft /hr   m /hr   d e f 1/2 x 1/2   85   2.3   4.2   6.8   7.6   8.5   0.4   0.6   0.8   120   200   340   370   415   3.4   5.7   9.6   10   20   30   VR8204   150   240   270   300   3 b,c   b,c   b,c   VR8304   VR8304   VR8304   1/2 x 3/4   3/4 x 3/4   1.05   11.8   a 3 Capacity based on 1000 Btu/ft , 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m , 0.64 sp gr natural gas   at 0.25 kPa pressure drop).   b c d e f Capacity is reduced by 5 percent when using an outlet screen.   Valves are guaranteed at only 77 percent of the rating.   Minimum regulation for LP gas is 15,000 Btuh.   Minimum regulation for LP gas is 40,000 Btuh.   Minimum regulation for LP gas is 50,000 Btuh.   Table 2. Gas Capacity Conversion Factor.   CE-Only Models   Multiply Listed   Capacity By   These gas controls are used in appliances up to 121kW   or 415 kBTUH on natural gas and approved on EN126,   which consists of one automatic safety shutoff valve,   Class B or C, one servo-operated shutoff valve, Class D,   pressure governor, Class C, manually-operated valve,   with or without pilot outlet. Only the A, H and U models   are available CE-approved.   Gas   Specific Gravity   Manufactured   Mixed   0.60   0.70   1.53   0.516   0.765   1.62   Propane   Table 4 shows the additional specifications for the   CE-only models.   ® U.S. Registered Trademark   Copyright © 2000 Honeywell Inc. • All Rights Reserved   69- 1225- 4   VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS   Table 6. Flange Adapter Part Numbers.   SPECIFICATIONS   a,b   Part Number   Inlet/Outlet   Body Pattern: Straight through; see Table 1 for inlet and   outlet size.   Pipe Size   (in. NPT)   Flange Without Hex   With Hex   Wrench   Type   Straight   Elbow   Wrench   393690-1   393690-2   393690-6   393690-3   393690-4   393690-5   3/8   393690-11   393690-12   393690-16   393690-13   393690-14   393690-15   Electrical Ratings:   Voltage and Frequency: 24 Vac, 60 Hz.   Current Draw: 0.5A with both operators energized.   3/8   1/2   1/2   3/4   3/4   Straight   Elbow   Capacity: See Table 1.   Straight   Elbow   Conversion: Use conversion factors in Table 2 to con-   vert capacities for other gases.   a Flange kits include one flange, one O-ring and four   mounting screws.   Regulation Range: See Table 1.   b Do not use flanges on control models with 3/4 in. inlet   and 3/4 in. outlet. On models with 1/2 in. inlet and   3/4 in. outlet, use flanges only on the 1/2 in. inlet side.   Natural-LP Gas Conversion Kits: See Table 5.   Table 5. Natural-LP Gas Conversion Kits.   Heavy demands are made on the controls when   intermittent pilot systems are used on central heating   equipment in barns, greenhouses, and commercial   properties and on heating appliances such as   commercial cookers, agricultural equipment, industrial   heating equipment and pool heaters.   Model No.   Suffix Letter Natural Gas to LP   Kit to Convert   Kit to Convert LP   to Natural Gas   H, K, M   P 393691   394588   Not field   convertible.   Not field   convertible.   Q R 396021   396025   Special steps may be required to prevent nuisance   shutdowns and control failure due to frequent cycling,   severe environmental conditions related to moisture,   corrosive chemicals, dust or excessive heat. These   applications require Honeywell Home and Building   Control Engineering review; contact your Honeywell   Sales Representative for assistance.   Not required,   convertible valve.   Not required,   convertible valve.   Pipe Adapters:   Angle and straight adapters available for 3/8-, 1/2- and   3/4-in. pipe. See Table 6. Flange kits include one   flange with attached O-ring, four mounting screws, a   9/64 in. hex wrench and instructions.   Review the following conditions that can apply to your   specific installation and follow the precautions   suggested.   Approvals:   American Gas Association Design Certificate: L2025006.   Canadian Gas Association Design Certificate: L2025006.   Australian Gas Association Design Certificate: 4214.   Approved for Delta C applications.   Frequent Cycling   European Community (CE) Certificate: Pending.   This control is designed for use on appliances that   typically cycle three to four times an hour only during the   heating season. In year-around applications with greater   cycling rates, the control can wear out more quickly.   Perform a monthly checkout.   PLANNING THE INSTALLATION   WARNING   Can cause property damage, severe injury,   Water or Steam Cleaning   Fire or Explosion Hazard.   If a control gets wet, replace it. If the appliance is likely to   be cleaned with water or steam, protect (cover) the   control and wiring from water or steam flow. Mount the   control high enough above the bottom of the cabinet so it   does not get wet during normal cleaning procedures.   or death.   Follow these warnings exactly:   1. Plan the installation as outlined below.   2. Plan for frequent maintenance as described in   the Maintenance section.   