White Rodgers Furnace G1N 4R9 User Manual

Stove Builder International Inc.  
1700, Léon-Harmel  
Québec(Québec)  
G1N 4R9  
Installation and Operating  
Instructions for Wood and  
Combined Wood-electric Furnaces  
THIS MANUAL CONCERNS THE FOLLOWING FURNACES  
WOOD  
COMBINED ELECTRIC  
PSG-2000  
PSG-3000  
PSG-4000  
PSG-4500  
PSG-5000  
15 KW, 18 KW, 20 KW  
15 KW, 18 KW, 20 KW, 25 KW  
18 KW, 20 KW, 25 KW, 30 KW  
18 KW, 20 KW, 25 KW, 30 KW  
40 KW, 50 KW, 60 KW  
All the instructions must be read carefully  
before installing and operating furnace.  
CONGRATULATIONS!  
You have just purchased one of the best wood or combined  
wood-electric furnace on the market.  
We are convinced that your furnace will provide you  
with many years of comfort, safely.  
Keep these instructions!  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10. SELECTION CRITERIA (COMBINED WOOD/ELECTRIC FURNACE).......................... 28  
11. TROUBLESHOOTING..................................................................................................... 29  
12. DUCTS AND REGISTER MEASUREMENTS ................................................................. 30  
LIMITED LIFETIME WARRANTY................................................................................. 31  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
To get maximum performance from your PSG furnace, keep in mind the following:  
Comply with local codes (if in doubt, contact your local heating specialist).  
Refer to the furnace’s certification label and your instruction manual for minimum installation clearances.  
Make sure that your furnace has been installed in accordance with the required standards specified on the  
furnace’s identification label.  
1. CHIMNEY AND DRAFT  
This furnace must be connected to a chimney approved for wood-burning appliances; the chimney connector for a  
PSG 2000 must have 6" diameter; 7” for PSG3000 and PSG4000, for all other models, use an 8" diameter chimney  
connector.  
Use the supplied barometric draft control. Never use a manual chimney damper.  
The barometric control must be adjusted so that the maximum draft measured at the furnace outlet does not exceed  
-0.06 in. w.c. Please note that a draft exceeding -0.06 in. w.c. could produce an uncontrollable fire. On the other  
hand, the minimum draft required is -0.04 in. w.c. in the evacuation pipe on the wood side, no matter what type of  
furnace (PSG Wood, PSG Wood/Electric and PSG Wood/Oil).  
Never light your furnace using chemicals or other liquid fuels. Never installed automatic feeder on that unit.  
Never store wood near the furnace. Respect the required minimum clearances between combustibles and  
your furnace.  
Keep your furnace, chimney and smoke pipe connector clean and in good working order at all times. We  
recommend that you establish clear procedures for wood storage, system maintenance and operation of  
your furnace. Check creosote accumulation daily until you can determine by experience how often to clean.  
Weekly cleanings may be necessary in mild weather, while a monthly cleaning may be all that is required  
during the colder months of the year.  
Keep loading and ash drawer doors shut during operation and make sure their gaskets are in good  
condition. To replace defective gaskets, see your dealer.  
A plentiful supply of air and a vigorous fire will reduce creosote accumulation.  
All controls adjustments must be performed by a qualified technician. The controls settings and the blower speed must  
conform to the recommendations of the National Warm Air Heating and Air Conditioning Association and respect the  
recommended static pressure ranges in the warm air bonnet of the furnace (see General Technical data static  
pressure).  
2. SAFETY RULES  
GENERAL REQUIREMENTS  
Make sure the chimney outlet and the pipes are clean and in good condition.  
Do not use chemical products or liquids to light the fire.  
Do not burn wood coated with paint, glue or chemical products.  
Do not burn wastes or flammable liquids such as gasoline, naphtha or motor oil.  
Do not install an automatic feeder on this furnace.  
Do not store wood in the vicinity of the furnace. Respect the required clearances between combustible materials  
and the source of heat.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
W A R N I N G  
-THE ASH DRAWER GET VERY HOT.  
-DO NOT MANIPULATE WITH BARE HANDS.  
ODOUR FROM THE PAINT  
It is normal that a smoke odor emanate from the unit when you first light it. It is recommended to burn it at high rate  
and ventilate the building until the odour resorbs.  
ASH DISPOSAL  
Ashes must be placed in a metal container with a tight fitting lid. The container should be placed outside, well away  
from combustible materials. If the ashes are meant to be buried in soil, you should wait until all cinders have  
thoroughly cooled.  
CREOSOTE BUILD-UP AND REMOVAL  
When wood is burned slowly, it produces tar and other organic vapours which, when combined with moisture, form  
creosote. The creosote vapours condensate in a relatively cool chimney flue. As a result, creosote residue  
accumulates in the flue lining.  
N.B.: To minimize the frequency of the chimney cleaning, buy your firewood at least one year before using it. Store it  
in a dry place in order to obtain the minimum moisture rate and optimize the efficiency. Do not store wood or  
combustible materials within the installation minimum clearances or the space required to reload the appliance and  
remove the ashes.  
When ignited, creosote produces an extremely hot fire inside the chimney.  
To avoid this situation, it is important to do the turnover of wood. Inspect the chimney system at regular intervals to  
determine a cleaning cycle. A weekly cleaning might be required during mild temperature periods but a monthly  
cleaning should be sufficient during cold periods. If a significant layer of creosote has accumulated, it should be  
removed immediately to eliminate the risk of a chimney fire. Remember that a small hot fire is preferable to a  
large smouldering one to prevent creosote build-up within the system. An emergency plan is necessary in case of a  
chimney fire. It’s recommended to clean up the heat exchangers at the end of season in order to prevent corrosion  
build-up.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
SMOKE DETECTOR  
We highly recommend the use of a smoke detector. It must be installed at least 15 feet (4,57 m) from the appliance  
in order to prevent undue triggering of the detector when reloading.  
ASH DRAWER  
Your appliance is equipped with an ash drawer to collect ashes produced by the combustion of wood. This drawer  
must not be left open during combustion as this will cause over firing and serious damage to the furnace.  
The drawer must be cleaned regularly.  
It is important that the door and the ash drawer be kept closed while the appliance is in use.  
Maintain all gaskets in good condition: in case of deterioration, contact your dealer for  
replacement.  
ASH GRATE  
You must replace the ash grate if it is damaged and a replacement may be obtained from your dealer.  
3. APPLIANCE INSTALLATION  
UNIT LOCATION  
The furnace must be installed where outside air supply is sufficient for proper combustion. In airtight houses, it  
might be necessary to install an outside air inlet (see details in: «3- INSTALLATION» D- COMBUSTION AIR).  
