| Mitsubishi Electronics Mitsubishi Digital Electronics Air Conditioner Muz Fd09na User Manual | 
| OUTDOOR UNIT   No. OBH498   HFC   utilized   SERVICE MANUAL   R410A   Wireless type   Models   MUZ-FD09NA   U1   MUZ-FD09NA-   MUZ-FD12NA   MUZ-FD12NA-   U1   Indoor unit service manual   MSZ-FD•NA Series (OBH497)   CONTENTS   1. TECHNICAL CHANGES ··································· 3   2. PART NAMES AND FUNCTIONS····················· 3   3. SPECIFICATION················································ 4   4. OUTLINES AND DIMENSIONS ························ 6   5. WIRING DIAGRAM············································ 7   6. REFRIGERANT SYSTEM DIAGRAM··············· 8   7. DATA·································································· 9   8. ACTUATOR CONTROL··································· 15   9. SERVICE FUNCTIONS ··································· 16   10. TROUBLESHOOTING····································· 16   11. DISASSEMBLY INSTRUCTIONS···················· 32   PARTS CATALOG (OBB498)   TM   NOTE:   RoHS compliant products have <G> mark on the spec name plate.   1 TECHNICAL CHANGES   MUZ-FD09NA   MUZ-FD12NA   MUZ-FD09NA -   MUZ-FD12NA -   U1   U1   1. New model   2 PART NAMES AND FUNCTIONS   MUZ-FD09NA   MUZ-FD12NA   Air inlet   Piping   Drain hose   Air outlet   Drain outlet   3 3 SPECIFICATION   Outdoor unit model   MUZ-FD09NA   MUZ-FD12NA   Cooling   1 Btu/h   Btu/h   Btu/h   W W W 9,000 (2,800~9,000)   10,900 (3,000~18,000)   12,500   12,000 (2,800~12,000)   13,600 (3,000~21,000)   13,600   Capacity   Rated (Minimum~Maximum)   Heating 47   Heating 17   1 2 Capacity Rated   Cooling   1 650 (160~650)   750 (150~2,400)   1,730   960 (160~960)   980 (150~2,400)   1,780   Power consumption   Rated (Minimum~Maximum)   Heating 47   Heating 17   Cooling   1 2 Power consumption Rated   1 EER   [SEER]   3 13.8 [23.0]   12.5 [22.0]   HSPF IV(V)   COP   4 Heating   Heating   10.55 (7.4)   10.55 (7.4)   1 4.30   4.10   External nish   Power supply   Munsell 3Y 7.8/1.1   208/230 , 1 , 60   V , phase , Hz   Max. fuse size (time delay)   Min. circuit ampacity   Fan motor   A A F.L.A   15   12   0.56   Model   SNB130FQAH   8.6   Compressor   R.L.A   L.R.A   10.8   Refrigerant control   Liner expansion valve   Cooling   Heating   dB(A)   dB(A)   48   49   48   49   Sound level   1 Defrost method   Dimensions   Reverse cycle   31-1/2   W D H in.   in.   in.   Ib.   11-1/4   21-5/8   80   Weight   Remote controller   Control voltage (by built-in transformer) VDC   Refrigerant piping   Wireless type   12 - 24   Not supplied   1/4 (0.0315)   3/8 (0.0315)   Flared   Liquid   Gas   Indoor   Outdoor   in.   in.   Refrigerant pipe size   (Min. wall thickness)   Connection method   Flared   Height differ-   ence   Piping length ft.   ft.   40   Between the indoor &   outdoor units   65   Refrigerant charge (R410A)   Refrigeration oil (Model)   2 lb. 9 oz.   NE022   NOTE : Test conditions are based on ARI 210/240.   1 : Rating conditions (Cooling) — Indoor : 80 FDB, 67 FWB, Outdoor : 95 FDB, (75 FWB)Rated frequency   (Heating) — Indoor : 70 FDB, 60 FWB, Outdoor : 47 FDB, 43 FWB Rated frequency   2 :   (Heating) — Indoor : 70 FDB, 60 FWB, Outdoor : 17 FDB, 15 FWBMaximum frequency   4 Test condition   3, 4   Indoor air condition   Dry bulb (°F) Wet bulb (°F)   Outdoor air condition   Dry bulb (°F) Wet bulb (°F)   Mode   ARI   Test   "A" Cooling Steady State   at rated compressor Speed   80   67   95   (75)   "B-2" Cooling Steady State   at rated compressor Speed   80   80   80   80   70   70   70   70   70   70   67   67   67   67   60   60   60   60   60   60   82   82   67   87   47   17   62   47   35   35   (65)   (65)   (53.5)   (69)   43   SEER "B-1" Cooling Steady State   (Cooling) at minimum compressor Speed   Low ambient Cooling Steady State   at minimum compressor Speed   Intermediate Cooling Steady State   at Intermediate compressor Speed   5 Standard Rating-Heating   at rated compressor Speed   Low temperature Heating   at rated compressor Speed   15   Max temperature Heating   at minimum compressor Speed   56.5   43   HSPF   (Heating)   High temperature Heating   at minimum compressor Speed   Frost Accumulation   at rated compressor Speed   33   Frost Accumulation   at Intermediate compressor Speed   33   5 5 : At Intermediate compressor Speed   =("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".   OPERATING RANGE   (1) POWER SUPPLY   Rated voltage   Guaranteed Voltage   208/230 V   1 phase   60 Hz   Min.187 V 208 V 230 V Max.253 V   Outdoor unit   (2) OPERATION   Intake air temperature (°F)   Mode   Condition   Standard temperature   Maximum temperature   Minimum temperature   Maximum humidity   lndoor   78 %   Outdoor   DB   80   90   67   WB   67   73   DB   95   115   14   WB   — — — Cooling   57   — Standard temperature   Heating Maximum temperature   Minimum temperature   70   80   70   60   67   60   47   75   14   43   65   13   5 4 OUTLINES AND DIMENSIONS   Unit: inch   MUZ-FD09NA   MUZ-FD12NA   REQUIRED SPACE   Basically open 4 inch or more   without any obstruction in front   and on both sides of the unit.   15-3/4   Air in   Drain hole 1-5/8   Air in   1-9/16   2- 3/8 13/16 Oval hole   Air out   29/32   11-1/4   17/32   7/8   Open two sides of left,   right, or rear side.   handle   Liquid pipe :1/4 (flared)   Gas pipe :3/8 (flared)   11-29/32   6-23/32   5-15/16   19-11/16   31-1/2   2-23/32   6 5 WIRING DIAGRAM   MUZ-FD09NA MUZ-FD12NA   7 6 REFRIGERANT SYSTEM DIAGRAM   Unit:inch   MUZ-FD09NA   MUZ-FD12NA   4-way valve   Refrigerant pipe ø3/8   (with heat insulator)   Muffler   Outdoor heat   exchanger   temperature   thermistor   RT68   Stop valve   (with service port)   Outdoor   heat   Muffler   Discharge   temperature   thermistor   RT62   Flared connection   exchanger   Service   port   Ambient   temperature   thermistor   RT65   Compressor   Service   port   Defrost   thermistor   RT61   Capillary tube   O.D. 0.118 × I.D. 0.071   × 23-5/8   (ø3.0 × ø1.8   × 600)   Strainer   #100   Expansion   valve   Flared connection   Stop valve   R.V. coil   heating ON   cooling OFF   (with strainer)   Capillary tube   O.D. 0.118 × I.D. 0.079   × 9-7/16   (ø3.0 × ø2.0 × 240)   Refrigerant pipe 1/4   (with heat insulator)   Refrigerant flow in cooling   Refrigerant flow in heating   MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE   Refrigerant piping : ft   Piping size O.D : in   Model   Max. Length   Max. Height difference   B Gas   3/8   Liquid   1/4   A MUZ-FD09NA   MUZ-FD12NA   65   40   Indoor   unit   Max. Height   difference   B Max. length   A Outdoor unit   ADDITIONAL REFRIGERANT CHARGE (R410A:oz.)   NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.   Refrigerant piping length (one way) : ft   Model   Outdoor unit precharged   2 lb. 9 oz.   25   0 30   40   50   60   65   MUZ-FD09NA   MUZ-FD12NA   1.62   4.86   8.10   11.34   12.96   Calculation : X oz. = 1.62/ 5 oz./ ft x (Refrigerant piping length (ft) - 25)   NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.   