| FOR YOUR SAFETY   If you smell gas:   1. Open windows.   ® 2. DO NOT try to light any appliance.   3. DO NOT use electrical switches.   4. DO NOT use any telephone in   your building.   Combat   5. Leave the building.   6. Immediately call your local gas   supplier after leaving the building.   Follow the gas suppliers   instructions.   7. If you cannot reach your gas   supplier, call the Fire Department.   UHA-Series   Tubular Unit Heaters   (Standard Range)   WARNING   Installation, Operation   & Service Manual   Models UHA[S]   150, 175, 200, 225   250, 300, 350, 400   Fire Hazard   Do not store or use gasoline or other   flammable vapors and liquids in the   vicinity of this or any other appliance.   Some objects will catch fire or explode   when placed close to heater.   Failure to follow these instructions can   result in death, injury or property   damage.   WARNING   Installer   Improper installation, adjustment, alteration, service   or maintenance can result in death, injury or property   damage. Read the Installation, Operation and Service   Manual thoroughly before installing or servicing   this equipment.   Please take the time to read and understand   these instructions prior to any installation.   Installer must give a copy of this manual to the owner.   Owner   Installation must be done by a contractor qualified   in the installation and service of gas-fired heating   equipment or your gas supplier.   Keep this manual in a safe place in order to provide   your serviceman with necessary information.   Roberts-Gordon, LLC   1250 William Street   P.O. Box 44   Buffalo, New York 14240-0044   Telephone: 716.852.4400   Fax: 716.852.0854   Toll Free: 800.828.7450   Quality in Any Language™   © Copyright 2007 Roberts-Gordon, LLC   P/N 111101NA 10/07 Rev. D   TABLE OF CONTENTS   SECTION 1: Heater Safety......................................................1 SECTION 11: User Instructions............................................22   SECTION 3: Critical Considerations .....................................3 SECTION 12: Servicing.........................................................24   3.9 Separated Combustion Installation..............................3 SECTION 13: Troubleshooting .............................................27   13.2 Troubleshooting For Automatic Ignition Burner   Systems...................................................................28   4.6 High Altitude ................................................................5 SECTION 14: Replacement Parts.........................................31   6.5 Vertical Venting............................................................8 SECTION 15: Specifications.................................................37   15.1 Standard (Models 150 - 400) UHA(S) Series   Dimension Data .........................................................37   7.2 Unvented Installation.................................................. 13 SECTION 16: The ROBERTS GORDON® COMBAT®   UHA-Series Warranty.....................................39   © 2007 Roberts-Gordon, LLC   All rights reserved. No part of this work covered by the copyrights herein may be reproduced   or copied in any form or by any means - graphic, electronic, or mechanical, including   photocopying, recording, taping or information storage and retrieval systems - without the   written permission of Roberts-Gordon, LLC.   Printed in U.S.A.   TABLE OF FIGURES   Figure 1: Installation Clearances and Clearances to   Combustibles.............................................................4   Figure 4: Standard Vented Heater - Vertical and   Horizontal Vent Termination ......................................9   Figure 5: Standard Vented Heater - Common Vertical Vent   Termination.............................................................. 10   Figure 6: Separated Combustion Heater - Vertical and   Horizontal Vent Termination .................................... 11   Figure 8: Concentric Vertical and Horizontal Vent   Termination - Separated Combustion Heater........... 12   SECTION 1: HEATER SAFETY   SECTION 1: HEATER SAFETY   Your Safety is Important to Us!   This symbol is used throughout   the manual to notify you of   possible fire, electrical or burn   hazards. Please pay special   attention when reading and   following the warnings in these   sections.   Installation, Service and Annual   Inspection of heater must be done by a contractor   qualified in the installation and service of gas-fired   heating equipment.   Read this manual carefully before installation,   operation or service of this equipment.   Heaters are not approved for residential installation.   These instructions, the layout drawing, local codes   and ordinances and applicable standards that apply   to gas piping, electrical wiring, venting, etc. must be   thoroughly understood before proceeding with the   installation.   Thin sheet metal parts, including the various venting   components, have sharp edges. To prevent injury,   the use of work gloves is recommended.   Before installation, check that the local distribution   conditions, nature of gas and pressure and   adjustment of the appliance are compatible.   1.1 Manpower Requirements   To prevent personal injury and damage to the   heater, two persons will be required for installation.   1 COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   SECTION 2: INSTALLER RESPONSIBILITY   The installer is responsible for the following:   2.2 Corrosive Chemicals   • To install the heater, as well as the gas and   electrical supplies, in accordance with applicable   specifications and codes. Roberts-Gordon   recommends the installer contact a Local   Building Inspector or Fire Marshal for guidance.   CAUTION   Do not use heater in an area containing corrosive   chemicals.   Avoid the use of corrosive chemicals to ensure a   longer life of the burner, heat exchanger and other   parts.   • To use the information given in a layout drawing   and in the manual together with the cited codes   and regulations to perform the installation.   Failure to follow these instructions can result in   property damage.   • To install the heater in accordance with the   clearances to combustibles.   Roberts-Gordon cannot be responsible for ensuring   that all appropriate safety measures are undertaken   prior to installation; this is entirely the responsibility   of the installer. It is essential that the contractor, the   sub-contractor, or the owner identifies the presence   of combustible materials, corrosive chemicals or   halogenated hydrocarbons* anywhere in the   premises.   • To furnish all needed materials not furnished as   standard equipment.   • To plan location of supports, vents and air   intakes.   • To provide access for servicing.   • To provide the owner with a copy of this   Installation, Operation and Service Manual.   • To never use heater as support for a ladder or   other access equipment and never hang or   suspend anything from heater.   * Halogenated Hydrocarbons are a family of chemical   compounds characterized by the presence of halogen ele-   ments (fluorine, chlorine, bromine, etc.). These compounds are   frequently used in refrigerants, cleaning agents, solvents, etc. If   these compounds enter the air supply of the burner, the life   span of the heater components will be greatly reduced. An out-   side air supply must be provided to the burners whenever the   presence of these compounds is suspected. Warranty will be   invalid if the heater is exposed to halogenated hydrocarbons.   • To ensure there is adequate air circulation   around the heater and to supply air for   combustion, ventilation and distribution in   accordance with local codes.   2.3 National Standards and Applicable Codes   2.1 Wall Tag   All appliances must be installed in accordance with   the latest revision of the applicable standards and   national codes. This refers also to the electric, gas   and venting installation. Note: Additional standards   for installations in public garages, aircraft hangars,   etc. may be applicable.   A laminated wall tag is included with the heater as a   permanent reminder of the safety instructions and   the importance of the required clearances to   combustibles. Affix the tag by peeling off the backing   of the adhesive strips on the rear surface and   position the tag on a wall near the heater.   A copy of the wall tag (P/N 91040031) is illustrated   on the back cover.   Know your model number. Model number is found   on the heater and in the Installation, Operation and   2 SECTION 3: CRITICAL CONSIDERATIONS   SECTION 3: CRITICAL CONSIDERATIONS   3.1 Basic Information   3.7 Electrical Supply   UHA(S) heaters have automatic ignition burners for A permanent 120 V 60 Hz 1 Ø electrical supply is   ON/OFF operation only.   required for the main electrical power. The heater   also requires suitable controls in accordance with   3.2 Location and Suspension   All models:   • Must be installed indoors.   3.8 Vent   Choose heater orientation to allow for the proper   location of the vent. Each heater must be fitted with   a correctly sized sealed vent system.   If vented horizontally, no other appliance may be   • Must be installed in a level position with   horizontal discharge.   • May be mounted on a shelf of non-combustible   material.   Figure 2) or from wall brackets of sufficient   strength to support the heater as listed in the   Drop rods must be a minimum of 3/8" diameter   mild steel. Four suspension points (3/8" nuts)   are located on top of the heater.   