Weil McLain Boiler 550 141 826 1201 User Manual

WGO  
SERIES 3 OIL-FIRED NATURAL DRAFT WATER BOILER  
This Manual  
Includes:  
Installation  
Start-Up  
Boiler Parts  
As an EVERGY STAR Partner, Weil-McLain  
has determined that this product meets the  
ENERGY STAR guidelines for energy efficiency  
Installer: • Make sure this is the correct manual for the boiler. Verify boiler model on  
rating label.  
• Leave all documentation received with boiler and burner with unit for  
future reference.  
User: Boiler and burner must be installed and serviced by qualified service technician.  
Part No. 550-141-826/1201  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Read all instructions before installing. Failure to follow all instructions in proper order can  
cause severe personal injury, death or substantial property damage.  
Read This Page First . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Before Installing Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5  
Install Packaged Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7  
Install Non-Packaged Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-11  
Connect Breeching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-13  
Connect Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14-18  
Connect Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19-21  
Connect Oil Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22  
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23  
Check-Out Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24  
Installation and Service Certificate . . . . . . . . . . . . . . . . . . . . . . . .24  
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25-27  
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28  
Parts Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29  
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30-31  
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Back Cover  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Before Installing Boiler  
Installations must comply with:  
Provide clearances around boiler  
(see FIGURE 1):  
U.S.  
— State and local plumbing, heating and  
electrical codes.  
Jacket cap must be in place on  
— National codes where applicable.  
Canada  
boiler to avoid requiring an 18"  
minimum clearance from back or top of boiler to  
combustible material.  
— Canadian Standards Association,  
CSA B139, Installation Code for  
Oil-Burning Equipment.  
— CSA C22.1 Canadian Electrical Code Part One.  
— Applicable local or provincial codes.  
Minimum clearances from vent pipe to  
combustible material:  
6 inches — Type “L” doublewall vent*  
18 inches — Singlewall vent*  
Before selecting boiler location:  
Check for nearby connections to:  
— System water piping.  
Flue pipe clearances must take  
precedence over jacket clearances.  
— Chimney. See pages 12-13. Boiler can be top  
or back vented.  
— Combustion and ventilation air supply. See  
page 5.  
— Oil supply. See page 22 for oil line routing.  
— Electrical power.  
Recommended service clearances:  
24 inches — Front and top  
6 inches — Left side, back and right side  
12 inches — Right side for burner door  
swing radius ∆  
Check area around boiler. Remove any  
combustible materials, gasoline and other  
flammable liquids.  
Special close clearances (alcove, closet, under  
counters, etc.) — see Appendix, pages 25-27.  
Failure to keep boiler area  
clear and free of combustible  
materials, gasoline and other flammable liquids  
and vapors can result in severe personal injury,  
death or substantial property damage.  
Ceiling  
*
6"  
(18")  
*
6"  
(18")  
24"  
Walls  
6" (12")  
*
6"  
(18")  
24"  
6"  
Wall  
6"  
Floor  
TopView  
Left Side  
Recommended Service Clearances  
FIGURE 1  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Before Installing Boiler  
CONTINUED  
Through horizontal ducts — at least 70 sq. in. per  
1 GPH boiler input (1 sq. in. per 2000 Btu input)  
of all fuel-burning appliances plus requirements for  
any equipment that can pull air from room  
(including clothes dryer and fireplace).  
Where ducts are used, they should have same  
cross-sectional area as free area of openings to  
which they connect. Compensate for louver,  
grille or screen blockage when calculating free  
air openings. Refer to their manufacturer’s  
instructions for details. If unknown, use:  
— Wood louvers, which provide 20-25% free air.  
— Metal louvers or grilles, which provide  
60-75% free air.  
Provide air for combustion and ventilation:  
Adequate combustion and  
ventilation air:  
Assures proper combustion.  
Reduces risk of severe personal injury or death  
from possible flue gas leakage and carbon  
monoxide emissions.  
Do not install exhaust fan in boiler room.  
Older buildings with single-pane windows,  
minimal weather-stripping and no vapor barrier  
often provide enough natural infiltration and  
ventilation without dedicated openings.  
Lock louvers in open position or interlock with  
equipment to prove open before boiler operation.  
New construction or remodeled buildings are most  
often built tighter. Windows and doors are  
weather-stripped, vapor barriers are used and  
openings in walls are caulked. As a result, such  
tight construction is unlikely to allow proper  
natural air infiltration and ventilation.  
Lay a foundation, if needed:  
Boiler may be installed on non-carpeted  
combustible flooring.  
For residential garage installation, install boiler so  
burner is at least 18 inches above floor to avoid  
contact with gasoline fumes.  
Follow state, provincial or local codes when sizing  
adequate combustion and ventilation air openings.  
In absence of codes, use the following guidelines  
when boiler is in a confined room (defined by NFPA  
31 as less than 7200 cubic feet per 1 GPH input of  
all appliances in area. A room 8 ft. high x 33.5 ft. x  
33.5 ft. is 7200 cu. ft.):  
A level concrete or masonry foundation is  
required when:  
Floor could possibly become flooded.  
Non-level conditions exist.  
Solid concrete blocks can be used to create a pad.  
Provide two permanent openings — one within 12  
inches of ceiling, one within 12 inches of floor.  
Minimum height or length dimension of each  
rectangular opening should be at least 3 inches.  
BOILER FOUNDATION SIZE TABLE  
MIN.  
BOILER  
MODEL  
LENGTH  
INCHES  
WIDTH  
INCHES  
HEIGHT  
INCHES  
When inside air is used — each opening must  
freely connect with areas having adequate  
WGO-2  
WGO-3  
WGO-4  
WGO-5  
WGO-6  
WGO-7  
WGO-8  
WGO-9  
14  
17  
17  
20  
23  
26  
29  
32  
22  
22  
22  
22  
22  
22  
22  
22  
2
2
2
2
2
2
2
2
infiltration from outside. Each opening should be at  
least 140 sq. in. per 1 GPH input (1 sq. in. per 1000  
Btu input) of all fuel-burning appliances plus  
requirements for any equipment that can pull air  
from room (including clothes dryer and fireplace).  
When outside air is used — connect each  
opening directly or by ducts to the outdoors or to  
crawl or attic space that freely connects with  
outdoors. Size per below:  
Through outside wall or vertical ducts — at least 35  
sq. in. per 1 GPH input (1 sq. in. per 4000 Btu  
input) of all fuel-burning appliances plus  
Go to page 6  
to install boiler  
requirements for equipment that can pull air from  
room (including clothes dryer and fireplace).  
