| 	
		 MODELS   
					P250AF   
					P265   
					P250AF-EP   
					P265F   
					P250AF-DI   
					P265-EP   
					P265-EP   
					WAYNE COMBUSTION SYSTEMS   
					801 GLASGOW AVE.   
					GAS BURNER   
					Publication Date 5/01   
					NOTE: Dimensions in ( ) are informational only. English values take priority.   
					- 
					Revision B   
					- 
					Manual 101220   
					FORT WAYNE, IN 46803   
					FOR YOUR SAFETY   
					WARNING: If the information in these   
					instructions is not followed exactly, a fire or   
					explosion may result causing property   
					damage, personal injury or death.   
					IF YOU SMELL GAS:   
					1. OPEN WINDOWS   
					2. DON’T TOUCH ELECTRICAL SWITCHES   
					3. EXTINGUISH ANY OPEN FLAME   
					4. IMMEDIATELY CALL YOUR GAS   
					SUPPLIER.   
					- 
					- 
					Do not store or use gasoline or other flammable vapors   
					and liquids in the vicinity of this or any other appliance.   
					WHAT TO DO IF YOU SMELL GAS   
					• Do not try to light the appliance.   
					• Do not touch any electrical switch; do not use any   
					phone in your building.   
					• Immediately call your gas supplier from a neighbor’s   
					phone. Follow the gas supplier’s instructions.   
					• If you cannot reach your gas supplier, call the fire   
					department.   
					CARBON MONOXIDE   
					POISONING HAZARD   
					CARBON MONOXIDE IS A COLORLESS, ODORLESS GAS   
					THAT CAN KILL. FOLLOW THESE RULES TO CONTROL   
					CARBON MONOXIDE.   
					- 
					Installation and service must be performed by a qualified   
					installer, service agency or the gas supplier. Warranty is   
					voided if not installed by qualified service person.   
					L Do not use this burner if in an unvented, enclosed area. Carbon   
					monoxide may accumulate.   
					L Do not adjust the pressure regulator. High pressures produce   
					carbon monoxide.   
					L Check flue gases for carbon monoxide. This check requires   
					specialized equipment.   
					L Allow only qualified burner service persons to adjust the burner.   
					Special instruments and training are required.   
					L Read the owner’s manual before using.   
					ELECTRIC SHOCK HAZARD   
					HIGH VOLTAGES ARE PRESENT IN THIS EQUIPMENT.   
					FOLLOW THESE RULES TO AVOID ELECTRIC SHOCK.   
					L Use only a properly grounded circuit. A ground fault   
					interrupter is recommended.   
					OVERHEATING HAZARD   
					L Do not spray water directly on burner.   
					L Turn off power before servicing.   
					SHOULD OVERHEATING OCCUR:   
					L Shut off the manual gas valve to the appliance.   
					L Do not shut off the control switch to the pump or blower.   
					L Read the owner’s manual before using.   
					THESE INSTRUCTIONS SHOULD BE AFFIXED TO THE   
					BURNER OR ADJACENT TO THE HEATING APPLIANCE.   
					NOTICE   
					SPECIFICATIONS   
					BURNER MODELS   
					MINIMUM INPUT   
					MAXIMUM INPUT   
					FUELS   
					P-250AF & P-250AF-EP & P250AF-DI   
					P-265 & P-265-EP   
					50,000 BTU/HR (14.65 kW/Hr)   
					65,000 BTU/HR (19.05 kW/Hr)   
					65,000 BTU/HR (19.05 kW/Hr)   
					250,000 BTU/Hr (73.27 kW/Hr) Natural & L.P. Gas   
					200,000 BTU/Hr (58.61 kW/Hr) Natural & L.P. Gas   
					200,000 BTU/Hr (58.61 kW/Hr) Natural & L.P. Gas   
					MOUNTING: Adjustable Flange is Standard   
					Pedestal Mount is Optional.   
					P-265-F & P-265F-EP   
					ELECTRICAL Power Supply - 115V/60HZ 1 Ph.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				FLUE PIPE AND CHIMNEY   
					The flue pipe should be carefully inspected and replaced if necessary in connection with installation of a draft hood. All   
					installations must operate with a negative draft overfire. Refer to your local gas company or codes for assistance or to the   
					furnace and/or boiler manufacturer for recommendations.   
					The flue pipe entrance into the chimney should be at least two feet (.610m) above the clean-out opening in the chimney.   
					The chimney should extend high enough above the dwelling or other neighboring obstructions so that wind from any direction   
					will not strike the chimney from any angle above horizontal. Unless the obstruction is of greater magnitude, it is the usual   
					experience that a chimney extending two feet above flat roofs or above fire wall parapets, and peaked roofs within 30 feet   
					(9.144m) will be reasonably free of downdraft.   
					Where the chimney is unlined or where local experience indicates that flue gas condensate might be a problem, the local gas   
					company should be consulted.   
					The chimney should be examined and thoroughly cleaned, if necessary, before installation is made to make sure it freely   
					conduct the flue gases to the outside.   
					Flue pipe should extend through the chimney wall to inner face of chimney liner but not beyond, and should be firmly   
					cemented to masonry. A thimble may be used to facilitate removal of flue pipe for cleaning, in which event the thimble should be   
					permanently cemented in place with mortar or other fireproof material that will not crack or check the flue pipe or thimble,   
					whichever is used, should be sealed into the chimney liner.   
					Flue connections from two or more appliances should not enter opposing or adjacent sides of the chimney at the same level.   
					Under no circumstances should the flue pipe be connected it to a flue of an open fireplace.   
					INSPECTION OF HEATING APPLIANCE   
					A careful inspection of furnace or boiler should be made. If cracked heating sections, leaking soft plugs or any other   
					condition which might make the unit unsatisfactory for gas conversion is found, proper arrangements should be made for   
					replacement or repair before proceeding with the burner installation. Cracked heating sections should be replaced.   
					A neutral pressure point adjuster, similar to the one shown in figure 2 may be installed in the flue pipe between the furnace   
					and a conventional type CSA draft hood. The neutral pressure point adjustment should be left in the fully open position until   
					after the burner rating has been established. The material used for flue pipe should be resistant to corrosion.   
					The necessity for installing a neutral pressure point adjuster as outlined above, may be eliminated by reducing the flue pipe   
					and draft hood to the sizes shown in the table.   
					NOTE: For oil fired conversions consult boiler or furnace manufacturer. Appliance must maintain negative draft overfire.   
					NOTE: Ducts used for make-up   
					air may be connected to the   
					cold air return of the heat-   
					Air Inet Opening 1 Sq.   
					ing system only if they connect   
					in. (645.2 mm2) for each   
					directly to outdoor air.   
					1,000 Btu (.2931 kW)   
					per hour input.   
					Attic Ventilation Louvers are   
					required at each end of attic   
					with alternate air inlet No. 1.   
					1, 2, and 3 mark alternate loca-   
					tions for air from outdoors. Free   
					area shall be not less than 1 Sq.   
					in. (645.2 mm2) per 5,000 Btu   
					(.1.465 kW) per hour of the total   
					per hour of the total input rating   
					of all appliances in the   
					enclosure.   
					Crawl-space Ventilation Louvers   
					for unheated crawl space   
					are required with alternate air   
					inlet No. 3.   
					Each Ventilation Air Opening   
					from inside the building shall   
					have a free area of not less than   
					1 Sq. in. (645.2 mm2) per 5,000   
					Btu (.1.465 kW) per hour of the   
					total per hour of the total input   
					rating of all appliances in the   
					enclosure.   
					Ventilating Air Opening   
					1 Sq. in. (645.2 mm2)   
					for each 1,000 Btu   
					(.2931 kW) per hour   
					input.   
					Application located in confined spaces. Ventilation air   
					from inside building combustion and draft hood   
					- 
					dilution air from outside. Ventilated attic or ventilated   
					craw space.   
					Illustration showing air opening necessary to supply air for combustion   
					when heating appliance is installed in an enclosed room.   
					FIGURE 1   
					2 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				1/2” (12.7 mm)   
					FIGURE 2   
					FIGURE 3   
					Minimum rise 1/4” (6.35   
					mm) to the foot (.305 m)   
					Minimum rise 1/4” (6.35   
					mm) to the foot (.305 m)   
					Minimum rise 1/4” (6.35   
					mm) to the foot (.305 m)   
					90˚ (1.57 rad) ANGLE TYPE DRAFT HOOD   
					(Always install in a vertical position)   
					FIGURE 4   
					3 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				PREPARATION OF FURNACE OR BOILER   
					Clean combustion chamber thoroughly. Scrape and brush all heating surfaces and flue ways. Soot and fly ash are excellent   
					insulators and unless removed the efficiency of the heating plant will be impaired. Plugged or restricted flue passages will   
					prevent burner from operating properly.   
					Be sure water column and gauge on boiler is clean and water level is visible. In all cases make sure the pigtail to limit control   
					is clear. Safety pop valves on team boilers and automatic relief valves on closed water systems should be thoroughly checked   
					to make sure they are in good working condition.   
