| Mitsubishi Electronics Mitsubishi Digital Electronics Air Conditioner Muz D30na User Manual | 
| OUTDOOR UNIT   No. OBH502   HFC   utilized   SERVICE MANUAL   R410A   Wireless type   Models   MUZ-D30NA   U1   MUZ-D30NA-   MUZ-D36NA   U1   MUZ-D36NA-   MUY-D30NA   MUY-D36NA   Indoor unit service manual   MSZ-D•NA Series (OBH501)   MSY-D•NA Series (OBH501)   CONTENTS   1. TECHNICAL CHANGES ··································· 3   2. PART NAMES AND FUNCTIONS····················· 3   3. SPECIFICATION················································ 4   4. OUTLINES AND DIMENSIONS ························ 6   5. WIRING DIAGRAM············································ 7   6. REFRIGERANT SYSTEM DIAGRAM··············· 9   7. DATA·································································11   8. ACTUATOR CONTROL··································· 18   9. SERVICE FUNCTIONS ··································· 19   10. TROUBLESHOOTING····································· 20   11. DISASSEMBLY INSTRUCTIONS···················· 39   PARTS CATALOG (OBB502)   TM   NOTE:   RoHS compliant products have <G> mark on the spec name plate.   1 TECHNICAL CHANGES   MUZ-D30NA   MUZ-D30NA -   MUZ-D36NA   MUZ-D36NA -   MUY-D30NA   MUY-D36NA   U1   U1   1. New model   2 PART NAMES AND FUNCTIONS   MUZ-D30NA MUZ-D36NA   MUY-D30NA MUY-D36NA   Air inlet   (back and side)   Piping   Drain hose   Air outlet   Drain outlet   3 3 SPECIFICATION   Item   Model   MSZ-D30NA   MSY-D30NA   MSZ-D36NA   MSY-D36NA   32,000/33,200   33,200/34,600   30,700   (9,800 ~ 30,700)   30,700   (9,800 ~ 30,700)   Cooling   1 Btu/h   (9,800 ~ 32,000) / (9,800 ~ 33,200) /   Capacity   (9,800 ~ 33,200)   (9,800 ~ 34,600)   Rated(Minimum~Maximum)   32,600   35,200   Heating 47 1 Btu/h   Heating 17 2 Btu/h   — — — — (8,700 ~ 34,000)   (8,700 ~ 36,000)   Capacity Rated   20,800   22,800   4,140/4,360   (620 ~ 4,140) /   (620 ~ 4,360)   3,840   (520 ~ 4,100)   4,210/4,240   (620 ~ 4,210) /   (620 ~ 4,240)   3,850   3,380   Cooling   1 W Power consumption   (620 ~ 3,850)   (620 ~ 3,380)   Rated(Minimum~Maximum)   (TOTAL)   3,360   (520 ~ 3,600)   Heating 47 1 W   Heating 17 2 W   Cooling   — — — — 7.9/8.2   [15.1]   Power consumption Rated   2,620   3,000   7.7/7.6   [14.5]   1 EER   [SEER]   3 8.0 [14.5]   9.1 [16.0]   HSPF IV(V)   COP   4 Heating   Heating   (8.2)   2.84   — — (8.2)   2.69   — — 1 Outdoor unit model   External finish   MUZ-D30NA   MUY-D30NA   MUZ-D36NA   MUY-D36NA   Munsell 3Y 7.8/1.1   Power supply   V , phase , Hz   208/230 , 1 , 60   Max. fuse size (time delay)   Min. circuit ampacity   Fan motor   A A 25   21   F.L.A   Model   R.L.A   L.R.A   0.93   TNB220FMCHT   Compressor   16   20   Refrigerant control   Liner expansion valve   Cooling   Heating   dB(A)   dB(A)   55   57   55   — — 56   57   56   — — Sound level   1 Defrost method   Dimensions   Reverse cycle   Reverse cycle   W D H in.   in.   in.   Ib.   33-1/16   13   33-7/16   Weight   141   126   141   126   Remote controller   Control voltage (by built-in transformer)   Refrigerant piping   Wireless type   12 - 24 VDC   Not supplied   3/8 (0.0315)   5/8 (0.0394)   Flared   Liquid   Gas   Indoor   Outdoor   in.   in.   Refrigerant pipe size   (Min. wall thickness)   Connection method   Flared   Height   ft.   50   Between the indoor &   outdoor units   difference   Piping length ft.   100   Refrigerant charge (R410A)   4 lb. 10 oz.   4 lb.   4 lb. 10 oz.   4 lb.   Refrigeration oil (Model)   NE022   NOTE : Test conditions are based on ARI 210/240.   1 : Rating conditions(Cooling) — Indoor : 80 ˚FDB, 67 ˚FWB, Outdoor : 95 ˚FDB, (75 ˚FWB)Rated frequency   (Heating) — Indoor : 70 ˚FDB, 60 ˚FWB, Outdoor : 47 ˚FDB, 43 ˚FWB Rated frequency   (Heating) — Indoor : 70 ˚FDB, 60 ˚FWB, Outdoor : 17 ˚FDB, 15 ˚FWBMaximum frequency   2 :   4 Test condition   3, 4   Indoor air condition   Dry bulb (°F) Wet bulb (°F)   Outdoor air condition   Dry bulb (°F) Wet bulb (°F)   Mode   ARI   Test   "A" Cooling Steady State   at rated compressor Speed   80   67   95   (75)   "B-2" Cooling Steady State   at rated compressor Speed   80   80   80   80   70   70   70   70   70   70   67   67   67   67   60   60   60   60   60   60   82   82   67   87   47   17   62   47   35   35   (65)   (65)   (53.5)   (69)   43   SEER "B-1" Cooling Steady State   (Cooling) at minimum compressor Speed   Low ambient Cooling Steady State   at minimum compressor Speed   Intermediate Cooling Steady State   at Intermediate compressor Speed   5 Standard Rating-Heating   at rated compressor Speed   Low temperature Heating   at rated compressor Speed   15   Max temperature Heating   at minimum compressor Speed   56.5   43   HSPF   (Heating)   High temperature Heating   at minimum compressor Speed   Frost Accumulation   at rated compressor Speed   33   Frost Accumulation   at Intermediate compressor Speed   33   5 5 : At Intermediate compressor Speed   =("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".   OPERATING RANGE   (1) POWER SUPPLY   Rated voltage   Guaranteed Voltage   208/230 V   1 phase   60 Hz   Min.187 V 208 V 230 V Max.253 V   Outdoor unit   (2) OPERATION   Intake air temperature (°F)   Mode   Condition   Standard temperature   Maximum temperature   Minimum temperature   Maximum humidity   Indoor   78 %   Outdoor   DB   80   90   67   WB   67   73   DB   95   115   14   WB   — — — Cooling   57   — Standard temperature   Heating Maximum temperature   Minimum temperature   70   80   70   60   67   60   47   75   14   43   65   13   5 4 OUTLINES AND DIMENSIONS   Unit: inch   MUZ-D30NA   MUZ-D36NA   MUY-D30NA   MUY-D36NA   Open as a rule   20 inch or more if   the front and both   sides are open   REQUIRED SPACE   4 inch or more /   8 inch or more if   there are obstacles   to both sides   Open as a rule   20 inch or more if the back,   both sides and top are open   6 5 WIRING DIAGRAM   MUZ-D30NA MUZ-D36NA   7 MUY-D30NA MUY-D36NA   8 6 REFRIGERANT SYSTEM DIAGRAM   Unit:inch   MUZ-D30NA   MUZ-D36NA   Oil   separator   Capillary tube   Strainer   #100   O.D. 0.071 x I.D. 0.024   x 39-3/8   Refrigerant pipe 5/8   (with heat insulator)   ( 1.8 x 0.6 x 1,000)   4-way valve   Service   port   Stop valve   (with service port)   Outdoor   heat   Defrost   High-pressure thermistor   RT61   Flared connection   Ambient   temperature   thermistor   RT65   exchanger   Switch   Discharge   temperature   thermistor   RT62   Service   port   Compressor   Outdoor heat   exchanger   temperature   thermistor   RT68   Flared connection   LEV   Strainer   #100   Strainer   #100   R.V. coil   heating ON   cooling OFF   Receiver   Stop valve   Capillary tube   O.D. 0.142 I.D. 0.094   1-31/32   Refrigerant pipe 3/8   (with heat insulator)   Refrigerant flow in cooling   Refrigerant flow in heating   ( 3.6   2.4 50)   Unit:inch   MUY-D30NA   MUY-D36NA   Oil separator   Capillary tube   Outdoor   heat   exchanger   O.D. 0.071 x I.D. 0.024   Ambient   x 39-3/8   Refrigerant pipe 5/8   (with heat insulator)   temperature   ( 1.8 x 0.6 x 1,000)   thermistor   RT65   Strainer   #100   Service   Stop valve   (with service port)   port   High-pressure   Switch   Flared connection   Outdoor heat   exchanger   temperature   thermistor   RT68   Discharge   temperature   thermistor   RT62   Service   port   Compressor   Flared connection   LEV   Strainer   #100   Capillary tube   Stop valve   O.D. 0.142 x I.D. 0.094   x 1-31/32   ( 3.6 x 2.4 x 50)   Refrigerant pipe 3/8   (with heat insulator)   Refrigerant flow in cooling   9 MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE   Refrigerant piping : ft.   Piping size O.D : in.   Model   Max. Length   Max. Height difference   B Gas   5/8   Liquid   3/8   A MUZ-D30NA   MUZ-D36NA   MUY-D30NA   MUY-D36NA   100   50   Indoor   unit   Max. Height   difference   B Max. length   A Outdoor unit   ADDITIONAL REFRIGERANT CHARGE (R410A:oz.)   Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.   Refrigerant piping length (one way) : ft.   Outdoor unit   precharged   Model   25   0 30   40   50   60   70   80   90   100   MUZ-D30NA   MUZ-D36NA   4 lb. 10 oz.   2.96   8.88   14.80   20.72   26.64   32.56   38.48   44.40   Calculation : X oz. = 2.96/5 oz. / ft. x (Refrigerant piping length (ft.) - 25)   Refrigerant piping length (one way) : ft.   