INSTALLATION
INSTRUCTIONS
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
DIRECT VENT
MULTI-OPEN SERIES
A French manual is available upon request. Order P/N 700,031CF
Ce manuel d’installation est disponible en francais, simplement en
faire la demande. Numéro de la pièce 700,031CF.
DIRECT VENT GAS FIREPLACE HEATERS
P/N 700,031M REV. C 11/2006
This appliance may be installed in an aftermarket
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes. This appliance is only for use with
the type of gas indicated on the rating plate. This
appliance is not convertible for use with other
gases, unless a certified kit is used.
MODELS
Millivolt Models
Electronic Models
SSDVST-CNM
SSDVPF-CNM
SSDVST-CNE
SSDVPF-CNE
In the Commonwealth of Massachusetts:
• Installation must be performed by a licensed plumber or
gas fitter;
• See Table of Contents for location of additional Com-
monwealth of Massachusetts requirements.
WARNING: IF THE INFORMATION IN THIS
MANUAL IS NOT FOLLOWED EXACTLY, A FIRE
OR EXPLOSION MAY RESULT CAUSING PROP-
ERTY DAMAGE, PERSONAL INJURY OR LOSS
OF LIFE.
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN
SUIVRE LES INSTRUCTIONS DONNÉ DANS CETTE
NOTICE POUR RÉDUIRE AU MINIMUM LE RISQUE
D'INCENDIE OU POUR ÉVITER TOUT DOMMAGE
MATÉRIEL, TOUTE BLESSURE OU LA MORT.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni
utiliser d'essence ni d'autre vapeurs ou liquides
inflammables dans le voisinage de cet appareil ou
de tout autre appareil.
FOR YOUR SAFETY: Do not store or use gasoline
or other flammables or liquids in the vicinity of
this or any other appliance.
FOR YOUR SAFETY: What to do if you smell gas:
POUR VOTRE SÉCURITÉ: Que faire si vous sentez
une odeur de gaz:
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow your gas suppliers
instructions.
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucun interrupteur. Ne pas vous
servir des téléphones se trouvant dans le bati-
ment où vous vous trouvez.
• Evacuez la piéce, le bâtiment ou la zone.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le service dos incendies.
• If your gas supplier cannot be reached, call
the fire department.
Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
L'installation et service doit être exécuté par un
qualifiéinstalleur,agencedeserviceoulefournis-
seur de gaz.
OTL Report No. 116-F-32-5
Download from Www.Somanuals.com. All Manuals Search And Download.
These fireplaces are designed as supplemen-
tal heaters. Therefore, it is advisable to have
an alternate heat source when installed in a
dwelling.
Manifold Gas Supply Pressure
(millivolt models)
• • Burner Orifice Sizes (all models)
Elevation
Natural Gas Propane Gas
Feet (meters)
drill size (inches) drill size (inches)
Fuel #
Low
High
0-4500
(0-1372)
#44 (.086")
60J8001 •
#55 (.052")
*
*
Natural (Lo) 2.2" WC
(Hi) 3.5" WC
(.87 kPa)
19L5201 •
Millivolt Models - The millivolt appliances are
manually controlled and feature a spark igniter
(piezo) that allows the appliance's pilot gas to
be lit without the use of matches or batteries.
This system provides continued service in the
event of a power outage.
Gas
(.55 kPa)
* Standard size installed at factory
• Part /Cat. Number
Table 6 • • Each model has two burners & 2 Orifices
(Lo) 6.3" WC (Hi) 10.0" WC
(1.57 kPa) (2.49 kPa)
Propane
Table 4
GasValveDiagrams-SeeFigure1 forMillivolt
models and Figure 2 For Electronic Models.
Manifold Gas Supply Pressure
(electronic models)
Millivolt models come standard with a manu-
ally-modulated gas valve; flame appearance and
heat output can be controlled at the gas valve.
The BTU Input for these appliances is shown
in Table 1.
SIT Millivolt Gas Valve
Fuel #
Maximum Manifold Pres-
sure
HI/LO Variable
Flame Height
Adjustment
Inlet Pressure Tap
Manifold Pressure Tap
Natural Gas
Propane
(Hi) 3.5" WC (.87 kPa)
(Hi) 10.0" WC (2.49 kPa)
O U T I N
Input (BTU) Manually-Modulated Gas
Valves (millivolt models)
Table 5
I
H
Models
Fuel Type
Input Rate
(BTU / HR)
O
F
P
I
L
O
L
O
W
T
Test gauge connections are provided on the
front of the millivolt gas control valve, identi-
fied IN for the inlet and OUT for the manifold
side. A 1/8" NPT Test gauge connection
is provided at the inlet and outlet side of
the electronic gas control valve.
O
N
P
I
L
Natural or
Propane Gas
37,500 high
30,000 low
SSDVST
SSDVPF
T
Main Gas Control Knob
OFF/PILOT/ON
Pilot Adjustment
Screw
Table 1
Electronic Models - Electronic models have
a fixed rate gas valve. The BTU input for the
electronic models is shown in Table 2.
Figure 1
Theseappliancesmustbeisolatedfromthe
gas supply piping system (by closing their
individualmanualshut-offvalve)duringany
pressure testing of the gas supply piping
system at test pressures equal to or less
than 1/2 psig (3.5 kPa).
BTU Input - Electronic Models
Honeywell Electronic Gas Valve
Input (BTU) - Fixed Rate
(electronic models)
Manifold Pressure
Port
ON / OFF Switch
Inlet
Models
Fuel Type
Input Rate
(BTU / HR)
Theseappliancesandtheirindividualshut-
off valves must be disconnected from the
gassupplypipingsystemduringanypres-
sure testing of that system at pressures
greater than 1/2 psig (3.5 kPa).
Pressure
Port
Natural or
Propane Gas
SSDVST
SSDVPF
37,500
Table 2
Orifice Sizes - Sea Level to High Altitude
(All Models)
Gas Pressure - All Models
Electronic Gas
Control Valve
Tables 3, 4 and 5 show the appliances' gas
pressure requirements:
These appliances are tested and approved for
installation at elevations of 0-4500 feet (0-1372
meters)abovesealevelusingthestandardburner
orifice sizes (marked with an "*" in Table 6). For
elevations above 4500 feet, contact your gas
supplier or qualified service technician . Install
the appliance according to the regulations of
the local authorities having jurisdiction and, in
the USA, the National Fuel Gas Code NFPA 54
/ ANSI Z223.1 - latest edition or, in Canada, the
CAN1-B149.1 and .2 codes - latest edition.
Figure 2
Inlet Gas Supply Pressure
(all models)
Fuel #
Minimum
Maximum
New York City, New York (MEA)
5.0" WC
(1.24 kPa)
10.5" WC
(2.61 kPa)
Natural Gas
Installation of these fireplaces are approved
for installation in New York City in the US state
of New York.
11.0" WC
(2.74 kPa)
13.0" WC
(3.23 kPa)
Propane
Table 3
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Note: The following requirements reference various Massachusetts
and national codes not contained in this document.
Inspection
The state or local gas inspector of the side wall horizontally vented gas
fueledequipmentshallnotapprovetheinstallationunless,uponinspection,
the inspector observes carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Requirements for the Commonwealth of Massachusetts
Forallsidewallhorizontallyventedgasfueledequipmentinstalledinevery
dwelling, building or structure used in whole or in part for residential
purposes, including those owned or operated by the Commonwealth and
where the side wall exhaust vent termination is less than seven (7) feet
above finished grade in the area of the venting, including but not limited
to decks and porches, the following requirements shall be satisfied:
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment Not Required
To Be Vented” in the most current edition of NFPA 54 as adopted by
the Board; and
Installation Of Carbon Monoxide Detectors
• Product Approved side wall horizontally vented gas fueled equipment
installed in a room or structure separate from the dwelling, building
or structure used in whole or in part for residential purposes.
At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard
wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed.
In addition, the installing plumber or gasfitter shall observe that a bat-
tery operated or hard wired carbon monoxide detector with an alarm is
installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall
be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon
monoxide detectors.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally
vented gas equipment provides a venting system design or venting sys-
tem components with the equipment, the instructions provided by the
manufacturer for installation of the equipment and the venting system
shall include:
In the event that the side wall horizontally vented gas fueled equipment
is installed in a crawl space or an attic, the hard wired carbon monoxide
detector with alarm and battery back-up may be installed on the next
adjacent floor level.
• Detailed instructions for the installation of the venting system design
or the venting system components; and
• A complete parts list for the venting system design or venting sys-
tem.
In the event that the requirements of this subdivision can not be met at
the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, how-
ever, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally
vented gas fueled equipment does not provide the parts for venting the
fluegases, butidentifies“specialventingsystems”, thefollowingrequire-
ments shall be satisfied by the manufacturer:
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certified.
• Thereferenced“specialventingsystem”instructionsshallbeincluded
with the appliance or equipment installation instructions; and
• The “special venting systems” shall be Product Approved by the
Board, and the instructions for that system shall include a parts list
and detailed installation instructions.
Signage
A metal or plastic identification plate shall be permanently mounted to
the exterior of the building at a minimum height of eight (8) feet above
grade directly in line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment. The sign shall read, in
print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
A copy of all installation instructions for all Product Approved side wall
horizontally vented gas fueled equipment, all venting instructions, all
parts lists for venting instructions, and/or all venting design instructions
shall remain with the appliance or equipment at the completion of the
installation.
• Installation and repair must be done by a plumber or gas fitter licensed
in the Commonwealth of Massachusetts.
• The flexible gas line connector used shall not exceed 36 inches (92
centimeters) in length.
• The individual manual shut-off must be a T-handle type valve.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY & WARNIING INFORMATION
IMPORTANT
AVERTISSEMENT
Surveiller les enfants. Garder les
vêtements, lesmeubles, l'essence
ouautres liquidesà vapeur inflam-
mables lin de l'appareil.
These appliances must not be
connected to a chimney or flue
serving a separate solid fuel
burning appliance.
WARNING
If the information in this
manual is not followed
exactly,afireorexplosion
may result causing prop-
erty damage, personal
injury or loss of life.
WARNING
Do not place clothing or other
flammable materials on or near
this appliance.
WARNING
This appliance may only be fitted
with doors certified for use with
the appliance.
WARNING
AVERTISSEMENT
Pourutilisationuniquementavec
les portes en verre certifiêes
avec l'appareil.
These fireplaces are vented heat-
ers. Do not burn wood or other
material in these appliances.
WARNING
Failuretocomplywiththeinstal-
lationandoperatinginstructions
provided in this document will
result in an improperly installed
andoperatingappliance,voiding
its warranty. Any change to this
appliance and/or its operating
controlsisdangerous. Improper
installation or use of this appli-
ance can cause serious injury or
deathfromfire,burns,explosion
or carbon monoxide poisoning.
WARNING
WARNING
This appliance is only for use
with the type of gas indicated on
the rating plate. This appliance
is not convertible for use with
other gases, unless a certified
kit is used.
Carbon monoxide poisoning:
early signs of carbon monoxide
poisoning are similar to the flu
withheadaches,dizzinessand/or
nausea. If you have these signs,
obtainfreshairimmediately.Turn
offthegassupplytotheappliance
and have it serviced by a quali-
fied professional, as it may not
be operating correctly.
AVERTISSEMENT
WARNING
Cet appareil doit être utilisé
uniquement avec les types de
gaz indiqués sur la plaque sig-
nalétique. Ne pas l'utiliser avec
d'autres gaz sauf si un kit de con-
version certifié est installé.
Do not attempt to alter or modify
the construction of the appli-
ance or its components. Any
modification or alteration may
void the warranty, certification
and listings of this unit.
WARNING
Do not use these appliances if
any part has been under water.
Immediately call a qualified,
professional service technician
to inspect the appliances and to
replace any parts of the control
system and any gas controls
which have been under water.
WARNING
Children and adults should be
alerted to the hazards of high
surface temperatures. Use
caution around the appliance
to avoid burns or clothing igni-
tion. Young children should be
carefully supervised when they
are in the same room as the
appliance.
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks
around the appliance with noncombustible
material and wherever cold air could enter
the room. It is especially important to insulate
outside chase cavity between studs and under
floor on which the appliance rests, if floor is
above ground level. Gas line holes and other
openings should be caulked or stuffed with
unfaced fiberglass insulation. If the fireplace
is being installed on a cement slab, in cold
climates, a sheet of plywood or other raised
platform can be placed underneath to prevent
conductingcoldupintotheroom.Italsohelpsto
sheetrockinsidesurfacesandtapeformaximum
air tightness and caulk firestops.
AVERTISSEMENT
Ne pas se servir de cet appar-
eil s'il a été plongé dans l'eau,
complètement ou en partie.
Appeler un technicien qualifié
pour inspecter l'appareil et rem-
placer toute partie du système de
contrôle et toute commande qui
ont été plongés dans l'lau.
Note: An Optional Screen Door or
ScreenPanelfortheglassisavail-
able(seeHomeownersManualfor
ordering information).
5
Download from Www.Somanuals.com. All Manuals Search And Download.
LOCATION
MANUFACTURED HOME
REQUIREMENTS
In selecting the location, the aesthetic and functional use of the appliance are primary concerns.
However, vent system routing to the outside atmosphere and access to the fuel supply are also im-
portant. Consideration should be given to traffic ways, furniture, draperies, etc., due to high surface
temperatures (see illustrations). The location should also be free of electrical, plumbing or other
heating / air conditioning ducting.
This appliance may be installed in an after-
market permanently located, manufactured
home (USA only) or mobile home, where not
prohibited by local codes.
These direct vent appliances are uniquely suited for installations requiring a utility shelf positioned
directly above the fireplace. Utility shelves like these are commonly used for locating television sets
and decorative plants. Be aware that this is a heat producing appliance. Objects placed above
the unit are exposed to elevated temperatures.
This appliance may be installed as an OEM
installation in a manufactured home (USA
only) or mobile home and must be installed
in accordance with the manufacturer's
instructions and the Manufactured Home
Construction and Safety Standard, Title 24
CPF, Part 3280 or Standard for Installa-
tion in Mobile Homes, CAN/CSA Z240 MH.
If a shelf is to be installed above appliance, see Shelf Height Minimum Clearances (Figure 8 on
Page 9).
The appliance should be mounted on a fully supported base extending the full width and depth of the
appliance. The appliance may be located on or near conventional construction materials. However, if
installed on combustible materials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering
the entire bottom surface of the appliance must be used.
Cet appareil peut être installé comme du
matérield'originedansunemaisonpréfabri-
quée(É.-U.seulement)oumobile etdoitêtre
installé selon les instructions du fabricant
et conformément à la norme Manufactured
HomeConstructionandSafetyStandard,Title
24 CPF, Part 3280 ou à la norme CAN/CSA
Z240 Série MM, Maisons Mobiles.
Cet appareil peut être installé dans un maison
préfabriquée (É.-U. seulement) ou mobile déjà
installée à demeure si les réglements locaux
le permettent.
Offset Venting
Vertical
Venting
(one end flush
with wall)
Manufactured Home installations must be
installed in accordance with these instructions
and the following standards / codes:
• Manufactured Home Construction and
Safety Standard Title 24 CFR, Part 3280, or
the current Standard for Fire Safety Criteria
for Manufactured Home Installations, Sites
and Communities ANSI / NFPA 501A in the
USA, andCAN/CSAZ240MHMobileHome
Standard in Canada
Vertical
Vent
Horizontal Vent
(top vent)
Horizontal Vent
(side vent)
• (when applicable) The American National
Standard for Manufactured Homes (NCS-
BCS / ANSI A225.1 - latest edition).
Figure 3
CAUTIONS
ManufacturedHomeInstallations:Ensurethatthecrossmembersarenotcutorweakenedduringinstallation.
The structural integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.
This appliance must be grounded to the chassis of the manufactured home in accordance with local codes
or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70 - latest edition or the
Canadian Electrical Code CSA C22.1 - latest edition.