					FLUE PIPE AND DRAFT HOOD   
					A CSA type draft hood or its equivalent shall be placed in and made part of the flue pipe from the appliance. At no time   
					should the draft hood be located at a point lower than the highest flue passage in the appliance. The draft hood should be   
					installed in the position for which it was designed and in no case installed in a false ceiling, separate room from the heating   
					appliance, or in any other manner that will permit a difference in pressure between the draft hood relief opening and the   
					combustion air supply. On sealed type appliances where all combustion air is taken from the outside, a cap should be installed   
					on end of flue pipe to prevent back drafts. In such cases no draft hood or diverter should be installed inside. See Figure 4.   
					When converting oil fire appliances the flue pipe and draft hood or diverter used should be the same size as the furnace flue   
					collar. It is recommended that a rise as great as possible or at least 1/4 inch (6.35mm) to the foot (.305m) (horizontal length) be   
					maintained in the flue pipe from the appliance to the chimney. The flue pipe should be relocated where possible to avoid sharp   
					turns.   
					DRAFT HOOD & FLUE PIPE SIZES FOR GAS CONVERSION   
					BURNERS IN UP-DRAFT COAL FURNACES ND BOILERS   
					Not more than 6,500 BTU (1.905 kW) per inch (645.2 mm2) of the flue area   
					Input - BTU (kW)   
					Per Hour   
					Draft Hood and   
					Flue Pipe Size   
					Up to --- 120,000 (35.17)   
					5 inch (127mm)   
					6 inch (152.4mm)   
					7 inch (177.8mm)   
					120,000 (35.17) --- 180,000 (52.75)   
					180,000 (52.75) --- 250,000 (73.27)   
					NOTE: If the flue pipe exceeds 10 ft. (3.048m) in length, or contains more than two elbows, use next size larger pipe and   
					draft hood.   
					NO MOVEABLE FLUE PIPE DAMPER SHOULD BE USED ON ANY INSTALLATION.   
					NOTE: All installations must operate with negative draft overfire. Refer to your local gas company and codes for assistance.   
					REVERTIBLE FLUE (DOWN DRAFT OR DIVING FLUE TYPE) FURNACES OR BOILERS   
					When installing the burner in the above type furnaces or boilers, the draft hood (or draft diverter) should be located at least   
					one foot higher than the top of the highest point of the appliance flue passage or combustion chamber. It is also recommended   
					that a vent pipe, not less than one inch in diameter, be provided from the highest point in the flue passage, directly to the flue   
					pipe. This is not necessary on the appliances with built in up draft bypass. (See Figure 3.) The gas company serving the area   
					should be consulted in regards to their recommendations for converting this type of furnace or boiler.   
					The flue pipe should be securely supported and the joints fastened with sheet metal screws or riveted to prevent sagging,   
					and in no case should be located in a manner that will present a hazard to combustible building material. (Refer to local building   
					code.)   
					PREPARATION OF COMBUSTION CHAMBER   
					THE POWER GAS BURNER IS DESIGNED FOR “INSHOT” FIRING INTO A REFACTORY LINED COMBUSTION   
					CHAMBER CONSTRUCTED IN THE ASH PIT OF ANY BOILER OR FURNACE ORIGINALLY DESIGNED FOR COAL OR OIL   
					FIRING. THE SIZE, SHAPE AND CONSTRUCTION OF THE CHAMBER SHOULD BE GIVEN SUCH CONSIDERATION AS   
					WILL RESULT IN THE MAXIMUM EFFICIENCY OF EACH INSTALLATION.   
					On smaller inputs precast chambers may be used if the firing door and ash pit are large enough to insert the chambers and   
					assemble.   
					When converting oil designed boilers and furnaces, it is recommended that the same combustion chamber be used with the   
					gas burner. If the blast tube opening into the combustion chamber is larger than the 4” (101.6mm) diameter, high temperature   
					cement should be used to reduce the opening to 4” (101.6mm) diameter.   
					IN NO CASE SHOULD THE TUBE BE ALLOWED TO EXTEND INTO THE CHAMBER PROPER. IT MUST BE AT LEAST   
					1/8” (3.175mm) SHORT OF THE INSIDE SURFACE OF THE COMBUSTION CHAMBER.   
					4 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				COMBUSTION CHAMBERS   
					The combustion chamber sizes given in Figure 5 are based on the maximum rated BTU capacity. If the input is to be   
					permanently set at a reduced rate, the combustion chamber floor area can be reduced proportionately to the proposed input,   
					allowing 200,000 BTU (211000kJ) per square foot (.093m2) of combustion chamber floor area and proportioning the length about   
					70% greater than the width.   
					The height of the walls of the combustion chamber is generally determined by the grate line. The side and front walls should   
					be built about 2” (50.8mm) above the grate line, covering the grate lugs and covering the bases of the water legs of boilers   
					about 3” (76.2mm) or 4” (101.6mm) to avoid heating sections that may be filled with sediment. The back wall should be carried   
					one or two courses higher and overhung to deflect hot gases from direct impingement on the rear heat exchanger surfaces.   
					Hard firebrick should be used for the overhung section to prevent erosion of the brick at this point by the high velocity gases   
					m9moving over it.   
					The remaining open spaces between the combustion chamber and ash pit walls should be filled with loose insulation. Since   
					this insulation may not stand combustion chamber temperatures, the top course of the combustion chamber walls be laid flat,   
					extending to, and fitting the contour of the firebox and covering the loose insulation.   
					Always use cement furnished by the brick manufacturer for cementing insulating firebrick. It should be thinned to the   
					consistency of a very thick cream so that the brick can be dipped into it and set in place. The use of other cement or mortar   
					may impair the insulating and radiating qualities of the brick.   
					Magnesia block insulation, common brick, hard fire brick, dry sand and/or expanded mica products such a “Vermiculite” or   
					“Zonolite” can be used to back up the insulating firebrick. High temperature furnace cement can be used to seal the openings   
					around the burner and furnace.   
					Approved insulating bricks are: Babcock & Wilcox No. K-23 and No. K-26, A. P. Grenn No. G-23 and No. G-26, Armstrong   
					Cork No. A-23 and No. A-26 an Johns Manville No. JM-23 and No. JM-26.   
					INSTALLATION OF BURNER AND CONTROLS   
					The inshot power gas burner was designed especially for converting gun fired oil designed furnaces and boilers. Due   
					consideration was given to making it as simple and easy to install and service as possible without weakening its durability or   
					efficiency. The burner is supplied as a completely assembled package unit.   
					NOTE: The burner must be installed in such a manner that they unit and all controls will be readily accessible for inspection,   
					cleaning, adjustment and repairs.   
					SIZING OF INPUT IN RELATION TO FURNACE   
					FIGURE 140,000 BTUs (147700KJ) per gal. of oil input. For example: Furnace rating 0.60 G.P.H. then 0.60 x 140,000 =   
					72,000 BTUs input rate   
					The orifice spud supplied with all burners is the size for the minimum BTU input of the burner for the type gas shown on the   
					rating plate. Figure 6 shows the correct drill size for various inputs.   
					The correct manifold pressure for natural gas is 3.5” w.c(871.8 Pa). Only minor adjustments in the input rate should be made   
					by adjusting the pressure regulator. The minimum manifold pressure should be 3.0” w.c. (747.2Pa) and the maximum pressure   
					should be 3.5 w.c. (871.8 Pa) the next size larger or smaller orifice size should be used if the desired input rating cannot be   
					obtained within the above manifold pressure adjustment range.   
					The correct manifold pressure for L.P. gas is 10” w.c. (2491Pa), only minor adjustments in the input rate should be made by   
					adjusting the pressure regulator. The minimum manifold pressure should be 9.5” w.c. (2366 Pa), the maximum pressure 10.0”   
					w.c. (2491 Pa). If the desired input rating cannot be obtained within the above manifold pressure and adjustment range then the   
					next size larger or smaller drill should be used.   
					B.T.U. (kW)   
					INPUT   
					PER HOUR   
					NATURAL GAS   
					3 1/2” (871.8Pa) W.C.P.   
					Drill Size   
					PROPANE GAS   
					10” (2491 Pa) W.C.P.   
					Drill Size   
					50,000 (14.65)   
					75,000 (21.98)   
					90,000 (26.38)   
					100,000 (29.31)   
					125,000 (36.63)   
					130,000 (38.1)   
					150,000 (43.96)   
					160,000 (46.89)   
					175,000 (51.29)   
					180,000 (52.75)   
					200,000 (58.61)   
					225,000 (65.94)   
					242,000 (70.92)   
					250,000 (73.27)   
					#30 (3.264mm)   
					5/32 (3.967mm)   
					#17 (4.394mm)   
					#14 (4.623mm)   
					#5 (5.22mm)   
					#4 (5.309mm)   
					#1 (5.791mm)   
					15/64 (5.954mm)   
					C (6.147mm)   
					1/4 (6.35mm)   
					G (6.629mm)   
					J (7.036mm)   
					L (7.366mm)   
					M (7.493mm)   
					#45 (2.083mm)   
					#41 (2.438mm)   
					#37 (2.642mm)   
					#35 (2.794mm)   
					1/8 (3.175mm)   
					#30 (3.264mm)   
					#29 (3.454mm)   
					#28 (3.569mm)   
					#26 (3.734mm)   
					#25 (3.797mm)   
					#22 (3.988mm)   
					#19 (4.216mm)   
					#17 (4.394mm)   
					#16 (4.496mm)   
					FIGURE 6   
					5 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				NOTE: The BTU input valves on the preceding page show the approximate hourly input of the burner for the various drill   
					sizes shown. To determine the actual input of the burner:   
					1) Turn off all other gas appliances.   