8 7 DATA   MUZ-FD09NA MUZ-FD12NA   7-1. PERFORMANCE DATA   1) COOLING CAPACITY   Indoor air   Outdoor intake air DB temperature (˚F)   85 95 105   TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC   Model   IWB   (˚F)   71   67   63   75   115   11.0 6.9 0.58 10.3 6.5 0.63 9.7   6.1 0.68 9.0   6.8 0.65 8.4   7.6 0.62 7.7   5.6 0.72 8.3   6.4 0.69 7.7   6.9 0.66 7.0   5.2 0.75   5.8 0.72   6.3 0.69   MUZ-FD09NA   10.4 7.9 0.55 9.7   9.8 8.8 0.52 9.1   7.4 0.60 9.0   8.1 0.58 8.5   71   67   14.7 8.8 0.85 13.7 8.2 0.94 12.9 7.7 1.01 12.0 7.2 1.06 11.0 6.6 1.10   13.9 10.2 0.81 13.0 9.5 0.89 12.0 8.8 0.96 11.2 8.1 1.02 10.3 7.5 1.07   MUZ-FD12NA   63   13.1 11.3 0.77 12.1 10.5 0.85 11.3 9.7 0.92 10.3 8.9 0.98 9.4   8.1 1.02   NOTE : 1. IWB : Intake air wet-bulb temperature   TC : Total Capacity (x103 Btu/h)   SHC : Sensible Heat Capacity (x103 Btu/h)   TPC : Total Power Consumption (kW)   2. SHC is based on 80 ˚F of indoor Intake air DB temperature.   2) COOLING CAPACITY CORRECTIONS   Refrigerant piping length (one way : ft.)   25 (std.)   40   65   MUZ-FD09NA   MUY-FD12NA   1.0   0.954   0.878   3) HEATING CAPACITY   Indoor air   Outdoor intake air WB temperature (˚F)   35 43   Model   IDB   (˚F)   75   70   65   75   70   65   15   25   45   55   TC   6.3   6.7   6.9   7.9   8.4   8.6   TPC   0.56   0.54   0.52   0.73   0.71   0.68   TC   7.9   8.2   8.6   9.9   TPC   TC   9.4   TPC   0.73   0.71   0.69   0.96   0.93   0.91   TC   TPC   0.77   0.75   0.73   1.00   0.98   0.96   TC   TPC   0.78   0.77   0.74   1.02   1.00   0.97   TC   TPC   0.66   0.64   0.62   0.86   0.84   0.81   10.6   10.9   11.2   13.3   13.6   14.0   11.0   11.2   11.6   13.7   14.0   14.4   12.4   12.7   13.0   15.5   15.8   16.2   0.81   0.80   0.78   1.06   1.04   1.02   MUZ-FD09NA   MUZ-FD12NA   9.6   10.0   11.8   12.0   12.4   10.2   10.7   NOTE : 1. IDB : Intake air dry-bulb temperature   TC : Total Capacity (x103 Btu/h)   TPC : Total Power Consumption (kW)   2. Above data is for heating operation without any frost.   How to operate with fixed operational frequency of the compressor.   1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL   mode or EMERGENCY HEAT mode before starting to operate the air conditioner.   2. The compressor starts with operational frequency.   3. The fan speed of the indoor unit is High.   4. This operation continues for 30 minutes.   5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on   the remote controller.   9 7-2. PERFORMANCE CURVE   Cooling   MUZ-FD12NA   MUZ-FD09NA   SHF at rating condition = 0.76   SHF at rating condition = 0.73   = 307 CFM   = 350 CFM   Airflow   Airflow   Indoor   15   14   13   13   12   11   10   9 intak   Indoor intak   e air WB temperat   e air WB te   mperature (°F   ure   (°F)   12   11   10   9 ) 71   67   63   71   67   63   8 7 1.2   1.1   1.0   0.9   0.8   0.7   71   67   63   rature (°F)   mpe   71   67   63   ure (°F)   0.7   0.6   0.5   mperat   WB te   WB te   e air   oor intak   Ind   oor intake air   Ind   65   75   85   95   105   115   65   75   85   95   105   115   Outdoor intake air DB temperature (°F)   Outdoor intake air DB temperature (°F)   Heating   MUZ-FD12NA   MUZ-FD09NA   = 381 CFM   65 70   75   Airflow   = 420 CFM   Airflow   20   18   12   10   65   70   75   16   14   12   8 6 10   8 6 75   70   65   1.1   1.0   0.9   0.8   0.6   0.4   75   70   65   0.8   0.7   0.6   15   25   35   45   55   15   25   35   45   55   Outdoor intake air WB temperature (°F)   Outdoor intake air WB temperature (°F)   This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships   between frequency and capacity.   10   7-3. CONDENSING PRESSURE   Cooling   Data is based on the condition of indoor humidity 50 %.   Air flow should be set to High speed.   MUZ-FD09NA   (PSIG)   580   540   500   (PSIG)   180   175   170   165   160   155   150   145   140   135   130   125   120   86   80   460   86   80   75   420   70   380   75   70   340   300   260   68 70   75   80   85   90   95   100 105(°F)   68 70   75   80   85   90   95   100 105(°F)   Outdoor ambient temperature   Outdoor ambient temperature   MUZ-FD12NA   (PSIG)   580   540   500   460   420   380   340   300   (PSIG)   180   175   170   165   160   155   150   145   140   135   130   125   120   86   80   75   70   86   80   75   70   260   68 70   75   80   85   90   95   100 105(°F)   68 70   75   80   85   90   95   100 105(°F)   Outdoor ambient temperature   Outdoor ambient temperature   11   Heating   Data is based on the condition of outdoor humidity 75 %.   Air flow should be set to High speed.   Data is for heating operation without any frost.   MUZ-FD09NA   (PSIG)   400   (PSIG)   380   360   340   320   300   280   260   240   220   200   180   160   140   170   160   150   140   130   120   110   100   90   75   70   65   75   70   65   58Hz   58Hz   80   70   60   14   20 25 30 35 40 45 50 55 60 65 70(°F)   Outdoor ambient temperature   14 20 25 30 35 40 45 50 55 60 6570(°F)   Outdoor ambient temperature   MUZ-FD12NA   (PSIG)   400   (PSIG)   380   360   340   320   300   280   260   240   220   200   180   160   140   170   160   150   140   130   120   110   100   90   75   70   65   75   70   65   58Hz   58Hz   80   70   60   14   20 25 30 35 40 45 50 55 60 65 70(°F)   Outdoor ambient temperature   14 20 25 30 35 40 45 50 55 60 6570(°F)   Outdoor ambient temperature   12   7-4. STANDARD OPERATION DATA   Model   MSZ-FD09NA   MSZ-FD12NA   Item   Unit   Cooling   Heating   10,900   — Cooling   Heating   13,600   — Capacity   SHF   Btu/h   — 9,000   0.76   0.650   35   12,000   0.73   Input   kW   Hz   0.750   43   0.960   51   0.980   54   Rated frequency   Indoor unit   MSZ-FD09NA   MSZ-FD12NA   V,   phase,   Hz   Power supply   208/230 , 1 , 60   Input   kW   A 0.018   0.024   0.024   0.030   Fan motor current   Outdoor unit   0.19/0.17   0.25/0.23   0.25/0.23   0.32/0.29   MUZ-FD09NA   MUZ-FD12NA   V,   phase,   Hz   Power supply   208/230 , 1 , 60   Input   kW   A 0.632   0.726   0.936   0.950   Comp. current   2.96/2.68   3.39/3.06   4.40/3.97   4.43/4.01   Fan motor current   A 0.35/0.32   Condensing pressure   Suction pressure   PSIG   PSIG   ˚F   376   154   143   112   51   355   108   144   108   46   402   148   161   117   51   392   104   159   115   45   Discharge temperature   Condensing temperature   Suction temperature   Comp. shell bottom temperature   Ref. pipe length   ˚F   ˚F   ˚F   144   128   146   129   ft.   25   2 lb. 9 oz.   