| 	
		 INSTALLATION INSTRUCTIONS   
					COOL/DRY/HEAT Model   
					– Split System Air Conditioner –   
					Contents   
					Model Combinations   
					Page   
					Combine indoor and outdoor units only as listed   
					below.   
					IMPORTANT!   
					Please Read Before Starting .................................. 2   
					Indoor Units   
					KHS0951   
					Outdoor Units   
					CH0951   
					1. GENERAL .......................................................... 3   
					1-1. Tools Required for Installation (not supplied)   
					1-2. Accessories Supplied with Unit   
					KHS1251   
					CH1251   
					1-3. Optional Copper Tubing Kit   
					1-4. Type of Copper Tube and Insulation Material   
					1-5. Field Wiring   
					1-6. Additional Materials Required for Installation   
					Power Source:   
					60 Hz, single-phase, 115 V   
					2. INSTALLATION SITE SELECTION ................... 4   
					2-1. Indoor Unit   
					KHS1852   
					CH1852   
					Power Source:   
					60 Hz, single-phase, 230/208 V   
					2-2. Outdoor Unit   
					3. HOW TO INSTALL THE INDOOR UNIT ............ 6   
					3-1. Remove the Rear Panel from the Unit   
					3-2. Make a Hole   
					3-3. Install the Rear Panel on the Wall   
					3-4. Remove the Grille to Install the Indoor Unit   
					3-5. Shape the Indoor Side Tubing   
					3-6. Wiring Instructions   
					3-7. Recommended Wire Length and Diameter   
					3-8. Wiring Instructions for Inter-unit Connections   
					3-9. Mounting   
					5-7. Finishing the Installation   
					6. AIR PURGING................................................... 18   
					I Air Purging with a Vacuum Pump (for Test Run)   
					I Basic Function of the Service Valves   
					I Pump Down   
					7. REMOTE CONTROL UNIT INSTALLATION   
					POSITION ......................................................... 22   
					7-1. Mounting on a Wall   
					3-10. Drain Hose   
					4. HOW TO INSTALL THE OUTDOOR UNIT ....... 15   
					4-1. Wiring Instructions for the Outdoor Unit   
					5. REFRIGERANT TUBING.................................. 16   
					5-1. Use of the Flaring Method   
					IMPORTANT   
					5-2. Flaring Procedure with a Flare Tool   
					5-3. Caution before Connecting Tubes Tightly   
					5-4. Connecting Tubing between Indoor and   
					Outdoor Units   
					Power source for CH0951 and CH1251 is 60 Hz,   
					single-phase 115 V.   
					5-5. Insulation of Refrigerant Tubing   
					5-6. Taping the Tubes   
					In Canada   
					SANYO FISHER COMPANY   
					SANYO Canada Inc.   
					A DIVISION OF SANYO NORTH AMERICA CORPORATION 300 Applewood Crescent, Concord   
					21605 Plummer Street   
					Ontario, L4K 5C7, Canada   
					85264189615003 © SANYO 2002 Chatsworth, CA 91311 U.S.A.   
					W 
				1. General   
					This booklet briefly outlines where and how to install the   
					air conditioning system. Please read over the entire set   
					of instructions for the indoor and outdoor units and   
					make sure all accessory parts listed are with the system   
					before beginning.   
					5. Carpenter’s level   
					6. Sabre saw or key hole saw   
					7. Hacksaw   
					8. Core bits   
					9. Hammer   
					10. Drill   
					1-1. Tools Required for Installation (not supplied)   
					1. Standard screwdriver   
					11. Tube cutter   
					12. Tube flaring tool   
					13. Torque wrench   
					14. Adjustable wrench   
					15. Reamer (for deburring)   
					2. Phillips head screwdriver   
					3. Knife or wire stripper   
					4. Tape measure   
					1-2. Accessories Supplied with Unit   
					Table 1   
					Parts   
					Figure   
					Q’ty   
					Parts   
					Figure   
					Truss-head   
					Phillips   
					5/32 × 5/8" (4 × 16 mm)   
					Q’ty   
					Parts   
					Remote   
					Figure   
					Q’ty   
					Tapping   
					screw   
					Rawl plug   
					12   
					12   
					1 
					control unit   
					Remote   
					control   
					holder   
					AAA alkaline   
					battery   
					Drain hose   
					adapter   
					1 
					2 
					1 
					1 
					Hex   
					wrench*   
					* Packed in the outdoor unit.   
					1-3. Optional Copper Tubing Kit   
					2. Foamed polyethylene insulation for the specified   
					O.D. copper tubes as required to precise length of   
					tubing. Wall thickness of the insulation should be   
					not less than 0.3 in. (8 mm).   
					Copper tubing for connecting the outdoor unit to the   
					indoor unit is available in kits which contain the narrow   
					and wide tubing, fittings and insulation. Consult your   
					nearest sales outlet or A/C workshop.   
					1-5. Field Wiring   
					1-4. Type of Copper Tube and Insulation Material   
					Use insulated copper wire for field wiring. Wire size   
					varies with the total length of wiring. Refer to 3-6. Wiring   
					Instructions for details.   
					If you wish to purchase these materials separately from   
					a local source, you will need:   
					1. Deoxidized annealed copper tube for refrigerant   
					tubing as detailed in Table 2.   
					Check local electrical codes   
					and regulations before   
					obtaining wire. Also, check   
					any specified instructions or   
					limitations.   
					CAUTION   
					When cutting tubing, add approximately 12" to 16"   
					(30 cm to 40 cm) to each tube length to reduce   
					vibration between the air conditioning units.   
					Table 2   
					Narrow Tube   
					Wide Tube   
					Model   
					Outer Dia.   
					Thickness   
					Outer Dia.   