					2) The hand on the dial with the lowest cubic feet value (fastest revolving dial) should be clocked for one complete revolution.   
					3) Divide 3,600 by the time in seconds for one complete revolution and multiply by the dial value (1 (.028), 2 (.057), or 5   
					(.142) cubic feet depending on size of meter.)   
					4) Multiply this by the heating value of the gas to obtain the input to the burner in BTU per hour.   
					EXAMPLE: Time in seconds for one complete revolution of dial is 72. 3,600 divided by 72 is 50, a 2 cubic foot dial was timed   
					therefore 50 x 2 is 100. Multiply 100 by heating value of gas which is 1,000 and this will give you an input of   
					100,000 BTU (29.31 kW) per hour.   
					IMPORTANT: The minimum gas supply pressure is 4.5” w.c. (1121Pa) for natural gas and 11.0” w.c. (2740Pa) for L.P. gas;   
					the maximum gas supply pressure is 10.5: w.c. (2615Pa) for natural gas and 13” w.c. (3238Pa) for L.P. gas.   
					P250 ONLY   
					Input   
					BTU/Hr.   
					(kW/Hr.)   
					Floor Area   
					Sq. Inches   
					(mm2)   
					Preferred   
					Width and   
					Length (mm)   
					Recommended   
					Minimum   
					Wall Thickness   
					Recommended   
					Minimum   
					Floor Construction   
					50,000 (14.65)   
					85,000 (24.91   
					100,000(29.31)   
					120,000(35.17)   
					140,000(41.03   
					154,000(45.13)   
					175,000(51.29)   
					210,000(61.55)   
					240,000(70.34)   
					250,000(76.2)   
					49 (31610)   
					56 1/4 (36290)   
					64 (41290)   
					7(177.8)x7 (177.8)   
					7 1/2(190.5)x7 1/2(190.5)   
					8(203.2) X 8(203.2)   
					2 1/2” (63.5mm)   
					insulating firebrick   
					plus back up of   
					1 1/2” (38.1mm)   
					or more loose   
					insulation.   
					2 1/2” (63.5mm)   
					Insulating firebrick   
					plus 1 1/2” (38.1mm)   
					asbestos or magnesia   
					block.   
					72 1/4 (46610)   
					81 (52260)   
					8 1/2(215.9) x * 1/2(215.9)   
					9(228.6) x 9(228.6)   
					90 1/4 (58230)   
					100 (64520)   
					9 1/2(241.3) x 9 1/2(241.3)   
					10(254) X 10(254)   
					122 (78710)   
					11(279.4) X 11(279.4)   
					12(304.8) x 12(304.8)   
					12 1/2(317.5) X 12 1/2(317.5)   
					144 (92900)   
					156 1/4 (100800)   
					FIGURE 5   
					P265 ONLY   
					Input   
					BTU/Hr.   
					(kW/Hr)   
					Floor Area   
					Sq. Inches   
					(mm2)   
					Preferred   
					Width and   
					Length (mm)   
					Recommended   
					Minimum   
					Wall Thickness   
					Recommended   
					Minimum   
					Floor Construction   
					65,000 (19.05)   
					75,000 (21.98)   
					100,000 (29.31)   
					150,000 (43.96)   
					200,000 (58.61)   
					63 (40650)   
					71 1/4 (45970)   
					180 (116100)   
					200 (129000)   
					220 (141900)   
					7 (177.8) x 9 (228.6)   
					7 1/2 (190.5) x 9 1/2 (241.3)   
					7 1/2 (190.5) x 9 1/2 (241.3)   
					12 (304.8) X 15 (381)   
					2 1/2” (63.5mm) insulating   
					firebrick plus back up   
					of 1 1/2” (38.1mm) or   
					more loose insulation.   
					2 1/2” (63.5mm) insulating   
					firebrick plus 1 1/2” (38.1mm)   
					asbestos or magnesia   
					block.   
					13 (330.2) x 17 (431.8)   
					FIGURE 5A   
					P265F ONLY   
					Input   
					BTU/Hr.   
					(kW/Hr.)   
					Floor Area   
					Sq. Inches   
					(mm2)   
					Preferred   
					Width and   
					Length (mm)   
					Recommended   
					Minimum   
					Wall Thickness   
					Recommended   
					Minimum   
					Floor Construction   
					65,000 (19.05)   
					75,000 (21.98)   
					100,000 (29.31)   
					150,000 (43.96)   
					200,000 (58.61)   
					63 (40650)   
					63 (40650   
					7 (177.8) x 9 (228.6)   
					7 (177.8) x 9 (228.6)   
					2 1/2” (63.5mm) insulating   
					firebrick plus back up   
					of 1 1/2” (38.1mm) or   
					more loose insulation.   
					2 1/2” (63.5mm) insulating   
					firebrick plus 1 1/2” (38.1mm)   
					asbestos or magnesia   
					block.   
					71 1/4 (45970)   
					110 (70970)   
					165 (106500)   
					7 1/2 (190.5) x 9 1/2 (241.3)   
					10 (254) x 11 (297.4)   
					11 (297.4) x 15 (381)   
					FIGURE 5B   
					6 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				ELECTRICAL WIRING   
					The power burner is shipped completely wired. It is only necessary to supply the 115 volt circuit, thermostat and limit circuit.   
					All wiring must conform with the National electric Code or the code legally authorized in the locality where the installation is   
					being made. The burner, when installed, must be electrically grounded in accordance with local codes or, in the absence of   
					local codes, with the National Electrical Code, ANSI/NFPA No. 70-1987. See wiring diagrams, Figures 12&13.   
					If an external electrical source is utilized, the conversion burner, when installed, must be electrically grounded in accordance   
					with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA No. 70-1987.   
					CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous   
					operation. Verify proper operation after servicing.   
					LIMIT CONTROL SWITCHES   
					Warm air furnaces (gravity and forced air) should be equipped with an automatic temperature limit control switch. Hot water   
					boilers (forced or gravity) should be equipped with an automatic temperature limit control switch.   
					Steam or vapor boilers be provided with means to guard against firing a dry boiler or one in which the water is dangerously low.   
					IMPORTANT: On installations where an oil burner replaced with a gas burner, the controls on the boiler or furnace will have   
					to be checked for compatibility with the gas burner. All controls should be checked to insure that they operate   
					properly and that they are in good condition. In no case should any limit or safety control be bypassed or   
					wired in such a manner that it will result in unsafe operation of the burner or appliance. If the controls on the   
					appliance are not compatible with the burner operation they should be replaced with the proper controls.   
					THERMOSTAT   
					The thermostat should be installed on an inside wall and should be located in the natural circulating path of room air.   
					Locations which would expose the thermostat to cold air, or drafts from windows, door, or openings leading to the outside, or to   
					air currents from cold or warm air registers, or where the natural circulation of air is shut off such as behind doors, above or   
					below mantels, shelves or in corners, should be avoided. The thermostat should not be exposed to heat from nearby radiators,   
					lamps, rays of the sun or mounted on a wall near pipes, warm air ducts or chimney flue. Any hole in the plaster or panel   
					through which the thermostat wires pass should be sealed to prevent drafts.   
					The maximum comfort to be obtained from any automatic heating installation is dependent to a great extent upon the proper   
					installation and adjustment of the room thermostat.   
					GAS PIPING   
					All piping must comply with local codes and ordinances or the National Fuel Gas Code ANSI Z223. 1-1984 and NFPA No.   
					54. A sediment trap or drip leg must be installed in the supply line to the burner.   
					A union shall be installed in the gas line adjacent to the upstream from the control manifold and downstream from the manual   
					main shutoff trap or drip leg must be installed in the supply line to the burner.   
					A 1/8” N.P.T. (3.175mm) plugged tapping accessible fro test gauge connection shall be installed immediately upstream of the   
					gas supply connection for the purpose of determining the gas supply pressure to the burner.   
					A manual shutoff valve shall be installed in the gas supply line external to the appliance, see Figure 7.   
					The gas line should be a separate supply direct from the meter to the burner. It is recommended that new pipe; be used and   
					located so that a minimum amount of work will be required in future servicing. The piping should be so installed as to be   
					durable, substantial and gas tight. It should be clear and free from cutting burrs and defects in structure or threading. Cast iron   
					fittings or aluminum tubing should not be used for the main gas circuit. Joint compounds (pipe dope) should be used sparingly   
					on male threads only and be approved for all gases.   
					It is recommended that table 8 be used to determine the size pipe to use from the meter to the burner.   
					The building structure should not be weak ended by installation for the gas piping. The piping should not be supported by the   
					other piping, but should be firmly supported with pipe hooks, straps, bands or hangers. Butt or lap welded pipe should not be   
					bent.   