Refrigerant charge (R410A)   DB   Intake air temperature   WB   ˚F   ˚F   80   67   70   60   80   67   70   60   DB   Discharge air temperature   WB   ˚F   59   100   — 56   105   — ˚F   56   54   Fan speed (High)   rpm   CFM   ˚F   1,020   307 (Wet)   95   1,120   381   47   1,120   350 (Wet)   95   1,220   420   47   Airflow (High)   DB   Intake air temperature   WB   ˚F   — 43   — 43   Fan speed   rpm   CFM   810   870   1,187   810   870   1,187   Airflow   1,102   1,102   13   7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY   MUZ-FD09NA   Correction of Cooling capacity   Correction of Cooling total input   Correction of Heating total input   Correction of Heating capacity   2.0   1.5   1.5   1.0   0.5   1.5   1.0   0.5   3.0   2.0   1.0   1.0   0.5   (Hz)   (Hz)   150   (Hz)   (Hz)   150   0 50   100   150   0 50   100   0 50   100   150   0 50   100   The operational frequency of compressor   The operational frequency of compressor The operational frequency of compressor   The operational frequency of compressor   MUZ-FD12NA   Correction of Cooling capacity   1.5   Correction of Cooling total input   Correction of Heating capacity   Correction of Heating total input   1.5   1.0   0.5   1.5   1.0   0.5   2.0   1.0   0.5   1.0   (Hz)   (Hz)   150   (Hz)   (Hz)   150   0 50   100   150   0 50   100   0 50   100   150   0 50   100   The operational frequency of compressor   The operational frequency of compressor The operational frequency of compressor   The operational frequency of compressor   7-6. TEST RUN OPERATION (How to operate fixed-frequency operation)   1. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).   2. Test run operation starts and continues to operate for 30 minutes.   3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.   4. Indoor fan operates at High speed.   5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor   varies).   6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on   remote controller.   14   8 ACTUATOR CONTROL   MUZ-FD09NA   MUZ-FD12NA   8-1. OUTDOOR FAN MOTOR CONTROL   The fan motor turns ON/OFF, interlocking with the compressor.   [ON] The fan motor turns ON 5 seconds before the compressor starts up.   [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.   5 seconds   15 seconds   ON   Compressor   OFF   ON   Outdoor fan   motor   OFF   8-2. R.V. COIL CONTROL   . . . . . . . . . . . . . . . . .   . . . . . . . . . . . . . . . . .   Heating   Cooling   ON   OFF   OFF   . . . . . . . . . . . . . . . . . . . .   Dry   NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.   <COOL>   <HEAT>   5 seconds   5 seconds   ON   OFF   Compressor   R.V.coil   ON   OFF   ON   OFF   Outdoor fan   motor   8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR   Actuator   Sensor   Purpose   Outdoor   fan motor   Indoor fan   motor   Compressor   LEV   R.V. coil   Discharge temperature thermistor   Indoor coil temperature thermistor   Protection   ○ ○   Cooling : Coil frost prevention   Heating : High pressure protection   Cooling : High pressure protection   Heating : Defrosting   ○ ○ ○   ○ ○   ○ ○ ○ ○ ○   Defrost thermistor   Fin temperature thermistor   Protection   ○ ○ Outdoor heat exchanger temperature thermistor   Ambient temperature thermistor   High pressure protection   Low ambient temperature operation   ○ ○ ○   ○ ○ ○   15   9 SERVICE FUNCTIONS   MUZ-FD09VA   MUZ-FD12VA   9-1. CHANGE IN DEFROST SETTING   Changing defrost finish temperature   <JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board.   (Refer to 10-6-1.)   Jumper   Defrost finish temperature   41 °F (5 °C)   Soldered   (Initial setting)   JS   None   (Cut)   50 °F (10 °C)   9-2. PRE-HEAT CONTROL SETTING   PRE-HEAT CONTROL   When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside tempera-   ture. The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 68 °F (20   °C) or below. When pre-heat control is turned ON, compressor is energized. (about 50 W)   <JK> To activate the pre-heat control, cut the JK wire of the inverter P.C. board. (Refer to 10-6.1)   NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.   10   TROUBLESHOOTING   MUZ-FD09NA MUZ-FD12NA   10-1. CAUTIONS ON TROUBLESHOOTING   1. Before troubleshooting, check the following   1) Check the power supply voltage.   2) Check the indoor/outdoor connecting wire for miswiring.   2. Take care of the following during servicing   1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after con-   firming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.   2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic   control P.C. board.   3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.   4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the   components.   5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.   Lead wiring   Housing point   3. Troubleshooting procedure   1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.   To make sure, check how many times the abnormality indication is flashing on and off before starting service work.   2) Before servicing check that the connector and terminal are connected properly.   3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the   components for bursting and discoloration.   4) Refer to 10-2. and 10-3.   16   10-2. FAILURE MODE RECALL FUNCTION   Outline of the function   This air conditioner can memorize the abnormal condition which has occurred once.   Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details   can be recalled.   This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.   1. Flow chart of failure mode recall function for the indoor/outdoor unit   Operational procedure   The cause of abnormality cannot be found because the abnormality doesn't recur.   Setting up the failure mode recall function   Turn ON the power supply.   <Preparation of the remote controller>   While pressing both OPERATION SELECT button and TOO COOL button on the   remote controller at the same time, press RESET button.   First, release RESET button.   And release the other two buttons after all LCD in operation display section of the   remote controller is displayed after 3 seconds.   1. Regardless of normal or ab-   normal condition, a short beep   is emitted once the signal is   received.   Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is   displayed) with the remote controller headed towards the indoor unit.   1 Does POWER lamp on the indoor unit blink at the interval of   Indoor unit is normal.   0.5 seconds?   But the outdoor unit might be abnormal because there are some abnor-   malities that can't be recalled with this way.   Confirm if outdoor unit is abnormal according to the detailed outdoor   unit failure mode recall function. (Refer to 10-2.2)   Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-   No   (OFF)   ted at the same timing as the blinking of POWER lamp.   2 Yes   (Blinks)   Judgment of indoor/outdoor abnormality   Before blinking, does POWER lamp stay ON for 3 seconds?   Stays ON for 3 seconds (without beep):   The outdoor unit is abnormal.   Yes   No   The indoor unit is abnormal.   The outdoor unit is abnormal.   Check the blinking pattern, and confirm the abnormal point with the indoor unit   failure mode table. (Refer to indoor unit service manual.)   Check the blinking pattern, and confirm the abnormal point with the   outdoor unit failure mode table. (Refer to 10-2.3)   Make sure to check at least two consecutive blinking cycles.   2 Make sure to check at least two consecutive blinking cycles.   3 Releasing the failure mode recall function   Release the failure mode recall function by the following procedures.   Turn OFF the power supply and turn it ON again.   Press RESET button of the remote controller.   Repair the defective parts.   Deleting the memorized abnormal condition   After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall   function" mentioned above.   Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)   with the remote controller headed towards the indoor unit.   Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.   Release the failure mode recall function according to "Releasing the failure mode recall function"   mentioned above.   NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.   2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.   2. Blinking pattern when the indoor unit is abnormal:   Blinking at 0.5-   second interval   Blinking at 0.5-   second interval   2.5-second OFF   2.5-second OFF   ON   OFF   Beeps   Beeps   Beeps   Repeated cycle   Repeated cycle   Repeated cycle   3.Blinking pattern when the outdoor unit is abnormal:   Blinking at 0.5-   second interval   Blinking at 0.5-   2.5-second OFF   3-second ON   second interval   2.5-second OFF   3-second ON   ON   OFF   No beep   Beeps   No beep   Beeps   Repeated cycle   Repeated cycle   Repeated cycle   17   2. Flow chart of the detailed outdoor unit failure mode recall function   Operational procedure   The outdoor unit might be abnormal.   Confirm if outdoor unit is abnormal according to the following procedures.   Confirm that the remote controller is in the failure mode recall function.   With the remote controller headed towards the indoor unit, press TOO   COOL or TOO WARM button to adjust the set temperature to 77 ˚F (25 ˚C).   1 1. Regardless of normal or abnormal condition, 2 short   beeps are emitted as the signal is received.   Does POWER lamp on the indoor unit blink at the   interval of 0.5 seconds?   Blinks: The outdoor unit is abnormal. Beep is emitted   No   at the same timing as the blinking of POWER   (OFF)   lamp.   2 Yes   (Blinks   ) The outdoor unit is abnormal.   Check the blinking pattern, and confirm the abnormal point with the out-   door unit failure mode table (10-2.3.).   The outdoor unit is normal.   Make sure to check at least two consecutive blinking cycles.   2 Releasing the failure mode recall function   Release the failure mode recall function by the following procedures.   Turn OFF the power supply and turn it ON again.   Press RESET button of the remote controller.   Release the failure mode recall function accord-   ing to the left mentioned procedure.   Repair the defective parts.   Deleting the memorized abnormal condition   After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall   function" (10-2.1.).   Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with   the remote controller headed towards the indoor unit.   Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.   Release the failure mode recall function according to "Releasing the failure mode recall function" men-   tioned above.   NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.   2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.   2.Blinking pattern when outdoor unit is abnormal:   Blinking at 0.5-   second interval   Blinking at 0.5-   second interval   2.5-second OFF   3-second ON   2.5-second OFF   3-second ON   ON   OFF   No beep   Repeated cycle   Beeps   No beep   Repeated cycle   Beeps   Repeated cycle   18   3. Outdoor unit failure mode table   Indoor/outdoor   unit failure   mode recall   function   Outdoor unit   failure mode   recall function   POWER lamp   (Indoor unit)   Abnormal point   LED indication   Condition   Correspondence   (Failure mode / protection) (Outdoor P.C. board)   OFF   None (Normal)   — — — — — 2-time flash   2.5 seconds   OFF   Outdoor power system   Overcurrent protection stop is   •Reconnect connectors.   continuously performed 3 times within •Refer to 10-5. "How   1 minute after the compressor gets   started.   to check inverter/   compressor".   •Check stop valve.   — ○ ○ 3-time flash   Discharge temperature   1-time flash every   Thermistor shorts or opens during   compressor running.   •Refer to 10-5.   2.5 seconds thermistor   OFF   2.5 seconds   "Check of outdoor   thermistors".   Defrost thermistor   Defective outdoor   thermistors can be   identified by checking   the blinking pattern of   LED.   Fin temperature thermistor   3-time flash   2.5 seconds OFF   ○ ○ P.C. board temperature   thermistor   4-time flash   2.5 seconds OFF   Ambient temperature   thermistor   2-time flash   2.5 seconds OFF   4-time flash   2.5 seconds   OFF   Overcurrent   11-time flash   Large current flows into intelligent   •Reconnect compressor   connector.   2.5 seconds OFF   power module.   •Refer to 10-5. "How   to check inverter/   compressor".   — — ○ ○ •Check stop valve.   Compressor synchronous   abnormality (Compressor   start-up failure protection)   12-time flash   2.5 seconds OFF   Waveform of compressor current is   distorted.   •Reconnect compressor   connector.   •Refer to 10-5. "How   to check inverter/   compressor".   5-time flash   2.5 seconds   OFF   Discharge temperature   Temperature of discharge temperature •Check refrigerant   thermistor exceeds 241 °F (116 °C),   compressor stops.   circuit and refrigerant   amount.   Compressor can restart if discharge   temperature thermistor reads 212 °F   (100 °C) or less 3 minutes later.   •Refer to 10-5. "Check   of LEV".   — — — — ○ 6-time flash   2.5 seconds   OFF   High pressure   Temperature of indoor coil thermistor •Check refrigerant   exceeds 158 °F (70 °C) in HEAT mode. circuit and refrigerant   Temperature of defrost thermistor   exceeds 158 °F (70 °C) in COOL   mode.   amount.   •Check stop valve.   ○ ○ 7-time flash   Fin temperature/ P.C. board   7-time flash   2.5 seconds OFF   Temperature of fin temperature   •Check around outdoor   unit.   2.5 seconds temperature   OFF   thermistor on the inverter P.C. board   exceeds 167 ~ 176 °F (75 ~ 80 °C), or •Check outdoor unit air   temperature of P.C. board temperature passage.   thermistor on the inverter P.C. board   exceeds 158 ~ 167 °F (70 ~ 75 °C).   — — •Refer to 10-5. "Check   of outdoor fan motor".   8-time flash   2.5 seconds   OFF   Outdoor fan motor   Outdoor fan has stopped 3 times in a •Refer to 10-5. "Check   row within 30 seconds after outdoor   fan start-up.   of outdoor fan motor".   Refer to 10-5. "Check   of inverter P.C. board".   — ○ ○ 9-time flash   2.5 seconds   OFF   Nonvolatile memory data   5-time flash   2.5 seconds OFF   Nonvolatile memory data cannot be   read properly.   •Replace the inverter   P.C. board.   ○ 10-time flash Discharge temperature   2.5 seconds   OFF   Temperature of discharge temperature •Refer to 10-5. "Check   thermistor has been 122 °F (50 °C) or of LEV".   — less for 20 minutes.   •Check refrigerant   circuit and refrigerant   amount.   — ○ ○ 11-time flash DC voltage   8-time flash   DC voltage of inverter cannot be   detected normally.   •Refer to 10-5. "How   to check inverter/   compressor".   2.5 seconds   2.5 seconds OFF   OFF   — Each phase current of   9-time flash   2.5 seconds OFF   Each phase current of compressor   cannot be detected normally.   compressor   12-time flash Overcurrent Compressor   2.5 seconds open-phase   OFF   10-time flash   2.5 seconds OFF   Large current flows into intelligent   power module (IPM).   The open-phase operation of   compressor is detected.   •Reconnect compressor   connector.   •Refer to 10-5. "How   to check inverter/   — The interphase short out occurs in the compressor".   output of the intelligent power module   (IPM).   ○ ○ The compressor winding shorts out.   14-time flash Stop valve (Closed valve)   2.5 seconds   OFF   14-time flash   2.5 seconds OFF   Closed valve is detected by   compressor current.   •Check stop valve   ○ NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).   19   10-3. TROUBLESHOOTING CHECK TABLE   Abnormal point/   Condition   No.   Symptom   LED indication   Condition   Correspondence   Outdoor unit 1-time flash every Outdoor power sys- Overcurrent protection stop is continuously performed 3 times •Reconnect connector of compres-   does not oper- 2.5 seconds   ate.   tem   within 1 minute after the compressor gets started, or failure of sor.   restart of compressor has repeated 24 times.   1 •Refer to 10-5. "How to check in-   verter/ compressor".   •Check stop valve.   Outdoor thermistors Discharge temperature thermistor, fin temperature thermistor, •Refer to 10-5. "Check of outdoor   defrost thermistor, P.C. board temperature thermistor or ambi- thermistors".   ent temperature thermistor shorts or opens during compressor   running.   2 3 Outdoor control sys- Nonvolatile memory data cannot be read properly.   tem   •Replace inverter P.C. board.   (POWER lamp of the indoor unit lights up or flashes 7-time.)   6-time flash   Serial signal   Stop valve/   The communication fails between the indoor and outdoor unit •Refer to 10-5. "How to check   4 5 2.5 seconds OFF   for 3 minutes.   miswiring and serial signal error.   11-time flash   Closed valve is detected by compressor current.   •Check stop valve.   2.5 seconds OFF Closed valve   14-time flash Outdoor unit   2.5 seconds OFF (Other abnormality)   Outdoor unit is defective.   •Refer to 10-2.2. "Flow chart of the   detailed outdoor unit failure mode   recall function".   6 7 'Outdoor unit 2-time flash   Overcurrent protec- Large current flows into intelligent power module.   •Reconnect connector of compres-   stops and   2.5 seconds OFF tion   When overcurrent protection occurs within 10 seconds after sor.   restarts 3 min-   utes later' is   repeated.   compressor starts, compressor restarts after 15 seconds. •Refer to 10-5. "How to check in-   verter/compressor".   •Check stop valve.   3-time flash   Discharge tempera- Temperature of discharge temperature thermistor exceeds 241 •Check refrigerant circuit and refrig-   2.5 seconds OFF ture overheat protec- °F (116 °C), compressor stops. Compressor can restart if dis- erant amount.   8 9 tion   charge temperature thermistor reads 212 °F (100 °C) or less 3 •Refer to 10-5. "Check of LEV".   minutes later.   4-time flash   Fin temperature /P.C. Temperature of fin temperature thermistor on the heat sink ex- •Check around outdoor unit.   ceeds 167 ~ 176 °F (75 ~ 80 °C) or temperature of P.C. board •Check outdoor unit air passage.   2.5 seconds OFF board temperature   thermistor overheat temperature thermistor on the inverter P.C. board exceeds 158 •Refer to 10-5. "Check of outdoor   protection   ~ 167 °F (70 ~ 75 °C).   fan motor".   5-time flash   High pressure pro-   Indoor coil thermistor exceeds 158 °F (70 °C) in HEAT mode. •Check refrigerant circuit and refrig-   10   11   2.5 seconds OFF tection   Defrost thermistor exceeds 158 °F (70 °C) in COOL mode.   erant amount.   •Check stop valve.   8-time flash   2.5 seconds OFF chronous abnormal-   ity   Compressor syn-   The waveform of compressor current is distorted.   •Reconnect connector of compres-   sor.   •Refer to 10-5. "How to check in-   verter/compressor".   10-time flash   2.5 seconds OFF   Outdoor fan motor   Outdoor fan has stopped 3 times in a row within 30 seconds   after outdoor fan start-up.   •Refer to 10-5. "Check of outdoor   fan motor.   •Refer to 10-5. "Check of inverter   P.C. board.   12   12-time flash   Each phase current Each phase current of compressor cannot be detected nor-   •Refer to 10-5. "How to check in-   verter/compressor".   13   14   15   2.5 seconds OFF of compressor   mally   13-time flash   2.5 seconds OFF   DC voltage   DC voltage of inverter cannot be detected normally.   •Refer to 10-5. "How to check in-   verter/compressor".   Outdoor unit 1-time flash   operates. 2.5 seconds OFF current protection   Frequency drop by Current from power outlet reaches the protection current, and The unit is normal, but check the   compressor frequency lowers.   following.   •Check if indoor filters are clogged.   •Check if refrigerant is short.   •Check if indoor/outdoor unit air cir-   culation is short cycled.   3-time flash   Frequency drop by Temperature of indoor coil thermistor exceeds 131 °F (55 °C)   2.5 seconds OFF high pressure pro-   tection   in HEAT mode, compressor frequency lowers.   16   17   Frequency drop by Indoor coil thermistor reads 46 °F (8 °C) or less in COOL   defrosting in COOL mode, compressor frequency lowers.   mode   4-time flash   Frequency drop by Temperature of discharge temperature thermistor exceeds 232 •Check refrigerant circuit and refrig-   2.5 seconds OFF discharge tempera- °F (111 °C), compressor frequency lowers.   ture protection   erant amount.   •Refer to 10-5. "Check of LEV".   •Refer to 10-5. "Check of outdoor   thermistors".   NOTE: 1. The location of LED is illustrated at the right figure. Refer to 10-6.1.   Inverter P.C. board(Parts side)   2. LED is lighted during normal operation.   The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF. Flashing   (Example) When the flashing frequency is “2”.   LED   Flashing →   0.5-second ON   0.5-second ON   2.5-second OFF   ON   2.5-second OFF   OFF   20   Abnormal point/   Condition   No.   18   Symptom   LED indication   Condition   Correspondence   Outdoor unit 7-time flash   Low discharge tem- Temperature of discharge temperature thermistor has been   operates. 2.5 seconds OFF perature protection 122 °F (50 °C) or less for 20 minutes.   •Refer to 10-5. "Check of LEV".   •Check refrigerant circuit and refrig-   erant amount.   8-time flash   PAM protection PAM: The overcurrent flows into IGBT (Insulated Gate Bipolar tran- This is not malfunction. PAM protec-   2.5 seconds OFF Pulse Amplitude   Modulation   sistor : TR821) or when the bus-bar voltage reaches 320 V or tion will be activated in the following   more, PAM stops and restarts.   cases;   19   20   1 Instantaneous power voltage drop   (Short time power failure)   2 When the power supply voltage is   high.   9-time flash   2.5 seconds OFF   Inverter check mode The connector of compressor is disconnected, inverter check •Check if the connector of the com-   mode starts.   pressor is correctly connected.   Refer to 10-5. "How to check   inverter/ compressor".   21   10-4. TROUBLE CRITERION OF MAIN PARTS   MUZ-FD09NA MUZ-FD12NA   Part name   Check method and criterion   Figure   Defrost thermistor   (RT61)   Measure the resistance with a tester.   Ambient temperature   thermistor (RT65)   Refer to 10-6. “Test point diagram and voltage”,1. “Inverter P.C.   board”, the chart of thermistor.   