					Thickness   
					6.35 mm (1/4")   
					6.35 mm (1/4")   
					6.35 mm (1/4")   
					0.8 mm (0.0314")   
					0.8 mm (0.0314")   
					0.8 mm (0.0314")   
					9.52 mm (3/8")   
					12.7 mm (1/2")   
					0.8 mm (0.0314")   
					0.8 mm (0.0314")   
					CH0951   
					CH1251   
					CH1852   
					15.88 mm (5/8") 1.0 mm (0.0394")   
					3 
				1-6. Additional Materials Required for Installation   
					Indoor unit   
					1. Refrigeration (armored) tape   
					2. Insulated staples or clamps for connecting wire   
					(See local codes)   
					3. Putty   
					4. Refrigeration lubricant   
					5. Clamps or saddles to secure refrigerant tubing   
					Drain hose   
					2. Installation Site Selection   
					Outside drainage   
					2-1. Indoor Unit   
					Fig. 1   
					To prevent abnormal heat genera-   
					WARNING   
					tion and the possibility of fire, do   
					2" (5 cm) min.   
					*6" (15 cm) min.   
					not place obstacles, enclosures   
					and grilles in front of or surround-   
					ing the air conditioner in a way that   
					may block air flow.   
					2" (5 cm) min.   
					*6" (15 cm) min.   
					2" (5 cm) min.   
					*6" (15 cm) min.   
					Front View   
					*KHS1852 only   
					AVOID:   
					Fig. 2   
					I direct sunlight.   
					Tubing length (L)   
					I nearby heat sources that may affect performance of the   
					INDOOR   
					UNIT   
					unit.   
					I areas where leakage of flammable gas may be expected.   
					Elevation   
					difference (H)   
					I places where large amount of oil mist exist.   
					OUTDOOR   
					UNIT   
					DO:   
					I select an appropriate position from which every corner of   
					Fig. 3a   
					the room can be uniformly cooled. (High on a wall is best.)   
					I select a location that will hold the weight of the unit.   
					CAUTION   
					Indoor unit   
					Wall   
					I select a location where tubing and drain hose have the   
					shortest run to the outside. (Fig. 1)   
					For stable operation of   
					the air conditioner, do   
					not install wall-mounted   
					type indoor units under   
					5 ft. (1.5 m) from floor   
					level.   
					I allow room for operation and maintenance as well as unre-   
					Minimum height   
					from floor level   
					5 ft. (1.5 m)   
					stricted air flow around the unit. (Fig. 2)   
					I install the unit within the maximum elevation difference (H)   
					above the outdoor unit and within a total tubing length (L)   
					from the outdoor unit as detailed in Table 3 and Fig. 3a.   
					Floor level   
					Fig. 3b   
					Table 3   
					Max. Allowable Tubing   
					Length at Shipment   
					(ft.)   
					Limit of Tubing   
					Length (L)   
					(ft.)   
					Limit of Elevation   
					Difference (H)   
					(ft.)   
					Required Amount of   
					Additional Refrigerant   
					(oz./ft.)*   
					Model   
					25   
					25   
					50   
					65   
					23   
					23   
					a) 0.16   
					b) 0.27   
					9,000 BTU   
					12,000/18,000 BTU   
					* If total tubing length becomes a) 25 to 50 ft. (max.), b) 25 to 65 ft. (max.) charge additional refrigerant (R22) by a) 0.16 oz./ft., b) 0.27 oz./ft.   
					No additional compressor oil is necessary.   
					4 
				2-2. Outdoor Unit   
					Exhaust fan   
					NO   
					Hot air   
					AVOID:   
					Heat source   
					I heat sources, exhaust fans, etc. (Fig. 4)   
					I damp, humid or uneven locations.   
					DO:   
					Outdoor unit   
					I choose a place as cool as possible.   
					I choose a place that is well ventilated.   
					I allow enough room around the unit for air intake/   
					Fig. 4   
					exhaust and possible maintenance. (Fig. 5a)   
					Obstacle above   
					CAUTION   
					Min.   
					Min.   
					7 ft.   
					(2 m)   
					7 ft.   
					(2 m)   
					I Install the outdoor unit above snowfall line.   
					Air intake   
					Min. 6" (15 cm)   
					Valve side   
					I Do not place objects on or sit on the out-   
					door unit. Also, never block the air   
					intake/outlet or exhaust. Distortion of the   
					outdoor unit or incomplete combustion   
					may result.   
					Min. 10"   
					(25 cm)   
					Min. 6"   
					Air discharge   
					Min. 12"   
					(30 cm)   
					(15 cm)   
					Ground   
					Min. 6 in.   
					(15 cm)   
					Air intake   
					I Do not introduce foreign matter into the air   
					intake/outlet or exhaust. Do not poke them   
					with such objects as a stick.   
					Fig. 5a   
					I provide a solid base (level concrete pad, concrete   
					block, 2 to 2-1/2 (CH09, 12) / 2-1/2 to 3 (CH18) in. ×   
					16 in. (5 to 6.5 / 6.5 to 7.5 × 40 cm) beams or equal),   
					a minimum of 4 in. (10 cm) above ground level to   
					reduce humidity and protect the unit against possible   
					water damage and decreased service life (Figs. 5b   
					and 5c).   
					Drain holes   
					Fig. 5b   
					Anchor bolts   
					(4 pcs)   
					A solid base must not cover   
					CAUTION   
					the hole of the bottom plate.   
					Min. 4"   
					(10 cm)   
					I use lug bolts or equal to bolt down unit, reducing   
					Air intake   
					vibration and noise.   
					Concrete   
					or equal   
					CH09, 12: 2 to 2-1/2" (5 to 6.5 cm)   
					CH18:   
					2-1/2 to 3" (6.5 to 7.5 cm)   
					Fig. 5c   
					5 
				3. How to Install the Indoor Unit   
					3-1. Remove the Rear Panel from the Unit   
					(1) Remove and discard the set screw on the rear panel. (Fig. 6)   
					(2) Press the 2 I marks on the frame cover and disengage the sta-   
					tionary tabs from the frame. (Fig. 7)   
					(3) Remove the rear panel.   