					The gas piping should be so installed so as to prevent an accumulation of condensation and it must be protected against   
					freezing. A horizontal pipe should be pitched so that it grades toward the meter and is free from sags. The pipe should not be   
					run through or in an air duct or clothes chute.   
					The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure   
					testing of the system at test pressure in excess of 1/2 (3447 PaG) psig.   
					The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any   
					pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 (3447 PaG) psig.   
					TESTING PIPING FOR LEAKS   
					Before turning gas under pressure into piping, all openings from which gas can escape should be closed. Immediately after   
					turning on gas, the system should be checked for leaks. This can be done by watching the 1/2 cubic feet (.014m3) test dial and   
					allowing 5 minutes to show any movement, or by soaping each pipe connection and watching for bubbles. If a leak is found,   
					make the necessary repairs and repeat the above test.   
					Defective pipes or fittings should be replaced and not repaired. Never use a flame or fire in any form to locate gas leaks, use   
					a soap solution.   
					7 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				After the piping and meter have been checked completely, purge the system of air. Do not bleed the air inside the furnace.   
					Be sure to relight all the gas pilots on other appliances.   
					PURGING   
					After the piping has been checked, all piping and appliances receiving gas through the meter shall be fully purged. A   
					suggested method for purging th gas line to the burner is to disconnect the pilot line at the outlet o the pilot valve. Under no   
					circumstances shall th line be purged into the combustion chamber.   
					After th e gad line to the conversion burner has been fully purged and the pilot line reconnected, the gas supply at other pilot   
					burners located on other gas appliances which were extinguished as the result of interrupted service shall be reignited.   
					LENGTH OF STANDARD PIPE THREADS inches (mm)   
					EFFECTIVE   
					LENGTH   
					OVERALL   
					LENGTH   
					PIPE SIZE   
					OF THREAD   
					OF THREAD   
					3/8 (9.525)   
					1/2 (12.7)   
					3/4 (19.05)   
					1 (25.4)   
					3/8 (9.525)   
					1/2 (12.7)   
					1/2 - 9/16 (14.29)   
					9/16 (14.29)   
					9/16 (14.29)   
					3/4 (19.05)   
					13/16 (20.64)   
					1 (25.4)   
					PIPE CAPACITY TABLE   
					Nominal Diameter of Pipe in Inches   
					3/4 (19.05) 1(25.4) 1-1/4 (31.75) 1-1/2 (38.1) 2 (50.8)   
					Length   
					of Pipe   
					in Feet   
					Capacity - Cu, Ft. Per Hr. with a 0.6   
					Sp. Gr. Gas and Press. Drop of 0.3 In. (74.72 Pa) Water Col.   
					15 (4.572)   
					30 (9.144)   
					45 (13.72)   
					60 (18.29)   
					75 (22.86)   
					105 (32)   
					172   
					120   
					99   
					86   
					77   
					345   
					241   
					199   
					173   
					155   
					131   
					120   
					100   
					750   
					535   
					435   
					380   
					345   
					285   
					270   
					225   
					850   
					700   
					610   
					545   
					450   
					420   
					350   
					65   
					920   
					860   
					720   
					120 (36.58)   
					180 (54.86)   
					FIGURE 8   
					To convert the figures given above to capacities for another   
					gas of different specific gravity, multiply the tabular values by   
					the multiplier shown below.   
					MULTIPLIER FOR VARIOUS   
					SPECIFIC GRAVITIES   
					SPECIFIC   
					GRAVITY   
					SPECIFIC   
					GRAVITY   
					MULTIPLIER   
					1.31   
					MULTIPLIER   
					.775   
					.35   
					1.00   
					.40   
					1.23   
					1.10   
					.740   
					.45   
					.50   
					.55   
					.60   
					.65   
					.70   
					.75   
					1.16   
					1.10   
					1.04   
					1.00   
					.962   
					.926   
					.895   
					1.20   
					1.30   
					1.40   
					1.50   
					1.60   
					1.70   
					1.80   
					.707   
					.680   
					.655   
					.633   
					.612   
					.594   
					.577   
					.80   
					.90   
					.867   
					.817   
					1.90   
					2.10   
					.565   
					.535   
					8 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				ADJUSTMENT OF BURNER   
					Starting the burner:   
					1. Depress the gas valve control knob on the combination gas valve and turn to “OFF”. Figure 9.   
					2. Set room thermostat above room temperature and let burner run five minutes to purge the unburned gas from the unit.   
					3. Set thermostat below room temperature.   
					4. Turn gas valve control to “PILOT”.   
					5. Depress red button on valve to start pilot gas flow.   
					6. Push re button down on spark generator until it snaps. Repeat this until the pilot lights. Note: this may take some time until   
					all the air is “bled: out of the line.   
					7. Hold the red button on the valve for seconds, then release.   
					8. Observe pilot - if not lit, SHUT OFF BURNER COMPLETELY AND WAIT 5 MINUTES. Repeat steps 1 through 7.   
					9. Turn gas control valves to “ON”.   
					10. Set room thermostat higher than room temperature so that the burner will start.   
					To put burner out of operation   
					1. Depress the gas valve control knob on the combination gas valve and turn to “OFF”.   
					2. Turn off electrical supply.   
					STANDING PILOT   
					COMBINATION GAS VALVE   
					FIGURE 9   
					ELECTRONIC PILOT   
					FIGURE 11   
					9 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				P265DI - JUNCTION BOX ROTATED   
					P265DI   
					10   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				All adjustments below must be made with the following instructions:   
					1. Draft Gauge   
					3. CO Tester   
					2 
					2 
					2. O or CO Analyzer   
					4. Water Column Gauge   
					After the burner has been in operation for 10 minutes and if a neutral pressure point adjuster was installed, proceed as   
					follows. Start from the wide open position and gradually close the neutral pressure point adjustment. Crack observation door   
					about 1/8 inch (3.175mm). Then by holding match flame along opening, the neutral pressure point can be determined. The   
					flame should be drawn in below the center of the door and it should be blown outward above the center. In other words, the   
					pressure inside the combustion chamber should be above atmospheric pressure above the burner flame and below atmospheric   
					pressure below the burner flame. The pressure should be neutral at the center. Closing the adjuster lowers the neutral   
					pressure point and opening the adjuster raises the neutral pressure point.   
					Once the neutral pressure point has been adjusted, the combination air shutter should be adjusted so that the percent CO   
					2 
					test must be made at the inlet side of the draft hood. If the CO reading is not within the recommended limits, then the   
					2 
					combustion air shutter should be re-adjusted and then the neutral pressure point be rechecked and reset if necessary.   
					IT IS ESSENTIAL TO MAKE CERTAIN THAT THE PRODUCTS OF COMBUSTION DO NOT CONTAIN CARBON   
					MONOXIDE, CO. It is possible to have flame impingement on cold surfaces with resultant CO even if CO and O are within   
					2 
					2 
					acceptable limits. The flue gas sample is taken through the same hole used for the CO test. CO test instrument must be used   
					2 
					for this test.   
					The most common causes of CO are flame impingement on cool surface and insufficient primary air, both of which could be   
					caused by over firing. The only answer is to reduce the firing rate or increase the primary air.   
					Combustion efficiency is determined by the percent CO and the temperature of the flue gases. These two measurements   
					2 
					are taken on the inlet side of the draft hood. Combustion efficiency and stack loss calculators provide slide rule convenience for   
					correlating CO and stack temperature readings. These calculators are available from several manufactures of combustion test   
					2 
					equipment.   
					IMPORTANT   
					DRAFT - When installing Wayne power gas burners in oil fired boilers a minimum negative draft of .02” (4.982 Pa) w.c. over   
					fire must be maintained.   
					Refer to your local gas company and codes for assistance.   
					For gad fired equipment requiring a double acting barometric the preferred location of the barometric draft control is part of   
					the bullhead tee shown in figures A, B OR C. During normal operation, flue gases make a right angle turn behind the control,   
					but do not infringe upon it. Should a downdraft occur, air flowing n the opposite direction strikes the control directly, causing it to   
					open outwardly and vents the air into the room with a minimum of resistance. Entrained products of combustion are thus   
					provided grater relief.   
					BEST LOCATIONS FOR GAS   
					WIRING DIAGRAM LADDER FORM   
					FIG. A   
					FIG. B   
					FIG. C   
					WIRING DIAGRAM FOR GAS BURNER WITH STANDING PILOT   
					FIGURE 12   
					WIRING DIAGRAM LADDER FORM   
					FIGURE 13   
					11   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				GENERAL INSTRUCTION   
					Gas burners require the services of an experienced technician for proper setting and adjustment. If the burner does not   
					appear to be operating properly, DO NOT ATTEMPT TO ADJUST THE BURNER YOURSELF, but call in a competent   
					serviceman.   
					A homeowner should be able to check several possible causes of shutdown before calling in a serviceman. The following   
					check list may eliminate the need for a service call or at least provide information for the serviceman.   
					1. Check thermostat. Make sure that it is set at the desired room temperature. If the thermostat is damaged or loose on the   
					wall, have it replaced or repaired.   
					2. Check fuses in service box for the burner circuit. Replaceable type fuses should not be loose in the socket. If a fuse is   
					blown out or if in doubt, replace with the same size and type. If circuit breaker are in the service box, check position of   
					indicator. If tripped, reset.   