3.9 Separated Combustion Installation   For separated combustion installation, the vent and   air intake must be fitted with an individual and   correctly sized sealed system and the vent and air   intake must terminate at approved wall and roof   terminals.   • Must be installed in a manner which allows   access to all serviceable components.   See Page 4, Figure 1 for details.   Separated combustion units may not be common   3.3 Minimum Required Installation Clearances   Clearances around the heater and vent must be as   through Page 12, Figure 8 to ensure access for   servicing, and correct operation.   3.4 Clearances to Combustibles   Clearances must be as indicated on Page 4, Figure   1. If clearances to combustibles are not indicated,   then installation clearances apply.   3.5 Ventilation   It is important to ensure that there is adequate air   space around the heater to supply air for   combustion, ventilation and distribution in   accordance with local and national codes.   3.6 Gas Supply   It is important that the gas supply pipe is sized   correctly to provide the inlet pressure as stated on   the heater data plate. The gas supply pipe and   electrical connections must not support any of the   heater's weight.   3 COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   WARNING   Fire Hazard   Some objects will catch fire or explode when placed   close to heater.   Keep all flammable objects, liquids and vapors the   required clearances to combustibles away from heater.   Failure to follow these instructions can result in death,   injury or property damage.   Figure 1: Installation Clearances and Clearances to Combustibles   Installation Clearances   Clearances to Combustibles   Roof Terminal   (Optional separated   combustion concentric   venting shown.)   6"   (15 cm)   Top   31"   (79 cm)   6"**   (15 cm)   10'   (3 m)   24" for   Wall   Terminal   adequate   air flow access   axial fan.   3"   20' (6.0 m) - 30' (9.1 m)   Max. Mounting Height*   * Recommended mounting height varies with heater input.   Heaters may be mounted at a higher level if destratification   Clearance to Vent: 2" (5 cm)   fans are installed.   Note: Venting directly from top of heater not applicable   on Models 150 - 400.   **31" (79 cm) minimum is necessary   for servicing.   The heater must always be installed at least 6' (2 m) above the floor.   The vent pipe must have clearance from combustibles by 2" (5 cm).   If installed at low levels where individuals can come in contact with hot heat   exchanger components, adequate guarding must be provided.   4 SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES   SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES   4.1 Gas Codes   4.3 Parking Structures and Repair Garages   The type of gas appearing on the nameplate   must be the type of gas used. Installation must   comply with national and local codes and   requirements of the local gas company.   Installation in garages must be in accordance   with the following codes:   United States: Standard for Parking Structures   NFPA 88A - latest revision or the Code for Motor   Fuel Dispensing Facilities and Repair Garages,   NFPA 30A - latest revision. Canada: Refer to   CSA B149.1 Natural Gas and Propane   Installation Code.   United States: Refer to NFPA 54/ANSI Z223.1 -   latest revision, National Fuel Gas Code.   Canada: Refer to CSA B149.1 Natural Gas and   Propane Installation Code.   • In accordance with the Standard for Parking   Structures NFPA 88A, heaters must be located   a minimum of 18" (50 cm) below the floor-ceiling   assembly or 18" (50 cm) above the floor.   4.2 Aircraft Hangars   Installation in aircraft hangars must be in   accordance with the following codes:   • In accordance with the Code for Motor Fuel   Dispensing Facilities and Repair Garages,   NFPA 30A - latest revision, heaters must not be   installed less than 8' (2.4 m) above the floor.   United States: Refer to Standard for Aircraft   Hangars, NFPA 409 - latest revision.   Canada: Refer to Standard CSA B149.1 Natural   Gas and Propane Installation Code.   4.4 Electrical   • In aircraft storage and servicing areas, heaters   shall be installed at least 10' (3 m) above the   upper surface of wings or of engine enclosures   of the highest aircraft which may be housed in   the hangar. The measurement shall be made   from the wing or engine enclosure (whichever is   higher from the floor) to the bottom of the heater.   The heater must be electrically grounded in   accordance with the following codes:   United States: Refer to National Electrical   Code®, NFPA 70 - latest revision. Wiring must   conform to the most current National Electrical   Code®, local ordinances and any special   diagrams furnished.   • In shops, offices and other sections of aircraft   hangars communicating with aircraft storage or   servicing areas, heaters shall be installed not   less than 8' (2.4 m) above the floor.   Canada: Refer to Canadian Electrical Code,   CSA C22.1 Part 1 - latest revision.   • Suspended or elevated heaters shall be so   located in all spaces of aircraft hangars that they   shall not be subject to injury by aircraft, cranes,   movable scaffolding or other objects. Provisions   shall be made to assure accessibility to   suspended heaters for recurrent maintenance   purposes.   4.5 Venting   The venting must be installed in accordance   with the requirements within this manual and   the following codes:   United States: Refer to NFPA 54/ANSI Z223.1 -   latest revision, National Fuel Gas Code.   Canada: Refer to CSA B149.1 Natural Gas and   Propane Installation Code.   4.6 High Altitude   These heaters are approved for installations up   to 2000' (610 m) (US), 4500' (1370 m) (Canada)   without modification. Consult factory if US   installation is above 2000' (610 m) or Canadian   installation is above 4500' (1370 m).   5 COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   SECTION 5: MAJOR COMPONENTS   5.1 General   Heaters are designed for installation above 6'   (1.8 m). These heaters must be installed within the   heated space. Duct delivery systems are not   permitted with axial fan units. When handling or   supporting the heater from below, ensure that the   weight is taken at the support points.   5.2 Suspension   WARNING   Crush Hazard   Use 3/8" threaded rod   minimum.   Failure of the supports can   result in death, injury   or property damage.   Figure 2: Suspension Methods   Ensure all suspension   hardware is torqued to   a minimum of 20 ft lbs.   Unistrut   Channel Nut   Washer   Nut   3/8"   Threaded   Rod   Cone Point   Set Pin   Window   Clamp   3/8"   Threaded   Rod   Unistrut   Nut   Washer   Riv   Nut   Support Points   6 SECTION 6: VENTING   SECTION 6: VENTING   6.1 Venting   mechanical air supply inlet to any building.   The vent shall not terminate within 3' (.9 m) of a   This heater must be vented in accordance with the   rules contained in this manual and with the following window or door that can be opened in any building,   national codes and any state, provincial or local   codes which may apply: United States: Refer to   NFPA 54/ANSI Z223.1 - latest revision, National   Fuel Gas Code; Canada: Refer to CSA B149.1   Natural Gas and Propane Installation Code.   Any portion of vent pipe passing through a   combustible wall must have an listed thimble to   conform with the above codes.   any non-mechanical air supply inlet to any building,   or of the combustion air inlet of any other appliance.   6.2 Vent Installation   WARNING   The heater may be installed unvented in   certain circumstances according to building   ventilation codes. Refer to the above codes and   Page 8, Section 6.3 for further information.   Unvented operation also requires compliance with   the clearances to combustibles given on Page 4,   Fire Hazard   Some objects will catch fire or explode when placed   close to heater.   Keep all flammable objects, liquids and vapors the   required clearances to combustibles away from heater.   The bottom of the vent or air intake terminal shall not   be located less than 1' (.3 m) above grade level.   Failure to follow these instructions can result in death,   injury or property damage.   The vent shall not terminate less than 7' (2.1 m)   above grade where located adjacent to public   walkways.   For vented units, the vent must terminate outside of   the building.   Vent terminal must be installed at a height sufficient   to prevent blockage by snow and building materials   protected from degradation by flue gasses.   Vents must be fully sealed and correctly sized for   the model. If the vent passes through a wall or   ceiling of combustible material, it must be enclosed   by a listed thimble and be separated from the   thimble by at least a 2" (5 cm) air gap.   Vent terminal must be beyond any combustible   overhang.   For separated combustion models, vents and air   intakes must be a fully sealed system and correctly   sized for the model. Vent should be assembled as   Figure 8. The joints between the vent terminal and   the roof or wall must be properly sealed. If the vent   passes through a wall or ceiling of combustible   material, it must be enclosed by a listed thimble and   be separated from the thimble by at least a 2" (5 cm)   air gap.   Secure all joints with corrosion resistant #8 x 3/8"   sheet metal screws.   For single wall venting, pressure sensitive aluminum   tape or silicone sealant must be used to seal all   joints.   