Thermo Products Furnace CDX1 100N User Manual

TWO STAGE CONDENSING GAS FURNACE  
INSTALLATION AND OPERATION MANUAL  
MODELS:  
FOR USE WITH NATURAL GAS OR LP GAS (PROPANE)  
CHX1-75N  
CHX1-100N  
CHX1-125N  
CDX1-75N  
CDX1-100N  
CDX1-125N  
: IF YOU DO NOT FOLLOW THE SAFETY PRECAUTIONS BELOW AND IN THIS  
MANUAL, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL  
INJURY, OR LOSS OF LIFE.  
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE  
VICINITY OF THIS OR ANY OTHER APPLIANCE.  
WHAT TO DO IF YOU SMELL GAS:  
DO NOT TRY TO LIGHT ANY APPLIANCE.  
DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE IN YOUR BUILDING.  
LEAVE THE BUILDING IMMEDIATELY.  
IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S PHONE. FOLLOW THE GAS  
SUPPLIER’S INSTRUCTIONS.  
IF YOU CANNOT REACH YOUR GAS SUPPLIER; CALL THE FIRE DEPARTMENT.  
INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER, SERVICE  
AGENCY OR THE GAS SUPPLIER. (REFERRED TO IN THESE INSTRUCTIONS AS A QUALIFIED  
HEATING CONTRACTOR).  
PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION, INITIAL FIRING, AND BEFORE  
PERFORMING ANY SERVICE OR MAINTENANCE. THESE INSTRUCTIONS MUST BE LEFT WITH  
THE HOMEOWNER AND SHOULD BE RETAINED FOR FUTURE REFERENCE BY QUALIFIED  
SERVICE PERSONNEL.  
THERMO PRODUCTS, LLC.  
BOX 217  
NORTH JUDSON, IN 46366  
PHONE: (574) 896-2133  
MADE IN USA  
MG-1010  
ECN4470-MA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
This and the previous page contain reproductions of the various warning and instruction labels placed on  
the Thermo Pride Two Stage Condensing Gas Furnaces. Please read and comply with the contents of  
these labels.  
The following safety information should be read, understood, and followed by the installer.  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
1. Use only with type of gas approved for this furnace. Refer to furnace rating plate.  
2. Connect this furnace to an approved vent system only. Combustion products must be carried outdoors.  
Refer to Section III, D thru H, of this manual.  
The following pages contain various warnings and cautions found throughout the Thermo Pride  
Highboy and Dual Poise Two Stage Condensing Gas Furnace Manual. Please read and comply  
with the statements below.  
: This furnace is not to be used for temporary heating of buildings or structures under  
construction.  
: These high efficiency condensing furnaces are not certified for and shall not be  
vented into a standard or any type of chimney.  
: These furnaces may not be common vented with any other appliance.  
: The vent and air intake elbows must be kept away from bushes, shrubs or any  
vegetation that may restrict the flow of flue products. It must also be kept clear of any leaves,  
weeds or other combustible materials. Keep the vent hood clear of snow. Avoid locating the  
terminals in areas where standing water or condensate drippage may be a problem.  
: Outside combustion air must not come from an area that is directly adjacent to a  
pool, hot tub or spa. Measures should be taken to prevent the entry of corrosive chemicals or  
vapors to the combustion and ventilation air supply. Such chemicals include but are not limited to  
chlorinated and/or fluorinated hydrocarbons such as found in refrigerants, aerosol propellants,  
dry cleaning fluids, degreasers and removers. Other harmful compounds may come from  
bleaches, air fresheners or mastics. Vapors from such products can form acid compounds when  
burned in a gas flame. Should acid compounds form in your furnace; it may reduce the life of the  
furnace.  
: Because of the potential of odorant fade, a gas leak may not be detected by smell. If  
this furnace is installed below grade, contact your gas supplier for a gas detector.  
: Turn off power to furnace before it is placed into service. The gas piping system  
must have been leak tested by a qualified heating contractor.  
: It may be necessary to purge the air out of the gas line for initial start-up of the  
furnace after installation. This should be done by a qualified heating contractor. If excessive gas  
escapes when purging the gas supply at the union, allow the area to ventilate for at least 15  
minutes before attempting to start the furnace. LP gas is especially dangerous because the  
specific gravity of LP gas allows it to accumulate at floor level at a dangerous concentration. For  
remainder of operating instructions, reference Users Information Manual.  
: Heat exchanger oil will burn off on initial firing creating an unpleasant odor. To  
prevent this odor from occurring more than once, it is suggested that:  
1. A window(s) be opened.  
2. The thermostat set at highest setting.  
3. The furnace remain running at conditions 1&2 for 30 minutes or until odor has dissipated.  
: The CHX1/CDX1 furnace models are sealed combustion design, which does not  
require an air shutter adjustment (air shutters are not used) for proper flame characteristics.  
Burner box access cover must always be secured with all screws in place and tightened before  
operating furnace.  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
: Personal injury or property damage could result from repair or service of this furnace  
by anyone other than a qualified heating contractor. Only the homeowner/user routine  
maintenance described in the Users Information Manual may be performed by the user.  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
INDEX  
SECTION  
BEGINNING PAGE  
I.  
SAFETY INFORMATION  
i
II.  
III.  
FURNACE SPECIFICATIONS  
GENERAL INSTALLATION  
1
6
A. CODES AND CLEARANCES  
6
B. FURNACE LOCATION  
7
B1.CDX1 HORIZONTAL APPLICATION  
C. REPLACING EXISTING FURNACE FROM A COMMON VENT  
D. GENERAL REQUIREMENTS FOR VENTING CHX1/CDX1  
E. SIDEWALL VENTING  
E1. SINGLE PIPE (SIDEWALL) VENTING OPTION  
F. INSTALLATION OF OUTSIDE VENT/AIR INTAKE TERMS.  
G. CONNECTING FURNACE TO VENT/AIR INTAKE TERMS.  
H. CONNECTING FURNACE TO ROOF VENT/AIR TERMS.  
I. CONDENSATE DRAIN LINE & TRAP ASSY.  
J. GENERAL GAS PIPING  
K. FILTERS  
L. WIRING  
STARTING THE UNIT  
A. SEQUENCE OF OPERATIONS  
B. INITIAL START-UP  
7
9
9
10  
12  
13  
14  
19  
20  
22  
23  
25  
29  
29  
32  
40  
40  
41  
IV.  
C. FURNACE CHECKOUT PROCEDURE  
INSTALLER’S INSTRUCTIONS TO USER  
TROUBLESHOOTING  
V.  
VI.  
APPENDIX – A  
APPENDIX – B  
REPLACEMENT PARTS LIST  
WIRING DIAGRAMS  
48  
52  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
II. FURNACE SPECIFICATIONS  
CHX1 SERIES  
MODEL NO.  
CHX1-75  
CHX1-100  
CHX1-125  
75,000 / 52,000 100,000 / 70,000 125,000 / 87,500  
BTU/HR INPUT (High fire/ Low fire)  
BTU/HR OUTPUT (High fire/ Low fire)  
70,875 / 49,612  
94,500 / 66,150 117,500 / 82,250  
44-1/4”  
17”  
27-1/2”  
15 x 18  
25 x 16  
44-1/4”  
21”  
27-1/2”  
19 x 18  
25 x 16  
44-1/4”  
24”  
27-1/2”  
22 x 18  
25 x 16  
HEIGHT OF CASING  
WIDTH OF CASING  
DEPTH OF CASING  
WARM AIR OUTLET  
RETURN AIR INLET  
2”  
2”  
3”  
3”  
3”  
3”  
DIA. OF FLUE  
DIA. OF COMBUSTION  
AIR INTAKE  
CFM from .2” & .5” w.c.  
EXTERNAL STATIC PRESSURE  
@COOLING TAP A  
COOLING  
COOLING  
COOLING  
1000  
800  
1200  
1400  
1200  
1000  
1400  
1600  
1400  
1200  
1600  
2000  
@COOLING TAP B  
@COOLING TAP C  
@COOLING TAP D  
HEATING  
931 / 760  
HEATING  
1243 / 1015  
HEATING  
1556 / 1270  
@HEATING TAP A (High fire/Low fire)  
70 / 60  
.5  
70 / 60  
.75  
70 / 60  
1
TEMPERATURE RISE  
BLOWER MOTOR HP  
-
2.65 Mh  
4 Ton  
2.1 Mh  
5 Ton  
POWER CHOKES  
LARGEST RECOMMEDED  
AIR CONDITIONER  
SIZE OF FILTERS  
NOTES:  
3.5 Ton  
24-3/4” x 15-3/4” 24-3/4” x 15-3/4” 24-3/4” x 19-3/4”  
1. BTU output based on annual fuel utilization efficiency rated by manufacturer.  
2. On all outlet and inlet dimensions, the first dimension is width.  
3. To permit largest recommended air conditioning (at .5 static pressure), selection of the highest motor  
speed is required.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
CDX1 SERIES  
MODEL NO.  
CDX1-75  
CDX1-100  
CDX1-125  
75,000 / 56,250 100,000 / 75,000 125,000 / 93,750  
69,750 / 52,312 93,000 / 69,750 116,250 / 87,187  
BTU/HR INPUT (High fire / Low fire)  
BTU/HR OUTPUT (High fire / Low fire)  
46-1/4”  
17”  
27-1/2”  
15 x 18  
15 x 22  
46-1/4”  
21”  
27-1/2”  
19 x 18  
19 x 22  
46-1/4”  
24”  
27-1/2”  
22 x 18  
22 x 22  
HEIGHT OF CASING  
WIDTH OF CASING  
DEPTH OF CASING  
WARM AIR OUTLET  
RETURN AIR INLET  
2”  
2”  
3”  
3”  
3”  
3”  
DIA. OF FLUE  
DIA. OF COMBUSTION  
AIR INTAKE  
CFM from .2” & .5” w.c.  
EXTERNAL STATIC PRESSURE  
COOLING  
COOLING  
COOLING  
1000  
800  
1200  
1400  
1200  
1000  
1400  
1600  
1400  
1200  
1600  
2000  
@COOLING TAP A  
@COOLING TAP B  
@COOLING TAP C  
@COOLING TAP D  
HEATING  
1012 / 826  
HEATING  
1340 / 1094  
HEATING  
1673 / 1366  
@HEATING TAP C (High fire / Low fire)  
65 / 60  
.5  
65 / 60  
.75  
65 / 60  
1
TEMPERATURE RISE  
BLOWER MOTOR HP  
-
2.65Mh  
4 Ton  
2.1Mh  
5 Ton  
POWER CHOKES  
LARGEST RECOMMEDED  
AIR CONDITIONER  
SIZE OF FILTERS  
NOTES:  
3.5 Ton  
21-3/4” x 14”(2) 21-3/4” x 14”(2)  
21-3/4” x 14”(2)  
1. BTU output based on annual fuel utilization efficiency rated by manufacturer.  
2. On all outlet and inlet dimensions, the first dimension is width.  
3. To permit largest recommended air conditioning (at .5 static pressure), selection of the highest motor  
speed is required.  