					Set screw only for transportation   
					NOTE   
					Fig. 6   
					Tubing can be extended in 5 directions (KHS0951, KHS1251 and   
					KHS1852) as shown in Fig. 8a or 8b. Select the direction you need   
					providing the shortest run to the outside unit.   
					Rear panel   
					3-2. Make a Hole   
					(1) Place the rear panel from the indoor unit on the wall at the loca-   
					tion selected. Make sure the panel is horizontal, using a carpen-   
					ter’s level or tape measure to measure down from the ceiling.   
					Wait until after cutting the hole before attaching the rear panel to   
					the wall.   
					Fig. 7   
					I marks   
					(2) Determine which side of the unit you should make the hole for   
					tubing and wiring. (Fig. 9)   
					KHS0951, KHS1251   
					Right-rear   
					tubing   
					(recommended)   
					(3) Before making the hole, check carefully that no studs or pipes   
					are directly run behind the spot to be cut.   
					Left   
					tubing   
					CAUTION   
					Left-rear   
					tubing   
					Right tubing   
					Fig. 8a   
					I Also avoid areas where electrical wiring or conduits are   
					Downward tubing   
					located.   
					KHS1852   
					I Switching drain hose and drain cap   
					Left   
					tubing   
					(a) Locate the drain hose and the drain cap. (Fig. 8c)   
					Right-rear   
					tubing   
					(recommended)   
					(b) Remove the drain hose on the right side by pushing and   
					turning the hose connector counter-clockwise to release it.   
					(Fig. 8c)   
					(c) Apply moderate force to pull off the drain cap on the left   
					side. (If you cannot pull it off by hand, use a long-nose pli-   
					ers.)   
					Right tubing   
					Fig. 8b   
					Downward tubing   
					(d) Reattach the drain hose to the left side and the drain cap   
					to the right side. (Fig. 8c)   
					The above precautions are also applicable if tubing goes through the   
					wall in any other location.   
					Drain hose   
					In case of right-rear   
					Clamp   
					To slip on   
					Drain cap   
					60°   
					To remove   
					Fig. 9   
					Fig. 8c   
					6 
				(4) Using a sabre saw, key hole saw or hole-cutting drill   
					attachment, cut a hole in the wall. See Table 4 and   
					Fig. 10.   
					NOTE   
					Hole should be made at a slight downward slant to the   
					outdoor side.   
					Table 4   
					Indoor   
					side   
					Outdoor   
					side   
					Hole Dia.   
					2-9/16" (65 mm) / 3-5/32" (80 mm)   
					(5) Measure the thickness of the wall from the inside   
					edge to the outside edge and cut PVC pipe at a   
					slight angle 0.25 in. (6 mm) shorter than the thick-   
					ness of the wall. (Fig. 11)   
					Fig. 10   
					PVC pipe (locally purchased)   
					(6) Place the plastic cover (locally purchased) over the   
					end of the pipe (for indoor side only) and insert the   
					pipe in the wall. (Fig. 12)   
					3-3. Install the Rear Panel on the Wall   
					Cut at slight angle   
					Be sure to confirm that the wall is strong enough to sus-   
					pend the unit.   
					Fig. 11   
					INSIDE   
					OUTSIDE   
					See either Item a) or b) below depending on the wall type.   
					Wall   
					Plastic   
					cover   
					a) If Wooden Wall   
					PVC pipe   
					Slight   
					angle   
					(1) Attach the rear panel to the wall with the 10 screws   
					provided. (Fig. 13)   
					If you are not able to line up the holes in the rear   
					panel with the beam locations marked on the wall,   
					use rawl plugs or toggle bolts to go through the   
					holes on the panel or drill 3/16 in. (5 mm) dia. holes   
					in the panel over the stud locations and then mount   
					the rear panel.   
					Fig. 12   
					(2) Double check with a ruler or carpenter’s level that   
					the panel is level. This is important to install the unit   
					properly. (Fig. 14)   
					Fig. 13   
					Fig. 14   
					(3) Make sure the panel is flush against the wall. Any   
					space between the wall and unit will cause noise   
					and vibration.   
					b) If Block, Brick, Concrete or Similar Type Wall   
					Make 3/16 in. (4.8 mm) dia. holes in the wall. Insert   
					rawl plugs for appropriate mounting screws. (Fig. 15)   
					3/16" (4.8 mm)   
					dia. hole   
					Rawl plug   
					Fig. 15   
					7 
				3-4. Remove the Grille to Install the Indoor Unit   
					KHS0951, KHS1251   
					Basically, these models can be installed and wired with-   
					out removing the grille. If access to any internal part is   
					needed, follow the steps as given below:   
					How to remove the grille   
					(1) Set the flap in the horizontal position.   
					(2) Unscrew the screws. (Fig. 16a or 16b)   
					(3) Remove the grille. (Fig. 17)   
					Screw cover   
					Flap   
					(Up and down air direction louvre)   
					Fig. 16a   
					(a) Hold both corners of the air intake grille, then   
					pull out and up to open.   
					KHS1852   
					(b) Pull the lower part of the grille toward you to   
					remove.   
					(c) Use a standard screwdriver to push up the 3   
					tabs to remove the grille.   
					How to replace the grille   
					(1) Close the flaps.   
					Fig. 16b   
					(2) Reinstall the grille into the lower part while aligning   
					its tabs on the upper part. (Fig. 18) Insert the tabs in   
					the slots and push the lower part of the grille back   
					into position.   