Aluminum tape shall have a minimum temperature   rating of 400° F (204° C) and meet SMACNA AFTS-   100-73 standards. High temperature silicone   sealant must have a minimum temperature rating of   480° F (250° C).   Vents and air intakes must be adequately   supported so that the heater does not bear the   weight of the pipes.   6.1.1 United States Requirements   Vent must terminate at least 3' (.9 m) above any   forced air inlet located within 10' (3.1 m).   Vent must terminate at least 4' (1.2 m) below,   4' (1.2 m) horizontally from, or 1' (.3 m) above any   door, operable window, or gravity air inlet into any   building.   6.2.1 Standard Vented Heaters   (Models UHA 150 - 400)   NFPA 54/ANSI Z223.1 - latest revision, National   Fuel Gas Code specifies a 4' (1.2 m) horizontal vent   terminal clearance from gas and electric meters,   regulators and relief equipment.   The vent must be fitted with a low resistance   Figure 4. Standard vented heaters do not allow   outdoor air intake for combustion air.   6.1.2 Canadian Requirements   The vent shall not terminate within 6' (1.8 m) of a   7 COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   6.2.2 Separated Combustion Heaters   (Models UHAS 150 - 400)   6.5 Vertical Venting   Vertically vented heaters can be common vented   (up to 4 heaters).   The heaters are designed to be installed as   separated combustion heaters. The vent and air   intake are run as separate pipes to the wall or roof   vent and air intake are run as separate pipes to a   concentric vent box and a concentric vent/air intake   pipe penetrates the wall or roof.   For vent lengths greater than 5' (1.5 m),   condensation will form. Insulation is recommended   and condensation drains may be desired. Vent from   the rear of the heater cabinet then run the vent   vertically and use a condensate drain at the bottom   of the vertical vent.   Vent pipe must be sloped 1/4'' (.6 cm) for every   1' (.3 m).   6.3 Unvented Operation   For 4'' (10 cm), an approved vent cap   (P/N 90502102) must be used.   WARNING   Carbon Monoxide Hazard   For 6'' (15 cm) common vent, an approved vent cap   (P/N 90502103) must be used.   Heaters installed unvented must   be interlocked with sufficient   building exhaust.   For common vertical venting of more than two   Heaters must be installed   according to the installation   manual.   A vent shall not extend less than 2' (.6m) above the   highest point where it passes through a flat roof of a   building.   Failure to follow these   instructions can result in death   or injury.   6.6 Length Requirements   For unvented operation in commercial installations,   sufficient ventilation must be provided in the amount   of 4 cfm per 1000 Btu/h firing rate (United States); 3   cfm per 1000 Btu/h firing rate (Canada).   If using vent lengths greater than 5' (1.5 m),   condensation will form in the vent pipe. Insulation   and additional sealing measures (high temperature   silicone at all seams) are required.   The entire vent should be insulated with foil faced   fiberglass insulation (1/2" thick, 1-1/2# density   minimum).   WARNING: Combustion by-products contain a   chemical known to the State of California to cause   cancer and birth defects or other reproductive   harm.   Maximum Vent Lengths Table   Model UHA(S)   # of Elbows   150 - 400   40 ft (12.2 m)   35 ft (10.7 m)   30 ft (9.1 m)   25 ft (7.6 m)   20 ft (6.1 m)   1 2 3 4 5 6.4 Horizontal Venting   Horizontally vented heaters must be individually   vented.   Vent pipe must be sloped ¼" (.6 cm) for every 1' (.3   m). For vent lengths greater than 5' (1.5 m),   condensation will form. Insulation is recommended   and condensation drains may be desired. For vents   pitched up toward the vent terminal, place the   condensation drain within 5' (1.5 m) of the heater.   In noncombustible walls only, vent terminal   (P/N 02537801-1P) may be used.   For 4'' (10 cm) vents in either combustible or   noncombustible walls, use vent terminal (P/N   90502100) or equivalent insulated vent terminal.   Follow the manufacturer's instructions for proper   installation.   Instead of an insulated vent terminal, a listed thimble   (with 2" air gap) may be used with a 4" vent cap (P/N   90502102).   8 SECTION 6: VENTING   6.7 Vent Material   Figure 3: Vent and Roof Detail   Vent material may be single wall 26 ga. (minimum)   galvanized steel or equal thickness stainless steel.   6.2.   Vent   Terminal   If penetrating a combustible wall or roof, a listed   thimble with 2" (5 cm) clearance must be used.   Where local codes permit, a single section of type   B-1 vent material may be used at the roof or wall   penetration instead of a thimble. Ensure vent   manufacturer's clearance from vent material is   maintained. Seal annular space of the type B-1 vent   as well as all joints in the remaining vent.   Flashing   or Rain Collar   Roof   Listed Thimble   Vent   2" Air Gap to   Combustible Material   Figure 4: Standard Vented Heater - Vertical and Horizontal Vent Termination   Vent Terminal   Flashing   (By Others)   Listed   Thimble   (2" Clearance)   4" Dia.Vent   Listed   Thimble   90°   Vertical   Option   (2" Clearance)   Bend   Flashing   (By Others)   Horizontal   Option   Vent   Vent   Terminal   12" (31 cm)   Minimum   Condensate   Trap to Drain   (Optional)   Note: Vent supports   not shown.   Model   Vent Diameter   Part Number   UHA 150 - 400   4" (10 cm)   90502102   9 COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   Figure 5: Standard Vented Heater - Common Vertical Vent Termination   Type "B" vent cap   (7" or 8") may be used.   (These are not available   from Roberts-Gordon.)   SIDE VIEW   Type "B" Vent Pipe   18" (46 cm)   Min.   Roof   Flashing   Roof   The last section of vent pipe   Approved   Thimble   passing through the roof or   wall may be Type "B" vent pipe.   All other vent materials in the   building must be single wall   vent pipe.   (If Applicable)   Single Wall Pipe   "D"   4" (10 cm)   Single Wall Pipe   4" (10 cm)   Single Wall Pipe   "D" Area must equal sum   of open area of   individual vents.   TOP VIEW   10   SECTION 6: VENTING   Figure 6: Separated Combustion Heater - Vertical and Horizontal Vent Termination   12" (31 cm)   Minimum from air inlet to vent   termination (may be horizontal   or vertical clearance).   Vent   Air Intake*   Vertical   Option   12" (31 cm)   Minimum from air inlet to vent   termination (may be horizontal   or vertical clearance).   Horizontal   Option   90°   Bend   Air Intake   Air Intake   Termination   Vent   Termination   Vent   12" (31 cm)   Minimum from wall   to vent termination.   Condensate   Trap to Drain   (Optional)   Model   UHAS 150 - 400   Model   UHAS 150 - 250   UHAS 300 - 400   Vent Diameter   4" (10 cm)   *Air Intake Diameter   4" (10 cm)   Terminal P/N   90502102   Terminal P/N   90502102   Listed Thimble through   Combustible Wall   5" (13 cm)   90502105   Note: Vent supports not shown   Figure 7: Concentric Vent Box   4" (10 cm) or   5" (13 cm)   Toward   Outside   Seal joint between single wall   and Type B vent with silicone sealant.   6" (15 cm) or 8" (20 cm)   Single Wall Inlet Air Pipe   (By Others)   Concentric   Vent Box   Use 3 sheetmetal   screws equally   spaced around joint.   Toward   Heater   Use 3 sheetmetal   screws equally   spaced around collar.   4" (10 cm) Single   Wall Vent Pipe   (By Others)   11   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   Figure 8: Concentric Vertical and Horizontal Vent Termination - Separated Combustion Heater   Vent Terminal   with Baffle Plate   4" Type B-1   Vent   UHA 150-250:   Storm Collar (By Others)   (Attach with 3 sheet metal screws.)   6" Dia. Single Wall   UHA 300-400:   8" Dia. Single Wall   Combustion   Air Terminal   Flashing   (By Others)   Concentric   Vent Box   6" (16 cm)   Minimum   Air Intake*   12" (31 cm)   Maximum   Vertical   Option   Vent   Condensate Trap   to Drain (Optional)   10' (3 m)   Maximum   Vent Terminal   4"   with Baffle Plate   Type   B-1   Vent   Horizontal   Option   Air Intake*   Concentric   Vent Box   Storm Collar (By Others)   (Attach with 3   sheet metal screws.)   Combustion   Air Terminal   Description   Part Number   UHVK1   Qty.   Concentric Vent Kit (150 - 250)   Concentric Vent Box Top & Side Assembly   Concentric Vent Box Bottom Assembly   Screw #6 x 3/8 Self Drilling   4" Vent Terminal with Baffle Plate   6" Combustion Air Terminal   90504113   90504112   91119100   90502102R   90502103   1 1 14   1 Model   UHAS 150 - 400   Model   UHAS 150 - 250   UHAS 300 - 400   Vent Diameter   4" (10 cm)   *Air Intake Diameter   4" (10 cm)   1 Description   Part Number   UHVK2   Qty.   5" (13 cm)   Concentric Vent Kit (300 - 400)   Concentric Vent Box Top & Side Assembly   Concentric Vent Box Bottom Assembly   Screw #6 x 3/8 Self Drilling   4" Vent Terminal with Baffle Plate   8" Combustion Air Terminal   90504013   90504012   91119100   90502102R   90502104   1 1 14   1 1 12   SECTION 7: AIR SUPPLY   SECTION 7: AIR SUPPLY   7.1 Separated Combustion Installation   When installed as a separated combustion heater,   the air for combustion is drawn in from outside the   building. It is important to ensure that there is   adequate space around heater to provide air for the   axial air distribution fan.   7.2 Unvented Installation   It is important to ensure that there is adequate fresh   air supply at all times for both combustion and   heating requirements in accordance with local and   national codes.   