4. Electrical characteristics at 115 volts, 60 Hz., 1 phase (less than 15 amps. for all models).  
5. All specifications are subject to change without notice.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
INSTALLATION PARTS PACKAGES – CHX1-75  
PARTS PACKAGE  
DESCRIPTION  
PART #  
QUANTITY  
#S00S4378  
2-3/8” ID radiator hose  
Thermostat lead bushing  
PVC trap assembly  
410017  
350750  
320816  
1
1
1
#8 x ¾ coated TEK screws for  
mounting trap & inlet/outlet collars  
11/16” OD x 1/2” ID vinyl tubing  
2 x 4 electrical J-box  
2 x 4 electrical J-box cover  
#8 x ½ TEK screws for  
mounting 2 x 4 J-box  
300283  
4
410060  
350024  
350020  
24”  
1
1
300208  
2
#10-32 x ½ green ground screw  
#10-32 hex nut  
3/16” dia. star washer  
Grounding instructions  
Wire nut  
3” stainless steel hose clamp  
J-box wire bushing  
Drain hose grommet  
300109  
300110  
300270  
MG-966  
300132  
300276  
350016  
350446  
300299  
MG-987  
320818  
1
1
1
1
2
2
1
1
3
1
1
Spring clamp, 11/16”  
Installation notice  
PVC tee assembly, 2” dia.  
INSTALLATION PARTS PACKAGES – CHX1-100-125  
PARTS PACKAGE  
DESCRIPTION  
#S00S4379  
PART #  
QUANTITY  
2-3/8” ID radiator hose  
Thermostat lead bushing  
PVC trap assembly  
410017  
350750  
320816  
1
1
1
#8 x ¾ coated TEK screws for  
mounting trap & inlet/outlet collars  
11/16” OD x ½” ID vinyl tubing  
2 x 4 electrical J-box  
2 x 4 electrical J-box cover  
#8 x ½ TEK screws for  
mounting 2 x 4 J-box  
300283  
4
410060  
350024  
350020  
24”  
1
1
300208  
2
#10-32 x ½ green ground screw  
#10-32 hex nut  
3/16” dia. star washer  
Grounding instructions  
Wire nut  
3” stainless steel hose clamp  
J-box wire bushing  
Drain hose grommet  
300109  
300110  
300270  
MG-966  
300132  
300276  
350016  
350446  
300299  
MG-987  
320817  
1
1
1
1
2
2
1
1
3
1
1
Spring clamp, 11/16”  
Installation notice  
PVC tee assembly, 2 x 3” dia.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
INSTALLATION PARTS PACKAGES – CDX1-75  
PARTS PACKAGE  
DESCRIPTION  
PART #  
QUANTITY  
#S00S4380  
2-3/8” ID radiator hose  
Thermostat lead bushing  
PVC trap assembly  
410017  
350750  
320816  
1
1
1
#8 x ¾ coated TEK screws for  
mounting trap & inlet/outlet collars  
11/16” OD x ½” ID vinyl tubing  
2 x 4 electrical J-box  
2 x 4 electrical J-box cover  
#8 x ½ TEK screws for  
mounting 2 x 4 J-box  
#10-32 x ½ green ground screw  
#10-32 hex nut  
3/16” dia. star washer  
Grounding instructions  
Wire nut  
3” stainless steel hose clamp  
J-box wire bushing  
Drain hose grommet  
Spring clamp, 11/16”  
Installation notice  
PVC tee assembly, 2” dia.  
Pipe 2” dia. PVC 15”  
Bracket  
300283  
6
410060  
350024  
350020  
24”  
1
1
300208  
2
300109  
300110  
300270  
MG-966  
300132  
300276  
350016  
350446  
300299  
MG-987  
320819  
14401  
1
1
1
1
2
2
1
1
3
1
1
1
1
14406  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
INSTALLATION PARTS PACKAGES – CDX1-100-125  
PARTS PACKAGE  
DESCRIPTION  
PART #  
QUANTITY  
#S00S4381  
2-3/8” ID radiator hose  
Thermostat lead bushing  
PVC trap assembly  
410017  
350750  
320816  
1
1
1
#8 x ¾ coated TEK screws for  
mounting trap & inlet/outlet collars  
11/16” OD x 1/2” ID vinyl tubing  
2 x 4 electrical J-box  
2 x 4 electrical J-box cover  
#8 x ½ TEK screws for  
mounting 2 x 4 J-box  
#10-32 x ½ green ground screw  
#10-32 hex nut  
3/16” dia. star washer  
Grounding instructions  
Wire nut  
3” stainless steel hose clamp  
J-box wire bushing  
Drain hose grommet  
Spring clamp, 11/16”  
Installation notice  
PVC tee assembly, 2 x 3” dia.  
PVC tee assembly, 2” dia.  
Pipe 2” dia. PVC 15”  
300283  
4
410060  
350024  
350020  
24”  
1
1
300208  
2
300109  
300110  
300270  
MG-966  
300132  
300276  
350016  
350446  
300299  
MG-987  
320817  
320819  
14401  
1
1
1
1
2
2
1
1
3
1
1
1
1
1
1
Bracket  
Reducer 2” x 3” PVC  
14406  
320067  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
III. GENERAL INSTALLATION  
These Category Type IV furnaces are shipped completely assembled and wired (internally). See the  
Dealer Receiving and Freight Claim Procedure Section of the price guide for parts shortage or damage.  
The furnace and duct system must be adjusted to obtain a temperature rise of 55°F to 85°F through the  
furnace after installation. (See rating label located on side panel inside the furnace vestibule). The  
installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas  
Codes (ANSI Z223.1 or latest edition) and with these instructions.  
: This furnace is not to be used for temporary heating of buildings or structures under  
construction.  
Many of the chemicals used during construction, when burned, form acid bearing condensate that can  
substantially reduce the life of the heat exchanger.  
A. CODES AND CLEARANCES  
The following items must be considered when choosing the size and location of the furnace.  
1. All local codes and/or regulations take precedence over the instructions in this manual and should be  
followed accordingly. In the absence of local codes, installation must conform with these instructions,  
regulations of the National Fire Protection Association, provisions of National Electrical Code  
(ANSI/NFPA70 or latest edition), and the National Fuel Gas Code (ANSI Z223.1 or latest edition).  
2. The BTU output capacity of the furnace proposed for installation should be based on a heat loss  
calculation made according to the manuals provided by the Air Conditioning Contractors of America  
(ACCA) or ASHRAE.  
3. MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS  
TABLE 1  
FROM SIDES OF  
FURNACE & REAR  
TOP OF  
PLENUM  
0 IN.  
FROM THE  
FLUE OR VENT  
0 IN.  
SIDE OF  
PLENUM  
1 IN.  
MODEL NO.  
FRONT  
0 IN.  
0 IN.  
0 IN.  
0 IN.  
0 IN.  
0 IN.  
6 IN.  
6 IN.  
6 IN.  
6 IN.  
6 IN.  
6 IN.  
CHX1-75  
CHX1-100  
CHX1-125  
CDX1-75  
CDX1-100  
CDX1-125  
0 IN.  
0 IN.  
0 IN.  
0 IN.  
0 IN.  
0 IN.  
0 IN.  
0 IN.  
1 IN.  
1 IN.  
1 IN.  
1 IN.  
0 IN.  
0 IN.  
1 IN.  
The CHX1-75, 100 and 125 furnaces may be installed on combustible flooring. The furnace shall not be  
installed directly on carpeting, tile or other combustible material other than wood flooring.  
The CDX1-75, 100 and 125 furnaces are to be installed on non-combustible flooring only. The non-  
combustible floor bases model no. 50 CA base for CDX1-75 model no. 100 CA base for the model no.  
CDX1-100 and model no. 125 CA base for CDX1-125 are available for the counterflow furnaces to allow  
their installations on combustible flooring.  
These furnaces may be installed in an alcove or in a closet if the minimum clearances to combustible  
construction (listed previously) are met. The CDX1 series furnaces may be installed in an attic or crawl  
space. Refer to section III, B1 of this installation manual.  
The minimum clearances are listed for fire protection. Clearance for servicing the front of the furnaces and  
to all points on the furnace requiring access must be 24”*.  
*For horizontal furnace installation, refer to section III, B1 of this installation manual.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Equipment must be installed in accordance with regulations of the National Board of Fire  
Underwriters. Authorities having jurisdiction should be consulted before installations are made.  
B. FURNACE LOCATION  
: These high efficiency condensing furnaces are not certified for and shall not be  
vented into a standard or any type of chimney.  
The following shall be considered for locating the furnace:  
1. For best performance locate the furnace so that it is centralized with respect to the duct system and  
as near as possible to a floor drain since condensate drainage must be provided.  
2. Place the unit so that proper venting can be achieved, with a minimum number of elbows, in accord  
with the instructions in this manual.  
3. The furnace must be located on a level, dry surface. The furnace must be installed so that the  
electrical components are protected from water. If the area becomes wet or damp at times, the  
furnace should be raised above the floor using a concrete base, bricks, patio blocks, etc.  
NOTICE: Ensure furnace is level after installation to ensure proper drainage and operation.  
4. This furnace must be connected to a drain in accordance with these instructions. If it is not practical to  
connect the unit to a drain, a condensate pump must be used and can be ordered as an accessory,  
part number 350225. If an acid neutralizer kit is required by local code or the customer, it is available  
under part number 320095.  
B1. CDX1 HORIZONTAL APPLICATION  
The CDX1-75, 100, and 125 furnaces may be installed in a horizontal position by placing the furnace on  
the left or right side (as viewed from the front in the upright position).  
For left or right horizontal applications of the CDX1 series units, the rollout switch located on the burner  
box must be moved to the pre-punched mounting holes on the side of the burner box. Screws are  
provided in pre-punched holes at the required limit location. Remove these screws and use them to mount  
the limit to new location. Utilize previously removed limit mounting screws to fill voided holes at previous  
limit location (See Figure 1).  
For a right side horizontal application of the CDX1 series units, the hose from the single tap pressure  
switch (top switch) is already connected correctly (See Figure 1).  
For a left side horizontal application of the CDX1 series units, the hose from the single tap pressure switch  
(bottom switch) must be moved to the lower front tap on the face of the collector box. Use the black cap  
removed from this tap to plug the original pressure switch tap.  
NOTE: The hose, when moved, must be shortened (cut) to ensure that no excess hose exists to cause a  
sag, loop, or "water trap".  