High Humidity or Dripping Water   Dripping water can cause the control to fail. Never install   an appliance where water can drip on the control. In   addition, high ambient humidity can cause the control to   corrode and fail. If the appliance is in a humid   atmosphere, make sure air circulation around the control   is adequate to prevent condensation. Also, regularly   check out the system.   3 69-1225—4   VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS   Corrosive Chemicals   CAUTION   Can burn out valve coil terminals.   Never apply a jumper across (or short) the valve   coil terminals, even temporarily.   Corrosive chemicals can attack the control, eventually   causing a failure. If chemicals are used for routine   cleaning, avoid contact with the control. Where   chemicals are suspended in air, as in some industrial or   agricultural applications, protect the control with an   enclosure.   Equipment Damage.   Follow the appliance manufacturers instructions if   available; otherwise, use these instructions as a guide.   Dust or Grease Accumulation   Heavy accumulations of dust or grease can cause the   control to malfunction. Where dust or grease can be a   problem, provide covers for the control to limit   contamination.   IMPORTANT   These gas controls are shipped with protective   seals over the inlet and outlet tappings. Do not   remove the seals until ready to install adapters   or connect the piping.   Heat   Converting Gas Control from Natural Gas   to LP Gas (or LP Gas to Natural Gas)   Excessively high temperatures can damage the control.   Make sure the maximum ambient temperature at the   control does not exceed the rating of the control. If the   appliance operates at very high temperatures, use   insulation, shielding, and air circulation, as necessary, to   protect the control. Proper insulation or shielding should   be provided by the appliance manufacturer; verify proper   air circulation is maintained when the appliance is   installed.   WARNING   Fire Or Explosion Hazard.   Can cause property damage, severe injury   or death.   1. Do not attempt to convert step-opening models   (suffix letter P).   2. Always change the main and pilot burner   orifices when converting from natural to LP gas   or from LP to natural gas. Carefully follow   appliance manufacturer specifications and   instructions to assure proper appliance   conversion.   3. Gas controls are factory-set for natural (and   manufactured) or LP gas. Do not attempt to   use a gas control set for natural   INSTALLATION   When Installing this Product...   1. Read these instructions carefully. Failure to follow   them could damage the product or cause a   hazardous condition.   2. Check the ratings given in the instructions and on   the product to make sure the product is suitable for   your application.   (manufactured) gas on LP gas, or a gas control   set for LP gas on natural (manufactured) gas.   3. Installer must be a trained, experienced service   technician.   Controls with standard, slow-opening, and two-stage   regulators (model numbers with suffix H, K, M, or Q) can   be converted from one gas to the other with a conversion   kit (ordered separately). See Table 4 for the correct   conversion kit.   4. After installation is complete, check out product   operation as provided in these instructions.   WARNING   Fire or Explosion Hazard.   Convertible Pressure Regulators   Can cause property damage, severe injury   or death.   Follow these warnings exactly:   Controls with suffix letter R are convertible pressure   regulator models. They can be converted from natural   gas to LP gas or from LP gas to natural gas without a   conversion kit.   1. Disconnect power supply before wiring to   prevent electrical shock or equipment damage.   2. To avoid dangerous accumulation of fuel gas,   turn off the gas supply at the appliance service   valve before starting installation, and perform   Gas Leak Test after installation is complete.   3. Do not bend pilot tubing at gas control or pilot   burner after compression fitting is tightened, or   gas leakage at the connection can result.   4. Always install a sediment trap in the gas   supply line to prevent contamination of the gas   control.   5. Do not force the gas control knob. Use only   your hand to turn the gas control knob. Never   use any tools. If the gas control knob will not   operate by hand, the gas control should be   replaced by a qualified service technician.   Force or attempted repair may result in fire or   explosion.   Before converting the control from one gas to another,   check the control label and the appliance manufacturer’s   rating plate to determine if the pressure regulator setting   (factory set) will meet the appliance manifold   requirements after conversion.   NOTE: Convertible pressure regulator models (suffix   letter R) do not have field-adjustable regulators.   