Go to page 8  
to install boiler  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Install Packaged Boiler  
Place boiler:  
1. Remove circulator strapped to pallet.  
Perform hydrostatic pressure test:  
1. Remove relief valve installed in boiler.  
2. Install air vent in “N” tapping on top boiler.  
Circulator will be damaged if  
not removed before boiler is  
lifted from pallet.  
3. Plug supply and return tappings.  
4. Drain valve is already factory-installed.  
5. Fill boiler. Vent all air. Pressure test boiler at  
1½ times working pressure.  
2. Remove boiler from pallet.  
Do not leave boiler unattended.  
Cold water fill can expand and  
damage cast iron, resulting in severe personal  
injury, death or substantial property damage.  
Do not drop boiler or bump  
jacket on floor or pallet.  
Damage to boiler can result.  
Smaller sized boilers may be top  
heavy. Use caution when  
handling to avoid minor personal injury or  
property damage.  
6. Check for maintained gauge pressure for more  
than 10 minutes. Visually check for leaks if  
gauge pressure drops.  
7. Drain boiler. Repair leaks if found.  
3. Boiler is shipped for back flue outlet. To  
change to top flue outlet (see FIGURE 2):  
a. Remove jacket cap on top of boiler.  
b. Loosen two screws holding flue cap strap  
to collector hood. Remove strap and flue  
cap from opening. Re-tighten screws.  
c. Check rope placement inside flue cap.  
Do not use petroleum-based  
sealing compounds to repair  
leaks. Damage to system components can  
result, causing property damage.  
8. Retest boiler after repairing leaks.  
9. Remove air vent and plugs. Reinstall relief  
valve.  
(Read  
under step #6 below).  
d. Loosen two screws on back flue outlet. Set  
flue cap on outlet. Install strap by engaging  
slots in screws. Tighten screws. Make sure  
cap is securely installed.  
e. Snap jacket cap in back outlet opening.  
Jacket cap must be in place  
on boiler to avoid requiring  
an 18” minimum clearance from back or  
top of boiler to combustible material.  
4. Check level. Shim legs, if needed.  
5. Check for secure placement of insulation on  
target wall, chamber floor and burner door.  
6. Visually check:  
a. Flue collector hood seal.  
b. Burner mounting door seal.  
Obtain gas-tight seal to prevent  
possible flue gas leakage and  
carbon monoxide emissions, which can lead to  
severe personal injury or death.  
Go to page 12 to connect  
breeching and venting  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Install Packaged Boiler  
CONTINUED  
Change From Back Flue Outlet to Top Flue Outlet (Optional)  
FIGURE 2  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Install Non-Packaged Boiler  
3) Loosen two screws on back flue outlet.  
Fiberglass wool and ceramic fiber materials:  
Set flue cap on outlet. Install strap by  
engaging slots in screws. Tighten screws.  
Make sure cap is securely installed.  
• POSSIBLE CANCER HAZARD  
BY INHALATION  
• CAN CAUSE RESPIRATORY,  
2.  
Non-Packaged WGO-7, 8 & 9 — split the  
assembled block for easier handling (see  
FIGURE 3):  
SKIN AND EYE IRRITATION  
This product contains fiberglass wool and ceramic  
fiber materials. Airborne fibers from these materials  
have been listed by the State of California as a  
possible cause of cancer through inhalation. Apply  
special care when handling ceramic fiber (chamber  
lining and base insulation) materials. Ceramic fibers  
can be converted to chrystobalites, a substance listed  
as a probable cause of cancer.  
a. Open burner mounting door and,  
using utility knife, slit floor insulation at  
joint to be separated.  
b. Remove 5½" draw rod and the longest  
draw rod from each side. Pull block apart.  
Save draw rods, nuts, washers and sealing  
rings for reassembly.  
c. Move divided block to location.  
d. Clean port openings with clean rag.  
Suppliers of fiberglass wool products recommend  
the following precautions be taken when handling  
these materials:  
Do not use petroleum-based  
compounds to clean openings.  
Precautionary measures:  
Avoid breathing fiberglass dust and contact  
Damage to system components can result,  
causing property damage.  
with skin and eyes.  
Use NIOSH approved dust/mist respirator.  
Wear long-sleeved, loose fitting clothing, gloves  
and eye protection.  
Wash work clothes separately from other  
clothing. Rinse washer thoroughly.  
Operations such as sawing, blowing, tearout  
and spraying may generate airborne fiber  
concentration requiring additional protection.  
e. Place rings in port openings. If ring slips  
out of groove, stretch ring gently for several  
seconds, then place in groove.  
f. Position sections so aligning lugs fit into  
sockets of next section. Make sure sealing  
rope is in good condition and in position.  
g. Oil threads on draw rods. Install  
washer and nut on end to be tightened.  
Use nut only on other end.  
h. With wrench at washer/nut end,  
uniformly tighten nuts starting with  
5½" rod at large port, 5½" rod at  
small port, bottom long rod and finally  
top long rod.  
First aid measures:  
Eye contact — Flush eyes with water to remove  
dust. If symptoms persist, seek medical attention.  
Skin contact — Wash affected areas gently  
with soap and warm water after handling.  
Place boiler:  
1. Non-Packaged WGO-2 through 6 — position on site.  
i. Torque on both 5½" rods and bottom  
long rod should be 50-60 ft. lbs; long  
top rod should be 20-25 ft. lbs. Do not  
back-off nuts.  
j. Metal-to-metal contact should be  
made around port openings. If gap  
does exist, it should be less than .020".  
Check with feeler gauge.  
Smaller sized boilers may be  
top heavy. Use caution when  
handling to avoid minor personal injury or  
property damage.  
a. Boiler is shipped for back flue outlet. To  
change to top flue outlet (see FIGURE 3):  
1) Loosen two screws holding flue cap  
strap to collector hood. Remove strap  
and flue cap from opening.  
k. If gap around port openings exceeds  
.020", check for dirt on port openings,  
sockets or misaligned lugs. If  
Re-tighten screws.  
2) Check rope placement inside flue cap.  
corrections are made and gap still  
exists, contact your Weil-McLain  
distributor or sales office before  
continuing installation.  