For a right side horizontal application of the CDX1 series units, the auxiliary limit switch located on the  
right side of the house air blower must be moved to the bracket on the opposite (left) side of the blower  
(See Figure 1).  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
NOTE: When the CDX1 is installed as horizontal unit, it is imperative that the auxiliary limit switch and  
bracket be located on the upper side of the house air blower; the burner rollout switch located on the  
burner box be relocated to the side of the burner box; and that the hose from the single tap pressure  
switch be connected to the lower tap on the front of the collector box (See Figure 1).  
Figure 1  
The horizontal furnace installation should be on a service platform large enough to allow for proper  
clearances on all sides and service access to the front of the furnace (See Table 1). If the furnace is  
suspended, it must be supported at both ends and in the middle with clearance allowed for removal of  
both access doors. Gas supply line contact is only permissible between lines formed by the intersection of  
the top and two sides of the furnaces casing and the building joists, studs, or framing (See Figure 1).  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Equipment must be installed in accordance with regulations of the National Board of Fire  
Underwriters and the National Fuel Gas Code. Authorities having jurisdiction should be consulted  
before installations are made.  
C. REPLACING AN EXISTING FURNACE FROM A COMMON VENT  
: These furnaces may not be common vented with any other appliance.  
D. GENERAL REQUIREMENTS FOR VENTING CHX1/CDX1  
The CHX1/CDX1 furnace venting system must be installed by a qualified service person in accordance  
with local codes, the National Fuel Gas Code (NFPA 54/ANSI Z223.1 or latest edition) and these  
instructions.  
The following items and local code requirements must be followed:  
1. The vent/air intake terminations outlined by Thermo Products in this manual must be used.  
2. The entire vent/air intake system must be made of PVC Schedule 40 pipe.  
NOTE: All CHX1/CDX1 furnaces recommended to be installed with outside combustion air.  
3. The flue vent pipe and combustion air pipe must be at least as large as the exhaust vent/air intake  
pipe specified by Thermo Products. No reduction in size is permissible. The CHX1, CDX1-75 requires  
2” Schedule 40 PVC pipe. The (CHX1, CDX1)-100 and 125 require 3” Schedule 40 PVC pipe.  
4. This CHX1/CDX1 furnace shall not be common vented with any other appliance including those  
burning solid fuels.  
5. Horizontal runs of exhaust vent pipe shall slope upward at least 1/4” per foot from the outlet of the  
furnace (CHX1’s) or the outlet of the drain tee (CDX1’s) to the vent termination at the outside wall.  
This will permit proper drainage of the condensate. Horizontal runs of inlet vent pipe shall slope  
downward at least 1/4” per foot from the outlet of the last elbow or last horizontal run, before exiting  
the wall, to the vent termination at the outside wall.  
6. The vent pipe must be supported every 4 feet and at every joint to prevent pipe blockage caused by  
condensate trapped by a sag in the vent.  
7. The maximum permissible vent length of straight pipe and number of elbows permitted for the  
exhaust vent and combustion air inlet is shown in Table 2. The elbows shown are in addition to the  
length of straight pipe permitted. When counting elbows, all elbows used in the exhaust vent or  
combustion air intake must be counted. This includes elbows used inside the furnace jacket and  
termination elbows. In addition, up to three elbows may be dropped and the vent length extended five  
feet for each elbow dropped.  
MAXIMUM VENT LENGTH  
TABLE 2  
VENT SIZE  
FURNACE  
MODEL  
2 IN. PVC  
EXHAUST  
LENGTH VENT  
3 IN. PVC  
EXHAUST  
LENGTH VENT  
VENT  
COMBUSTION  
AIR INTAKE  
VENT  
COMBUSTION  
AIR INTAKE  
(FT.)  
ELBOWS (NO.)  
ELBOWS (NO.)  
(FT.)  
ELBOWS (NO.)  
ELBOWS (NO.)  
2
CHX1/CDX1-75  
CHX1/CDX1-100  
CHX1/CDX1-125  
35  
8 1, 2  
7
-
35  
35  
-
-
NOT PERMITTED  
NOT PERMITTED  
8 1, 2  
8 1, 2  
7 2  
7 2  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
NOTES:  
1 The drain tee supplied with CHX1/CDX1 furnaces count as 1 elbow.  
2
(2) 45° elbows can be substituted for (1) 90° elbow.  
Care should be taken to plan out the vent system to be as short as possible (but not shorter than 8 ft.) and  
to contain as few elbows as possible to insure the best possible operation of the furnace.  
8. A hack saw may be used to cut the PVC pipe. It must be cut smoothly at right angles with all burrs  
removed. All joints must use standard PVC Schedule 40 elbows and couplings. Joints are not to be  
made by gluing and butting together the cut or raw edges of the vent pipe. The joints inside the  
vestibule should be sealed with a silicone caulk to allow for maintenance.  
Note: Do not use silicone caulk to seal the PVC sleeve or coupling to the metal air intake collar on  
the burner box. The screw securing the sleeve or coupling to the collar is sufficient.  
9. Vent connections shall be checked for leakage with the furnace induced draft blower running and with  
the vent termination blocked. A mild soap and water solution may be used to check for leaks.  
10. Vent pipe passing through an unheated space must be insulated with 1.0” thick foil faced fiberglass  
insulation or it’s equivalent to prevent freezing of any condensate within the pipe.  
11. Minimum clearance from the PVC pipe to combustible material is zero inches.  
12. Screens are not required by Thermo Products for the vent and intake. However, optional stainless  
steel screens are available from Thermo Products, should the homeowner request them.  
IMPORTANT: The CHX1/CDX1 furnace models may be vented either through the sidewall or roof. For  
sidewall instructions continue reading the following section. For roof venting refer to Section III, H, of this  
manual.  
E. SIDEWALL VENTING  
1. The maximum wall thickness through which the vent and combustion air pipes may pass is 18” and  
the minimum is 2”. The maximum distance from the outer wall to the center of the elbow is 12” (See  
Figure 2).  
Figure 2  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
NOTICE: If exterior sidewall building materials are subject to degradation from flue gases or moisture, a  
minimum 12” diameter shield made from stainless steel or high density plastic shall be used for protection.  
2. The PVC vent termination elbow must be installed in accord with local codes and these instructions.  
The bottom edge of the vent termination elbow must be installed at least 12 in. above the outlet of the  
combustion air intake termination elbow and must be installed in the same atmospheric pressure zone  
(i.e. on the same wall). It is recommended that the horizontal distance between the inlet and flue  
termination be kept to a minimum when possible and not exceed 24 in. apart. The vent and air intake  
should utilize the same numbers of elbows and approximately the same length of straight pipe to  
reach the outside termination elbows. (See Figures 2 & 3).  
Figure 3  
3. VENT TERMINAL LOCATION REQUIREMENTS  
a. The vent terminal shall be located at least 3 ft. above any forced air inlet located within 10 ft.  
b. The terminal shall be at least 1 ft. below, 1 ft. horizontally from or 1 foot above any door, window or  
gravity air inlet into any building. The bottom of the vent terminal shall be located at least 18 in. above  
grade.  
c. The terminal shall not be located over public walkways or over an area where condensate or vapor  
could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves  
or other equipment.  
d. A minimum horizontal clearance of 4 ft. must be maintained from electric meters, gas meters,  
regulators and relief equipment. The vent terminal shall not be installed over these or any other  
equipment where condensate or vapor could be detrimental to the operation of this equipment and/or  
controls.  
e. The unit shall be located so a minimum of 1/4" per foot upward slope can be maintained from the  
furnace to the terminal outlet and 1/4” per foot downward slope for the last horizontal run of inlet, to  
the outside inlet terminal.  
f. The vent discharge must be installed a minimum of 12” above grade, 14” from any obstruction and  
three feet from an inside corner of an L-shaped structure.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Figure 4  
: The vent and air intake elbows must be kept away from bushes, shrubs or any  
vegetation that may restrict the flow of flue products. It must also be kept clear of any leaves,  
weeds or other combustible materials. Keep the vent hood clear of snow. Avoid locating the  
terminals in areas where standing water or condensate drippage may be a problem.  
VENT TERMINAL LOCATION GUIDELINES  
In addition to following the requirements outlined by local codes, utilizing the guidelines below when  
possible in locating the vent terminal will help insure the trouble-free operation of your horizontally vented  
furnace:  
Avoid locating the vent terminal on a wall facing the prevailing winds and wide open areas.  
When this is not practical, choose locations that protect the vent from strong winds such as behind a  
fence or hedge. NOTICE: The vent terminal must be located a sufficient distance from bushes,  
shrubs, and vegetation so as not to have the flue products restricted or blocked from such vegetation.  
In areas with considerable snowfall, it is advisable to locate the vent terminal higher than the minimum  
12 in. above the ground as to prevent blockage by snow accumulation or drifting.  
Measures should be taken to prevent the entry of corrosive chemicals or vapors to the combustion and  
ventilation air supply. Such chemicals include but are not limited to chlorinated and/or fluorinated  
hydrocarbons such as found in refrigerants, aerosol propellants, dry cleaning fluids, degreasers and  
removers. Other harmful compounds may come from bleaches, air fresheners or mastics. Vapors from  
such products can form acid compounds when burned in a gas flame. The life of the furnace could be  
reduced should acid compounds form within your furnace.  
NOTICE: Heat exchanger failure caused from contaminated air will void its limited lifetime warranty.  
NOTICE: The vent termination and air inlet elbow shall be checked periodically, at least at the start of  
each heating season, for restriction or blockage from foreign material in the vent pipe or in the air inlet.  
The air inlet and vent pipe should be cleaned when necessary.  
E1. SINGLE PIPE (SIDEWALL) VENTING OPTION  
This furnace may be horizontally vented with a single exhaust pipe. This will be a non-direct vent  
installation. The same exhaust venting guidelines apply except the exhaust termination will be similar to  
the air intake of the "2 pipe" direct vent installation. Refer to intake terminal instructions Figure 3 and  
Figure 5. Termination will consist of one 90° elbow pointed downward. (See figure 2)  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
F. INSTALLATION OF OUTSIDE VENT/AIR INTAKE TERMINATIONS  
NOTICE: Installation of the outside exhaust and combustion air vents must be performed by a qualified  
installer or service person in accord with local codes, the National Fuel Gas Code (NFPA 54, ANSI Z223.1  
or latest edition) and the sections on venting in this manual.  
1. Observing all clearances specified in this manual, cut two 2-3/8” diameter holes in the outside wall for  
CHX1/CDX1-75 and two 3-1/2” diameter holes for the CHX1/CDX1-100 and 125.  
2. Cut two 2” diameter PVC pipes 1-1/2” longer than the depth of the wall. This allows for 3/4” connection  
on both ends of the pipe. (For 3” PVC pipe, leave 3” for connection). Using PVC pipe cement, cement  
a PVC elbow or coupler to one end of each pipe.  
