| Mitsubishi Electronics Mitsubishi Digital Electronics Air Conditioner Muz Ana U User Manual | 
| Revision B:   • MXZ-2A20NA- 1 , MXZ-4A36NA, MSZ-FD,   MSZ-D and MSY-D have been added.   Please void OBT16 REVISED EDITION-A.   No. OBT16   REVISED EDITION-B   SERVICE TECHNICAL GUIDE   Wireless type Models   MS-A•WA   MSZ-A•NA   · MU-A•WA   · MUZ-A•NA   · MUZ-A•NA -   · MUY-A•NA   U MSY-A•NA   MSZ-FD•NA · MUZ-FD•NA   U · MUZ-FD•NA -   · MUZ-D•NA   MSZ-D•NA   MSY-D•NA   U · MUZ-D•NA -   · MUY-D•NA   Inverter-controlled multi system type Models   · MXZ-A•NA   CONTENTS   1. MS MICROPROCESSOR CONTROL··················4   2. MSZ, MSY MICROPROCESSOR CONTROL······7   3. MXZ MICROPROCESSOR CONTROL··············21   1. MS MICROPROCESSOR CONTROL···························································4   Indoor unit models   Outdoor unit models   MS-A09WA   MS-A12WA   MU-A09WA   MU-A12WA   1-1. COOL OPERATION ···············································································4   1-2. DRY OPERATION ··················································································4   1-3. AUTO VANE OPERATION·····································································6   2. MSZ, MSY MICROPROCESSOR CONTROL···············································7   Indoor unit models   Outdoor unit models   MSZ-A09NA   MSZ-A12NA   MSZ-A15NA   MSZ-A17NA   MSZ-A24NA   MSY-A15NA   MSY-A17NA   MSY-A24NA   MSZ-FD09NA MUZ-A09NA   MSZ-FD12NA MUZ-A12NA   MUZ-FD09NA   MUZ-FD12NA   MUZ-D30NA   MUZ-D36NA   MUY-D30NA   MUY-D36NA   MSZ-D30NA   MSZ-D36NA   MSY-D30NA   MSY-D36NA   MUZ-A15NA   MUZ-A17NA   MUZ-A24NA   MUY-A15NA   MUY-A17NA   MUY-A24NA   2-1. COOL OPERATION ··············································································7   2-2. DRY OPERATION ·················································································8   2-3. HEAT OPERATION···············································································8   2-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION ·····················10   2-5. OUTDOOR FAN MOTOR CONTROL·················································11   2-6. AUTO VANE OPERATION··································································11   2-7   2-8   2-9   . . . INVERTER SYSTEM CONTROL························································12   OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT ·····17   EXPANSION VALVE CONTROL (LEV CONTROL)···························18   3. MXZ MICROPROCESSOR CONTROL·······················································21   Outdoor unit models   MXZ-2A20NA   MXZ-3A30NA   MXZ-4A36NA   3-1. INVERTER SYSTEM CONTROL·························································21   3-2. EXPANSION VALVE CONTROL (LEV CONTROL)····························23   3-3. OPERATIONAL FREQUENCY RANGE ··············································29   3-4. HEAT DEFROSTING CONTROL·························································30   3-5. DISCHARGE TEMPERATURE PROTECTION CONTROL·······················30   3-6. OUTDOOR FAN CONTROL ································································30   3-7. PRE-HEAT CONTROL·········································································31   3-8. COOL OPERATION····················································································31   3-9. DRY OPERATION·································································· BACK COVER   3-10   . HEAT OPERATION···························································BACK COVER   3 1 MS MICROPROCESSOR CONTROL   MS-A•WA   MU-A•WA   1-1. COOL ( ) OPERATION   1. Thermostat control   Thermostat is ON or OFF by difference between room temperature and set temperature   Room temperature minus   Room temperature minus   set temperature (Initial)   set temperature (During operation)   Thermostat   ON   OFF   -1.8 °F or more   less than-1.8 °F   -1.8 °F   -1.3 °F   2. Indoor fan speed control   Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat’s OFF-   ON.   In AUTO the fan speed is as follows.   Room temperature minus   set temperature (Initial)   3.1 °F or more   Room temperature minus   set temperature (During operation)   Fan speed   High   Med.   Low   between 1.8 and 3.1 °F   less than 1.8 °F   5.4 °F   3.1 °F   1.8 °F   3. Coil frost prevention   Temperature control   When the indoor coil thermistor RT12 reads 37 °F or below the coil frost prevention mode starts immediately.   However, the coil frost prevention doesn’t work for 5 minutes since the compressor has started.   The indoor fan operates at the set speed and the compressor stops for 5 minutes.   After that, if the indoor coil thermistor still reads below 37 °F, this mode is prolonged until the indoor coil thermistor reads   over 37 °F.   Time control   When the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.   a. Compressor has been continuously operating.   b. Indoor fan speed is Low or Med.   c. Room temperature is below 79 °F.   When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the   beginning.   Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds 79 °F.   However, when two of the above conditions (b. and c.) are satisfied again. Time accumulation is resumed.   Operation chart   Example   ON   Compressor   Outdoor fan   OFF   ( Continuously at set speed)   Indoor fan   ON   Set temperature and   initial room temperature in dry mode   1-2. DRY ( ) OPERATION   °F   95   Set temperature is as shown on the right chart.   The system for dry operation uses the same refrigerant circuit as the   cooling circuit.   The compressor and the indoor fan are controlled by the room tem-   perature.   By such controls, indoor flow amounts will be reduced in order to   lower humidity without much room temperature decrease.   86   77   68   59   50   50   59   68   77   86   95 °F   Initial room temperature   4 1. Thermostat control   Thermostat is ON or OFF by difference between room temperature and set temperature.   Room temperature minus   Room temperature minus   set temperature (Initial)   set temperature (During operation)   Thermostat   ON   OFF   -1.8 °F or more   less than-1.8 °F   -1.8 °F   -1.3 °F   2. Indoor fan speed control   Indoor fan operates at the set speed by FAN SPEED CONTROL button.   When thermostat OFF (compressor OFF), fan speed becomes Very Low.   In AUTO the fan speed is as follows.   Room temperature minus   set temperature (Initial)   3.1 F or more   Room temperature minus   set temperature (During operation)   Fan speed   High   Med.   Low   between 1.8 and 3.1 F   less than 1.8 F   4.5   F 3.1   F 1.8   F 3. The operation of the compressor and indoor/ outdoor fan   Compressor operates by room temperature control and time control.   Set temperature is controlled to fall 4 °F from initial room temperature.   Indoor fan and outdoor fan operate in the same cycle as the compressor.   •When the room temperature is 73 °F or over:   When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.   When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.   •When the room temperature is under 73 °F.   When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.   When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.   Operation time chart   Example   ON   Thermostat   OFF   ON   Indoor fan   OFF   ON   Outdoor fan   Compressor   OFF   8 minutes   4 minutes   3 minutes   1 minute   4. Coil frost prevention   Coil frost prevention is as same as COOL mode. (2-1.3.)   The indoor fan maintains the actual speed of the moment. However ,when coil frost prevention works while the compressor   is not operating, its speed becomes the set speed.   5 1-3. AUTO VANE OPERATION   1. Horizontal vane   ECONO COOL (   ) operation (ECONOmical operation)   When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6 °F higher than that in   COOL mode.   Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger (indoor coil   thermistor).   SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that   in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved.   ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE CONTROL button is   pressed or change to other operation mode.   <SWING operation>   In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.   According to the temperature of indoor coil thermistor at starting of this operation, next downward blow time is decided.   Then when the downward blow has been finished, next horizontal blow time is decided.   For initial 10 minutes the swing operation is performed in table G~H for quick cooling.   