The furnace must be positioned so that the connector is as short as possible in order to minimize the use of 90o  
elbows.  
The owner must ensure a proper installation to allow a safe operation of the appliance.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
CLEARANCES TO COMBUSTIBLE MATERIALS  
N.B. This appliance must be installed in accordance with the instructions on the unit’s certification.  
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS FOR PSG FURNACES  
2”  
24” both sides for  
PSG5000  
N.B. THE AIR RETURN CONDUITS SHOULD BE AT LEAST EQUAL TO THE COLD AIR  
PLENUM DIMENSIONS.  
PIPE CONNECTOR AND DAMPER  
Before proceeding to connection, remove all accessories such as:  
scraper, shovel and poker in the evacuation pipe of the furnace.  
A 6” diameter chimney listed for use with wood burning heating appliances is recommended for the PSG2000, 7” for  
PSG3000-4000 and 8” for the others models. Install the barometric control provided with the furnace. Never install a  
manual damper.  
OIL FLUE  
PIPE  
(OPTION)  
WOOD  
FLUE  
PIPE  
MAIN  
COLLECTOR  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For a proper installation, follow the advices below:  
1. All the joints of the evacuation pipe must be secured, using three screws.  
Make sure that each screw goes through the inner walls of both connectors (male and female). See  
pictures below showing a male-female coupling.  
PROPER INSTALLATION  
UNPROPER INSTALLATION  
CAUSE RESTRICTION  
2. A minimum rise of 1/4 inch per horizontal foot must be respected.  
DAMPER  
The barometric control must be adjusted so that the maximum draft measured at the furnace outlet is limited to -0.06  
in. w.c. Please note that a draft higher than -0.06 in. H2O could result in an uncontrollable fire. On the other hand,  
the minimum draft to be respected is -0.04 in. w.c. in the evacuation pipe on the solid fuel side, no matter what  
type of furnace.  
COMBUSTION AIR  
In the event that the furnace and the chimney are completely cold, it might be necessary before lighting, to provide  
fresh air by opening a door or a window for a few minutes.  
Take note that a house constructed or renovated in order to be airtight is liable to lack fresh air which is necessary  
for a proper combustion and a proper operation of heating units.  
In such a case, when starting up the fire, do not operate appliances which evacuate air outside the house such as:  
-
-
-
-
-
Range hood  
Air exchanger  
Cloths dryer  
Bathroom fan  
Ventilated central vacuum system  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE:  
It is recommended to install an outside air inlet of minimum 4” diameter in the room where the heating appliance is  
installed (see drawing below). To do so, it is preferable to choose a wall which is not exposed to extreme winds,  
according to the conditions surrounding your house.  
Insulated conduit full lenght  
Fresh air  
Free air  
intake  
entry  
Exterior  
wall  
N.B. The owner of the furnace is responsible for the room salubrity in case of negative pressure or temporary  
negative pressure.  
ELECTRICAL CONNECTION  
The following instructions do not supersede the local code.  
WOOD ONLY  
Installed limit control on support provided on proper location of the appliance (two holes are predrilled on the edge of  
the furnace), and connected to the electrical box along with the transformer. Install the servo-motor on the front facade  
above the door, on the right side (use pre-drilled holes). The chain that links the air inlet latch to the motor must have a  
play of 1/8 in. When there is no call for heat, the air inlet latch must be completely shut and the chain must be affixed  
to the servo-motor at “8 o’clock”. *  
The switch located on the fan limit control activates high speed operation, in either automatic or manual (continuous  
operation) modes.  
The switch located on the electric unit controls low speed operation, in either ON (continuous operation) or OFF  
modes.  
WARNING: USE FEEDING WIRES SUITABLE FOR 75OC  
WOOD/ELECTRIC  
The limit control is a manual reset thermostatic captor and is located directly inside the electric element (see  
WIRING DIAGRAMS). The electric elements must be installed as shown on the diagram. Install the combined limit  
control on the support provided, at the determined location. The connections must conform to the diagram.  
Install the servo-motor on the front façade above the door, on the right side (use pre-drilled holes). The chain that  
links the air inlet latch to the motor must have a play of 1/8 in. When there is no call for heat, the air inlet latch must be  
completely shut and the chain must be affixed to the servo-motor at “8 o’clock”. *  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
The switch located on the fan limit control activates the blower at high speed, in either automatic or manual  
(continuous operation) modes.  
The switch located on the electric unit controls low speed operation, in either ON (continuous operation) or OFF  
modes (PSG 3000 or PSG 4000 models only).  
WARNING: USE FEEDING WIRES SUITABLE FOR 75OC  
* (With all reserves on the minimum combustion air to be increased depending on the type and quality of the  
combustible).  
ELECTRIC ELEMENT  
The WOOD / ELECTRIC combined model is installed with two thermostats: one thermostat controls the electric  
heating, the other one controls the wood heating. With this system, the electric heating has priority over the wood  
heating. When the thermostat activates the electric heating, the air inlet closes down (if opened), the blower starts and  
the electric elements are successively activated per block of 5 kW. The system might be equipped with an exterior  
thermostat which will allow the last block of elements (5 kW) to start up only when the outside temperature is cold  
enough. This will reduce the power of the systems by 5 kW during mild temperature for more comfort.  
When the call for electric heating is completed, the wood system will take over if the starting point of the wood  
system is superior to the electric system.  
So, in normal bi-energy use, you must set the wood system thermostat 2o to 3o higher than the electric system  
thermostat.  
Take note that this furnace is equipped with a four speed motor. Aside from low speed, three choices are available:  
medium-low, medium-high or high.  
If the temperature of the element exceeds the limit allowed, the thermodisk will disengage the element. For  
reactivation, press the red button “manual reset” of the thermodisk L-170 and find out why the temperature limit has  
been exceeded (static pressure too high, fan breakage, dirty filter, etc.)  
INSIDE VIEW OF THE ELECTRIC ELEMENT  
Red button  
manual reset  
Thermodisk L-170  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OUTSIDE VIEW OF THE ELECTRIC ELEMENT  
THERMOSTAT  
The thermostat must be installed on an inside wall in a location where it is not likely to be affected by the draft  
coming from an air outlet. It must be installed at a minimum of 55 inches above the floor.  
N.B. The combined wood / electric model must be installed with two thermostats at same level.  
FAN CONTROL  
The fan control setting varies depending on the type of heating installation. The setting “out of service” is preset at  
110o F in factory. This setting should provide a proper operation for most installations. The temperature “in service” is  
pre-set at 150o F.  