WARNING: Combustion by-products contain a   chemical known to the State of California to cause   cancer and birth defects or other reproductive   harm.   7.3 Building Ventilation   Where ventilation is required, air must be taken from   an outside point where it is not likely to be   contaminated or obstructed.   7.4 Outside Combustion Air Supply   If outside combustion air supply is required,   separated combustion model (UHAS) heaters must   be used.   IMPORTANT: If the building has a slight negative   pressure or corrosive contaminants such as   halogenated hydrocarbons are present in the air, an   outside combustion air supply to the heater is   required. Seal all combustion air pipe joints.   The air supply duct may have to be insulated to   prevent condensation on the outer surface. The   outside air terminal must not be more than 1' (31   cm) above the vent terminal.   7.4.1 Length Requirements   13   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   SECTION 8: GAS PIPING   • Meter and service must be large enough to   handle all the burners being installed plus any   other connected load. The gas pipe which feeds   the system must be large enough to supply the   required gas with a maximum pressure drop of   1/2" w.c. When gas piping is not included in the   layout drawing, contact the local gas supplier.   WARNING   • An isolating valve and union connection should   be used and fitted into the supply adjacent to the   heater.   Fire Hazard   Gas can leak if not installed properly.   • A minimum 1/8" NPT plugged tapping   accessible for test connection must be installed   immediately upstream of the gas supply   connection to the heater.   Failure to follow these instructions can result in death,   injury or porperty damage.   It is important that the gas supply pipe and the   electrical connections do not support any of the   heater’s weight.   A gas meter is connected to the service pipe by the   gas supply company. An existing meter should be   checked, preferably by the company, to ensure that   the meter is adequate for the rate of gas supply   required.   • For suspended heaters, an approved metal   flexible connection between the isolating valve   and the heater may be used. To reduce   pressure loss, use one pipe size larger than   the heater gas connection.   IMPORTANT - The complete installation must be   purged and tested for gas soundness in accordance   with local and national codes.   Installation pipes must be fitted in accordance with   local and national codes. Pipes of smaller size than   the heater inlet gas connection should not be used.   • Do not high pressure (in excess of 1/2 psi   [14" w.c.]) test the gas piping with the burner   connected. Close manual shut-off valve   during any pressure testing equal to or less   than 1/2 psi (14" w.c.). Failure to follow these   instructions can result in property damage.   Check the pipe and tubing ends for leaks before   placing heating equipment into service. When   checking for gas leaks, use a soap and water   solution; never use an open flame.   8.1 Connections   Connect the heater to the gas supply ensuring that   the final connections are as follows:   • Gas supply pipe work is run in medium or heavy   gauge tubing in compliance with local and   national codes.   Figure 9: Gas Connection   • Hold gas nipple   securely with pipe   wrench when   attaching the flex gas   connector.   Option A:   Stainless Steel   Do not bend flexible   Flex Gas   Connector   gas connector   sharply.   • Do not twist flexible   gas connector.   • Ensure all   joints are   gas tight.   Option B:   Medium or Heavy   Gauge Pipe   Gas Shut-off Valve   Gas Connector   Drip Leg   Cap   Union   Connection   14   SECTION 9: WIRING   SECTION 9: WIRING   codes in accordance with: United States: refer to   National Electrical Code® ANSI/NFPA 70 - latest   revision Canada: refer to Canadian Electrical Code   CSA C22.1 Part I - latest revision.   WARNING   9.1 Positioning Thermostats   A room thermostat or ROBERTS GORDON®   control should be mounted on a vibration-free wall or   column at a height of approximately 5' (1.5 m) from   the floor to measure the ambient temperature. It   should be clear of both cold drafts and the direct   path of warm air from the heater.   Avoid mounting thermostat on outside walls or in   areas directly exposed to radiant heat or sunlight.   Install wall tag in a visible location near thermostat.   Electrical Shock Hazard   Disconnect electrical power and gas supply before   servicing.   This appliance must be connected to a properly   grounded electrical source.   Failure to follow these instructions can result in   death or electrical shock.   All heater models require constant 120 V 60 Hz 1Ø   power supply. Check heater(s) rating plate for   electrical rating for proper circuit sizing. For   servicing, a disconnect switch of proper electrical   rating should be installed in the vicinity of the heater.   9.1.1 Fan Control   The heater’s axial fan can be used during the off-   season for air circulation. A low voltage thermostat   with fan control must be used. See Page 15, Section   9.2 for thermostat connection details.   All heaters are equipped with thermostat   connections suitable to power a 24 V thermostat.   Heater must be wired and electrically grounded in   accordance with local codes. In the absence of local   9.2 Low Voltage Thermostat with One Heater   24 Volt   Thermostat   Heating Only   Terminal   Strip   R G R W C W Electrical   Supply   24 Volt   Thermostat   with Fan Control   Terminal   Strip   R G R G W C W C Electrical   Supply   15   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   9.3 UHA(S) Series Internal Wiring Diagram   AXIAL FAN   AXIAL FAN (UH 300, 350, 400 ONLY)   BLACK   GREEN   WHITE   L2 L1   WHITE   BLACK   WHITE   GREEN   BLACK   BLOWER   BLACK   WHITE   GREEN   GREEN   GAS VALVE   3 1 BLACK   TRANSFORMER   BLUE   WHITE   GREEN   4 5 YELLOW   YELLOW   BLUE   BROWN   PRESSURE SWITCH   3 1 BLUE   2 5 6 4 ORANGE   ORANGE   R G W C LIMIT SWITCH   (UH 300, 350,   400 ONLY)   R = 24 VAC TO THERMOSTAT (RED)   G = MANUAL FAN INPUT FROM THERMOSTAT (GREEN)   ORANGE   ORANGE   W= HEAT DEMAND INPUT FROM THERMOSTAT (WHITE)   C = COMMON SIDE OF TRANSFORMER   LIMIT SWITCH   MANUAL RESET LIMIT SWITCH   (UH 30 - 125 ONLY)   IGNITION MODULE   THERMOSTAT INPUT: FIELD SUPPLIED   SENSE   ELECTRODE   BLACK   BLACK   BLACK   BLACK   ACC   CMB BLOWER   BLACK   L1   BLACK   NOTE:   For field wiring into service junction box, or if any of the original wire supplied with the heater   must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C   and 600 volts. For supply connections use No. 14 AWG or larger wires.   16   SECTION 9: WIRING   9.4 UHA(S) Series Ladder Wiring Diagram   120 VAC   UH 300, 350, 400 Only   CIRCULATION FAN   CIRCULATION FAN   COMBUSTION BLOWER   TRANSFORMER   GAS VALVE   PRESSURE SWITCH   2 5 3 1 FLAME   SENSOR   6 4 FLAME   SPARK   IGNITION   MODULE   LIMIT SWITCH (UH 300, 350, 400 ONLY)   LIMIT SWITCH   ELECTRODE   MANUAL RESET LIMIT SWITCH   (UH 30 - 125 ONLY)   THERMOSTAT CONNECTION   NOTE:   For field wiring into service junction box, or if any of the original wire supplied with the heater   must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C   and 600 volts. For supply connections use No. 14 AWG or larger wires.   17   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   9.5 Electrical Connection to the Heater   Flexible Conduit   BX Connector   Burner   L1   L2   Ground   Connect wires together   with suitable approved   wire connectors.   Junction Box   Green to Ground   White to L2   Black   White   Green   Black to L1   Note: Junction box is not provided with heater.   Conduit can also be attached directly to heater with wire junction made within the heater cabinet.   18   SECTION 10: OPERATION AND MAINTENANCE   SECTION 10: OPERATION AND MAINTENANCE   Installation, service, and annual inspection of the   heater must be done by a contractor qualified in the   installation and service of gas-fired heating   10.1.2 Electrical Checks   All pre-start-up checks must be carried out before   start-up the heater.   equipment. Read this manual carefully before   installation, operation, or service of this equipment.   All components are accessed via the door secured   by 4 sheet metal screws. Opening the door exposes   live electrical connections and hot components.   1. Check that all site wiring is connected in   accordance with the appropriate wiring diagram   10.1.3 Gas Supply   All aspects of the gas installation including the gas   meter must be inspected, tested for gas tightness   and purged in accordance with local and national   codes.   WARNING   Ensure that the air is fully purged from the heater   inlet pipe up to the main gas valve inlet test nipple.   10.1.4 Mechanical Checks   1. Check that the fan is free to run and   delivery louvers are turned to give required   air deflection.   Electrical Shock Hazard   2. Check that the flue (and air intake for separated   combustion units) is installed in accordance   with these instructions and local regulations.   Use extreme caution during start-up.   Controls compartment contains live electrical   connections.   Failure to follow these instructions can result in   death or electrical shock.   10.2 Begin Start-Up   10.2.1 Before Operating the Heater   To ensure that all the controls are in safe working   order, operate the heater for the first time with the   isolating gas valve turned off and power supply   turned on.   10.1 Pre-Start-Up Checks   All pre-start-up checks must be carried out   before lighting the heater.   