Mark the pipe before inserting into the wall so the elbow orientation can be determined. Also, if a  
protective shield will be used on the exterior surface of the wall, it should be installed at this time. Glue a  
coupling or elbow to each pipe, depending on your installation with the PVC pipe cement being careful to  
maintain the proper orientation of the elbows. Complete the assembly of the outlet and inlet as shown in  
Figure 5, making sure that the spacing between the inlet and outlet complies with that shown in Figure 3.  
Figure 5  
3. Finish the vent installation by caulking around the two holes where the PVC pipes pass through the  
wall.  
4. An optional vent or intake terminal (stainless steel) screen is available under part no. 320226.  
Optional Terminations  
Two optional vent kits are available for vent terminations on horizontal vent applications. The concentric  
vent kit (part no. 370171) allows for the vent and intake to be installed through one 4.5-inch diameter  
hole. The side wall vent cap (part no. 370191) is a cover to be installed over the vent and intake pipe as  
they exit the exterior of the building. These optional kits shall be installed according to the instructions  
provided with each kit. The locations and clearances are identical to the requirements of the standard  
vent terminations described in this manual. These vent kits may be used on any size of the CHX1/CDX1  
furnace series.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
G. CONNECTING FURNACE TO THE VENT/AIR INTAKE TERMINATION AND  
DRAIN  
1. The following diagrams show the typical vent and air inlet connection for a CHX1 and CDX1 furnace  
as well as a list of the parts that will be needed to install each.  
Figure 6  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Figure 7  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Figure 8  
2. CONNECTING THE EXHAUST VENT TO THE INDUCER  
a. Insert the end of the 2”dia. PVC elbow (2" dia. PVC tee assembly for CDX1 horizontal installations)  
onto the outlet of the inducer blower assembly. Measure the length of 2” dia. PVC pipe needed to  
clear the furnace side casing, while allowing for the 2-3/8” rubber radiator hose to be installed within  
the casing of the furnace. Cut the 2” dia. PVC measured lengths and be sure to allow sufficient length  
of pipe for connections. Refer to Figures 9, 10 and 11.  
NOTE: For CDX1 series units, a length of 2" dia. PVC pipe and a 2" dia PVC tee assembly are supplied  
with the unit. For the CDX1-100 and CDX1-125 units, a 2" x 3" dia. PVC reducer is also supplied.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
IMPORTANT: Horizontal installations of CDX1-100 and CDX1-125 units must utilize the 2" x 3" dia. PVC  
reducer as soon as the vent inlet exits the side casing of the unit. The CDX1-100 and CDX1-125 series  
units must be vented with 3" dia. PVC. Refer to Figure 8.  
b. After preparation of the 2” PVC pipe, use silicone type sealant on the 2” dia. PVC elbow (2" dia. PVC  
tee for CDX1 horizontal applications) before inserting it onto the outlet of the inducer. Install a black  
coated #8x3/4” sheet metal screw through the elbow and on the outlet flange of the inducer to secure  
the elbow in place.  
Figure 9  
Figure 10  
Figure 11  
c. PVC cement the pre-cut 2” dia. PVC from step a. to the 2” dia. PVC elbow (2" dia. PVC tee for CDX1  
horizontal applications). Attach to the drain tee assembly using the radiator hose and the 2 clamps  
(supplied).  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
NOTICE: The exhaust vent piping must slope upward at least 1/4” per foot from the furnace to outdoor  
vent terminal. The inlet vent piping must slope downward at least 1/4” per foot from the beginning of the  
last horizontal run of pipe to the outdoor vent terminal. The PVC pipe must be supported directly over the  
vent tee assembly (CDX1) or (CHX1), every four feet thereafter and at every joint. After making sure the  
slope and length of the piping are correct, glue the furnace tee and vent terminal connections in place.  
3. CONNECTING THE COMBUSTION AIR INLET  
a. Install a 2” PVC elbow with sleeve and coupling (CHX1/CDX1-75 series) or 3” PVC elbow with sleeve  
(CHX1/CDX1-100, 125 series) on the inlet of the burner box. Using a tape measure, measure the  
length of 2” or 3” PVC pipe needed to clear the casing. Be sure to allow sufficient length for insertion  
to the elbow at the burner box and the elbow or coupling on the end. Cut the 2” or 3” PVC to the  
measured length.  
b. After preparation of the PVC pipe, secure the coupling or sleeve in place using a black-coated #8x3/4  
sheet metal screw through the PVC into the metal collar of the burner box.  
Note: The PVC connection to the metal burner box collar does not require silicone sealant or PVC  
cement. Attach the PVC elbow to the sleeve and then to the coupling where required, using  
silicone type sealant (see figure 12).  
c. Install the precut 2” or 3” PVC pipe into the elbow at the burner box and to the elbow or coupler just  
outside the furnace using silicone type sealant. To make these seals, run a bead of silicone type  
sealant around the PVC pipe 3/8” from either end, insert into the appropriate couplings and elbows  
and rotate 1/4” turn. This will allow for easy disconnection in case the burner assembly must be  
removed at a later date (see figure 12).  
Note: When applying silicone sealant, ensure that no excess sealant is pushed into the vent  
opening. This may cause flow restriction within the vent.  
DO NOT! SILICONE OR SEAL  
THIS CONNECTION IN  
ANYWAY. MUST BE LOOSE  
FIT WITH LEAKAGE BETWEEN  
PVC AND METAL COLLAR.  
Figure 12  
NOTICE: The air intake pipe must be supported every 4 feet. After making sure the length of the piping is  
correct, glue all connections in place except the length of pipe between the combustion air fitting on the  
burner box and the first fitting.  
If the combustion air piping is installed in a warm humid place, such as a laundry room or above a  
suspended ceiling, it must be insulated with a 1.0” foil faced insulation or its equivalent.  
If the vent piping is run through an unconditioned space, it must be insulated with a1.0” foil faced  
insulation or its equivalent.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
: Outside combustion air must not come from an area that is directly adjacent to a  
pool, hot tub or spa. Measures should be taken to prevent the entry of corrosive chemicals or  
vapors to the combustion and ventilation air supply. Such chemicals include but are not limited to  
chlorinated and/or fluorinated hydrocarbons such as found in refrigerants, aerosol propellants,  
dry cleaning fluids, degreasers and removers. Other harmful compounds may come from  
bleaches, air fresheners or mastics. Vapors from such products can form acid compounds when  
burned in a gas flame. Should acid compounds form in your furnace; it may reduce the life of the  
furnace.  
H. CONNECTING THE FURNACE TO ROOF VENT/AIR TERMINATIONS  
The furnace may be vented vertically through the roof if it is not possible to vent the furnaces through the  
sidewall. The outlet/inlet of the vent and air intake terminations shall be a minimum of 12 inches above  
highest anticipated snow level. The vent outlet must be installed a minimum of 12 in. above the air intake  
inlet. The combustion air intake shall be installed upwind of the vent outlet when exposed to prevailing  
winds. The exhaust vent and combustion air intake can be a minimum of 3 in. and a max. of 24 in. apart  
(see Figure 13). NOTE: When the vent termination is installed correctly, no draft should be present in the  
system during the furnace off cycle.  
Figure 13  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
I. CONDENSATE DRAIN LINE AND TRAP ASSEMBLY  
1. The following diagrams show the typical drain and trap connection for a CHX1 and CDX1 furnace.  
Figure 14. TRAP ASSEMBLY MOUNTED ON CHX1  
Figure 15. TRAP ASSEMBLY MOUNTED ON CDX1  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Figure 16. TRAP ASSEMBLY MOUNTED ON CDX1 RIGHT SIDE HORIZONTAL INSTALLATION  
2. Determine on which side of furnace the condensate disposal line is to be run (NOTICE: On  
CHX1/CDX1’s this must be the same side as the flue outlet or bottom of unit). Attach the condensate  
trap to the furnace casing using the #8x3/4” sheet metal screws provided in the parts package. Pilot  
holes are provided on both sides of the casing for mounting.  
NOTE: When the CDX1 series unit is used in a horizontal application, the drain hose from the  
collector box will require a location change from it's factory shipped connection. A knockout has  
been provided in the unit side casing for the drain hose to exit. The connection change can be  
accomplished as follows: Refer to Figure 16.  
a) Locate and disconnect the drain hose at the collector box from its factory shipped connection  
location.  
b) Locate and uncap the drain at the bottom (as it is oriented) of the collector box.  
c) Connect the drain hose from step a to the uncapped bottom drain from step b.  
d) Cap the previous drain connection from step a with the existing cap removed in step b.  
3. Attach the drain hose (11/16” diameter clear tubing) from the front (CHX1) or bottom (CDX1) of the  
condensing coil cover plate to one side of the PVC tee provided in the trap assembly. Secure the  
drain hose (11/16” o.d. tubing) with the silver clamp provided in the parts package. Be careful to route  
the tubing through the proper hole in the furnace casing using the Heyco bushing provided. While  
making all connections with the clear tubing, be careful to route the tubing in a manner to prevent  
kinking or abrasion of the tubing.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
4. Measure the drain hose (11/16” o.d. clear tubing) provided and remove any extra length, making sure  
that the hose has sufficient length not to kink or otherwise be restricted once installed. Attach the  
drain hose (11/16” o.d. clear tubing) to the other side of the condensate trap tee. On CHX1/CDX1’s,  
this hose is shipped in the parts package and it will be necessary to attach the other end to the PVC  
drain tee assembly (see Figure 15). Use the silver clamp(s) provided in the parts package to secure  
all connections.  
5. Install field supplied 1/2” CPVC drain pipe and elbows using CPVC cement to reach a nearby drain. A  
minimum 1/4” per foot downward slope toward the drain must be maintained. The drain line must be  
water tight, supported and secured so that it can’t be moved. The length of the drain must be kept as  
short as possible.  
IMPORTANT: If an air conditioning condensate drain line is combined with the furnace condensate drain  
line, it must have a separate trap ahead of the joint connection.  
6. If a drain is not readily available or is above the trap outlet level on the furnace or the drain line cannot  
be sloped downward its full length to the drain, then a condensate pump (part #350225) can be  
ordered from the factory. Follow the pump manufacturers installation instructions.  
7. The furnace condensate is slightly acidic with a pH of 3.5. Cola drinks with a pH of 3.1 are actually  
more acidic. If local codes require a neutralizing kit, the kit may be ordered using part no. 320095.  
Instructions included with the neutralizing kit must be followed for its proper installation.  
8. The condensate piping in the furnace and the drain system must be flushed out at the start of every  
heating season. This will assure trouble free operation and will keep the acidity level well above 3.4  
pH.  
To flush the condensate drain system, turn off power to the furnace at the electrical disconnect switch and  
turn the thermostat to the lowest setting.  