It is preferable for a prolonged operation of the blower that the setting “out of service” be low enough. But a setting  
“out of service” too low will cause a cold air circulation. To modify the setting, turn the button at the desired position on  
the temperature scale.  
The adjustment of all controls must be performed by a qualified technician. The controls setting and the blower  
speed must conform to the recommendations of the “Warm Air Heating and Air Conditioning National Association”. To  
obtain a continuous air circulation during summer, push the manual switch of the limit control from the “automatic”  
position to the “manual or summer” position.  
The switch located below the limit control or on the electric unit, controls the low speed either at the “on” position or  
the “off” position. For a better efficiency we recommend to leave the high speed on automatic(wood side fan limit  
control).  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. OPERATING INSTRUCTIONS  
Control system  
On the wood furnaces only, the thermostat controls the air inlet damper. When the thermostat calls for heat, the  
damper opens and the fire burns up. When the furnace gets hot enough, the combined limit control activates the  
blower motor at the speed selected for wood heating.  
The chain that links the air inlet damper to the motor must have a play of 1/8 inch. When there is no call for heat,  
the air inlet damper must be completely closed and the chain must be affixed to the servo-motor at “8 o’clock”. *  
* (With all reserve on the minimum air to be increased depending on the type and quality of the combustible).  
LIGHTING:  
1. Open the door  
Note: In the case that there is a bed of coals in the bottom of the furnace, go to step b) Pre-heating.  
2. Place one or two dry kindlings at the front of the furnace.  
3. Place newspaper strips on top of the kindlings.  
4. Cover the newspaper with more kindlings and small pieces of dry wood.  
5. Add newspaper strips, then light the fire a low as possible and leave the door 1/2" (13 mm) opened. If you fail  
lighting the fire, you might experience a back draft through the air inlets.  
PREHEATING  
1. Once the kindling is well ignited or the coals revived, put 2 or 3 fire logs in such a way that the flames can interlace  
between the logs then close the door. It is important to respect these loading sequences so that the wood will burn  
from the front to the back of the furnace.  
2. Wait 15 to 20 minutes, then proceed with loading the furnace.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEATING  
1. When loading the furnace, lower the kindled pieces of wood and place them at the center of the combustion  
chamber before adding new logs.  
2. Do not overload. Air must circulate freely in the upper part of the furnace in order to obtain an efficient operation of  
the appliance. Please note that a small hot fire will produce much less residues than a large smouldering one.  
IMPORTANT: DURING THE HEATING PROCESS, REMOVE THE ASHES AND WOOD THAT COULD  
OBSTRUCT THE 1/4" (6.4 mm) HOLE LOCATED BELOW THE DOOR INSIDE THE FURNACE.  
PROCEDURE TO OPEN THE LOADING DOOR  
TO MINIMIZE THE RISK OF A BACK DRAUGHT OPEN THE DOOR 1”  
AND WAIT ABOUT 10 SECONDS BEFORE OPENING COMPLETELY.  
THE PURPOSE IS TO STABILIZE THE PRESSURE INSIDE THE FURNACE.  
EARLY SIGNS OF OVERFIRED FURNACE  
1. Roaring fire.  
2. Chimney connector is glowing red.  
3. Extreme heat coming from the furnace. If this occurs, DO NOT OPEN THE DOOR, shut-off the air inlet opening  
completely, and wait until the glow has completely subsided.  
ALWAYS KEEP THE DOOR AND THE ASH DRAWER CLOSED  
(except for lighting and maintenance).  
WOOD AS HEATING FUEL  
We recommend that you burn dry wood only.  
There are two important factors to be considered when choosing a type of wood: the moisture content and the wood  
density. Hardwood, such as maple, oak and beech will provide better results because of the high density and minimal  
tar produced during combustion. It is highly recommended to use wood that has been dried at least six months. Do  
not use coal as heating fuel in this appliance.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Whenever a high rate of smoke is noticed in the room, you must:  
1. Open doors and windows.  
2. Make sure the furnace door is closed as well as the damper (if necessary, lower the thermostat starting point or  
undo the chain of the damper and close manually the barometric draft control).  
3. When the furnace has cooled down, inspect the chimney to detect obstructions and consult a specialist to  
determine the cause.  
CARBON MONOXYDE IS A LETHAL GAS (ODOURLESS AND COLOURLESS), WHICH YOU MUST  
BEWARE OF.  
CHIMNEY FIRES  
This might occur when the fire gets extremely hot. Burning cardboard, branches or pieces of wood can ignite the  
creosote residue accumulated in the evacuation flue system. The usual signs are:  
1. Rumbling  
2. The flue gets extremely hot  
3. Flames are coming out of the chimney  
In case of a chimney fire, first call your local fire department and sprinkle the roof around  
the chimney with water.  
Make sure that the furnace door is closed as well as the damper (if necessary, lower the thermostat starting point or  
release the chain from the damper and CLOSE the barometric draft control manually).  
If the fire gets uncontrollable due to an improper use or because the draft is too strong, follow the same procedure  
as in a chimney fire except that you will have to OPEN manually the barometric draft control.  
LOCAL FIRE DEPARTMENT.  
Phone number: ___________________________________  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. MAINTENANCE  
MAINTENANCE OF THE EXCHANGERS  
The evacuation pipe and the exchangers should be inspected regularly during the burning season. Using the  
scraper, clean the three exchanger pipes.  
INSTRUCTIONS  
1o Wait until fire is completely out before cleaning.  
2o Remove the smoke pipe connector from the furnace.  
3o Inspect the furnace’s heat exchangers (rectangular tubes) through the smoke outlet for creosote accumulation.  
4o Using the supplied scraper, clean the heat exchangers and the combustion chamber and remove creosote residues.  
5o Reassemble the smoke pipe connector.  
CHIMNEY MAINTENANCE  
One of the most efficient methods is to sweep the chimney, using a hard brush. Brush up and down. Soot and  
creosote residue will come off the inside surface and fall at the bottom of the chimney where it can be removed easily.  
The chimney must be checked regularly and if creosote has accumulated, it must be removed. Cleaning on a  
monthly basis should be sufficient during the coldest months.  
Smoke flue inspection  
-
-
-
-
-
-
The smoke flue should be inspected regularly during the heating season.  
If possible, the smoke flue should be dismantled and cleaned.  
The flue should be inspected to detect any defect.  
If no defect is noticed, put the flue back in place; otherwise, it must be replaced.  
Use only wood as a combustible.  
Seasoned hard wood logs 18” to 22” long are recommended as a combustible.  