Also, after 10 minutes when the difference of set temperature and room temperature is more than 3.6 °F, the swing   operation is performed in table D~H for more cooling.   The air conditioner repeats the swing operation in various cycle as follows.   Temperature of indoor   coil thermistor (°F)   Downward blow time Horizontal blow time   (second)   (second)   A B C D E F 59 or less   59 to 63   63 to 64   64 to 68   68 to 70   70 to 72   72 to 75   more than 75   2 5 8 11   14   17   20   23   23   20   17   14   11   8 G H 5 2 6 2 MSZ,MSY MICROPROCESSOR CONTROL   MSZ-A•NA   MSY-A•NA   MUZ-A•NA   MUY-A•NA   MSZ-FD•NA MSY-D•NA   MSZ-D•NA   MUZ-FD•NA MUY-D•NA   MUZ-D•NA   2-1. COOL ( ) OPERATION   1. Thermostat control   Thermostat is ON or OFF by difference between room temperature and set temperature   Room temperature minus   set temperature (Initial)   Room temperature minus   set temperature (During operation)   Thermostat   ON   OFF   -1.8 °F or more   less than-1.8 °F   -1.8 °F   -1.3 °F   2. Indoor fan speed control   Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat’s OFF-   ON.   In AUTO the fan speed is as follows.   Room temperature minus   set temperature (Initial)   3.1 °F or more   Room temperature minus   set temperature (During operation)   MSZ-A   MSY-A   Fan speed   High   Med.   Low   between 1.8 and 3.1 °F   less than 1.8 °F   5.4 °F   3.1 °F   1.8 °F   Room temperature minus   set temperature (Initial)   2.7 °F or more   between 1.8 and 2.7 °F   less than 1.8 °F   Room temperature minus   set temperature (During operation)   MSZ-FD   MSZ-D   MSY-D   Fan speed   High   Med.   Low   5.4 °F   2.7 °F   1.8 °F   3. Coil frost prevention   The compressor operational frequency is controlled to prevent the temperature of indoor heat exchanger from falling exces-   sively.   The compressor is turned OFF for 5 minutes when the temperature of indoor coil thermistor continues 37 °F or less for 5   minutes or more.   The indoor fan maintains the actual speed of the moment.   4. Low outside temperature operation   If the outside temperature falls to 64 °F or less during operation in COOL mode, the unit will switch to the low outside tem-   perature operation mode.   <Operation>   (1) Outdoor fan control   The outdoor fan rotation speed slows down to maintain sufficient cooling capacity.   NOTE: Even when the unit is in the "thermostat-off" status under the low outside temperature operation mode, the out-   door fan rotation does not stop.   (2) Dew drop prevention   When the ambient temperature thermistor reads 10 °F (MUZ-A MUY-A MUZ-D MUY-D), -4 °F (MUZ-FD) or less, as   coil frost or dew drop from indoor unit may occur, the compressor turns OFF with the outdoor fan ON for prevention of   them.   (3) Outdoor temperature detecting control   To detect the exact outdoor temperature in this mode, the compressor turns OFF but the outdoor fan stays ON for 3   minutes once 1 hour. If the outdoor temperature rises over 64 °F, the unit goes back to the normal COOL mode. If the   outside temperature stays below 64 °F, the unit continues to run in the low outside temperature operation mode.   Other protections work as well as in the normal COOL mode.   7 Set temperature and   initial room temperature in dry mode   2-2. DRY ( ) OPERATION   °F   95   Set temperature is as shown on the right chart.   The system for dry operation uses the same refrigerant circuit as the   cooling circuit.   The compressor and the indoor fan are controlled by the room tem-   perature.   By such controls, indoor flow amounts will be reduced in order to   lower humidity without much room temperature decrease.   86   77   68   59   50   50   59   68   77   86   95 °F   Initial room temperature   1. Thermostat control   Thermostat is ON or OFF by difference between room temperature and set temperature.   Room temperature minus   set temperature (Initial)   Room temperature minus   set temperature (During operation)   Thermostat   ON   OFF   -1.8 °F or more   less than-1.8 °F   -1.8 °F   -1.3 °F   2. Indoor fan speed control   Indoor fan operates at the set speed by FAN SPEED CONTROL button.   When thermostat OFF (compressor OFF), fan speed becomes Very Low.   In AUTO the fan speed is as follows.   Room temperature minus   set temperature (Initial)   3.1 F or more   Room temperature minus   set temperature (During operation)   Fan speed   High   Med.   Low   between 1.8 and 3.1 F   less than 1.8 F   4.5   F 3.1   F 1.8   F 3. Coil frost prevention   Coil frost prevention is as same as COOL mode. (2-1.3.)   The indoor fan maintains the actual speed of the moment. However ,when coil frost prevention works while the compressor   is not operating, its speed becomes the set speed.   4. Low outside temperature operation   Low outside temperature operation is as same as COOL mode. (2-1.4.)   2-3. HEAT ( ) OPERATION (MSZ)   1. Thermostat control   Thermostat is ON or OFF by difference between room temperature and set temperature.   Room temperature minus   set temperature (Initial)   less than 3.6 °F   Room temperature minus   set temperature (During operation)   Thermostat   ON   OFF   3.6 °F or more   3.6 °F   3 °F   2. Indoor fan speed control   (1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.   In Auto the fan speed is as follows.   Room temperature minus   set temperature (Initial)   Room temperature minus   set temperature (During operation)   Fan speed   High   Med.   Low   3.6 °F or more   between 0.4 and 3.6 °F   less than 0.4 °F   3.6 °F 7.2 °F   0.4 °F   3 °F   8 (2) Cold air prevention control   MSZ-A09/12/15/17 MSZ-FD MSZ-D   When the compressor is not operating,   ( ) if the temperature of room temperature thermistor is less than 66 °F, the fan stops.   ( ) if the temperature of room temperature thermistor is 66 °F or more and   ( ) if the temperature of indoor coil themistor is less than 32 °F, the fan stops.   ( ) if the temperature of indoor coil themistor is 32 °F or more, the fan operates at Very Low.   When the compressor is operating,   ( ) if the temperature of indoor coil themistor is 104 °F or more, the fan operates at set speed.   ( ) if the temperature of indoor coil themistor is less than 104 °F and   ( ) if heating operation starts after defrosting, the fan stops.   ( ( ) if the temperature of room temperature thermistor is 66 °F or less, the fan stops.   ) if the temperature of room temperature thermistor is more than 66 °F, the fan operates at Very Low.   NOTE : When 3 minutes have passed since the compressor started operation, this control is released regardless of the   temperature of room temperature thermistor and indoor coil thermistor.   MSZ-A24   When the compressor is not operating,   ( ) if the temperature of room temperature thermistor is 59 °F or less, or temperature of indoor coil thermistor is   less than 64 °F, the fan stops.   ( ) if the temperature of room temperature thermistor is more than 59 °F, or temperature of indoor coil themistor is   more than 64 °F, the fan operates at Very Low.   When the compressor is operating,   ( ) if the temperature of indoor coil themistor is 64 °F or more, the fan operates at set speed.   ( ) if the temperature of indoor coil themistor is less than 64 °F and   ( ) if heating operation starts after defrosting, the fan stops.   ( ( ) if the temperature of room temperature thermistor is 59 °F or less, the fan stops.   ) if the temperature of room temperature thermistor is more than 59 °F, the fan operates at Very Low.   NOTE : When 3 minutes have passed since the compressor started operation, this control is released regardless of the   temperature of room temperature thermistor and indoor coil thermistor.   (3) Warm air control (MSZ-FD)   When the following any condition of (a. ~ c.) and the condition of are satisfied at the same time, warm air control   works.   a.) Fan speed is used in MANUAL.   b.) When cold air prevention has been released.   c.) When defrosting has been finished.   When the temperature of indoor coil thermistor is less than 104 °F.   When warm air control works, the fan speed changes as follows to blow out warm air gradually.   Gradation of fan speed in initial   <Time condition>   <Indoor fan speed>   Less than 2 minutes------------ Low   2 minutes to 4 minutes -------- Med.   More than 4 minutes ----------- High or Super high   The upper limit of the fan speed in MANUAL is the set speed.   When the temperature of indoor coil thermistor has been 104 °F or more, or when the set speed has been changed, this   control is released and the fan speed is the set speed.   