If the factory pressure regulator setting meets the   appliance manifold requirement, convert the control as   follows:   1. Remove the pressure regulator cap, Fig. 1.   2. Invert the cap so that the letters appear that   represent the gas type appropriate for the   appliance. NAT for natural manufactured gas, LP   for liquid petroleum gas.   3. Replace the cap and tighten firmly.   69-1225—4   4 VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS   OR   OTHER SIDE   OF CAP   PRESSURE   REGULATOR   CAP   1 VALVE OUTLET   FLANGE   M11678   9/64 INCH HEX SCREWS (4)   Fig. 1. Top view of convertible   pressure regulator cap.   DO NOT OVERTIGHTEN SCREWS. TIGHTEN TO   25 INCH-POUNDS.   1 M9046   Fig. 2. Firmly fasten flange to valve, but   do not overtighten screws.   Install Adapters To Control   If adapters are being installed on the control, mount them   as follows:   Location   The combination gas control is mounted in the appliance   vestibule on the gas manifold. If this is a replacement   application, mount the gas control in the same location   as the old control.   Flanges   1. Choose the appropriate flange for your application.   2. Remove the seal over the gas control inlet or   outlet.   3. Make sure that the O-ring is fitted in the groove of   the flange. If the O-ring is not attached or is   missing, do not use the flange.   4. With the O-ring facing the control, align the screw   holes on the gas control with the holes in the   flange. Insert and tighten the screws provided with   the flange. See Fig. 2. Tighten the screws to 25   inch-pounds of torque to provide a gas-tight seal.   Locate the combination gas control where it cannot be   affected by steam cleaning, high humidity, or dripping   water, corrosive chemicals, dust or grease accumulation   or excessive heat. To assure proper operation, follow   these guidelines:   • • Locate gas control in a well-ventilated area.   Mount gas control high enough above cabinet bottom   to avoid exposure to flooding or splashing water.   Assure the ambient temperature does not exceed the   ambient temperature ratings for each component.   Cover gas control if appliance is cleaned with water,   steam, or chemicals or to avoid dust and grease   accumulation.   • • Bushings   1. Remove the seal over the control inlet or outlet.   2. Apply a moderate amount of good quality pipe   compound to the bushing, leaving two end threads   bare. On an LP installation, use compound that is   resistant to LP gas. Do not use Teflon tape.   • Avoid locating gas control where exposure to   corrosive chemical fumes or dripping water are likely.   3. Insert the bushing in the control and carefully   thread the pipe into the bushing until tight.   Install Piping to Control   All piping must comply with local codes and ordinances   or with the National Fuel Gas Code (ANSI Z223.1,   NFPA No. 54), whichever applies. Tubing installation   must comply with approved standards and practices.   Complete the instructions below for installing the piping,   installing the control, connecting the pilot gas tubing and   the wiring. Make sure the leak test you perform on the   control after completing the installation includes leak   testing the adapters and screws. If you use a wrench on   the valve after the flanges are installed, use the wrench   only on the flange, not on the control. See Fig. 5.   1. Use new, properly reamed pipe that is free from   chips. If tubing is used, make sure the ends are   square, deburred and clean. All tubing bends must   be smooth and without deformation.   2. Run pipe or tubing to the control. If tubing is used,   obtain a tube-to-pipe coupling to connect the   tubing to the control.   3. Install a sediment trap in the supply line to the   control. See Fig. 3.   5 69-1225—4   VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS   4. Apply a moderate amount of good quality pipe   compound (do not use Teflon tape) only to the   pipe, leaving two end threads bare. On LP   installations, use a compound resistant to LP gas.   See Fig. 4.   DROP   PIPED   GAS   SUPPLY   GAS   CONTROL   HORIZONTAL   5. Remove the seals over the control inlet and outlet if   RISER   necessary.   GAS   CONTROL   6. Connect the pipe to the control inlet and outlet. Use   a wrench on the square ends of the control. If a   flange is used, place the wrench on the flange   rather than on the gas control. Refer to Fig. 5   and 6.   PIPED   GAS   SUPPLY   3 IN.   (76 MM)   MINIMUM   2 DROP   Connect Pilot Gas Tubing   HORIZONTAL   3 IN.   1. Cut tubing to the desired length and bend as   necessary for routing to the pilot burner. Do not   make sharp bends or deform the tubing. Do not   bend the tubing at the gas control after the   compression nut is tightened, because this can   result in gas leakage at the connection.   2. Square off and remove burrs from the end of the   tubing.   (76 MM)   MINIMUM   TUBING   GAS   SUPPLY   1 2 GAS   CONTROL   RISER   3 IN.   (76 MM)   MINIMUM   3. Unscrew the brass compression fitting from the   pilot outlet (Fig. 6). Slip the fitting over the tubing   and slide out of the way. See Fig. 7.   2 ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.   1 2 NOTE: When replacing a control, cut off the old   compression fitting and replace with the   compression fitting provided on the combination   gas control. Never use the old compression   fitting because it may not provide a gas-tight   seal.   CAUTION: SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING   END CAP TO PREVENT GAS FROM FILLING THE WORK AREA. TEST   FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.   M3077   Fig. 3. Sediment trap installation.   4. Push the tubing into the pilot gas tapping on the   outlet end of the control until it bottoms. While   holding the tubing all the way in, slide the fitting   into place and engage the threads; then turn until   finger tight. Tighten one more turn with a wrench,   but do not overtighten.   5. Connect the other end of the tubing to the pilot   burner according to the pilot burner manufacturer’s   instructions.   Install Control   1. Mounted 0 to 90 degrees in any direction, including   vertically, from the upright position of the gas   control knob.   2. Mount so the gas flow is in the direction of the   arrow on the bottom of the control.   3. Thread the pipe the amount shown in Table 7 for   insertion into control or adapters. Do not thread   pipe too far. Valve distortion or malfunction can   result if the pipe is inserted too deeply.   TWO IMPERFECT   GAS CONTROL   THREADS   Table 7. NPT Pipe Thread Length (in.).   PIPE   Pipe   Size   Thread Pipe Maximum Depth Pipe can   this Amount   be Inserted into Control   THREAD PIPE THE AMOUNT   SHOWN IN TABLE FOR   INSERTION INTO GAS CONTROL   APPLY A MODERATE AMOUNT OF   PIPE COMPOUND TO PIPE ONLY   (LEAVE TWO END THREADS BARE).   3/8   9/16   3/8   1/2   3/4   3/4   1/2   3/4   M3075B   13/16   Fig. 4. Use moderate amount of pipe compound.   69-1225—4   6 VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS   WHEN FLANGE IS USED   WHEN FLANGE IS NOT USED   APPLY WRENCH   FROM TOP OR   BOTTOM OF GAS   CONTROL TO   APPLY WRENCH   TO FLANGE ONLY   EITHER SHADED AREA   M3079   Fig. 5. Proper use of wrench on gas control with and without flanges.   HI-LO   ADJUSTMENT SCREWS   (UNDER CAP)   PRESSURE REGULATOR   ADJUSTMENT   (UNDER CAP SCREW)   WIRING   TERMINALS (3)   REGULATOR   VENT COVER   OUTLET   PRESSURE   TAP   INLET   PRESSURE TAP   LO   HI   OUTLET   INLET   TWO-STAGE   PRESSURE   REGULATOR   MODEL   PILOT OUTLET   INLET   GAS   PILOT ADJUSTMENT   CONTROL   KNOB   (UNDER CAP SCREW)   M10968A   Fig. 6. Top view of gas control.   All wiring must comply with applicable electrical codes   and ordinances.   GAS CONTROL   TIGHTEN NUT ONE TURN   BEYOND FINGER TIGHT.   Disconnect power supply before making wiring   connections to prevent electrical shock or equipment   damage.   TO PILOT   BURNER   FITTING BREAKS OFF AND CLINCHES   TUBING AS NUT IS TIGHTENED.   1. Check the power supply rating on the gas control   and make sure it matches the available supply.   Install a transformer, thermostat and other controls   as required.   M3076A   Fig. 7. Always use new compression fitting.   2. Connect control circuit to the gas control terminals.   See Fig. 8.   Wiring   Follow the wiring instructions furnished by the appliance   manufacturer, if available, or use the general instructions   provided below. When these instructions differ from the   appliance manufacturer, follow the appliance   manufacturer instructions.   7 69-1225—4   VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS   Turn On Main Burner   S8600   Follow appliance manufacturer instructions or turn up   VENT   DAMPER   PLUG   thermostat to call for heat.   5 GND   TH-W   (OPT)   24V   24V   GND   (BURNER)   (OPT)   MV MV/PV PV   SENSE SPARK   Perform Gas Leak Test   3 5 WARNING   PV   Fire or Explosion Hazard.   Can cause property damage, severe injury   or death.   2 PV/MV   MV   4 Perform Gas Leak Test every time work is done   on a gas system.   THERMOSTAT   GAS CONTROL   TERMINALS   IMPORTANT   LIMIT   Do not spray soap and water solution on the   gas control. Do not use an excessive amount of   soap and water solution to perform the gas leak   test. These can damage the control.   CONTROLLER   Q345, Q346,   Q348, Q362, Q381   PILOT BURNER/   IGNITER-SENSOR   GROUND   L1 L2   (HOT)   PILOT GAS   SUPPLY   1 Gas Leak Test   1. Paint pipe connections upstream of the gas control   with rich soap and water solution. Bubbles indicate   a gas leak.   2. If a leak is detected, tighten the pipe connections.   3. Light the main burner. Stand clear of the main   burner while lighting to prevent injury caused from   hidden leaks that could cause flashback in the   appliance vestibule.   