Regular maintenance is required for safe and efficient operation of a controlled-combustion heating system. Chimney,  
gaskets and smoke pipes must remain in good working condition. Change the air filter regularly, with the same type  
and same size.  
MAINTENANCE OF THE BLOWER MOTOR  
The two bearings of the motor must be lubricated once a year using non detergent SAE 20 oil.  
DO NOT OVERLUBRICATE  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FILTERS  
The furnace must not be operated without the filters. In order to operate a slow combustion heating system  
efficiently and safely, you have to ensure a regular maintenance. This means that the chimney, the joints and the flue  
must be in good condition. The air filters must be replaced regularly. Use the same size and same type as the original  
filters.  
DOOR GASKET MAINTENANCE  
It is important to maintain the door gasket in good condition. After a while, the gasket might sag; a door adjustment  
may be then required.  
6. REPLACEMENT PARTS  
Your PSG furnace is designed to burn clean and required little maintenance. It’s recommended conduct a visual  
inspection at least once a month to uncover that any damage on the unit. Repairs must be done as soon as possible  
with the original parts. You can find a complete list of replacement parts on our website at www.psg-distribution.com.  
GASKET  
We recommend to replace gasket that seal the door once a year, in order to maintain a good control of the combustion  
for maximum efficiency and security. To replace your door gasket, remove the old gasket and glue. Clean the surface  
thoroughly, apply glue sold for that particular use, and put the new gasket onto the door. Wait for at least 2 hours  
before lighting your furnace.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. ELECTRIC DIAGRAMS FOR UNITS BUILT FROM 2005  
WOOD-ONLY FURNACES  
FAN LIMIT HONEYWELL L6064(MOTOR (G-10) 4 SPEED AND (G-12) 2 SPEED)  
HONEYWELL  
L6064  
FAN  
LINE  
LIMIT  
LOAD  
ON 150°F  
OFF 110°F  
LIMIT 250°F  
LOW HIGH LINE  
THERMOSTAT  
24 V.A.C.  
SERVO-MOTOR  
24 V.A.C.  
JUNCTION BOX  
BLUE  
L1  
BLACK  
ON  
1
2
3
BLOWER  
120 V.A.C.  
BLACK  
WHITE  
L2  
OFF  
4 SPEED  
MOTOR  
THERMINAL  
BOARD  
120 V.A.C.  
HIGH  
MED HIGH  
MED LOW  
LOW  
TRANSFORMER  
24 V.A.C.  
MOVE THIS WIRE  
TO CHANGE  
MOTOR SPEED  
REVISION JUNE 17TH 2005  
COMMUN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WOOD/ELECTRIC FURNACES  
FAN LIMIT HONEYWELL L6064(MOTOR (G-10) 4 SPEED AND (G-12) 2 SPEED)  
ELEMENTS  
CONTACTOR  
HONEYWELL  
L6064  
POWER  
BLOCK  
E
COIL  
24V  
25 KW OR 30 KW ONLY  
40 A IND/50A RES  
PER POLE  
240V  
FAN  
LIMIT  
600 V.A.C. MAX.  
ON 150°F  
L1  
N
L2  
OFF 110°F  
COMMAND  
BLOCK  
TRANSFO  
240V  
4
BLACK  
LIMIT 250°F  
LINE  
LOAD  
24V  
SEQUENCER  
S3  
BLACK/RED  
RELAY  
40VA  
POWER  
BLOCK  
B
7
A
S1  
S1  
S4 S6  
S6  
LOW HIGH LINE  
POWER  
BLOCK  
20 A  
S2  
S5  
5 KW ELEM.  
L -170 RESET  
FAN  
S5  
S6  
S1 S3  
S2  
5 KW ELEM.  
5 KW ELEM.  
1
2
3
6
S4  
S6  
B
A
C
S1  
S1  
S3  
S6  
S4  
5 KW ELEM.  
5 KW ELEM.  
TRANSFO  
120V  
S6  
S1  
BLACK  
BLACK  
COMMAND  
BLOCK  
POWER  
BLOCK  
7
8
E
1
1
POWER  
BLOCK  
24V  
COMMAND  
BLOCK  
RELAY  
6
S1  
S3  
S6  
S4  
A
B
C
D
E
F
20VA  
S1  
S5 S6  
BLOWER  
4 SPEED  
MOTOR  
TERMINAL  
2
1
8
7
HIGH  
1
2
MED HIGH  
MED LOW  
LOW  
RELAY  
WOOD  
THERMOSTAT  
MOVE THIS WIRE  
TO CHANGE MOTOR SPEED  
3
4
5
6
3
4
COMMON  
ELECTRIC  
THERMOSTAT  
COMMAND  
BLOCK  
15 KW @ 30KW  
1
2
3
4
5
6
7
8
S3  
S4  
5
6
S2  
S5  
S6  
SERVO  
MOTOR  
S1  
CONNECTORS INDENTIFICATION OF THE SEQUENCER  
REVISION JUNE 16TH 2005  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSG5000 WOOD-ONLY FURNACES  
FAN LIMIT HONEYWELL L6064(MOTOR (G-12) 2 SPEED)  
HONEYWELL  
L6064  
HONEYWELL  
L6064  
ON 150°F  
OFF 110°F  
LIMIT 250°F  
FAN  
LIMIT  
FAN  
LIMIT  
LINE  
LOAD  
LINE  
LOAD  
LOW HIGH LINE  
LOW HIGH LINE  
THERMOSTAT  
24 V.A.C.  
SERVO-MOTOR  
24 V.A.C.  
RED  
BLACK  
JUNCTION BOX  
FAN  
FAN  
1
2
3
1
2
3
L1 - BLACK  
120 V.A.C. OR 240 V.A.C.  
L2 - WHITE  
BLOWER  
RED - HIGH SPEED  
120 V.A.C.  
BLACK - LOW SPEED  
2 SPEED  
MOTOR  
TRANSFORMER  
WHITE - COMMON  
24 V.A.C.  
REVISION  
JUNE 21ST 2005  
RED - HIGH SPEED  
2 SPEED  
MOTOR  
BLACK - LOW SPEED  
WHITE - COMMON  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSG5000 WOOD/ELECTRIC FURNACES  
FAN LIMIT HONEYWELL L6064(MOTOR (G-12) 2 SPEED)  