3. Overload starting   When the room temperature thermistor reads 64 °F or more, the compressor runs with its maximum frequency regulated for   10 minutes after the start-up.   4. Defrosting   (1) Starting conditions of defrosting   When the following conditions a) ~ c) are satisfied, the defrosting starts.   a) The defrost thermistor reads 27 °F or less.   b) The cumulative operation time of the compressor has reached any of the set values (40, 45, 55, 65, 75, 85, 95, 105,   115, 125, 150 minutes.   c) More than 5 minutes have passed since the start-up of the compressor.   Set value of compressor operation time (here in after referred to as defrost interval)   This is decided by the temperature of defrost thermistor, ambient temperature thermistor, and the previous defrosting   time. For example, the first defrost interval is 40 minutes long, and the second is 45 minutes long. The third and sub-   sequent intervals are set to be longer, and less frequent, depending on defrosting time.   … The third and subsequent defrost intervals follow any of the three patterns 5 or 10 to 20 minutes longer, the same,   … or 5 or 10 to 20 minutes shorter compared with the previous defrost interval   shortest 40 minutes.   with the longest 125 minutes and the   9 (2) Releasing conditions of defrosting   Defrosting is released when any of the following conditions is satisfied:   a) The defrost thermistor continues to read 50 °F or more (MUZ-A09/12 MUZ-D) / 41 °F or more (MUZ-A15/17 MUZ-FD) /   59 °F or more (MUZ-A24) for 30 seconds.   b) Defrosting time has exceeded 10 minutes.   c) Any other mode than HEAT mode is set during defrosting.   Time chart of defrosting in HEAT mode (reverse type)   <Indoor unit>   horizontal   set position   set speed   set position   set speed   Horizontal vane   Indoor fan   < horizontal (temperature of indoor coil thermistor 102 °F)   Very Low (temperature of indoor coil thermistor > 64 °F)   OFF   30   seconds   <Outdoor unit>   Maximum frequency   Compressor normal   OFF   30   OFF   30   40   40   seconds seconds   seconds seconds   5 seconds   5 seconds   ON   ON   Outdoor fan   OFF   ON (HEAT)   ON (HEAT)   R.V. coil   (21S4)   OFF (COOL)   2-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION (MSZ)   Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation.   1. Mode selection   (1) Initial mode   At first indoor unit operates only indoor fan with outdoor unit OFF for 3 minutes to detect present room temperature.   Following the conditions below, operation mode is selected.   If the room temperature thermistor reads more than set temperature, COOL mode is selected.   If the room temperature thermistor reads set temperature or less, HEAT mode is selected.   10   (2) Mode change   In case of the following conditions, the operation mode is changed.   COOL mode changes to HEAT mode when 15 minutes have passed with the room temperature 4 °F below the set   temperature.   HEAT mode changes to COOL mode when 15 minutes have passed with the room temperature 4 °F above the set   temperature.   In the other cases than the above conditions, the present operation mode is continued.   NOTE1: Mode selection is performed when multi standby (refer to NOTE2) is released and the unit starts operation with   ON-timer.   NOTE2: If two or more indoor units are operating in multi system, there might be a case that the indoor unit, which is   operating in AUTO (   of standby.   ), cannot change over the other operating mode (COOL   HEAT) and becomes a state   (3) Indoor fan control/ Vane control   As the indoor fan speed and the horizontal vane position depend on the selected operation mode, when the operation   mode changes over, they change to the exclusive ones.   2-5. OUTDOOR FAN MOTOR CONTROL   Fan speed is switched according to the compressor frequency.   <Relation between compressor frequency and fan speed>   Compressor frequency (Hz)   Fan speed   High   Down   Up   Down   Up   MUZ-A   MUY-A   33   44   Low   Min. Compressor frequency Max.   MUZ-FD   33   39   44   54   MUZ-D   MUY-D   2-6. AUTO VANE OPERATION   1. Horizontal vane   (1) Cold air prevention in HEAT operation (MUZ)   When any of the following conditions occurs in HEAT operation, the vane angle changes to Horizontal position automati-   cally to prevent cold air blowing on users.   Compressor is not operating.   Defrosting is performed.   Indoor coil thermistor temperature does not exceed 102 °F within about 3 minutes after compressor starts.   NOTE: When 2 or more indoor units are operated with multi outdoor unit, even if any indoor unit turns thermostat off,   this control doesn’t work in the indoor unit.   (2) ECONO COOL (   ) operation (ECONOmical operation)   When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6 °F higher than that in   COOL mode.   Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger (indoor coil   thermistor).   SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that   in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved.   ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE CONTROL button is   pressed or change to other operation mode.   11   <SWING operation>   In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.   According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is   decided. Then when the downward blow has been finished, next horizontal blow time is decided.   For initial 10 minutes the swing operation is performed in table G~H for quick cooling.   Also, after 10 minutes when the difference of set temperature and room temperature is more than 3.6 °F, the swing   operation is performed in table D~H for more cooling.   The air conditioner repeats the swing operation in various cycle as follows.   Temperature of indoor   coil thermistor (°F)   Downward blow time Horizontal blow time   (second)   (second)   A B C D E F 59 or less   59 to 63   63 to 64   64 to 68   68 to 70   70 to 72   72 to 75   more than 75   2 5 8 11   14   17   20   23   23   20   17   14   11   8 G H 5 2 2-7. INVERTER SYSTEM CONTROL   2-7-1. Inverter main power supply circuit   MUZ-A09/12/15/17   MUY-A15/17   MUZ-FD   CURRENT   DIODE   TRANSFORMER   REACTOR   MODULE1   U U V P NOISE   FILTER   CIRCUIT   RESISTOR   RELAY   + + POWER   SUPPLY   ~ ~ SMOOTHING   CAPACITOR   MS   3~   V - N W W IPM   COMPRESSOR   + ~ ~ SWITCHING   POWER   TRANSISTOR   DIODE   MODULE2   - BOOSTER CHOPPER CIRCUIT   Function of main parts   NAME   FUNCTION   INTELLIGENT POWER MODULE (IPM)   SMOOTHING CAPACITOR   CURRENT TRANSFORMER   DIODE MODULE 1   It supplies three-phase AC power to compressor.   It stabilizes the DC voltage and supply it to IPM.   It measures the current of the compressor motor.   It converts the AC voltage to DC voltage.   It absorbs the rush current not to run into the main power supply circuit when   the electricity turns ON.   RESISTOR   RELAY   It short-circuits the resistance which restricts rush current during the normal   operation after the compressor startup.   DIODE MODULE 2   BOOSTER   It improves power factor.   It controls the bus-bar voltage.   SWITCHING POWER TRANSISTOR   CHOPPER   CIRCUIT   REACTOR   12   MUZ-A24   MUY-A24   MUZ-D   MUY-D   CURRENT   TRANSFORMER   REACTOR   U U V P N NOISE   FILTER   CIRCUIT   RESISTOR   RELAY   + POWER   SUPPLY   SMOOTHING   CAPACITOR   MS   3~   PFC   V W W IPM   COMPRESSOR   Function of main parts   NAME   FUNCTION   INTELLIGENT POWER MODULE (IPM)   SMOOTHING CAPACITOR   It supplies three-phase AC power to compressor.   It stabilizes the DC voltage and supplies it to IPM.   It measures the current of the compressor motor.   It measures the current of the main power supply circuit.   CURRENT TRANSFORMER   REACTOR   It rectifies AC, controls its voltage and improves the power factor of power   supply.   POWER FACTOR CORRECTION MODULE (PFC)   RESISTOR   RELAY   It restricts rush current with the resistance.   It short-circuits the resistance which restricts rush current during the compres-   sor operates.   13   2-7-2. Outline of main power supply circuit   MUZ-A09/12/15/17 MUY-A15/17 MUZ-FD   1. At the start of operation   Main power supply circuit is formed when RELAY is turned ON at COMPRESSOR startup.   To prevent rush current from running into the circuit when power supply is turned ON,   RESISTOR is placed in sub circuit.   2. At normal operation   When AC runs into POWER P.C. board, its external noise is eliminated in NOISE FILTER CIRCUIT.   