1 POWER SUPPLY. PROVIDE DISCONNECT MEANS   AND OVERLOAD PROTECTION AS REQUIRED.   2 3 4 ALTERNATE LIMIT CONTROLLER LOCATION.   MAXIMUM WIRE LENGTH 3 ft [.9 m].   CONTROLS IN 24V CIRCUIT MUST NOT BE IN   GROUND LEG TO TRANSFORMER.   5 FOR MODULE WITH TH-W TERMINAL AND VENT DAMPER   PLUG, CONNECT THERMOSTAT TO TH-W. LEAVE   24V OPEN. DO NOT REMOVE VENT DAMPER PLUG.   4. With the main burner in operation, paint the pipe   joints (including adapters) and the control inlet and   outlet with rich soap and water solution.   M9056   5. If another leak is detected, tighten the adapter   screws, joints, and pipe connections.   6. Replace the part if a leak cannot be stopped.   Fig. 8. Typical wiring connections for 24 volt control   in intermittent ignition system with S8600.   Check and Adjust Pilot Flame   STARTUP AND CHECKOUT   The pilot flame should envelop 3/8 to 1/2 in. (10 to 13   mm) of the tip of the igniter-sensor. See Fig. 9. If the pilot   flame is small or lazy, the inlet gas pressure may be too   low, or the pilot orifice may be partially clogged. Check   and repair as necessary. If the pilot flame is hard and   noisy, the inlet gas pressure may be too high. The gas   control has a pilot adjustment mechanism to reduce the   pilot flow if necessary. If pilot adjustment is necessary,   proceed as follows:   WARNING   Fire or Explosion Hazard.   Can cause property damage, severe injury   or death.   1. Do not force the gas control knob on the   appliance. Use only your hand to turn the gas   control knob. Never use any tools.   2. If the knob does not operate by hand, the   control should be replaced by a qualified   service technician.   1. Remove pilot adjustment cover screw. See Fig. 6.   2. The pilot adjustment is shipped at the full pilot gas   flow rate. Turn the inner adjustment screw   clockwise   if the inlet pressure is too high.   Turn the inner adjustment screw clockwise   Gas Control Knob Settings   to decrease or counterclockwise   pilot flame.   to increase   Gas control knob settings are as follows:   OFF: Prevents pilot and main gas flow through the   control.   3. Replace the cover screw after the adjustment to   prevent gas leakage.   ON: Permits gas to flow into the control body. Under   control of the thermostat and intermittent pilot module,   gas can flow to the pilot and main burners.   PROPER FLAME   ADJUSTMENT   3/8 TO 1/2 INCH   (10 TO 13 mm)   NOTE: Controls are shipped with the gas control knob   in the ON position.   IGNITER-   SENSOR   Turn On System   Rotate the gas control knob counterclockwise   ON.   to   M3080A   Fig. 9. Proper flame adjustment.   69-1225—4   8 VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS   NOTE: If the burner firing rate is above 150,000 Btuh   Check and Adjust Gas Input   and Burner Ignition   on VR8304 models (see Table 1 for VR8304   capacities), it may not be possible to deliver the   desired outlet pressure. This is an application   issue, not a control failure. Take whatever steps   are required to correct the situation.   IMPORTANT   1. Do not exceed input rating stamped on   appliance nameplate, or manufacturer’s   recommended burner orifice pressure for size   orifice(s) used. Make certain primary air supply   to main burner is properly adjusted for complete   combustion. Follow appliance manufacturer   instructions.   Step-Opening (P) Models   Step-opening models require that you check and adjust   the full-rate pressure first and then check the step   pressure. The step pressure is not field adjustable.   2. IF CHECKING GAS INPUT BY CLOCKING   GAS METER: Make certain there is no gas flow   through the meter other than to the appliance   being checked. Other appliances must remain   off with the pilots extinguished (or deduct their   consumption from the meter reading). Convert   flow rate to Btuh as described in form 70-2602,   Gas Controls Handbook, and compare to Btuh   input rating on appliance nameplate.   1. Carefully check the main burner lightoff. Make sure   that the main burner lights smoothly and that all   ports remain lit.   2. Check the full rate manifold pressure listed on the   appliance nameplate. Gas control full rate outlet   pressure should match this rating.   3. With main burner operating, check the gas control   flow rate using the meter clocking method or check   pressure using a manometer connected to the   outlet pressure tap on the gas control. See Fig. 6.   4. If necessary, adjust the pressure regulator to   match the appliance rating. See Tables 8A and 8B   for factory-set nominal outlet pressure and   adjustment range.   3. IF CHECKING GAS INPUT WITH   MANOMETER: Make sure the gas control knob   is in the OFF position before removing outlet   pressure tap plug to connect manometer   (pressure gauge). Also move the gas control   knob to the OFF position when removing the   gauge and replacing the plug. Before removing   inlet pressure tap plug, shut off gas supply at   the manual valve in the gas piping to the   appliance or, for LP, at the tank. Also shut off   gas supply before disconnecting manometer   and replacing plug. Repeat Gas Leak Test at   plug with main burner operating.   