HONEYWELL  
L6064  
HONEYWELL  
L6064  
ON 150°F  
ON 150°F  
CONTACTOR  
CONTACTOR  
OFF 110°F  
ELEMENTS  
OFF 110°F  
LIMIT 250°F  
FAN  
LIMIT  
FAN  
LIMIT  
LIMIT 250°F  
ELEMENTS  
COIL  
24V  
COIL  
24V  
25KW OR 30 KW ONLY  
25KW OR 30 KW ONLY  
SERVO  
MOTOR  
40  
A
IND/50A RES  
40  
A
IND/50A RES  
PER POLE  
PER POLE  
E
POWER  
BLOCK  
POWER  
BLOCK  
600 V.A.C. MAX.  
600 V.A.C. MAX.  
LINE  
LOAD  
E
LINE  
LOAD  
240V  
COMMAND  
BLOCK  
COMMAND  
BLOCK  
TRANSFO  
240V  
TRANSFO  
240V  
4
4
LOW HIGH LINE  
LOW HIGH LINE  
240V  
N
L1  
N
L2  
24V  
1
2
24V  
SEQUENCER  
S3  
SEQUENCER  
WOOD  
THERMOSTAT  
RELAY  
RELAY  
L1  
L2  
40VA  
POWER  
BLOCK  
40VA  
POWER  
BLOCK  
7
B
7
A
B
S6  
S3  
S6  
S1  
S1  
S1  
S4  
S4  
S5  
S5  
POWER  
BLOCK  
POWER A  
20 A  
BLOCK  
20 A  
L-170 RESET  
S2  
S2  
S3  
S5  
S5  
5
KW ELEM.  
5
KW ELEM.  
S1  
S1  
S1  
S1  
S1  
S1  
S1  
S6  
S6  
S6  
S6  
S6  
S6  
B
A
C
B
A
C
FAN  
FAN  
6
L -170 RESET  
6
S3  
5
5
KW ELEM.  
KW ELEM.  
S1  
S1  
S1  
S1  
S1  
S1  
5
5
KW ELEM.  
KW ELEM.  
1
2
3
1
2
3
S4  
S4  
S4  
S4  
S2  
S3  
S2  
S3  
S6  
S6  
S6  
S6  
5
KW ELEM.  
KW ELEM.  
5
KW ELEM.  
KW ELEM.  
7
8
7
8
S6  
A
B
C
D
E
F
A
B
C
D
E
F
S6  
S4  
S3  
S3  
5
S4  
5
POWER  
BLOCK  
POWER  
BLOCK  
TRANSFO  
120V  
TRANSFO  
120V  
S5 S6  
S5 S6  
BLACK  
BLACK  
COMMAND  
BLOCK  
BLACK  
COMMAND  
BLOCK  
POWER  
BLOCK  
POWER  
BLOCK  
E
1
1
6
E
1
1
6
24V  
24V  
COMMAND  
BLOCK  
BLACK  
COMMAND  
BLOCK  
RELAY  
RELAY  
20VA  
20VA  
2
3
1
8
7
2
3
1
8
7
BLOWER  
BLOWER  
RED - HIGH SPEED  
WHITE - COMMON  
BLACK - LOW SPEED  
RED - HIGH SPEED  
WHITE - COMMON  
BLACK - LOW SPEED  
RELAY  
#1  
RELAY  
2
3
1
8
7
6
4
5
6
4
5
6
RELAY  
#2  
COMMAND  
BLOCK  
20 KW @ 30KW  
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
4
5
S3  
S4  
20 KW @ 30KW  
COMMAND  
BLOCK  
S2  
S5  
S6  
S1  
3
4
3
4
ELECTRIC  
THERMOSTAT  
9
10  
ELECTRIC  
THERMOSTAT  
CONNECTORS INDENTIFICATION OF THE SEQUENCER  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. ELECTRIC DIAGRAMS FOR UNITS BUILT BEFORE 2005  
WOOD ONLY FURNACES PSG 4000 & 4500  
BELT-DRIVE G12 MOTOR  
HONEYWELL  
L4064  
WHITE RODGERS  
ON 150°F  
F
L
OFF 110°F  
L
F
RED  
WHITE  
LIMIT 250°F  
THERMOSTAT  
24 V.A.C.  
SERVO-MOTOR  
24 V.A.C.  
JUNCTION BOX  
L1  
ON  
120 V.A.C.  
L2  
OFF  
BLOWER  
120 V.A.C.  
RED - HIGH SPEED  
TRANSFORMER  
2 SPEED  
MOTOR  
24 V.A.C.  
WHITE - COMMON  
15 MARS 1990  
BLACK - LOW SPEED  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WOOD ONLY FURNACES PSG 5000  
BELT-DRIVE G12 MOTOR  
HONEYWELL  
L4064  
HONEYWELL  
L4064  
WHITE RODGERS  
ON 150°F  
F
L
F
L
OFF 110°F  
L
F
L
F
ROUGE  
ROUGE  
BLANC  
LIMIT 250°F  
THERMOSTAT  
24 V.A.C.  
SERVO-MOTOR  
24 V.A.C.  
RED  
BLACK  
JUNCTION BOX  
L1  
120 V.A.C. OR 240 V.A.C.  
L2  
BLOWER  
MOTOR  
120/240  
120 V.A.C.  
BLACK  
WHITE  
1 SPEED  
MOTOR  
TRANSFORMER  
24 V.A.C.  
240 V.A.C.  
TRANSFORMER  
FOR 240 VOLT ONLY  
MARCH 15TH 1990  
24 V.A.C.  
MOTOR  
120/240  
1 SPEED  
MOTOR  
BLACK  
WHITE  
IMPORTANT: A BREAKER IS MANDATORY FOR 240 VOLT  
VERIFY CONNECTIONS OF THE MOTOR 3/4 H.P.  
IF CONNECTED ONTO THE RIGHT CIRCUIT(120/240)  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WOOD/ELECTRIC FURNACES PSG 4000 & 4500  
BELT-DRIVE G12 MOTOR  
WHITE RODGERS  
HONEYWELL  
L4064  
CONTACTOR  
ON 150°F  
F
L
L
F
RED  
WHITE  
OFF 110°F  
LIMIT 250°F  
COIL  
24V  
40 A IND/50A RES  
PER PÔLE  
600 V.A.C. MAX.  
ELEMENTS  
COMMAND  
LOW SPEED  
SWITCH  
BLACK  
TRANSFO  
240V  
4
BLOCK  
POWER  
BLOCK  
24V  
E
SEQUENCER  
RELAY  
40VA  
POWER  
BLOCK  
110 VOLT  
MOTOR 3/4 H.P.  