Ensure that the heater and all controls are suitable   for the gas, pressure and electrical supply to which   they are to be connected.   1. Turn off the isolating gas valve.   2. Turn up the thermostat above room   temperature. The automatic ignition   sequence will now begin as described   10.1.1 Louvers   Where fitted, the air delivery louvers need to be set   during start-up to give the required air distribution   (optional vertical louvers).   There will be no ignition of the burner and lockout   will occur, which proves the controls are operating   correctly.   WARNING   Cut Hazard   Turn off gas and electrical supply before maintenance.   Fan can start automatically at any time.   Failure to follow these instructions can result in severe   injury or product damage.   19   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   Figure 10: Automatic Burner Control Sequence   Burner Sequence for Ignition Control   START   RUN   SHUT DOWN   Thermostat 24 V   Flue Fan   30 Sec. Purge*   NO   30 Sec. Post Purge   P Pressure   Switch   C NC   ts = 10 seconds   Ignition Spark   Start Gas Valve   Flame Signal   Axial Fan   30 Sec. Delay   90 Sec. Delay   *Purge time begins at pressure switch change over.   Required Incoming Signals   If at any stage the flame fails, the control will retry   for ignition. The control has four trials for ignition   before a one hour lockout.   Signals Output By Control   Figure 11: Gas Valve for Models UHA(S) 150 - 400   Top View   Regulator   End View   C ON   OFF   Outlet   Gas Inlet   Pressure   Description   Part Number   Gas Valve 150 - 225 NG   Gas Valve 150 - 225 LP   Gas Valve 250 - 400 NG   Gas Valve 250 - 400 LP   90032505   90032506   90032520   90032521   Inlet Pressure   20   SECTION 10: OPERATION AND MAINTENANCE   10.2.2 Start-Up the Gas Valve (All Gases)   10.2.2.1 Check Burner Gas Pressure   1. Remove the plug in the outlet (burner) pressure   test point and connect a pressure tap and a   manometer.   10.2.5 External Controls   External controls may include time switch, interlock   switch, room thermostat and frost thermostat.   Operate each control to ensure that they function   correctly. Set the switches (if fitted) and   thermostat(s) to the users’ requirements.   2. With the burner firing, measure the pressure on   the manometer. To adjust the burner pressure,   remove the regulator cover from the valve and   turn the regulator adjustment screw to set the   required burner pressure as stated in the   Technical Data Tables for the correct gas and   10.3 Complete the Start-Up   Ensure that all covers are fitted correctly and all test   points are properly sealed.   10.3.1 Instruction to the User   Explain the controls of the heater to the user   including how to turn it on and off, using the controls   fitted on site.   Give this manual to the user.   Ensure that the user is shown and understands the   importance of maintaining clearances to   combustibles and the user instructions on Page 22,   warnings defined in this manual.   NOTE: If the correct burner pressure cannot be   reached, then check the inlet pressure to the valve   Page 38, Section 15.3 for inlet pressure   requirement.   Do not continue to adjust the regulator if the   pressure is not changing.   If the inlet pressure is too low to allow correct burner   pressure setting, then the gas inlet pressure must be   corrected before completing the commission.   Check Gas Rate   1. After burner pressure adjustment, allow the   heater to operate for at least 15 minutes and   then re-check settings. Adjust pressure setting   if necessary.   2. Check gas flow rate at gas meter.   3. Turn off heater and electrical supply.   4. Remove the manometer and refit all covers to   the valve and tighten the screw of the outlet   pressure tap.   10.2.3 Pressure Switch   The pressure switch is factory pre-set for each   model and is not adjustable.   10.2.4 Turning Off the Heater   Set the thermostat to the "OFF" position or lowest   setting and the main burner will stop.   The fan will run until it is stopped automatically by   the fan thermostat.   Do not use a disconnect switch for control of   heater. Disconnect switch will turn off the fan.   Heat exchanger could be damaged. Warranty will   not cover damage to the heat exchanger if   operated improperly. Only use the disconnect   switch for turning off heater for service or during   off-season.   21   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   SECTION 11: USER INSTRUCTIONS   11.1 User Instructions   11.5 Simple Troubleshooting   The UHA(S) Series heaters are fully automatic and Some possible reasons for the heater not operating   operate from the external controls fitted on site.   are:   1. Gas supply not "ON".   2. Electricity supply not "ON".   WARNING   3. The time and/or temperature controls are not   "ON".   4. A limit switch may have operated. This may be   caused by an interruption of the electrical   supply, failure of the distribution fan or vent or   heat exchanger blockage.   Electrical Shock Hazard   If a temperature limit switch persistently trips, there   is a fault which must be investigated by a contractor   qualified in the installation and service of gas-fired   heating equipment.   Disconnect electrical power before servicing.   Failure to follow these instructions can result in   death or electrical shock.   11.2 Heater Operation   11.5.1 Simple Troubleshooting (Burner Faults)   When the heater has been switched on by the   thermostat installed on site, the main burner will   automatically turn on.   The burner control box will control the safe ignition   of the flame.   All heaters require a constant gas and electricity   supply which must not be interrupted during the   normal operation of this heater.   If the burner fails to ignite for any reason, it will retry   for ignition (4 trials total). After 4 unsuccessful   ignition trials, the control will put the heater into   lockout for 1 hour.   Lockout should not occur during normal operation of   the heater and indicates there is a fault condition   which must be corrected. There is an LED light on   the ignition control that flashes codes to assist in   codes.   11.3 Common User Controls   11.4 Lighting Instructions   Figure 12: LED Diagnostic Codes   11.4.1 To Turn On Heater   LED INDICATION FAULT MODE   1. Ensure that the electrical and gas supplies to   the heater are on. Check that the on site   controls are "ON".   Slow Flash   Fast Flash   2 Flashes   3 Flashes   4 Flashes   Normal Operation - No call for heat.   Normal Operation - Call for heat.   Ignition Lockout - No flame detected.   Airflow Fault - Pressure switch open or closed.   NOTE: The thermostat setting must be above the   ambient temperature for the heater to operate.   Temperature Limit or   Manual Reset Limit Switch Open   5 Flashes   Steady On   Flame Sense Error - Gas valve not energized.   Internal Control Failure   2. The automatic firing sequence will begin as   will now operate automatically under the control   of the on site controls.   11.4.2 To Turn the Heater Off   Set the thermostat to the "OFF" position.   The burner will turn off immediately.   The fan will continue to run for 90 seconds.   To restart, turn the thermostat above room   temperature.   22   SECTION 11: USER INSTRUCTIONS   FOR YOUR SAFETY   If you smell gas:   1. Open windows.   2. DO NOT try to light any appliance.   3. DO NOT use electrical switches.   4. DO NOT use any telephone in   your building.   5. Leave the building.   6. Immediately call your local gas   supplier after leaving the building.   Follow the gas suppliers   instructions.   7. If you cannot reach your gas   supplier, call the Fire Department.   WARNING   Fire Hazard   Do not store or use petrol or other   flammable vapours and liquids in the   vicinity of this or any other appliance.   Some objects will catch fire or explode   when placed close to heater.   Failure to follow these instructions can   result in death, injury or property   damage.   23   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   SECTION 12: SERVICING   12.1 Servicing Instructions   12.3 Fan/Motor Assembly Maintenance   After start-up, the heater will require maintenance to The main fan bearings are permanently sealed and   be carried out annually. If the heater is used in a   do not need lubrication. Before cleaning, turn off gas   dirty or dusty area, more frequent maintenance may and electrical supply. Remove the fan and use a   be necessary.   small brush or duster to clean the fan blades from   each side. Replace fan when done.   WARNING   12.4 Heat Exchanger Maintenance   The heat exchanger will remain clean unless a   problem has developed with combustion. Inspect the   heat exchanger. Look for signs of overheating at the   front tubes which may indicate burner over firing or   persistently low air flows.   Cut Hazard   12.5 Gas Valve Maintenance   Turn off gas and electrical supply before maintenance.   Fan can start automatically at any time.   No regular maintenance is required on this device.   Do not repair or disassemble gas valve.   Replace faulty gas valves with genuine   ROBERTS GORDON® replacement parts.   Failure to follow these instructions can result in severe   injury or product damage.   NOTE 1: After any maintenance or repair work,   always test fire the heater in accordance with the   are in working order before leaving the heater to   operate. Minor faults may be traced by using the   12.6 Combustion Fan   The combustion fan should not require   maintenance. However, if the air pressure switch is   causing burner lockout, then remove the combustion   fan from the vent box by unscrewing the three   screws at the mounting plate. Remove the four   screws attaching the mounting plate to the fan inlet   free to run and that the fan wheel is clean.   