Outdoor unit   precharged   Model   25   0 30   40   50   60   70   80   90   100   MUY-D30NA   MUY-D36NA   4 lb.   1.08   3.24   5.40   7.56   9.72   11.88   14.04   16.20   Calculation : X oz. = 1.08/5 oz. / ft. x (Refrigerant piping length (ft.) - 25)   NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.   10   7 DATA   MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   7-1. PERFORMANCE DATA   1) COOLING CAPACITY   Indoor air   IWB   (˚F)   71   Outdoor intake air DB temperature (˚F)   Model   75   85   95   105   115   TC   SHC TPC   TC   SHC TPC   TC   SHC TPC   TC   SHC TPC   TC   SHC TPC   37.6 19.1 3.43 35.2 17.8 3.75 33.0 16.7 4.04 30.7 15.6 4.25 28.2 14.3 4.43   35.6 22.8 3.23 33.2 21.2 3.56 30.7 19.6 3.85 28.6 18.3 4.08 26.2 16.8 4.27   33.5 25.9 3.08 31.0 24.0 3.41 28.9 22.3 3.68 26.2 20.3 3.93 23.9 18.5 4.08   40.7 19.8 3.88 38.0 18.5 4.25 35.7 17.4 4.58 33.2 16.2 4.82 30.5 14.9 5.01   38.5 23.9 3.66 35.9 22.2 4.03 33.2 20.6 4.36 30.9 19.1 4.62 28.4 17.6 4.84   36.2 27.3 3.49 33.5 25.3 3.86 31.2 23.5 4.16 28.4 21.4 4.45 25.9 19.5 4.62   37.6 19.1 3.01 35.2 17.8 3.30 33.0 16.7 3.55 30.7 15.6 3.73 28.2 14.3 3.89   35.6 22.8 2.84 33.2 21.2 3.13 30.7 19.6 3.38 28.6 18.3 3.58 26.2 16.8 3.75   33.5 25.9 2.70 31.0 24.0 2.99 28.9 22.3 3.23 26.2 20.3 3.45 23.9 18.5 3.58   40.7 19.8 3.75 38.0 18.5 4.10 35.7 17.4 4.42 33.2 16.2 4.65 30.5 14.9 4.84   38.5 23.9 3.54 35.9 22.2 3.89 33.2 20.6 4.21 30.9 19.1 4.46 28.4 17.6 4.67   36.2 27.3 3.37 33.5 25.3 3.73 31.2 23.5 4.02 28.4 21.4 4.29 25.9 19.5 4.46   42.4 20.6 3.77 39.6 19.3 4.13 37.2 18.1 4.45 34.6 16.8 4.69 31.8 15.5 4.88   40.1 24.9 3.56 37.4 23.2 3.92 34.6 21.5 4.24 32.2 20.0 4.49 29.6 18.3 4.71   37.7 28.4 3.39 34.9 26.3 3.75 32.5 24.5 4.05 29.6 22.3 4.32 27.0 20.3 4.49   MUZ-D30NA   MUZ-D36NA   MUY-D30NA   67   63   71   67   63   71   67   63   71   MUY-D36NA   (208 V)   67   63   71   MUY-D36NA   (230 V)   67   63   NOTE : 1. IWB : Intake air wet-bulb temperature   TC : Total Capacity (x103 Btu/h)   SHC: Sensible Heat Capacity (x103 Btu/h)   TPC : Total Power Consumption (kW)   2. SHC is based on 80 ˚F of indoor Intake air DB temperature.   2) COOLING CAPACITY CORRECTIONS   Refrigerant piping length (one way : ft.)   25 (std.)   1.0   40   65   100   MUZ-D30NA   MUZ-D36NA   MUY-D30NA   MUY-D36NA   0.95   0.878   0.713   3) HEATING CAPACITY   Indoor air   Outdoor intake air WB temperature (˚F)   Model   IDB   (˚F)   75   15   25   35   43   45   55   TC   TPC   TC   TPC   TC   TPC   3.28   3.19   3.11   3.74   3.65   3.55   TC   TPC   3.44   3.36   3.28   3.94   3.84   3.74   TC   TPC   3.49   3.43   3.33   3.99   3.92   3.80   TC   TPC   3.63   3.56   3.49   4.15   4.07   3.99   18.9   20.0   20.5   20.4   21.6   22.2   2.50   2.42   2.32   2.86   2.76   2.65   23.6   24.5   25.6   25.5   26.4   27.6   2.94   2.87   2.77   3.36   3.28   3.17   28.2   28.9   29.8   30.4   31.2   32.2   31.8   32.6   33.6   34.3   35.2   36.3   32.8   33.6   34.6   35.4   36.3   37.3   37.2   38.0   38.8   40.1   41.0   41.9   MUZ-D30NA   MUZ-D36NA   70   65   75   70   65   NOTE : 1. IDB : Intake air dry-bulb temperature   TC : Total Capacity (x103 Btu/h)   TPC : Total Power Consumption (kW)   2. Above data is for heating operation without any frost.   How to operate with fixed operational frequency of the compressor.   1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL   mode or EMERGENCY HEAT mode before starting to operate the air conditioner.   2. The compressor starts with operational frequency.   3. The fan speed of the indoor unit is High.   4. This operation continues for 30 minutes.   5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on   the remote controller.   11   7-2. PERFORMANCE CURVE   Cooling   MUZ-D36NA   MUY-D30NA   MUZ-D30NA   SHF at rating condition = 0.64   SHF at rating condition = 0.62   SHF at rating condition = 0.64   = 763 CFM   = 763 CFM   = 763 CFM   Airflow   Airflow   Airflow   40   38   36   34   32   30   28   26   24   43   41   39   37   35   33   31   29   27   40   38   36   34   32   30   28   26   24   Indoor intake air   Indoor intake air   Indoor intake air   WB temperature (°F)   WB temperature (°F)   WB temperature (°F)   71   67   63   71   67   63   71   67   63   ) ) 4.5   4.3   4.1   3.9   3.7   3.5   3.3   3.1   5.2   4.8   4.4   4.0   3.6   4.0   3.8   3.6   3.4   3.2   3.0   2.8   2.6   71   67   63   71   67   63   71   67   63   ure (°F   ure (°F   mperature (°F)   Indoor intake air WB temperat   Indoor intake air WB temperat   Indoor intake air WB te   65   75   85   95   105   115   65   75   85   95   105   115   65   75   85   95   105   115   Outdoor intake air DB temperature (°F)   Outdoor intake air DB temperature (°F)   Outdoor intake air DB temperature (°F)   MUY-D36NA   SHF at rating condition = 0.62   = 763 CFM   Airflow   46   42   38   34   30   26   Ind   oor intak   e air WB temperature (°F)   71   67   63   5.0   4.6   4.2   3.8   3.4   71   67   63   rature (°F)   mpe   oor intake air WB te   Ind   65   75   85   95   105   115   Outdoor intake air DB temperature (°F)   Heating   MUZ-D36NA   MUZ-D30NA   45   = 848 CFM   Airflow   = 848 CFM   Airflow   48   43   38   33   28   23   18   65   70   75   65   70   75   40   35   30   25   20   15   4.0   3.6   3.2   2.8   2.4   4.5   4.1   3.7   3.3   2.9   75   70   65   75   70   65   15   25   35   45   55   15   25   35   45   55   Outdoor intake air WB temperature (°F)   Outdoor intake air WB temperature (°F)   This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships   between frequency and capacity.   12   7-3. CONDENSING PRESSURE   Cooling   Data is based on the condition of indoor humidity 50 %.   Air flow should be set to High speed.   MUZ-D30NA   (PSIG)   580   86   80   75   70   540   500   460   420   380   340   300   260   (PSIG)   150   140   130   120   110   100   90   86   80   75   70   68 70   75   80   85   90   95   100 105(°F)   68 70   75   80   85   90   95   100 105(°F)   Outdoor ambient temperature   Outdoor ambient temperature   MUZ-D36NA   (PSIG)   580   86   80   75   70   540   500   460   420   380   340   300   260   (PSIG)   150   140   130   120   110   100   90   86   80   75   70   68 70   75   80   85   90   95   100 105(°F)   68 70   75   80   85   90   95   100 105(°F)   Outdoor ambient temperature   Outdoor ambient temperature   MUY-D30NA   (PSIG)   580   540   500   460   420   380   340   300   260   86   80   75   70   (PSIG)   150   140   130   120   110   100   90   86   80   75   70   68 70   75   80   85   90   95   100 105(°F)   68 70   75   80   85   90   95   100 105(°F)   Outdoor ambient temperature   Outdoor ambient temperature   13   MUY-D36NA   (PSIG)   580   86   80   75   70   540   500   460   420   380   340   300   260   (PSIG)   150   140   130   120   110   100   90   86   80   75   70   68 70   75   80   85   90   95   100 105(°F)   68 70   75   80   85   90   95   100 105(°F)   Outdoor ambient temperature   Outdoor ambient temperature   Heating   Data is based on the condition of outdoor humidity 75 %.   Air flow should be set to High speed.   Data is for heating operation without any frost.   MUZ-D30NA   (PSIG)   (PSIG)   500   480   460   440   420   400   380   360   340   320   300   280   260   240   220   200   150   140   130   120   110   100   90   75   70   65   75   70   65   58Hz   80   58Hz   70   60   50   14   20 25 30 35 40 45 50 55 60 65 70(°F)   Outdoor ambient temperature   14 20 25 30 35 40 45 50 55 60 6570(°F)   Outdoor ambient temperature   MUZ-D36NA   (PSIG)   500   (PSIG)   150   75   70   65   480   460   440   420   400   380   360   340   320   300   280   260   240   220   200   140   130   120   110   100   90   75   70   65   58Hz   80   58Hz   70   60   50   14   20 25 30 35 40 45 50 55 60 65 70(°F)   Outdoor ambient temperature   14 20 25 30 35 40 45 50 55 60 6570(°F)   Outdoor ambient temperature   14   7-4. STANDARD OPERATION DATA   Model   MSZ-D30NA   MSZ-D36NA   MSY-D30NA MSY-D36NA   Item   Unit   Btu / h   — Cooling   Heating   32,600   — Cooling   Heating   35,200   — Cooling   30,700   0.64   Cooling   33,200/34,000   0.62   Capacity   SHF   30,700   0.64   3.85   84   32,000/33,200   0.62   Input   kW   3.36   84   4.14/4.36   91   3.84   91   3.38   4.21/4.24   92   Rated frequency   Indoor unit   Hz   79   MSZ-D30NA   MSZ-D36NA   MSY-D30NA MSY-D36NA   V,   phase,   Hz   Power supply   Input   208/230 , 1 , 60   0.058   kW   A Fan motor current   Outdoor unit   0.45/0.42   MUZ-D30NA   MUZ-D36NA   MUY-D30NA MUY-D36NA   V,   phase,   Hz   Power supply   208/230 , 1 , 60   Input   kW   A 3.792   3.302   4.082/4.302   3.782   3.322   4.152/4.182   18.95/17.26   Comp. current   17.25/15.56   14.95/13.46   18.65/17.86   17.25/15.56   15.05/13.56   Fan motor current   A 0.80/0.72   Condensing pressure   Suction pressure   PSIG   PSIG   ˚F   468   126   404   96   480   122   420   94   453   125   475   119   Discharge temperature   Condensing temperature   Suction temperature   Comp. shell bottom temperature   Ref. pipe length   186.8   126.5   45.5   169.7   114.3   29.8   156.4   198.7   128.5   48.0   168.8   117.0   29.1   155.7   191.3   123.8   54.7   197.1   127.4   48.6   ˚F   ˚F   ˚F   175.6   187.0   177.4   182.7   ft.   25   Refrigerant charge (R410A)   — 4 lb. 10 oz.   4 lb.   