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
VENT TERMINATION CLEARANCES
Horizontal Vent Termination Clearances
These instructions should be used as a guideline and do not supersede local codes in any
way. Install vent according to local codes, these instructions, the current National Fuel Gas
Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and -B149.2 in
Canada.
The horizontal vent termination must have
a minimum of 3" (76 mm) clearance to any
overhead combustible projection of 2 1/2" (64
mm) or less. See Figure 5. For projections
exceeding 2 1/2" (64 mm), see Figure 5. For
additional vent location restrictions refer to
Figure 6 on Page 8.
Terminate multiple vent terminations according to the installation codes listed above.
Terminate single vent caps relative to building components according to Figure 4.
Horizontal Vent Termination Clearances
Vertical Vent Termination Clearances
Combustible Projection
2-1/2 inches or less in length
TERMINATION HEIGHTS FOR VENTS ABOVE
Termination Heights For Vents
FLAT OR SLOPED ROOFS
Combustible Projection greater
than 2-1/2 inches in length
Above Flat Or Sloped Roofs
Horizontal Overhang
Ref. NFPA 54 / ANSI Z223.1, 7.6
Ventilated
2 FT
Vertical
Wall
Roof Pitch
Flat to 6/12
* Feet *Meters
Soffit
Unventilated
Soffit
MIN.
2 FT MIN.
1.0
1.25
1.5
2.0
2.5
3.25
4.0
5.0
6.0
7.0
7.5
8.0
0.3
Lowest
Discharge
Opening
6/12 to 7/12
0.38
0.46
0.61
0.76
0.99
1.22
1.52
1.83
2.13
2.29
2.44
3"
18"
12"
(76 mm)
Vent
Termination
(457 mm)
(305 mm)
7/12 to 8/12
8/12 to 9/12
H*
Storm Collar
Flashing
X
9/12 to 10/12
10/12 to 11/12
11/12 to 12/12
12/12 to 14/12
14/12 to 16/12
16/12 to 18/12
18/12 to 20/12
20/12 to 21/12
Note - See Figure 34 on
Page 20 for the exterior
wall recess allowances
of the square horizontal
termination.
12
Roof Pitch is X/12
Termination Kit
1 inch (25.4 mm) Minimum
Clearance to Combustibles
Side Elevation View
Concentric
Vent Pipe
*H = MINIMUM HEIGHT FROM ROOF TO
LOWEST DISCHARGE OPENING OF VENT
Figure 5
The vent / air intake termination clearances above the high
side of an angled roof is as shown in the following chart:
Figure 4 - Gas Vent Rule
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
VENT TERMINATION CLEARANCES
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS
See Item D in the Text Below.
Center Line
Exterior Wall
Inside
Corner Detail
of Termination
*18”
Horizontal
G
Termination
18”
V
Ventilated Soffit
A
Inside Corner
= 9" in U.S.
= 12" in Canada
A
DETAIL D
H
3 ft.
X
B
B
B
E
D
C
C
A
A
V
V
Fixed
Operable
Window
V
L
V
Closed
3 ft.
Window
V
F
J
M
V
C
C
B
B
V
I
A
X
= Air Supply Inlet
= Vent Terminal
= Area where Terminal is NOT permitted
V
Minimum Clearances
Canadian Installation *
US Installation **
A = Clearance above grade, veranda, porch, deck 12 inches (30 cm) *
or balcony.
12 inches (30 cm) **
B = Clearance to window or door that may be 6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW),
6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW),
opened.
12 in. (30 cm) for appliances > 10,000 BTU/hr (3kW) and < 9 in. (23 cm) for appliances > 10,000 BTU/hr (3kW) and <
100,000 BTU/hr (30kW), 36 inches (91 cm) for appliances 50,000 BTU/hr (15kW), 12 inches (30 cm) for appliances
> 100,000 BTU/hr (30kW)*
> 50,000 BTU/hr (15kW)*
C = Clearance to permanently closed window
12 inches (305 mm) recommended to prevent window 9 inches (229 mm) recommended to prevent window
condensation
condensation
D = Vertical clearance to ventilated soffit located 18 inches (458 mm)
abovetheterminalwithinahorizontaldistanceof18
18 inches (458 mm)
in. (458 mm) from the center line of the terminal
E = Clearance to unventilated soffit
F = Clearance to outside corner
G = Clearance to inside corner
12 inches (30 cm)
5 inches (12.7 cm)
6 in. (15 cm)
12 inches (30 cm)
5 inches (12.7 cm)
6 in. (15 cm)
H = Clearance to each inside of center line extended 3 feet (91 cm) within a height of 15 feet above the meter / 3 feet (91 cm) within a height of 15 feet above the meter
above meter / regulator assembly
regulator assembly *
/ regulator assembly **
I = Clearance to service regulator vent outlet
3 feet (91 cm) *
3 feet (91 cm) **
J = Clearance to non-mechanical air supply inlet 6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 12 6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 9
to building or the combustion air inlet to any other in. (30 cm) for appliances > 10,000 BTU/hr (3kW) and < in. (23 cm) for appliances > 10,000 BTU/hr (3kW) and <
appliance
100,000 BTU/hr (30kW), 36 inches (91 cm) for appliances 50,000 BTU/hr (15kW), 12 inches (30 cm) for appliances
> 100,000 BTU/hr (30kW)*
> 50,000 BTU/hr (15kW)*
K = Clearance to mechanical air supply inlet
6 feet (1.8 meters) *
3 feet (91 cm) above, if within 10 feet (3 m) horizon-
tally**
L = Clearance above paved sidewalk or paved 7 feet (2.13 m) ‡
driveway located on public property
7 feet (2.13 m) ‡
M = Clearance under veranda, porch, deck or 12 in. (30 cm) * ‡
balcony
12 in. (30 cm) ** ‡
* In accordance with the current CSA-B149.1 National Gas and B149.2 Propane Installation Code - Latest Editions.
** In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Codes - Latest Edition.
‡ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
*‡ Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor.
Figure 6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Appliance and Vent Clearances
MINIMUM CLEARANCES TO COMBUSTIBLES
Hearth Extension - A hearth extension is not required with this appliance. If a hearth extension is used,
do not block the lower control compartment access door. Any hearth extension used is for appearance
only and does not have to conform to standard hearth extension installation requirements.
Maintain clearances from appliance to
combustible materials as detailed in Table 7,
withthefollowingexception:Whentheappliance
is installed with one side flush with a wall, the
wall on the other side of the appliance must not
extend beyond the front edge of the appliance.
In addition, when the appliance is installed in
themiddleofaroom,thesidewallssurrounding
the appliance must not extend beyond the front
edge of the appliance. See Figure 3.
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach
the area defined by the appliance front and back faces (black sheet metal). Never allow combustible
materials to be positioned in front of or overlapping the appliance front and back faces. See Figure
57 on Page 30.
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the
appliance front and back faces with the following exception: If the optional radiant panels are
installed, the non-combustible material may cover any portion of the top radiant panel or the air
gaps surrounding the top radiant panel down to the top edge of eyebrow hood. The material must
NOT cover any portion of the glass door or louvered panels.
MINIMUM CLEARANCES Inches (millimeters)
Sides
Top Spacers
Floor
1/2 (13)
0 (0)
Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See
Figure 7. Mantels constructed of non-combustible materials may be installed at any height above the
appliance opening; however, do not allow anything to hang below the hood.
0 (0)
Bottom of Appliance
To Ceiling
64 (1626)
Mantel Depth
Minimum Mantel Clearances
14 (356)
3 (76) Top *
1 (25.4) Sides & Bottom
Vent
12 (305)
10 (254)
8 (203)
6 (152)
inches (millimeters)
SERVICE CLEARANCES Feet (meters)
Front & Back Faces
3 ft. (0.9 m)
Table 7
Top of
Appliance
*Note: 3 in. (75 mm) above any horizontal /
inclined vent component.
4 (102)
12 10
8
6
4
2
Side Clearances
(305) (254) (203) (152) (102) (51)
Combustible materials may project beyond the
sides of the fireplace opening as long as they
are kept within the shaded areas illustrated in
Figure 9.
Hood
Front or Rear Face
of Appliance
Figure 7
Combustible Materials Allowed In
Shaded Area “Safe Zone.” Com-
bustible Walls shown in dark gray.
At 14" mini-
Do not insulate this space
above the appliance.
Top View
Fireplace
At 8-1/4" side
wall clearance,
a combustible
wall can project
12"
mum side wall
clearance, a
Do not insulate this space
above the appliance.
combustible wall
can project to any
length.
Shelf Height
(see table)
Shelf Height
(see table)
45o
5
(127)
Shelf Above Fireplace With Side Venting
Shelf Above Fireplace With Top Venting
To achieve the lowest possible shelf height, use the side vent outlet. Do not insulate space between
appliance and the area above it. Maintain the minimum height from appliance base to the underside
of combustible materials (used to construct a utility shelf) as shown here.
12 (305)
19 (483)
SSDVST & SSDVPF Shelf Height - Inches (millimeter)
Side Vent - Straight Out Back
Secure Vent & Secure Flex
41-1/8 (1045)
Top Vent - with One 90 Degree Elbow
Protected wall
shown in white
14
(356)
8-1/4
(209)
Secure Vent
Secure Flex
Minimum Distance to
Unprotected Side Wall
53-7/8 (1366)
55-5/8 (1410)
Inches (millimeters)
Figure 8 - Shelf Height Minimum Clearances
Figure 9
9
Download from Www.Somanuals.com. All Manuals Search And Download.
If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed. Headers may be in direct contact
with the appliance top spacers but must not be
supportedbythemornotchedtofitaroundthem.
All construction above the appliance must be
self supporting, DO NOT USE THE APPLIANCE
FOR STRUCTURAL SUPPORT.
DETAILED INSTALLATION STEPS
Proper Sizing of Gas Line
1. Remove the shipping carton.
2. Remove the top louvered panel and locate the
pressure relief plates.
Properly size and route the gas supply line
from the supply regulator to the area where the
appliance is to be installed per requirements
outlined in the National Fuel Gas Code, NFPA
54 - latest edition (USA) or B149 - latest edition
(Canada). Neverusegalvanizedorplasticpipe.
Refer to Table 8 for proper sizing of the gas
supply line, if black iron pipe is being used. Gas
lines must be routed, constructed and made
of materials that are in strict accordance with
local codes and regulations. We recommend
that a qualified individual such as a plumber
or gas fitter be hired to correctly size and route
the gas supply line to the appliance. Installing
a gas supply line from the fuel supply to the
applianceinvolvesnumerousconsiderationsof
materials,protection,sizing,locations,controls,
pressure,sediment,andmore.Certainlynoone
unfamiliarandunqualifiedshouldattemptsizing
or installing gas piping.
3. Lift the pressure relief plates and remove
the cardboard from beneath each plate (be
careful not to damage the white gasket). See
Figure 10.
* NOTE: INSTALLATION DIAGRAMS AND
INSTRUCTIONS SHOW THE FRONT OF
THE APPLIANCE AS THE SIDE WHICH HAS
VALVE ACCESS, EXCEPT WHERE NOTED.
Side Nailing Flanges
The fireplace should be secured to the fram-
ing at the side(s) of the appliance using the
factory-provided nailing flanges. Install the 8
nailing flanges as shown in Figure 11 using the
existing screws. Position the fireplace within
the framing. When required, the tabs may be
bent 90 degrees by hand or with the assistance
of a hammer. Use wood screws to secure the
nailing flanges to the framing. See Table 7 on
Page 9 for clearances of framing members
to cabinet parts. The nailing flange itself can
directly contact framing.
Pressure Relief Plates
REMOVE
REMOVE
D
G
BOAR
CARD
D
G
BOAR
CARD
E
USIN
BEFOR
E
USIN
BEFOR
Floor Nailing Tabs - Secure the fireplace to the
floor as shown in Figure 11.
Remove Cardboard Before
Using Appliance
Schedule 40 / Black Iron Pipe
Inside Diameter (Inches)
Schedule 40 Pipe
Length (feet)
Natural
Gas
Propane
Gas
SSDVST Shown (SSDVPF - No nailing
flanges on end with glass panel)
Figure 10
Remove these screws and use them
when installing nailing flanges.
0-10
10-40
1/2
1/2
1/2
3/4
3/4
3/8
1/2
1/2
1/2
1/2
TYPICAL INSTALLATION SEQUENCE
40-100
The typical sequence of installation follows,
however, each installation is unique resulting
in variations to those described.
100-150
150-200
Table 8
SeethePagenumbersreferencesinthefollow-
ing steps for detailed procedures.
Step 1. (Page 10) Construct the appliance fram-
ing. Position the appliance within the framing and
secure with nailing flanges.
Notes:
• All appliances are factory-equipped with a
flexiblegaslineconnectorand1/2inchshutoff
valve (see Figure 47 on Page 27).
Nailing Flanges
Step 2. (Page 10) Route gas supply line to appli-
ance location.
Turn nailing tabs down and secure to floor with 8d
nails or other appropriate fasteners on both sides of
appliance which do not have viewing glass panels.
• See Massachusetts Requirements on Page
3 for additional requirements for installations
in the state of Massachusetts in the USA.
• The gas supply line should Not be connected
to the appliance until Step 6 (Page 27).
• Apipejointcompoundratedforgasshouldbe
used on the threaded joints. Ensure propane
resistant compounds are used in propane
applications. Be very careful that the pipe
compound does not get inside the pipe.
• It is recommended to install a sediment trap
in the supply line as close as possible to the
appliance (see Figure 47). Appliances using
Propane should have a sediment trap at the
base of the tank.
Step 3. (Page 13) Install the vent system and
exterior termination.
Step 4.(Page 25) Field Wiring
Figure 11 - Nailing Flanges
a. Millivolt Appliances – Install the OFF/ON
burner control switch.
Step 2. ROUTING GAS LINE
Routeagaslinealongtheinsideoftherightside
framing as shown in Figure 12. Gas lines must
be routed, constructed and made of materials
that are in strict accordance with local codes
and regulations.
b. Electronic Appliances – Connect 120 VAC
electrical power to the appliance receptacle.
Step 5. (Page 26) Install blower kit (optional
equipment).
Step 6.( Page 27) Make connection to gas
supply.
Step 7. (Page 28) Checkout appliance operation.
Step 8. (Page 28) Install embers, volcanic stone
and embers.
Step 9. (Page 29) Install glass enclosure pan-
els.
Also see
Figures 13 & 14
• Checkwithlocalbuildingofficialforlocalcode
requirements(i.e.arebelowgradepenetrations
of the gas line allowed?, etc).
Step10.(Page29)Adjustburnerprimaryairshutter
to achieve proper flame appearance.
Step 11(Page 30) Install the decorative trim and
hoods.
IMPORTANT: If propane is used, be aware that
if tank size is too small (i.e. under 100-lbs, if
this is the only gas appliance in the dwelling.
Ref. NPFA 58), there may be loss of pressure,
resulting in insufficient fuel delivery (which
can result in sooting, severe delayed ignition
or other malfunctions). Any damage resulting
from an improper installation, such as this, is
not covered under the limited warranty.
3-1/8"
(79 mm)
5-5/8"
(143 mm)
Step 1. FRAMING
FrametheseappliancesasillustratedinFigures
13 & 14. All framing details must allow for a
minimum clearance to combustible framing
members as shown in Table 7 on Page 9.
Figure 12 - ROUTE GAS LINE
10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
FIREPLACE SPECIFICATIONS - SSDVST (SEE-THROUGH)
SPECIFICATIONS
• Inches (millimeters)
•
Minimum Framing Stud Size is 2 x 4
• See side views of fireplace below for
gas line inlet location options.
11-3/8
(289)
Natural & Propane
Gas BTU Input
37,500
(MV Low 30,000)
**25-1/4
(641)
4-1/2" Inner
7-1/2" Outer
10-1/2
(267)
Co-axial DV Vent Size
Vent Framing
- Top Vent With
One 90º Elbow
Dimension A
Vent Center - Top
Vent with one 90
degree elbow
Secure Vent 47-1/8 (1194)
Secure Flex 47-7/8 (1216)
10-1/2
(267)
NOTES
Vent Framing - Rear
Vent With No Elbows
• Annual Fuel Utilization Efficiency
7
(178)
DuetoLennox'ongoingcommitmenttoquality,
all specifications, ratings and dimensions are
subject to change without notice.