FOR 240 V  
B
7
A
POWER  
BLOCK  
240V  
N
5 KW ELEM.  
L1  
L2  
A
B
C
D
L- 160  
F- 110  
5 KW ELEM.  
5 KW ELEM.  
20 A  
6
5 KW ELEM.  
5 KW ELEM.  
7
8
1
2
WOOD  
THERMOSTAT  
A
B
C
D
E
F
POWER  
BLOCK  
TRANSFO  
120V  
BLACK  
BLACK  
COMMAND  
BLOCK  
POWER  
BLOCK  
E
1
6
24V  
COMMAND  
BLOCK  
RELAY  
1
20VA  
3
4
ELECTRIC  
THERMOSTAT  
2
3
1
8
7
6
BLOWER  
HIGH SPEED - RED  
COMMON - WHITE  
LOW SPEED - BLACK  
RELAY  
2 SPEED  
MOTOR  
5
6
SERVO  
MOTOR  
4
5
1
2
3
4
5
6
7
8
15 KW @ 30KW  
COMMAND  
BLOCK  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WOOD/ELECTRIC FURNACES PSG 5000 40KW @ 60KW  
BELT-DRIVE G12 MOTOR  
HONEYWELL  
L4064  
HONEYWELL  
L4064  
WHITE RODGERS  
WHITE RODGERS  
CONTACTOR  
CONTACTOR  
F
L
F
L
ON 150°F  
ON 150°F  
BLACK FROM  
TRANSFO  
BLACK FROM  
TRANSFO  
RED  
RED  
L
F
L
F
OFF 110°F  
LIMIT 250°F  
COIL  
24V  
OFF 110°F  
LIMIT 250°F  
COIL  
24V  
SERVO  
MOTOR  
BLACK  
BLACK  
40  
A
IND/50A RES  
40  
A
IND/50A RES  
PER POLE  
PER PÔLE  
600 V.A.C. MAX.  
600 V.A.C. MAX.  
BLOC  
COMMANDE  
COMMAND  
BLOCK  
ELEMENTS  
POWER  
ELEMENTS  
TRANSFO  
240V  
4
TRANSFO  
240V  
4
POWER  
BLOCK  
24V  
1
2
24V  
E
E
SEQUENCER  
SEQUENCER  
BLOCK  
WOOD  
THERMOSTAT  
RELAY  
RELAY  
40VA  
POWER  
BLOCK  
40VA  
POWER  
BLOCK  
110 VOLT LINE  
3/4 H.P. MOTOR  
240  
110 VOLT LINE  
3/4 H.P. MOTOR  
B
B
7
7
POWER  
BLOCK  
POWER  
BLOCK  
B
C
A
B
C
A
V
240  
V
A
A
240V  
240V  
5
KW ELEM.  
5
KW ELEM.  
L1  
N
L2  
L1  
N
L2  
L- 160  
F- 110  
L -160  
F -110  
5
5
KW ELEM.  
KW ELEM.  
5
5
KW ELEM.  
KW ELEM.  
20 A  
20 A  
6
6
IMPORTANT:  
IMPORTANT:  
5
KW ELEM.  
KW ELEM.  
5
KW ELEM.  
KW ELEM.  
IT IS MANDATORY TO CHANGE THE  
TRANSFORMER 120-24 FOR 240-24  
IF YOU USED 3/4 H.P. MOTOR ON 240  
IT IS MANDATORY TO CHANGE THE  
TRANSFORMER 120-24 FOR 240-24  
IF YOU USED 3/4 H.P. MOTOR ON 240  
A
A
V
V
7
8
7
8
A
B
C
D
E
F
A
B
C
D
E
F
5
5
POWER  
BLOCK  
POWER  
BLOCK  
TRANSFO  
120V  
TRANSFO  
BLACK  
BLACK  
COMMAND  
BLOCK  
BLACK  
BLACK  
120V  
COMMAND  
BLOCK  
POWER  
BLOCK  
POWER  
BLOCK  
E
1
1
6
E
1
1
6
24V  
24V  
COMMAND  
BLOCK  
COMMAND  
BLOCK  
RELAY  
RELAY  
20VA  
20VA  
2
3
1
8
7
6
2
3
1
8
7
6
BLOWER  
BLOWER  
RELAY  
RELAY  
WHITE  
BLACK  
WHITE  
BLACK  
2
3
1
8
7
6
4
5
4
5
RELAY  
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
4
5
20 KW @ 30KW  
20 KW @ 30KW  
COMMAND  
BLOCK  
COMMAND  
BLOCK  
3
4
3
4
ELECTRIC  
THERMOSTAT  
9
10  
ELECTRIC  
THERMOSTAT  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
WOOD ONLY FURNACES PSG 2000-3000-4000  
DIRECT-DRIVE G10 MOTOR  
HONEYWELL  
L4064  
WHITE RODGERS  
F
L
BLACK FROM  
TRANSFO  
ON 150°F  
RED  
L
F
OFF 110°F  
LIMIT 250°F  
THERMOSTAT  
24 V.A.C.  
SERVO-MOTOR  
24 V.A.C.  
RELAY  
JUNCTION BOX  
RED  
L1  
2
5
1
4
3
ON  
1
2
BLOWER  
120 V.A.C.  
L2  
BLACK  
3
OFF  
4 SPEED  
MOTOR  
TERMINAL  
BOARD  
120 V.A.C.  
HIGH  
MED HIGH  
MED LOW  
LOW  
TRANSFORMER  
24 V.A.C.  
REVISION MAY 20TH 1994  
COMMUN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WOOD/ELECTRIC FURNACES PSG 2000-3000-4000  