After noise is eliminated from AC, it is rectified to DC by DIODE MODULE 1.   DC voltage, to which AC has been rectified by process , is stabilized by SMOOTHING CAPACITOR and supplied to IPM.   DC voltage, which has been stabilized in process , is converted to three-phase AC by IPM and supplied to COMPRES-   SOR.   CURRENT TRANSFORMER, which is placed in the power supply circuit to COMPRESSOR, are used to measure the val-   ue of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls impressed   voltage and frequency with those information.   3. Purpose of PAM adoption   PAM : Pulse Amplitude Modulation   PAM has been adopted for the efficiency improvement and the adaptation to IEC harmonic current emission standard   Outline of simple partial switching method   In conventional inverter models, DIODE MODULE rectifies AC voltage to DC voltage, SMOOTHING CAPACITOR makes its   DC waveform smooth, and IPM converts its DC voltage to imitated AC voltage again in order to drive the compressor motor.   However, it has been difficult to meet IEC harmonic current emission standard by above circuit because harmonic gets   generated in the input current waveform and power factor gets down. The simple partial switching method with PAM, which   has been adopted this time, places and utilizes BOOSTER CHOPPER CIRCUIT before rectifying AC voltage in the general   passive-method converter circuit. As harmonic gets suppressed and the peak of waveform gets lower by adding BOOSTER   CHOPPER CIRCUIT as mentioned above and by synchronizing the timing of switching with the zero-cross point of waveform,   the input current waveform can be improved and the requirement of IEC harmonic current emission standard can be satisfied.   Since the switching synchronized with the zero cross point, this simple partial switching method has the feature of lower en-   ergy loss compared to active filter method. In addition, output and efficiency is enhanced by combining with vector-controlled   inverter in order to boost the voltage of power supplied to IPM.   Input current waveform without PAM   Input current waveform with PAM   Due to the time of no electricity;   · Power factor gets worse.   · Harmonic gets increased.   Owing to the increase of energized time;   · Power factor gets better.   · Harmonic gets suppressed.   Input current   Input voltage   Energized time is short in   case L inductance is small.   No electricity runs into   diode module because the   voltage at both sides of smoothing   capacitor is higher than input voltage.   14   4. Intelligent power module   IPM consists of the following components   · IGBT (x6)   : Converts DC waveform to three-phase AC waveform and outputs it.   · Drive Circuit   · Protection circuit   : Drives transistors.   : Protects transistors from overcurrent.   Since the above components are all integrated in IPM, IPM has a merit to make the control circuit simplify and miniaturize.   5. Elimination of electrical noise   NOISE FILTER CIRCUIT, which is formed by *CMC COILS capacitors placed on the POWER P.C. board, eliminates electri-   cal noise of AC power that is supplied to main power supply circuit. And this circuit prevents the electrical noise generated in   the inverter circuit from leaking out.   *CMC COILS; Common mode choke coils   MUZ-A24 MUY-A24 MUZ-D MUY-D   1. At the start of operation   Main power supply circuit is formed when RELAY is turned ON at COMPRESSOR startup.   To prevent rush current from running into the circuit when power supply is turned ON, RESISTOR are placed in sub circuit.   2. At normal operation   When AC runs into noise filter P.C. board, its external noise is eliminated in NOISE FILTER CIRCUIT.   After noise being eliminated from AC, it is rectified to DC by REACTOR and PFC. If the operating frequency becomes 25   Hz or more, DC voltage rises to 370 V.   DC voltage, to which has AC been rectified by process , is stabilized by SMOOTHING CAPACITOR and supplied to IPM.   The DC (Bus voltage), which has been stabilized in process , is converted to three-phase AC by IPM and supplied to   COMPRESSOR.   CURRENT TRANSFORMER, which is placed in the power supply circuit to COMPRESSOR, are used to measure the   value of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls im-   pressed voltage and frequency with those information.   3. Power factor improvement   Booster coil reactor and power factor controller rectify AC to DC and control its voltage.   In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. PFC and reactor stabi-   lize the voltage of DC supplied to inverter circuit and make its waveform smooth.   4. Power transistor module   IPM consists of the following components.   · Power Transistors (x6) : Converts DC waveform to three-phase AC waveform and outputs it.   · Drive Circuit   : Drives transistors.   · Protection circuit   : Protects transistors from over current.   Since the above components are all integrated in IPM, IPM has a merit that can get the control circuit simplified and miniatur-   ized.   5. Elimination of electrical noise   NOISE FILTER CIRCUIT, which is formed by *CMC COILS and capacitors placed on the noise filter P.C. board, eliminates   electrical noise of AC power that is supplied to main power supply circuit. In short, common mode noise is absorbed in this   circuit.   Moreover, normal mode noise is absorbed in another NOISE FILTER CIRCUIT which is formed by *NMC COILS and capaci-   tors.   Both NOISE FILTER CIRCUIT exists for preventing the electrical noise generated in the inverter circuit from leaking out.   *CMC COILS; Common mode choke coils   *NMC COILS; Normal mode choke coils   15   2-7-3. Sine wave control   In these air conditioners, compressor equips brushless DC motor which doesn't have Hall element.   In short, the motor is sensorless. However, it's necessary to locate the polar direction of rotor in order to drive brushless DC mo-   tor efficiently. The general detection method of the polar direction for such a DC motor is to locate it from the voltage induced by   unenergized stator.   Therefore, it is necessary to have a certain period of time in which the stator is being unenergized for the rotor position detection   when the voltage of supplied power is impressed.   So the motor has been driven by square wave control (the conventional motor drive system) which energizes the motor only   when the range of electrical angle is within 120° because it is forced to be unenergized within 30° at start & end of one heap in   one waveform cycle (180°) when the voltage is impressed.   However, torque pulsation occurs at rotation in this method when the current-carrying phases are switched over to other phases   in sequence. Therefore, sine wave control system is adopted for these air conditioners because it can make the phase-to-phase   current waveform smoother (sine wave) in order to drive the motor more efficiently and smoothly.   2-7-4. Characteristics of sine wave control in case of brushless DC motor   Although ordinary three-phase induction motor requires energy to excite the magnetic field of rotor, brushless DC motor   doesn't need it. So, higher efficiency and torque are provided.   ● This control provides the most efficient waveform corresponding to the rotation times of compressor motor.   The rotation can be set to higher compared to the conventional motor drive system. So, the time in which air conditioner   can be operated with energy saved is longer than conventional models. This can save annual electric consumption.   ● ● Compared to square wave control, the torque pulsation is reduced at rotation so that the motor operates more quietly.   Since response and efficiency of motor are enhanced in sine wave control, finer adjustment can be provided.   ● ● DC Motor   Permanent magnet is embedded   Necessary   AC Motor   Excited by magnetic field of stator   Unnecessary   Rotor   Rotor Position Signal   In brushless DC motor, permanent magnet is embedded in the rotor. Therefore, it doesn't require energy to excite the rotor   like AC motor does. However, it's necessary to control the frequency of three-phase AC current supplied to the stator accord-   ing to the polar direction of magnet embedded in the rotor so as to drive the motor efficiently. Controlling 3 phase AC current   frequency also means controlling the timing to switch the polarity of stator. Therefore, the polar direction of rotor needs to be   detected.   