12-1/8
(308)
12-1/8
(308)
5-1/8
7
(130)
(178)
5-1/8
(130)
Appliance has a factory-installed vent seal cap
(see Figures 15 & 16 on Page 13) in each flue
outlet.
Vent Center- Side
Vent (no elbows)
12-1/8
(308)
5-1/8
(130)
A
12-1/8
(308)
PRODUCT REFERENCE INFORMATION
A
5-1/8
(130)
26-3/4
(679)
Cat.
No.
Model
Ship
Wt.
Ship.
Volumn
Gas
Line
*41-1/2
(1054)
6-1/4
(159)
26-3/4
(648)
H3333 SSDVST-CNM 282 lbs 52W x 27D x 44-
1/2H (36.2 cu.ft).
H3334 SSDVST-CNE
282 lbs 52W x 27D x 44-
1/2H (36.2 cu.ft).
22-3/4
(578)
48-1/2
(1108)
Gas Line Center of gas line is 3 in. (76 mm) up from floor.
EFFICIENCIES
*
This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm) clearance between framing and unit framing
spacers. (The 41-1/2 in. dimension permits easier fireplace installation, if unit is installed after framing is erected).
** This dimension based on 5/8" drywall. For 1/2" drywall use 25-1/2" (648 mm). The finished dimension should be 26-1/2" (673 mm).
See also, Side Vent Seal Cap note below.
SSDVST
61% (NG)
62 % (LP)
Vertical Venting Through the Ceiling:
Frame ceiling opening -Use a plumb line from the ceiling above the appliance to locate center of the vertical run. Cut and/or frame an opening,
10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center mark (see Figure 19).
72 % (NG)
73 % (LP)
Steady State
• AFUE
68 % (NG)
68 % (LP)
10
(254)
FINISH WALL BRACKET
(Front and back edge of unit top)
12 (305)
FRAMING SPACERS
(Top and Both Sides)
1/2
FLUE
(13)
(Top or Side)
5/8
(16)
40-1/8
(1019)
3-1/2
(89)
Stepped to Accept Drywall(all 4 corners)
3-1/2(89)
Detail fo Finish
Wall Bracket
Top View
2-1/2
(63.5)
1/2
(13)
24
(610)
47-1/8
(1197)
12
(305)
1/2
(13)
4 (102)
10-1/4
(260)
34-3/8
(873)
41
(1041)
2-1/2
(63.5)
Provide additional
space for Side Vent
Seal Cap if installing
against a solid wall.
GAS INLET
24
(610)
FLUE
(Top or Side)
ELECTRICAL
INLETS
37
(940)
ELECTRICAL
INLETS
3
(76)
GAS INLET
ELECTRICAL
INLETS
3 (76)
6-7/8
(175)
10-1/2
(267)
Front View
Louvered Control
Compartment Door
Figure 13
Left Side View
Right Side View
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
FIREPLACE SPECIFICATIONS - SSDVPF (PENINSULA VIEW)
Fireplace Framing Specifications
Minimum Framing Stud Size is 2 x 4
• See right side viewsof fireplace below for gas line inlet location options.
• Inches (millimeters)
SPECIFICATIONS
•
Natural & Propane
Gas BTU Input
37,500
inches (millimeters)
**25-1/4
(641)
11-3/8
(MV Low 30,000)
Minimum Framing
Stud Size is 2 x 4
10-1/2
(267)
Dimension A
Secure Vent 47-1/8 (1194)
Secure Flex 47-7/8 (1216)
4-1/2" Inner
7-1/2" Outer
Co-axial DV Vent Size
Vent Center - Top
Vent with one 90
degree elbow
Vent Framing - Top Vent
With One 90º Elbow
10-1/2
(267)
Vent Framing - Rear Vent
With No Elbows
NOTES
7
(178)
• Annual Fuel Utilization Efficiency
12-1/8
(308)
12-1/8
(308)
7
DuetoLennox'ongoingcommitmenttoquality,
all specifications, ratings and dimensions are
subject to change without notice.
5-1/8
(178)
5-1/8
(130)
(130)
Vent Center- Side
Vent (no elbows)
12-1/8
(308)
Appliance has a factory-installed vent seal cap
(see Figures 15 & 16 on Page 13) in each flue
outlet.
5-1/8
(130)
A
A
5-1/8
(130)
26-3/4
(679)
12-1/8
(308)
Gas Line
PRODUCT REFERENCE INFORMATION
6-1/4
(159)
*41-1/2
(1054)
Center of gas line
is 3 in. (76 mm)
up from floor.
Cat.
No.
Model
Ship
Wt.
Ship.
Volumn
26-3/4
(648)
22-3/4
(578)
Dimension A
Secure Vent - 46-1/2 (1181)
Secure Flex - 48-1/4 (1226)
H3335 SSDVPF-CNM 270 lbs 52W x 27D x 44-
1/2H (36.2 cu.ft).
43-5/8
(1108)
H3336 SSDVPF-CNE
270 lbs 52W x 27D x 44-
1/2H (36.2 cu.ft).
Gas Line Center of gas line is 3 in. (76 mm) up from floor.
*
This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm) clearance between framing and unit framing
spacers. (The 41-1/2 in. dimension permits easier fireplace installation, if unit is installed after framing is erected).
EFFICIENCIES
** This dimension based on 5/8" drywall. For 1/2" drywall use 25-1/2" (648 mm). The finished dimension should be 26-1/2" (673 mm).
See also, Side Vent Seal Cap note below.
SSDVPF
58 % (NG)
61 % (LP)
Vertical Venting Through the Ceiling:
Frame ceiling opening -Use a plumb line from the ceiling above the appliance to locate center of the vertical run. Cut and/or frame an opening,
10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center mark (see Figure 19).
72 % (NG)
73 % (LP)
Steady State
• AFUE
10
(254)
FINISH WALL BRACKET
(Front, back, and left edge of unit top)
Stepped to Accept Drywall on 2 Corners
68 % (NG)
68 % (LP)
FRAMING SPACERS
(Top and Side)
12 (305)
FLUE
(Top or Side)
DETAIL OF
FINISH WALL BRACKET
1/2
(13)
5/8
(16)
40-1/8
(1019)
(89)
3-1/2
Top View
2-1/2
(63.5)
12
(305)
24
(610)
43-5/8
(1108)
1/2 (13)
4 (102)
10-1/4
(260)
37
34-3/8
(873)
(940)
41
(1041)
Provide
additional
space for Side
Vent Seal Cap
if installing
against a solid
wall.
2-1/2
(63.5)
FLUE
(Top or Side)
24
(610)
24
(610)
ELECTRICAL
INLETS
GAS INLET
3 (76)
18-1/4
(464)
Left Side View
6-7/8
(175)
Louvered Control
Compartment Door
Right Side View
Front View
Figure 14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 3. INSTALL THE VENT SYSTEM
WARNING
The VENT SEAL CAP must remain securely installed
on unused vent collar. Failure to do so could result in
leakage of flue products into living space.
These instructions should be used as a guideline and do not supersede
localcodesinanyway.Installventaccordingtolocalcodes,theseinstruc-
tions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the
current standards of CAN/CGA-B149.1 and -B149.2 in Canada.
• Use only approved venting components. See Approved Vent Compo-
nents, Page 2.
• These fireplaces must be vented directly to the outside.
INSTALLING VENT RESTRICTOR
(Top Vent Installations with Vertical Terminations Only)
The vent system must NOT service multiple appliances, and must never
be connected to a flue serving a solid fuel burning appliance. The vent
pipe is tested to be run inside an enclosure (such as a chase). There is
no requirement for inspection openings in the enclosure at any of the
joints in the vent pipe.
A vent restrictor (provided) may be needed with this appliance. If needed,
install the vent restrictor (provided) in the appliance top flue outlet as
shown in Figure 17 when vertically terminating the vent system above
the roof. It may be installed either from inside or outside the appliance,
in the inner fireplace collar. It is press-fitted in place.
REMOVE VENT SEAL CAP
(From the vent that will be used only)
Restrictor
Top Vent - See Figure 15 and Side Vent - See Figure 16
Preparing the Appliance Vent Collar
Each of the appliances' two vent collars are sealed with a seal cap which
must be removed from the vent collar being used. Refer to Figure 15
for top vent installations and Figure 16 for side vent installations and
the following steps to prepare the appropriate collar for use.
VentRestrictor
Installation
(TopVent)
From the vent collar being used, remove the two screws securing the
vent seal cap. Twist the cap counterclockwise. Pull it away from the
appliance and discard, along with the piece of insulation.
Appliance Top
Vent Outlet
Figure 17
Securing Screws
Top Vent
Vent Seal Cap
VENTING SYSTEM - HORIZONTAL OR VERTICAL
(OUTSIDE of
Appliance)
With the appliance secured in framing, determine vent routing and identify
the exterior termination location. The following sections describe vertical
(roof) and horizontal (exterior wall) vent applications. Refer to the section
relating to your installation. A list of approved venting components is
shown on Pages 31 and 32.
Insulation
Cabinet Top
CROSS SECTION
Firebox Top
(INSIDE of Appliance)
TOP VENT SEAL CAP REMOVAL
(TOP VENT INSTALLATIONS ONLY)
Figure 15 -
Vent Seal Cap
Insulation
CROSS SECTION
(OUTSIDE of
Appliance)
(INSIDE of
Appliance)
Side Vent
Securing Screws
Cabinet Back
SIDE VENT SEAL CAP REMOVAL
(SIDE VENT INSTALLATIONS ONLY)
Figure 16 -
13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
VERTICAL TERMINATION SYSTEMS (ROOF)
VENT SECTION LENGTH CHART
VENT SECTION LENGTH CHART
T
O
T
A
L
Nominal
Section Length
(inches)
6
12
24
36
48
Nominal Section
Length (inches)
6
12
24
36
48
See Figure 18 and Figures 27 to 31 and their
associated Vertical Vent Tables illustrate the
vertical venting configurations that are allowed
to be used with these appliances. Secure Vent
pipe applications are shown in these figures;
Secure Flex pipe may also be used. See Page
24. A Vertical Vent Table summarizes each
system’s minimum and maximum vertical and
horizontal length values that can be used to
design and install the vent components in a
variety of applications.
T
O
T
A
L
Net Section
Length (inches)
4 ½ 10 ½ 22 ½ 34 ½ 46 ½
Number of Vent Sections
Net Section
Length (inches)
4 ½ 10 ½ 22 ½ 34 ½
Number of Vent Sections
46
½
Q
T
Y
Height of Vent
Q
T
Height of Vent
*inches
feet
Y
*inches
feet
144
150
12
1
0
1
0
0
1
0
0
1
0
0
0
1
0
1
1
2
0
0
1
0
0
1
1
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
5
5
5
0
0
0
5
6
6
3
3
3
3
0
0
0
4
4
4
0
0
0
4
4
5
5
5
6
6
4
5
5
7
6
7
4.5
9
0.375
0.75
1
2
0
1
2
0
0
1
0
0
1
0
0
1
1
1
2
0
2
3
0
1
0
0
0
0
0
0
1
0
0
0
1
0
0
0
0
0
0
0
0
0
1
0
0
0
0
1
2
1
2
3
2
1
3
3
1
3
12.5
154.5 12.875
160.5 13.375
172.5 14.375
10.5 0.875
15 1.25
19.5 1.625
21 1.75
0
0
Both these vertical vent systems terminate
through the roof. In the USA, the minimum
ventheightabovetheroofand/oradjacentwalls
is specified in ANSI Z223.1 (latest edition); in
Canada, by the current CAN-1 B149 installation
code.Itisalsospecifiedinmajorbuildingcodes.
Always consult your local codes for specific
requirements. A general guide to follow is the
Gas Vent Rule (refer to Figure 4 on Page 7).
177
183
186
14.75
15.25
15.5
0
0
0
0
0
0
22.5 1.875
25.5 2.125
31.5 2.625
34.5 2.875
37.5 3.125
190.5 15.875
196.5 16.375
205.5 17.125
43.5 3.625
0
0
0
1
2
0
0
0
1
2
0
2
0
0
0
0
0
0
1
0
3
2
1
3
207
17.25
45
3.75
211.5 17.625
Vertical (Straight) Installation
46.5 3.875
49.5 4.125
Determine the number of straight vent sec-
tions required. 4-1/2" (114 mm), 10-1/2" (267
mm), 22-1/2" (572 mm), 34-1/2" (876 mm)
and 46-1/2" (1181 mm) net section lengths
are available (see Table 10 and Page 31 - Item
3). Plan the vent lengths so that a section joint
does not occur within the space defined by
ceiling joists or roof rafters. Refer to the Vent
Section Length Chart.
217.5 18.125
229.5 19.125
232.5 19.375
0
0
0
1
0
1
0
0
0
0
1
1
0
0
0
1
0
1
0
0
1
0
1
0
0
1
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
6
6
0
0
5
5
0
0
0
0
0
6
0
6
6
6
0
0
7
7
7
0
0
8
8
0
9
9
7
7
51
4.25
1
0
0
0
0
0
1
1
0
0
0
0
0
1
1
0
1
0
2
0
0
0
0
1
0
2
0
0
0
0
0
2
1
2
3
0
3
0
0
0
1
2
0
1
0
0
0
1
0
0
2
0
2
2
1
0
0
0
2
0
1
0
0
0
0
0
0
0
0
1
1
1
2
0
2
2
3
2
4
3
2
4
3
3
2
4
3
2
4
3
0
5
55.5 4.625
237
19.75
0
6
57
66
4.75
5.25
241.5 20.125
7
7
246
252
264
276
279
20.5
21
7
8
67.5 5.625
7
8
69
72
5.75
6
22
7
8
23
8
8
73.5 6.125
79.5 6.625
23.25
0
6
280.5 23.375
283.5 23.625
289.5 24.125
301.5 25.125
310.5 25.875
8
9
SV4.5CGV-1
SV4.5FA or SV4.5FB
Termination
81
90
6.75
7.5
0
7
Flashing and SV4.5SC
Storm Collar
0
7
91.5 7.625
0
7
93
96
7.75
8
9
9
315
26.5
9
10
7
97.5 8.125
102 8.5
103.5 8.625
325.5 27.125
0
1” (25.4 mm)
Minimum
Clearance to
Combustibles
2
0
1
0
0
0
0
0
0
0
3
3
2
0
0
4
3
4
330
336
345
27.5
28
0
8
0
8
108
114
117
9
28.75
10
10
0
10
11
8
9.5
9.75
0
1
1
0
1
0
0
0
1
2
0
1
0
0
0
0
0
0
0
5
0
1
1
6
0
0
0
0
0
3
3
3
0
4
0
4
2
0
0
0
0
0
0
3
0
4
6
5
4
5
6
4
3
5
349.5 29.125
372 31
-1 ptSV4.5VF
Firestop / spacer
118.5 9.875
126 10.5
130.5 10.875
376.5 31.375
379.5 31.625
418.5 34.875
0
9
11
0
11
9
135
138
11.25
11.5
423
465
35.25
38.75
0
10
0
10 10
40 ft. Max.
139.5 11.625
142.5 11.875
SV4.5L6 / 12 / 24 / 36 / 48
(12.2 M)
Vent Sections
Table 9b
Table 9a
When using Secure
ꢀ
Effective Vent Length
Flex use Firestop / spacer
SF4.5VF
Model
Effective Length
4-1/2"
SV4.5L6
SV4.5L12
SV4.5L24
SV4.5L36
SV4.5L48
See Figure 21
for "support strap"
requirements
* Convert inches into metric equiva-
lent measure, as follows:
10-1/2"
22-1/2"
Millimeters (mm) = Inches x 25.4
Centimeters (cm) = Inches x 2.54
Meters (M) = Inches x .0254
34-1/2"
Figure 18
46-1/2"
14
Table 10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
Vertical (offset) Installation
D. Install firestop / spacer at ceiling - When
usingSecureVent,useSV4.5VFfirestop/spacer
at ceiling joists; when using Secure Flex, use
SF4.5VF firestop / spacer. If there is living space
abovetheceilinglevel,thefirestop/spacermust
be installed on the bottom side of the ceiling.