(Read  
under Step #3 on page 9.)  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Install Non-Packaged Boiler  
CONTINUED  
3. Non-Packaged WGO-7, 8 & 9 — install flue  
d. Install washers and nuts. Tighten nuts  
until collector hood makes contact with  
tinnerman clip.  
collector hood (see FIGURE 3):  
Obtain gas-tight seal to prevent  
possible flue gas leakage and  
carbon monoxide emissions, leading to severe  
personal injury or death.  
e. Back flue outlet boiler — Position flue  
cap and strap over opening in flue collector  
hood. Make sure rope in cap is in place  
and in good condition. Tighten strap to  
hood with screws provided.  
a. Thread tinnerman clip on screw so that  
clip fits snugly in notch of hold-down lug.  
Screw must not turn.  
b. Remove paper on sealing rope. Starting at  
back section near flue collar, position  
sealing rope around top of block with  
adhesive side to sections. Do not stretch  
rope. Make sure rope ends meet. Trim  
excess rope.  
Top flue outlet boiler — Position flue cap  
and strap over opening in back section.  
Make sure rope in cap is in place and in  
good condition. Tighten strap to boiler with  
screws provided in section. Install  
remaining screws in holes in flue  
collector hood.  
4. Check level. Shim legs, if needed.  
c. Position flue collector hood on top of boiler  
sections and over screws and clips as  
shown in FIGURE 3.  
Nut  
Washer  
Tinnerman  
Clip  
Flue Collector  
Hood  
Sealing Rope in  
Groove Inside Cap  
Screw  
Hold-down  
Lug  
Sealing Rope  
with Adhesive  
Tape  
Flue  
Cap  
Flue Cap  
Strap  
Change From Back Flue Outlet to Top Flue Outlet (Optional)  
FIGURE 3  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Install Packaged and Non-Packaged Boiler  
7. Visually check:  
Perform hydrostatic pressure test:  
1. See FIGURE 4 and Control Tapping Table  
below to install:  
a. Sealing rope placement.  
b. Metal-to-metal contact around port openings.  
c. Flue collector hood seal.  
d. Burner mounting door seal.  
a. Boiler drain.  
b. Water pressure gauge (test only). Be sure  
gauge can handle test pressure.  
Obtain gas-tight seal to prevent  
possible flue gas leakage and  
c. Air vent in upper “N” tapping.  
d. Plugs in remaining tappings.  
carbon monoxide emissions, which can lead to  
severe personal injury or death.  
2. Fill boiler. Vent all air. Pressure test boiler at 1  
times working pressure. For boilers split and  
reassembled, test between 75 and 85 psig.  
Install jacket (sizes 7 through 9 only):  
Before installing jacket, remove burner mounting  
door. See jacket instructions for details.  
Do not leave boiler unattended.  
Cold water fill could expand and  
damage cast iron, resulting in severe personal  
injury, death or substantial property damage.  
Install boiler controls:  
See Control Tapping Table and FIGURES 4 and 5  
to install controls.  
3. Check for maintained gauge pressure for more  
than 10 minutes. Visually check for leaks if  
gauge pressure drops.  
1. Install limit control. If not furnished, use high  
limit with maximum 220°F setting.  
2. Affix CP number label(s) on jacket front panel.  
4. Drain boiler. Repair leaks if found.  
Do not use petroleum-based  
compounds to repair leaks.  
CONTROLTAPPINGTABLE  
Damage to system components can result,  
causing property damage.  
LOCATION  
SIZE  
1½"  
FUNCTION  
Return Piping  
B1  
Alternate Return Piping  
for A/B WGO  
Supply Piping  
Pressure-Temperature Gauge  
DrainValve  
B2  
1
"
½
5. Re-test boiler after repairing leaks.  
6. Remove pressure gauge, air vent and plugs  
from tappings used for controls.  
C
E3  
H
1½"  
¾"  
¾"  
¾"  
L
High Limit Control  
Air Vent or  
N
½"  
¾"  
Expansion Tank Piping  
R1  
Relief Valve  
N
C
E3  
L
R1  
B2  
B1  
Front Section  
H
Back Section  
Control Tapping Location  
FIGURE 4  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Install Packaged and Non-Packaged Boiler  
Install burner (also refer to instructions packed with burner):  
Burners designed for use with Weil-McLain 68 boilers must not be used on GOLD Oil  
boilers. Contact individual burner manufacturers for GOLD Oil applications.  
For P-WGO and A-WGO boiler:  
from inside wall of burner door refractory. Check  
for secure placement of insulation on target wall,  
chamber floor and burner mounting door.  
Securely close door with nut.  
1. Secure universal mounting flange and gasket to  
burner mounting door. Use three bolts provided.  
2. Secure burner on flange with three bolts.  
3. Position burner so end of air tube is level to 1½°  
tilt downward. Open door to verify burner position.  
End of air tube should be flush to ¼" recessed  
Circulator  
Water  
Pressure-Temperature  
Gauge  
Relief  
Valve  
Limit Control  
Drain Valve  
Water Boiler Controls  
FIGURE 5  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect Breeching  
General chimney requirements:  
MINIMUM CHIMNEY SIZE TABLE  
Designed for natural draft firing. Connect  
boiler to vertical chimney.  
MINIMUM  
I=B=R  
***  
BOILER  
MODEL  
NUMBER  
WGO-2  
WGO-3  
WGO-4  
WGO-5  
WGO-6  
WGO-7  
WGO-8  
WGO-9  
MINIMUM  
MINIMUM  
CHIMNEY SIZE CHIMNEY  
BREECHING  
DIAMETER  
Insufficient draft can cause flue  
gas leakage and carbon  
monoxide emissions, which will lead to severe  
personal injury or death.  
RECT. ROUND  
HEIGHT  
15'  
5"  
8" x 8"  
*
6"  
6"  
6"  
Use vent material approved by local codes for  
oil-fired burners. In their absence, refer to:  
— NFPA 31, Installation of Oil-Burning Equipment.  
— NFPA 211, Standard for Chimneys, Fireplaces,  
Vents and Solid Fuel Burning Appliances.  
— In Canada, refer to CSA B139, Installation  
Code for Oil-Burning Equipment.  
8" x 8"  
*
7"  
7"  
15'  
20'  
7"  
7"  
8" x 12"  
**  
*
6¾" x 6¾" inside liner  
** 6½" x 10½" inside liner  
*** Flue collar on boiler is 7" diameter  
NFPA 211 requires chimney to be lined before  
connected to boiler.  