Outdoor heat ex-   changer temperature   thermistor (RT68)   Discharge tem-   perature thermistor   (RT62)   Measure the resistance with a tester. Before measurement, hold the   thermistor with your hands to warm it up.   Refer to 10-6. “Test point diagram and voltage”,1. “Inverter P.C.   board”, the chart of thermistor.   Fin temperature   thermistor (RT64)   Measure the resistance between terminals using a tester.   (Winding temperature : -4 ~ 104 °F (-20 ~ 40 °C))   WHT   2 RED BLK   3 1 W Normal   U-V   U-W   V-W   Compressor   1.52 ~ 2.17 Ω   V U Measure the resistance between lead wires using a tester.   (Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))   WHT   RED BLK   2 3 1 Color of lead wire   Normal   Outdoor fan motor   R. V. coil (21S4)   W RED – BLK   BLK – WHT   WHT – RED   11 ~ 16 Ω   V U Measure the resistance using a tester.   (Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))   Normal   970 ~ 1380 Ω   Measure the resistance using a tester.   (Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))   WHT   RED   ORN   LEV   Color of lead wire   WHT – RED   RED – ORN   YLW – BRN   BRN – BLU   Normal   Expansion valve coil   (LEV)   37 ~ 54 Ω   22   10-5. TROUBLESHOOTING FLOW   POWER lamp flashes 5-times.   Outdoor unit does not operate.   A How to check inverter/ compressor   Disconnect the connector (CN61) between   compressor and the intelligent power module   (IPM).   See 10-5. “Check of open phase”.   Replace the inverter P.C. board.   See 10-5. “Check of compressor”.   Check the voltage between terminals.   Are the voltages balanced?   Yes   No   Check the compressor.   B Check of open phase   ●With the connector between the compressor and the intelligent power module disconnected,   activate the inverter and check if the inverter is normal by measuring the balance of voltage   between the terminals.   Output voltage 115 V   << Operation method>>   Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the   indoor unit. (TEST RUN OPERATION : Refer to 7-6.)   <<Measurement point>>   at 3 points   BLK (U)-WHT (V)   BLK (U)-RED (W)   WHT(V)-RED (W)   9-time flash   Measure AC voltage between the   lead wires at 3 points.   2.5-second OFF   NOTE: 1. Output voltage varies according to power supply voltage.   2. Measure the voltage by analog type tester.   3. During this check, LED of the inverter P.C. board flashes 9 times. (Refer to 10-6.1.)   C Check of compressor   Refer to 10-5. “Check of compressor   winding”.   Is the compressor normal?   Replace the compressor.   No   No   Yes   Refer to 10-5. “Check of compressor   operation time”.   Does the compressor operate continuously?   Refer to 10-5. “Check of compressor start failure”.   Yes   OK.   23   D Check of compressor winding   ●Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between   the compressor terminals.   <<Measurement point>>   at 3 points   BLK-WHT   BLK-RED   Measure the resistance between the lead wires at 3 points.   WHT-RED   <<Judgement>>   Refer to 10-4.   0[Ω] ················Abnormal [short]   Infinite[Ω] ·······Abnormal [open]   NOTE: Be sure to zero the ohmmeter before measurement.   E Check of compressor operation time   <<Judgement>>   0 second   ●Connect the compressor and activate the inverter. Then measure   the time until the inverter stops due to over current.   <<Operation method>>   Start heating or cooling operation by pressing EMERGENCY   OPERATION switch on the indoor unit.   Compressor starts   1 second   Abnormal   (IPM failure)   (Compressor winding short)   2 seconds   (TEST RUN OPERATION : Refer to 7-6.)   <<Measurement>>   Measure the time from the start of compressor to the stop of   compressor due to overcurrent.   Abnormal   (Compressor lock out)   (Starting defect)   Abnormal   (Poor contact,)   (Outdoor P.C. board defect)   (Disconnected connector)   10 seconds   10 minutes   Abnormal   (Refrigerant circuit defect)   (Closed valve)   Normal   F Check of compressor start failure   Confirm that 1~4 is normal.   • Electrical circuit check   1.Contact of the compressor connector (including CN61)   2.Output voltage of inverter P.C. board and balance of them (See 10-5. )   3.Direct current voltage between DB61(+) and (-) on the inverter P.C. board   4.Voltage between outdoor terminal block S1-S2   Check the refrigerant circuit.   Check the stop valve.   Does the compressor run for 10 seconds or   more after it starts?   Yes   No   No   After the compressor is heated with a drier,   Replace the compressor.   does the compressor start?   1 Yes   1 Heat the compressor with   a drier for about 20 minutes.   Do not recover refrigerant   gas while heating.   Compressor start failure. Activate pre-heat control.   (Refer to 9-2. "PRE-HEAT CONTROL SETTING")   Heating part   24   POWER lamp flashes 6-time.   The thermistors in the outdoor unit are abnormal.   G Check of outdoor thermistors   Disconnect the connector of thermistor in the outdoor P.C. board (see   below table), and measure the resistance of thermistor.   Replace the thermistor except RT64. When RT64 is   abnormal, replace the inverter P.C. board.   Is the thermistor normal? (Refer to 10-6.1.)   No   Yes   Reconnect the connector of thermistor.   Turn ON the power supply and press EMERGENCY OPERATION switch.   Does the unit operate for 10 minutes or more   without showing thermistor abnormality?   Replace the inverter P.C. board.   No   Yes   OK.   (Cause is poor contact.)   Thermistor   Symbol   Connector, Pin No.   Board   Defrost   Discharge temperature   Fin temperature   RT61 Between CN641 pin1 and pin2   RT62 Between CN641 pin3 and pin4   RT64 Between CN642 pin1 and pin2   RT65 Between CN643 pin1 and pin2   Inverter P.C. board   Ambient temperature   Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3   H Check of R.V. coil   First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4.   In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector   although any signal is not being transmitted to R.V. coil.   Check if CN721 is connected.   Unit operates COOL mode even if it is set to HEAT mode.   Disconnect connector (CN61)   between the compressor and the   intelligent power module.   Turn ON the power supply and   press EMERGENCY OPERATION   switch twice (HEAT mode).   Is there 230 VAC between CN721 and   on the inverter P.C. board 3 minutes   after the power supply is turned ON?   Replace the inverter   P.C. board.   No   Yes   Replace the 4-way valve.   Unit operates HEAT mode even if it is set to COOL mode.   Disconnect connector (CN61)   between the compressor and the   intelligent power module.   Turn ON the power supply and   press EMERGENCY OPERATION   switch once (COOL mode).   Is there 230 VAC between CN721 and   on the inverter P.C. board 3 minutes   after the power supply is turned ON?   Replace the inverter   P.C. board.   Yes   No   Replace the 4-way valve.   25   Outdoor fan motor does not operate.   I Check of outdoor fan motor   Disconnect CN932 from the inverter P.C. board, and   measure the resistance of the outdoor fan motor.   Is the outdoor fan motor normal?   (Refer to 10-4.)   Replace the outdoor fan motor.   No   Yes   Replace the inverter P.C. board.   Inverter does not operate.   J Check of power supply   Disconnect the connector (CN61)   between compressor and intelligent   power module.   Turn ON power supply and press   EMERGENCY OPERATION switch.   Rectify indoor/ outdoor   connecting wire.   Yes   Is there voltage 208 / 230 VAC   between the indoor terminal   block S1 and S2?   Replace the indoor   electronic control P.C.   board.   Does POWER lamp on the indoor   unit light up?   No   No   No   Yes   Is there voltage 280 ~ 370 VDC   between DB61 (+) and DB61 (–) on   the inverter P.C. board?   Dose LED on the inverter P.C.   board light up or flash? (Refer   to 10-6.1.)   Replace the inverter   P.C. board.   Yes   (Refer to 10-6.1.)   Yes   No   280 ~ 370 VDC   If light up, OK.   If flash, refer to 10-3.   Check the electric parts in main circuit.   DB61   Inverter P.C. board   (Solder side)   26   Heating/Cooling does not work sufficiently.   K Check of LEV (Expansion valve)   Turn ON the power supply.   <Preparation of the remote controller>   While pressing both OPERATION SELECT button   and TOO COOL button on the remote controller at the   same time, press RESET button.   First, release RESET button.   And release the other two buttons after all LCD except   the set temperature in operation display ection of the   remote controller is displayed after 3 seconds.   Press OPERATE/STOP (ON/OFF) button of the remote   controller (the set temperature is displayed) with the   remote controller headed towards the indoor unit.   1 1. Regardless of normal or abnormal condition, a short beep   is emitted once the signal is received.   Expansion valve operates in full-opening direction.   Do you hear the expansion valve "click,   click·······"?   OK.   Do you feel the expansion valve vibrate   Yes   on touching it ?   No   Is LEV coil properly fixed to   the expansion valve?   Properly fix the LEV coil to the expansion valve.   No   Yes   Measure each voltage between connector   pins of CN724 on the inverter P.C. board.   1.Pin (-) — Pin (+)   2.Pin (-) — Pin (+)   Does the resistance of LEV   coil have the characteristics?   (Refer to 10-4.)   Replace the inverter P.C.   board.   3.Pin (-) — Pin (+)   4.Pin (-) — Pin (+)   Is there about 3 ~ 5 VAC between each?   NOTE: Measure the voltage by an analog   tester.   Yes   No   No   Replace the LEV coil.   Yes   Replace the expansion valve.   NOTE : After check of LEV, do the undermentioned operations.   1. Turn OFF the power supply and turn ON it again.   2. Press RESET button on the remote controller.   27   Outdoor fan motor does not operate, or stops immediately after starting up.   L Check of inverter P.C. board   Check the outdoor fan motor.   (Refer to10-5. .)   Is the fuse (F901) blown on the in-   verter P.C. board?   Yes   No   Inverter P.C. board   (Solder side)   Check the connection of the connectors   (CN932) of the outdoor fan motor.   If the connection is poor, make it correct.   CN932   Operate the outdoor unit by starting   EMERGENCY OPERATION.   Check the corresponding parts   following LED indication.   (Refer to 10-3.)   Check the LED indication on the in-   verter P.C. board.   Does the LED flash 10-time?   No   Yes   (10-time flash)   Replace the inverter P.C. board.   28   • Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.   Indoor unit does not operate.   • POWER lamp flashes ON and OFF in every 0.5 seconds.   Outdoor unit doesn’t operate.   M How to check miswiring and serial signal error (outdoor unit does not work)   Turn OFF the power supply.   Is there rated voltage in the   Check the power supply.   power supply?   No   No   Yes   Turn ON the power supply.   Is there rated voltage between   outdoor terminal block S1 and   S2?   Yes   Check the wiring.   Press EMERGENCY OPERATION switch once.   Does AREA-L lamp light up? <Confirmation of   the power to the indoor unit>   No   No   Yes   Is there any miswiring,   poor contact, or wire   disconnection of the   indoor/outdoor connect-   ing wire?   Is serial signal error indicated 6 minutes later?   Yes   Correct them.   Yes   No   A Turn OFF the power supply.   Check once more if the indoor/outdoor   connecting wire is not miswiring.   B 1. Miswiring may damage indoor electronic control P.C.   board during the operation.   Be sure to confirm the wiring is correct before the opera-   tion starts.   Short-circuit outdoor terminal block S2   and S3.   1 3. Be sure to check this within 3 minutes after turning ON.   After 3 minutes, LED blinks 6 times. Even when the   inverter P.C. board or the outdoor electronic control P.C.   board is normal, LED blinks 6 times after 3 minutes.   Turn ON the power supply.   Does the LED on the inverter P.C. board or   the outdoor electronic control P.C. board   repeat "3.6-second-OFF and 0.8-second-   Replace the inverter P.C. board or the out-   door electronic control P.C. board.   2 No   (Lighted   or not   ON quick blinking"?   3 2. Be careful to the residual   voltage of smoothing capacitor.   Yes   lighted)   Turn OFF the power supply.   Remove the short-circuit between   outdoor terminal block S2 and S3.   Turn ON the power supply.   Is there amplitude of 10 to 20 VDC   between outdoor terminal block S2 and   S3? <Confirmation of serial signal>   Yes   Is there any error of the in-   Replace the indoor/   outdoor connecting   wire.   door/outdoor connecting wire,   such as the damage of the wire,   intermediate connection, poor   contact to the terminal block?   No   A No   Yes   • Turn OFF inverter-controlled lighting   equipment.   • Turn OFF the power supply and then   turn ON again.   • Press EMERGENCY OPERATION   switch.   Is there any error of the in-   door/outdoor connecting wire,   such as the damage of the wire,   intermediate connection, poor   contact to the terminal block?   No   Is there rated voltage between   indoor terminal block S1 and S2?   <Confirmation of power voltage>   Replace the indoor/   outdoor connecting   wire.   • Reinstall   No   Yes   either the unit   or the light   each other   Yes   away.   Is serial signal   error indicated 6   minutes later?   • Attach a filter   on remote   control receiv-   ing section   of the indoor   unit.   No   Yes   Replace the indoor electronic control P.C. board.   Be sure to release the failure-mode recall function   after checking.   B 29   N Electromagnetic noise enters into TV sets or radios   Is the unit grounded?   Yes   Ground the unit.   No   Is the distance between the antennas   and the indoor unit within 9.91 ft., or is   the distance between the antennas and   the outdoor unit within 9.91 ft.?   Extend the distance between the antennas and   the indoor unit, and/or the antennas and the   outdoor unit.   Yes   No   Is the distance between the TV sets or   radios and the indoor unit within 3.28   ft., or is the distance between the TV   sets or radios and the outdoor unit   within 9.91 ft.?   Extend the distance between the TV sets and/or   radios and the indoor unit, or the TV sets or   radios and the outdoor unit.   Yes   No   Are the antennas damaged?   Is the coaxial cable damaged?   Is there any poor contact in the anten-   na wiring?   Replace or repair the antenna.   Replace or repair the coaxial cable.   Yes   Yes   No   Is the indoor/outdoor connecting wire   of the air conditioner and the wiring of   the antennas close?   Extend the distance between the indoor/outdoor   connecting wire of the air conditioner and the wir-   ing of the antennas.   No   Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength   or the installation condition (combination of specific conditions such as antennas or wiring).   Check the followings before asking for service.   1. Devices affected by the electromagnetic noise   TV sets, radios (FM/AM broadcast, shortwave)   2. Channel, frequency, broadcast station affected by the electromagnetic noise   3. Channel, frequency, broadcast station unaffected by the electromagnetic noise   4. Layout of ;   indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver   5. Electric field intensity of the broadcast station affected by the electromagnetic noise   6. Presence or absence of amplifier such as booster   7. Operation condition of air conditioner when the electromagnetic noise enters in   1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic   noise.   2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller   for power ON, and check for the electromagnetic noise.   3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the elec-   tromagnetic noise.   4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the   indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.   30   10-6. TEST POINT DIAGRAM AND VOLTAGE   1. Inverter P.C. board   MUZ-FD09NA MUZ-FD12NA   Smoothing   capacitor   (C62)   Smoothing   capacitor   (C63)   Smoothing   capacitor   (C61)   Fuse(F701)   250 V 3.15 A   DB61   Back side of unit   DC260 ~300 V   (-)   (+)   Fuse(F801)   AC 208 / 230 V   250 V 3.15 A   R.V.coil   (CN721)   208 / 230 VAC   Fuse(F901)   250 V 3.15 A   Output to   drive com-   pressor   (LDU,   AC208/230 V   LDV,   LDW)   Jumper wire   for pre-heat   control setting   (JK)   LEV   connector   (CN724)   Jumper wire for   changing defrost   setting (JS)   Front side of unit   Defrost thermistor(RT61)   Ambient temperature thermistor(RT65)   Outdoor heat exchanger temperature thermistor(RT68)   Fin temperature thermistor(RT64)   200   100   90   80   70   60   50   40   30   20   10   0 180   160   140   120   100   80   Discharge temperature thermistor(RT62)   700   600   500   400   300   200   100   0 60   40   20   0 32 50 68 86 104 122 140 158 176 194 212 230 248   32 50 68 86 104 122 140 158 176   -4   14 32 50 68 86 104   Temperature(°F)   Temperature(°F)   Temperature(°F)   31   11   DISASSEMBLY INSTRUCTIONS   <"Terminal with locking mechanism" Detaching points>   The terminal which has the locking mechanism can be detached as shown below.   There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.   The terminal without locking mechanism can be detached by pulling it out.   Check the shape of the terminal before detaching.   (1) Slide the sleeve and check if there is a locking lever or not.   (2) The terminal with this connector has the   locking mechanism.   Sleeve   Slide the sleeve.   Hold the sleeve, and   Pull the terminal while   pull out the terminal   slowly.   pushing the locking   lever.   Locking lever   Connector   11-1. MUZ-FD09NA MUZ-FD12NA   OPERATING PROCEDURE   NOTE : Turn OFF power supply before disassembling.   PHOTOS   1. Removing the cabinet   Photo 1   (1) Remove the screw fixing the service panel. (See   Photo 1.)   Screws   of the top   panel   (2) Pull down the service panel and remove it. (See Photo   1.)   (3) Remove the screws fixing the conduit cover. (See   Photo 2.)   Screw of the   cabinet   Screws of   the top panel   Back   panel   (4) Remove the conduit cover. (See Photo 2.)   (5) Disconnect the power supply wire and indoor/outdoor   connecting wire.   (6) Remove the screws fixing the top panel. (See Photo 1.)   (7) Remove the top panel. (See Photo 1.)   (8) Remove the screws fixing the cabinet.   (9) Remove the cabinet.   Screw of   the service   panel   (10) Remove the screws fixing the back panel.   (11) Remove the back panel.   Photo 2   Hooks   Screw of the   conduit cover   Screws of   Service   panel   the cabinet   Conduit plate   Conduit cover   32   OPERATING PROCEDURE   PHOTOS   2. Removing the inverter assembly, inverter P.C. board   (1) Remove the cabinet and panels. (Refer to 1.)   (2) Disconnect the lead wire to the reactor and the following   connectors;   Photo 3   Screws of the   relay panel   <Inverter P.C. board>   CN721 (R.V.coil)   CN932 (Fan motor)   CN641 (Defrost thermistor and discharge temperature ther-   mistor)   CN643 (Ambient temperature thermistor)   CN644 (Outdoor heat exchanger temperature thermistor)   CN724 (LEV)   (3) Remove the compressor connector (CN61).   (4) Remove the screws fixing the relay panel. (See Photo 3.)   (5) Remove the inverter assembly. (See Photo 4.)   (6) Remove the screw of the ground wire and screw of the   T.B.support. (See Photo 4.)   (7) Remove the inverter P.C. board from the inverter assembly.   Photo 4 (inverter assembly)   Inverter   P.C. board   Screw of the   T.B.support   Heat sink   T.B.support   3. Removing R.V. coil   (1) Remove the cabinet and panels. (Refer to 1.)   (2) Remove the R.V. coil. (See Photo 5.)   Screw of the   ground wire   4. Removing the discharge temperature thermistor,   defrost thermistor and outdoor heat exchanger tem-   perature thermistor.   Photo 5   R.V. coil   (1) Remove the cabinet and panels. (Refer to 1.)   (2) Pull out the discharge temperature thermistor from its hold-   er. (See Photo 5.)   (3) Pull out the defrost thermistor from its holder. (See Photo 6.)   (4) Pull out the outdoor heat exchanger temperature thermistor   from its holder. (See Photo 6.)   Discharge temperature thermistor   33   OPERATING PROCEDURE   PHOTOS   Photo 6   5. Removing outdoor fan motor   (1) Remove the cabinet and panels. (Refer to 1.)   (2) Disconnect the connectors for outdoor fan motor.   (3) Remove the propeller nut. (See Photo 7.)   (4) Remove the propeller. (See Photo 7.)   Outdoor heat   exchanger tempera-   ture thermistor   (5) Remove the screws fixing the fan motor. (See Photo 7.)   (6) Remove the fan motor.   6. Removing the compressor and 4-way valve   (1) Remove the cabinet and panels. (Refer to 1.)   (2) Remove the inverter assembly. (Refer to 2.)   (3) Recover gas from the refrigerant circuit.   NOTE: Recover gas from the pipes until the pressure   gauge shows 0 PSIG.   Defrost thermistor   Photo 7   Screws of the outdoor fan motor   (4) Detach the welded part of the suction and the discharge   pipe connected with compressor.   (5) Remove the nuts of compressor legs.   (6) Remove the compressor.   (7) Detach the welded part of pipes connected with 4-way   valve. (See Photo 8.)   Propeller nut   Propeller   Photo 8   Welded parts of 4-way valve   34   35   TM   HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN   Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD   Distributed in Jan. 2008. No. OBH498 7   Made in Japan   New publication, effective Jan. 2008   Specifications subject to change without notice.   |