NOTE 2: Check all gas pipes and pipe joints to   ensure there are no cracks or gas leaks. Any cracks   in the pipes or pipe joints must be repaired.   12.7 Venting and Air Intake Pipe   Inspect all venting and air intake pipe. Ensure that   all seams are sealed and suspension points secure.   Repair suspension points if any part of the venting   or combustion air pipe is sagging. Check to make   sure any insulation is not missing or in poor   condition. Replace as necessary. Check all venting   and air intake components to ensure they are in   good condition, gas tight and corrosion-free.   NOTE 3: Inspect all suspended components and   hardware. Ensure that they are in good condition,   properly tightened, and corrosion free.   12.2 Burner Maintenance   1. Open the door and remove the burner compart-   2. Clean any deposits from the main burner which   may have formed in the injectors or venturi of   3. Remove the ignition electrode and flame probe.   Check condition of ignition electrode and flame   probe. Clean off any deposits which may have   been formed, check condition of ceramic   insulators. Replace as necessary.   24   SECTION 12: SERVICING   12.8 Maintenance Checklist   Installation Code and Annual Inspections: All   installations and service of ROBERTS GORDON®   equipment must be performed by a contractor   qualified in the installation and service equipment   sold and supplied by Roberts-Gordon and conform   to all requirements set forth in the ROBERTS   GORDON® manuals and all applicable   WARNING   governmental authorities pertaining to the   installation, service and operation of the equipment.   Explosion Hazard   Service and annual inspection must be done by a   contractor qualified in the installation and service of   gas-fired heating equipment or your gas supplier.   To help facilitate optimum performance and safety,   Roberts-Gordon recommends that a qualified   contractor annually inspect your ROBERTS   GORDON® equipment and perform service where   necessary, using only replacement parts sold and   Turn off gas and electrical supplies before performing   service or maintenance.   Failure to follow these instructions can result in death, supplied by Roberts-Gordon.   injury or property damage.   The Vicinity of the Heater Do not store or use flammable objects, liquids or vapors near the heater.   Immediately remove these items if they are present.   Vehicles and Other   Objects   Maintain the clearances to combustibles.   Do not hang anything from, or place anything on, the heater.   Make sure nothing is lodged in between the heat exchanger or in the louvers.   Immediately remove objects in violation of the clearances to combustibles.   Vent Pipe/Terminals   Venting must be intact. Using a flashlight, look for obstructions, cracks on the   pipe, gaps in the sealed areas or corrosion.   The area must be free of dirt and dust.   Remove any carbon deposits or scale using a wire brush.   If the vent terminal has a screen built in, remove any dirt, dust or deposits   from the screen.   Combustion Air Intake   Pipe   Intake pipe and inlet must be intact. Look for obstructions, cracks on the pipe,   gaps in the sealed areas or corrosion.   The area must be free of dirt and dust. Clean and reinstall as required.   Heat Exchanger   Make sure there are no cracks.   Make sure there is no sagging, bending or distortion.   Clean or replace as required.   Gas Line and Shut-off   Valves   25   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   Burner Observation   Window   Make sure it is clean and free of cracks or holes.   Clean and replace as required.   Combustion Fan Scroll,   Wheel and Motor   Compressed air or a vacuum cleaner may be used to clean dust and dirt.   Inshot Burners and   Orifices   Clear of obstructions (even spider webs will cause problems).   Carefully remove any dust and debris from the burner.   Direct-Spark Igniter   Replace if there are cracked ceramics, excessive carbon residue, or erosion   of the electrode.   The electrode gap should be 1/8" (3.2 mm).   Thermostat   There should be no exposed wire or damage to the device or wiring.   Suspension Points   Make sure the heater is hanging securely.   Look for signs of wear on the suspension materials or ceiling.   Silicone Tubing   Gas Valve   Ensure tight, secure fit on all pressure fittings at pressure switch,   burner partition, and blower outlet.   Verify that cap covering pressure regulator adjustment screw is secure and   has not been tampered with.   Verify all wiring connections.   Condensate Drain   (when installed)   Flush drain and clear any obstructions.   26   SECTION 13: TROUBLESHOOTING   SECTION 13: TROUBLESHOOTING   13.1 General   WARNING   Explosion Hazard   Installation must be done by a registered installer/   contractor qualified in the installation and service of   gas-fired heating equipment or your gas supplier.   Failure to follow these instructions can result in death,   injury or property damage.   Start   Are gas & electrical   supplies on?   No   Turn on supplies.   Yes   Wait 10-15 minutes for limit   switch to cool. Does fan   stop running?   Does axial fan run   immediately upon supplying   power to heater?   Fan and limit switch are   operating normally.   Yes   Yes   No   Replace temperature   limit switch.   No   Burner has locked out due   to ignition failure. Use   Troubleshooting for Automatic   Ignition Burner Systems   section to test burner.   Is ignition control showing a   "2 flashes" led code?   Yes   No   No   Use Troubleshooting for   Combustion Fan section to   test fan.   Does the combustion   fan run?   Yes   With external controls (i.e.   thermostat) on, does the   burner continue through the   heating cycle?   The limit switch has   tripped. See Manual Reset   Limit Switch Figure.   Has burner Locked Out?   Yes   No   No   Replace limit switch.   No   Yes   Use Troubleshooting for   Automatic Ignition Burner   Systems section to test burner.   Ensure proper air flow   clearance for axial fan.   Open louvers slightly.   Replace axial fan if it does   not operate.   Yes   If problems persist, contact   Roberts-Gordon, LLC at   Heater Operating   TROUBLESHOOT ENDS.   No   27   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   13.2 Troubleshooting For Automatic Ignition Burner Systems   WARNING   Start   Are gas & electrical   Turn on supplies.   Turn on controls.   No   No   supplies on?   Yes   Electrical Shock Hazard   Are external controls   (i.e. Thermostat) on?   Do not touch ignition components.   Voltage from ignition components is high.   Yes   Failure to follow these instructions can   Press in reset button on   manual reset limit switch   result in death or electrical shock.   Is ignition control showing   a "4 flashes" led code?   Yes   No   No   Is 120 V supply at fan   connections?   Does flue fan run?   Yes   Flue fan faulty; replace   No   Burner control faulty or wiring   connections faulty. Repair   or replace as necessary   Yes   Check for too much vent/air inlet duct. Check for blockage in   vent and combustion air circuit. Check for faulty air pressure   switch. Check pressure switch hoses for leaks or cracks.   Do not attempt to circumvent pressure switch circuit to   place unit in operation.See Pressure Switch section for details.   Does air pressure switch   change over?   No   Yes   Is ignition lead okay and   connected?   Ignition control faulty;   replace.   Wait 30 - 40 seconds.   No   No   Yes   Yes   No   Does ignition spark operate?   Is spark electrode okay?   See Ignition Control section.   Yes   Is the gas valve operating?   To test valve, See   Troubleshooting for Gas   Valves section.   Replace valve.   Does the flame light?   Yes   Trace fault in supervision   system. See   Troubleshooting   for Flame Supervision   System section.   Is the flame current at   least 1 µAmp DC when   the flame ignites?   Is ignition control showing   a "2 flashes" led code?   Yes   No   If problems persist, contact   Roberts-Gordon, LLC at   Heater Operating   TROUBLESHOOT ENDS.   No   For your safety and optimum heater performance,   use only ROBERTS GORDON® replacement parts.   Conduct start-up procedure as shown on Page   28   SECTION 13: TROUBLESHOOTING   13.3 Troubleshooting for Flame Supervision System   To measure flame current, connect a 0 - 50 μA DC meter in   series with the flame probe. If the meter reads negative   values, then reverse the test leads.   START   Connect a DC ammeter in   series with the flame probe.   Use General   Troubleshooting section to   trace the fault.   Is the flame present and   at least 1 µA DC flame   current?   No   Yes   Yes   Yes   Is the connecting lead   damaged? Is the flame probe   damaged or touching earthed   components?   Is there a current flowing in the   flame probe circuit with no   flame present?   Repair or replace as   necessary.   Yes   No   Is inlet burner gas pressure   correct? Is live and neutral   polarity correct? Is   Does lockout occur when   there is a flame present?   Yes Replace ignition control.   flame probe circuit correct?   No   Repair or replace as   necessary.   No   If problems persist, contact   Roberts-Gordon, LLC at   Heater Operating   TROUBLESHOOT ENDS.   No   NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.   