Remove the 11/16” diameter clear tubing from the coil drain nipple and run tap water into the open end of  
the tubing. This should keep the drain system clean. Replace the tubing by pushing it firmly onto the  
nipple. Make sure the spring clamp is returned to the original position to prevent leaks. If any of the  
electrical controls are exposed to water, dry with a soft cloth and wait 24 hours before operating the  
furnace. Set the room thermostat to the desired temperature and restore electrical power to the furnace.  
J. GENERAL GAS PIPING  
: Because of the potential of odorant fade, a gas leak may not be detected by smell. If  
this furnace is installed below grade, contact your gas supplier for a gas detector.  
1. Left and right gas supply piping - These furnaces are set-up to be gas piped through either the left or  
right side by using a street elbow and a straight pipe. For the purposes of service, it is recommended  
that the gas union be located inside the furnace, when possible.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Figure 18  
2. A drip leg must be used on both LP and natural gas installations prior to the furnace in order to trap  
oil, condensate and other impurities which might otherwise lodge in the gas valve or plug the burner  
orifice. A drip leg shall be provided at the outlet of the gas meter when there is excessive  
condensation between the gas meter and the furnace. Failure to install a drip leg may void the limited  
warranty on the furnace.  
: All gas piping must be leak tested using a soap and water solution (when the gas is  
turned on) following the procedure outlined in Section III, J, of this manual. A final test for gas  
leakage must be made after purging the gas line (refer to Section IV, B, of this manual). This test  
must be conducted with the unit operating and should include the furnace piping and gas valve.  
Never use an open flame to check for a gas leak.  
: Care must be taken not to wet electronic components during leak test. Wetting the  
primary ignition module may damage its circuitry and cause a hazardous situation. Dry moisture  
from all leads and terminals if wetting occurs. Wait at least 24 hours for the circuit to fully dry  
before energizing the burner circuit.  
K. FILTERS  
1. CHX1 MODELS: HIGHBOYS  
It is necessary to cut the return air opening in the bottom or side casing depending upon the needs of the  
specific installation.  
NOTICE: If your CHX1 will require air delivery above 1800 CFM, it is advisable that both sides, a  
combination of 1 side and the bottom, or the bottom only be used for return air. (If a return is cut in the  
bottom, it should be as large as the return opening in the equivalent CDX1 model. (See specification sheet  
in beginning of this manual).  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
This CHX1 furnace has been factory supplied with a high quality re-usable filter rated for air velocities up  
to 600 ft/min. An optional Thermo Products filter rack assembly (part no. AOPS7547 for CHX1-75 thru 100  
and AOPS7375 for CHX1-125) is available which is sized for the filter provided.  
If an optional Thermo Pride filter rack AOPS7547 (figure 19) is used with the furnace, it will serve as a  
template to scribe a mark for the return air opening on the casing. Place the filter rack on the casing one  
inch up from the bottom of the furnace and centered from side to side. Place the securing flange against  
the casing for locating the return air opening.  
Figure 19  
PLEASE NOTE: While scribing the return air opening, the filter rack can be held into position by tape or  
similar means.  
Position the open end of the filter rack so that it is accessible for filter replacement. Once the filter rack is  
positioned correctly, scribe a line along the inside of the securing flange of the filter rack on three of the  
sides. To scribe a line on the fourth side, on the open end, use the open end support for a guide.  
Remove the filter rack and cut the return air opening in the casing. Now the filter rack can be permanently  
attached to the furnace with screws or pop-rivets along the securing flange.  
Connect the return plenum to the filter rack and slide the filter into place.  
2. CDX1 MODELS: COUNTERFLOWS  
This CDX1 furnace has been factory supplied with two high quality reusable filters rated at 600 ft/min.  
These filters are designed to be mounted on the return air plenum opening on the top of the furnace in the  
double “vee” style rack provided (see Figure 20). If feasible, it is recommended that slits be cut in the  
return front to allow for easier access of the filters.  
Figure 20  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
3. USE OF NON-THERMO PRIDE FILTER RETENTION MEANS  
If a method other than the Thermo Pride filter rack is selected for retention of the filter and/or use of a  
different filter type is desired, see Table 3 for minimum size guidelines for selecting a filter system for the  
CHX1 or CDX1 furnaces.  
MINIMUM FILTER AREA REQUIRED (LENGTH X WIDTH, SQ. IN.)  
TABLE 3  
FILTER TYPE  
MAXIMUM  
RATE  
Required CFM / (Filter Velocity Rating x 144) = min. filter  
(in2)  
AIR VELOCITY  
FURNACE MODEL  
CHX1,CDX1-75  
CHX1,CDX1-100  
CHX1,CDX1-125  
*THERMO  
600 FT./MIN.  
254 IN.2*  
328 IN.2*  
402 IN.2*  
PRODUCTS  
SUPPLIED  
PERMANENT FILTER  
STANDARD  
PERMANENT FILTER  
DISPOSABLE TYPE  
FILTER  
500 FT./MIN.  
300 FT./MIN.  
304 IN.2  
506 IN.2  
394 IN.2  
656 IN.2  
484 IN.2  
804 IN.2  
* The Thermo Products supplied filter can be cut to size to fit other filter retention systems as long as the  
minimum size requirement is met. NOTICE: Any internal stiffeners used in the filter must not be removed,  
although they can be cut to size as needed.  
NOTICE: The filter areas in table 3 are the minimum areas required based on the CFM generated by the  
furnace for standard heating speeds only. The following formula can be used to determine the minimum  
filter area required for cooling if the unit is equipped with cooling. This value should then be compared to  
the value shown in table 3 and the larger of the two should then be used for determining the minimum filter  
area required for that installation.  
FORMULA:  
(tons of cooling) x (400 CFM per ton) (144 square inches per foot)  
(max. air velocity of filter from table 3 for the filter type)  
= filter area sq.inches  
= length x width of  
filter in inches  
EXAMPLE: If you had a CHX1-100 furnace and 4 tons of cooling and a standard permanent filter.  
4 tons x 400 CFM x 144 = 460 square inches for cooling  
500  
For heating a CHX1-100 needs 394 square inches of filter. The filter system must be designed for the  
larger CFM requirement determined for cooling of 460 square inches. A filter would have to be sized so  
that the area (length X width) was at least 460 sq. in.  
L. WIRING  
All wiring shall be performed by a qualified electrician or service person. The wiring must comply with local  
codes, the instructions in this manual, and in the absence of codes with the National Electrical Code  
(ANSI/NFPA-70 or latest edition).  
1. The following items are guidelines to complete the wiring portion of the installations.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
a. A separate power supply circuit with over current protection and a disconnect switch must be  
provided. The minimum fuse or circuit breaker size is 20 amp.  
b. All CHX1 and CDX1 Series furnaces are supplied with a fuse disconnect switch box to be mounted on  
the outside surface of the right or left side casing so a fuse disconnect can be mounted on the  
furnace. Make the 115 volt supply connection in this junction box. A green screw and a strain relief are  
provided in order to connect the power supply ground wire and provide strain relief for the 115 volt  
power leads from the furnace in the fuse disconnect box. A disconnect switch can be field mounted on  
the 2x4 box provided. If not, the disconnect switch must be located reasonably close to and within  
sight of the furnace.  
NOTICE: The hot surface igniter and operation of this furnace depends on correct polarity. The hot leg of  
the supply circuit must be connected to the black line lead and the common leg to the white line lead in  
the field mounted junction box. The hot leg must pass through the disconnect switch in all cases to  
prevent the hazard of electrical shock when servicing.  
IMPORTANT: The furnace must be grounded in accordance with local codes and with the National  
Electrical Code (ANSI/NFPA NO. 70 or latest edition) when an external electrical source is utilized.  
2. ELECTRONIC AIR CLEANER (EAC) AND HUMIDIFIER INSTALLATION  
The ignition module on this furnace has designated terminals to control the operation of an electronic air  
cleaner and/or humidifier. These terminals provide line voltage (110-20VAC) for the control of these  
accessories. (See Figure 21). NOTICE: It is important to confirm that the operating voltage of the  
humidifier or EAC being installed matches the output of this control. If not, a field supplied relay or  
transformer may be necessary to provide the proper control and supply voltage for the accessory being  
installed. See the manufacturers instructions for the humidifier or EAC for additional instructions.  
3. THERMOSTAT CONNECTIONS AND ANTICIPATOR SETTING  
NOTICE: For two-stage thermostat wire connectors see wire diagram page 44. For single-stage  
thermostat with two-stage operation connect W from thermostat to W1 on control. W2 on control board is  
not used. Thermostat shunt on control board (Fig. 21) will need to be moved to single t’stat. In this  
configuration the furnace will light and burn on low fire for 10 minutes (5 minutes optional). If thermostat  
has not been satisfied in 10 minutes the control will step up to high fire until thermostat is satisfied. If the 5  
minutes option is desired turn dip switch S1-3 (Fig. 21) off.  
Proper control of the indoor temperature can only be achieved if the thermostat is calibrated to the heating  
and/or cooling cycle. A vital consideration of this calibration is related to the thermostat heat anticipator.  
The proper thermostat heat anticipator setting is 0.4 AMPS for furnace operation only. To increase length  
of cycle, increase setting of heat scale; to decrease length of cycle, decrease setting of heat scale.  
Anticipators for the cooling operation are generally pre-set by the thermostat manufacturer and require no  
adjustment.  
Anticipators for the heating operation are of two types, pre-set and adjustable. Those that are pre-set will  
not have an adjustment scale and are generally marked accordingly.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
4. BLOWER AND CONTROL PANEL WIRING  
Figure 21  
: TURN OFF THE ELECTRICAL POWER to the furnace before attempting to disconnect  
blower wiring.  
DIP SWITCH (S1):  
HEAT “OFF” DELAY  
SW1  
ON  
OFF  
*ON  
OFF  
SW2  
ON  
ON  
OFF  
OFF  
SECS.  
60 SEC.  
90 SEC.  
120 SEC.  
180 SEC.  
2ND STAGE DELAY FOR SINGLE STAGE  
THERMOSTATS  
SW3  
OFF  
*ON  
MINUTES  
5 MIN.  
10 MIN.  
*Factory Setting  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Modifications to ECM blower speed settings are done using the S3 and S4 dip switch controls. (Labeled 1  
to 8 in Figure 21). Thermo Pride two-stage furnaces are factory shipped at the CFM settings listed below  
in Table 4.  