Connect breeching:  
Inspect existing chimney before  
installing new boiler. Failure to  
do any of the following will result in severe  
personal injury or death:  
— Clean chimney, including removal of blockage.  
— Repair or replace damaged pipe or liner.  
— Repair mortar and joints.  
Long horizontal breechings,  
excessive number of tees and  
elbows or other obstructions restricting  
combustion gas flow can result in possibility of  
condensation, flue gas leakage and carbon  
monoxide emissions, which can lead to severe  
personal injury or death.  
To prevent downdrafts, extend chimney at  
least 3 feet above highest point where it passes  
through roof and 2 feet higher than any  
portion of building within 10 feet. Increase  
chimney cross-sectional area and height at  
least 4% per 1,000 feet above sea level.  
1. Install 2 flue pipe brackets.  
2. Connect full-sized breeching when possible.  
See Minimum Chimney Size Table.  
— Back outlet — see FIGURE 6.  
— Top outlet — see FIGURE 7.  
3. Connection must be made above bottom of  
chimney to avoid blockage. Breeching must not  
enter chimney far enough to cause obstruction.  
Use thimble or slip joint where breeching enters  
chimney to allow removal for cleaning.  
4. When burner and boiler are properly installed,  
draft overfire will be approximately -0.01"  
to -0.02" W.C. Install barometric control in  
breeching, per control manufacturer’s  
instructions, when excess draft needs to be  
relieved or to comply with applicable codes  
and regulations. Use draft gauge to adjust  
proper opening.  
Minimum clearances from vent pipe to  
combustible material:  
6 inches — Type “L” doublewall vent  
18 inches — Singlewall vent  
Minimum chimney sizes should be used.  
Oversized chimneys, outside  
masonry chimneys and/or derated  
inputs can result in condensation in chimney.  
5. An induced draft fan for the chimney may be  
necessary if:  
— Excessive resistance to flow of combustion  
gases can be expected.  
— Cross-sectional area of chimney is smaller  
than minimum recommended.  
— Chimney height is less than recommended.  
Seal all vent joints. Interlock burner with  
fan operation.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect Breeching  
CONTINUED  
Typical Location for  
Barometric Control  
(Also see Control  
Manufacturer’s  
Instructions)  
Flue Pipe  
Bracket  
(one on each  
side of pipe)  
Back Outlet Breeching Connection  
FIGURE 6  
Typical Location for  
Barometric Control  
(Also see Control  
Manufacturer’s  
Instructions)  
Flue Pipe Bracket  
(one on each side of pipe)  
Top Outlet Breeching Connection  
FIGURE 7  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect Water Piping  
General piping information:  
DIAPHRAGM expansion tank (FIGURE 8):  
If installation is to comply with ASME or  
Canadian requirements, an additional high  
temperature limit is needed. Install control in  
supply piping between boiler and isolation  
valve. Set control to a minimum of 20°F above  
set point of combination control. Maximum  
allowable set point is 220°F. Wire control as  
shown on wiring diagram.  
Use a low water cutoff device when:  
— Boiler is installed above radiation level.  
— Required by certain state or local codes or  
insurance companies.  
Use low water cutoff designed for water  
installations. Probe-type is recommended.  
Purchase and install in tee in supply line  
above boiler.  
Use backflow check valve in cold water supply  
as required by local codes.  
Make sure expansion tank size will handle  
boiler and system water volume and  
temperature. Tank must be located near boiler  
before inlet to circulator. See tank  
manufacturer’s instructions for details.  
Undersized expansion tanks  
cause system water to be lost  
from relief valve and makeup water added  
through fill valve. Eventual section failure  
can result.  
Install automatic air vent in “N” tapping as  
shown in FIGURE 8.  
CLOSED expansion tank (FIGURE 9):  
Ensure expansion tank size will handle boiler  
and system water volume and temperature.  
Install piping:  
Undersized expansion tanks cause  
system water to be lost from relief  
valve and makeup water added through fill valve.  
Eventual section failure can result.  
See FIGURE 8 or 9 on page 15 and Water  
Piping Size Table at right for near-boiler piping  
and single-zone piping. See page 16 to complete  
multiple-zone piping or page 17 to complete  
piping for systems operating below 140°F.  
Connect tank from “N” tapping shown in  
FIGURE 9 to expansion tank. Use ½" N.P.T.  
piping. Pitch any horizontal piping up towards  
tank 1 inch per 5 feet of piping.  
For multiple-boiler piping, refer to Weil-McLain’s  
“Primary/Secondary Piping Guide” and “M-WGO  
Multiple Boiler Manual.”  
WATER PIPING SIZE TABLE *  
BOILER  
Install relief valve vertically in “R1” tapping on  
front of boiler. See FIGURE 8 or 9 and also  
refer to tag attached to relief valve for  
manufacturer’s instructions.  
MODEL  
TO  
FROM  
NUMBER  
SYSTEM  
SYSTEM  
WGO-2  
WGO-3  
WGO-4  
WGO-5  
WGO-6  
WGO-7  
WGO-8  
1"  
1"  
Pipe relief valve discharge line  
near floor close to floor drain to  
eliminate potential of severe burns. Do not  
pipe to any area where freezing could occur.  
Do not plug, valve or place any obstruction in  
discharge line.  
1¼"  
1¼"  
1½"  
1½"  
1½"  
2"  
1¼"  
1¼"  
1½"  
1½"  
1½"  
2"  
WGO-9  
2"  
2"  
*
All piping sizes based on 20°F  
temperature rise through boiler.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect Water Piping  
CONTINUED  
Isolation  
Valve  
Circulator  
Automatic  
AirVent  
To  
System  
“CTapping  
“NTapping  
Relief  
Valve  
From  
System  
Isolation  
Valve  
Cold Water  
Fill  
To Diaphragm  
ExpansionTank  
and Fittings  
*Circulator  
“B1Tapping  
*Alternate Pump Location  
Piping with DIAPHRAGM Expansion Tank  
FIGURE 8  
Closed Type Expansion Tank  
Circulator  
Cold Water Fill  
IsolationValve  
To System  
“CTapping  
“NTapping  
From  
System  
Relief  
Valve  
Isolation  
Valve  
*Circulator  
“B1Tapping  
*Alternate Pump Location  
Piping with CLOSED Expansion Tank  
FIGURE 9  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect Water Piping  
CONTINUED  
Piping MULTIPLE ZONES:  
1. Follow instructions on page 14 and 15 to install piping near boiler.  
2. See FIGURE 10 or 11 to complete installation  
3. Zoning with circulators:  
a. Size each circulator to individual circuit requirements.  
b. Remove circulator (when furnished as standard equipment).  
c. Install balancing valves to adjust flow to distribute heat to all zones.  
d. Separate relay is required for each circulator.  