DIRECT-DRIVE G10 MOTOR  
HONEYWELL  
L4064  
WHITE RODGERS  
F
L
ON 150°F  
BLACK TO  
TRANSFOMER  
RED  
L
F
OFF 110°F  
LIMIT 250°F  
CONTACTOR  
BLACK  
COIL  
24V  
40 A IND/50A RES  
PER POLE  
600 V.A.C. MAX.  
ELEMENTS  
POWER  
COMMAND  
BLOCK  
TRANSFO  
240V  
4
24V  
B
C
A
E
BLOCK  
SEQUENCER  
RELAY  
7
40VA  
POWER  
BLOCK  
B
POWERA  
240V  
BLOCK  
ELEM. 5 KW  
L1  
N
L2  
FAN  
L -170 RESET  
ELEM. 5 KW  
ELEM. 5 KW  
20 A  
6
5
FAN  
RELAY  
ELEM. 5 KW  
ELEM. 5 KW  
TRANSFO  
120V  
BLACK  
COMMAND  
BLOCK  
POWER  
BLOCK  
7
8
E
1
1
6
POWER  
BLOCK  
24V  
BLACK  
COMMAND  
BLOCK  
RELAY  
A
B
C
D
E
F
20VA  
BLOWER  
FAN RELAY  
POWER  
BLOCK  
POWER  
BLOCK  
2
5
3
4
D
B
4 SPEED  
MOTOR  
TERMINAL  
BOARD  
1
2
3
1
8
7
6
E
A
HIGH  
MED HIGH  
MED LOW  
LOW  
POWER  
BLOCK  
POWER  
BLOCK  
RELAY  
MOVE THIS WIRE  
TO CHANGE MOTOR SPEED  
1
2
WOOD  
THERMOSTAT  
4
5
COMMUN  
3
4
ELECTRIC  
THERMOSTAT  
1
2
3
4
5
6
7
8
15 KW @ 30KW  
COMMAND  
BLOCK  
5
6
SERVO  
MOTOR  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9. TECHNICAL SPECIFICATIONS  
2000 3000 4000 4500 5000  
45 ¼"  
47"  
50"  
52 ½" 54 ½"  
A
B
C
D
E
F
23 ½" 25 ½" 29 ½" 33 ½"  
54"  
45 ½" 47 ¼"  
48"  
19"  
28"  
48"  
19"  
30"  
56 ¾"  
19 ¾"  
31 ½"  
15 " 15 "  
26 "  
28"  
22 ½" 24 ½" 28 ½" 32 ½" 51 "  
40 ½" 41 ¼"  
42"  
42"  
49 ½"  
G
PIPES  
WEIGHT  
7"  
445  
8"  
540  
8"  
600  
8"  
8"  
660  
1200  
GENERAL TECHNICAL DATA  
MODEL  
BELT DRIVE  
DIRECT DRIVE  
FAN  
MOTOR SPEED  
FAN  
MOTOR SPEED OUTPUT TEMP BTU/  
STATIC  
PRESSURE  
( "WATER)  
FILTER  
(2)  
*
(C.F.M.)  
VAR.  
HR  
(WOOD)  
(O F)  
H2O  
2000  
3000  
4000  
4000  
4500  
5000  
N/A  
N/A  
N/A  
G-12  
G-12  
G-12  
G-10  
G-10  
G-10  
N/A  
N/A  
N/A  
1/3  
1/3  
1/3  
4
4
4
950  
68  
78  
128  
93  
121  
125  
70000  
0,2  
0,4  
0,6  
0,6  
0,8  
0,8  
1,45  
11 x 20  
12 x 24  
12 x 24  
12 x 24  
12 x 24  
20 x 24  
1300  
1300  
1800  
1800  
3600  
110000 0,2  
180000 0,2  
180000 0,2  
235000 0,2  
350000 0,2  
3/4  
3/4  
3/4  
2
2
2
TECHNICAL DATA – ELECTRIC MODE  
MODEL OUTPUT TEMP. VAR. BTU/HR AMPERES BREAKER FEEDER  
VOLTAGE  
ELEMENTS  
QTY  
3 – 5 KW  
(C.F.M.)  
950  
(O F)  
50  
36  
26  
60  
44  
32  
67  
49  
35  
83  
61  
44  
73  
53  
TOTAL  
75  
REQUIRED GAUGE SINGLE PHASE  
15 KW  
18 KW  
20 KW  
25 KW  
51195  
61434  
68260  
85325  
102390  
100  
100  
115  
140  
170  
4
4
3
2
1
120/240  
120/240  
120/240  
120/240  
1300  
1800  
950  
1300  
1800  
950  
1300  
1800  
950  
1300  
1800  
1300  
1800  
87  
95  
2 – 5 KW, 2 – 4 KW  
4 – 5 KW  
115  
5 – 5 KW  
30 KW  
WOOD  
140  
15  
120/240  
120  
6 – 5 KW  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10. SELECTION CRITERIA (COMBINED WOOD/ELECTRIC FURNACE)  
RESIDENTIAL AREA  
House including: basement, first floor and second floor (half)  
Floor area *  
New house  
Existing house  
1100 square feet or less  
1100 to 1450 square feet  
1400 to 2000 square feet  
2000 to 3000 square feet  
PSG 2000 – 15  
PSG 3000 – 18  
PSG 4000 – 20  
PSG 4500 – 25  
PSG 2000 – 18 or 20  
PSG 3000 – 20 or 25  
PSG 4000 – 25 or 30  
PSG 4500 – 30  
COMMERCIAL AREA  
Building including:  
Walls 14 to 16 feet high  
Garage doors, no basement  
Floor area  
2500 to 3800 square feet  
PSG 4500 Wood  
4000 to 10000 square feet  
* Consider main floor only.  
PSG 5000 – 40 or 60  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11. TROUBLESHOOTING  
PROBLEM  
CAUSES  
SOLUTIONS  
1. Sudden drop in heating  
performance follows adequate  
heating from first loadings.  
Ash accumulation at lower intake  
blocks combustion air intake and  
causes deposits in heat exchanger  
and flue pipes.  
Clear air intake of any ash  
accumulation.  
Clean heat exchanger and flue pipes.  
2. Insufficient heat from first loadings, Wrong setting of draft regulator  
Set draft regulator (reduce opening).  
Reduce distance between furnace  
low draft  
(opening too large).  
Restriction in chimney flue (excessive and chimney and eliminate 90o  
length of chimney connector, right-  
angled elbows).  
elbows.  
Maximum length: 10 feet.  
Tight-angle elbows: maximum 3.  
3. Poor heating in the rooms while  
hot air plenum and furnace are hot.  
Inadequate duct installation.  
Insufficient static pressure.  
Reposition ducts.  
Unbalanced system (too many hot air  
outlets for too few cold air intakes).  
4. Furnace burns too much wood.  
The thermostats controlling the air  
combustion damper is located too  
close to cold air and demands heat  
continuously.  
Wrong setting of air intake register.  
Poor building insulation.  
Relocate thermostat.  
Adjust chain between damper motor  
and combustion air damper.  
Balance the ventilation system as to  
increase the flow air in room where  
thermostat is located.  
Ash drawer left open.  
Furnace too small for heating needs.  
Unbalanced ventilation system,  
insufficient heat near thermostat.  
5. Fan starts too late.  
Fan starting temperature is too high.  
Cold air return is too cold.  
Inappropriate location of fan limit  
control in hot air plenum.  
Lower starting temperature (the fan  
limit control is normally set at 150 oF);  
under certain conditions, this limit  
should be reduced.  
Reduce the cold air intake.  
Relocate fan limit control within the  
hot air plenum.  