If attic space is above the ceiling, the firestop /
spacer must be installed on the top side of the
joist.Routetheventsectionsthroughtheframed
opening and secure the firestop / spacer with
8d nails or other appropriate fasteners at each
corner. Remember to maintain 1" (25 mm)
clearancetocombustibles,framingmembers,
andatticorceilinginsulationwhenrunningver-
tical chimney sections. Attic insulation shield
(96K94) may be used to obtain the required
clearances indicated here. See installation
accessories o n Pages 31 and 32.
B. Attach vent components to appliance
-SecureVent SV4.5directventsystemcompo-
nents are unitized concentric pipe components
featuring positive twist lock connections (see
Figure20). Alloftheappliancescoveredinthis
document are fitted with collars having locking
inclined channels. The dimpled end of the vent
components fit over the appliance collar to cre-
ate the positive twist lock connection.
Analyze the vent routing and determine the
number of vent sections and elbows required.
Refer to Vertical Vent Figures and Tables on
Pages 17 and 18 to select the type of vertical
installation desired. Refer to the Vent Section
Length Charts on Page 14 for an aid in se-
lecting vent length combinations. Elbows are
available in 45° and 90° configurations. Refer
to Figure 23 for the SV4.5E45 and SV4.5E90
elbow dimensional specifications.
Align the dimple (four places) of the
upper vent section with the opening
of the locking incline channel on the
lower vent section or appliance col-
lar. Twist vent component clockwise
to engage and seal until arrow and
Where required, a Telescopic Vent Section
(SV4.5LA) may be used to provide the installer
with an option in installing in tight and confined
spaces or where the vent run made up of fixed
length pieces develops a joint in a undesirable
location, or will not build up to the required
length. The SV4.5LA Telescopic Vent Section
dimple align.
Arrow
Dimple
E. Support the vertical vent run sections -
Note-Properventingsupportisveryimportant.
The weight of the vent must not be supported
by the fireplace in any degree.
has an effective length of from 1-
1/2" (38
Locking Incline
Channel
mm) to 7-1/2" (191 mm). The SV4.5LA is fitted
with a locking inclined channel end (identical to
a normal vent section component) and a plain
endwith3pilotholes.Sliptheplainendoverthe
locking channel end of a standard SV4.5 vent
component the required distance and secure
with three screws.
Connected Vent
Sections
Arrow
Support the vertical portion of the venting
system every 8 feet (2.4 m) above the fireplace
vent outlet. One method of support is by utiliz-
ing field provided support straps (conventional
plumber's tape). Secure the plumber's tape to
the framing members with nails or screws.
Loop the tape around the vent, securing the
ends of the tape to the framing. If desired,
sheet metal screws #6 x 1/2" length may be
used to secure the support straps to the vent
pipe. See Figure 21.
Appliance Collar or
Vent Section
Figure 20
Maintain a minimum 1" (25 mm) clearance
to combustible materials for all vertical
elements. Clearances for all horizontal ele-
ments are 3" (76 mm) on top, 1" (25 mm)
on sides and 1" (25 mm) on the bottom.
To attach a vent component to the appliance
collar, align the dimpled end over the collar,
adjusting the radial alignment until the four
locking dimples are aligned with the inlet of
the four inclined channels on the collar (refer
to Figure 20). Push the vent component
against the collar until it fully engages, then
twist the component clockwise, running the
dimples down and along the incline channels
until they seat at the end of the channels. The
unitizeddesignoftheSecureVentcomponents
will engage and seal both the inner and outer
pipe without the need for sealant or screws.
If desired a #6 x 1/2" screw may be used at the
joint, butitnotrequiredasthepipewillsecurely
lock when twisted.
A. Frame ceiling opening - Use a plumb line
from the ceiling above the appliance to locate
center of the vertical run. Cut and/or frame an
opening, 10-1/2" x 10-1/2" (267 mm x 267
mm)insidedimensions, aboutthiscentermark
(Figure 19).
10-1/2" Min.
(267 mm)
Blocking
Support Straps
(Plumber's tape)
Note: An elbow may also be attached to the
appliance collar. Attach in the same manner
as you would a vent section.
10-1/2" Min.
(267 mm)
8 feet (2.4 m)
Maximum
C. Attach vent components to each other
- Other vent sections may be added to the
previously installed section in accordance with
the requirements of the vertical vent Figures
and Tables. To add another vent component
to a length of vent run, align the dimpled end
over the inclined channel end of the previously
installedsection, adjustingtheradialalignment
untilthefourlockingdimplesarealignedwiththe
inletsofthefourinclinechannelsoftheprevious
section. Push the vent component against the
previoussectionuntilitfullyengages,thentwist
the component clockwise running the dimples
down and along the incline channels until they
seat at the end of the channels. This seating
position is indicated by the alignment of the
arrow and dimple as shown in Figure 20.
1 inch (25.4
mm) minimum
clearance to
combustibles
Figure 21
Another method, where the vent is not adjacent
to a wall, is illustrated in Figure 22. Here,
support straps (96K93) and support plates
(96K92) can be used to support the weight
of the vent.
Figure 19
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Use a carpenter’s level to measure from a
constant surface and adjust the support straps
as necessary.
SV4.5CGV-1
Termination
SV4.5FA or
SV4.5FB Flashing
and SV4.5SC
Storm Collar
Storm
Collar
It is important to maintain the required clear-
ancestocombustibles:1"(25mm)atallsides
forallverticalruns;and3"(76mm)atthetop,
1" (25 mm) at sides, and 1" (25 mm) at the
bottom for all horizontal / inclined runs.
1” (25.4 mm)
Minimum
Clearance to
Combustibles
ꢁWhen using
secure Flex, use
Firestop/Spacer
SF4.5VF
Flashing
ꢁSV4.5VF
Ceiling Framing
Firestop / spacer
H. Frame roof opening - Identify location for
vent at the roof. Cut and/or frame opening per
Roof Framing Chart and Figure 24.
Figure 25
ꢀSV4.5SP
Support Plate
8 ft. (2.4 M)
Maximum
K. Install the vertical termination - The final
Step involves installation of the SV4.5CGV-1
Vertical Termination. Extend the vent sections
to the height as shown in the "Vertical vent
termination section" (Page 7, Figure 4). The
SV4.5CGV-1 Vertical Termination (Figure 26)
canbeinstalled intheexactsamefashionasany
otherSecureVentsection.Alignthetermination
over the end of the previously installed section,
adjusting the radial alignment until the four
locking dimples of the termination are aligned
withtheinletsofthefourinclinechannelsofthe
last vent section. Push the termination down
until it fully engages, then twist the termination
clockwise running the dimples down and along
the incline channels until they are seated at the
end of the channels.
ꢀSV4.5SU
Support Strap
C
ꢀSecured
to Vent with
Appropriate
Fasteners
D
Figure 22
Framing Dimensions for Roof
Inches (millimeters)
F.Changeventdirectiontohorizontal/inclined
run - At transition from or to a horizontal / in-
clined run, install the SV4.5E45 and SV4.5E90
elbows in the same manner as the straight vent
sections. The elbows feature a twist section to
allow them to be routed about the center axis
of their initial collar section to align with the
required direction of the next vent run element.
Twist elbow sections in a clockwise direction
onlysoastoavoidthepossibilityofunlocking
anyofthepreviouslyconnectedventsections.
See Figure 23.
Pitch
0/12
C
D
10-1/2 in.
(267 mm)
10-1/2 in.
(267 mm)
6/12
10-1/2 in.
(267 mm)
12 in.
(305 mm)
12/12
10-1/2 in.
(267 mm)
17-3/4 in.
(451 mm)
Figure 24 - Roof Framing
I. Install the roof flashing - Extend the vent
sections through the roof structure. Install the
roof flashing over the vent section and position
such that the vent column rises vertically (use
carpenters level - see Figure 25). Nail along
perimeter to secure flashing or adjust roofing
to overlap the flashing edges at top and sides
only and trim where necessary. Seal the top
and both sides of the flashing with waterproof
caulking.
8-1/8"
4-13/16
(206 mm)
(122 mm)
Swivel Joint
(360° swivel)
SV4.5E45
Swivel Joint
(360° swivel)
SV4.5E90
45° Elbow)
90° Elbow)
Figure 23
Figure 26
G.Continueinstallationofhorizontal/inclined
sections - Continue with the installation of the
straightventsectionsinhorizontal/inclinedrun
as described in Step C. Install support straps
every 5 feet (1.52 m) along horizontal / inclined
vent runs using conventional plumber’s tape.
See Page 19, Figure 32. It is very important
thatthehorizontal/inclinedrunbemaintained
in a straight (no dips) and recommended to
be in a slightly elevated plane, in a direction
awayfromthefireplaceof1/4"riseperfoot(20
mm per meter) which is ideal, though rise per
footrunratiosthataresmallerareacceptable
all the way down to at or near level.
J. Install the storm collar - Install the storm
collar, suppliedwiththeflashing, overthevent/
flashingjoint.SeeFigure25. Loosenthestorm
collar screw. Slide collar down until it meets
the top of the flashing. Tighten the adjusting
screw. Apply non-combustible caulking or
mastic around the circumference of the joint
to provide a water tight seal.
If the vent system extends more than 5 feet
(1.5 m)above the roof flashing, stabilizers may
be necessary. Additional screws may be used
at section joints for added stability. Guide wires
may be attached to the joint for additional sup-
port on multiple joint configurations.
16
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
VERTICAL VENT FIGURES/TABLES
Table A
V Minimum
Note: Secure Vent (rigid vent pipe) is shown
in the Figures; Secure Flex (flexible vent pipe)
may also be used.
ꢀWhen using Secure Flex, use Firestop
/ Spacer SF4.5VF
H Maximum
feet (meter)
feet
(meter)
(0.305)
(0.610)
(0.914)
(1.219)
2
4
6
8
(0.610)
(1.219)
(1.829)
(2.438)
1
2
3
4
WARNING
UnderNoCircumstances,MaySepa-
rate Sections of Concentric Flexible
Vent Pipe Be Joined Together.
ꢀCeiling Firestop / Spacer (SV4.5VF)
V + H = 40 feet (12.2 meters) Max.
H = 8 feet (2.4 meters) Max.
Ratio V to H ratio is 1:2
Notes:
V
• It is very important that the horizontal/in-
clined run be maintained in a straight (no
dips) and recommended to be in a slightly
elevated plane, in a direction away from the
fireplace of 1/4" rise per foot (20 mm per
meter) which is ideal, though rise per foot
run ratios that are smaller are acceptable all
the way down to at or near level.
Example: If 8 feet of (H) horizontal vent run
is needed, then 4 feet minimum (V) vertical
vent will be required.
This table shows a 1(V) to 2(H) ratio. For
every 1 foot of (V) vertical, you are allowed 2
feet of (H) horizontal run, up to a maximum
horizontal run of 8 feet.
H
• SV4.5VF (Secure Vent), SF4.5VF (Secure
Flex) firestop/spacer must be used anytime
vent pipe passes through a combustible
floor or ceiling. SV4.5HF (Secure Vent),
SF4.5HF (Secure Flex)firestop/spacer must
be used anytime vent pipe passes through
a combustible wall.
Figure 28- Side Vent - ONE 90 DEGREE ELBOW
• Two 45 degree elbows may be used in place
of one 90 degree elbow. The same rise to
run ratios, as shown in the venting Figures
for90elbows, mustbefollowedif45degree
elbows are used.
• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF
VERTICALRISEEXCEPTWHEREANELBOW
IS THE ONLY VERTICAL COMPONENT IN
THE SYSTEM (See Figure 36).
Table B
H Maximum
V Minimum
feet (meter)
Elbow Only
feet
(meter)
(1.524)
H
5
5
(1.524)
(3.048)
(4.572)
(6.096)
1
(0.305)
(0.610)
(0.914)
(1.219)
10
15
20
2
3
4
ꢀCeiling Firestop
ꢀCeiling Firestop /
/ Spacer (SV4.5VF)
Spacer (SV4.5VF)
V + V + H = 40 feet (12.2 m) Max.
H = 20 feet (6.096 meters) Max.
1
Example: If 20 feet of (H) hori-
zontal vent run is needed, then 4
feet minimum of (V) vertical vent
V1
40 feet
(12.2 meters)
Maximum
will be required.
V
This table shows a 1(V) to 5(H)
ratio. Forevery1footof(V)verti-
cal, you are allowed 5 feet of (H)
horizontal run, up to a maximum
horizontal run of 20 feet.
A Vent Restrictor, as
shown in Figure 17,
Page 13, must be used
in this application
ꢁWall Firestop/
An elbow is acceptable as 1 foot
of vertical rise except where
an elbow is the only vertical
component in the system. See
Figure 36.
Spacer (SV4.5HF)
ꢀWhen using Secure Flex, use
ꢁWFirheesntoupsi/nSgpSaecceurrSeFF4l.e5xV,Fu.se
Firestop / Spacer SF4.5HF.
ꢀWhenusingSecureFlex,useFirestop/Spacer
SF4.5VF
Figure 29 - Top Vent - TWO 90 DEGREE ELBOWS
Figure 27 - Top Vent - STRAIGHT
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
VERTICAL VENT FIGURES / TABLES (CONTINUED)
Table C
H1
H+H Maximum
H Maximum
V Minimum
1
feet (meter) feet (meter)
feet
(meter)
(0.305)
(0.610)
(0.914)
(1.219)
ꢀCeiling
Firestop / Spacer
(SV4.5VF)
5
(1.524)
(3.048)
(4.572)
(6.096)
2
4
6
8
(0.610)
(1.219)
(1.829)
(2.438)
1
2
3
4
10
15
20
Wall Firestop/
ꢁ
V + V + H + H = 40 feet (12.2 m) Max
H = 8 feet (2.438 meters) Max.
1
1
Spacer (SV4.5HF)
V1
H + H = 20 feet (6.096 meters) Max.
ꢀCeiling Firestop /
1
Spacer (SV4.5VF)
ꢀWhen using Secure Flex, use Firestop / Spacer SF4.5VF
ꢁWhen using Secure Flex, use Firestop / Spacer SF4.5HF
Example: If 20 feet total (H+H1) horizontal vent run is needed,
then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet of (H+H1) horizontal run up to a
maximum total horizontal run of 20 feet.
V
H
Figure 30 - Side Vent - THREE ELBOWS
Table D
V Minimum
(meter)
Elbow Only
(0.305)
H + H Maximum
1
feet
(meter)
(1.524)
(1.524)
(3.048)
(4.572)
(6.096)
feet
5
ꢀCeiling
5
1
2
3
4
V
1
Firestop / Spacer ꢁWall Firestop/
10
15
20
(0.610)
(0.914)
(1.219)
(SV4.5VF)
Spacer (SV4.5HF)
H
H + H = 20 feet (6.096 m) Max.
V + V + H + H = 40 ft. (12.192 m) Max.
1
1
1
V
Example: If 20 feet total (H+H1) horizontal vent run is needed, then
4 feet minimum of (V) vertical vent will be required.
H
1
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V) vertical,
you are allowed 5 feet of (H+H1) horizontal run up to a maximum total
horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical rise except where an elbow
is the only vertical component in the system. See Figure 36.
ꢀWhen using Secure Flex, use Firestop / Spacer SF4.5VF
ꢁWhen using Secure Flex, use Firestop / Spacer SF4.5HF
Figure 31 - Top Vent - THREE ELBOWS
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
To add another vent component to a length
of vent run, align the dimpled end of the
component over the inclined channel end of
the previously installed section, adjusting the
radial alignment until the four locking dimples
are aligned with the inlets of the four incline
channelsoftheprevioussection. Pushthevent
componentagainsttheprevioussectionuntilit
fully engages, then twist the component clock-
wise running the dimples down and along the
incline channels until they seat at the end of the
channels. This seating position is indicated
by the alignment of the arrow and dimple as
shown in Figure 20 on Page 15.