2-7-5. Control Method of Rotation Times   Sine wave control makes the current transformers conduct real time detection of the value of the current running into the mo-   tor, locates the rotor position from the detected value, and decides if voltage should be impressed and if frequency should be   changed.   Compared to the conventional control and rotor position detection method, sine wave control can provide finer adjustment of the   voltage of supplied power. The value of the current running into the motor is determined by each motor characteristic.   16   2-8. OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT   1. Outline   The operational frequency is as following:   First, the target operational frequency is set based on the difference between the room temperature and the set tem-   perature.   Second, the target operational frequency is regulated by discharge temperature protection, high pressure protection,   electric current protection and overload protection and also by the maximum/minimum frequency.   2. Maximum/minimum frequency in each operation mode.   Unit: Hz   COOL   HEAT (MUZ)   DRY   Applied model   Minimum Maximum Minimum Maximum Minimum Maximum   frequency frequency frequency frequency frequency frequency   MUZ-A09   MUZ-A12   32   32   70   73   32   32   76   71   32   32   57   57   MUZ-A15   MUY-A15   MUZ-A17   MUY-A17   MUZ-A24   MUY-A24   10   10   15   82   87   15   15   15   93   93   10   10   15   68   68   110   108   102   MUZ-FD09   MUZ-FD12   MUZ-D30   MUY-D36   MUZ-D36   MUY-D36   10   10   20   20   20   20   52   62   84   79   91   92   10   10   20   — 20   — 100   100   87   10   10   20   20   20   20   41   41   83   79   83   79   — 94   — The operation frequency in COOL mode is restricted by the upper limit frequency after 1 hour or 0.5 ~ 1 hour as   shown below for dew prevention.   It is rated frequency or less.   Maximum   frequency   Upper limit   1 hour   frequency   or   Rated frequency or less   Time   0.5~1 hour   17   2-9. EXPANSION VALVE CONTROL (LEV CONTROL)   (1) Outline of LEV control   The LEV basic control is comprised of setting LEV opening degree to the standard opening °F set for each operational   frequency of the compressor. However, when any change in indoor/outdoor temperatures or other factors cause air con-   ditioning load fluctuation, the LEV control also works to correct LEV opening degree based on discharge temperature   (Shell temperature) of the compressor, developing the unit’s performance.   Minimum   : 33 pulse (MUZ-A09/12/15/17 MUY-A15/17)   59 pulse (MUZ-A24 MUY-A24)   54 pulse (MUZ-FD)   Control range   58 pulse (MUZ-D MUY-D)   : 500 pulse   Maximum   Open : 40 pulse/second   Close : 90 pulse/second.   Actuating speed   Opening degree adjustment   LEV opening degree is always adjusted in opening direction.   (When reducing the opening degree, LEV is once over-closed,   and then adjusted to the proper degree by opening.   Unit OFF   LEV remains at maximum opening degree (reaches maximum   opening degree approximate in 15 minutes after compressor   stops)   Remote controller ON   LEV is positioned. (first full-closed at zero pulse and then posi-   tioned.)   COOL · DRY MODE   During 1 to 5 minutes after compressor starts   LEV is fixed to standard opening degree according to opera-   tional frequency of compressor.   HEAT MODE   During 1 to 15 minutes after compressor starts   More than 5 (COOL, DRY), 15 (HEAT (MUZ)) minutes LEV opening degree is corrected to get target discharge tem-   have passed since compressor start-up   perature of compressor.   (For lower discharge temperature than target temperature,   LEV is corrected in closing direction.)   (For higher discharge temperature than target temperature,   LEV is corrected in opening direction.)   It may take more than 30 minutes to reach target tempera-   ture, depending on operating conditions.   Thermostat OFF   Thermostat ON   LEV is adjusted to exclusive opening degree for thermostat   OFF.   LEV is controlled in the same way as that after the compres-   sor has started up.   Defrosting in HEAT mode   LEV is adjusted to open 500 pulse.   18   (2) Time chart   Air conditioner OFF   (thermostat off)   Air conditioner ON   Positioning   Opening degree is   corrected according   to discharge   Standard   opening   degree   Commanded   to open   temperature.   about 5 minutes <COOL, DRY>   about 15 minutes <HEAT>   Time   ON   OFF Time   (3) Control data   06   05   F E D 04   03   02   01   C B A(target discharge temperature)   (Hz)   30   50   70   90   110   130   Operational frequency of the compressor   (a) Reference value of target discharge temperature   (COOL / HEAT (MUZ) F)   Applied model   A B C D E F COOL   HEAT   COOL   HEAT   COOL   HEAT   COOL   HEAT   COOL   HEAT   122   113   129   120   140   140   120   109   126   131   127   126   136   136   140   145   131   124   135   140   140   138   147   151   140   149   142   138   149   149   151   154   158   165   145   153   153   156   167   154   158   169   158   180   147   158   162   167   183   162   158   169   158   185   153   158   169   176   187   167   MUZ-A09/12   MUZ-A15/17   MUY-A15/17   MUZ-A24   MUY-A24   MUZ-FD   MUZ-D   MUY-D   In COOL operation, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super   heat) at the heat exchanger, and when temperature difference have developed, the indoor coil thermistors adjust   LEV opening degree to get approximate 10 degrees lower temperature than the target temperature in the table   above, thus diminishing super heat.   19   (b) Reference value of LEV standard opening degree (pulse)   Applied model   A B C D E F COOL   HEAT   COOL   HEAT   COOL   HEAT   COOL   HEAT   COOL   HEAT   130   100   290   130   150   130   180   130   150   100   190   130   300   150   166   150   240   180   170   120   240   170   350   220   186   170   300   240   210   140   260   210   350   250   206   196   320   270   250   190   260   230   370   280   230   210   320   300   280   240   260   230   370   300   260   226   320   300   300   280   MUZ-A09/12   MUZ-A15/17   MUY-A15/17   MUZ-A24   MUY-A24   MUZ-FD   MUZ-D   MUY-D   20   3 MXZ MICROPROCESSOR CONTROL   MXZ-A•NA   3-1. INVERTER SYSTEM CONTROL   3-1-1. Inverter main power supply circuit   CURRENT   TRANSFORMER   REACTOR   U U V P N NOISE   FILTER   CIRCUIT   RESISTOR   RELAY   + POWER   SUPPLY   SMOOTHING   CAPACITOR   MS   3~   PFC   V W W IPM   COMPRESSOR   Function of main parts   NAME   FUNCTION   INTELLIGENT POWER MODULE (IPM)   SMOOTHING CAPACITOR   It supplies three-phase AC power to compressor.   It stabilizes the DC voltage and supplies it to IPM.   It measures the current of the compressor motor.   CURRENT TRANSFORMER   It measures the current of the main power supply circuit.   REACTOR   It rectifies AC, controls its voltage and improves the power factor of power   supply.   POWER FACTOR CORRECTION MODULE (PFC)   RESISTOR   RELAY   It restricts rush current with the resistance.   It short-circuits the resistance which restricts rush current during the compres-   sor operates.   3-1-2. Outline of main power supply circuit   1. At the start of operation   Main power supply circuit is formed when RELAY is turned ON at COMPRESSOR startup.   To prevent rush current from running into the circuit when power supply is turned ON, RESISTOR are placed in sub circuit.   2. At normal operation   When AC runs into noise filter P.C. board, its external noise is eliminated in NOISE FILTER CIRCUIT.   After noise being eliminated from AC, it is rectified to DC by REACTOR and PFC. If the operating frequency becomes 25   Hz or more, DC voltage rises to 370 V.   DC voltage, to which has AC been rectified by process , is stabilized by SMOOTHING CAPACITOR and supplied to IPM.   The DC (Bus voltage), which has been stabilized in process , is converted to three-phase AC by IPM and supplied to   COMPRESSOR.   CURRENT TRANSFORMER, which is placed in the power supply circuit to COMPRESSOR, are used to measure the val-   ue of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls impressed   voltage and frequency with those information.   21   3. Power factor improvement   Booster coil reactor and PFC rectify AC to DC and control its voltage.   In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. PFC and reactor stabi-   lize the voltage of DC supplied to inverter circuit and make its waveform smooth.   4. Power transistor module   IPM consists of the following components.   · Power Transistors (x6) : Converts DC waveform to three-phase AC waveform and outputs it.   · Drive Circuit   : Drives transistors.   · Protection circuit   : Protects transistors from over current.   Since the above components are all integrated in IPM, IPM has a merit that can get the control circuit simplified and miniatur-   ized.   5. Elimination of electrical noise   NOISE FILTER CIRCUIT, which is formed by *CMC COILS and capacitors placed on the noise filter P.C. board, eliminates   electrical noise of AC power that is supplied to main power supply circuit. In short, common mode noise is absorbed in this   circuit.   Moreover, normal mode noise is absorbed in another NOISE FILTER CIRCUIT which is formed by *NMC COILS and capaci-   tors.   Both NOISE FILTER CIRCUIT exists for preventing the electrical noise generated in the inverter circuit from leaking out.   *CMC COILS; Common mode choke coils   *NMC COILS; Normal mode choke coils   3-1-3. Sine wave control   In these air conditioners, compressor equips brushless DC motor which doesn't have Hall element.   In short, the motor is sensorless. However, it's necessary to locate the polar direction of rotor in order to drive brushless DC mo-   tor efficiently. The general detection method of the polar direction for such a DC motor is to locate it from the voltage induced by   unenergized stator.   Therefore, it is necessary to have a certain period of time in which the stator is being unenergized for the rotor position detection   when the voltage of supplied power is impressed.   So the motor has been driven by square wave control (the conventional motor drive system) which energizes the motor only   when the range of electrical angle is within 120° because it is forced to be unenergized within 30° at start & end of one heap in   one waveform cycle (180°) when the voltage is impressed.   However, torque pulsation occurs at rotation in this method when the current-carrying phases are switched over to other phases   in sequence. Therefore, sine wave control system is adopted for these air conditioners because it can make the phase-to-phase   current waveform smoother (sine wave) in order to drive the motor more efficiently and smoothly.   3-1-4. Characteristics of sine wave control in case of brushless DC motor   Although ordinary three-phase induction motor requires energy to excite the magnetic field of rotor, brushless DC motor   doesn't need it. So, higher efficiency and torque are provided.   ● This control provides the most efficient waveform corresponding to the rotation times of compressor motor.   The rotation can be set to higher compared to the conventional motor drive system. So, the time in which air conditioner can   be operated with energy saved is longer than conventional models. This can save annual electric consumption.   ● ● Compared to square wave control, the torque pulsation is reduced at rotation so that the motor operates more quietly.   Since response and efficiency are enhanced in sine wave control, finer adjustment can be provided.   ● ● DC Motor   Permanent magnet is embedded   Necessary   AC Motor   Excited by magnetic field of stator   Unnecessary   Rotor   Rotor Position Signal   In brushless DC motor, permanent magnet is embedded in the rotor. Therefore, it doesn't require energy to excite the rotor   like AC motor does. However, it's necessary to control the frequency of three-phase AC current supplied to the stator accord-   ing to the polar direction of magnet embedded in the rotor so as to drive the motor efficiently. Controlling 3 phase AC current   frequency also means controlling the timing to switch the polarity of stator. Therefore, the polar direction of rotor needs to be   detected.   3-1-5. Control Method of Rotation Times   Sine wave control makes the current transformers conduct real time detection of the value of the current running into the mo-   tor, locates the rotor position from the detected value and decides if voltage should be impressed and if frequency should be   changed.   Compared to the conventional control and rotor position detection method, sine wave control can provide finer adjustment of the   voltage of supplied power. The value of the current running into the motor is determined by each motor characteristic.   22   3-2. EXPANSION VALVE CONTROL (LEV CONTROL)   Linear expansion valve (LEV) is controlled by “Thermostat ON” commands given from each unit.   Indoor unit status   LEV opening   Stop of all indoor unit   Opening before stop → 500 pulse in 15 minutes   When outdoor unit is operating, COOL : 5 pulse (full closed)   some indoor units stop and some HEAT :(MXZ-2A / 3A30NA) : 140 pulse (slightly opened)   1 :(MXZ-3A30NA-   / 4A ) : 100 → 59 pulse   operate.   When the outdoor unit operates (When the other indoor unit operates) : 5 pulse.   When outdoor unit stops. (When the other indoor unit stops or thermo off) :   Maintain LEV opening before stop → 500 pulse in 15 minutes   Thermostat OFF in COOL or DRY   mode   • LEV opening for each indoor unit is determined by adding adjustment in accordance   with the number of operating unit and the capacity class to standard opening, based   on the operation frequency:   Ex.) Opening 130 pulse in standard opening 1 → Minimum 80 pulse, Maximum 205   pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 3 units operation)   Thermostat ON in COOL or DRY • After starting operation, adjustment in accordance with intake super heat, discharge   mode   temperature is included in standard opening. 1   NOTE: LEV opening in each frequency at DRY operation and COOL operation is the   same. However, velocity and compressor operation frequency controls are differ-   ent. See 3-3. OPERATIONAL FREQUENCY RANGE   (As far as the indoor unit velocity control goes, refer to DRY operation in MICRO-   PROCESSOR CONTROL in indoor unit.)   • When the outdoor unit operates. (When the other indoor unit operates) : 140 pulse.   Thermostat OFF in HEAT mode • When the outdoor unit stops. (When the other indoor unit stops or thermo off) : Main-   tain LEV opening before stop → 500 pulse in 15 minutes. “   • LEV opening for each indoor unit is determined by adding adjustment in accordance   with the number of operating unit and the capacity class to standard opening, based   on the operation frequency:   Ex.) Opening 120 pulse in standard opening 1 → Minimum 70 pulse, Maximum 165   pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 3 units operation)   • After starting operation, opening becomes the one that adjustment in accordance with   discharge temperature was added to basic opening. 1 “   Thermostat ON in HEAT mode   1 LEV opening when the outdoor unit is operating: Upper limit 500 pulse, Lower limit 53pulse (MXZ-2A / 3A30NA), 59 pulse   1 (MXZ-3A30NA-   / 4A).   23   MXZ-2A20NA/3A30NA   The table below shows the role of Exclusive LEV and Receiver LEV in each operation mode.   Discharge   Capacity Distribution Temperature   Protection   Evaporation   Temperature   Protection   Circulation Amount   Control   High Pressure   Protection   Exclusive LEV   Receiver LEV   Exclusive LEV   Receiver LEV   ○ × × ○ ○ × ○ × ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ — — COOL   HEAT   Outdoor   heat   Indoor heat Exclusive   exchanger LEV   exchanger   Receiver   Receiver   LEV   (MXZ-3A30NA)   In COOL mode, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the   heat exchanger, and when temperature difference have developed, the indoor coil thermistors adjust LEV opening to dimin-   ish the super heat. This action is called Evaporation Temperature Protection.   The opening pulse of the Receiver LEV is fixed to the standard No.3 in cooling operation, and so is that of each Exclusive   LEV in heating operation.   However the opening pulse will be changed to the standard No.4 or No.5 when the discharge temperature protection or high-   pressure protection is working.   In addition to that, it will also be changed to standard No.2 or No.1 when the opening pulse of the each Exclusive LEV   becomes 100 pulse or less in cooling operation or so does that of Receiver LEV in heating operation.   <MXZ-2A20NA>   Number of   operating   indoor units   LEV opening (pulse)   COOL   HEAT   Standard No.   1 unit   200   300   400   450   500   2 units   1 unit   120   140   160   220   280   2 units   120   140   160   220   1 2 3 4 5 150   320   360   410   500   280   <MXZ-3A30NA>   Number of   operating   indoor units   LEV opening (pulse)   COOL   HEAT   1 unit   2 units   250   320   360   410   3 units   1 unit   2 units   250   300   380   400   3 units   Standard No.   1 2 3 4 5 150   250   350   400   450   250   320   370   420   470   250   300   450   460   470   250   300   380   390   440   460   450   24   Determination of LEV standard opening in each indoor unit   • The standard opening is on the straight line, which connects an each standard point in the section where divided into   seven according to the operation frequency of compressor as shown in the figure below.   (LEV opening is controlled in proportion to the operation frequency.)   NOTE: Opening is adjusted at the standard opening according to the indoor unit conditions.   However, inclination of standard opening in each point of opening does not change with the original curve.   • Add opening provided in Difference in capacity in the table below to the standard opening from 1 to 8, when capacity   of the indoor unit is excluding code 1.   • Add opening provided in Difference in operation number in the table below to determined LEV opening for each   indoor unit, when 2 or 3 indoor units are operated at the same time.   NOTE: Even when the adjusted standard opening exceeds the driving range from 59 to 500 pulse, actual driving out-   put opening is in a range from 59 to 500 pulse.   4Hz   10   09   08   07   06   05   04   03   02   01   23 38 54 69 84 100 115 131 146 MXZ-2A   14 23 32 41 50 59 68 77 86 MXZ-3A/4A   Compressor operating frequency (Hz)   MXZ-2A20NA   Standard opening (pulse)   LEV Opening (code)   COOL   1 2 3 4 5 6 7 8 9 10   120 130 136 146 156 160 170 180 190 200   100 110 120 130 146 160 170 180 190 200   HEAT   Difference in capacity   Difference in operation number   Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above   2 -20   0 COOL   HEAT   3 3 6 6 9 9 12   52   15   55   25   65   35   75   MXZ-3A30NA   Standard opening (pulse)   LEV Opening (code)   COOL   1 2 3 4 5 6 7 8 9 10   126 130 134 138 140 142 182 228 296 310   140 146 150 170 180 200 224 244 272 280   HEAT   Difference in capacity   Difference in operation number   Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above   2 -20   0 3 -30   0 COOL   HEAT   3 3 6 6 9 9 12   52   15   55   25   65   35   75   25   1 MXZ-2A20NA-   Exclusive LEV   Standard opening (pulse)   LEV Opening (code)   COOL   1 2 3 4 5 6 7 8 9 10   120 130 136 146 156 160 170 180 190 200   248 248 258 266 274 280 286 292 300 306   HEAT   Difference in capacity   Difference in operation number   Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above   2 COOL   HEAT   3 3 6 6 9 9 12   52   15   55   25   65   35   75   -20   30   Receiver LEV   Standard opening (pulse)   LEV Opening (code)   COOL   1 2 3 4 5 6 7 8 9 10   140 150 160 170 180 190 200 200 200 200   80 84 90 110 120 130 140 150 160 170   HEAT   Difference in operation number   Operation number   2 COOL   HEAT   -20   30   1 MXZ-3A30NA-   MXZ-4A36NA   Exclusive LEV   Standard opening (pulse)   LEV Opening (code)   COOL   1 2 3 4 5 6 7 8 9 10   126 130 134 138 150 160 170 180 190 200   248 248 258 266 274 280 286 292 300 306   HEAT   Difference in capacity   Difference in operation number   Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above   2 -20   -4   3 -30   -8   4(MXZ-4A)   -30   -12   COOL   HEAT   3 3 6 6 9 9 12   52   15   55   25   65   35   75   Receiver LEV   Standard opening (pulse)   LEV Opening (code)   COOL   1 2 3 4 5 6 7 8 9 10   270 280 290 300 310 320 330 340 350 360   140 152 160 170 180 200 224 244 274 280   HEAT   Difference in operation number   Operation number   2 28   -45   3 56   -60   4(MXZ-4A)   84   COOL   HEAT   -60   Capacity code   Indoor unit   4 7 9 10 12   09 12 15 17 24   26   <Correction>   COOL   DRY   HEAT   Discharge temperature   2 2 ● ● ● Each correction   • (Each gas pipe temperature thermistor - Minimum gas pipe temperature thermistor)   1 — ● ● • (Main indoor coil thermistor - Sub indoor coil thermistor)   1 Perform this, when number of operation units is 2 units or more.   1 1 MXZ-2A20NA-   MXZ-3A30NA-   and MXZ-4A36NA are excluded.   , 2 Correct the LEV opening by discharge temperature.   (1) LEV opening correction by discharge temperature   The target discharge temperature is determined according to frequency zone and number of operation unit of the com-   pressor.   MXZ-2A20NA   Target discharge temperature (°F)   Number of operating unit   Operation frequency   of compressor (Hz)   COOL   COOL   COOL   HEAT   HEAT   HEAT   1 unit   95   104   120.2   136.4   149   2 units   136.4   140   1 unit   122   132.8   140   2 units   122   122   132.8   140   140   Minimum ~ 23   24 ~ 38   39 ~ 54   55 ~ 69   70 ~ 85   149   154.4   158   140   140   86 ~ Maximum   158   158   140   140   MXZ-2A20NA-   1 Target discharge temperature (°F)   Number of operating unit   Operation frequency   of compressor (Hz)   1 unit   95   104   120.2   136.4   149   2 units   136.4   140   1 unit   122   132.8   140   2 units   122   122   132.8   140   140   Minimum ~ 23   24 ~ 38   39 ~ 54   55 ~ 69   70 ~ 85   149   154.4   158   158   145.4   150.8   152.6   86 ~ Maximum   158   140   MXZ-3A30NA   Target discharge temperature (°F)   Number of operating unit   Operation frequency   of compressor (Hz)   1 unit   95   104   120.2   136.4   149   154.4   158   2 units   131   131   136.4   140   149   154.4   158   163.4   167   3 units   134.6   134.6   145.4   149   158   163.4   167   1 unit   125.6   136.4   149   154.4   154.4   154.4   154.4   154.4   154.4   172.4   2 unit   143.6   150.8   165.2   172.4   172.4   172.4   172.4   172.4   172.4   172.4   3 units   122   131   Minimum ~ 14   15 ~ 23   24 ~ 32   33 ~ 41   42 ~ 50   51 ~ 59   60 ~ 68   69 ~ 77   78 ~ 86   140   152.6   161.6   168.8   168.8   168.8   168.8   168.8   167   167   167   176   179.6   179.6   87 ~ Maximum   176   27   MXZ-3A30NA-   MXZ-4A36NA   1 Target discharge temperature (°F)   COOL   HEAT   Operation frequency   of compressor (Hz)   Number of operating unit   4 units   4 units   (MXZ-4A36)   1 unit   2 units   3 units   1 unit   2 unit   3 units   (MXZ-4A36)   140   Minimum ~ 14   15 ~ 23   95   131   131   136.4   140   149   154.4   158   163.4   167   176   134.6   134.6   145.4   149   158   163.4   167   176   179.6   179.6   125.6   136.4   149   143.6   150.8   165.2   172.4   172.4   172.4   172.4   172.4   172.4   172.4   122   131   140   152.6   161.6   168.8   168.8   168.8   168.8   168.8   122   122   122   122   131   140   140   140   140   140   107.6   120.2   136.4   149   154.4   158   167   167   167   140   140   24 ~ 32   33 ~ 41   42 ~ 50   51 ~ 59   60 ~ 68   69 ~ 77   78 ~ 86   143.6   149   158   154.4   154.4   154.4   154.4   154.4   154.4   172.4   158   161.6   161.6   161.6   87 ~ Maximum   Correct the LEV opening according to the difference between target discharge temperature and discharge temperature.   MXZ-2A   LEV opening correction (pulse)   Discharge temperature (°F)   More than Target discharge temperature+18   Target discharge temperature + 18 to Target discharge temperature + 9   Target discharge temperature + 9 to Target discharge temperature + 3.6   Target discharge temperature + 3.6 to Target discharge temperature - 3.6   Target discharge temperature - 3.6 to Target discharge temperature - 9   Target discharge temperature - 9 to Target discharge temperature - 18   Target discharge temperature - 18 or less   COOL   HEAT   5 4 8 3 2 1 0 0 -1   -3   -4   -1   -2   -3   MXZ-3A MXZ-4A   LEV opening correction (pulse)   Discharge temperature (°F)   COOL   HEAT   More than Target discharge temperature + 21.6   4 2 1 6 2 1 Target discharge temperature + 21.6 to Target discharge temperature + 9   Target discharge temperature + 9 to Target discharge temperature + 5.4   Target discharge temperature + 5.4 to Target discharge temperature - 5.4   Target discharge temperature - 5.4 to Target discharge temperature - 9   Target discharge temperature - 9 to Target discharge temperature - 21.6   Target discharge temperature - 21.6 or less   0 0 -1   -3   -8   -1   -2   -8   (2) Separate correction (COOL,DRY)   (Correction by the separate super heat)   a) Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe   temperature of all.   Calculate each super heat of the unit from the expression below;   (Super heat) = (Each gas pipe temperature) - (Minimum gas pipe temperature)   Separate correction is performed according to each super heat in the table below.   