6. Creosote accumulation, very  
average performance.  
Damp wood.  
Insufficient draft.  
Clogged chimney.  
Use dry wood.  
Adjust draft regulator.  
Clean chimney, chimney connector  
and furnace heat exchangers.  
7. Hot air plenum remains barely  
Damp wood.  
Use dry wood.  
warm while furnace in full operation.  
Too much cold air return in relation to Redistribute ventilation system.  
hot air ducts.  
Unbalanced ventilation system.  
IMPORTANT NOTE  
WE STRONGLY RECOMMEND CONSULTING A HEATING SYSTEM SPECIALIST  
FOR THE INSTALLATION OF A CENTRAL HEATING VENTILATION SYSTEM.  
N.B.: STOVE BUILDER INTERNATIONAL INC. IS NOT LIABLE FOR ANY FAULTY INSTALLATION WHICH RENDERS THIS  
UNIT INOPERATIVE  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12. DUCTS AND REGISTER MEASUREMENTS  
(sample calculations)  
SIMPLIFIED METHOD  
WARM AIR SYSTEM INSTALLATION  
DISTRIBUTION SYSTEM  
HOUSE DIMENSIONS  
Example: 28 x 40 bungalow: 1,120 sq. ft.  
Ducts size (heat)  
4 inch outlet reduce by 1”  
28 x 40 x 8: 8,960 cu. ft. x 1.8 Ch. air/hr:  
16,128 Btu  
5 inch outlet reduce by 2” Always by 8” thick  
6 inch outlet reduce by 3”  
Exposed walls:  
N.B.: The main duct must be reduced every 2  
outlets.  
40 + 40 + 28 + 28: 136 x 8: 1,088 cu. ft. x 22: 23,936 Btu  
Number of windows:  
12 of 3 x 4: 144 x 60:  
Number of doors:  
2 x 3 x 7: 42 x 100:  
8,640 Btu  
Ducts specifications (heat)  
Dimensions Length Elbow  
Average equivalence  
Max 4,000 Btu  
4,200 Btu  
4”  
5”  
6”  
10’  
10’  
10’  
1 x 90o  
1 x 90o  
1 x 90o  
52,904 Btu  
Max 6,000 Btu  
Non-insulated basement: 25%  
Insulated basement: 15%  
Max 7,000 Btu  
7,906 Btu  
or 54 Btu per sq. ft.  
60,840 Btu  
FOR ELECTRIC ELEMENTS 80%:48,672 Btu or 14,28 kW  
TO BE ADDED:House 1 1/2 floor = 25%  
DAMPER  
House 2 floors  
= 40%  
For a 4” warm air outlet: 2” x 10” damper  
For a 5” warm air outlet: 2” x 12” damper or 4” x 10”  
For a 6” warm air outlet: 2” x 14” damper or 4” x 12”  
BEDROOM (for example: 12 x 12)  
12 x 12 x 8: 1,152 cu. ft. x 1.8 Ch. air/hr:  
Exposed walls:  
2,074 Btu  
4,224 Btu  
12 + 12 x 8: 192 x 22:  
Windows:  
3 x 4 x 60  
720 Btu  
7,018 Btu  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1700, rue Léon-Harmel, Québec (Québec) G1N 4R9  
tel. : (418) 527-3060 fax : (418) 527-4311  
e-mail : tech@sbi-international.com web site : www.psg-distribution.com  
LIMITED LIFETIME WARRANTY  
The PSG warranty extends only to the original consumer purchaser and is not transferable. This warranty covers brand new  
products only, which have not been altered, modified nor repaired since shipment from factory. Proof of purchase (dated bill of  
sale), model name and serial number must be supplied when making any warranty claim to your PSG dealer  
This warranty applies to normal use only. Damages caused by misuse, abuse, improper installation, lack of maintenance, over firing,  
negligence or accident during transportation are not covered by this warranty.  
This warranty does not cover any scratch or discoloration caused by over firing, abrasives or chemical cleaners. Any defect or  
damage caused by the use of unauthorized parts or others than original parts void this warranty.  
An authorized qualified technician must perform the installation in accordance with the Instructions supplied with this product and  
all local and national building codes. Any service call related to an improper installation is not covered by this warranty.  
Returned products are to be shipped prepaid to PSG for investigation. If a product is found to be defective, PSG will repair or replace  
such defect and reasonable transportation fees will be refund. Repair work covered by the warranty, executed at the purchaser  
domicile by an authorized qualified technician requires the prior approval of PSG. Labour cost and repair work to the account of PSG  
are based on predetermined rate schedule and must not exceed the wholesale price of the replacement part.  
PSG at its discretion may decide to repair or replace any part or unit after inspection and investigation of the defect. PSG may, at its  
discretion, fully discharge all obligations with respect to this warranty by refunding the wholesale price of any warranted but  
defective parts  
PSG shall in no event be responsible for any special, indirect, consequential damages of any nature, which are in excess of the  
original purchase price of the product.  
WARRANTY APPLICATION  
DESCRIPTION  
LABOUR  
5 years  
n/a  
Combustion chamber (weldings only)  
Perforation caused by rust  
Stainless steel baffle  
1 year  
1 year  
n/a  
Carbon steel baffle  
Handle assembly  
Ash drawer  
1 year  
1 year  
n/a  
Cast iron parts  
Ceramic glass (thermal breakage only)  
Paint, refractory bricks, gasket, blower, thermal switch (thermodisc) and  
rheostat  
1 year  
n/a  
n/a  
Plating  
Shall your unit or a components be defective, contact immediately your PSG dealer. Prior to your call make sure you have the  
following information necessary to your warranty claim treatment:  
You name, address and telephone number;  
Bill of sale, dealer’s name;  
Serial number and model name as indicated on the  
nameplate fixed to the back of your unit;  
Nature of the defect and any relevant information.  
Before shipping your unit or defective component to our plant, you must obtain from your PSG dealer an  
Authorization Number. Any merchandise shipped to our plant without authorization will be refused  
automatically and returned to sender.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Westinghouse Flat Panel Television SK 26H640G User Manual
Westinghouse Outdoor Timer Outdoor Timer User Manual
Whirlpool Dishwasher DU1015 User Manual
Whirlpool Range EDP EDN User Manual
Whirlpool Range FEC330B User Manual
Whirlpool Washer 2DLSQ8000JQ0 User Manual
Whirlpool Washer Dryer CSP2760TQ User Manual
Wolf Appliance Company Range DF484DG User Manual
Woodstock Satellite TV System m1043 User Manual
Zanussi Coffeemaker Built In Coffee Machine User Manual