Support
Brackets
Horizontal / Inclined Run
Building
Support
Framing
SV4.5HT-2
Termination
Shown
SV4.5E90
Elbow
SV4.5L6/12/24/36/48
Vent Sections
Exterior
Wall
Ceiling
ꢀFirestop / Spacer
SV4.5VF
Vertical
Rise
Support Bracket Spacing
Every 5 ft (1.52 m)
ꢀWhen Using Secure Flex,
Use Firestop / Spacer SF4.5VF
SV4.5HT-2
Termination
Shown
F. Install firestop / spacer at ceiling -
See Figures 21 & 22 for verti-
cal vent section support.
WhenusingSecureVent, useSV4.5VFfirestop
/ spacer at ceiling joists; when using Secure
Flex, use SF4.5VF firestop / spacer. If there is
livingspaceabovetheceilinglevel,thefirestop/
spacer must be installed on the bottom side of
the ceiling. If attic space is above the ceiling,
the firestop/ spacer must be installed on the
top side of the joist. Route the vent sections
through the framed opening and secure the
firestop / spacer with 8d nails or other ap-
propriate fasteners at each corner.
Fireplace
Figure 32 -TYPICAL HORIZONTAL VENT INSTALLATION
HORIZONTAL (OUTSIDE WALL)
TERMINATION SYSTEM
Maintain a minimum 1" (25 mm) clearance to
combustibles on the vertical sections. Clear-
ances for the horizontal runs are; 3" (76 mm)
on top, 1" (25 mm) on sides, and 1" (25 mm)
at the bottom.
See Figure 32, and Figures 35 to 40 and
their associated Horizontal Vent Table which
illustrates the horizontal venting configura-
tions that are allowed to be used with these
appliances. Secure Vent pipe applications are
shown in these figures; Secure Flex pipe may
also be used (see Page 24). A Horizontal Vent
Tablesummarizeseachsystem’sminimumand
maximum vertical and horizontal length values
that can be used to design and install the vent
components in a variety of applications.
Remembertomaintain1"(25mm)clearance
tocombustibles,framingmembers,andattic
or ceiling insulation when running vertical
chimney sections. Attic insulation shield
(96K94) may be used to obtain the required
clearances indicated here. See installation
accessories Tables on Pages 31 and 32.
B. Frame exterior wall opening -
Locate the center of the vent outlet on the exte-
rior wall according to the dimensions shown in
Figures 13 & 14 on Pages 11 & 12.
Cut and/or frame an opening, 10-1/2" x 12 1/8"
(267 mm x 308 mm) inside dimensions, about
this center.
G. Support the vertical run sections -
See Step E on Page 15.
C. Frame ceiling opening - If the vertical route
istopenetrateaceiling,useplumblinetolocate
thecenterabovetheappliance.Cutand/orframe
an opening, 10-1/2" x 10-1/2" (267 mm x 267
mm)insidedimensions,aboutthiscenter(refer
to Figure 19 on Page 15).
Bothofthesehorizontalventsystemsterminate
throughanoutsidewall. BuildingCodeslimitor
prohibit terminating in specific areas. Refer to
Figure 6 on Page 8 for location guidelines.
H. Change vent direction - At transition from
or to a horizontal / inclined run, install the
SV4.5E45 and SV4.5E90 elbows in the same
manner as the straight vent sections. The
elbows feature a twist section to allow them to
be routed about the center axis of their initial
collar section to align with the required direc-
tion of the next vent run element. Twist elbow
sections in a clockwise direction only so as
to avoid the possibility of unlocking any of
the previously connected vent sections. See
Figure 20 on Page 15.
Secure Vent SV4.5 direct vent system compo-
nents are unitized concentric pipe components
featuring positive twist lock connection, (refer
to Figure 20 on Page 15). All of the appli-
ances covered in this document are fitted with
collars having locking inclined channels. The
dimpled end of the vent components fit over
the appliance collar to create the positive twist
lock connection.
D. Attach vent components to appliance - To
attachaventcomponenttotheappliancecollar,
align the dimpled end over the collar, adjust-
ing the radial alignment until the four locking
dimples are aligned with the inlets of the four
incline channels on the collar (refer to Figure
20 on Page 15).
I.Continueinstallationofhorizontal/inclined
sections - Continue with the installation of the
straightventsectionsinhorizontal/inclinedrun
as described in Step E. Install support straps
every 5 ft. (1.52 m) along horizontal / inclined
vent runs using conventional plumber’s tape.
See Figure 32. It is very important that the
horizontal / inclined run be maintained in a
straight (no dips) and recommended to be in
a slightly elevated plane, in a direction away
from the fireplace of 1/4" rise per foot (20 mm
per meter) which is ideal, though rise per foot
runratiosthataresmallerareacceptableallthe
way down to at or near level. Use a carpenter’s
level to measure from a constant surface and
adjust the support straps as necessary.
Push the vent component against the collar
until it fully engages, then twist the component
clockwise,runningthedimplesdownandalong
the incline channels until they seat at the end of
thechannels.TheunitizeddesignoftheSecure
Ventcomponentswillengageandsealboththe
inner and outer pipe elements with the same
procedure. Sealant and securing screws are
not required.
A. Plan the vent run -
Analyze the vent routing and determine the
types and quantities of sections required
4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2"
(572 mm), 34-1/2" (876 mm) and 46-1/2" (1181
mm) net section lengths are available. Plan the
vent lengths so that a section joint does not occur
within the space defined by ceiling joists, roof
rafters or wall studs. Make allowances for elbows
as indicated in Figure 23 on Page 16.
E. Attach vent components to each other
- Other vent sections may be added to the
previously installed section in accordance with
the requirements of the vent tables.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
It is important to maintain the required clear-
ancestocombustibles:1"(25mm)atallsides
forallverticalruns;and3"(76mm)atthetop,
1" (25 mm) at sides, and 1" (25 mm) at the
bottom for all horizontal / inclined runs.
To help minimize water infiltration it is
recommended that the Firestop/Spacer
(SV4.5HF) be installed on the exterior
side of the wall.
SV4.5 HT-2
Termination
7"
(178)
J. Assemble vent run to exterior wall - If not
previously measured, locate the center of the
vent at the exterior wall. Prepare an opening as
describedinStepB. Assembletheventsystem
to point where the end of the last section is
within 5 in. (127 mm) to 9-1/4 in. (235 mm)
inboard of the exterior surface to which the
SV4.5HT-2 termination is to be attached, see
Figure 34. If the end of the last section is not
withinthisdistance,usethetelescopicventsec-
tion SV4.5LA, as the last vent section. For wall
thicknesses greater than that shown in Figure
34, refer to Table 11 on Page 21. This Table
lists theadditionalventingcomponentsneeded
(in addition to the termination and adapter) for
a particular range of wall thicknesses.
10¹⁄₂"
12¹⁄₈"
(267mm)
(308 mm)
5¹⁄₈"
(130 mm)
3"
(76 mm)
1"
Adapter
SV4.5RCH
(25.4 mm)
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
the Framed Opening.
See Figures 13 & 14 for Min.
Distance to Base of Appliance.
6 to 48 inch Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Base of Appliance
Figure 33 - INSTALLING SQUARE HORIZONTAL TERMINATION (SV4.5HT-2)
K. Attach termination adapter - Attach the
adapter (SV4.5RCH - provided with the termi-
nation) to the vent section or telescoping vent
section), elbow or appliance collar as shown
in Figures 33 & 34 in the same manner as any
SV4.5 vent component (refer to Step E).
Maximum Wall Thickness
Use silicone caulking to seal
ꢀ
10 in. (254 mm)
ꢁ
the top and sides of the
termination, up to the
underlayment, stucco, or
masonry wall surface.
Exterior Surface of Siding
Exterior Surface of
Framing
Interior Surface of
Finished Wall
L. Install Firestop / Spacer at exterior wall
- When using the square termination, install
SV4.5HF (Secure Vent), SF4.5HF (Secure Flex)
Firestop/Spacerovertheopeningattheexterior
sideoftheframing,longsideup,withthe3inch
spacer clearance at the top as shown in Figure
33, and nail into place. The Firestop / Spacer
may also be installed over the opening at the
interior side of the framing.
Maximum Extent of
Vent Run Sections
Relative to Exterior
Surface of Framing
Siding
6 in. to 9-1/4 in.
(152 to 235 mm)
ꢁ
Caulk
ꢀ
Last Vent Section.
Use Telescopic Vent
Section (SV4.5LA), If
Necessary
SV4.5 HT-2
Termination
Caulk
ꢀ
M. Install the Square Termination (SV4.5HT-2)
Install the square termination - For the last
step , from outside the exterior wall, slide the
collars of the termination onto the adapter until
the termination seats against the exterior wall
surface to which it will be attached. Orient
the housing of the termination with the arrow
pointed upwards. Secure the termination to
the exterior wall. The horizontal termination
must not be recessed into the exterior wall
or siding by more than the 1-1/4" (32 mm) as
shown in Figure 34.
SV4.5 HT-2
Termination
Adapter
SV4.5RCH
1-1/4” Maximum Recess of
Square Termination
into Exterior Finishing Material
Stucco
For thicknesses greater than
ꢁ
10", see Table 11
Venting Connection and Exterior Wall Recessing of the Horizontal Square
Termination (SV4.5HT-2).
Figure 34
Horizontal terminations have been designed to perform in a wide range of weather condi-
tions. Our terminations meet or exceed industry standards.
IMPORTANT
When selecting the locations of your horizontal terminations, do not place the termina-
tion where water from eaves and adjoining rooflines may create a heavy flow of cascad-
ing water onto the termination cap. If the cap must be placed where the possibility of
cascading water exists, it is the responsibility of the builder to direct the water away
from the termination cap by using gutters or other means.
The vent termination is hot while
in operation and for a period of
time following the use of the fire-
place. To prevent contact with hot
surfaces, we recommend the use
of a Termination Guard. See Items
12 and 13 on Page 31. This can be
purchased at your local dealer.
Take care to carefully follow the installation instructions for the termination, including
the use of silicone caulking where required.
20
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
HORIZONTAL VENT FIGURES/TABLES
Square termination
(SV4.5HT-2) shown.
Notes:
• Secure Vent components (rigid vent pipe and terminal) are shown in
the Figures; Secure Flex components (flexible vent pipe and terminal)
may also be used.
H = 28 in. (711 mm)
Maximum
21 in. (533 mm)
Maximum
• Two 45 degree elbows may be used in place of one 90 degree elbow.
The same rise to run ratios, as shown in the venting Figures for 90
elbows,must be followed if 45 degree elbows are used.
7 in. (711 mm)
• SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must
be used anytime vent pipe passes through a combustible floor or ceil-
ing. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer
must be used anytime vent pipe passes through a combustible wall.
Wall Firestop / Spacer
(SV4.5HF)
ꢀ
When using Secure Flex, use Firestop / Spacer SF4.5HF
ꢀ
• It is very important that the horizontal/inclined run be maintained
in a straight (no dips) and recommended to be in a slightly elevated
plane, in a direction away from the fireplace of 1/4" rise per foot (20
mm per meter) which is ideal, though rise per foot run ratios that are
smaller are acceptable all the way down to at or near level.
Figure 35 - Side Vent, NO ELBOWS
• The tables show a 1(V) to 5(H) ratio up to a maximum horizontal run
of 20 feet except for installations where an elbow is the only vertical
vent section in the system (see Figure 36).
Example: If 20 feet of (H)
Table E
horizontal vent run is needed,
V Minimum
H Maximum
then 4 feet minimum of (V)
vertical vent will be required.
feet (meter) feet
(meter)
• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT
WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE
SYSTEM. See Figure 36.
This table shows a 1(V) to
5(H) ratio. For every 1 foot
of vertical, you are allowed 5
feet of (H) horizontal run up
to a maximum (H) horizontal
run of 20 feet.
3
(0.914)
(1.524)
(3.048)
(4.572)
(6.096)
Elbow Only
(0.305)
5
1
2
3
4
10
15
20
(0.610)
Venting Components Required for Various Exterior Wall Thick-
nesses, when using Square Termination Kit (SV4.5HT-2)
(0.914)
Vent Components Required Exterior Wall Thickness - inches (mm)
(1.219)
Termination Kit Only
6 to 9-1/4 (152 to 235)
V + H = 40 feet (12.2 m) Max.
H = 20 ft. (6.096 m) Max.
TerminationKitand 6In.Vent
Section (SV4.5L6)
10-3/4 to 14 (273 to 356)
Square termination
(SV4.5HT-2) shown.
Termination Kit and 12 in.
Vent Section (SV4.5L12)
16-3/4 to 20 (426 to 508)
11-3/4 to 20 (299 to 508)
Termination Kit and Tele-
scopic Section (SV4.5L12)
H
Note:SeeFigure34showingwallthicknessrange
when using SV4.5HT-2 termination kit only.
Table 11
V
See Table 11 as an aid in venting component selection for a particular
range of exterior wall thicknesses.
WARNING
Under no circumstances, may separate sections of
concentric flexible vent pipe be joined together.
ꢁWall Firestop/
Spacer (SV4.5HF)
ꢀWhen using Secure Flex, use Firestop / Spacer SF4.5VF
ꢁWhen using Secure Flex, use Firestop / Spacer SF4.5HF
Square termination (SV4.5HT-2) shown
Figure 36 - Top Vent, ONE 90 DEGREE ELBOW
21
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
HORIZONTAL VENT FIGURES / TABLES (CONTINUED)
Table F
V Minimum
H
+H1 Maximum
H Maximum
H
H
1
feet (meter) feet (meter)
feet
(meter)
(0.305)
(0.610)
(0.914)
(1.219)
5
(1.524)
(3.048)
(4.572)
(6.096)
2
4
6
8
(0.610)
(1.219)
(1.829)
(2.438)
1
2
3
4
10
15
20
ꢁWall Firestop/
Spacer (SV4.5HF)
V + H + H = 40 feet (12.2 m) Max
1
H = 8 feet (2.438 meters) Max.
ꢀCeiling
H + H = 20 feet (6.096 meters) Max.
1
Firestop / Spacer
(SV4.5VF)
Example: If 20 feet of (H + H ) horizontal
vent run is needed, then 4 feet 1minimum of
(V) vertical vent will be required.
V
ꢁWall Firestop/
Spacer (SV4.5HF)
Thistableshowsa1(V)to5(H)ratio. Forevery
1 foot of (V) vertical, you are allowed 5 feet
of (H+ H1) horizontal run, up to a maximum
horizontal run of 20 feet.
ꢀWhen using Secure Flex, use Firestop /
Spacer SF4.5VF
ꢁWhen using Secure Flex, use Firestop /
Spacer SF4.5HF
Note: See Table 11 as an aid in venting
component selection for a particular range
of exterior wall thicknesses.
Square termination (SV4.5HT-2) shown
Figure 37 - Side Vent, TWO 90 DEGREE ELBOWS
Table G
ꢁWall Firestop/
Spacer (SV4.5HF)
V Minimum
feet (meter)
Elbow Only
H + H Maximum
1
feet
3
(meter)
(0.914)
(1.524)
(3.048)
(4.572)
(6.096)
H
5
1
(0.305)
(0.610)
(0.914)
(1.219)
H
1
10
15
20
2
3
4
V
V + H + H = 40 feet (12.2 m) Max.
1
H + H = 20 ft. (6.096 m) Max.
ꢁWall Firestop/
Spacer (SV4.5HF)
1
ꢀWhen using Secure Flex, use Firestop
/ Spacer SF4.5VF
ꢁWhen using Secure Flex, use Firestop
/ Spacer SF4.5HF
Example: If 20 feet of (H + H ) horizontal
vent run is needed, then 4 feet 1minimum of
(V) vertical vent will be required.