29   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   13.4 Troubleshooting for Gas Valves   START   Is gas pressure at inlet of the   valve correct for gas type?   Note pressure found.   Fault elsewhere.   No   No   Correct pressure problem.   Yes   Valve or ignition control   faulty. Replace with   one of correct type.   Does gas pressure at outlet   of the valve rise when   valve turns on?   Yes   Does gas pressure at   outlet of valve return to zero or   lower when valve turns off?   Valve faulty.   Replace with one of   correct type.   No   No   Yes   If problems persist, contact   Roberts-Gordon, LLC at   Valve Operating   TROUBLESHOOT ENDS.   13.5 Troubleshooting for Combustion Fan   START   Does combustion fan run   automatically when there   is a call for heat?   Correct power   supply problem.   No   Yes   Fan motor faulty.   Replace with correct type.   Yes   Does fan turn on and   off while burner is firing   continously?   Check fan motor leads for   loose connections.   Yes   No   If problems persist, contact   Roberts-Gordon, LLC at   Fan Operating   TROUBLESHOOT ENDS.   No   For your safety and optimum heater performance,   use only genuine ROBERTS GORDON® replacement parts.   30   SECTION 14: REPLACEMENT PARTS   SECTION 14: REPLACEMENT PARTS   See warnings and notes on Page 24, Section 12   before removing or replacing parts.   Burner Components   All serviceable burner parts are accessed by the   door on the side of the heater. Remove the   sheetmetal screws.   14.1 Gas Valve   Remove the gas supply pipe at the heater inlet.   C ON   OFF   Description   Part Number   Gas Valve, NG (Models UHA[S] 150 - 225)   Gas Valve, LP (Models UHA[S] 150 - 225)   Gas Valve, NG (Models UHA[S] 250 - 400)   Gas Valve, LP (Models UHA[S] 250 - 400)   90032505   90032506   90032520   90032521   remove gas valve/manifold.   Replace in reverse order. Verify that the gas flow   direction of the valve is correct. Use a minimum   amount of gas seal on the thread joint. Check that   all the joints are leak free. Reset gas valve. See   IT IS IMPORTANT THAT ONLY THE CORRECT   GAS VALVE IS USED WHEN REPLACING THESE   CONTROLS.   31   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   14.2 Burner Compartment   The burner compartment is   a sealed compartment.   Following any work,   Burner   compartment   cover   re-seal the compartment   with the gas pipe rubber   seal fully in place and all   screws fitted and tight.   Flame probe   Viewing port   for flame probe   Remove flexible   air duct from spigot   Ignition electrode   Viewing port   for ignition electrode   Remove   access plate   Rubber Seal   Remove screws and   pull off burner cover   14.2.1 Burner Injectors   Ensure gas tight fitting of injectors.   Ensure correct alignment with burners.   Ensure all pipe joints are gas tight.   Manifold   Burners   Injectors   Remove manifold   screws and pull   out manifold   Manifold   Unscrew   Injectors   Burner   Screws   Marking   Folded   Hem   UHA[S]   150   UHA[S]   175   UHA[S]   200   UHA[S]   225   UHA[S]   250   UHA[S]   300   UHA[S]   350   UHA[S]   400   Orifice Quantity   Natural Gas (G20)   Orifice Marking   7 8 9 10   11   12   14   14   43   43   2.25 mm   2.25 mm   2.25 mm   40   40   40   RG P/N   91930043   91930043   91930225   91930225   91930225   91930040   91930040   91930040   Propane (G31)   Orifice Marking   RG P/N   1.35 mm   1. 35 mm   54   54   54   1.45 mm   53   53   91930135   91930135   91930054   91930054   91930054   91930145   91930053   91930053   32   SECTION 14: REPLACEMENT PARTS   14.3 Ignition Electrode and Flame Probe   Burners   Limit   Thermostat   Flame   Probe   Flame   Probe   Remove all   burner compartment   screws to remove   the burner   Remove   Screw   compartment and   access the   "Front View".   Burner Compartment   Front Views   Ignition   Electrode   Ignition   Electrode   .120   (3 mm)   spark   gap   Burners   To replace the electrode or flame probe, remove the electrical lead and screw.   Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the   front view of the burner compartment.   Description   Spark Electrode   Part Number   90427411   90439300   92000001   92000002   90412103   90412105   Qty.   1 1 1 1 Automatic Ignition Flame Probe   Inshot Burners (150, 175)   Inshot Burners (200 - 400)   Limit Switch (150 - 400)   Limit Switch (300 - 400)   1 2 33   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   14.4 Combustion Fan Vertical Installation   Remove screws securing outlet   flange to the flue adapter.   Rear Panel   Flue Adapter   to Flue Fan   screws   Hole   Refit in reverse order.   Vent Box   Flue   Adapter   Vent Box   Screws   Outlet   Gasket   Flue Fan   Disconnect   electrical connections   at plug in tabs.   Remove screws securing flue   fan mounting plate to vent box.   Remove screws securing   mounting plate to fan.   Vent Box   Mounting   Plate   Refit in reverse.   Mounting Plate   to Vent Box   Screws   Use new gaskets.   Ensure sealed joints.   Ensure mounting plate orifice is   clear and not obstructed.   Gasket   Gasket   Mounting Plate   to Flue Fan   Screws   Air Plate   UHA[S]   150 - 175   UHA[S]   200 - 300   UHA[S]   350 - 400   Exhaust Fan P/N   90710405   90710403   90710402   IT IS IMPORTANT THAT ONLY THE CORRECT COMBUSTION FAN SPECIFIED FOR EACH MODEL   TYPE IS USED WHEN REPLACING THESE ITEMS.   34   SECTION 14: REPLACEMENT PARTS   14.5 Pressure Switch   Pull off 3 way connector. Spring open plastic clips of   mounting cradle. Replace with correct type of   pressure switch for model. The pressure switches   are color coded for each pressure setting.   WARNING   Carbon Monoxide Hazard   Use correct pressure switch specified for each model.   Use of incorrect pressure switch or disabling   pressure switch circuit could cause unsafe condition.   Failure to follow these instructions can result in   death or serious injury.   Carry out a commission after working on or   changing a pressure switch. See Page 19, Section   UHA[S]   UHA[S]   UHA[S]   250   UHA[S]   UHA[S]   400   P/N   150 - 175   200 - 225   300 - 350   90439802   yellow   .32   90439808   orange   .79   90439803   gray   90439807   brown   .68   90439808   orange   .79   Color Code   Set Point in. w.c.   .41   35   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   14.6 Ignition Control   14.8 Limit Switches   The control mounts to the electrical plate. Pull out   ignition cable and wiring from board, noting their   positions.   Release the four mounting standoffs.   Refit in reverse. Ensure correct location of ignition   cable and all other wiring.   14.8.1 Removal and Replacement   1. Remove the electrical connections to the   switch.   2. Unscrew the two screws securing the   switch.   3. Fit a new switch with two screws.   14.7 Axial Fan/Guard/Motor Assembly   The axial fan unit for the heater is supplied   completely assembled and balanced.   4. Reconnect the electrical connections and test   operation.   14.7.1 Fan Removal and Replacement   Remove the mounting hardware.   Description   Part Number   Qty.   1 1 Axial Fan UHA[S] 150 - 175   Axial Fan UHA[S] 200 - 250   Axial Fan UHA[S] 300 - 400   90710416   90710417   90710416   2 14.7.2 To Replace the Fan Assembly   To replace the fan assembly, reverse the procedure   shown above.   • Check that the fan blades are free to rotate   before turning on the power to the fan.   • Strictly comply with the color code of the fan   wires to ensure correct operation. See Page 16,   Section 9.3 wiring diagram.   • Use only genuine ROBERTS GORDON®   replacement parts.   36   SECTION 15: SPECIFICATIONS   SECTION 15: SPECIFICATIONS   15.1 Standard (Models 150 - 400) UHA(S) Series Dimension Data   Top View   Heater must be supported   at these points from above   or below.   C E D 77   Support   Centers   4 x 3/8" Captive Nuts Provided   19 3/8"   (49 cm)   End View   25 1/2" (65 cm)   I Z Rear View   Air Intake   (UHAS only)   F G B H Flue   Lockout Reset   Electrical   Cable Entry   Gas   Supply   6 1/2"   (17 cm)   A UHA[S] UHA[S]] UHA[S]   UHA[S]   225   UHA[S]   250   UHA[S]   300   UHA[S]   350   UHA[S]   400   Model   150   175   200   in   (cm)   in   (cm)   in   (cm)   in   (cm)   in   (cm)   in   (cm)   42.4   (108)   26.9   (68)   17.7   (45)   12.3   (31)   12.4   (32)   15.5   (39)   42.4   (108)   26.9   (68)   17.7   (45)   12.3   (31)   12.4   (32)   15.5   (39)   42.4   (108)   35.2   (89)   17.7   (45)   12.3   (31)   12.4   (32)   17.5   (44)   42.4   (108)   35.2   (89)   17.7   (45)   12.3   (31)   12.4   (32)   17.5   (44)   42.4   (108)   35.2   (89)   17.7   (45)   12.3   (31)   12.4   (32)   17.5   (44)   52.3   (133)   43.5   (110)   24.7   (63)   12.3   (31)   15.3   (39)   13.8   (35)   52.3   (133)   43.5   (110)   24.7   (63)   12.3   (31)   15.3   (39)   13.8   (35)   52.3   (133)   43.5   (110)   24.7   (63)   12.3   (31)   15.3   (39)   13.8   (35)   A B C D E F G H I Width   Height   Support Spacing   Support Spacing   Support Spacing   Centre of Flue   Centre of   Flue/Air Intake   in   (cm)   5.5   (14)   5.5   (14)   6.4   (16)   6.4   (16)   6.4   (16)   7 (18)   7 (18)   7 (18)   in   (cm)   in   (cm)   in   (cm)   8.2   (21)   5.8   (15)   34   (86)   8.2   (21)   5.8   (15)   34   (86)   8.8   (22)   5.8   (15)   34   (86)   8.8   (22)   5.8   (15)   34   (86)   8.8   (22)   5.8   (15)   34   (86)   11   (28)   5.8   (15)   34   (86)   11   (28)   5.8   (15)   34   (86)   11   (28)   5.8   (15)   34   (86)   Position of Flue   Gas Inlet Position   Length   Z 37   COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   15.2 General Technical Data Table (All Models)   UHA[S] UHA[S] UHA[S] UHA[S] UHA[S] UHA[S] UHA[S] UHA[S]   150   175   200   10.6   3716   225   10.6   3716   250   10.6   3716   300   350   400   Full Load Amps @ 115 V   Air Volume   A 5.8   5.8   11.6   11.6   11.6   CFM   2245   2245   4663   4663   4663   Flue and AIr Intake   Flue Intake Size   Air Intake Size   in (cm) 4 (10)   in (cm) 4 (10)   4 (10)   4 (10)   40 (1)   4 (10)   4 (10)   40 (1)   4 (10)   4 (10)   40 (1)   4 (10)   4 (10)   40 (1)   4 (10)   5 (13)   40 (1)   4 (10)   5 (13)   40 (1)   4 (10)   5 (13)   40 (1)   *Maximum Straight Flue/Air Intake ft (m)   40 (1)   *Do not exceed the maximum length of flue stated or heater may not operate properly.   