					Air intake grille   
					(3) Press at each of the 4 tabs to completely close the   
					grille. Make sure that the grille and frame are firmly   
					fitted together. (Fig. 19)   
					Fig. 17   
					Fig. 18   
					Fig. 19   
					8 
				3-5. Shape the Indoor Side Tubing   
					1) Arrangement of tubing by directions   
					a) Right or left tubing   
					Frame   
					Cut out the corner of the right/left frame with a   
					hacksaw or the like. (Figs. 20 and 21)   
					Left tubing   
					outlet   
					b) Right-rear or left-rear tubing   
					In this case, the corner of the frame need not be   
					cut.   
					2) To mount the indoor unit on the rear panel:   
					Fig. 20   
					Hang the 2 mounting slots of the unit on the   
					upper tabs of the rear panel. (Fig. 22)   
					Frame   
					3-6. Wiring Instructions   
					General precautions on wiring   
					Right tubing   
					outlet   
					1) Before wiring, confirm the rated voltage of the unit   
					as shown on its nameplate, then carry out the   
					wiring closely following the wiring diagram.   
					2) Provide a power outlet to be used exclusively for   
					each unit, with a power supply disconnect and cir-   
					cuit breaker for overcurrent protection provided in   
					the exclusive line.   
					Fig. 21   
					3) To prevent possible hazard due to insulation failure,   
					the unit must be grounded.   
					4) Each wiring connection must be done tightly and in   
					accordance with the wiring system diagram. Wrong   
					wiring may cause the unit to misoperate or become   
					damaged.   
					Fig. 22   
					5) Do not allow wiring to touch the refrigerant tubing,   
					compressor, or any moving parts of the fan.   
					6) Unauthorized changes in the internal wiring can be   
					very dangerous. The manufacturer will accept no   
					responsibility for any damage or misoperation that   
					occurs as a result of such unauthorized changes.   
					9 
				3-7. Recommended Wire Length and Diameter   
					WIRING SYSTEM DIAGRAM   
					Regulations on wiring diameter differ from locality to   
					locality. For field wiring requirements, please refer to   
					your local electrical codes. Carefully observe these reg-   
					ulations when carrying out the installation.   
					CH0951, CH1251 Models   
					Disconnect   
					(Inter-unit)   
					INDOOR UNIT   
					Terminal   
					OUTDOOR UNIT   
					Terminal   
					switch   
					(Field supply)   
					Power lines   
					1 
					2 
					3 
					4 
					5 
					6 
					1 
					2 
					3 
					4 
					5 
					6 
					NOTE   
					Refer to the wiring system diagram (Fig. 23)   
					Refer to your local codes or in the absence of local   
					codes with the National Electric Code: ANSI/NFPA70.   
					L 
					N 
					7 
					8 
					(Inter-unit)   
					Control lines   
					Grounding   
					line   
					G 
					G 
					G 
					WARNING   
					I Be sure to comply with local codes on running   
					the wire from the outdoor unit to the indoor unit   
					(size of wire and wiring method, etc.).   
					CH1852 Model   
					Disconnect   
					(Inter-unit)   
					INDOOR UNIT   
					Terminal   
					OUTDOOR UNIT   
					Terminal   
					switch   
					Power lines   
					I Each wire must be firmly connected.   
					(Field supply)   
					I No wire should be allowed to touch refrigerant   
					tubing, the compressor, or any moving part.   
					1 
					2 
					3 
					4 
					5 
					6 
					1 
					2 
					3 
					4 
					5 
					6 
					WARNING   
					L1   
					7 
					L2   
					8 
					I To avoid the risk of electric shock, each air   
					(Inter-unit)   
					Control lines   
					conditioner unit must be grounded.   
					Grounding   
					line   
					G 
					G 
					G 
					Fig. 23   
					CAUTION   
					I Be sure to connect the power supply line to the   
					outdoor unit as shown in the wiring diagram. The   
					indoor unit draws its power from the outdoor   
					unit.   
					3-8. Wiring Instructions for Inter-unit Connections   
					a) Remove the grille. (See 3-4. Remove the Grille to   
					Install the Indoor Unit on page 8.)   
					Rear   
					panel   
					Wall   
					Plastic   
					cover   
					b) Insert the inter-unit wiring (according to local codes)   
					into the through-the-wall PVC pipe. Run the wiring   
					toward the indoor side allowing approx. 10 in. (25   
					cm) to extend from the wall face. (Fig. 24)   
					Wiring   
					Never fix the wiring by any   
					10 in.   
					(25 cm)   
					CAUTION   
					means before the indoor unit   
					is fully seated on the rear   
					panel.   
					Fig. 24   
					10   
				c) Remove the screws to open the cover plate secur-   
					ing the electrical component box. (Figs. 25a, 25b,   
					25c and 25d)   
					KHS0951, KHS1251   
					KHS0951, KHS1251   
					Cover   
					plate   
					Electrical   
					component box   
					Cover   
					plate   
					d) Insert the wrapped tubing into the hole in the wall.   
					e) Hang the indoor unit on the rear panel.   
					Terminal   
					plate   
					f) Using a Phillips screwdriver, take out the screws on   
					the earth plate. (Fig. 26a KHS09, 12 models only)   
					Remove the earth plate.   
					Earth plate   
					Electrical   
					component   
					box   
					g) Remove the lock nut from the conduit connector.   
					Insert the conduit connector through the opening   
					from the underside of the electrical component box.   
					After insertion, Fit the screw at the top of the con-   
					duit connector into the cut-out. (Fig. 26b). Position   
					the earth plate over the conduit connector, allowing   
					the connector and wires to extend through the hole   
					in the plate. Next, attach the conduit connector to   
					the earth plate by replacing and tightening the lock   
					nut (Figs. 26c and 26d). Then re-attach the earth   
					plate to the electrical component box with the 2   
					screws.   
					Fig. 25b   
					Fig. 25a   
					KHS1852   
					KHS1852   
					Electrical   
					component box   
					Cover   
					plate   
					Cover   
					plate   
					Terminal   
					plate   
					Earth plate   
					h) Give some play to the inter-unit wiring from the out-   
					door unit to the corresponding terminals on the termi-   
					nal base. (See Wiring System Diagram on page 10.)   