2-Stage Blower Settings (from factory)  
Table 4  
Control Board  
Dip Switch  
Settings  
Heating  
CFM  
(low fire)  
Heating  
CFM  
(high fire)  
Constant Fan  
CFM  
Cooling  
CFM  
Unit  
1-7 Off  
8 On  
CDX1-75  
CHX1-75  
CDX1-100  
CHX1-100  
CDX1-125  
CHX1-125  
885  
760  
1012  
931  
500  
500  
600  
600  
700  
700  
1000  
1000  
1200  
1200  
1400  
1400  
1-8 Off  
1-7 Off  
8 On  
1094  
1015  
1366  
1270  
1340  
1243  
1673  
1556  
1-8 Off  
1-7 Off  
8 On  
1-8 Off  
For adjustments to the Cooling CFM settings, as well as all additional CFM changes, please reference the  
dip switch tables listed in the ECM operation manual. (Included with every furnace.)  
5. FIELD WIRING AND REPLACING WIRING  
Field wiring between the furnace and devices not attached to the furnace shall conform with the  
temperature limitation for Type T wire[63°F rise (35°C)] when installed in accordance with the  
manufacturer’s instructions. If any of the original factory supplied furnace wiring is replaced or a separate  
device other than the thermostat is wired internal to the unit 105°C thermoplastic or equivalent wire must  
be used.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
IV. STARTING THE UNIT  
A. SEQUENCE OF OPERATIONS  
AT ANY TIME THE  
GAS VALVE IS  
NOT ENERGIZED  
CONTINUOUS SAFE OPERATION CHECK  
IF FLAME SIMULATION CONDITION PRESENT OR ROLL-OUT SWITCH  
OPENS, SYSTEM ENERGIZES INDUCER FAN FOR 15 SECONDS AND  
CIRCULATOR BLOWER AT HEATING SPEED UNTIL SITUATION CORRECTION  
THERMOSTAT CALLS FOR  
HEAT W1 OR W1 & W2,  
CONTACTS CLOSE  
50V61-143 CONTROL  
ENERGIZED, INDUCER  
ENERGIZED ON HIGH SPEED  
LOW FIRE PRESSURE  
SWITCHES SENSES ADEQUATE  
DIFFERENTIAL PRESSURE,  
CONTACTS CLOSE  
PREPURGE IGNITION DELAY,  
INDUCER RUNS FOR 30 SECONDS  
INDUCER REDUCES  
TO LOW SPEED  
LOW PRESSURE SWITCH  
SENSES ADEQUATE  
PRESSURE DIFFERENTIAL,  
CONTACTS STAY CLOSED  
POWER IS APPLIED TO  
THE WHITE RODGERS 768A  
SILICON NITRIDE IGNITOR.  
IGNITOR WARM-UP IS  
20 SECONDS  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
AFTER IGNITOR WARM-UP,  
THE 36E54 GAS VALVE IS  
ENERGIZED TO OPEN ON  
LOW FIRE SETTING  
FLAME MUST BE DETECTED  
WITHIN 4 SECONDS IF  
FLAME IS DETECTED, THE  
DELAY-TO-FAN-ON TIME  
BEGINS (45 SECONDS)  
IF FLAME IS NOT DETECTED, THE  
GAS VALVE IS DE-ENERGIZED,  
THE IGNITOR IS TURNED OFF AND  
THE 50V61-143 CONTROL GOES  
INTO "RETRY" SEQUENCE  
IF NOT  
THE RETRY SEQUENCE  
PROVIDES A 60 SECOND  
WAIT BEFORE IGNITION  
RETRY. RETRY IS  
ATTEMPTED WITH A  
DIFFERENT VOLTAGE  
SETTING.  
IF IGNITION ATTEMPT IS  
UNSUCCESSFUL, ONE MORE  
RETRY WILL BE MADE  
IF SO  
BEFORE THE 50V61-143  
GOES INTO SYSTEM LOCKOUT  
IF FLAME IS DETECTED, THEN LOST,  
THE 50V61-143 WILL REPEAT THE  
INITIAL IGNITION SEQUENCE FOR A  
TOTAL OF TEN RECYCLES. AFTER  
TEN UNSUCCESSFUL RECYCLE  
ATTEMPTS, THE CONTROL WILL  
GO INTO SYSTEM LOCKOUT.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
IF SYSTEM IS IN LOCKOUT,  
THE MODULE WILL RESET  
ITSELF AFTER 60 MINUTES  
OR MAY BE MANUALLY  
IF THERMOSTAT  
W2 CONTACTS  
RESET BY INTERRUPTING  
ARE CLOSED  
THE POWER TO THE FURNACE  
AT THE DISCONNECT OR  
INTERRUPTING THE CALL FOR  
HEAT AT THE THERMOSTAT.  
IF THIS DOES NOT RESTART  
OTHERWISE  
THE SYSTEM, REFER TO THE  
TROUBLESHOOTING SECTION  
OF THIS MANUAL.  
AFTER DELAY-TO-FAN-ON PERIOD  
ENDS (45 SECONDS), CIRCULATING  
AIR FAN IS ENERGIZED AT LOW  
FIRE HEATING SPEED OR HIGH  
FIRE IF W2 IS ENERGIZED. THE  
(OPTIONAL) ELECTRONIC AIR  
CLEANER AND HUMIDIFIER  
THERMOSTAT CLOSES W2  
CALLING FOR HIGH FIRE  
HEATING.  
CALL  
FOR  
HIGH  
FIRE  
ARE ENERGIZED.  
GAS VALVE, INDUCER AND  
AIR FAN ARE ENERGIZED  
TO HIGH FIRE SETTINGS  
NO CALL  
FOR  
HIGH FIRE  
WHEN THERMOSTAT HAS  
SATISFIED W2, CONTACTS  
OPEN AND THE GAS VALVE  
AND AIR FAN HIGH FIRE  
SETTINGS ARE DE-ENERGIZED  
AFTER 30 SECOND DELAY.  
WHEN THERMOSTAT W1 IS SATISFIED,  
CONTACTS OPEN AND THE GAS  
VALVE IS DE-ENERGIZED. AFTER  
PROOF OF FLAME LOSS, INDUCER  
STARTS 5 SECOND POST PURGE  
AND (OPTIONAL) HUMIDIFIER IS  
DE-ENERGIZED. THE DELAY-TO-  
FAN-OFF PERIOD BEGINS (120 SECONDS)  
AFTER THE DELAY-TO-FAN-OFF  
PERIOD ENDS, THE CIRCULATING  
AIR FAN AND (OPTIONAL) ELECTRONIC  
AIR CLEANER ARE DE-ENERGIZED.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
B. INITIAL START UP:  
This furnace does not have a pilot. It is equipped with a hot surface igniter, which automatically lights the  
burner. Do not attempt to light the burner by hand. Check the following items before the initial start-up.  
1. Check all wiring for loose connections and proper hook up.  
2. Leak test gas piping connections.  
3. Check all tubing to the pressure switch and drains to make sure they are connected firmly at all their  
connection points.  
4. Check flue pipe, combustion air inlet and all PVC connections for tightness and to make sure there is  
no blockage.  
5. Make sure air filter is in place.  
6. Make sure the outside vent and air intakes are installed according to instructions and that they are  
free from blockage.  
7. Make sure that the drain trap is properly connected to the furnace and to the buildings drain system.  
OPERATING INSTRUCTIONS:  
: Turn off power to furnace before it is placed into service. The gas piping system  
must have been leak tested by a qualified heating contractor. (See Section III, J, of these  
instructions on the installation of gas piping).  
: It may be necessary to purge the air out of the gas line for initial start-up of the  
furnace after installation. This should be done by a qualified heating contractor. If excessive gas  
escapes when purging the gas supply at the union, allow the area to ventilate for at least 15  
minutes before attempting to start the furnace. LP gas is especially dangerous because the  
specific gravity of LP gas allows it to accumulate at floor level at a dangerous concentration. For  
remainder of operating instructions, reference Users Information Manual.  
: Heat exchanger oil will burn off on initial firing creating an unpleasant odor. To  
prevent this odor from occurring more than once, it is suggested that:  
1. A window(s) be opened.  
2. The thermostat be set at highest setting.  
3. The furnace remain running at conditions 1&2 for 30 minutes or until odor has dissipated.  
Check for the model number of this furnace, its input, the type of gas and the manifold pressure on the  
information plate located on the vestibule panel behind the upper front panel. If using the above example,  
the furnace was a CHX1-100 model and the 98,663 BTU input would be acceptable because it was within  
2% of the listed high fire input of 100,000.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Measuring And Adjusting Heat Input Rate  
DO NOT exceed input rating stamped on furnace nameplate or manufacturer's  
recommended burner manifold pressure for orifice size used.  
Observe the following precautions when measuring:  
A. Burner manifold pressure with a pressure gauge.  
1. Close the gas valve (turn the gas control knob to the OFF position) BEFORE removing the:  
a. burner manifold pressure tap plug to connect the manometer (or calibrated pressure  
gauge)  
b. manometer, or gauge, and replacing the pressure tap plug.  
2. Shut off the gas supply at the appliance service (manual gas shutoff) valve (or for LP  
gases, shut off the gas at the storage tank service valve) BEFORE removing the:  
a. gas valve inlet pressure tap plug  
b. manometer, or gauge and replacing the inlet pressure tap plug.  
3. Perform a gas leakage test at the gas valve inlet and burner manifold pressure tap plugs.  
B. Gas flowrate by clocking gas meter.  
1. To determine the amount of flow, through the gas meter, due to the operation of the  
furnace.  
a. Turn off all other appliances and extinguish their pilot flames, if equipped, or  
b. Deduct the gas consumption of all other operating appliances from the total meter  
reading.  
2. Convert the gas flowrate to the heat input rate (in BTUH) as described in step 10 (in the  
following section) and compare the value to the heat input rating on the furnace nameplate.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
NOTICE: A U-tube manometer, measuring pressure in inches of water column, is recommended for  
all gas pressure measurements. However, an aneroid pressure gauge, in good working condition,  
capable of reading pressure changes of 0.05 in. W.G., or less, that was recently calibrated (within  
the last year), is a satisfactory alternate. These two (2) devices will be considered as equivalent and  
interchangeable. Either device is referred to below as a “pressure gauge”  
NOTICE: This 2-stage gas valve has two separate gas pressure regulators. Checks and  
adjustments must be made at both high fire (high adjustment) and low fire (low adjustment).  
1. Shut off the gas at the automatic gas control valve (turn gas control knob to the OFF position).  
2. Remove the outlet pressure tap plug from gas burner manifold and connect a pressure gauge.  
Refer to Figure 22, below.  
Figure 22: Exploded View of CDX/CHX Gas Control System  
3. Turn on the gas at the automatic gas control valve (turn gas control knob to the ON position).  
4. Adjust the room thermostat so the furnace will operate on low fire only.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
5. To obtain an accurate manifold gas pressure reading, the main burner must be cycled on and off  
several times to stabilize the gas control valve pressure regulator diaphragm.  
6. Allow the burner to operate for at least 3 minutes before taking gas pressure readings.  
7. Using a pressure gauge, measure the burner manifold gas pressure.  
8. If checking the input rate by measuring burner manifold pressure, skip to step 12. If  
measuring the input rate using a gas meter, proceed to step 9.  