DB   Intake air temperature   WB   ˚F   80   67   70   60   80   67   70   60   80   67   80   67   ˚F   DB   Discharge air temperature   WB   ˚F   53.9   53   112.2   73.9   53   114.9   74.6   53.7   52.8   51.7   50.8   ˚F   52.1   Fan speed (High)   rpm   CFM   ˚F   1,100   Airflow (High)   741 (Wet)   795   47   738 (Wet)   794   47   718 (Wet)   710 (Wet)   DB   Intake air temperature   WB   95   — 95   — 95   — 95   — ˚F   43   43   Fan speed   rpm   CFM   800   Airflow   1,941   15   7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY   MUZ-D30NA   Correction of Cooling capacity   Correction of Cooling total input   Correction of Heating total input   Correction of Heating capacity   1.5   1.0   0.5   1.5   1.0   0.5   1.5   1.0   0.5   1.5   1.0   0.5   (Hz)   (Hz)   150   (Hz)   (Hz)   150   0 50   100   150   0 50   100   0 50   100   150   0 50   100   The operational frequency of compressor   The operational frequency of compressor The operational frequency of compressor   The operational frequency of compressor   MUZ-D36NA   Correction of Cooling capacity   1.5   Correction of Cooling total input   Correction of Heating capacity   Correction of Heating total input   1.5   1.0   0.5   1.5   1.5   1.0   0.5   1.0   0.5   1.0   0.5   (Hz)   (Hz)   150   (Hz)   (Hz)   150   0 50   100   150   0 50   100   0 50   100   150   0 50   100   The operational frequency of compressor   The operational frequency of compressor The operational frequency of compressor   The operational frequency of compressor   MUY-D30NA   Correction of Cooling capacity   Correction of Cooling total input   1.5   1.5   1.0   0.5   1.0   0.5   (Hz)   0 50   100   150   0 50   100   150   The operational frequency of compressor   The operational frequency of compressor   MUY-D36NA   Correction of Cooling capacity   1.5   Correction of Cooling total input   1.5   1.0   0.5   1.0   0.5   (Hz)   0 50   100   150   0 50   100   150   The operational frequency of compressor   The operational frequency of compressor   16   7-6. TEST RUN OPERATION (How to operate fixed-frequency operation)   1. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).   2. Test run operation starts and continues to operate for 30 minutes.   3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.   4. Indoor fan operates at High speed.   5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor   varies).   6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on   remote controller.   17   8 ACTUATOR CONTROL   MUZ-D30NA   MUZ-D36NA   MUY-D30NA   MUY-D36NA   8-1. OUTDOOR FAN MOTOR CONTROL   The fan motor turns ON/OFF, interlocking with the compressor.   [ON] The fan motor turns ON 5 seconds before the compressor starts up.   [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.   5 seconds   15 seconds   ON   Compressor   OFF   ON   Outdoor fan   motor   OFF   8-2. R.V. COIL CONTROL   <MUZ>   . . . . . . . . . . . . . . . . .   . . . . . . . . . . . . . . . . .   Heating   ON   OFF   OFF   Cooling   . . . . . . . . . . . . . . . . . . . .   Dry   NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.   <COOL>   <HEAT>   5 seconds   5 seconds   ON   ON or OFF   R.V.coil   ON or OFF   OFF   ON   Outdoor fan   motor   OFF   8-3. Relation between main sensor and actuator   Actuator   Sensor   Purpose   Outdoor   fan motor   Indoor   fan motor   Compressor   LEV   R.V. coil   Discharge temperature thermistor Protection   ○ ○   Cooling : Coil frost prevention   Heating : High pressure protection   Defrosting   ○ Indoor coil temperature thermistor   ○ ○ ○   Defrost thermistor   ○ ○ ○ ○ ○   Fin temperature thermistor   Protection   ○ ○ Outdoor heat exchanger temperature Protection   Ambient temperature thermistor Cooling : Low ambient temperature operation   ○ ○ ○   ○ ○ ○   18   9 SERVICE FUNCTIONS   MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   9-1. PRE-HEAT CONTROL   If moisture gets into the refrigerant cycle, or when refrigerant is liquefied and col-   lected in the compressor, it may interfere the start-up of the compressor.   To improve start-up condition, the compressor is energized even while it is not   operating.   ON   This is to generate heat at the winding.   1 2 3 4 The compressor uses about 50 W when pre-heat control is turned ON.   Pre-heat control is ON at initial setting.   [How to activate pre-heat control]   1. Turn OFF the power supply for the air conditioner before making the setting.   2. Set the 2nd Dip Switch of SW1 on the outdoor electronic control P.C. board to   ON to activate pre-heat control function.   The compressor is energized even while it is not operating.   This is to generate heat at the winding to improve the compressor's start-up condition.   ON   Power   OFF   ON   Compressor   OFF   Outside temperature   68 °F (20 °C)   30min.   30min.   30min.   30min.   30min.   30min. 15min. 30min. 15min. 30min.   ON   Pre-heat   OFF   Breaker ON   Start   Stop   When outside   temperature is   above 68 °F   (20 °C)   operation operation   1. Pre-heat control is turned ON for 15 or 30 min. after the breaker is turned ON.   2. 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 min. and turned OFF for 30 min.   This is repeated as shown in the graph until the breaker is turned OFF.   When outside temperature is 68 °F (20 °C) or below , pre-heat control is ON for 30 min.   When outside temperature is 70 °F (21 °C) or above, pre-heat control is ON for 15 min.   NOTE: When the unit is started with the remote controller, pre-heat control is turned OFF.   Compressor uses 50 W when pre-heat control is turned ON.   9-2. CHANGE IN DEFROST SETTING   Changing defrost finish temperature   1. Turn OFF the power supply for the air conditioner before making the setting.   2. Set the 4th Dip Switch of SW1 on the outdoor electronic control P.C. board to   ON to change the defrost finish temperature. (Refer to 10-6-1.)   ON   1 2 3 4 4th Dip Switch of SW1   Defrost finish temperature   49.5 °F (9.7 °C)   OFF   (Initial setting)   ON   64.9 °F (18.3 °C)   19   10   TROUBLESHOOTING   MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   10-1. CAUTIONS ON TROUBLESHOOTING   1. Before troubleshooting, check the following   1) Check the power supply voltage.   2) Check the indoor/outdoor connecting wire for miswiring.   2. Take care of the following during servicing   1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after con-   firming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.   2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic   control P.C. board.   3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.   4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the   components.   5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.   Lead wiring   Housing point   3. Troubleshooting procedure   1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.   To make sure, check how many times the abnormality indication is flashing on and off before starting service work.   2) Before servicing check that the connector and terminal are connected properly.   3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the   components for bursting and discoloration.   4) Refer to 10-2. and 10-3.   20   10-2. FAILURE MODE RECALL FUNCTION   Outline of the function   This air conditioner can memorize the abnormal condition which has occurred once.   Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details   can be recalled.   This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.   This figures show about MSZ type.   1. Flow chart of failure mode recall function for the indoor/outdoor unit   Operational procedure   The cause of abnormality cannot be found because the abnormality doesn't recur.   Setting up the failure mode recall function   Turn ON the power supply.   <Preparation of the remote controller>   While pressing both OPERATION SELECT button and TOO COOL button on the   remote controller at the same time, press RESET button.   First, release RESET button.   And release the other two buttons after all LCD in operation display section of the   remote controller is displayed after 3 seconds.   Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature   is displayed) with the remote controller headed towards the indoor unit.   1 1. Regardless of normal or abnormal condition, a short   beep is emitted once the signal is received.   Does the left lamp of OPERATION INDICATOR lamp on the   indoor unit blink at the interval of 0.5 seconds?   Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-   ted at the same timing as the blinking of the left lamp   Indoor unit is normal.   But the outdoor unit might be abnormal because there are some abnor-   malities that can't be recalled with this way.   Confirm if outdoor unit is abnormal according to the detailed outdoor   unit failure mode recall function. (Refer to 10-2.2)   No   (OFF)   of OPERATION INDICATOR lamp.   2 Yes   (Blinks)   Judgment of indoor/outdoor abnormality   Before blinking, does the left lamp of OPERATION INDICA-   TOR lamp stay ON for 3 seconds?   Yes   Stays ON for 3 seconds (without beep):   The outdoor unit is abnormal.   No   The indoor unit is abnormal.   The outdoor unit is abnormal.   Check the blinking pattern, and confirm the abnormal point with the indoor unit   failure mode table. (Refer to indoor unit service manual.)   Check the blinking pattern, and confirm the abnormal point with the   outdoor unit failure mode table. (Refer to 10-2.3)   Make sure to check at least two consecutive blinking cycles.   2 Make sure to check at least two consecutive blinking cycles.   3 Releasing the failure mode recall function   Release the failure mode recall function by the following procedures.   Turn OFF the power supply and turn it ON again.   Press RESET button of the remote controller.   Repair the defective parts.   Deleting the memorized abnormal condition   After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall   function" mentioned above.   Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)   with the remote controller headed towards the indoor unit.   Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.   Release the failure mode recall function according to "Releasing the failure mode recall function"   mentioned above.   NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.   2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.   2. Blinking pattern when the indoor unit is abnormal:   Blinking at 0.5-   second interval   Blinking at 0.5-   second interval   2.5-second OFF   2.5-second OFF   ON   OFF   Beeps   Beeps   Beeps   Repeated cycle   Repeated cycle   Repeated cycle   3.Blinking pattern when the outdoor unit is abnormal:   Blinking at 0.5-   Blinking at 0.5-   second interval   2.5-second OFF   3-second ON   second interval   2.5-second OFF   3-second ON   ON   OFF   No beep   Beeps   No beep   Beeps   Repeated cycle   Repeated cycle   Repeated cycle   21   2. Flow chart of the detailed outdoor unit failure mode recall function   Operational procedure   The outdoor unit might be abnormal.   Confirm if outdoor unit is abnormal according to the following procedures.   Confirm that the remote controller is in the failure mode recall function.   With the remote controller headed towards the indoor unit, press TOO   COOL or TOO WARM button to adjust the set temperature to 77 ˚F (25 ˚C).   1 1. Regardless of normal or abnormal condition, 2 short   beeps are emitted as the signal is received.   Does left lamp of OPERATION INDICATOR lamp on   the indoor unit blink at the interval of 0.5 seconds?   Blinks: The outdoor unit is abnormal. Beep is emitted   No   at the same timing as the blinking of the left   (OFF)   lamp of OPERATION INDICATOR lamp.   Yes   2 ) (Blinks   The outdoor unit is abnormal.   Check the blinking pattern, and confirm the abnormal point with the out-   door unit failure mode table. (10-2.3.)   The outdoor unit is normal.   Make sure to check at least two consecutive blinking cycles.   2 Releasing the failure mode recall function   Release the failure mode recall function by the following procedures.   Turn OFF the power supply and turn it ON again.   Press RESET button of the remote controller.   Release the failure mode recall function accord-   ing to the left mentioned procedure.   Repair the defective parts.   Deleting the memorized abnormal condition   After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall   function" (10-2.1.).   Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)   with the remote controller headed towards the indoor unit.   Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.   Release the failure mode recall function according to "Releasing the failure mode recall function"   mentioned above.   NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.   2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.   2.Blinking pattern when outdoor unit is abnormal:   Blinking at 0.5-   second interval   Blinking at 0.5-   second interval   2.5-second OFF   3-second ON   2.5-second OFF   3-second ON   ON   OFF   No beep   Beeps   No beep   Beeps   Repeated cycle   Repeated cycle   Repeated cycle   22   3. Outdoor unit failure mode table   MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   LED indication   (Outdoor P.C.   board)   The left lamp of OPERA-   TION INDICATOR lamp   (Indoor unit)   Indoor/outdoor   unit failure mode   recall function   Abnormal point   Condition   Correspondence   — (Failure mode / protection)   LED 1   LED 2   OFF   Non (Normal)   — — — — •Check the connection of the   compressor connecting wire.   •Refer to 10-5. "How to check   inverter / compressor".   IPM protection stop or lock protection stop is continuously   performed 3 times within 1 minute after the compres-   2-time flash   Outdoor power system   Lighting Lighting sor gets started, or converter protection stop or bus-bar   ○ voltage protection stop is continuously performed 3 times •Refer to 10-5. "Check of   within 3 minutes after start-up.   compressor start failure".   •Check the stop valve.   Discharge temperature thermistor Lighting   Once   Once   Twice   Defrost thermistor (MUZ)   Lighting   Lighting   •Refer to 10-5. "Check of   outdoor thermistors".   Ambient temperature thermistor   Fin temperature thermistor   3-time flash   Thermistor shorts or opens during compressor running.   ○ Lighting 3 times   •Replace the outdoor electronic   control P.C. board.   P.C. board temperature thermistor Lighting 4 times   Outdoor heat exchanger tempera-   Lighting 9 times   •Refer to 10-5. "Check of   outdoor thermistors".   ture thermistor   •Reconnect compressor con-   nector.   •Refer to 10-5. "How to check   inverter/ compressor."   •Refer to 10-5. "Check of   compressor start failure".   •Check the stop valve.   Goes   out   4-time flash   Overcurrent   Once   28 A current flow into intelligent power module.   — Temperature of discharge temperature thermistor exceeds •Check refrigerant circuit and   241 °F (116 °C), compressor stops. Compressor can   restart if discharge temperature thermistor reads 212 °F   (100 °C) or less 3 minutes later.   refrigerant amount.   •Refer to 10-5. "Check of   LEV".   5-time flash   Discharge temperature   High pressure   Lighting Lighting   — — The outdoor heat exchanger temperature exceeds 158 °F •Check refrigerant circuit and   Lighting Lighting (70 °C) during cooling or the indoor gas pipe temperature   exceeds 158 °F (70 °C) during heating (MUZ).   6-time flash   refrigerant amount.   •Check the stop valve.   Goes   out   The fin temperature exceeds 189 °F (87 °C) during opera-   •Check around outdoor unit.   •Check outdoor unit air pas-   sage.   •Refer to 10-5. "Check of   outdoor fan motor".   Fin temperature   3 times   4 times   tion.   7-time flash   — — Goes   out   The P.C. board temperature exceeds 158 °F (70 °C) during   operation.   P.C. board temperature   Failure occurs continuously 3 times within 30 seconds   after the fan gets started.   •Refer to 10-5. "Check of   outdoor fan motor".   8-time flash   Outdoor fan motor   Lighting Lighting   •Replace the outdoor electronic   control P.C. board.   9-time flash   Nonvolatile memory data   Lighting 5 times Nonvolatile memory data cannot be read properly.   ○ •Check refrigerant circuit and   refrigerant amount.   •Refer to 10-5. "Check of   LEV".   The frequency of the compressor is kept 80 Hz or more   Lighting Lighting and the discharge temperature is kept under 102 °F (39 °C)   for more than 20 minutes.   10-time flash   Discharge temperature   — •Check the connecting wire   between outdoor electronic   control P.C. board and power   board.   Communication error occurs between the electronic control   P.C. board and power board for more than 10 seconds.   Lighting 6 times   — Communication error between   P.C. boards   The communication between boards protection stop is   continuously performed twice.   ○ •Replace the power board.   A short or open circuit is detected in the current sensor   — during compressor operating.   Current sensor   Lighting 7 times   11-time flash   Current sensor protection stop is continuously performed   twice.   ○ •Check the connecting wire   among electronic control P.C.   board, noise filter P.C. board   and power board.   Zero cross signal cannot be detected while the compres-   sor is operating.   — Zero cross detecting circuit   5 times Goes out   The protection stop of the zero cross detecting circuit is   continuously performed 10 times.   ○ NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).   23   LED indication (Out-   door P.C. board)   The left lamp of OPERA-   TION INDICATOR lamp   (Indoor unit)   Indoor/outdoor   unit failure mode   recall function   Abnormal point   (Failure mode / protection)   Condition   Correspondence   LED 1   LED 2   •Replace the power board.   A failure is detected in the operation of the converter dur-   ing operation.   Converter   5 times Goes out   5 times Goes out   Bus-bar voltage   (1)   The bus-bar voltage exceeds 400 V or falls to 200 V or   below during compressor operating.   11-time flash   — Bus-bar voltage   (2)   Even if this protection stop   The bus-bar voltage exceeds 400 V or falls to 50 V or   below during compressor operating.   is performed continuously 3 6 times Goes out   times, it does not mean the   abnormality in outdoor power   system.   24   10-3. TROUBLESHOOTING CHECK TABLE   MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   Indication   No. Symptom   Abnormal point / Condition   Condition   Correspondence   LED1   (Red)   LED2   (Yellow)   •Check the connection of the compressor connect-   ing wire.   •Refer to 10-5. "How to check inverter/compres-   sor".   •Refer to 10-5. "Check of compressor start failure".   •Check the stop valve.   IPM protection stop or lock protection stop is continuously   performed three times within 1 minute after the compressor   gets started, or converter protection stop or bus-bar voltage   protection stop is continuously performed 3 times within 3   minutes after start-up.   1 Lightning Twice   Outdoor power system   A short circuit is detected in the thermistor during opera-   tion, or an open circuit is detected in the thermistor after 10   minutes of compressor start-up.   Discharge temperature therm-   istor   2 3 Lightning 3 times   Lightning 4 times   •Refer to 10-5. "Check of outdoor thermistor".   Fin temperature thermistor   •Refer to 10-5. "Check of outdoor thermistor".   •Replace the outdoor electronic control P.C. board.   A short or open circuit is detected in the thermistor during   operation.   P.C. board temperature therm-   istor   Ambient temperature thermis- A short or open circuit is detected in the thermistor during   tor   operation.   Outdoor   A short circuit is detected in the thermistor during operation,   or an open circuit is detected in the thermistor after 5 minutes   (in cooling) and 10 minutes (in heating (MUZ)) of compressor •Refer to 10-5. "Check of outdoor thermistor".   start-up.   unit does   not oper-   ate.   Outdoor heat exchanger   temperature thermistor   4 Lightning 5 times   A short circuit is detected in the thermistor during operation,   or an open circuit is detected in the thermistor after 5 minutes   of compressor start-up.   Defrost thermistor (MUZ)   The communication fails between the indoor and outdoor unit •Refer to 10-5. "How to check miswiring and serial   5 6 7 Lightning 6 times   Lightning 7 times   Lightning 8 times   Serial signal   for 3 minutes.   signal error.   Nonvolatile memory data   Current sensor   The nonvolatile memory data cannot be read properly.   •Replace the outdoor electronic control P.C. board.   Current sensor protection stop is continuously performed   twice.   •Replace the power board.   Communication error between The communication protection stop between boards is con-   •Check the connecting wire between outdoor elec-   tronic control P.C. board and power board.   8 9 Lightning 11 times   P.C. boards   tinuously performed twice.   •Check the connecting wire among outdoor elec-   tronic control P.C. board, noise filter P.C. board and   power board.   The protection stop of the zero cross detecting circuit is   continuously performed 10 times.   Lightning 12 times Zero cross detecting circuit   IPM protection   Overcurrent is detected after 30 minutes of compressor start- •Reconnect compressor connector.   up.   •Refer to 10-5. "How to check inverter/compres-   sor".   10   11   Twice   Goes out   •Refer to 10-5. "Check of compressor start failure".   •Check the stop valve.   •Check the power module (PAM module).   Overcurrent is detected within 30 minutes of compressor   start-up   Lock protection   Temperature of discharge temperature thermistor exceeds   Discharge temperature protec- 241 °F (116 °C), compressor stops. Compressor can restart   •Check the amount of gas and refrigerant circuit.   if discharge temperature thermistor reads 212 °F (100 °C) or •Refer to 10-5. "Check of LEV".   3 times   4 times   Goes out   Goes out   tion   less 3 minutes later.   Fin temperature protection   The fin temperature exceeds 189 °F (87 °C) during operation.   •Check refrigerant circuit and refrigerant amount.   •Refer to 10-5. "Check of LEV".   12   P.C. board temperature pro-   tection   The P.C. board temperature exceeds 158 °F (70 °C) during   operation.   The outdoor heat exchanger temperature exceeds 158 °F (70   °C) during cooling or indoor gas pipe temperature exceeds   158 °F (70 °C) during heating (MUZ).   'Outdoor   unit stops   and restarts   3 minutes   later' is   repeated.   •Check around of gas and the refrigerant circuit.   •Check of stop valve.   13   5 times   8 times   Goes out High-pressure protection   Goes out Converter protection   A failure is detected in the operation of the converter during   operation.   14   •Replace the power board.   •Replace the power board.   The bus-bar voltage exceeds 400 V or falls to 200 V or below   during compressor operating.   Bus-bar voltage protection (1)   Goes out   15   9 times   The bus-bar voltage exceeds 400 V or falls to 50 V or below   during compressor operating.   Bus-bar voltage protection (2)   Failure occurs continuously three times within 30 seconds   after the fan gets started.   16   17   13 times Goes out Outdoor fan motor   •Refer to 10-5. "Check of outdoor fan motor".   •Replace the power board.   A short or open circuit is detected in the current sensor during   compressor operating.   Lighting   Lighting   8 times   Current sensor protection   Communication error occurs between the outdoor electronic   control P.C. board and power board for more than 10 sec-   onds.   Communication between P.C.   boards protection   •Check the connecting wire between outdoor elec-   tronic control P.C. board and power board.   18   19   11 times   •Check the connecting wire among outdoor elec-   tronic control P.C. board, noise filter P.C. board and   power board.   