ꢀCeiling Firestop /
Note: See Table 11 as an aid in venting
componentselectionforaparticularrange
of exterior wall thicknesses.
Thistableshowsa1(V)to5(H)ratio. Forevery
1 foot of (V) vertical, you are allowed 5 feet
of (H+ H1) horizontal run, up to a maximum
horizontal run of 20 feet.
Spacer (SV4.5VF)
Square termination (SV4.5HT-2) shown
An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only vertical
component in the system. See Figure 36.
Figure 38 - Top Vent, TWO 90 DEGREE ELBOWS
22
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
HORIZONTAL VENT FIGURES / TABLES (CONTINUED)
ꢀWhen using Secure Flex, use
Firestop / Spacer SF4.5VF
ꢁWhen using Secure Flex, use
Firestop / Spacer SF4.5HF
ꢁWall Firestop / Spacer
(SV4.5HF)
H
1
Note: See Table 11 as an aid in
venting component selection for
H
a particular range of exterior wall
thicknesses.
2
Table H
H Maximum
V Minimum
H + H + H Maximum
1
2
ꢀCeiling Firestop /
feet
5
(meter)
(1.524)
(3.048)
(4.572)
(6.096)
feet
(meter)
(0.610)
(1.219)
(1.829)
(2.438)
feet
(meter)
(0.305)
(0.610)
(0.914)
(1.219)
Spacer (SV4.5VF)
2
4
6
8
1
2
3
4
V
10
15
20
V + H + H + H = 40 feet (12.2 m) Max
1
2
H
H = 8 feet (2.438 meters) Max.
H + H + H = 20 feet (6.096 meters) Max.
1
2
Example: If 20 feet total (H+H1+H2) horizontal vent run is needed, then 4 feet minimum
of (V) vertical vent will be required.
Square termination (SV4.5HT-2) shown
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V) vertical, you are allowed 5
feet of horizontal run up to a maximum total (H+H1+H2) horizontal run of 20 feet.
Figure 39 - Side Vent, THREE 90 DEGREE ELBOWS
Square termination (SV4.5HT-2) shown
Table I
V Minimum
feet (meter)
Elbow Only
H + H Maximum
1
H
1
feet
5
(meter)
(1.524)
(1.524)
(3.048)
(4.572)
(6.096)
Ceiling Firestop /
Spacer (SV4.5VF)
ꢀ
5
1
2
3
4
(0.305)
(0.610)
(0.914)
(1.219)
10
15
20
H
H + H = 20 feet (6.096 m) Max.
1
V + V + H + H = 40 ft. (12.192 m) Max.
V
1
1
ꢁWall Firestop / Spacer
1
(SV4.5HF)
Example: If20feettotal(H+H1)horizontal
vent run is needed, then 4 feet minimum
of (V) vertical vent will be required.
ꢀWhen using Secure Flex,
use Firestop / Spacer
SF4.5VF
ꢁWhen using Secure Flex,
use Firestop / Spacer
SF4.5HF
V
This table shows a 1(V) to 5(H) ratio. For
every1footof(V)vertical,youareallowed
5 feet of (H+ H1) horizontal run, up to a
maximum horizontal run of 20 feet.
Anelbowisacceptableas1footofvertical
rise except where an elbow is the only
vertical component in the system. See
Figure 36.
ꢁWall Firestop
/ Spacer (SV4.5HF)
Note: See Table 11 as an aid
in venting component selec-
tion for a particular range of
exterior wall thicknesses.
Wall Firestop /
ꢀ
Spacer (SV4.5VF)
Figure 40- Top Vent, THREE 90 DEGREE ELBOWS
23
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
VERTICAL OR HORIZONTAL VENTING USING
SECURE FLEX KITS AND COMPONENTS
Flex Vent
Note: Outer Pipe Is Pulled Away To Show
The Detail of The Inner Pipe
Securing Screw - 3 Places
Equidistant (equally spaced)
Just Below Gear Clamp)
Secure Flex venting kits and components
may be used in any venting application in
place of rigid Secure Vent (SV4.5) direct vent
components. All restrictions, clearances and
allowances that pertain to the rigid piping apply
to the flexible venting. Secure Flex kits may
notbemodified;also,undernocircumstances
may separate sections of flex pipe be joined
together.
APPLY ONLY MIL-PAC BLACK
HIGH TEMPERATURE SEALANT
(Cat. No. 10K81) to the outside
surface of both collars of the
adapter (be especially careful to
fill the grooves of the outer collar
tobecoveredbytheflexiblepipe)
and slide flexible pipe over inner
and outer adapter collars.
Gear Clamps
Using adapter (SV4.5RF), Secure Flex kits
may be added to the end of a vent run made
up of rigid Secure Vent (SV4.5) vent sections
provided that doing so does not violate any of
the venting length, height, routing, horizontal
to vertical ratio requirements or clearance
considerations detailed in this manual.
1-3/4 inch (44 mm) Flexible
PipeandAdapterOuterCollar
Overlap
1-3/4 in. (44 mm) Flexible
PipeandAdapterInnerCollar
Overlap
Adapter (SV4.5RF)
Securing Screw
- 3 Places, 120° apart
(equally spaced) Just
Below Gear Clamp
Secure Flex kits come with an adapter that
can be fitted to the inclined channel end of the
last Secure Vent (SV4.5) vent section in a rigid
system in the exact same fashion as any other
Secure Vent section.
Attach Adapter to Appliance
Figure 41
Collar, or Secure Vent Sections
B. Install the Outer Flex Pipe -
D. Install Firestop / Spacers at ceilings and walls
- When Secure Flex penetrates a wall or ceiling,
a firestop / spacer is required: use the SF4.5 VF
firestop / spacer for ceilings and the SF4.5 HF
firestop / spacer for walls. See the appropriate
sectionsandFigures shownthroughoutthevent-
ing section for their installation requirements.
1. Install the large gear clamp loosely around
the outer flexible vent pipe, push it back out
of the way.
Align the dimpled end of the adapter over
the previously installed section or appliance
collar, adjusting the radial alignment until the
four locking dimples of the adapter are aligned
with the inlets of the four incline channels of
the last vent section or collar. Push on the
adapter until it fully engages, then twist the
adapter clockwise running the dimples down
and along the incline channels until they seat
at the end of the channels.
2. ApplyabeadofMill-PacBlack(700°F)high
temperature sealant - Catalog No. 10K81)
to the outer adapter collar; to the grooves
of the collar which extend approximately 1
inch from the end and to the flat surface,
approximately 1-3/8 inches from the end.
3. Pull and extend outer flexible vent pipe.
4. Slidetheouterflexpipeovertheadaptercol-
lar. Ensure the flexible vent pipe completely
engages the adapter collar to a distance of
1-3/4 inches from the end, and that it is free
from damage or tears.
5. Slide the gear clamp down and tighten it
fullytosecuretheflexibleventtotheadapter
outer collar approximately 3/4 inch from the
end of the flex.
6. Install three screws 120 degrees apart
through the flexible vent pipe and into the
adapter collar just below the gear clamp to
provide additional security to the connec-
tion.
Flexible Vent
Section
Attach the flexible vent to the adapter as fol-
lows (see also Figure 41):
A. Install the Inner Flex Pipe -
1. Install the small gear clamp loosely around
the inner flexible vent pipe, push it back out
of the way.
2. ApplyabeadofMill-PacBlack(700°F)high
temperature sealant - Catalog No. 10K81
to the inner adapter collar, approximately
1/2 inch from the end.
3. Pull and extend the inner flexible vent pipe.
4. Slidetheinnerflexpipeovertheadaptercol-
lar. Ensure the flexible vent pipe completely
engages the adapter collar to a distance of 1
3/4 inches from the end, and that it is free
from damage or tears.
5. Slide the gear clamp down and tighten it
fullytosecuretheflexibleventtotheadapter
inner collar approximately 3/4 inch from the
end of the flex.
6. Installthreescrews120degreesapartthrough
theflexibleventpipeandintotheadaptercollar
justbelowthegearclamptoprovideadditional
security to the connection.
5” (127 mm)
Radius
Minimum
Figure 42
E. Attach Flex Vent to Termination -
Secure Flex components can be purchased
separately and attached to bulk lengths of Se-
cure Flex flexible tubing cut to size at the job
site. SecuretheflexibleventtotheSecureFlex
terminations in the same manner (see Figure
41) as it was attached to the adapter.
C. Route Flex Vent -
Ensure that the flex vent is properly routed to
providetherequiredclearance.Donotallowthe
flexible vent to bend in a radius tighter than 5"
(127 mm). Refer to Figure 42. Space out the
internalflexventspacersevenly-approximately
every 6 inches - and avoid kinking of inner pipe.
Support horizontal sections of flex with metal
straps at 2 foot (0.61 m) intervals.
Note:SecureFlexventmustbeattachedtoSecure
Flex terminations only. DO NOT substitute Secure
Vent terminations or the Secure Vent adapter for
Secure Flex components. The collars of Secure
Flex terminations and adapters have a different
diameter than that used with the Secure Vent
pipe. Additionally, Secure Flex components have
anextendedlengthcentertubeforuseinattaching
the flexible vent.
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Install the junction box and receptacle outlet
totheleftofthevalveinthefront(foroptional
blowerkit). Seejunctionboxandreceptacle
outlet as explained in steps 1-11 for (B)
Electronic Wiring (on this page).
B. Electronic Wiring (See Figures 45 & 46)
Step 4. FIELD WIRING
Notes:
• The electronic appliance must be connected
to the main 120 VAC power supply.
• The junction box can be installed in any of the
4 outside corners of the control compartment (it
can be found factory installed in the right front
corner viewed from the valve access side (where
it should be reinstalled if an optional blower kit
is installed).
CAUTION
Label all wires prior to disconnec-
tionwhenservicingcontrols.Wiring
errors can cause improper and dan-
gerous appliance operation.
Install OFF/ON Switch
(millivolt models)
1. Connect the 2 wires (provided in Electrical
Outlet Kit) to the TP/TH and TH terminals
on valve.
2. Pass the 2 wires through the opening where
OFF/ONswitchwillbeinstalled(leftofpiezo,
below valve).
Refer to Section A for millivolt appliances and
Section B for electronic appliances.
1. Route a 3-wire, 120 VAC, 60 Hz, 1 ph power
supply to the location on appliance where
junction box is to be installed.
2. Openthecontrolcompartmentaccesspanel
(see Control Compartment Access Instruc-
tions on Page 27).
3. Remove the junction box/outlet receptacle
assemblybyremovingthesecuringscrewat
the front right corner of the unit. See Figure
45.
4. Remove the outlet receptacle from the
junction box by removing the two securing
screws.
5. Install a field-provided strain relief in the
cabinet knockout opening for the protection
of the power supply wires.
6. Connect the power supply wires to the
receptacle as shown in Figure 46 on Page
26.
7. Connectthegroundsupplywiretothegreen
wire attached to the outlet receptacle’s
green ground screw.
8. Wire and install the outlet receptacle to
junction box. Next, install into the chosen
cornerofthecontrolcompartmentasshown
in Figure 45.
A. Millivolt Wiring (See Figure 43):
1. Install and wire in the burner control switch.
Install either "a" or "b" below, NOT BOTH
(installingbothmayresultinimproperburner
operation).
3. Connect the two wires to the OFF/ON
Switch.
Connect
OFF/ON
wires to
a. Optional OFF/ON Switch - Install the
OFF/ON burner control switch (rocker
switch) as shown in Figures 43 &
44.
Switch
terminals
4. Press the OFF/ON switch into bracket as
shown below (it will snap into place).
b. OptionalWallSwitch,WallThermostat
Or Remote Control Receiver - Install
snap bushing (provided in Electrical
Outlet Kit) into control switch knock-
out in side panel (see Figures 13,14 &
45). Wire the optional control switch
within the millivolt control circuit (as
shown in Figure 43) using the 15 feet
of 2 conductor wire supplied (route
wires through the snap bushing to
the optional control switch). Mount
the optional control switch or wall
thermostat in a convenient location
on a wall near the fireplace.
TP TH
Gas
Valve
TH
OFF/ON
Switch
Control Compartment
Access panel
CAUTION: DO NOT CONNECT OPTIONAL
CONTROL SWITCH TO 120VAC POWER
SUPPLY.
9. After the receptacle/junction box wiring is
complete, install the field-provided metal
junction box cover plate (see Figure 45).
Figure 44
Note: The supplied 15 feet of 2 conductor
wire has one end of each conductor con-
nected to the gas valve circuit and the other
end of each conductor placed loose on top
of the appliance.
Thermopile
IMPORTANT NOTE
*
The gas valve OFF/ON switch is
shown in Figure 46 on Page 26. It
is integral with the gas valve and
should be set to the ON position.
* Optional
Control Switch
* Twist wires together to operate unit
solely by manipulating the gas valve
control knob; or connect wires to
optional control switch (wall switch,
remote control or wall thermostat to
operate unit.
Schematic
Representation
Only
Field Wired
Factory
Wired
•
If any of the original wire as supplied must
be replaced, it must be replaced with Type AWM
105 C - 18 gage wire.
* Optional Kits Installed - ON/OFF wall switch, unit mounted burner ON/OFF switch, wall thermostat or
remote control.receiver.
Figure 43 - Millivolt Wiring Diagram
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Receptacle, Junction Box
and Cover Plate Installation
CAUTION
CAUTION
Ensure that wires are positioned
away from hot surfaces and sharp
edges.
Outlet Receptacle
Ground supply lead must be con-
nected to the wire attached to the
green ground screw located on the
outletbox. SeeFigure46.Failureto
dosowillresultinapotential safety
hazard. The appliance must be
electricallygroundedinaccordance
withlocalcodesor,intheabsenceof
local codes, the National Electrical
Code,ANSI/NFPA70-latestedition.
(In Canada, the current CSA C22-1
Canadian Electrical Code).
Junction Box
CAUTION
Do not connect the optional wall
switch to a 120 Volt AC power
supply.
View Of Right
Plug blower
Green
Bottom Corner Of Unit
into this
White
Black
Ground - Green
Neutral - White
120 VAC - Black
receptacle
Field-provided Metal Junction Box
Cover Plate With Screw
Junction Box
Blower
Junction Box
* Wall-mounted
ON/ OFF Blower
Switch or Variable
knock-out (2
Ground
Tab
Broken
Fireplace
Side
places each side)
Tab Intact
Speed Control Switch.
Press snap
bushing into the
knock-out for
control switch
wires.
Red
J-BOX WIRING FOR
WALL SWITCH
BLOWER CONTROL
Green
Ground
Screw
Neutral
Hot
Side of
Side of
Receptacle
Receptacle
Figure 45
View A
J-Box Wiring when
using unit mounted
relay module.
Relay Module C/W FBK-250 only. Plug blower
into J-Box receptacle for FBK-100 or FBK-200
application. See View A for J-Box wiring.
Step 5.WIRING - OPTIONAL FORCED AIR
BLOWER KIT
BK
W
G
Optional Blower
FBK-100, FBK-200 and FBK-250 Kits
Junction Box
(See Figure 46 for wiring) -
*OFF/ON Switch
(Integral with
Gas Valve)
Pilot Burner
Assembly
An electrical receptacle is provided for the
installation of the FBK-100, FBK-200 and FBK-
250 forced air blower kits. Electrical power
must be connected to this receptacle in order
to operate these blowers. Install the blower
kits according to the installation instructions
provided with the kits.
Honeywell
Electronic
Gas
Valve
Igniter
Connector
*
Leave the OFF/ON switch, which is
integral with the gas valve, in the ON
position.
GROUND
Transformer
** Optional Control Switches: Wall
Switch, Wall Thermostat or Remote
Control Receiver.
BL
BL
CAUTION
BL
BK
R
24 V
120 VAC
Primary
Remove the carton support from
the control compartment before
operating the appliance.
Secondary
Notes:
BK
1. If any of the original wire as supplied
must be replaced, use Type AWM 105°C
- 18 gage wire ONLY.