9. Using a clock (or watch) capable of measuring time in seconds, carefully clock the gas meter to  
determine the time for one (1) complete revolution of the gas meter dial or reel. At least one (1)  
cubic foot of gas flow should be measured. Use Table 6 to determine the main burner gas flow  
rate in cubic feet per hour (CFH).  
NOTICE: Some gas meters will require more than one (1) cubic foot of gas pass through the  
meter for reasons of accuracy. When more than one (1) cubic foot of gas is consumed, divide the  
total time by the number of cubic feet for comparison to the figures in Table 6.  
10. Compare actual heat input rate with our recommended input (printed on the furnace rating label).  
To convert the rating label input rate (given in BTUH) to the equivalent gas flowrate (in CFH), use  
the following formula:  
Heat input rate (in BTUH) =  
æ
ö
BTU  
ft3  
ç
÷
÷
Fuel gas higher heating value in  
× Fuel gas flowrate  
(
in CFH  
)
ç
è
ø
or,  
Heat input rate (in BTUH)  
Fuel gas flowrate  
(in CFH  
)
=
æ
ö
BTU  
ft3  
ç
÷
÷
Fuel gas higher heating value in  
ç
è
ø
11. If the measured input rate is above, or below, the rating label value by more than 2%, adjust the  
manifold gas pressure using the gas control valve pressure regulator to obtain the input rating  
within a ± 2% range. Refer to steps 12(a) through 12(d).  
12. If the gas pressure is not within the specified low fire manifold pressure range (refer to  
Table 5), use the following procedure to adjust the low fire, gas pressure regulator to match the  
specified low fire manifold pressure.  
a. Remove the gas pressure regulator adjustment cap screw from the automatic gas control  
valve. The cap screw is located on the outlet side of the valve. Refer to Figure 23.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Figure 23: Outlet view of two-stage, automatic gas control valve  
b. Using a 3/32-in. hex key (or Allen wrench), turn the inner adjustment screw clockwise to  
increase, or counterclockwise to decrease, the gas pressure (and gas flow) to the main  
burner.  
c. Replace the cap screw and tighten it firmly to prevent gas leakage.  
d. Referring to Table 5, measure the gas pressure and to confirm it has been adjusted to within  
the allowable range. Repeat adjustments (a) through (c), as required.  
Table 5 Design Gas Pressures for each Furnace Model Series,  
Operating Mode, and Type of Fuel.  
Fuel Gas Type  
Propane  
Natural  
Operating Mode and  
Model Series  
CHX Low CDX Low  
CHX Low CDX Low  
High Fire  
High Fire  
Fire  
Fire  
Fire  
Fire  
Normal Manifold  
Pressure (in. W.G.)  
10.0 ± 0.3 4.8 ± 0.3 5.6 ± 0.3 3.5 ± 0.3 1.8 ± 0.3 2.0 ± 0.3  
Maximum Gas Supply  
Pressure (in. W.G.)  
14.0  
11.0  
14.0  
4.5  
Minimum Gas Supply  
Pressure (in. W.G.)  
13. Adjust the room thermostat so the burner will operate on high fire only.  
NOTICE: There is a 30 second delay before the gas control will step up to high fire.  
14. To obtain an accurate manifold gas pressure reading, the main burner must be cycled on and off  
several times to stabilize the gas control valve pressure regulator diaphragm.  
15. Allow the burner to operate for at least 3 minutes before taking gas pressure readings.  
16. Using a pressure gauge, measure the burner manifold gas pressure.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                               
                               
                                  
                                  
All installations and services must be performed by qualified service personnel.  
17. If checking the input rate by measuring burner manifold pressure, proceed to step 18. If  
measuring the input rate by clocking the gas meter, repeat steps 9 through 11, above.  
18. If the gas pressure is not within the specified high fire manifold pressure range (refer to  
Table 5), repeat steps 12(a) through 12(d), above, adjusting the high fire gas pressure regulator.  
If the manifold pressure remains low and it cannot be adjusted into the proper range, the supply  
pressure may be too low. Follow these steps.  
a. Turn off the gas at the manual gas shutoff valve.  
b. Remove the automatic gas control valve inlet pressure tap and attach another pressure gauge  
to the inlet tap.  
c. Turn on the gas and repeat steps 14 and 15, above.  
d. Adjust the upstream (inlet) gas pressure to 14.0 in. W.G., or as close as possible.  
e. Using a pressure gauge, measure and adjust the burner manifold gas pressure.  
If it is still not possible increase the manifold gas pressure to within the required range, there  
is too little gas supply to operate the furnace at full (high fire) input rate under present  
conditions. If necessary, consult your gas supplier or qualified heating contractor for  
recommendations to alleviate the problem.  
19. Turn off the gas at the manual gas shutoff valve (turn handle to the OFF position).  
20. Remove all pressure gauges and replace all pressure tap plugs.  
21. Go to Checkout Procedure below.  
Adjusting Burner Input For Altitudes Above 2000 Feet  
Ratings of gas utilization equipment are based on sea level operation and shall not be changed for  
operation at elevations up to 2,000 feet (600 m.). For operation at elevations above 2,000 feet (600  
m), equipment ratings shall be reduced at the rate of 4 percent for each 1,000 feet (300 m) above sea  
level.  
For additional information, refer to the latest edition of the National Fuel Gas Code.  
Checking The Burner Flame  
?ꢀCAUTION: The furnace model series CDX1 and CHX1 are sealed combustion designs that do not  
require an air shutter adjustment (air shutters are not used) for proper flame characteristics. The  
burner box access cover must always be secured with all screws in place and tightened before  
operating furnace.  
Once the input rate has been confirmed correct for a specific application, the burner flames should be  
checked for proper adjustment.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
This furnace is designed not to require any burner adjustment. Burner aeration is fixed in this design.  
Burner flames can be seen by looking through the sight glass located on the burner box. Burner  
flames should be well-defined, light to medium blue in color, and almost transparent. (refer to Figure  
24).  
Figure 24: Sketch of Typical Main Burner Flames During Operation  
NOTICE: When operating on propane gas, it is not unusual for flames to have yellow or orange  
colored tips.  
If combustion problems are evident, it may indicate problems with either the furnace air supply or the  
vent system. Refer to the installation and maintenance sections of this manual, or contact Thermo  
Products at (574) 896-2133.  
Checkout Procedure  
1. Confirm the furnace exhaust vent and combustion air intake are constructed as outlined in the  
installation and service manual. They must not be blocked or otherwise obstructed.  
2. Place system in operation and observe at least one (1) complete cycle to ensure all controls are  
operating properly. The main burner must light reliably under all conditions.  
3. Perform gas leakage test on all gas pipe connections and pressure tap plugs.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
TIME (sec.)  
FLOW (cfh)  
TABLE 6 - CONVERTING GAS FLOW RATE  
40  
41  
42  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
62  
64  
66  
68  
70  
72  
74  
76  
78  
80  
84  
88  
92  
90  
88  
86  
82  
80  
78  
77  
75  
73  
72  
71  
69  
68  
67  
65  
64  
63  
62  
61  
60  
58  
56  
54  
53  
51  
50  
49  
47  
46  
45  
43  
41  
39  
38  
36  
34  
33  
31  
30  
29  
28  
27  
26  
24  
23  
21  
20  
* For one cubic foot per revolution gas meter dials,  
use Table directly.  
* For 1/2 cubic foot per revolution gas meter dials:  
1. Determine time for two dial revolutions  
2. Use Table directly  
* For two cubic foot per revolution gas meter dials:  
1. Determine time for one complete dial revolutions  
2. Divide time by two  
3. Use Table directly  
96  
100  
105  
110  
115  
120  
125  
130  
135  
140  
150  
160  
170  
180  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
C. FURNACE CHECKOUT PROCEDURE  
Before any system of gas piping is finally put into service, it shall be carefully tested to assure that it is gas  
tight as indicated in the manual.  
NOTICE: All controls on the unit should be checked for proper functioning prior to the qualified service  
personnel leaving the job site. Specifically the following should be checked:  
With furnace in normal heating operation, check to make certain blower will start and stop automatically  
under control of integrated fan control.  
1. Check safety limit control as follows:  
a. Shut off incoming power.  
b. Disconnect blower motor leads.  
c. Restore power to furnace.  
d. Set thermostat above room temperature calling for heat.  
e. When temperatures are reached in furnace at limit control setting with blower out of operation,  
burner should shut off.  
f. Shut off electrical power.  
IMPORTANT: Remove blockage or reconnect blower motor and restore power.  
2. Make certain thermostat will automatically start and stop furnace.  
3. Block the flue pipe gradually with a flat piece of metal, until the pressure switch functions shutting off  
the main burners. Note: If the burner was initially operating in high fire, the burner will first reduce rate  
to the low fire setting. As the flue becomes more blocked, the pressure switch will function and  
completely shut off the main burners.  
4. Block the PVC pipe inlet gradually with a flat piece of metal until pressure switch functions shutting off  
the main burners. Note: If the burner was initially operating in high fire, the burner will first reduce  
rate to the low fire setting. As the flue becomes more blocked, the pressure switch will function and  
completely shut off the main burners.  
IMPORTANT: Remove flue air inlet blockage when done.  
5. Remove the blower compartment access door with the furnace operating. The door interrupt switch is  
in the 120 volt circuit and will shut down the entire system. Replace the blower door and the furnace  
start-up cycle will begin.  
V. INSTALLER'S INSTRUCTIONS TO USER:  
After completing the installation, the installer shall inform and/or demonstrate to the homeowner:  
1. The location of all the instructions in the furnace and that these instructions and the users information  
manual must be kept along with instructions for any accessories in the plastic pouch on the inside of  
the furnace.  
2. The location and use of the manual gas shut off valve and furnace electrical disconnect switch.  
Instruct user to always shut off gas before shutting off electric power.  
3. The sequence of operation of the furnace.  
4. The correct operation and maintenance of the appliance as outlined in the users information manual.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
5. That failure to maintain and operate this furnace in accordance with these instructions could result in  
hazardous conditions, bodily injury, property damage and may void the limited warranty on the  
furnace.  
6. Review with and encourage the user to read the label reproductions and all warnings and instructions  
outlined on the front cover and in sections I, II and III of this manual and in the Users Information  
Manual.  
7. Recommend that the user have a qualified heating contractor inspect the furnace at the start of each  
heating season. Inform the user of the frequency of inspection required for reach item in Section III of  
the Users Manual.  
Figure 25  
VI. TROUBLESHOOTING  
NOTICE: BEFORE TROUBLESHOOTING, FAMILIARIZE YOURSELF WITH THE START UP AND  
CHECKOUT PROCEDURE.  