4. Zoning with zone valves:  
a. Install balancing valves to adjust flow to distribute heat to all zones.  
b. Separate transformer is required to power zone valves. Refer to “Weil-McLain Zone Valve Wiring  
Guide” for details.  
Legend:  
1
2
3
4
5
Isolation valve  
Flow control valve  
Circulator  
Zone valve  
Drain valve  
ZONE 2  
ZONE 2  
ZONE 1  
ZONE 1  
1
1
1
1
2
4
3
2
1
1
5
5
1
1
5
5
Multiple Zoning With CIRCULATORS  
FIGURE 10  
Multiple Zoning With ZONE VALVES  
FIGURE 11  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect Water Piping  
CONTINUED  
Piping for systems requiring temperatures below 140°F:  
In most systems, this type of piping is not required. If system water temperature requirements are less  
than 140°F, such as radiant panels or converted gravity systems, use piping as shown in FIGURE 12 or  
13. If system piping is plastic without an oxygen barrier, a heat exchanger must be used.  
Legend:  
1
2
3
4
5
6
7
Isolation valve  
Flow control valve  
Circulator  
System temperature gauge  
Zone valve  
Drain valve  
System temperature valves  
Adjust valves so that:  
- the temperature at gauge 8 is at least 140°F  
- the temperature at gauge 9 is at least 160°F  
8
9
Blend temperature gauge  
Boiler temperature gauge  
Piping with CIRCULATORS  
FIGURE 12  
Piping with ZONE VALVES  
FIGURE 13  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect Water Piping  
CONTINUED  
Use with refrigeration systems:  
If boiler is connected to heating coils located in  
air handling units where they can be exposed  
to refrigerated air, use flow control valves or  
other automatic means to prevent gravity  
circulation during cooling cycle.  
Install boiler so that chilled medium is piped in  
parallel with heating boiler. Use appropriate valves  
to prevent chilled medium from entering boiler.  
Consult I=B=R Installation and Piping Guides.  
1
Supply  
Exp.Tank  
1
Circ.  
Circ.  
Chiller  
Strainer  
Exp. Tank  
1
1
2
1
Isolation valve  
Balancing valve  
2
Use with Refrigeration System  
FIGURE 14  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect Wiring  
General wiring requirements:  
Junction box (furnished):  
Junction box houses electrical connections for  
all boiler components.  
Electric shock hazard. Can cause  
“P” boilers have harnesses furnished.  
“A” boilers are furnished with burner and limit  
harnesses.  
severe personal injury or death if  
power source, including service switch on boiler, is  
not disconnected before installing or servicing.  
All field-provided high voltage wiring must be  
sheathed in flexible metal conduit.  
Connect incoming line voltage “HOT” wire to  
service switch, and neutral wire to white wire.  
Field-install equipment ground wire to green  
wire with wire nut.  
Installations must follow these codes:  
— National Electrical Code, ANSI/NFPA 70,  
latest edition and any additional national,  
state or local codes.  
— In Canada, CSA C22.1 Canadian Electrical  
Code Part 1 and any local codes.  
Service switch (15 amp) is provided with boiler.  
“A” boilers — install switch as shown.  
Some local codes may require an emergency  
shut-off switch installed at a location away  
from boiler. Follow local codes.  
Wiring must be N.E.C. Class 1. If original wire  
as supplied with boiler must be replaced, type  
105°C wire or equivalent must be used. Supply  
wiring to boiler and additional control wiring  
must be 14 ga. or heavier.  
Burner wiring:  
Provide electrical ground at boiler as required  
by codes.  
Burner harness incorporates a disconnect  
plug, providing a convenient way to disconnect  
wiring when burner mounting door is opened.  
All “P” boilers have a power disconnect plug  
installed on burner.  
On “A” boilers, mount the plug (provided in  
water trim carton) on the burner housing as  
shown in FIGURE 15. For Carlin burners, screw  
burner plug into threaded conduit coupling,  
then mount this assembly to the burner housing  
using the chase nipple. Route wires through  
housing and make connections in burner  
junction box as shown in boiler wiring diagram.  
Thermostat wiring:  
Install thermostat on inside wall away from  
influences of drafts, hot or cold water pipes,  
lighting fixtures, television, sun rays or fireplaces.  
Follow instructions with thermostat. If it has a  
heat anticipator, set heat anticipator in  
thermostat to match power requirements of  
equipment connected to it. Boiler wiring  
diagrams give setting for standard equipment.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect Wiring  
CONTINUED  
Limit Control  
Wiring Harness  
Circulator Wiring  
Harness  
(Not Furnished  
on “A” Boilers)  
Service Switch  
On Boiler  
Burner Wiring  
Harness  
Burner  
Disconnect Plug  
Boiler Wiring for Forced Hot Water  
FIGURE 15  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect Wiring  
CONTINUED  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect Oil Piping  
Do not use Teflon tape as an oil  
pipe sealant. It can cause valves  
to fail, creating hazards. Do not use  
General oil piping requirements:  
Location and installation of oil tanks, oil piping  
and burners must follow:  
compression fittings.  
— NFPA 31, Standard for the Installation of  
Oil-Burning Equipment.  
— In Canada, CSA B139, Installation of  
Oil-Burning Equipment.  
Underground pipe must be run in a casing to  
prevent oil leaking into ground or under floor.  
Check local codes for information.  
— Local codes and regulations.  
— Information provided with burner and  
fuel pump.  
Oil piping connection at burner:  
See FIGURE 16 for recommended connection at  
burner, allowing burner mounting door to swing  
open completely for servicing.  
If any part of fuel oil tank is above level of  
burner, an anti-siphon device must be used to  
prevent flow of oil in case of oil line break.  
Support oil lines as required by codes.  
Make tank connections with swing joints or  
copper tubing to prevent breaking in case the  
tank settles. Make swing joints so they will  
tighten as tank settles. Non-hardening pipe joint  
compounds should be used on all threads.  