a. Remove the pressure regulator adjustment cap   screw.   Using a screwdriver, turn the inner adjustment screw   (Fig. 6) clockwise   counterclockwise   to the burner.   to increase or   to decrease the gas pressure   b. Always replace the cap screw and tighten   firmly to prevent gas leakage.   5. If the desired outlet pressure or flow rate cannot be   achieved by adjusting the gas control, check the   gas control inlet pressure using a manometer at   the inlet pressure tap of the control. If the inlet   pressure is in the nominal range (see Tables 8A   and 8B), replace the control. Otherwise, take the   necessary steps to provide proper gas pressure to   the control.   6. Carefully check the burner lightoff at step pressure.   Make sure the burner lights smoothly and without   flashback to the orifice. Make sure all ports remain   lit. Cycle the burner several times, allowing at least   60 seconds between cycles for the regulator to   resume the step function. Repeat after allowing the   burner to cool. Readjust the full rate outlet   pressure, if necessary, to improve lightoff   characteristics.   NOTE: Check the inlet pressure before adjusting the   pressure regulator.   Standard and Slow-Opening   (H, K and M) Models   1. Carefully check the main burner lightoff. Make sure   that the main burner lights smoothly and that all   ports remain lit.   2. Check the full rate manifold pressure listed on the   appliance nameplate. Gas control full rate outlet   pressure should match this rating.   3. With main burner operating, check the control flow   rate using the meter clocking method or check   pressure using a manometer connected to the   outlet pressure tap on the control. See Fig. 6.   4. If necessary, adjust the pressure regulator to   match the appliance rating. See Tables 8A and 8B   for factory-set nominal outlet pressure and   adjustment range.   Two-Stage (Q) Models   Two-stage models require that you check and adjust both   high and low pressure regulator settings. Two-stage   appliance operating sequences vary. Consult the   appliance manufacturer instructions for the specific   operating sequence and regulator adjustment procedure   for the appliance in which the control is installed.   a. Remove the pressure regulator adjustment cap   screw.   b. Using a screwdriver, turn the inner adjustment   screw (Fig. 6) clockwise   counterclockwise   to increase or   to decrease the gas   pressure to the burner.   c. Always replace the cap screw and tighten   firmly to prevent gas leakage.   1. Set appliance to operate on high.   2. Carefully check the main burner lightoff. Make sure   that the main burner lights smoothly and that all   ports remain lit.   3. Check the full rate (high) manifold pressure listed   on the appliance nameplate for high pressure. The   gas control full rate outlet pressure should match   this rating.   5. If the desired outlet pressure or flow rate cannot   be achieved by adjusting the gas control, check the   gas control inlet pressure using a manometer at   the inlet pressure tap of the gas control. If the inlet   pressure is in the nominal range (see Tables 8A   and 8B), replace the gas control. Otherwise, take   the necessary steps to provide proper gas   pressure to the control.   9 69-1225—4   VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS   4. With main burner operating, check the gas control   flow rate using the meter clocking method or check   pressure using a manometer connected to the   outlet pressure tap on the gas control. See Fig. 6.   5. If necessary, adjust the high pressure regulator to   match the appliance rating. See Tables 8A and 8B   for factory-set nominal outlet pressure and   adjustment range.   flow rate cannot be achieved by adjusting the gas   control, check the control inlet pressure using a   manometer at the inlet pressure tap of the control.   If the inlet pressure is in the nominal range   (see Tables 8A and 8B), replace the gas control.   Otherwise, take the necessary steps to provide   proper gas pressure to the control.   a. Remove the pressure regulator adjustment cap   (Fig. 6).   b. Using a screwdriver, turn the inner adjustment   Check Safety Shutdown Performance   screw for HI pressure clockwise   increase or counterclockwise   to   to   WARNING   Can cause property damage, severe injury   or death.   Perform the safety shutdown test any time work   is done on a gas system.   decrease the gas pressure to the burner.   6. After high pressure has been checked, check low   pressure regulation. Two-stage appliance   operating sequences vary. Consult the appliance   manufacturers instructions for the specific   operating sequence and regulator adjustment   procedure for the appliance in which the control is   installed and for instructions on how to prevent the   control from moving to high stage while checking   the low pressure regulator setting.   