2. 120 VAC, 60 Hz - Less than 3 Amps.
Caution: label all wires prior to
disconnection when servicing controls.
Wiring errors can cause improper and
dangerous operation.
BK = BLACK BL = BLUE
BK
Optional Control Switch
R = RED
W = WHITE
W
G = GREEN
Field Wired
Factory
Wired
Schematic Representation Only
Electronic Wiring Diagram (Honeywell) Showing Blower Wiring for Optional FBK-100, FBK-200 & FBK-250 Kits
Figure 46
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 6. CONNECTING GAS LINE
GAS CONNECTION
Gas Flex Line Connector
Gas
Valve
Make gas line connections. All codes require a
shut-offvalvemountedinthesupplyline.Figure
47 illustrates two methods for connecting the
as supply. The flex-line method is acceptable
in the U.S., however, Canadian requirements
vary depending on locality. Installation must
be in compliance with local codes.
3/8" NPT x
Flare Fitting
1/2" x 3/8" Flare
Shut-off Valve
3/8" Flex Tubing
These appliances are equipped with a gas flex
line for use (where permitted) in connecting
the appliance to the gas line. A gas flex line
is provided to aid in attaching the direct vent
appliance to the gas supply. The gas flex line
can only be used where local codes permit.
See Figure 47 for flex line description. The flex
line is rated for both natural gas and propane
gas. A manual shut off valve is also provided
with the flex line.
3"
Min.
*Sediment Trap
Gas
Stub
1/2" x 3/8"
Reducer
*A Sediment Trap is recom-
mended to prevent moisture
and debris in gas line from
damaging the valve.
3/8" Nipple
3/8" Union
3/8" Close Nipple
Note:The gas supply line must be installed in
accordance with building codes by a qualified
installer approved and/or licensed as requed by
the locality. In the Commonwealth of Massachu-
setts, installation must be performed by a licensed
plumber or gas fitter.
3/8" Shut-off Valve
The incoming gas line should be piped into
the valve compartment and connected (see
Figures 47 & 48). The millivolt control
valve has a 3/8" (10 mm) NPT thread
inlet port. The electronic control valve
has a 1/2" (13 mm) NPT thread inlet port
and is fitted with a 1/2" x 3/8" (13 mm x
10mm) NPT fitting.
Figure 47
WARNING
Never use an open flame to check for leaks.
Control Compartment Access
Secure all joints tightly using appropriate
toolsandsealingcompounds(ensurepropane
resistant compounds are used in propane
applications).
OFF/PILOT/ON (gas control knob)
Glass Door is Above
Control Compartment
HI/LO (flame height
control knob)
Optional: Seal around the gas line to prevent
cold air leakage.
Gas Flex Line
Optional OFF/ON
Switch Can be
Installed Here
TEST ALL CONNECTIONS FOR GAS LEAKS
(FACTORY AND FIELD):
Latch for
Glass Door
Gas Valve
Turn on gas supply and test for gas leaks using a
gas leak test solution (also referred to as bubble
leaksolution). Note:Usingasoapywatersolution
(50% dish soap, 50% water) is an effective leak
test solution but it is not recommended, because
the soap residue that is left on the pipes/fittings
can result in corrosion over time.
Piezo Igniter
Figure 48
CONTROL COMPARTMENT ACCESS/LOUVER
Lift the Lower Control
Compartment Door
up and pull out to
remove.
PANEL INSTRUCTIONS (Ref. Figure 49)
OPENING CONTROL
COMPARTMENT DOOR
Turnongassupplyandtestforgasleaksusing
a gas leak test solution.
A. Light the appliance (refer to the lighting
instructions label in control compartment
or homeowner's manual).
NOTE: The top louvered panel and the bottom
louvered control panel door remove and install
the same way as follows:
Hook Catch
Out
Thegascontrolscanbefoundbehindthecontrol
compartment access door.
Control Valve
B. Brush all joints and connections with the gas
leaktestsolutiontocheckforleaks. Ifbubbles
are formed, or gas odor is detected, turn the
gas control knob (off/pilot/on) to the “OFF”
position. Eithertightenorrefastentheleaking
connection, then retest as described above.
C. Whenthegaslinesaretestedandleakfreebe
sure to rinse off the leak testing solution,
D. Turn on burner then observe the individual
tongues of flame on the burner. Make sure
allportsareopenandproducingflameevenly
acrosstheburner. Ifanyportsareblocked,or
partially blocked, clean out the ports.
Up
Removing Control Compartment Door:
Openthedoorby gentlyliftingitupwarduntilthe
hook catches on boths sides clear the locating
slots. Then pull door out to remove.
Lower Control
Compartment Door
Figure 49
On millivolt systems, the piezo igniter, HI/LO
flame adjustment knob, and pilot and main
gas OFF/ON control knob are located below
the glass panel enclosure. The gas valve for
electronic systems is also located below the
glass enclosure panel. See Figure 48.
Reinstalling Control Compartment Door:
To reinstall, insert the hook catches on each
side of the door into the corresponding slots
in the control compartment opening, then
gently push forward and slide down until it
locks in place.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 7. CHECK APPLIANCE OPERATION
Burner / Grate Location Reference
ELECTRONIC
(see Figures 53 & 54)
With the gas line installed, run initial system
checkout before closing up the front of the
appliance. Follow the pilot lighting instructions
provided in the Homeowner's Care and Opera-
tion Instructions. For piezo igniter location see
Figure 48 (millivolt appliances only).
3/8" to 1/2"
(9 -13 mm)
Proper Flame
Adjustment
Note: If the burners have been removed for
any reason, rear burner must be installed
before front burner. See Figures 53 and 54.
Pilot
Nozzels
Ground
Electrode
NOTE: INSTALL REAR BURNER FIRST,
THEN FRONT BURNER.
Note:The(pull-out)Lightinginstructionslabel
can be found in the control compartment
(see Figure 48).
BURNER
BRACKET A
PORTS
REAR BURNER
Flame Rod
Hot Surface
Igniter
When first lighting the appliance, it will take
a few minutes for the line to purge itself of
air. Once purging is complete, the pilot and
burner will light and operate as indicated in
the instruction manual. Subsequent lightings
of the appliance will not require such purging.
Inspect the pilot flame.
Figure 51
PILOT
BURNER
Step 8. INSTALLING LOG SET, VOLCANIC
STONE AND GLOWING EMBERS
FRONT BURNER
Millivolt Appliance Checkout
WARNING
Note: The burners are not identical. Position them so
that the circular burner ports run as shown. Note
especially the vertical run of ports relative to the pilot
burner. Bracket A on the rear burner will interfere
with the pilot burner if an attempt is made to install
the rear burner in the front burner’s position.
The pilot flame should be steady, not lifting
or floating. Flame should be blue in color with
traces of orange at the outer edge.
DO NOT attempt to install logs
until the appliance installation
hasbeencompleted,thegasline
connected and tested for leaks
and the initial burner operation
has been checked out.
The top 3/8" (10 mm) at the pilot generator
(thermopile) and the top 1/8" min (tip) of the
quickdropoutthermocoupleshouldbeengulfed
in the pilot flame. The flame should project 1"
(25 mm) beyond the hood at all three ports
(Figure 50).
Figure 53
NOTE: INSTALL REAR BURNER FIRST,
THEN FRONT BURNER.
Outer Log
Notch Location
REAR BURNER
Tolighttheburner;rotatethegasvalvecontrolknob
counterclockwise to the “ON” position then turn
“ON” the OFF/ON switch (installed at Step 4).
WARNING
Outer Log
Notch Location
Riser - Inner Log
Notch Location
Logs get very hot and will remain
hotuptoonehouraftergassupply
is turned off. Handle only when
logs are cool. Turn off all elec-
tricitytotheappliancebeforeyou
install grate and logs.
Observe the individual tongues of flame on
the burner. Make sure all ports are open and
producing flame evenly across the burner. If
any ports are blocked, or partially blocked,
clean out the ports.
Riser - Inner Log
Notch Location
Outer Log
Notch Location
Outer Log
Notch Location
FRONT BURNER
Pilot Assembly
SIT MILLIVOLT PILOT ASSEMBLY
Proper Pilot Flame Appearance
WARNING
Igniter Rod
Hood
Thisapplianceisnotdesignedto
burn wood. Any attempt to do so
couldcauseirreparabledamage
to the appliance and prove haz-
ardous to your safety.
FIREBOX SUBFLOOR
FRONT OF FIREPLACE
Thermocouple
3/8" Min.
(9 mm)
LOG NOTCH LOCATION RELATIVE TO BURNER
Figure 54
Proper Burner Flame Appearance
Figure 52
Pilot
Nozzels
Thermopile
Figure 50
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the OFF/ON switch
(locatedinthecontrolcompartment).Ensurethe
igniter lights the pilot. The pilot flame should
engulf the flame rod as shown in Figure 51.
Unitized Log Set
Observe the individual tongues of flame on
the burner. Make sure all ports are open and
producing flame evenly across the burner. If
any ports are blocked, or partially blocked,
clean out the ports.
Volcanic Stone
28
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
Removing Glass Enclosure Panels
(see Figure 55)
LOG & VOLCANIC STONE INSTALLATION
PROCEDURE:
WARNING
1. Remove the top louver assembly by lifting it
up and pulling it out.
Do not attempt to substitute the
materials used on this door, or
replace cracked or broken glass
with any materials other than
those provided by the appliance
manufacturer.
2. Remove the control compartment access
door (see removal instructions on Page 27
- Removing Control Compartment Door).
3. Locate the two (2) latches at the top of the
control compartment. To disengage the two
latches from the bottom vee-flange of the
glass enclosure panel, reach for the handles
located towards the back of the latches and
pull the handles down toward the front of
the appliance.
WARNING
Iflogsarenotinstalledaccording
to the log installation instruc-
tions, flame impingement and
improper combustion could
occur and result in soot and/or
excessive production of carbon
monoxide (CO), a colorless,
odorless, toxic gas.
WARNING
4. Swing the bottom of the door out and raise
it slightly to lift the top flange of the door
frame away from the appliance.
Handle this glass with extreme
care! Temperedglassissuscep-
tible to damage – do not scratch
orhandleroughlywhilereinstall-
ing the glass door frame.
Installing Glass Enclosure Panels
(see Figure 55)
Thelogsetfoampackageislocatedinthefirebox
and the bags of decorative volcanic stone and
the glowing embers (rockwool) are located in
thecontrolcompartment.Refertothefollowing
information and Figures 52 and 54 for detailed
placement instructions.
1.Visuallyinspectthegasketonthebacksideofthe
glass panel. The gasket surface must be clean,
free of irregularities and seated firmly.
2. Position the glass enclosure panel in front of
the firebox opening at a 45 degree angle and
engage the top flange over the lip at the top
of the firebox opening. See Figure 55.
3. Swing the glass enclosure panel down and
back. Ensure the gasket seats evenly as the
panel draws shut. Engage the Vee-flange at
the bottom of the panel with the latches and
close the latches to secure the panel.
4. Reinstall top louver assembly and control
compartmentdoorseeinstallationinstructions
on Page 27, Reinstalling Control Compart-
ment Door).
WARNING
The glass door of this appli-
ance must only be replaced as a
complete unit as provided by the
manufacturer. Do not attempt to
replacebroken,crackedorchipped
glass separately.
Install the decorative volcanic stone and
glowing embers (rockwool):
Spread the decorative volcanic stone on the
simulated brick floor of the firebox around
the burners to simulate ashes. Maintain a 1/2
inch (13 mm) gap between the bottom of the
horizontal grate section and the top of the pile
of decorative volcanic stone. Place a few dime-
sized pieces of the glowing ember material
on the pan burner in front of the burned out
area on both sides of the log set. The glowing
embers may touch one another, but should not
overlap each other.
Top Flange on
Glass Door
Glass Door
Step 10. BURNER ADJUSTMENTS
Flame Appearance and sooting
Proper flame appearance is a flame which is
blue at the base and becomes yellowish-orange
in the body of the flame. When the appliance
is first lit, the entire flame may be blue and will
gradually turn yellowish-orange during the first
15 minutes of operation. If after a short period
the flame stays lowered blue, or if the flame is
orange with evidence of sooting (black tip), the
air shutter opening may need to be adjusted.
Install the unitized log set:
a. The bottom of the log set is notched to ac-
commodate the pilot.
b. Placethelogsetsothatthe fourinnernotches
on the underside of the log set fit over the
four risers located on the burner ends. See
Figure 52. This procedure is accomplished
primarily by feel, as the log set masks the
burner risers as it is being installed.
c. Asafinalcheckforcorrectlogsetplacement,
check that the four outer notches on the
underside of the log set fit over the burner
tines as indicated in Figure 52.
Iftheairshutteropeningsclosedtoofar,sooting
maydevelop.Sootingisindicatedbyblackpuffs
developingatthetipsofverylongorangeflames.
Sootingresultsinblackdepositsformingonthe
logs, appliance inside surfaces and on exterior
surfacesadjacenttotheventtermination. Soot-
ing is caused by incomplete combustion in the
flames and lack of combustion air entering the
air shutter opening. To achieve a warm yellow-
ish-orangeflamewithanorangebodythatdoes
not soot, the shutter opening must be adjusted
between these two extremes.
Bottom Vee-flange
Glass Door
Firebox Floor
Glass Door Latch
Step 9. INSTALLING THE GLASS DOOR
Figure 55 - INSTALLING GLASS DOOR
WARNING
WARNING
Do not attempt to touch the front
enclosure glass with your hands
while the fireplace is in use.
Do not operate appliance with
theglassfrontremoved,cracked
or broken. Replacement of
the glass should be done by a
licensed or qualified service
technician.
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, first check
the log set positioning to ensure that the
flames are not impinging on any of the logs.
If the log set is properly positioned and a
sooting condition still exists, then the air
shutter opening should be increased.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
• Themoreoffsetsintheventsystem,thelarger
the air shutter opening will need to be.
Burner Air Shutter Adjustment Procedure
Step 11. HOOD INSTALLATION
All of these appliances must have hoods
installed prior to operating (see Figure 57).
• An appliance operated with the air shutter
opened too far, may have flames that appear
blue and transparent. These weak, blue and
transparent flames are termed anemic.
• Propane models may exhibit flames which
candle or appear stringy. If this is present and
persists, adjust the air shutter to a more closed
position, then operate the appliance for a few
moreminutestoensurethattheflamenormal-
izes and the flames do not appear sooty.
The following chart is provided to aid you in
achieving the correct air shutter adjustment
for your installation.
1. Locateadjustmentrodandadjustairshutter
to the standard setting as shown in Figure
56 (adjustment rod is located in the lower
control area).
Slide the hood into the slots on the lower edge
of the cabinet top (see Figure 57).
Note: Rotating the adjustment rod coun-
terclockwise decreases air and clockwise
increases air.
FINISHING REQUIREMENTS
Wall Details
2. Light appliance (follow lighting procedure
on lighting label in control compartment or
see homeowners manual).
3. Allow the burner to operate for at least 15
minutes while observing the flame continu-
ouslytoensurethattheproperflameappear-
ance has been achieved (see Figure 52). If
the following conditions are present, adjust
accordingly.
Complete finished interior wall. To install the
appliance facing flush with the finished wall,
position framework to accommodate the thick-
ness of the finished wall (Figure 57).
See Page 5 for Cold Climate Insula-
tion and Page 9 for Clearances.
Air Shutter Adjustment Guidelines:
Amount of
Primary Air
Flame
Color
Air Shutter
Adjustment
• If flame appears weak or sooty, adjust
theairshutter, incrementally, toamore
open position until the proper flame
appearance is achieved.
• If flame stays lowered blue, adjust the
air shutter, incrementally, to a more
closed position until the proper flame
appearance is achieved.
If air shutter is
closed too far
Flame will Air shutter
be orange gap should be
increased
This Area Must
Remain Clear of
3"
If air shutter is
open too far
Flame will Air shutter
be blue gap should be
decreased
(76 mm)
Combustible
Combustible
Materials
Finished
Wall Materials
1 in. Min.