Recommended Oil Piping Connection to Burner  
FIGURE 16  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up  
Follow information below to  
prevent severe personal injury,  
death or substantial property damage:  
When using antifreeze:  
Do not use automotive, ethylene  
Do not use gasoline crankcase drainings or  
any oil containing gasoline. See burner manual  
for proper fuel oil.  
Do not attempt to start burner when excess oil  
has accumulated, when unit is full of vapor or  
when combustion chamber is very hot.  
Do not start burner unless collector hood, flue  
cap, jacket cap, breeching and burner  
mounting door are secured in place.  
glycol, undiluted or petroleum-  
based antifreeze. Severe personal injury, death  
or substantial property damage can result.  
— Use antifreeze especially made for  
hydronic systems. Inhibited propylene  
glycol is recommended.  
— 50% solution provides protection to  
about -30°F. Do not exceed 50% mixture.  
— Local codes may require back-flow  
preventer or actual disconnect from city  
water supply.  
— Determine quantity according to system  
water content. Boiler water content is listed  
on back cover of manual. Percent of solution  
will affect sizing of heat distribution units,  
circulator and expansion tank.  
Never burn garbage or paper in the boiler.  
Never leave combustible material around it.  
Fill the system:  
1. Close manual and automatic air vents and  
boiler drain cock.  
2. Fill to correct system pressure. Correct  
pressure will vary with each installation.  
Normal cold water fill pressure for residential  
systems is 12 psig. Boiler water pH 7.0 to 8.5  
is recommended.  
— Follow antifreeze manufacturer’s instructions.  
To place in operation:  
1. Verify boiler is filled with water.  
2. Open burner mounting door and verify rear  
target wall, floor and burner door insulations  
are in proper position.  
Failure to maintain  
recommended pH level can  
cause section failure and leaks.  
3. Verify burner mounting door is closed tightly  
and burner wiring harness is connected to  
junction box.  
3. Open automatic air vent one turn.  
4. Open other vents.  
a. Starting on the lowest floor, open air vents  
one at a time until water squirts out.  
Close vent.  
4. Factory burner adjustment and settings may not  
be suitable for specific job conditions. See  
Appendix, page 25.  
b. Repeat with remaining vents.  
5. Refill to correct pressure.  
Make final burner adjustments  
using combustion test  
equipment to assure proper operation. Do not  
fire boiler without water. Sections will  
overheat, damaging boiler and resulting in  
substantial property damage.  
Tips for water systems:  
Check boiler and system piping for leaks.  
Continual makeup water will reduce boiler life.  
Minerals can build up in sections, reducing  
heat transfer and causing cast iron to  
overheat, resulting in section failure.  
5. Vent air from system. Repeat steps 4 and 5  
under “Fill the system.” Air in system can  
interfere with water circulation and cause  
improper heat distribution.  
Failure to maintain  
recommended pH and repair  
leaks can cause section iron corrosion, leading  
to section failure and leaks. Do not use  
petroleum-based sealing or stop-leak  
compounds in boiler systems. Damage to  
system components can result.  
6. Check boiler and system piping for leaks. See  
“Tips for water systems.”  
7. Inspect breeching and venting for proper operation.  
For pH conditions outside 7.0 to 8.5 range or  
unusually hard water areas (above 7 grains  
hardness), consult local water treatment company.  
23  
For additional information, refer to instructions packed with boiler or burner:  
Burner Manual  
Maintenance and Service Guide for GOLD Oil Water Boilers  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check-Out Procedure  
Check off steps as completed:  
J 8. Test additional field-installed controls: If  
boiler has a low water cutoff, additional  
high limit or other controls, test for  
J 1. Boiler and heat distribution units filled  
with water?  
operation as outlined by manufacturer.  
Burner should be operating and should go  
off when controls are tested. When controls  
are restored, burner should re-ignite.  
J 2. Automatic air vent, if used, opened one  
full turn?  
J 3. Air purged from system? Piping checked  
J 9. Limit control set to system temperature  
for leaks?  
requirements (max. 220°F)?  
J 4. Air purged from oil piping? Piping checked  
J 10. For multiple zones, flow adjusted to  
for leaks?  
distribute heat in all zones?  
J 5. Flue cap in place and tightened? Burner  
door closed, sealed and nut tight? Burner  
plugged in and service switch on?  
J 11. Thermostat heat anticipator setting (if  
available) set properly? Refer to “Connect  
wiring,” page 19.  
Obtain gas-tight seal to  
prevent possible flue gas  
leakage and carbon monoxide emissions,  
leading to severe personal injury or death.  
J 12. Boiler cycled with thermostat? Raise to  
highest setting and verify boiler goes  
through normal start-up cycle. Lower to  
lowest setting and verify boiler goes off.  
J 6. Proper draft and burner flame? Final  
adjustment made with combustion  
test equipment?  
J 13. Observed several operating cycles for  
proper operation?  
J 14. Set room thermostat(s) to desired  
J 7. Test limit control: While burner is  
operating, move indicator on limit control  
below actual boiler water temperature.  
Burner should go off while circulator  
continues to operate. Raise setting on limit  
control above water temperature and  
burner should re-ignite.  
room temperature?  
J 15. Completed Installation and Service  
Certificate below?  
J 16. Reviewed Maintenance and Service Manual  
with owner or maintenance person and  
instructed person to keep for future reference?  
J 17. Returned all instructions provided with  
boiler to its envelope and placed with boiler  
for future reference?  
Installation and Service Certificate  
Date Installed: ______________________________________________  
Boiler Model Number: __________________ Series: _________  
CP Number(s):______________________________________________  
Measured Btu or GPH Input: _____________________________  
J Installation instructions have been followed.  
J Check-out procedure has been performed.  
J Above information is certified to be correct.  
J Information received and left with owner/  
maintenance person.  
Installer:__________________________________________________________________________________________________________________________  
(Company) (Address) (Phone)  
_________________________________________________________________  
24  
(Installer’s Signature)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Burner adjustments for “P” and “A” boilers:  
To connect WGO boilers to Weil-McLain  
PLUS indirect-fired water heaters:  
Install and wire per water heater manual provided  
with water heater.  
Final burner adjustments must be  
made using combustion test  
equipment to assure proper operation. Do not fire  
boiler without water or sections will overheat.  