					3. Check on-off switch for the burner circuit, it may have been accidentally turned off.   
					4. With the thermostat set 10 degrees above room temperature, the burner should start automatically. If it does not start,   
					check pilot. If no flame is visible, relight pilot following lighting instructions.   
					It is advisable, periodically, to visually inspect the burner. Check air inlet blower to make sure it is not clogged or   
					blocked. Check air shutter to make sure that it has not been tampered with, make sure that it is in the same position as   
					when final adjustments were made. Check blower wheel to see if it is dirty or full of lint. Open observation door and   
					check pilot flame. If the flame does not appear normal or if in doubt, call a serviceman.   
					The areas around the conversion burner should be kept clear and free of combustible materials, gasoline and other   
					flammable vapors and liquids.   
					The flow of combustion and ventilating air to the burner must not be blocked or obstructed in any manner.   
					CLEANING OF BURNERS: Remove the burner from the appliance and visually inspect the blast tube for any deterioration.   
					On burners equipped with standing pilot or intermittent ignition, inspect pilot burner for dust or corrosion and clean if necessary.   
					Check pilots, thermo-couples, electrodes, etc. with illustrations in the owner’s manual for proper locations.   
					Check flame spreaders if applicable for any deterioration and replace if necessary.   
					Remove corrugated flame ring from the end of the venturi and clean. Visually inspect the inside of the venturi for any   
					excessive rust or corrosion and clean if necessary. Replace corrugated flame ring and reinstall burner.   
					TROUBLE CHART   
					SYMPTOMS   
					CAUSE   
					a. Air in Gas Line.   
					b. High or low gas pressure.   
					c. Blocked pilot orifice.   
					1. PILOT DOES NOT LIGHT   
					a. Restriction in the pilot gas line.   
					b. Low gas pressure.   
					c. Blocked pilot orifice.   
					2. PILOT GOES OUT FREQUENTLY   
					DURING STANDBY.   
					d. Loose thermocouple connection on 100% shut off.   
					e. Defective thermocouple or pilot safety switch.   
					f. Poor draft condition.   
					3. PILOT GOES OUT WHEN MOTOR STARTS.   
					4. MOTOR DOES NOT RUN.   
					g. Draft tube set into or flush with inner wall of combustion chamber.   
					a. Restriction in pilot gas line.   
					b. High or low gas pressure.   
					c. Excessive pressure drop when the main gas valve opens.   
					a. Burned out fuse or current off.   
					b. Thermostat or limit defective or improperly set.   
					c. Relay or transformer defective.   
					d. Motor burned out.   
					5. MOTOR RUNNING BUT NO FLAME.   
					6. SHORT NOISY BURNER FLAME.   
					7. LONG YELLOW FLAME.   
					e. Improper wiring.   
					a. Pilot out.   
					b. Thermocouple not generating sufficient voltage.   
					c. Very low or no gas pressure.   
					d. Vent in regulator plugged.   
					e. Defective regulator.   
					8. MAIN GAS VALVE DOES NOT   
					CLOSE WHEN BLOWER STOPS.   
					a. Air shutter not open enough.   
					b. Air openings or blower wheel clogged.   
					c. Too much input.   
					9. REGULATOR VENT LEAKING GAS.   
					a. Hole in diaphragm.   
					12   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				P 265-EP, P265F-EP, P250AF-EP   
					INTERMITTENT PILOT INSTRUCTION   
					FOR HONEYWELL SYSTEM   
					STARTING BURNER   
					1. Depress the gas valve control knob on the combination gas valve and turn to “OFF”. See Figure 9.   
					2. Set the room thermostat above room temperature and wait five (5) minutes.   
					3. Set thermostat below room temperature.   
					4. Turn gas control valve knob to “ON”.   
					5. Set room thermostat higher than room temperature so that the burner will start.   
					SHUTTING DOWN THE BURNER   
					1. Depress the gas valve control knob on the combination gas valve and turn to “OFF”.   
					2. Turn off electrical supply.   
					OPERATION   
					FIRST STAGE -- TRIAL FOR PILOT IGNITION   
					On every call for heat (system start), the S8600 performs an internal safe-start check. A system start is prevented if the   
					check shows that a flame-simulating condition is present..   
					During a normal start, the S8600 opens the first operator in the gas control. This allows gas to flow to the pilot burner.   
					Simultaneously, the electronic spark generator in the S8600 produces a 15,000 volt spark pulse output. This voltage produces a   
					spark at the pilot burner ignitor-sensor rod, igniting the gas flowing around the electrode. If the pilot flame is not detected during   
					the trial for pilot ignition, the S86E an F will continue trying for pilot ignition until a flame is established. The S86G and H contain   
					a safety locknut timer to limit the trial for pilot ignition period.   
					SECOND STAGE -- MAIN BURNER OPERATION   
					When the pilot flame is established, a flame rectification circuit is completed to the burner ground. The S8600 flame sensing   
					circuit detects the flame current and shuts the spark generator off. At the same time the second operator (main) is opened in   
					the gas control, allowing gas flow to the main burner. The pilot flame ignites the main burner conventionally. On the S86G and   
					H the flame current also holds the safety lockout timer in the reset, or normal, operating condition.   
					SAFETY LOCKOUT TIME (S8600 only)   
					The safety lockout timer circuit starts timing the moment the trial for pilot ignition starts. When the timing period runs out, the   
					trial for ignition ends, and the control module goes into lockout. Before another attempt to start can be made, the S8600 must   
					be reset. Reset by adjusting the thermostat or controller below room temperature, or to its “OFF” position. An alternate method   
					is to shut the system power “OFF”. Wait at least one (1) minute, then turn the system “ON”. If normal ignition does not occur,   
					use the troubleshooting table to determine the problem.   
					SERVICE   
					PRELIMINARY CHECK   
					The following visual checks should be made before troubleshooting an after installation or maintenance.   
					1. Check the power to the appliance and S8600.   
					2. Manual shutoff cocks in gas line to appliance must be open.   
					3. Make certain all wiring connections are clean and tight.   
					4. S86G, H module must not be in safety lockout. First de-energize the system and wait at least one(1) minute. This resets   
					the module, allowing a return to start condition.   
					5. Review the S8600 system normal sequence of operation.   
					SYSTEM TROUBLESHOOTING   
					Start the system by setting the thermostat or controller above required temperature. Observe system response. Establish   
					type of malfunction or deviation from normal operation. Use the S8600 Intermittent Pilot System Troubleshooting Table (Page   
					13) to check for normal system operation.   
					Use table by following instruction question in box. If the condition is true or okay (answers yes), go down to next box   
					underneath. If the condition is not true or not okay (answers no), go right to the next box alongside. Continue checking and   
					answering conditions in each box encountered, until a problem and/or the repair are explained. After any maintenance or repair,   
					the troubleshooting sequence should be repeated until the troubleshooting procedure ends with normal system operation.   
					13   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				IMPORTANT: The electronic S8600 Control Module cannot be repaired. If troubleshooting procedure indicates a malfunction in   
					the S8600 the S8600 Control Module must be replaced. Intermittent pilot systems should be serviced only by   
					trained and experienced personnel.   
					SEQUENCE OF OPERATION   
					1 
					THERMOSTAT (CONTROLLER)   
					CALLS FOR HEAT   
					START   
					2 
					SPARK GENERATOR   
					powered by First Valve (pilot) operator opens   
					STAGE 1   
					TRIAL FOR   
					IGNITION   
					3 
					PILOT BURNER OPERATION   
					Pilot burner lights.   
					Module senses   
					flame current.   
					Pilot burner does not light   
					OR   
					Module   
					Response   
					S8600A,F   
					S8610A, F   
					Ignition spark continues, pilot valve remains   
					open until system is reset   
					S8600B, H   
					S8610B, H   
					After 15 or 90 sec. a system   
					lock outs; must be manually reset   
					S8600M   
					After on sec. a system shuts off; after 5 minutes   
					min. (6 minutes nom.), module restarts trial for   
					ignition; ignition trial, shutoff, wait sequence   
					repeats until pilot lights or call for heat ends.   
					a Shutoff/lockout timing is stamped on module   
					4 
					FLAME CURRENT SENSED   
					• Spark generator off   
					• Second valve operator (main) opens.   
					POWER INTERRUPTION   
					System shuts off, restarts when power is   
					restored.   
					STAGE 2   
					MAIN BURNER   
					OPERATION   
					4 
					4 
					MAIN BURNER OPERATION   
					Module monitors pilot flame current.   
					PILOT FLAME FAILURE   
					Mail valve closes.   
					Module starts trial for ignition.   
					THERMOSTAT (CONTROLLED)   
					SATISFIED   
					Valves close, pilot and main burners are off.   
					END   
					WIRING DIAGRAM HONEYWELL EP SYSTEM   
					WIRING DIAGRAM LADDER FORM   
					S86   
					14   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				S8600, S8610 TROUBLESHOOTING GUIDE   
					START   
					NOTE: Before troubleshooting, familiarize yourself with the start up and checkout procedure.   