					Electrical   
					Component   
					box   
					Fig. 25c   
					KHS0951, KHS1251   
					Fig. 25d   
					WARNING   
					Top of conduit   
					connector   
					KHS1852   
					I Be sure to refer to the Wiring System Diagram   
					label inside the electrical component box and   
					carry out the correct field wiring. Wrong wiring   
					can cause the unit to misoperate or result in a fire   
					hazard.   
					Earth   
					Plate   
					Screw   
					Screw   
					hole   
					I Check local electrical codes and any specified   
					wiring instructions or limitations.   
					Fig. 26a   
					i) Fix cover plate and cover plate and back into posi-   
					tion with their screws.   
					KHS0951, KHS1251   
					Fig. 26b   
					Inter-unit   
					(Power line)   
					wiring   
					Inter-unit   
					(Control line)   
					wiring   
					NOTE   
					Inter-unit   
					Control line   
					Wiring   
					When closing the air intake grille, press on both corners   
					and the center. (Fig. 27)   
					KHS1852   
					Earth   
					Plate   
					Lock nut   
					Power line   
					Fig. 26c   
					Earth   
					plate   
					Lock   
					nut   
					Top of conduit   
					Fig. 27   
					Fig. 26d   
					11   
				Loose wiring may cause the termi-   
					nal to overheat or result in unit mal-   
					function. A fire hazard may also   
					exist. Therefore, be sure all wiring   
					is tightly connected.   
					WARNING   
					When connecting each power wire to the corresponding termi-   
					nal, follow the instructions “How to connect wiring to the termi-   
					nal” and fasten the wire securely tight with the fixing screw of   
					the terminal plate.   
					9/32" (7 mm)   
					(ACTUAL   
					SIZE)   
					STRIP   
					SIZE   
					Fig. 28   
					How to connect wiring to the terminal   
					a) For Indoor Unit   
					(1) Cut the wire end with a cutting pliers, then strip the insu-   
					lation to expose the wire about 9/32 in. (7 mm). See the   
					label (Fig. 28) near the terminal plate.   
					Solid wire   
					Loop   
					(2) Using a screwdriver, loosen the terminal screw on the ter-   
					minal plate.   
					Insulation   
					(3) Insert the wire and tighten the terminal screw completely   
					using a screwdriver.   
					Fig. 29   
					Stranded wire   
					b) For Outdoor Unit   
					Ring   
					Connector   
					I For solid core wiring (or F-cable)   
					(1) Cut the wire end with a cutting pliers, then strip the insu-   
					lation to expose the solid wire about 15/16 in. (25 mm).   
					(Fig. 29)   
					Fig. 30   
					(2) Using a screwdriver, remove the terminal screw(s) on the   
					terminal plate.   
					Twist wire ends   
					(3) Using the pliers, bend the solid wire to form a loop suit-   
					able for the terminal screw.   
					(4) Shape the loop wire properly, place it on the terminal   
					plate and fix it securely with the removed terminal screw   
					using a screwdriver.   
					I For stranded wiring   
					Fig. 31   
					(1) Cut the wire end with a cutting pliers, then strip the insu-   
					lation to expose the stranded wiring about 3/8 in. (10 mm)   
					and tightly twist the wire ends. (Figs. 30 and 31)   
					Special   
					washer   
					Screw   
					(2) Using a screwdriver, remove the terminal screw(s) on the   
					terminal plate.   
					Screw and   
					special washer   
					Ring connector   
					Terminal plate   
					(3) Using a ring connector fastener or pliers, securely clamp   
					each stripped wire end with a ring connector. (Fig. 30)   
					Ring   
					connector   
					Wire   
					(4) Place the ring connector wire, and replace and tighten the   
					removed terminal screw using a screwdriver. (Fig. 32)   
					Wire   
					Fig. 32   
					12   
				3-9. Mounting   
					(1) To install the indoor unit, mount the indoor unit onto   
					the 2 tabs on the upper part of the rear plate.   
					(2) Hold down the air discharge outlet and press the   
					lower part of the indoor unit until it clicks to secure-   
					ly fasten to the 2 tabs on the lower part of the rear   
					plate. (Fig. 33)   
					Push   
					NOTE   
					Fig. 33   
					For tubing, choose either the right or left tubing direc-   
					tion and follow the steps below. Also, extend the sup-   
					port on the back of the indoor unit as a stand to make   
					your work easier. (Fig. 34)   
					I Right-side tubing   
					(1) Shape the refrigerant tubing so that it can easily go   
					into the wall hole. (Fig. 35)   
					Stand   
					Fig. 34   
					(2) Push the wiring, refrigerant tubing, and drain hose   
					through the hole in the wall. Adjust the indoor unit   
					so it is securely seated on the rear panel. (Fig. 36)   
					Rear panel   
					Cover   
					(3) Carefully bend the tubing (if necessary) to run   
					along the wall in the direction of the outdoor unit   
					and then tape as far as the fittings. (See Caution   
					on page 17.) The drain hose should come straight   
					down the wall to a point where water runoff won’t   
					stain the wall.   
					Refrigerant   
					tubing   
					Inter-unit   
					wiring   
					Drain hose   
					(4) Connect the refrigerant tubing to the outdoor unit.   
					(After performing a leak test on the connecting part,   
					insulate it with the tubing insulation (Fig. 37a)).   
					Also, refer to Section 5-4. Connecting Tubing   
					between Indoor and Outdoor Units.   
					Fig. 35   
					(5) Assemble the refrigerant tubing, drain hose, and   
					conduit (including inter-unit wiring) as shown in   
					Fig. 37b.   