ALL INSTALLATION AND SERVICES MUST BE PERFORMED BY QUALIFIED HEATING  
CONTRACTORS.  
To assist you in troubleshooting this furnace, it is equipped with an integrated ignition control with  
diagnostics. These diagnostics evaluate what control system has experienced a failure and will activate a  
flashing light on the control in different sequences to help pinpoint the failure which has occurred.  
IMPORTANT: For your convenience, Thermo Products has installed a sight glass in the blower door of  
this furnace. The number of flashes in groups should be observed through this sight glass and recorded  
before turning off power to the furnace. Otherwise power to the furnace will be when turning off power or  
removing the blower door which is equipped with door interlock switch, which will reset the control. Should  
this occur, it will be necessary to restart the furnace and have the failure occur again.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
DIAGNOSTIC FEATURES  
The 50V61 control used on this furnace continuously monitors its operation and the operation of the  
system.  
If the sensed failure is in the system (external to the control), the red LED will flash in the following flash-  
pause sequences to indicate failure status (each flash will last approximately 0.25 seconds, and each  
pause will last approximately 2 seconds):  
1 flash, then pause  
2 flashes, then pause  
3 flashes, then pause  
4 flashes, then pause  
5 flashes, then pause  
6 flashes, then pause  
7 flashes, then pause  
8 flashes, then pause  
9 flashes, then pause  
Continuous flash  
system lockout (retries or recycles exceeded)  
low pressure switch stuck closed  
low pressure switch stuck open  
open high temperature limit switch  
not used  
115 V AC power reversed  
low flame sense signal  
check igniter or improper ground  
high pressure switch stuck open  
flame sensed with gas valve de-energized  
The LED will also flash once at power-up.  
A green LED indicator is also present to obtain an estimate of the air flowrate (in CFM) produced by the  
house air blower. This LED cycles regularly by providing a constant light, followed by a sequence of  
flashes. Each flash can be translated to programmed CFM by using the following:  
1 flash per 100(programmed) CFM  
: Power must be disconnected before servicing.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
TROUBLESHOOTING GUIDE  
THE SYSTEM IS STARTED BY SETTING THE THERMOSTAT TO CALL FOR  
HEAT. THE FOLLOWING SHOULD HELP ESTABLISH THE TYPE OF  
MALFUNCTION OR DEVIATION FROM THE NORMAL OPERATION.  
NOTE: IF LED LIGHT IS FLASHING, REFER TO PAGE 34 FOR A QUICK TROUBLESHOOTING GUIDE.  
TO USE THIS DIAGRAM, YOU JUST NEED TO FOLLOW THE INSTRUCTIONS IN THE BOXES.  
SET THERMOSTAT TO CALL FOR HEAT  
(MAKE CERTAIN ROOM TEMPERATURE IS BELOW THERMOSTAT SETTING)  
IS THERE 120 VOLTS  
CHECK INPUT POWER,  
ACROSS "L1" AND  
"NEUTRAL" AT THE  
50V61-143 CONTROL  
MODULE?  
IS THE INDUCER  
BLOWER OPERATING?  
NO  
NO  
DOOR INTERLOCK,  
SERVICE SWITCH  
AND FUSES  
YES  
IS THERE 24 VOLTS  
ACROSS "TH" & "TR"  
AT THE INTEGRATED  
CONTROL MODEL  
50V61-143?  
CHECK 115 VOLT  
CONNECTIONS. IF OK,  
REPLACE TRANSFORMER  
NO  
YES  
YES  
IS THERE 24V  
ACROSS R AND B/C  
NO  
CHECK FUSE ON  
W/R 50V61-143  
YES  
CHECK WIRING TO  
THERMOSTAT. IF OK,  
REPLACE THERMOSTAT.  
IS THERE 24 VOLTS  
ACROSS "R" AND "W1"?  
YES  
NO  
IS THERE LINE VOLTAGE  
ACROSS INDUCER POWER  
TERMINALS "IND HI" TO  
"IND N" OR "IND LO" TO  
"IND N" AT THE 50V61-143  
CONTROL?  
NO  
REPLACE THE  
50V61-143 CONTROL.  
YES  
CHECK WIRING TO INDUCER  
AND IF OK, REPLACE  
INDUCER ASSEMBLY.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
CHECK CONTACTS ON LOW  
FIRE PRESSURE SWITCH  
AND FOR BLOCKAGE IN FLUE.  
IF OK, REPLACE DUAL  
PRESSURE SWITCH.  
IS INDUCER RUNNING  
ON LOW SPEED?  
NO  
NO  
REPLACE THE  
50V61-143 CONTROL.  
YES  
YES  
IS THERE VOLTAGE ACROSS  
HOT SURFACE IGNITOR  
TERMINALS "IGN" & "IGN N"  
AT THE 50V61-143 CONTROL  
AFTER 25 SECOND PREPURGE?  
IS THE HIGH LIMIT,  
ROLL-OUT LIMIT, AND  
AUX LIMIT ON  
DOES THE HOT  
SURFACE IGNITOR  
ENERGIZE AND GLOW?  
NO  
(CDX MODELS)  
SWITCHES CLOSED?  
YES  
NO  
CHECK WIRING TO HOT  
SURFACE IGNITOR AND  
IF OK, REPLACE HOT  
SURFACE IGNITOR  
ASSEMBLY  
IF HIGH LIMIT OR  
AUX LIMIT OPEN CHECK  
FOR RESTRICTED  
FILTERS OR DUCT WORK  
IF ROLL-OUT SWITCH  
OPEN INSPECT FLUE FOR  
RESTRICTIONS.  
YES  
CHECK ACROSS "MVL" AND  
"MV COM" TERMINALS ON  
50V61-143 CONTROL FOR 24  
VOLTS DURING THE 4 SECOND  
FLAME PROVING PERIOD  
AFTER IGNITOR WARM-UP.  
IS THERE 24 VOLTS?  
AFTER HOT SURFACE  
IGNITOR WARM-UP,  
DOES GAS VALVE OPEN?  
NO  
NO  
REPLACE THE  
50V61-143 CONTROL.  
YES  
CHECK DRAIN FOR  
BLOCKAGE WATER  
TRAPPED IN HOSE,  
REPLACE SWITCH.  
IS COLLECTOR BOX  
PRESSURE SWITCH CLOSED?  
NO  
YES  
YES  
CHECK WIRING TO GAS  
VALVE AND IF OK,  
REPLACE GAS VALVE.  
CHECK FOR PROPER LINE  
AND MANIFOLD PRESSURE.  
REFERENCE GAS PRESSURE  
CHART PAGE 31.  
AFTER GAS VALVE  
OPENS, DO THE  
BURNERS IGNITE?  
NO  
YES  
OK  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
IS IGNITOR  
NO  
REPOSITION TO  
POSITIONED CORRECTLY?  
CORRECT LOCATION  
YES  
CHECK AND CLEAN BURNERS  
CHECK FOR PROPER LINE  
AND MANIFOLD PRESSURE  
REFERENCE GAS  
DO BURNERS STAY  
LIT PAST PROOF OF  
FLAME CHECK?  
NO  
PRESSURE CHART PAGE 31.  
OK  
CHECK FLAME PROB2  
AND WIRE AND CHECK  
POLARITY ON INCOMING  
POWER AND GROUND  
YES  
IS THERE LINE  
VOLTAGE ACROSS  
INDUCER POWER  
TERMINALS "IND HI"  
TO "IND N"?  
DOES INDUCER  
GO TO  
HIGH SPEED?  
REPLACE  
NO  
YES  
NO  
IS W2 ENERGIZED?  
THE 50V61-143  
CONTROL.  
YES  
CHECK CONNECTIONS  
TO INDUCER. IF OK,  
REPLACE INDUCER.  
YES  
NO  
CHECK  
CONTACTS  
IN HIGH  
FIRE SWITCH  
IS THE HIGH FIRE  
PRESSURE SWITCH  
CLOSED?  
DOES BURNER  
NO  
NO  
AND FOR  
BLOCKAGE IN  
FLUE. IF OK,  
REPLACE DUAL  
PRESSURE  
SWITCH.  
STEP TO HIGH FIRE?  
YES  
YES  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
IS THERE 24 VOLTS  
ACROSS "MVH" AND  
"MV COM" ON  
NO  
REPLACE THE  
50V61-143 CONTROL.  
50V61-143 CONTROL?  
YES  
CHECK CONNECTIONS  
TO GAS VALVE. IF OK,  
REPLACE GAS VALVE.  
CONFIRM IF EITHER  
BLOWER WHEEL  
IS RUBBING AGAINST  
HOUSING OR MOTOR  
SHAFT IS SPINNING  
FREELY AND REPAIR  
OR REPLACE AS  
IS THE VARIABLE  
SPEED AIR FAN  
OPERATING?  
NO  
DOES BLOWER  
SPIN FREELY?  
NO  
YES  
NECESSARY  
REFERENCE ECM  
OPERATION MANUAL  
YES  
DOES SYSTEM RUN  
UNTIL THERMOSTAT  
IS SATISFIED?  
IS LED LIGHT  
ON 50V61-143  
CONTROL FLASHING?  
NO  
NO  
CHECK ALL WIRING FOR  
LOOSE CONNECTIONS.  
YES  
REFERENCE LED  
CHART ON PG. 34  
OF THIS MANUAL.  
YES  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
DOES BURNER SHUT OFF  
WHEN THERMOSTAT IS  
SATISFIED?  
NO  
CHECK FOR 24 VOLTS  
AT GAS VALVE.  
NO  
REPLACE GAS VALVE  
YES  
YES  
CHECK FOR SHORT IN WIRE TO  
THERMOSTAT AND CORRECT  
IF NECESSARY.  
DOES THE CIRCULATING  
AIR BLOWER TURN OFF  
AFTER THERMOSTAT IS  
SATISFIED WITHIN  
NO  
REFERENCE ECM  
OPERATION MANUAL  
120 SECONDS?  
YES  
TROUBLE SHOOTING COMPLETE  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Appendix –A Replacement Parts List  
1. Replacement parts list for CHX1-75, CHX1-100 and CHX1-125.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
2. Replacement parts list for CDX1-75, CDX1-100 and CDX1-125.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
Appendix – B Wiring Diagrams  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All installations and services must be performed by qualified service personnel.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Thermador Ventilation Hood VCH 3 User Manual
Triax Satellite TV System SR 322 User Manual
Tricity Bendix Ventilation Hood CH 550 User Manual
Tripp Lite Switch PAM 1 User Manual
Uniden Cordless Telephone DXAI7288 2 User Manual
Universal Electronics Universal Remote CABLE 4 User Manual
Universal Electronics Universal Remote OCAP 5 User Manual
ViewSonic Network Card VS13789 User Manual
VTech Baby Toy 91 002554 006 000 User Manual
Weber Gas Grill 41894 User Manual