15.3 Technical Data Table (All Models)   UHA[S] UHA[S] UHA[S] UHA[S] UHA[S] UHA[S] UHA[S] UHA[S]   150   150   123   82   175   200   200   164   82   225   225   184.5   82   250   250   205   82   300   300   246   82   350   350   287   82   400   385   315.7   82   Total Input   Total Output   Efficiency   (Btu/h) x (1000)   (Btu/h) x (1000)   % 175   143.5   82   Natural Gas (G20) Data - Inlet Pressure 5.0 in w.c. Min., 14 in w.c. Max.   Burner Pressure in. w.c. 3.2 3.4 3.7   3.7   4.0   2.7   9.4   2.5   9.3   3.3   LPG / Propane (G31) Data - Inlet Pressure Inlet Pressure 12.0 in w.c. Min., 14 in w.c. Max.   Burner Pressure in. w.c. 9.9 10.4 10.5 10.7 10.7   11.1   38   SECTION 16: THE ROBERTS GORDON® COMBAT® UHA-SE-   SECTION 16: THE ROBERTS GORDON®   COMBAT® UHA-SERIES WARRANTY   ROBERTS-GORDON WILL PAY FOR:   Within 24 months from date of purchase by buyer or 27   months from date of shipment by Roberts-Gordon   (whichever comes first), replacement parts will be   provided free of charge for any part of the product which   fails due to a manufacturing or material defect.   The data plate and/or serial number are removed,   defaced, modified or altered in any way.   The ownership of the ROBERTS GORDON® COMBAT®   UHA-Series is moved or transferred. This warranty is   nontransferable.   Roberts-Gordon is not permitted to inspect the damaged   controller and/or component parts.   READ YOUR INSTALLATION, OPERATION AND   SERVICE MANUAL   If you have questions about your controller, contact your   installing professional. Should you need Replacement   Parts or have additional questions, call or write Roberts-   Gordon:   U.S.A.   1250 William Street   P. O. B ox 4 4   Roberts-Gordon will require the part in question to be   returned to the factory. Roberts-Gordon will, at its sole   discretion, repair or replace after determining the nature   of the defect and disposition of part in question.   ROBERTS GORDON® Replacement Parts are warranted   for a period of 18 months from date of shipment from   Roberts-Gordon or the remaining ROBERTS GORDON®   COMBAT® UHA-Series warranty.   Buffalo, New York 14240-0044   716.852.4400   On the web at: www.rg-inc.com   ROBERTS-GORDON WILL NOT PAY FOR:   Service trips, service calls and labor charges.   Shipment of replacement parts.   Roberts-Gordon's liability, and your exclusive   remedy, under this warranty or any implied warranty   (including the implied warranties of merchantability   and fitness for a particular purpose) is limited to   providing replacement parts during the term of this   warranty. Some jurisdictions do not allow limitations on   how long an implied warranty lasts, so this limitation may   not apply to you. There are no rights, warranties or   conditions, expressed or implied, statutory or otherwise,   other than those contained in this warranty.   Claims where the total price of the goods have not   been paid.   Damage due to:   • Improper installation, operation or maintenance.   • Misuse, abuse, neglect, or modification of the   ROBERTS GORDON® COMBAT® UHA-Series in any   way.   • Use of the ROBERTS GORDON® COMBAT® UHA-   Series for other than its intended purpose.   Roberts-Gordon shall in no event be responsible for   incidental or consequential damages or incur liability   for damages in excess of the amount paid by you for   the ROBERTS GORDON® COMBAT® UHA-Series.   Some jurisdictions do not allow the exclusion or limitation   of incidental or consequential damages, so this limitation   or exclusion may not apply to you. This warranty gives   you specific legal rights, and you may also have other   rights which vary from jurisdiction to jurisdiction.   • Incorrect gas or electrical supply, accident, fire, floods,   acts of God, war, terrorism, or other casualty.   • Improper service, use of replacement parts or   accessories not specified by Roberts-Gordon.   • Failure to install or maintain the ROBERTS   GORDON® COMBAT® UHA-Series as directed in the   Installation, Operation and Service manual.   • Relocation of the ROBERTS GORDON® COMBAT®   UHA-Series after initial installation   • The use of the ROBERTS GORDON® COMBAT®   UHA-Series in a corrosive atmosphere containing   contaminants.   • The use of the ROBERTS GORDON® COMBAT®   UHA-Series in the vicinity of a combustible or   explosive material.   • Any defect in the ROBERTS GORDON® COMBAT®   UHA-Series arising from a drawing, design, or   specification supplied by or on behalf of the   consumer.   • Damage incurred during shipment. Claim must be   filed with carrier.   Roberts-Gordon shall not be responsible for failure to   perform under the terms of this warranty if caused by   circumstances out of its control, including but not limited   to war, fire, flood, strike, government or court orders, acts   of God, terrorism, unavailability of supplies, parts or   power. No person is authorized to assume for Roberts-   Gordon any other warranty, obligation or liability.   LIMITATIONS ON AUTHORITY OF   REPRESENTATIVES:   No representative of Roberts-Gordon, other than an   Executive Officer, has authority to change or extend these   provisions. Changes or extensions shall be binding only if   confirmed in writing by Roberts-Gordon's duly authorized   Executive Officer.   WARRANTY IS VOID IF:   The ROBERTS GORDON® COMBAT® UHA-Series is not   installed by an electrician qualified in the installation and   service of control systems for heating equipment.   You cannot prove original purchase date and required   annual maintenance history.   39   Attach this information to the wall near the ROBERTS GORDON® heater   ® Read the Installation, Operation and Service Manual thoroughly before installation, operation or service.   OPERATING INSTRUCTIONS   WARNING   1. STOP! Read all safety instructions on this information sheet.   2. Open the manual gas valve in the heater supply line.   3. Turn on electric power to the heater.   4. Set the thermostat to desired setting (above ambient temperature).   The automatic starting sequence begins.   TO TURN OFF THE HEATER   1. Turn the thermostat/time switch to 'OFF' or lowest setting. The burner   will turn 'OFF' immediately, but fans will continue to cool heat exchanger   until the fan thermostat switches off.   Fire Hazard   Some objects can catch fire or explode when placed   IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,   close to heater.   FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER   Keep all flammable objects, liquids and vapors the   required clearances to combustibles away from heater.   1. Set the thermostat to off or the lowest setting.   2. Turn off electric power to the heater.   3. Turn off the manual gas valve in the heater supply line.   Failure to follow these instructions can result in death,   injury or property damage.   4. Call your installer/contractor qualified in the installation and service   of gas-fired heating equipment.   Installation Clearances   Clearances to Combustibles   Roof Terminal   Top   Top   (Optional separated   combustion concentric   venting shown.)   Left   Left   Right   Right   Top*   10'   (3 m)   Bottom   Bottom   Wall   Terminal   Rear*   Max. Mounting Height*   Models 30 - 125   Models 150 - 400   150 - 400   6" (15 cm)   3" (8 cm)   31" (79 cm)*   6" (15 cm)   2" (5 cm)   30 - 125   1" (2.5 cm)   0" (0 cm)   1" (2.5 cm)   18" (46 cm)*   2" (5 cm)   Models   Top   Bottom   Right   Left   30 - 125   1" (2.5 cm)   18" (46 cm)   *Models   Top   150 - 400   6" (15 cm)   24" (61 cm)   Rear   Max Mounting Height1   12' (3.7 m) - 20' (6 m)   20' (6 m) - 30' (9 m)   1Heaters can be mounted higher if destratification fans are installed. See Installation, Operation   and Service Manual for specific mounting height recommendations.   NOTE: Venting directly from top of heater not applicable on Models 150-400.   Vent   * Clearance needed for servicing.   Roberts-Gordon, LLC   Telephone: 716.852.4400   Fax: 716.852.0854   Toll Free: 800.828.7450   1250 William Street   P.O. Box 44   Buffalo, NY 14240-0044 USA   Installation Code and Annual Inspections:   All installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and   conform to all requirements set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help   facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON® equipment and perform service where necessary,   using only replacement parts sold and supplied by Roberts-Gordon.   For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.   Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives. Please   contact us for any further information you may require, including the Installation, Operation and Service Manual.   Models 100-400 are not for residential use.   © 2007 Roberts-Gordon, LLC   Printed in U.S.A.   P/N 91040031 Rev B   |