Zero cross detecting circuit   protection   Zero cross signal cannot be detected while the compressor is   operating.   Lighting   12 times   NOTE 1. The location of LED is illustrated at the right figure. Refer to 10-6.1.   Outdoor electronic control P.C. board(Parts side)   2. LED is lighted during normal operation.   LED2 LED1   Lighting   0.5-second ON   0.5-second ON   ON   OFF   2.5-second OFF   2.5-second OFF   The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.   (Example) When the flashing frequency is “2”.   25   Indication   No. Symptom   20   Abnormal point / Condition   Primary current protection   Condition   The input current exceeds 15 A.   Correspondence   LED1   (Red)   LED2   (Yellow)   •These symptoms do not mean any abnormality of   the product, but check the following points.   •Check if indoor filters are clogged.   •Check if refrigerant is short.   •Check if indoor/outdoor unit air circulation is short   cycled.   Once   Lighting   Lighting   Secondary current protection The current of the compressor exceeds 15 A.   High-pressure protection   (MUZ)   The indoor gas pipe temperature exceeds 113 °F (45 °C) dur-   ing heating.   21   Twice   The indoor gas pipe temperature falls 37 °F (3 °C) or below   during cooling.   Defrosting in cooling   •Check refrigerant circuit and refrigerant amount.   •Refer to 10-5. "Check of LEV".   •Refer to 10-5. "Check of outdoor thermistors".   Discharge temperature protec- The discharge temperature exceeds 212 °F (100 °C) during   22   23   3 times   4 times   Lighting   Lighting   Outdoor   unit oper-   ates.   tion   operation.   The frequency of the compressor is kept 80 Hz or more and   the discharge temperature is kept under 102 °F (39 °C) for   more than 20 minutes.   Low discharge temperature   protection   •Refer to 10-5. "Check of LEV".   •Check refrigerant circuit and refrigerant amount.   •This symptom does not mean any abnormality of   the product, but check the following points.   Cooling high-pressure protec- The outdoor heat exchanger temperature exceeds 136 °F (58 •Check if indoor filters are clogged.   24   5 times   Lighting   tion   °C) during operation.   •Check if refrigerant is short.   •Check if indoor/outdoor unit air circulation is short   cycled.   25   26   9 times   Lighting   Lighting Inverter check mode   Lighting Normal   The unit is operated with emergency operation switch.   – – – Outdoor   unit oper-   ates   26   10-4. TROUBLE CRITERION OF MAIN PARTS   MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   Part name   Check method and criterion   Figure   Defrost thermistor   (RT61) (MUZ)   Measure the resistance with a tester.   Ambient temperature   thermistor (RT65)   Refer to 10-6. “Test point diagram and voltage”, 1. “Outdoor electron-   ic control P.C. board”, the chart of thermistor.   Outdoor heat ex-   changer temperature   thermistor (RT68)   Discharge tem-   perature thermistor   (RT62)   Measure the resistance with a tester. Before measurement, hold the   thermistor with your hands to warm it up.   Refer to 10-6. “Test point diagram and voltage”, 1. “Outdoor electron-   ic control P.C. board”, the chart of thermistor.   Fin temperature   thermistor (RT64)   Measure the resistance between terminals using a tester.   (Winding temperature : 14 ~ 104 °F (-10 ~ 40 °C))   W RED   Compressor   Normal   V WHT   U BLK   1.24 ~ 1.53 Ω   Measure the resistance between lead wires using a tester.   (Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))   RED   (W)   U Color of lead wire   RED – BLK   BLK – WHT   WHT – RED   Normal   WHT   BLK   Outdoor fan motor   R. V. coil (MUZ)   (V)   (U)   V 13 ~ 16 Ω   W Measure the resistance using a tester.   (Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))   Normal   1.20 ~ 1.55 kΩ   Measure the resistance using a tester.   (Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))   WHT   RED   ORN   LEV   Color of lead wire   WHT – RED   RED – ORN   YLW – BRN   BRN – BLU   Normal   Linear expansion   valve   38 ~ 50 Ω   YLW BRN BLU   27   10-5. TROUBLESHOOTING FLOW   OPERATION / INDICATOR lamp flashes 5-times.   Outdoor unit does not operate.   A How to check inverter/ compressor   Disconnect the terminal of the compressor. 3 minutes after turn-   ing on the power supply, start EMERGENCY OPERATION.   •After the outdoor fan starts running, wait for 1 minute or more   before measuring the voltage.   •The output voltage values have the tolerance of ±20 %.   Measure the voltage between each lead wire leading   to the compressor.   U (BLK) - V (WHT)   V (WHT) - W (RED)   No   W (RED) - U (BLK)   Is voltage output on right table?   Yes   Is output balanced?   Yes   No   No   Is the input voltage to the outdoor electronic control   P.C. board 370 V or more?   Replace the power board.   Replace the compressor.   Yes   Turn off power supply of indoor and outdoor unit, and   measure the compressor winding resistance between   the compressor terminals.   No   Is the resistance between each terminal normal?   Yes   Reconnect the lead wire of compressor, and turn on power   supply to indoor and outdoor unit.   3 minutes later, starts EMERGENCY OPERATION.   Clarify the causes by counting time until the inverter stops.   0 to 10 seconds: compressor rare short   10 to 60 seconds: compressor lock   60 seconds to 5 minutes: refrigerant circuit defective   5 minutes or more: normal   28   OPERATION INDICATOR lamp flashes 6-times.   Thermistor is abnormal.   B Check of outdoor thermistors   Disconnect the connector of thermistor in the outdoor P.C. board (see   below table), and measure the resistance of thermistor.   Replace the thermistor except RT64.   When RT64 is abnormal, replace the   outdoor power board.   Is the thermistor normal? (Refer to 10-6.1.)   No   Yes   Reconnect the connector of thermistor.   Turn ON the power supply and press EMERGENCY OPERATION switch.   Does the unit operate for 10 minutes or more   without showing thermistor abnormality?   Replace the outdoor power board.   No   Yes   OK.   (Cause is poor contact.)   Thermistor   Defrost (MUZ)   Discharge temperature   Outdoor heat exchanger temperature RT68   Ambient temperature   Fin temperature   Symbol   RT61   RT62   Connector, Pin No.   Board   Between CN661 pin1 and pin2   Between CN661 pin3 and pin4   Between CN661 pin7 and pin8   Between CN663 pin1 and pin2   Between CN3 pin1 and pin2   Outdoor electronic control P.C. board   Outdoor power board   RT65   RT64   29   The cooling operation or heating operation does not operate.   C Check of R.V. coil   MUZ-D30/36   • Heating operation does not work.   1. Disconnect the lead wire leading to the compressor.   2. 3 minutes after turning on the power supply, start EMERGENCY   OPERATION in HEAT mode.   Is there voltage of 208 / 230 VAC between pin1   and pin 2 at connector CN912?   1. Turn off power supply of indoor and outdoor unit, and discon-   nect the connector CN781 in the outdoor electronic control P.C.   board.   2. 3 minutes after turning ON the power supply, start EMER-   GENCY OPERATION in HEAT mode.   No   Yes   Turn OFF power supply of indoor and outdoor unit.   Disconnect the connec-   tor CN912 in noise filter   P.C. board. Is there normal   resistance to R.V. coil?   Is there voltage 12 VDC be-   Replace the electronic   tween the connector CN781   Replace the R.V. coil.   No   control P.C. board.   No   pin 5 (+) and pin 3 (-)?   Yes   Yes   Replace the noise filter P.C. board.   Replace the 4-way valve.   • Cooling operation does not work.   If the connector CN912 is not   1. Disconnect the lead wire leading to the compressor.   2. 3 minutes after turning on the power supply, start EMERGENCY   OPERATION in COOL mode.   connected or R.V. coil is open,   voltage occurs between terminals   even when the control is OFF.   Is there voltage of 208 / 230 VAC between pin1   and pin 2 at connector CN912?   Replace the 4-way valve.   No   1. Turn OFF power supply of indoor and outdoor unit, and   disconnect the connector CN781 in the outdoor electronic   control P.C. board.   2. 3 minutes after turning ON the power supply, start EMER-   GENCY OPERATION in COOL mode.   Is there voltage 12 VDC between the connector   CN781 pin 5 (+) and pin 3 (-)?   Replace the noise filter P.C. board.   