					TURN GAS SUPPLY OFF,   
					TURN THERMOSTAT   
					(CONTROLLER) TO CALL   
					FOR HEAT   
					Check line voltage power, low voltage transformer, limit controller, thermostat (controller) and   
					wiring. Also, check air proving switch on combustion air blower system (if used) and that vent   
					damper (if used) is open and end switch is made.   
					NO   
					NO   
					POWER TO MODULE   
					(24V NOMINAL)   
					Pull ignition lead and   
					check spark at module   
					• 
					• 
					On modules with vent damper plug, make sure   
					vent damper has not been installed, then   
					removed. Replace vent damper if necessary.   
					YES   
					NO   
					SPARK ACROSS   
					IGNITER/SENSOR GAP   
					Spark okay?   
					On other models, replace module.   
					YES   
					YES   
					• Check ignition cable, ground wiring, ceramic insulator and gap, and correct.   
					• Check boot of the ignition cable for signs of melting or buckling. Take protective   
					action to shield cable and boot from excessive temperatures.   
					TURN GAS SUPPLY ON   
					PILOT BURNER LIGHTS?   
					NO   
					• Check that all manual gas valves ar open, supply tubing and pressures are good, and pilot   
					burner orifice is not blocked.   
					YES   
					• Check electrical connections between module and pilot operator on gas control.   
					• Check for 24 Vac across PV-Mv/PV terminals on module. If voltage if okay, replace gas   
					control; if not, replace module.   
					NOTE: If S8600B, H; S8610B, H goes into lockout, reset system. For S8600M, wait 6 min.   
					norm. for retry or reset system.   
					• Check continuity of ignition cable and ground wire.   
					• Clean flame rod.   
					SPARKS STOP WHEN   
					PILOT IS LIT?   
					NO   
					• Check electrical connections between flame rod and module.   
					• Check for cracked ceramic flame rod insulator.   
					• Check that pilot flame covers flame rod and is steady and blue.   
					• Adjust pilot flame.   
					YES   
					• If problem persists, replace the module.   
					• Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.   
					MAIN BURNER LIGHTS?   
					NO   
					NO   
					• Check electrical connections between module and gas control. If okay, replace gas control   
					or gas control operator.   
					YES   
					NOTE: If S8600B, H; S8610B, H goes into lockout, reset system. For S8600M, wait 6 min.   
					norm. for retry or reset system.   
					• Check continuity of ignition cable and ground wire.   
					SYSTEM RUNS UNTIL   
					CALL FOR HEAT ENDS?   
					NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation   
					is normal at the time of checkout.   
					YES   
					• Check that pilot flame covers flame rod and is steady and blue.   
					• If checks are okay, replace the module.   
					CALL FOR HEAT END   
					SYSTEM SHUTS OFF?   
					• Check for proper thermostat (controller) operation.   
					NO   
					• Remove MV lead at module; if valve closes, recheck temperature controller and wiring; if   
					not, replace gas control.   
					YES   
					TROUBLESHOOTING   
					ENDS   
					Repeat procedure until trouble   
					free operation is obtained.   
					15   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				P250AF DIRECT SPAR ELECTRODE LOCATION   
					7/16”   
					1/16”   
					1/16”   
					+/- (1.587 mm)   
					1/4”   
					(6.35 mm)   
					(11.11 mm) +/- (1.587 mm)   
					1/8” (3.175 mm) GAP   
					31/64”   
					(12.3 mm)   
					1/16”   
					+/- (1.587 mm)   
					P265DI   
					DIRECT SPARK IGNITION   
					HONEYWELL S87K SYSTEM   
					P250AF/P265-DI   
					DIRECT SPARK IGNITION   
					HONEYWELL SYSTEM   
					Starting the burner:   
					1) Turn the gas valve control knob to “OFF”, wait five minutes.   
					2) Turn gas valve control knob to “ON”.   
					3) Set room thermostat above room temperature.   
					4) If burner does not light, SHUT OFF BURNER COMPLETELY AND WAIT FIVE MINUTES, then repeat steps 1 through 3   
					above.   
					To shut off burner:   
					1) Turn the gas valve control knob to “OFF”.   
					2) Turn off electrical supply.   
					DESCRIPTION   
					The Honeywell S87K (24VAC) Direct Spark Ignition Systems operate through a thermostat to provide a means of ignition for   
					the main burner on gas-fired equipment. This is accomplished by generating a spark between high voltage electrode and   
					ground. Once the flame is established a flame rod monitors the main burner flame.   
					SEQUENCE OF OPERATION   
					On a call for heat, voltage is applied to the ignitor across Terminals 1 (power) and ^ (ground) of the input connector. A high   
					voltage spark is then generated from the spark electrode to ground. Simultaneously, the gas valve is energized.   
					At the start of each heat cycle, there is a “Trial for ignition period” of three seconds duration. Normally main burner flame will   
					be established before the end of this period. Once the flame is established, sparking will cease and the “flame rod” will provide   
					flame monitoring for the remainder of heat cycle. If the flame is extinguished during this cycle, the ignitor will start sparking   
					automatically in an attempt to re-establish the flame. If this does not occur within the “Trial for ignition period,” the system will go   
					into lockout, closing the gas valve.   
					16   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TROUBLESHOOTING   
					Although the following tests can be made using standard volt meter, it is quicker and more convenient to use a Fenwal   
					Model 05-125539-001 Test Adapters.   
					PRELIMINARY CHECKS   
					1. Input Polarity   
					If a spark is present and the gas valve opens for the flame establishing period but then locks out   
					to ten seconds, check the input voltage at Terminals 1 and 6 for the proper polarity. Terminal 1 should be “hot”; 14AVC   
					(05-16) with respect to ground. Terminal 6 is neutral, or zero voltage, with respect to ground.   
					at the end of other   
					2. Improper Grounding   
					If a flame is present during the Trial for Ignition period but th system shuts down, insure that the burner is properly   
					grounded. If the burner is not grounded, the flame monitoring signal will not function and the system will go into lockout.   
					Check for loose or corroded terminals and replace if necessary. Insure good electric connection by scraping paint or any   
					other foreign matter off the area where ground connection is made.   
					It is equally important to be certain that the electrode bracket assembly is properly grounded. The bracket should be   
					common with the ground lead on the input connector (ground terminal 6). If the bracket is not properly grounded,   
					damage to the ignitor can result.   
					3. Inoperative High Voltage   
					If there is no spark or sparking is intermittent, check the following after disconnecting voltage to the system.   
					a. Check spark gap. Gap should be 1/8 (3.175mm)+/- 1/32”(.7937mm) form H.V. to ground.   
					CAUTION: NEVER REPLACE THE COMPONENT BOARD WITHOUT FIRST CHECKING TO INSURE THAT THE   
					ELECTRODE HAS THE PROPER GAP. IF THE GAP IS TOO WIDE, DAMAGE TO THE IGNITOR CAN RESULT.   
					b. Check electrode leads and determine there is no corrosion at the terminals. If there is corrosion, clean it off.   
					c. Check ceramic insulators for cracks, foreign matter, and carbon. If there are cracks, replace electrodes. If there is   
					carbon or foreign matter, clean it off.   
					d. Check high voltage lead wire for cracks or breaks. If there are cracks, breaks or chaffing, replace high voltage wire.   
					e. Check that the high voltage lead wire is not too close to a metal surface to insure that arcing will not occur at any   
					point other than across the H.V. electrode. Also, insure that the high voltage lead wire is not taped or connected to a   
					metal frame along its length, sharp metal edges, or crossing, do not bundle with other wires. Always leave one inch   
					spacing between the high voltage lead wire and any other metal or wires.   
					f. For best operation, the high voltage wire should be short as possible and should not exceed 23 inches (584.2 mm) in   
					length.   
					g. Check to insure that the high voltage terminal is clear of dust, moisture or any foreign matter that could create high   
					voltage leakage to ground.   
					4. Valve Malfunction   
					With power applied to the ignitor, sparking should occur and the solenoid valve should open simultaneously. If sparking   
					occurs but the valve does not open, place a volt meter between Terminal 4 on the input connector and ground (or across   
					valve). (terminals 4 (valve) and 6 (ground) in Figure 1). If voltage is present and the valve does not open, remove wires   
					from the valve terminals and retest the valve on a known voltage source. If valve still does not function, it should be   
					replaced. If the voltage is not present at Terminals 4 and 6, the ignitor should be replaced. Check p.c. connection area.   
					(clean with soft rubber eraser only). Also, check the terminals in the plastic connector for good contact.   
					The valve relay is rated for 24VAC on th 05-16, at .5 amps. If a valve is used with a higher current rating than that   
					specified, damage can result to the relay contacts.   
					5. Electrode Placement   
					a. Electrode should be placed so optimum flame current is achieved for proper application.   
					b. Flame should not impinge on any portion of ceramic insulator.   
					6. Flame Current   
					The flame detector circuit uses the ionized gas flame to conduct the flame signal. This signal is a small DC current   
					which can be measured directly with a 0 to 50 microamp meter.   
					Although the minimum flame current necessary to keep the 05-16 ignitor from going into lockout is 2.5 ,microamps, the   
					lowest recommended is 5.0 microamps. These ignitors can stand flame currents as high as 30 to 40 microamps.   