MXZ-2A20NA   MXZ-3A30NA   LEV opening   correction (pulse)   LEV opening   correction (pulse)   Superheat   Superheat   more than 16.2   10.8 to 16.2   5.4 to 10.8   3 2 1 0 more than 16.2   10.8 to 16.2   5.4 to 10.8   12   8 4 5.4 or less   5.4 or less   0 28   b) Correct the LEV separately by temperature difference “ ∆RT” between main/sub indoor coil thermistor.   LEV opening   ∆RT   correction (pulse)   10.8 ∆RT   7.2 ∆RT < 10.8   ∆RT < 7.2   2 1 1 In addition, decrease the target discharge temperature corresponding ∆RT.   Temperature to be   decreased (°F)   ∆ RT   10.8 ∆RT   7.2 ∆RT< 10.8   ∆RT < 7.2   18   9 9 3-3. OPERATIONAL FREQUENCY RANGE   MXZ-2A20NA   COOL (Hz)   HEAT (Hz)   Max.   92   Number of operating   unit   Capacity code   DRY (Hz)   Min.   20   20   20   20   30   30   30   20   Max.   65   85   100   100   105   105   105   105   Min.   48   48   48   48   58   58   58   58   Defrost   92   92   100   100   100   100   100   100   4 7 9,10   12   8 ~ 10   11 ~ 13   14 ~ 16   17 ~   25   30   75   75   52   52   52   100   92   100   100   112   112   112   112   1 2 1 MXZ-2A20NA-   COOL (Hz)   HEAT (Hz)   Max.   92   Number of operating   unit   Capacity code   DRY (Hz)   Min.   20   20   20   20   30   30   30   30   Max.   65   85   93   93   93   93   93   93   Min.   48   48   48   48   58   58   58   58   Defrost   92   92   92   92   101   101   101   101   4 7 9,10   12   8 ~ 10   11 ~ 13   14 ~ 16   17 ~   35   34   75   75   52   52   52   93   92   92   92   110   110   110   110   1 2 MXZ-3A30NA   COOL (Hz)   HEAT (Hz)   Number of operating   unit   Capacity code   DRY (Hz)   Min.   15   15   15   15   24   24   24   24   52   Max.   58   58   62   68   80   80   80   80   90   Min.   22   22   22   22   35   35   35   35   39   Max.   48   48   62   90   70   90   94   94   94   Defrost   48   48   58   58   58   58   58   58   4 7 9,10   12   8 ~ 10   11 ~ 13   14 ~ 16   17 ~   12 ~   20   25   44   44   31   31   31   59   65   1 2 3 58   29   1 MXZ-3A30NA-   MXZ-4A   COOL (Hz)   Min.   HEAT (Hz)   Max.   70   Number of operating   unit   Capacity code   DRY (Hz)   Max.   58   58   71   80   80   80   80   80   80   90   90   Min.   20   20   20   20   20   20   20   20   20   20   20   Defrost   58   58   58   58   58   58   58   58   4 7 9,10   12   8 ~ 10   11 ~ 13   14 ~ 16   17 ~   12 ~   12 ~   16 ~   25   25   25   25   25   25   25   25   25   25   25   25   25   25   35   31   31   42   42   52   52   52   70   80   80   80   80   80   80   80   1 2 3 (MXZ-3A)   3 (MXZ-4A)   4 (MXZ-4A)   58   58   58   103   113   3-4. HEAT DEFROSTING CONTROL   (1) Starting conditions of defrosting   When the following conditions a) ~ c) are satisfied, the defrosting starts.   a) The defrost thermistor reads 26.6 °F or less.   b) The cumulative operation time of the compressor has reached any of the set values (31, 35, 45, 55, 65, 75, 85, 95,   105, 115, 150 minutes).   c) More than 5 minutes have passed since the start-up of the compressor.   Set value of compressor operation time (hereinafter referred to as defrost interval)   This is decided by the temperature of defrost thermistor and ambient temperature thermistor, the previous defrosting   time. For example, the first defrost interval is 40 minutes long, and the second is 45 minutes long. The third and sub-   sequent intervals are set to be longer, and less frequent, depending on defrosting time.   … The third and subsequent defrost intervals follow any of the three patterns 5 or 10 to 20 minutes longer, the same,   … or 5 or 10 to 20 minutes shorter compared with the previous defrost interval   shortest 40 minutes.   with the longest 125 minutes and the   (2) Releasing conditions of defrosting   Defrosting is released when any of the following conditions is satisfied:   a) The defrost thermistor continues to read 50.7 °F.   b) Defrosting time exceeds 10 minutes.   c) Any other mode than HEAT mode is set during defrosting.   3-5. DISCHARGE TEMPERATURE PROTECTION CONTROL   This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge tempera-   ture thermistor.   (1) Compressor ON/OFF   When temperature of the discharge temperature thermistor exceeds 240.8 °F, the control stops the compressor.   When temperature of the discharge temperature thermistor is 176 °F (2A/3A30NA)/ 212 °F (3A30NA- 1 /4A) or less, the   controls starts the compressor.   (2) Compressor operation frequency   When temperature of the discharge temperature thermistor is expected to be higher than 240.8 °F, the control decreases   12 Hz from the current frequency.   When temperature of the discharge temperature thermistor is expected to be higher than 231.8 °F and less than 240.8 °F,   the control decreases 6 Hz from the current frequency.   When temperature of the discharge temperature thermistor is expected to be higher than 219.2 °F and less than 231.8 °F,   the control is set at the current frequency.   3-6. OUTDOOR FAN CONTROL   Fan speed is switched according to the number of operating indoor unit and the compressor frequency.   <Relation between compressor frequency and fan speed>   Fan speed   Compressor frequency (Hz)   Down   Up   High   Down   Up   MXZ-2A   MXZ-3A30NA   30   40   Low   1 MXZ-3A30NA-   MXZ-4A   Min. Compressor frequency Max.   40   50   NOTE : When the indoor coil thermistor is 134.6 ˚F or more on HEAT operation, fan speed is fixed to Low speed.   Or, the indoor coil thermistor is 113 ˚F or less on HEAT operation, fan speed is back to normal.   30   3-7. PRE-HEAT CONTROL   MXZ-2A20NA- MXZ-3A30NA-   1 1 MXZ-4A36NA   The compressor is energized even while it is not operating.   This is to generate heat at the winding to improve the compressor's start-up condition.   Power   ON   OFF   Compressor ON   OFF   Outside temperature   68 °F   30min.   30 min.   30 min.   30 min.   30 min.   30 min. 15 min. 30 min.15 min. 30 min.   Pre-heat   ON   OFF   Start   Stop   When outside   temperature is   above 68 °F   Breaker ON   operation operation   1. Pre-heat control is turned ON for 15 or 30 min, after the breaker is turned ON.   2. 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 min. and turned OFF for 30 min."   This is repeated as shown in the graph until the breaker is turned OFF.   When outside temperature is 68 °F or below, pre-heat control is ON for 30 min."   When outside temperature is 69.8 °F or above, pre-heat control is ON for 15 min."   NOTE: When the unit is started with the remote controller, pre-heat control is turned OFF."   Compressor uses 50 W when pre-heat control is turned ON.   3-8. COOL OPERATION   1. Thermostat control   Thermostat is ON or OFF by difference between room temperature and set temperature.   Room temperature minus   set temperature (Initial)   Room temperature minus   set temperature (During operation)   Thermostat   ON   OFF   -1.8 °F or more   less than-1.8 °F   -1.8 °F   -1.3 °F   2. Coil frost prevention   The compressor operational frequency is controlled to prevent the indoor heat exchanger temperature from falling exces-   sively.   Compressor is turned OFF for 5 minutes when temperature of indoor coil thermistor continues 37.4 °F or less for 5 min-   utes or more.   31   3-9. DRY OPERATION   1. Thermostat control   Thermostat is ON or OFF by difference between room temperature and set temperature.   Room temperature minus   set temperature (Initial)   Room temperature minus   set temperature (During operation)   Thermostat   ON   OFF   -1.8 °F or more   less than-1.8 °F   -1.8 °F   -1.3 °F   2. Coil frost prevention   Coil frost prevention is as same as COOL mode. (3-8.2.)   3-10. HEAT OPERATION   1. Thermostat control   Thermostat is ON or OFF by difference between room temperature and set temperature.   Room temperature minus   set temperature (Initial)   Room temperature minus   set temperature (During operation)   Thermostat   ON   OFF   less than 3.6 °F   3.6 °F or more   3.6 °F   3 °F   2. High pressure protection   In HEAT operation the indoor coil thermistor detects the temperature of the indoor heat exchanger. The compressor opera-   tional frequency is controlled to prevent the condensing pressure from increasing excessively.   HEAD OFFICE: TOKYO BLDG.,2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN   Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD   Distributed in Feb. 2008. No. OBT16 REVISED EDITION-B 6   Distributed in May 2007. No. OBT16 REVISED EDITION-A 7   Distributed in Apr. 2006. No. OBT16 7   Made in Japan   New publication, effective Feb. 2008   Specifications subject to change without notice.   |