(25 mm)
4. Leave the control knob (off/pilot/on) in the
ON position and the burner OFF/ON switch
OFF (& remote switches, if applicable).
5. When satisfied that the burner flame ap-
pearance is normal, close the lower control
compartment door then proceed to finish
the installation.
WARNING
Airshutteradjustmentshouldonly
beperformedbyaqualifiedprofes-
sional service technician.
Top Spacers
Drywall
Bracket/Spacer
Air Shutter
Adjusting
Rod
Combustible
Top of Appliance
Louvers
Top of Door Frame
material may
touch
Burner
Venturi
Tube
Air Shutter
Opening
WARNING
Ensure glass panels are in place
and sealed during adjustment.
appliance
top
Orifice
Hood must be installed as shown.
Figure 57 - Combustible Wall Framing
CAUTION
Carbon/soot will be produced
if the air shutter is closed too
much. Any damage due to
carbon/sooting resulting from
improperly setting the air shut-
ter is not covered under the
warranty.
Increase Shutter
Opening In This
Direction
Air Shutter
Adjusting
Decrease Shutter
Opening In This
Direction
Arms
Ref. Air shutter Patent:
U.S. Pat. 5,553,603
Note - Both air shutters open and close simultaneously
when the air shutter adjusting rod is moved.
Note - Burners are omitted in this view for clarity.
***Main Burner Factory Air Shutter
Opening Setting - All Models
CAUTION
Natural Gas
Propane Gas
inches (millimeters)
inches (millimeters)
The air shutter door and nearby
appliancesurfacesarehot.Exer-
cisecautiontoavoidinjurywhile
adjusting flame appearance.
* TWO 1/8 (3) Slots
** TWO 11/16 (17) Slots
Adjustment Rod Positions, viewed from above:
* Natural Gas - fully clockwise
** Propane- fully counter clockwise
***Settings are shown for each burner.
Figure 56
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION ACCESSORIES
Item
Cat. No.
Model
Description
1
1
H1968
SV4.5HT-2
Horizontal Square Termination With Firestop / spacer
(H2246) & Adapter (74L61)
2a
2b
2b
2b
3
H2152
H4687
H4716
H4717
77L70
77L71
77L72
77L73
77L74
77L75
77L76
77L77
SV4.5CGV-1
SV4.5CTS
SV4.5CTS-B
SV4.5CTS-TC
SV4.5L6
Vertical Termination Cap
Chase Top Termination Square
Chase Top Termination Square, Black
Chase Top Termination Square, Terra Cotta
6 Inch (152 mm) Vent Section
12 Inch (305 mm) Vent Section
24 Inch (610 mm) Vent Section
36 Inch (914 mm) Vent Section
48 Inch (1219 mm) Vent Section
Telescopic Section (1-1/2" to 7-1/2" effective length)
45 Degree Elbow
3
SV4.5L12
SV4.5L24
SV4.5L36
SV4.5L48
SV4.5LA
3
3
3
3
3
4
SV4.5E45
SV4.5E90
5
90 Degree Elbow
4
5
The following flashings come packaged with a storm collar:
6
6
6
77L78
77L79
77L80
SV4.5F
Flat Roof Flashing
SV4.5FA
SV4.5FB
1/2 to 7/12 Adjustable Flashing
7/2 to 12/12 Adjustable Flashing
6
7
8
77L81
H2246
SV4.5SC6
SV4.5HF
Storm Collar (6 per box)
Firestop / Spacer-Horizontal (3-1-1 spacing), 10 Pack
8
H2247
96K93
96K94
96K92
17M52
SV4.5VF
Firestop / Spacer-Vertical (1-1-1 spacing), 10 Pack
Support Strap
9
SV4.5SU
SV4.5RSA
SV4.5SP
10
11
12
Attic Insulation Shield
Support Plate
7
SV4.5HGS-1
Termination Guard, Square (1 pack)
(for square termination)
12
13
17M53
87L02
SV4.5HGS-12
SV4.5HGS
Termination Guard, Square (12 pack)
(for square termination)
Termination Guard for Square Termination (Deluxe)
(1 pack) (for square termination)
12
11
8
10
9
Ref. 750,109M
13
2a
2b
Ref. 750,055M
Ref. 750,207M
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Item Cat. No.
Model
Description
19
18
18
18
18
18
18
19
H1969
77L87
77L88
77L89
77L90
77L91
56L74
SF4.5HT-2 Horizontal Square Termination (without flex)
SFKIT12S Flex Square Term. (with 12 inch [305 mm] * compressed flex)
SFKIT18S Flex Square Term. (with 18 inch [457 mm] * compressed flex)
SFKIT24S Flex Square Term. (with 24 inch [610 mm] * compressed flex)
SFKIT36S Flex Square Term. (with 36 inch [914 mm] * compressed flex)
SFKIT48S Flex Square Term. (with 48 inch [1219 mm] * compressed flex)
SFVT30
VerticalTerminationforflex (flatto6/12)withflexadapter, sectionofrigidvent,
roof support collar assembly, roof flashing and storm collar.
19
56L75
SFVT45
Vertical Termination for flex (6/12 to 12/12) with flex adapter, section of rigid
vent, roof support collar assembly, roof flashing and storm collar.
*20
*20
22
22
23
23
25
26
26
26
8
60L10
98K03
10K81
89L40
91L66
91L67
H1988
H1985
H1987
H1986
H2248
H2249
SF-18
SF-12
18 ft. (5.49 m) * compressed flex
12 ft. (3.66 m) * compressed flex
SFMP
Mill-Pac, Black, High Temperature Sealant
Mill-Pac, Black, High Temperature Sealant - Bulk 12 pack
Gear Clamp 4.5 in. (114 mm) for flex (6 pieces)
Gear Clamp 7.5 in. (190.5 mm) for flex (6 pieces)
Chase Top Shroud Kit, Arch Top 3 X 3
SFMP-12
SF-GC4-6
SF-GC7-6
CTSA-33
CTSO-33
CTSO-44
CTSO-46
SF4.5HF
SF4.5VF
Chase Top Shroud Kit, Open Top 3 X 3
Chase Top Shroud Kit, Open Top 4 X 4
Chase Top Shroud Kit, Open Top 4 X 6
Firestop / Spacer - Horizontal (flex) (3-1-1 spacing), 10 Pack
Firestop / Spacer - Vertical (1-1-1 spacing), 10 Pack
8
1
typ.
All compressed flex vents can be
expanded up to two times.
*
CTSO-46 Shroud
26
E
for double
terminations
25
2a
2b
C
2a
2b
2b
18
2a
D
2a
B
A
A
Ref. Form #750,193M
B
C
1
typ.
D
C
typ.
2
E
D
Ref. Form #750,194M
B
A
CTSO-33/44 Shrouds
for Single terminations
20
23
Closed Top Shroud Termination Kits
Inches (millimeters)
Open Top Shroud Kits
Inches (millimeters)
Model
A
B
C
D
Model
A
B
C
D
*E
37-5/8 37-5/8 7-1/2 24-1/2
(955) (955) (191) (622)
3
CTSO-33
34"
5"
34"
34"
CTSA-33
(76)
22
(864) (127) (864) (864)
S
e
a
l
a
n
t
48-5/8 48-5/8 7-1/2 24-1/2
(1235) (1235) (191) (622)
3
(76)
CTSO-44
CTSO-46
48-5/8 73 1/4 7-1/2 24-1/2
(1235) (1860) (191) (622)
3
(76)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
GAS CONVERSION KITS
Gas conversion kits are available to adapt the
appliance from the use of one type of gas to
the use of another. These kits contain all the
necessarycomponentsneededtocompletethe
task including labeling that must be affixed to
ensure safe operation.
IMPORTANT
WARNING
CANADA ONLY
This conversion kit shall be
installed by a qualified service
agency in accordance with the
manufacturer's instructions and
all applicable codes and require-
ments of the authorized having
jurisdiction. If the information in
these instructions is not followed
exactly, a fire, explosion or pro-
duction of carbon monoxide may
result causing property damage,
personal injury or loss of life.
The installation is not proper and
completeuntiltheoperationofthe
convertedapplianceischeckedas
specifiedintheownerinstructions
suppliedwiththekit.Thequalified
service agency performing this
installationassumesresponsibil-
ity for this conversion.
The conversion shall be carried
outinaccordancewiththerequire-
mentsoftheprovincialauthorities
having jurisdiction and in accor-
dance with the requirements of
the CAN1-B149.1 And B149.2
Installation code.
Kitpartnumbersarelistedhereandthefollowing
steps detail the conversion procedure.
Step1.Turnoffthegassupplytotheappliance.
Removethefrontglassdoor/framefromtheap-
pliance (see Removing Glass Enclosure Panels
onPage29).Removethecontrolcompartment
door(seeControlCompartmentDoorRemoval
on Page 27).
ATTENTION
LE CANADA SEULEMENT
Step 2. Carefully remove the logs. Exercise
care so as not to break the logs.
La conversion devra être effec-
tuée conformément aux recom-
mandations des autorités pro-
vinciales ayant juridiction et
conformémentauxexigencesdu
coded'installationCAN1-B149.1
Et.2.
Step 3. Referring to Figure 58, remove the
front burner and then the rear burner.
NOTE: REMOVE FRONT BURNER FIRST,
THEN REAR BURNER.
REAR BURNER
VENTURI
TUBE ARM
AVERTISSEMENT
Natural Gas to Propane Gas
Conversion Kits
FRONT BURNER
Cet Équipement de conversion
sera installÉ par une agence
qualifiÉe de service conformÉ-
ment aux instructions du fabri-
cantettoutesexigencesetcodes
applicables de l’autorisÉs avoir
la juridiction. Si l’information
dans cette Instruction n’est pas
suivieexactement,unfeu,explo-
sion ou production de protoxyde
de carbone peut rÉsulter le
dommages causer de propriÉtÉ,
perte ou blessure personnelle
de vie. L’agence qualifiÉe
de service est esponsable de
l’installation propre de cet
Équipment. L’installation n’est
pas propre et complÉte jusqu’à
l’opÉrationdel’appareilconverti
est chÉque suivant les critères
Établis dans les instructions de
propriÉtaire provisionnÉes avec
l’Équipement.
VENTURI
Fireplace
Type
Cat. No.
(model)
TUBE ARM
AIR SHUTTER
ADJUSTMENT LEVER
85L65
FGCK-DMOMNP
Millivolt
85L79
FGCK-DMOENP
Electronic
FIREBOX SUBFLOOR
FRONT OF FIREPLACE
Table 12
Propane Gas to Natural Gas
Conversion Kits
Figure 58
Fireplace
Type
Cat. No.
(model)
Step 4. Millivolt Appliances - SIT Systems
a. See Figure 59 and the instructions
provided with the kit. Using a Torx T20,
tool or or standard flat screwdriverremove
and discard the three pressure regulator
mounting screws. Remove the pressure
regulator, spring, poppet, diaphragm and
bushing. Discard all removed components.
Ensure the rubber gasket installed on the
back of the replacement pressure regulator
is properly positioned and install the new
pressure regulator using the new screws
supplied with the kit. Tighten screws to 25
In. lb. torque.
85L72
FGCK-DMOMPN
Millivolt
85L86
FGCK-DMOEPN
Electronic
Table 13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
When reinstalling the igniter assembly, use
extreme care to prevent damage and break-
age. Do not apply any leverage to the igniter
assembly while restoring the retainer clip to
its original position.
b. Attach manometer to the manifold side
pressuretestfittingandverifymanifoldpres-
sure reads 3.5 inches water column (0.87
kPa) for natural gas, and 10.0 inches water
column (2.49 kPa) for propane gas.
Electronic Appliances
Step 7. Honeywell Electronic Valves - See
Figure 61 and the instructions provided with
the kit. Remove the slotted cap screw, o-ring,
pressure-regulatingadjustingscrewandspring.
Retain all parts for possible later use. Install
new components from the kit. Black cap and
red spring for propane gas appliances. Silver
cap and stainless steel spring for natural gas
appliances. Before installing the cap, attach
manometer to the manifold side pressure test
fitting and adjust screw until pressure reads
3.5 inches water column (0.87 kPa) for natural
gas, and 10.0 inches water column (2.49 kPa)
for propane gas.
c.RefertoFigure60andremovethepilothood
assembly to access the hexed pilot orifice.
Remove and replace the orifice with the one
provided with the kit.
Pilot
Assembly
Pilot
Orifice
Igniter
Assembly
SIT Millivolt Gas Valve
Pressure
Regulator
SeeFigure62 andreplacethepilotorificeasfol-
lows: Removetheigniterassemblyretainerclip,
and carefully remove the igniter assembly.
Retaining
Flare Nut
Clip
Note: If the igniter is damaged, a replacement kit
is available, order Catalog No. 87L54.
Gas Valve
Assembly
Figure 62
Remove
These
Components
All Models
Figure 59
Manifold
Pressure
Test Port
Step 8. (Refer to Figure 58 on Page 33)
A. Remove the two orifices from the manifold
and replace them with the ones provided in the
kit. Table 14 shows the orifice sizes for natural
and propane models. Figure 63 illustrates the
orifice.
Slotted
Cap
Pilot for SIT Millivolt
Gas Valve
Spring
Adjusting
Screw
B. Install rear burner first, followed by front
burner, as shown in Figure 64. Ensure that the
armoftheventuriofeachburnerishookedonto
the air shutter adjustment lever (refer to Figure
58 on Page 33). The primary air opening can
be adjusted by rotating the adjustment lever
from beneath the firebox floor. Refer to Figure
56 on Page 30 for the recommended minimum
primary air opening setting.
Figure 61
Pilot
Orifice
Exercise extreme care to prevent damage to
or breakage of the igniter assembly.
Remove the screw securing the pilot assembly
to its mounting bracket. Back off the flare nut
at the end of the pilot gas line to free the pilot
assembly from the gas line. Remove the pilot
orifice and replace it with the one provided with
the conversion kit. Reinstall the pilot assembly
by reversing the steps detailed here.
Figure 60
• • Burner Orifice Sizes (all models)
Step 5. Attach manometer to the manifold side
pressure test fitting and verify manifold pres-
sure reads 3.5 inches water column (0.87 kPa)
for natural gas, and 10.0 inches water column
(2.49 kPa) for propane gas.
Elevation
Natural Gas
Propane
Feet (meters)
drill size (inches)
Gas
drill size (inches)
0-4500
(0-1372)
#44 (.086")
60J8001 •
#55 (.052")
*
*
19L5201 •
Step 6. Refer to Figure 60 and remove the
pilot hood assembly to access the hexed pilot
orifice. Remove and replace the orifice with
the one provided with the kit.
* Standard size installed at factory
• Part /Cat. Number
• • Each model has two burners & 2 Orifices
Table 14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
BURNER ORIFICE
BURNER POSITIONING
NOTE: INSTALL REAR BURNER FIRST,
THEN FRONT BURNER.
BURNER
PORTS
BRACKET A
REAR BURNER
Figure 63
Step9.Reassembletheremainingcomponents
by reversing the procedures outlined in the
preceding steps. Use pipe joint compound or
Teflon tape on all pipe fittings before installing
(ensurepropaneresistantcompoundsareused
in propane applications, do not use pipe joint
compounds on flare fittings).
PILOT
BURNER
Step 10. Attach the conversion label provided
in the conversion kit to the rating plate on the
appliance.
FRONT BURNER
Note: The burners are not identical. Position them so
that the circular burner ports run as shown. Note
especially the vertical run of ports relative to the pilot
burner. Bracket A on the rear burner will interfere with
the pilot burner if an attempt is made to install the
rear burner in the front burner’s position.
Step 11. Turn on gas supply and test for gas
leaks.
Figure 64
35
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
LHP reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor
for fireplace code information.
Printed in U.S.A. © 2005 by LHP
LHP
P/N 700,031M REV. C 11/2006
1110 West Taft Avenue • Orange, CA 92865
Download from Www.Somanuals.com. All Manuals Search And Download.
|