1. Refer to burner manual for start-up.  
2. Allow boiler to heat to design condition.  
3. Using combustion test equipment, adjust  
burner for:  
a. CO2 between 11% and 12% and 0 smoke.  
b. -0.01" to -0.02" W.C. draft in  
combustion chamber.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
CONTINUED  
To provide close clearances as described in pages 26 and 27, Close Clearance Kit,  
W-M Part No. 386-500-050, must be obtained and installed as described below. Failure to  
use kit or install as described can result in a fire hazard, causing severe personal injury, death or  
substantial property damage.  
Close clearance installation:  
1. Install boiler using clearances described at left.  
2. Install barometric control 18-20 inches from  
boiler in breeching.  
Substitute these instructions for corresponding  
material in manual. All other procedures and  
practices must remain the same.  
3. Attach manual reset temperature switch near  
upper surface of enclosed area. See FIGURE 17.  
4. Wire switch in series with thermostat. See  
FIGURE 18.  
Recommended service and minimum clearances  
shown on page 4 should be used where possible.  
Where closer clearances are required:  
5. Provide two combustion/ventilation openings  
when installing in confined space. Size opening  
140 sq. in. (1000 Btu) per 1 GPH input. Locate  
openings near top and bottom of enclosed space.  
Top of boiler — If less than 24" available,  
provide removable surface to allow for cleaning  
boiler flueways.  
Right or left side — Minimum 2 inches.  
Front — Minimum 2 inches from burner.  
Doublewall flue pipe to combustible surface —  
as listed in Table on page 27 and FIGURES 19  
through 21.  
Jacket cap must be in place on  
boiler to avoid requiring an 18"  
minimum clearance from back or top of boiler to  
combustible material. Flue pipe clearances must  
take precedence over jacket clearances.  
Combustible  
Surface  
Manual Reset  
Temperature Switch  
#6 x ½" Phil.  
Sht. Mtl. Screw  
44156  
1 to 5  
inches  
Thermostat  
#10 x ½" Phil.  
Sht. Mtl. Screw  
Manual  
Bracket  
Reset  
Temperature  
Switch  
Area Above Boiler  
Manual Reset Temperature Switch Location  
FIGURE 17  
Manual Reset Temperature Switch Wiring  
FIGURE 18  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
CONTINUED  
PROTECTION REQUIRED FOR CLEARANCES LESS  
THAN 6 INCHES FROM DOUBLEWALL VENT PIPE*  
DIMENSION A  
When desired minimum  
clearance from type “L”  
doublewall vent pipe to  
combustible surface is:  
Use the following  
protection**:  
Combustible Surface  
A
½" thick insulation board ***  
over one-inch glass fiber or  
mineral wool batts+  
3"  
24 gauge sheet metal with  
one-inch ventilated air space  
6"  
6"  
2"  
3"  
Protection  
Type “L” Doublewall  
Vent Piping  
½" thick insulation board ***  
with one-inch ventilated air space  
*
All clearances measured from outer surface of equipment to combustible  
surface, not to the protection used.  
Flue Pipe Clearances  
FIGURE 19  
** Apply to combustible surface unless otherwise noted. Cover all surfaces as  
specified in Table and FIGURE 19. Thicknesses are minimum.  
*** Factory-fabricated board made of non-combustible materials, normally fibers,  
having thermal conductivity in range of one (Btu-inch)/(hr./sq. ft./°F) or less.  
+
Mineral wool batts (blanket or board), having min. density of 8 lb/ft3 and a min.  
melting point of 1500°F.  
OTHER DIMENSIONS AVAILABLE. REFER TO NFPA-31.  
A
A
24" For Servicing  
or Min. 2" for Close  
Clearances  
A
Combustible  
Surface  
24" For Servicing  
or Min. 2" for Close  
Clearances  
A
Combustible  
Surface  
2"  
Combustible  
Surface  
Combustible  
Surface  
2"  
2"  
NOTE: 2" Min. on Sides  
NOTE: 2" Min. on Sides  
Back Vent Clearances  
FIGURE 20  
Top Vent Clearances  
FIGURE 21  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Parts List  
Repair parts must be purchased through Weil-McLain for the specific boiler as  
indicated in the list below. Results from using modified or other manufactured  
parts will not be covered by warranty and may damage boiler or impair operation.  
Fig.  
No.  
A
B
B
C
D
E
W-M Sales  
Description  
Regular Front Section 7012  
Wide Intermediate Section (WGO-3) 7010  
Regular Intermediate Section 7015  
Part Number  
316-700-250  
316-700-075  
316-700-065  
316-700-070  
316-700-265  
386-700-852  
Intermediate Section w/Draw Rod Lugs 7016  
Back Section w/7" Flue, Supply & 2" Return 7017  
Section Replacement Kit (For 1 Joint, includes Seals, Rope,Adhesive and  
Collector Hood Hardware) Front or Back Section  
Section Replacement Kit (For 2 Joints, includes Seals, Rope and Adhesive) Intermediate Section  
Section Assembly Complete, For WGO-2  
Section Assembly Complete, For WGO-3  
Section Assembly Complete, For WGO-4  
Section Assembly Complete, For WGO-5  
Section Assembly Complete, For WGO-6  
Section Assembly Complete, For WGO-7  
Section Assembly Complete, For WGO-8  
Section Assembly Complete, For WGO-9  
Collector Hood Kit For WGO-2*  
Collector Hood Kit For WGO-3*  
Collector Hood Kit For WGO-4*  
Collector Hood Kit For WGO-5*  
Collector Hood Kit For WGO-6*  
Collector Hood Kit For WGO-7*  
Collector Hood Kit For WGO-8*  
386-700-851  
386-700-650  
386-700-651  
386-700-652  
386-700-653  
386-700-654  
386-700-655  
386-700-656  
386-700-657  
386-700-336  
386-700-337  
386-700-337  
386-700-338  
386-700-339  
450-020-170  
450-020-172  
450-020-160  
560-234-464  
560-234-491  
560-234-492  
560-234-470  
560-234-495  
560-234-472  
560-234-534  
560-234-538  
560-234-542  
560-234-497  
386-700-355  
386-700-358  
330-054-302  
330-054-300  
386-700-359  
591-222-115  
460-039-867  
590-735-105  
590-735-109  
F
F
F
F
F
F
F
F
G
G
G
G
G
G
G
G
G
G
H
Collector Hood Kit For WGO-9*  
Tie Rod 1/2 x 51/2 (WGO-7, 8, 9)  
Tie Rod 1/2 x 103/4 (WGO-2 & 7)  
Tie Rod 1/2 x 12 (WGO-7)  
Tie Rod 1/2 x 14 (WGO-3, 4, 8, 9)  
Tie Rod 1/2 x 15 (WGO-9)  
Tie Rod 1/2 x 17 (WGO-5)  
Tie Rod 1/2 x 20 (WGO-6)  
Tie Rod 1/2 x 231/4 (WGO-7)  
Tie Rod 1/2 x 263/8 (WGO-8)  
Tie Rod 1/2 x 291/2 (WGO-9)  
Combustion Chamber Kit (Rear & Frt. Ref., Door Ref. Blanket, Rope, Blanket & Water Glass)  
Burner Mounting Door Assembly (Door, Obs. Port, Rope, Ins. & Pins)  
Burner Mounting Door 7070  
Door Hinge 7054  
Door Refractory  
J
K
L
M
N
P
Door Refractory Blanket  
Observation Port Shutter  
Door Seal Rope 5'  
3
Q
/8" Glass Rope For Collector Hood (7' For Largest Size Hood)  
R
Flue Cap Assembly (Cap, Strap, Rope & Screws)  
Flue Brush 123D  
386-700-344  
591-706-214  
* Includes flue cap assembly, rope and hardware for installation.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Parts Drawing  
R
D
E
F
Q
G
B
A
K
H
G
H
H
H
J
N
G
C
L
M
P
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
1
20 /4 [514.4]  
3
1
7 /4  
5 /16 [128.6]  
[196.9]  
9
2 /16 [65.1]  
Supply  
DIMENSIONS - in.  