No   Yes   Replace the outdoor electronic control P.C. board.   30   Fan motor does not operate or stops operating shortly after starting the operation.   D Check of outdoor fan motor   Check the connection between the   connector CN931 and CN932.   Is the resistance between each ter-   minal of outdoor fan motor normal?   (Refer to 10-4.)   Yes   No   Disconnect CN932 from outdoor electronic control P.C. board,   and turn on the power supply.   Rotate the outdoor fan motor manually and measure the voltage   of CN931.   Between 1(+) and 5(-)   Between 2(+) and 5(-)   Between 3(+) and 5(-)   (Fixed to either 5 or 0 VDC)   No   Does the voltage between each terminal become 5 VDC   and 0 VDC repeatedly?   Yes   Does the outdoor fan motor rotate smoothly?   Yes   No   Replace the outdoor DC fan motor.   Replace the outdoor electronic control P.C. board.   Outdoor unit does not operate.   E Check of power supply   Check the connecting of parts of main power   supply circuit.   Turn ON power supply.   Is there voltage of 208 / 230 VAC in the   power supply terminal block?   Check the power supply cable.   Replace the noise filter P.C. board.   Replace the reactor.   No   No   No   No   Yes   Is the output voltage from the noise filter P.C.   board 208 / 230 VAC?   Yes   Is the input voltage to the power board 208 /   230 VAC?   Yes   Is the input voltage to the outdoor electronic   control P.C. board 294 / 325 VDC?   Replace the power board.   Yes   Replace the outdoor electronic control P.C. board.   31   F Check of compressor start failure   Confirm that 1~4 is normal.   •Electrical circuit check   1.Contact of lead wire leading to compressor   2.Output voltage of the outdoor electronic control P.C. board and balance of them   (See 10-5. )   3.Direct current voltage to the outdoor electronic control P.C. board   4.Voltage between outdoor terminal block S1-S2   Check the refrigerant circuit.   Check the stop valve.   Does the compressor run for 10 seconds or   more after it starts?   Yes   No   No   After the compressor is heated with a drier,   Replace the compressor.   does the compressor start?   1 Yes   1 Compressor start failure. Activate pre-heat control.   (Refer to 9-1. "PRE-HEAT CONTROL")   Heat the compressor with   a drier for about 20 minutes.   Do not recover refrigerant   gas while heating.   Heating part   When cooling, heat exchanger of non-operating indoor unit frosts.   When heating, non-operating indoor unit gets warm.   G Check of LEV   Turn ON power supply to the outdoor unit after checking   LEV coil is mounted to the LEV body securely.   Is "click - click" sound heard?   Or, do you feel vibration of the LEV coil with a hand?   Normal   Yes   Yes   No   Disconnect the connector CN795.   Is there normal resistance to LEV coil?   Replace the outdoor electronic   control P.C. board.   No   Replace the LEV coil.   32   • Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.   Indoor unit does not operate.   • OPERATION INDICATOR lamp flashes ON and OFF in every 0.5 seconds.   Outdoor unit doesn’t operate.   H How to check miswiring and serial signal error   Turn OFF the power supply.   Is there rated voltage in the   Check the power supply.   power supply?   No   Yes   Turn ON the power supply.   Is there rated voltage between   outdoor terminal block S1 and   S2?   Yes   Check the wiring.   No   Press EMERGENCY OPERATION switch once.   Does the left lamp of OPERATION INDICA-   TOR lamp light up? <Confirmation of the   power to the indoor unit>   No   No   Yes   Is there any miswiring, poor   contact, or wire disconnec-   tion of the indoor/outdoor   connecting wire?   Is serial signal error indicated 6 minutes later?   Yes   Correct them.   Yes   Is fuse (F65) broken?   No   A Turn OFF the power supply.   Check once more if the indoor/outdoor   connecting wire is not miswiring.   B 1. Miswiring may damage indoor electronic control P.C.   board during the operation.   Be sure to confirm the wiring is correct before the opera-   tion starts.   Short-circuit outdoor terminal block S2   and S3.   1 3. Be sure to check this within 3 minutes after turning ON.   After 3 minutes, LED blinks 6 times. Even when the   inverter P.C. board or the outdoor electronic control P.C.   board is normal, LED blinks 6 times after 3 minutes.   Turn ON the power supply.   Outdoor electronic control P.C. board   (Parts side)   LED2 LED1   Does the LED on the inverter P.C. board or   the outdoor electronic control P.C. board   repeat "3.6-second-OFF and 0.8-second-   Replace the inverter P.C. board or   the outdoor electronic control P.C. board.   2 No   (Lighted   or not   ON quick blinking"?   3 Lighted Blinking   2. Be careful to the residual   voltage of smoothing capacitor.   Yes   lighted)   Turn OFF the power supply.   Remove the short-circuit between   outdoor terminal block S2 and S3.   Turn ON the power supply.   Is there amplitude of 10 to 20 VDC   between outdoor terminal block S2 and   S3? <Confirmation of serial signal>   Yes   Is there any error of the in-   Replace the indoor/   outdoor connecting   wire.   door/outdoor connecting wire,   such as the damage of the wire,   intermediate connection, poor   contact to the terminal block?   No   A No   Yes   • Turn OFF inverter-controlled lighting   equipment.   • Turn OFF the power supply and then   turn ON again.   • Press EMERGENCY OPERATION   switch.   Is there any error of the in-   door/outdoor connecting wire,   such as the damage of the wire,   intermediate connection, poor   contact to the terminal block?   No   Is there rated voltage between   indoor terminal block S1 and S2?   <Confirmation of power voltage>   Replace the indoor/   outdoor connecting   wire.   • Reinstall   No   Yes   either the unit   or the light   each other   Yes   away.   Is serial signal   error indicated 6   minutes later?   • Attach a filter   on remote   control   No   Yes   Replace the indoor electronic control P.C. board.   receiving   Be sure to release the failure-mode recall function   after checking.   section of the   indoor unit.   B 33   The operation frequency does not go up from lowest frequency.   I Check of HPS   1. Disconnect the connector CN681 in the electronic control P.C. board.   2. Check the resistance of HPS 1 minute after the outdoor unit power supply was turned OFF.   Check the resistance between each terminal.   Replace HPS.   Infinity   0 Ω   Reconnect CN681.   Turn ON power supply to the indoor and outdoor unit.   3 minutes later, start EMERGENCY OPERATION.   Is HPS protection displayed immediately after   compressor starts?   Replace the outdoor electronic   control P.C. board.   Yes   No   Normal   34   J Electromagnetic noise enters into TV sets or radios   Is the unit grounded?   Yes   Ground the unit.   No   Is the distance between the antennas   and the indoor unit within 9.91 ft., or is   the distance between the antennas and   the outdoor unit within 9.91 ft.?   Extend the distance between the antennas and   the indoor unit, and/or the antennas and the   outdoor unit.   Yes   No   Is the distance between the TV sets or   radios and the indoor unit within 3.28   ft., or is the distance between the TV   sets or radios and the outdoor unit   within 9.91 ft.?   Extend the distance between the TV sets and/or   radios and the indoor unit, or the TV sets or   radios and the outdoor unit.   Yes   No   Are the antennas damaged?   Is the coaxial cable damaged?   Is there any poor contact in the anten-   na wiring?   Replace or repair the antenna.   Replace or repair the coaxial cable.   Yes   Yes   No   Is the indoor/outdoor connecting wire of   the air conditioner and the wiring of the   antennas close?   Extend the distance between the indoor/outdoor   connecting wire of the air conditioner and the wir-   ing of the antennas.   No   Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength   or the installation condition (combination of specific conditions such as antennas or wiring).   Check the followings before asking for service.   