					17   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				To measure flame current, first shut off the power to the system and then remove the flame sensing lead wire form the   
					electrode terminal and insert a 0-50 DC microamp meter in series with the sensor electrode and the sensor lead wire. “Plus”   
					terminal of meter to component board and “negative”: terminal to sense electrode. Energize the ignitor. If the meter reads   
					below zero, shut the system off and reverse meter leads.   
					Once the flame is established, assure that the flame current is above the minimum specified. If not, assure that the system   
					has the proper input voltage, and ten relocate the sensor electrode in the flame pattern until flame current is increased.   
					Once the flame has been established and the system is in its heat cycle, occasional sparking may occur. This is common in   
					some installations and is not significant. Sparking will not damage the ignitor.   
					7. Ambient Temperatures   
					The 05-16 is designed to operate over the temperature range of -40 to 150 F (-40 to 65.56 C). Care should be taken to   
					insure that it operates within this range. If these limits are exceeded, the ignitor should be relocated to an area that is   
					within this temperature range.   
					8. Relative Humidity   
					The 05-16 is coated for moisture resistance to 90 percent relative humidity. Caution should be taken to protect the   
					component board against direct exposure to water.   
					SERVICE HINT, DIAGNOSIS AND CORRECTIVE MEASURES   
					WHAT’S WRONG   
					WHY   
					WHAT TO DO   
					1. Lockout Occurs 3-10   
					seconds after ignition.   
					1. Reverse polarity.   
					Para. 1.   
					Para. 2.   
					Check to ensure input pressure   
					as specified on manufacturer’s   
					data plate.   
					2. System improperly grounded   
					3. Gas pressure too high, causing   
					flame to lift off burner.   
					4. Sensor probe incorrectly   
					positioned in flame pattern.   
					Spark gap too small.   
					Spark too large.   
					Corroded connector.   
					1. Cracked or dirty insulator.   
					Para. 6.   
					2. Flame not established.   
					Arching to ground.   
					3. No spark.   
					Para. 3a   
					Para. 3a.   
					Para. 3b.   
					Para. 3c.   
					4. Arching other than across gap.   
					2. Broken high voltage lead.   
					High voltage lead too close to   
					metal surface.   
					Para. 3c.   
					Para. 3e.   
					Weak Spark.   
					No flame.   
					Valve malfunction.   
					Electrode improperly placed.   
					Para. 4.   
					Para. 5.   
					Low flame current and/or   
					nuisance lockouts.   
					Nuisance lockouts.   
					1. Flame current falls below 2.5 uA   
					2. Low gas pressure.   
					Para. 6.   
					Check to ensure that manifold   
					pressure meets manufacturer’s   
					specifications.   
					WIRING DIAGRAM   
					HONEYWELL S87KDI SYSTEM   
					WIRING DIAGRAM   
					LADDER FORM   
					18   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				No.   
					Req’d   
					Part   
					No.   
					Description   
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					2 
					2 
					2 
					2 
					2 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					Air Tube & Housing Assy. 5” (127mm) Burner   
					Air Tube & Housing Assy. 8” (203.2mm) Burner   
					Air Tube & Housing Assy. 11” (279.4mm) Burner   
					Air Tube & Housing (F) 5” (127mm) Burner   
					Air Tube & Housing (F) 8” (203.2mm) Burner   
					Air Tube & Housing (F) 11” (279.4mm) Burner   
					Adjustable Flange   
					62715-001   
					62715-003   
					62715-005   
					62715-002   
					62715-004   
					62715-006   
					21756-011   
					60214   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Mounting Pedestal   
					Pedestal Mounting Bracket   
					Motor/Blower Assembly   
					60215   
					60172-002   
					60944   
					Venturi w/o Flame Spreader   
					Venturi with Flame Spreader   
					Control Box/Strap Assembly   
					Control Box Cover   
					61403   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					62903-001   
					62899-001   
					62653-001   
					63228-001   
					63062-001   
					62249-002   
					60195   
					• 
					• 
					• 
					• 
					• 
					• 
					Pilot Shield   
					Pilot Burner   
					Pilot Burner   
					• 
					• 
					• 
					• 
					Ignition Cable   
					Pilot Tube 5” (127mm) Burner   
					Pilot Tube 5” (127mm) Burner EP   
					Pilot Tube 8” (203.2mm) Burner   
					Pilot Tube 8” (203.2mm) Burner EP   
					Pilot Tube 11” (279.4mm) Burner   
					Pilot Tube 11” (279.4mm) Burner EP   
					Spark Generator Bracket   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					62320-002   
					62320-003   
					63212-001   
					62901-001   
					61770-002   
					60187   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Air Shutter Body (Stationary Part)   
					Air Shutter Disk (Moveable Part)   
					Motor relay   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Transformer 120/24V   
					60186-003   
					61455   
					Bulkhead Union   
					Thermocouple 5” (127mm) Burner   
					Thermocouple 8” (203.2mm) Burner   
					Thermocouple 11” (279.4mm) Burner   
					Venturi Spacer 8” (203.2mm) Burner`   
					Venturi Spacer 11” (279.4mm) Burner   
					Venturi Mounting Bolt 5” (127mm) Burner   
					Venturi Mounting Bolt 8” (203.2mm) Burner   
					Venturi Mounting Bolt 11” (279.4mm) Burner   
					Orifice - Natural Gas   
					60154   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					60987   
					60280   
					60252   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					61054   
					60072   
					60083   
					60085   
					see chart   
					Pg. 15   
					Orifice - L.P. Gas   
					Orifice Holder Assy. 5” (127mm) Burner   
					Orifice Holder Assy. 8” (203.2mm) Burner   
					Orifice Holder Assy. 11” (279.4mm) Burner   
					Elbow - 1/2” (12.7mm) Pipe - Black Iron   
					Valve Spring Kit   
					60155   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					60249   
					60250   
					60001   
					62672-004   
					60013   
					Nipple - 1/2” (12.7mm) Pipe - Special   
					Piezo Ignitor   
					• 
					• 
					63213-001   
					63217-001   
					63217-002   
					63217-003   
					60182   
					• 
					• 
					Ignitor Wire 5” (127mm) Burner   
					Ignitor Wire 8” (203.2mm) Burner   
					Ignitor Wire 11” (279.4mm) Burner   
					Gas Valve Cord Assy.   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Pilot Orifice - (Natural Gas) .024 (.610mm)   
					Pilot Orifice - (L.P. Gas) .018 (.457mm)   
					Gas Valve - (Standing Pilot)   
					Gas Valve - (Electronic Pilot)   
					Ignition Control - S8600   
					60680-002   
					60680   
					• 
					• 
					• 
					• 
					60270-002   
					62246-004   
					62243-003   
					62947-001   
					63646-002   
					60645   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Ignition Wire   
					Pilot Bracket   
					• 
					• 
					• 
					• 
					• 
					• 
					Feeder Tube   
					Electronic   
					63210-001   
					19   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				No.   
					Req’d   
					Part   
					No.   
					Description   
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					Control Box Assembly   
					Power Cord Assembly   
					Transformer   
					62296   
					60182-002   
					60186-003   
					60187   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Relay   
					Control Box Cover   
					Motor and Blower Assembly   
					Air Shutter Stationary Part   
					Air Shutter Disc   
					62899-001   
					60172-002   
					61874   
					61770-002   
					62715-003   
					63228-001   
					63062-001   
					See Chart   
					Pg. 15   
					Air Tube and Housing Assembly   
					Pilot Burner   
					Pilot Burner with Ignitor/Sensor   
					Orifice - Natural Gas   
					• 
					Orifice - L.P. Gas   
					Pilot Orifice (Natural Gas) .024 (.610mm)   
					Pilot Orifice (L.P. Gas) .018 (.457mm)   
					Thermocouple   
					60680-002   
					60680   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					60987   
					Flame Spreader Assembly   
					Piezo Ignitor   
					61818   
					• 
					63213-001   
					60270-002   
					60246-004   
					62243-003   
					63212-001   
					62672-004   
					63220   
					Gas Valve - (Standing Pilot)   
					Gas Valve - ( Electronic Pilot)   
					Ignition Control   
					• 
					• 
					Spark Generator Bracket   
					Valve Spring Kit   
					• 
					• 
					• 
					• 
					• 
					Valve Spring Kit   
					• 
					Lead Wire Assembly - Ignitor   
					Ignitor Wire   
					62947-001   
					63217-004   
					62261   
					Electrode Assembly UL   
					Gas Valve (Direct Ignition)   
					Ignition Cable - High Voltage   
					Ignition Cable - DI   
					• 
					• 
					• 
					• 
					• 
					62374-002   
					61987   
					61990   
					Wire Assembly - Low Voltage   
					61986   
					20   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				PARTS LIST - P265/P265F SERIES GAS BURNERS   
					Qty   
					Part No.   