					Fig. 36   
					Refrigerant tubing   
					Insulation   
					Fig. 37a   
					Conduit   
					Drain hose   
					Inter-unit wiring   
					Fig. 37b   
					13   
				To unmount indoor unit   
					Press the 2 I marks on the lower part of the indoor   
					unit and unlatch the tabs. Then lift the indoor unit and   
					unmount. (Fig. 38)   
					3-10. Drain Hose   
					a) The drain hose should be slanted downward to the   
					outdoors. (Fig. 39)   
					b) Never form a trap in the course of the hose.   
					c) If the drain hose will run in the room, insulate the   
					hose with insulation* so that chilled condensation   
					will not damage furniture or floors. (Fig. 40)   
					Push   
					Fig. 38   
					* Foamed polyethylene or its equivalent is recom-   
					mended.   
					Slant   
					Do not supply power to the   
					unit or operate it until all   
					tubing and wiring to the   
					outside unit are completed.   
					WARNING   
					Indoor   
					unit   
					Drain   
					hose   
					Fig. 39   
					Risk of Electric Shock   
					Condensation   
					Insulation material   
					(locally purchased)   
					must be used.   
					Fig. 40   
					14   
				Terminal   
					block   
					4. How to Install the Outdoor Unit   
					Lock nut   
					First refer to Section 2. Installation Site Selection.   
					Access panel   
					4-1. Wiring Instructions for the Outdoor Unit   
					Regulations on wire size differ from locality to locality. For field   
					wiring requirements, please refer to your local electrical   
					codes. Make sure that the installation fully complies with all   
					local and national regulations.   
					Conduit   
					plate   
					(1) Remove access panel. (Fig. 41)   
					Plug   
					Power supply   
					(Conduit)   
					(2) Connect the power line according to the drawing on the   
					panel side.   
					Power line   
					(Conduit)   
					Control line   
					(Sheath cable)   
					Fig. 41   
					(3) Be sure to size each wire allowing approx. 4 in. (10 cm)   
					longer than the required length for wiring. Store excess   
					wiring inside the cabinet.   
					Apply sealer (putty, etc.) to   
					the gap between the sheath   
					cable and the hole of the   
					conduit plate to prevent   
					water from entering.   
					CAUTION   
					(4) When connections are completed, check that all connec-   
					tions are correct as shown in the wiring system diagram   
					on panel side.   
					(5) Be sure to ground the unit according to your local codes.   
					CAUTION   
					I Examples of Incorrect Wiring   
					The following are examples of improper wiring that result in system misoperation. You should confirm that you have   
					wired the units correctly before beginning the test run.   
					Problem 1   
					Problem 2   
					Short circuit will occur after approx.   
					3 minutes and the power circuit fuse   
					blows.   
					I 
					Air conditioner will not operate.   
					I 
					Disconnect   
					(A)   
					Disconnect   
					(B)   
					Disconnect   
					switch   
					(C)   
					switch   
					switch   
					1 
					2 
					3 
					1 
					2 
					3 
					1 
					2 
					3 
					1 
					2 
					3 
					1 
					2 
					3 
					1 
					2 
					3 
					G 
					G 
					G 
					G 
					G 
					G 
					Grounding line   
					Grounding line   
					Grounding line   
					Outdoor unit   
					Outdoor unit   
					Outdoor unit   
					Indoor unit   
					Indoor unit   
					Indoor unit   
					Problem 3   
					Compressor will not start; only indoor unit will operate.   
					I 
					Disconnect   
					switch   
					Disconnect   
					switch   
					(D)   
					(E)   
					1 
					2 
					3 
					1 
					2 
					3 
					1 
					2 
					3 
					1 
					2 
					3 
					G 
					G 
					G 
					G 
					Grounding line   
					Grounding line   
					Outdoor unit   
					Outdoor unit   
					Indoor unit   
					Indoor unit   
					15   
				5. Refrigerant Tubing   
					Deburring   
					After   
					Before   
					5-1. Use of the Flaring Method   
					Many of the conventional split system air conditioners   
					employ the flaring method to connect refrigerant tubes   
					which run between indoor and outdoor units. In this   
					method, the copper tubes are flared at each end and   
					connected with flare nuts.   
					5-2. Flaring Procedure with a Flare Tool   
					a) Cut the copper tube to the required length with a   
					tube cutter. It is recommended to cut approx. 12 to   
					20 in. (30 to 50 cm) longer than the tubing length   
					you estimate.   
					Fig. 42   
					Copper   
					tubing   
					b) Remove burrs at the end of the copper tube with a   
					tube reamer or file. This process is important and   
					should be done carefully to make a good flare.   
					(Fig. 42)   
					Reamer   
					NOTE   
					When reaming, hold the tube end downward and be   
					sure that no copper scraps fall into the tube. (Fig. 43)   
					Fig. 43   
					c) Remove the flare nut from the unit and be sure to   
					mount it on the copper tube.   
					d) Make a flare at the end of copper tube with a flare   
					tool.* (Fig. 44)   
					Flare nut   
					Copper   
					tubing   
					(*Use “RIGID” or equivalent.)   
					NOTE   
					A good flare should have the following characteristics:   
					I inside surface is glossy and smooth.   
					I edge is smooth.   
					Flare tool   
					Fig. 44   
					I tapered sides are of uniform length.   
					5-3. Caution before Connecting Tubes Tightly   
					a) Be sure to apply a sealing cap or water-proof tape   
					to prevent dust or water from getting into the tubes   
					before they are used.   
					Apply refrigerant   
					lubricant here and here   
					Fig. 45   
					b) Be sure to apply refrigerant lubricant to the match-   
					ing surfaces of the flare and union before connect-   
					ing them together. This is effective for reducing gas   
					leaks. (Fig. 45)   
					c) For proper connection, align the union tube and   
					flare tube straight with each other, then screw in   
					the flare nut lightly at first to obtain a smooth   
					match. (Fig. 46)   
					Flare nut   
					Union   
					Fig. 46   
					16   
				5-4. Connecting Tubing between Indoor and   
					Outdoor Units   
					Torque wrench   
					a) Tightly connect the indoor side refrigerant tubing extend-   
					ed from the wall with the outdoor side tubing. (Fig. 47)   
					Spanner   
					Indoor unit   
					b) To fasten the flare nuts, apply specified torque as:   
					Table 5   
					Outdoor unit   
					Tube Dia.   
					Tightening Torque   
					Approx. 130 – 170 lbs. in. (150 – 200 kg cm)   
					Fig. 47   
					1/4" (6.35 mm)   
					3/8" (9.52 mm)   
					1/2" (12.7 mm)   
					5/8" (15.88 mm)   
					· 
					· 
					Approx. 300 – 340 lbs. in. (350 – 400 kg cm)   
					· 
					· 
					Approx. 430 – 470 lbs. in. (500 – 550 kg cm)   
					· 
					· 
					Approx. 520 – 560 lbs. in. (600 – 650 kg cm)   
					· 
					· 
					Insulation   
					5-5. Insulation of Refrigerant Tubing   
					IMPORTANT   
					Fig. 48   
					To prevent heat loss and wet floors due to dripping of con-   
					densation, both tubes must be well insulated with a prop-   
					er insulation material. (Fig. 48) The thickness of the insula-   
					tion should be a minimum 5/16" (8 mm). (Fig. 49)   
					Insulation   
					Thickness:   
					min. 5/16" (8 mm)   
					Min.   
					5/16" (8 mm)   
					After a tube has been insulated,   
					CAUTION   
					never try to bend it into a narrow   
					curve, as this may cause the tube to   
					break or crack.   
					Fig. 49   
					5-6. Taping the Tubes   
					a) At this time, the 2 refrigerant tubes (and electrical wire if   
					local codes permit) should be taped together with armor-   
					ing tape. The drain hose may also be included and taped   
					together as 1 bundle with the tubing.   
					Clamp   
					Insulated tubes   
					b) Wrap the armoring tape from the bottom of the outdoor   
					unit to the top of the tubing where it enters the wall. As   
					you wrap the tubing, overlap half of each previous tape   
					turn. (Fig. 50)   
					Fig. 50   
					c) Clamp tubing bundle to wall, using 1 clamp approx. every   
					47 in. (120 cm).   
					Apply putty here   
					NOTE   
					Do not wind the armoring tape too tightly, since this will   
					decrease the heat insulation effect. Also, be sure the conden-   
					sation drain hose splits away from the bundle and drips clear   
					of the unit and the tubing.   
					Tubing   
					5-7. Finishing the Installation   
					Fig. 51   
					After finishing insulating and taping over the tubing, use seal-   
					ing putty to seal off the hole in the wall to prevent rain and   
					draft from entering. (Fig. 51)   
					17   
				6. Air Purging   
					Indoor unit   
					Air and moisture remaining in the refrigerant system have   
					undesirable effects as indicated below. Therefore, they must   
					be purged completely.   
					I pressure in the system rises   
					I operating current rises   
					Outdoor unit   
					I cooling (or heating) efficiency drops   
					I moisture in the air may freeze and block capillary tubing   
					I water may lead to corrosion of parts in the refrigerant sys-   
					tem   
					I Air Purging with a Vacuum Pump (for Test Run)   
					(1) Check that each tube (both narrow and wide tubes)   
					between the indoor and outdoor units have been properly   
					connected and all wiring for the test run has been com-   
					pleted. Note that both narrow and wide tube service   
					valves on the outdoor unit are kept closed at this stage.   
					Manifold valve   
					(2) Using an adjustable wrench or box wrench, remove the   
					valve caps from the service valve on both narrow and   
					wide tubes.   
					Pressure   
					gauge   
					Lo   
					Hi   
					(3) Connect a vacuum pump and a manifold valve (with pres-   
					sure gauges) to the service port on the wide tube service   
					valve. (Fig. 52)   
					Be sure to use a manifold valve for   
					CAUTION   
					air purging. If it is not available, use   
					a stop valve for this purpose. The   
					“Hi” knob of the manifold valve   
					must always be kept closed.   
					(4) With the “Lo” knob of the manifold valve open, run the   
					vacuum pump. The operation time for the vacuum pump   
					varies with tubing length and the capacity of the pump.   
					The following table shows the amount of time for evacua-   
					tion:   
					Vacuum pump   
					Fig. 52   
					Table 6   
					Required time for evacuation when capacity   
					of 100 liter/h vacuum pump is used   
					If tubing length is   
					If tubing length is   
					less than 33 ft. (10 m)   
					more than 33 ft. (10 m)   
					10 min. or more   
					15 min. or more   
					NOTE   
					The required time in the above table is calculated based on   
					the assumption that the ideal (or target) vacuum condition is   
					around 10 mmHg abs.   
					18   
				(5) With the vacuum pump still running, close the “Lo”   
					knob of the manifold valve. Then stop the vacuum   
					pump.   
					90° (1/4 turn)   
					Narrow tube   
					(6) With the accessory hex wrench, turn the valve   
					stem on the narrow tube service valve counter-   
					clockwise by 90 degrees (1/4 turn) for 10 seconds,   
					and then turn the stem clockwise to close it again.   
					(Fig. 53)   
					Hex wrench   
					Wide tube   
					Be sure to completely insert   
					CAUTION   
					Valve cap   
					the hex wrench before   
					Vacuum hose to manifold valve   
					attempting to turn the valve.   
					Fig. 53   
					(7) Leak test all joints at the tubing (both indoor and   
					outdoors) with liquid soap. Bubbles indicate a leak.   
					Be sure to wipe off the soap with a clean cloth.   
					(8) With the hex wrench, turn the wide tube service   
					valve stem counter-clockwise to fully open the   
					valve.   
					(9) Turn the narrow tube service valve stem counter-   
					clockwise to fully open the valve.   
					(10) Loosen the vacuum hose connected to the wide   
					tube service port slightly to release the pressure.   
					Then, remove the hose.   
					(11) Replace the bonnet and flare nut on the wide tube   
					service port and fasten the flare nut securely with   
					an adjustable wrench or box wrench. Next, mount   
					the valve cap and tighten it with a torque wrench   
					(the cap needs to be tightened with the torque of   
					170 lbs.•in. (200 kg•cm)). This process is very   
					important to prevent gas from leaking from the   
					system.   
					(12) Test run the air conditioner. (See next page.)   
					(13) While the air conditioner is running, apply liquid   
					soap to check for any gas leaks around the ser-   
					vice valves or caps.   
					(14) If there is no leakage, stop the air conditioner.   
					(15) Wipe off the soap on the tubing.   
					This completes air purging with a vacuum pump and   
					the air conditioner is ready for actual operation.   
					19   
				* How to Test Run the Air Conditioner.   
					KHS0951, KHS1251   
					(1) Switch on the power source.   
					(2) Press the ON/OFF button on the remote control   
					unit once.   
					ON   
					OFF   
					TEST   
					(3) Set the operation selector switch of the indoor unit   
					to the TEST position. This starts the fan, producing   
					uncooled forced air. (Figs. 54a and 54b)   
					(4) After 3 minutes, the system shifts into cooling   
					operation, and cool air will start to be felt. Cooling   
					operation during with the switch at the TEST posi-   
					tion is unaffected by the room temperature.   
					(5) After stopping the test run, turn the operation   
					selector switch of indoor unit to the OFF position   
					once, then move to ON position.   
					OPERATION   
					TIMER   
					(6) Press the ON/OFF button on the remote control   
					unit to stop the air conditioner.   
					STANDBY   
					NOTE   
					If the unit does not operate and the OPERATION lamp   
					on the unit is blinking after going through the proce-   
					dure, check the wiring between the units.   
					Fig. 54a   
					KHS1852   
					Operation   
					selector   
					switch   
					ON   
					OFF   
					TEST   
					Fig. 54b   
					20   
				I Basic Function of the Service Valves   
					The basic function of the service valves are given in Table 7 below.   
					Table 7   
					Narrow Tube Service   
					Valve (2-Way)   
					Wide Tube Service   
					Valve (3-Way)   
					Action   
					O-ring   
					Valve cap   
					Stem   
					CLOSED   
					Shipping   
					Fully OPEN   
					Fully OPEN   
					CLOSED   
					Operating and   
					test running   
					the air conditioner   
					Measuring pressure   
					and gas charging   
					* 
					Air purging with   
					a vacuum pump   
					* 
					* The service port on the wide tube service   
					valve uses a Schrader core valve to access   
					the refrigerant system. Therefore, be sure to   
					use a hose connector which has a push-pin   
					inside. (Fig. 55)   
					Service valve   
					Hose with push-pin   
					PUSH   
					Fig. 55   
					I Pump Down   
					valve clockwise all the way to close the service   
					valve. (Be sure to confirm that the wide tube ser-   
					vice valve is fully open.)   
					Pump down means collecting all refrigerant gas in the   
					system back into the outdoor unit without losing any of   
					the gas. Pump down is used when the unit is to be   
					moved or before servicing the refrigerant circuit.   
					(3) Press the operation button and start cooling opera-   
					tion.   
					Pump Down Procedure   
					(4) When the low pressure gauge reading falls to 1 to   
					0.5 kg/cm2 (14.2 to 7.1 PSI), fully close the wide   
					tube valve stem with a standard screwdriver. Then   
					quickly stop the unit.   
					Be sure to carry out pump down with the unit in   
					cooling mode.   
					(1) Connect the Lo side charging hose of the manifold   
					valve to the service port on the wide tube service   
					valve.   
					(5) Disconnect all gauges and hoses, and replace the   
					bonnets and the valve caps as they were before.   
					(2) Using a hex wrench, turn the narrow tube service   
					21   
				7. Remote Control Unit Installation Position   
					The remote control unit can be operated from either a   
					non-fixed position or a wall-mounted position.   
					To ensure that the air conditioner operates correctly, do   
					not install the remote control unit in the following   
					places:   
					I In direct sunlight   
					I Behind a curtain or other place where it is covered   
					I More than 26 ft. (8 m) away from the air conditioner   
					I In the path of the air conditioner’s airstream   
					I Where it may become extremely hot or cold   
					I Where it may be subject to electrical or magnetic   
					interference   
					7-1. Mounting on a Wall   
					Truss-head   
					tapping screw   
					5/32 × 5/8" (4 × 16mm supplied)   
					1) Confirm the indoor unit beeps when the   
					ON/OFF button is pressed at the wall location   
					where the remote control unit is to be attached,   
					then attach the holder to the wall. (Fig. 56)   
					2) When taking out the remote control unit, pull it   
					from the holder.   
					Remote   
					control   
					unit holder   
					When using the remote control unit   
					• 
					Point the transmission portion of the remote   
					control unit at the receiver area of the indoor   
					unit when operating the remote control unit,   
					and during operation of the air conditioner.   
					Fig. 56   
					• 
					Do not place objects that may block the trans-   
					mitted signals between the receiver and the   
					remote control unit.   
					When mounting the remote control unit to   
					prevent theft   
					Truss-head   
					tapping screw   
					5/32 × 5/8" (4 × 16mm supplied)   
					1) Mount the holder to the wall with one of the   
					screws (using only the hole in the top of the   
					holder) (Fig. 57).   
					Holder   
					2) Remove the cover of the remote control unit   
					and take out the batteries. Next, place the   
					remote control unit in the holder.   
					3) Fasten both the remote control unit and holder   
					to the wall with the remaining screw (using the   
					hole in the bottom of the holder).   
					Holder   
					Fig. 57   
					4) Install the batteries in the remote control unit   
					and close the cover.   
					22   
				 |