1. Devices affected by the electromagnetic noise   TV sets, radios (FM/AM broadcast, shortwave)   2. Channel, frequency, broadcast station affected by the electromagnetic noise   3. Channel, frequency, broadcast station unaffected by the electromagnetic noise   4. Layout of ;   indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver   5. Electric field intensity of the broadcast station affected by the electromagnetic noise   6. Presence or absence of amplifier such as booster   7. Operation condition of air conditioner when the electromagnetic noise enters in   1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic   noise.   2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for   power ON, and check for the electromagnetic noise.   3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the elec-   tromagnetic noise.   4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the   indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.   35   10-6. TEST POINT DIAGRAM AND VOLTAGE   1. Outdoor electronic control P.C. board   MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   Defrost thermistor (RT61)   Ambient temperature thermistor (RT65)   Outdoor heat exchanger temperature thermistor (RT68)   100   Fin temperature thermistor (RT64)   Discharge temperature thermistor (RT62)   200   180   160   140   120   100   80   700   600   500   400   300   200   100   0 90   80   70   60   50   40   30   20   10   0 60   40   20   0 32 50 68 86 104 122 140 158 176   32   50   68   86 104 122 140 176 194 122 212 230 248   Temperature (°F)   Temperature (°F)   -4   14   32   50   68   86 104   Temperature (°F)   LED 1   LED 2   CN801   294 ~ 370   VDC   Input   F801   FUSE   3.15 A / 250 V   CN601   ( ( 208/230 VAC   60 Hz   for indoor   5~10 VDC   Input   ( CN681   High pressure switch   36   2. Noise filter P.C. board   MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   CN901   To electronic   control P.C.   board   CN902   To power   board   CN903   To power   board   208 / 230 VAC   60 Hz   Input   MUZ   CN912   R.V. coil   208 / 230 VAC   60 Hz   { Output   208 / 230 VAC   60 Hz   Output   { CN61   F64 FUSE   2 A / 250 V   NR64 VARISTOR   37   3. Outdoor power board   MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   Connect to the compressor   Voltage among phases: 180 V   Connect to the earth   294-370 VDC   CN2   Output   (Red)   Connect to the controller board   (+)1-5(–): Signal transmission   (To electronic control P.C. board)   5 VDC pulse wave   (+)   (–)   1 3 (+)2-5(–): Zero cross signal   3-4 : Not used   (White)   (+)6-5(–): 15 V   (+)7-5(–): 15 V   CN3   Fin temperature thermistor RT64   Signal reception (From electronic   control P.C. board)   ) 5 VDC pulse wave   CN5   Primary current detection   (Connect to the noise filter)   38   11   DISASSEMBLY INSTRUCTIONS   <"Terminal with locking mechanism" Detaching points>   The terminal which has the locking mechanism can be detached as shown below.   There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.   The terminal without locking mechanism can be detached by pulling it out.   Check the shape of the terminal before detaching.   (1) Slide the sleeve and check if there is a locking lever or not.   (2) The terminal with this connector has the   locking mechanism.   Sleeve   ꢀSlide the sleeve.   ꢀHold the sleeve, and   ꢁPull the terminal while   pushing the locking   pull out the terminal   slowly.   Locking lever   lever.   Connector   MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   OPERATING PROCEDURE   PHOTOS   1. Removing the cabinet   Photo 1   (1) Remove the screws of the service panel.   (2) Remove the screws of the top panel.   (3) Remove the screw of the valve cover.   (4) Remove the service panel.   Screw of   the top   panel   (5) Remove the top panel.   (6) Remove the valve cover.   (7) Remove the screws of the cabinet.   (8) Remove the cabinet.   (9) Remove the screws of the back panel.   (10) Remove the back panel.   Screws   of the   cabinet   Screws of the cabinet   Photo 2   Photo 3   Screw of the motor support   Screw of the service panel   Screws of the   top panel   Conduit plate   Set screws of   the back panel   Screws of   the back   panel   Screws   of the   cabinet   Screw of the   valve cover   Set screws of the back panel   39   OPERATING PROCEDURE   PHOTOS   2. Removing the inverter assembly, P.C. board and   power board   Photo 4   (1) Remove the top panel, cabinet, service panel and the back   panel. (Refer to 1.)   (2) Disconnect the following connectors;   <Electronic control P.C. board>   Screws of the reactor   CN931 and CN932 (Fan motor)   CN795 (LEV)   CN661 (Discharge temperature thermistor, defrost   thermistor (MUZ) and outdoor heat exchanger   temperature thermistor)   HPS   CN663 (Ambient temperature thermistor)   CN681 (High pressure switch) (MUZ)   <Noise filter P.C. board>   Discharge temperature   thermistor   CN912 (4-way valve) (MUZ)   <Compressor>   <Reactor>   (4) Remove the screws fixing the relay panel.   (5) Remove the inverter assembly.   (6) Disconnect all connectors and lead wires on the electronic   control P.C. board.   (7) Remove the electronic control P.C. board from the inverter   assembly.   Photo 5 (Inverter assembly)   (8) Remove the screws fixing the power board assembly.   (9) Disconnect all connectors and lead wires on the power   board.   Screws of the power board assembly   (10) Remove the power board from the inverter assembly.   (11) Disconnect all connectors and lead wires on the noise filter   P.C. board.   (12) Remove the noise filter P.C. board from the inverter   assembly.   3. Removing R.V. coil (MUZ)   (1) Remove the top panel, cabinet, service panel and the back   panel. (Refer to 1.)   (2) Disconnect the following connectors;   <Noise filter P.C. board>   Screws of the relay panel   CN912 (4-way valve)   (3) Remove the R.V. coil. (Photo 9)   Photo 6   Screws of the   relay panel   Propeller   40   OPERATING PROCEDURE   PHOTOS   4. Removing the defrost thermistor (MUZ), discharge   temperature thermistor, outdoor heat exchanger   temperature thermistor and ambient temperature   thermistor   Photo 7   Outdoor heat   exchanger   temperature   thermistor   (1) Remove the top panel, cabinet, service panel and the back   panel. (Refer to 1.)   (2) Disconnect the following connectors;   <Electronic control P.C. board>   CN661 (Discharge temperature thermistor, defrost therm-   istor (MUZ) and outdoor heat exchanger tem-   perature thermistor)   Ambient   temperature   thermistor   CN663 (Ambient temperature thermistor)   (3) Pull out the defrost thermistor from its holder. (Photo 7)   (MUZ)   (4) Pull out the discharge temperature thermistor from its hold-   er. (Photo 4)   (5) Pull out the outdoor heat exchanger temperature thermistor   from its holder. (Photo 7)   (6) Pull out the ambient temperature thermistor from its holder.   (Photo 7)   Defrost   thermistor   (for MUZ)   5. Removing outdoor fan motor   (1) Remove the top panel, cabinet, service panel and the back   panel. (Refer to 1.)   Photo 8   Screws of the outdoor fan motor   (2) Disconnect the following connectors;   <Electronic control P.C. board>   Propeller   CN931 and CN932 (Fan motor)   (3) Remove the propeller.   (4) Remove the screws fixing the outdoor fan motor.   (5) Remove the outdoor fan motor.   41   OPERATING PROCEDURE   PHOTOS   6. Removing the compressor and 4-way valve   (1) Remove the top panel, cabinet, service panel and the back   panel. (Refer to 1.)   Photo 9   (2) Remove the inverter assembly. (Refer to 2.)   (3) Remove the R.V. coil. (Refer to 3.)   (4) Recover gas from the refrigerant circuit.   NOTE: Recover gas from the pipes until the pressure   gauge shows 0 PSIG.   (5) Detach the welded part of the suction and the discharge   pipe connected with compressor. (Photo 9)   (6) Remove the compressor nuts.   (7) Remove the compressor.   (8) Detach the welded part of 4-way valve and pipe. (Photo 8)   Welded parts of 4-way valve   R.V. coil   Photo 10   Welded part of the   discharge pipe   Welded part of the   suction pipe   7. Removing the reactor   (1) Remove the top panel, cabinet, service panel and the back   panel. (Refer to 1.)   (2) Disconnect the reactor lead wire.   (3) Remove the screws of the reactor, and remove the reactor.   42   43   TM   HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN   Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD   Distributed in Feb. 2008. No. OBH502 7   Made in Japan   New publication, effective Feb. 2008   Specifications subject to change without notice.   |