7. Check the low rate manifold pressure listed on the   appliance nameplate. Gas control low rate outlet   pressure should match this rating.   8. With main burner operating, check the gas control   flow rate as before (using the meter clocking   method or check pressure using a manometer   connected to the outlet pressure tap on the   control).   Fire or Explosion Hazard.   NOTE: Read steps 1 through 7 before starting, and   compare to the safety shutdown or safety   lockout tests recommended for the intermittent   pilot (IP) ignition module. Where different, use   the procedure recommended for the module.   1. Turn off gas supply.   2. Set thermostat or controller above room   temperature to call for heat.   3. Watch for ignition spark or for glow at hot surface   igniter either immediately or following prepurge.   See IP module specifications.   9. If necessary, adjust the low pressure regulator to   match the appliance rating. See Tables 8A and 8B   for factory-set nominal outlet pressure and   adjustment range.   a. Remove the pressure regulator adjustment cap   (Fig. 6).   Using a screwdriver, turn the inner adjustment screw for   4. Time the length of the spark operation. See the IP   module specifications.   5. After the module locks out, open the manual gas   cock and make sure no gas is flowing to the pilot or   main burner. With modules that continue to spark   until the pilot lights or the system shuts down   manually, the pilot should light when the manual   gas control knob is opened.   LO pressure clockwise   counterclockwise   the burner.   to increase or   to decrease the gas pressure to   6. Set the thermostat below room temperature and   wait one minute.   7. Operate system through one complete cycle to   make sure all controls operate properly.   10. Once high and low pressure have been checked   and adjusted, replace pressure regulator   adjustment cap. If the desired outlet pressure or   Table 8A. Pressure Regulator Specification Pressures (in. wc).   Factory Set Nominal Outlet   Pressure   Setting Range   Full Rate   Type of Nominal Inlet   Model Type   Gas   Pressure Range   Step   Full Rate   3.5   Step   Standard,   Slow   NAT   5.0 to 7.0   — — 3.0 to 5.0   LP   12.0 to 14.0   5.0 to 7.0   — 10.0   3.5   — 8.0 to 12.0   0.7 to 1.7   1.4 to 5.5   Step   NAT   LP   0.9   2.2   — None   None   — 12.0 to 14.0   5.0 to 7.0   10.0   a Two-Stage   NAT   1.7 Low   3.5 High   0.9 to 3.0 Low   3.0 to 5.0 High   LP   121.0 to 14.0   — 4.9 Low   — 3.5 to 5.5 Low   10.0 High   8.0 to 11.0 High   a Low Fire setting range for VR8304Q 1/2 in. by 1/2 in. and 1/2 in. by 3.4 in. is 1.5 to 3.0 in. wc.   69-1225—4   10   VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS   Table 8B. Pressure Regulator Specification Pressures (kPa).   Factory Set Nominal Outlet   Pressure   Setting Range   Type of   Gas   Nominal Inlet   Pressure Range   Model Type   Step   Full Rate   Step   Full Rate   Standard,   Slow   NAT   1.2 to 1.7   — 0.9   — 0.7 to 1.2   LP   2.9 to 3.9   1.2 to 1.7   2.9 to 3.9   1.2 to 1.7   — 2.5   0.9   2.5   — 2.0 to 3.0   Step   NAT   LP   0.2   0.5   — None   None   — 0.17 to 0.48   1.4 to 1.37   a Two-stage   NAT   0.48 Low   0.9 High   0.22 to 0.75 Low   0.75 to 1.2 High   LP   2.9 to 3.9   — 1.2 Low   2.5 High   — 0.9 to 1.4 Low   2.0 to 2.5 High   a Low Fire setting range for VR8304Q 1/2 in. by 1/2 in. and 1/2 in. by 3.4 in. is 0.37 to 0.75 kPa.   • Dusty, wet, or corrosive environments. Since these   environments can cause the gas control to deteriorate   more rapidly, the system should be checked more   often.   Non-Regulating On-Off (U) Models   Non-regulating VR8204U Valves are designed for   application in various parts of Europe where a separate,   distinct, pressure regulator is required. The VR8204U is   similar to the VR8204A in all other aspects and should be   installed accordingly.   The system should be replaced if:   • • • It does not perform properly on checkout or   troubleshooting.   The gas control is likely to have operated for more   than 200,000 cycles.   MAINTENANCE   The control is wet or looks as if it has been wet.   WARNING   Can cause property damage, severe injury,   or death.   SERVICE   Fire or Explosion Hazard.   Do not disassemble the gas control; it contains   no replaceable components. Attempted   disassembly, repair, or cleaning can damage the   control, resulting in gas leakage.   WARNING   Can cause property damage, severe injury   or death.   Fire or Explosion Hazard.   Do not disassemble the control; it contains no   replaceable components. Attempted   disassembly, repair, or cleaning can damage   the gas control, resulting in gas leakage.   Regular preventive maintenance is important for   applications in the commercial cooking and agricultural   and industrial industries that place a heavy load on   system controls because:   • In many such applications, particularly commercial   cooking, the equipment operates 100,000 to 200,000   cycles per year. Such heavy cycling can wear out the   gas control in one to two years.   Exposure to water, dirt, chemicals and heat can   damage the gas control and shut down the control   system.   CAUTION   Can burn out valve coil terminals.   Never apply a jumper across (or short) the valve   coil terminals, even temporarily.   Equipment Damage.   • The maintenance program should include regular   checkout of the control as outlined in the Startup and   Checkout section, and the control system as described in   the appliance manufacturer literature.   After servicing, verify proper system operation.   If Main Burner Does Not Come   On With Call For Heat   Maintenance frequency must be determined individually   for each application. Some considerations are:   1. Confirm the gas control knob is in the ON position.   2. Adjust thermostat several degrees above room   temperature.   • Cycling frequency. Appliances that may cycle 20,000   times annually should be checked monthly.   Intermittent use. Appliances that are used seasonally   should be checked before shutdown and again before   the next use.   3. Using ac voltmeter, check for 24V at gas control:   • • • If pilot lights, measure across MV/PV and MV.   If pilot does not light, measure across MV/PV   and PV before safety lockout occurs.   • Consequence of unexpected shutdown. Where the   cost of an unexpected shutdown would be high, the   system should be checked more often.   4. If voltage is incorrect or not present, check control   circuit for proper operation.   5. If 24V is present, replace gas control.   11   69-1225—4   VR8104, VR8204 AND VR 8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS   STOP: Read the Warnings Above Before   INSTRUCTIONS TO THE   HOMEOWNER   Proceeding.   The pilot flame is lit automatically. If the appliance does   not turn on when the thermostat is set several degrees   above room temperature, follow these instructions:   1. Set the thermostat to its lowest setting to reset the   safety control.   WARNING   Fire or Explosion Hazard.   2. Disconnect all electric power to the appliance.   3. Remove the burner access panel if provided on   your appliance.   Can cause property damage, severe injury,   or death.   Follow these warnings exactly:   4. Turn the gas control knob clockwise   to the   1. Pilot flame is lit automatically. Do not light the   pilot flame manually.   OFF position.   5. Wait five minutes to clear out any unburned gas.   Then if you smell gas, STOP! Follow Step 2 in the   Warning above. If you do not smell gas, continue   with the next step.   2. Before lighting the pilot burner flame, smell   around the appliance for gas. Be sure to smell   next to the floor because LP gas is heavier   than air. If you smell gas:   6. Turn the gas control knob counterclockwise   to the ON position.   7. Replace the burner access panel.   8. Reconnect all electric power to the appliance.   9. Set the thermostat to the desired setting.   10. If the appliance does not turn on, turn the gas   control knob to the OFF position and contact a   qualified service technician for assistance.   • Turn off the gas supply at the appliance   service valve. On LP gas systems, turn off   the gas supply at the gas tank.   Do not light any appliances in the house.   Do not touch electrical switches or use the   phone.   Leave the building and use a neighbor’s   phone to call your gas supplier.   If you cannot reach your gas supplier, call   the fire department.   • • • • Turning Off the Appliance   Vacation Shutdown   Set the thermostat to the desired room temperature while   you are away.   3. Replace the gas control in the event of any   physical damage, tampering, bent terminals,   missing or broken parts, stripped threads, or   evidence of exposure to heat.   IMPORTANT   Follow the operating instructions provided by   the heating appliance manufacturer. The   information below describes a typical control   application, but the specific controls used and   the procedures outlined in your appliance   manufacturer instructions can differ, requiring   special instructions.   Complete Shutdown   Turn off power to the appliance. Turn off the gas supply   to the appliance. Turn the gas control knob to OFF. The   appliance will completely shut off. Follow the procedure   in the Instructions to the Homeowner section above to   resume normal operation.   Home and Building Control   Home and Building Control   Honeywell Inc.   1985 Douglas Drive North   Golden Valley, Minnesota 55422   Honeywell Limited-Honeywell Limitée   35 Dynamic Drive   Scarborough, Ontario   M1V 4Z9   Printed in U.S.A. on recycled   paper containing at least 10%   post-consumer paper fibers.   69-1225—4 G.R. Rev. 9-00   |