Air Vent or  
Expansion Tank  
BOILER  
MODEL  
NUMBER  
B
L
WGO-2  
101/2  
133/4  
5
35 /8  
[904.9]  
WGO-3  
WGO-4  
WGO-5  
WGO-6  
WGO-7  
WGO-8  
WGO-9  
131/2  
135/8  
167/8  
20  
167/8  
167/8  
20  
43/8 DIA [111.1]  
Burner Opening  
Return  
231/8  
261/4  
293¼8  
321/2  
231/8  
261/4  
293/8  
91/2 [241.3]  
7
2 /16  
[61.9]  
1
1 /8 [28.6]  
7
2 /16 [61.9]  
WGO Front  
3
7 /16  
[182.6]  
DIMENSIONS - mm.  
5
2 /8  
[66.7]  
BOILER  
MODEL  
NUMBER  
7 DIA  
[177.8]  
B
L
WGO-2  
WGO-3  
WGO-4  
WGO-5  
WGO-6  
WGO-7  
WGO-8  
WGO-9  
266.7  
342.9  
345.9  
428.7  
508  
349.2  
428.7  
428.7  
508.0  
587.2  
666.7  
746.2  
825.5  
B
1
587.2  
666.7  
746.2  
15 /2  
[393.7]  
14  
Approx.  
L
WGO Side with Burner  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
CONTINUED  
Intermediate  
7 DIA.  
[177.8]  
1
6 /4  
[158.8]  
For 7 DIA. [177.8]  
Vent Pipe  
9
Alternate Return  
(“A” Boilers Only)  
29 /16  
[750.9]  
Back  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ratings  
WGO GOLD OIL WATER BOILER RATINGS (1)  
ROUND  
FLUE  
OUTLET  
SIZE CONTENT BOILER  
IN (7)  
DRAFT  
LOSS  
THRU  
I=B=R  
BURNER  
CAPACITY  
GPH (3)  
NET  
I=B=R  
RATINGS  
(5)  
DOE  
SEASONAL  
EFFICIENCY %  
AFUE  
MINIMUM  
I=B=R CHIMNEY  
BOILER  
WATER  
BOILER  
MODEL  
NUMBER  
DOE HEATING  
CAPACITY (4)  
MBH (2)  
RECT  
ROUND HEIGHT  
IN  
IN  
FT  
GAL  
IN W.C. (8)  
*-WGO-2  
*-WGO-3  
*-WGO-4  
*-WGO-5  
*-WGO-6  
**-WGO-7  
**-WGO-8  
**-WGO-9  
0.70  
0.95  
1.20  
1.45  
1.75  
2.00  
2.30  
2.55  
86  
75  
86.4  
85.3  
85.0  
85.0  
85.0  
85.0  
8 x 8  
8 x 8  
8 x 8  
8 x 8  
8 x 8  
8 x 8  
8 x 12  
8 x 12  
6
6
6
7
7
8
8
8
15  
15  
15  
15  
15  
15  
20  
20  
7
7
7
7
7
7
7
7
11.0  
14.9  
13.4  
15.9  
18.4  
20.8  
23.3  
25.8  
.010  
.020  
.010  
.015  
.015  
.015  
.025  
.030  
115  
100  
126  
152  
184  
210  
231  
257  
145  
175  
212  
242  
266 (6)  
295 (6)  
*
Substitute “P” for completely assembled packaged boiler without burner (WGO-2 through WGO-6 only).  
Substitute “A” for boiler only for use with approved burners as listed with I-B=R.  
* * Available only as an “A” unit.  
(1) WGO boiler designed with convertible vertical and horizontal flue outlet.  
(2) MBH refers to thousands of Btu per hour.  
(3) Based on 140,000 Btu/gal.  
(4) Based on standard test procedures prescribed by the United States Department of Energy at combustion condition of 13.5% CO2 and -0.02" W.C. draft  
overfire.  
(5) Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal  
piping and pick-up. Water ratings are based on a piping and pick-up allowance of 1.15. An additional allowance should be made for unusual piping and  
pick-up loads. Consult local Weil-McLain Sales Office.  
(6) I=B=R gross output  
(7) See page 12 for minimum breeching diameter.  
(8) Listed draft losses are for factory-shipped settings.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Weed Eater Trimmer 545137271 User Manual
Weider Fitness Equipment 831159480 User Manual
Westinghouse Power Hammer AK 1 50 9 User Manual
Whirlpool Dishwasher DU1055XTSB1 User Manual
Whirlpool Ventilation Hood 99044504A User Manual
White Outdoor Snow Blower Single Stage Snow Thrower User Manual
White Rodgers Thermostat 1F57 312 User Manual
Windsor Carpet Cleaner QTFSD User Manual
Winegard Satellite TV System MV 0500 User Manual
Xerox Printer 4635 IPS User Manual