					Description   
					Req’d   
					62903-001   
					60182-002   
					60186-004   
					100986-002   
					62899   
					Control Box/Strap Assembly   
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Power Cord Assembly   
					• 
					Transformer - 24V   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Relay   
					• 
					• 
					• 
					Control Box Cover   
					• 
					• 
					• 
					60172-002   
					620901-001   
					61770-002   
					62715-001   
					62715-003   
					62715-005   
					62715-002   
					62715-004   
					62715-006   
					62715-007   
					21724-011   
					100428-002   
					21760-011   
					60270-002   
					62246-004   
					62374-004   
					62898-001   
					60249   
					Motor/Blower (inch end switch)   
					Air Shutter - Stationary Position   
					Air Shutter - Disc   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Air Tube/Housing Assembly   
					Air Tube/Housing Assembly   
					Air Tube/Housing Assembly   
					Air Tube/Housing Assembly   
					Air Tube/Housing Assembly   
					Air Tube/Housing Assembly   
					Air Tube/Housing Assembly   
					Adjustable Flange w/Gasket   
					Flange Gasket   
					5” (127mm)   
					8” (203.0mm)   
					11”(279.4mm)   
					5”(127mm)   
					8” (203.0mm)   
					11”(279.4mm)   
					5”(127mm)   
					8” (203.0mm)   
					11”(279.4mm   
					5” (127mm)   
					8” (203.0mm)   
					11”(279.4mm)   
					5” (127mm)   
					8” (203.0mm)   
					11”(279.4mm)   
					5” (127mm)   
					8” (203.0mm)   
					11”(279.4mm)   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Base Assembly   
					Gas Valve - Standing Pilot   
					Gas Valve - EP Pilot   
					• 
					• 
					• 
					• 
					Gas Valve - Direct Spark (DI)   
					Orifice Holder - 5” (127mm) Units   
					Orifice Holder - 8” (203.2mm) Units   
					Orifice Holder - 11” (279.4mm) Units   
					Orifices - Natural gas   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					60250   
					See Chart   
					See Chart   
					61455   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Orifices - LP gas   
					Bulkhead Union   
					63432-001   
					60944   
					Venturi - Less Fixed Flamespreader   
					Venturi - Less Fixed Flamespreader   
					Venturi - With Fixed Flamespreader   
					Venturi - With Fixed Flamespreader   
					Thermocouple-5” (127mm) & 8” (203.2mm) Units   
					Thermocouple - 11” (279.4) Units   
					Pilot Burner   
					61403   
					• 
					• 
					• 
					• 
					61637-003   
					60987   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					60280   
					63228-001   
					63062-001   
					60680-002   
					60680   
					Pilot Burner   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Pilot Orifice - Natural gas   
					Pilot Orifice - LP gas   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					63210-001   
					63212-001   
					62261-002   
					61818   
					Electrode Assembly - Piezo System   
					Electrode Bracket - Piezo   
					Electrode Assembly - DI   
					Flamespreader   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					62243-003   
					101243-001   
					63213-001   
					63217-003   
					62947-003   
					63375-001   
					62955-001   
					62956-001   
					Control - EP Pilot   
					Control - Direct Spark (DI)   
					Spark Generator - Pushbutton Piezo   
					Ignitor Wire - Piezo Electrode   
					Ignition Wire Assembly   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Wire Set   
					Burner Conversion Kit - Nat to LP   
					Burner Conversion Kit - LP to Nat   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					21   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				PARTS LIST - P250AF SERIES GAS BURNERS   
					No.   
					P250AF   
					P250AF EP   
					P250AF DI   
					Part No.   
					Description   
					Req’d   
					62903-001   
					60182-002   
					60186-004   
					100986-002   
					62899   
					Control Box/Strap Assembly   
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					1 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Power Cord Assembly   
					Transformer-24V   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Relay   
					Control Box Cover   
					60172-002   
					62901-001   
					61770-002   
					62715-003   
					63228-001   
					63062-001   
					62261   
					Motor/Blower (inch end switch)   
					Air Shutter - Stationary Portion   
					Air Shutter - Disc   
					Air Tube/Housing Assembly   
					Pilot Burner   
					Pilot Burner   
					• 
					Electrode Assembly - DI   
					Electrode Assembly - DI   
					Orifices - Natural gas   
					Orifices - LP gas   
					• 
					• 
					• 
					• 
					62261-002   
					See Chart   
					See Chart   
					60680-002   
					60680   
					• 
					• 
					• 
					• 
					• 
					• 
					Pilot Orifice - Natural gas   
					Pilot Orifice - LP gas   
					Thermocouple   
					• 
					• 
					• 
					• 
					• 
					60987   
					61818   
					Flamespreader   
					• 
					• 
					63213-001   
					60270-002   
					62246-004   
					62374-004   
					62243-003   
					101243-001   
					63212-001   
					62955-001   
					62956-001   
					63217-004   
					62947-003   
					63375-001   
					Piezo Spark Generator   
					Gas Valve - Standing Pilot   
					Gas Valve - EP Pilot   
					Gas Valve - Direct Spark (DI)   
					Control - EP Pilot   
					• 
					• 
					• 
					• 
					Control - Direct Spark (DI)   
					Spark generator   
					• 
					• 
					• 
					• 
					Burner Conversion Kit - Nat to LP   
					Burner Conversion Kit - LP to Nat   
					Ignitor Wire - Piezo Electrode   
					Ignition Wire Assembly   
					Wire Set   
					• 
					• 
					• 
					• 
					• 
					22   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Notes   
					23   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				WAYNE COMBUSTION SYSTEMS   
					801 GLASGOW AVE.   
					FORT WAYNE, IN 48803   
					LIMITED WARRANTIES FOR OIL AND   
					GAS BURNERS, MADE BY WAYNE AND   
					USED IN RESIDENTIAL INSTALLATIONS   
					WAYNE COMBUSTION SYSTEMS (“WAYNE”) warrants to those who purchase its Oil Burner Models for resale or   
					for incorporation into a product of resale, that its burner is free from defects in material and workmanship under normal   
					use and service for thirty-six (36) months from the date of manufacture. ALL GAS BURNERS manufactured by   
					“WAYNE” will be similarly warranted for eighteen(18) months from date of manufacture except where original   
					manufacture offers a greater warranty. (Reference #6 below) THESE LIMITED WARRANTIES DO NOT APPLY   
					UNLESS THE BURNER COVERED BY IT IS PROPERLY INSTALLED BY A QUALIFIED, COMPETENT   
					TECHNICIAN, WHO IS LICENSED WHERE STATE AND/OR LOCAL CODES PREVAIL, AND WHO IS   
					EXPERIENCED IN MAKING SUCH INSTALLATIONS, IN ACCORDANCE WITH NFPA #31 OF THE NATIONAL FIRE   
					PROTECTION ASSOCIATION AND IN ACCORDANCE WITH ALL LOCAL, STATE AND NATIONAL CODES.   
					Any IN-WARRANTY burner component which is defective in material or workmanship will be either repaired or   
					replaced as follows:   
					1. Fuel units, motors, transformers, gas valves, and controls should be returned to an authorized service station or   
					distributor of WAYNE for determination of applicability of this LIMITED WARRANTY as to either repair or   
					replacement, where said service station or distributor is reasonably available in the customer’s locality. The   
					manufacturers of burner components regularly publish and distribute listings showing the locations of their network   
					of service stations. Where such local service is NOT available for the burner components described above or other   
					burner parts are involved, these items should be returned, freight prepaid, to WAYNE Service Department, 801   
					Glasgow Ave, Fort Wayne, Indiana 46803.   
					2. Burners and/or component(s) determined to be covered under this LIMITED WARRANTY by WAYNE shall be   
					repaired or replaced at WAYNE’s sole option.   
					3. WAYNE is not responsible for any labor cost for the removal and replacement of said burner or burner components   
					and equipment associated therewith.   
					4. A burner so repaired will then carry the LIMITED WARRANTY equal to the unexpired portion of the original   
					burner LIMITED WARRANTY.   
					5. If inspection by WAYNE does NOT disclose any defect covered by this LIMITED WARRANTY, the burner or   
					burner component(s) will be either repaired or replaced at the expense of the customer and WAYNE’s regular   
					charges will apply.   
					6. If the original manufacturer of a burner component offers a warranty greater than either of our LIMITED   
					WARRANTIES described above, then this portion will be added to our LIMITED WARRANTY.   
					This LIMITED WARRANTY does NOT cover products which have been damaged as the result of accident, abuse,   
					misuse, neglect, improper installations, improper maintenance or failure to operate in accordance with WAYNE’s   
					written instructions.   
					These LIMITED WARRANTIES do not extend to anyone except the first purchaser at retail and only when the burner   
					is in the original installation site.   
					IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE SHALL BE   
					LIMITED TO THE DURATION OF THE LIMITED EXPRESS WARRANTIES CONTAINED HEREIN. WAYNE   
					EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES   
					OF ANY NATURE FOR BREACH OF ANY EXPRESS OR IMPLIED WARRANTY.   
					Some states do not allow limitation on how long an implied warranty lasts, so the above limitation may not apply to you.   
					Also, some states do not allow the exclusion or limitation of incidental or consequential damages, so the above   
					limitation or exclusion may not apply to you. WAYNE neither assumes or authorizes any person to assume for WAYNE   
					any other liability or obligation in connection with the sale of these products. This warranty gives you specific legal   
					rights, and you may also have other rights which vary from state to state.   
					24   
					MSR & MSR-DC 22019-003 Rev. C 08/15/00   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |