		 SANYO AIR CONDITIONING PRODUCTS   
					DUCTLESS SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS   
					SPECIFICATIONS - SECTION 15700   
					Covers Sanyo System Models > 18XS52, 18XLS52 (See plans for specified models & details)   
					DUCTLESS SPLIT SYSTEM AIR CONDITIONERS - RECESSED CEILING MOUNT   
					1) GENERAL SPECIFICATIONS   
					Furnish & install a Sanyo manufactured Ductless, Split System Air Conditioner(s) consisting of an   
					indoor recessed ceiling mounted evaporator/blower section with four (4) way airflow & matching   
					outdoor condensing section. System(s) shall bear the ARI label showing that the system(s) is ARI   
					210 or 240 & 270 Certified. Systems shall be listed by ETL Testing Laboratories and bear the   
					ETL label. Matching systems shall meet or exceed the minimum, Federally mandated Seasonal   
					Energy Efficiency Rating (SEER) of 10, as certified by the ARI testing programs. System(s)   
					indoor & outdoor units will operate at sound levels equal to or below specified system(s) (see   
					plans). Installation & Owners Manuals shall be provided with each system.   
					Matching indoor & outdoor sections shall be connected by deoxidized, annealed refrigerant copper   
					tubing, type “L”, cleaned & capped. All systems shall have flared refrigeration connections on   
					both indoor & outdoor sections. Size & insulate tubing according to manufacturer’s specifications.   
					System(s) indoor & outdoor sections shall be completely factory assembled & wired, with a pre-   
					charge of refrigerant. A single power source shall provide voltage to both the outdoor & indoor   
					units. Electrical wire & connections to outdoor section, and between indoor & outdoor section(s),   
					shall be sized, installed & grounded by the installer in conformance with the National Electrical   
					Code (N.E.C.), local codes, as well as, manufacturer’s instructions.   
					System(s) shall be equipped with a microprocessor control system, utilizing an infrared remote   
					controller with LCD display that provides access to all system functions, and transmits room   
					conditions & programs to the indoor microprocessor every 3 minutes. Infrared remote controller   
					shall be capable of operating system mounted up to 26’ from the indoor section, according to   
					manufacturer’s recommendations & instructions. System(s) shall have the capability of continuous   
					operation in the case of a lost or damaged remote controller, utilizing a factory installed, integral   
					manual switch in conjunction with the system microprocessor.   
					1A) System Infrared Remote Controller Functions will include: system mode selection,   
					programmable temperature control, 24 hour programmable timer, one (1) hour off timer,   
					automatic three (3) speed indoor fan speed control, constant fan speed selection, night setback   
					mode, automatic sweep/flap control, user selectable room temperature sensor located on either   
					infrared remote controller or indoor unit, multiple system control using a single controller.   
					-1-   
				with overload protection, permanent lubrication & multi-speed capability. Unit(s) shall contain a   
					Printed Circuit Board (PCB) with a control circuit fuse & microprocessor, factory wired &   
					mounted, that receives & processes all commands & transmissions from the system Infrared   
					Remote Controller. Indoor unit(s) shall also contain an Operation Switch with visible lamps for   
					operation, standby & timer functions, as well as, a system test switch & a manual ON/OFF switch.   
					Unit(s) shall contain an air sensor thermistor, a coil freeze safety thermistor to prevent freeze-up, a   
					factory installed light-duty condensate drain pump, drain pan, hose & fitting, and refrigeration line   
					connections with flare nuts.   
					Indoor section shall be provided with a factory assembled concentric supply & return air grille   
					with a motorized louver/flap on each of the four (4) supply air openings. Motorized louvers/flaps,   
					controlled by the infrared remote controller, shall provide automatic, full oscillating supply   
					airflow, as well as being capable of being placed in a set, stationary position. Up to two (2) of the   
					supply air openings may be closed for ceiling perimeter or corner mounting, and to utilize   
					alternate plenum supply air option. Indoor Unit(s) will be furnished with an in-ceiling plenum,   
					which surrounds the evaporator coil section. Plenum shall contain alternate supply air knockout(s)   
					to allow for ducted airflow to a separate room. Unit(s) shall be capable of utilizing fresh, outside   
					air up to a maximum of 20% of the rated CFM of the system, with the field installed, optional   
					Fresh Air Intake Chamber manufactured by Sanyo. Unit(s) shall be furnished with long life (2,500   
					hour), anti-mold, poly type washable air filters that can be easily removed without removing   
					indoor unit casing. Indoor unit(s) shall be powered by voltage from the matching outdoor unit(s).   
					4) AVAILABLE SANYO ACCESSORIES – Recessed Ceiling Mount Models   
					Insulated Copper Line Sets, Condensate Pumps, Outdoor   
					Section Wall Mounting Bracket, Hard Wired Remote Controller, and Fresh Air Intake Chamber.   