Studer Innotec Battery Charger C 4000 48 User Manual

STUDER INNOTEC  
COMPACT  
User and installer Manual  
Sine wave Inverter, Battery charger, Transfersystem  
COMPACT C 1600-12  
COMPACT C 2600-24  
COMPACT C 4000-48  
Temperature sensor CT-35  
Remote control RCC-01  
Solar charge controller Cxxxx-S  
Remote power sharing RPS-01  
AC cable cover CFC-01  
IP-23 top cover C-IP23  
User manual  
COMPACT V4.0 E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
4.7.3 DELAYED MODE OF THE TRANSFER SYSTEM.....................................................................................17  
4.8 THE SOLAR CHARGE CONTROLLER (OPTION) ............................................................................................17  
4.9 THE MULTIFUNCTIONAL CONTACT............................................................................................................18  
4.10 THE REMOTE CONTROL..........................................................................................................................18  
4.11 THE TEMPERATURE SENSOR ...................................................................................................................19  
5
PROGRAMMING..........................................................................................................................19  
5.1 STANDARD SETTING ................................................................................................................................19  
5.1.1 WORKING MODE..............................................................................................................................19  
5.1.2 BATTERY VOLTAGE..........................................................................................................................19  
5.1.3 AUXILIARY CONTACT .......................................................................................................................19  
5.2 RESET VALUE…......................................................................................................................................19  
5.3 BATTERY VOLTAGES AND ABSORPTION TIME .............................................................................................19  
5.3.1 TABLE OF VOLTAGE AND TIMING THRESHOLD ....................................................................................19  
5.3.2 SET THE VOLTAGE AND TIMING THRESHOLD ......................................................................................20  
5.4 PROGRAMMING THE AUXILIARY CONTACT..................................................................................................20  
5.4.1 PRINCIPLE ......................................................................................................................................20  
5.4.2 THE PROGRAMMING OF THE AUXILIARY CONTACT IS CARRIED OUT IN THE FOLLOWING STEPS .............20  
5.4.3 EXAMPLES......................................................................................................................................21  
5.4.4 MANUAL OPERATING OF AUXILIARY CONTACT...................................................................................21  
5.5 DISABLING SOME OF THE COMPACT FUNCTIONS ........................................................................................21  
5.5.1 DIAGRAM OF THE DIFFERENT MODES ...............................................................................................22  
6
7
8
MAINTENANCE ...........................................................................................................................22  
EC COMPLIANCE .......................................................................................................................22  
TECHNICAL DATA.......................................................................................................................23  
User manual  
COMPACT V4.0 E  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
1 General Information  
1.1 Operating instructions  
This manual is a part of the delivery package of every COMPACT inverter-charger. It serves as  
guidelines for safe and efficient operation of COMPACT. The instructions are only valid for use with  
the following devices and options:  
COMPACT C 1600-12  
COMPACT C 2600-24  
COMPACT C 4000-48  
Temperature sensor CT-35  
Remote Control RCC-01  
AC cable cover CFC-01  
IP23 cover C-IP23  
Power sharing remote control RPS-01  
Solar charge controller CxxxxS  
Every person who installs a COMPACT and/or works with it must be fully familiar with the contents  
of this manual and must follow exactly all the warnings and safety instructions. Installation of or any  
work on the COMPACT must be carried out by a qualified and trained staff. Installation and  
application must comply with the respective local installations codes and safety regulations.  
1.2 Quality and Warranty  
During production and assembling, all COMPACT appliances go through many controls and tests.  
Fabrication, controls and tests are carried out in accordance with firm and established procedures.  
Every COMPACT has its own serial number, which helps to refer back to its original data in the  
event of controls or repairs. That is why you should never remove the identification plate showing  
the serial number. The production assembly and tests on all COMPACT appliances are totally  
carried out in our company in Sion, Switzerland. The warranty for these appliances is valid for uses  
and operating possibilities mentioned in this manual.  
The warranty period for the COMPACT is 2 Years.  
1.3 Warranty Disclaimer  
We do not accept any responsibility for any damages occurring through use, manipulation, working  
situation and handling, which are not explicitly mentioned in these operating instructions.  
Following cases are not covered by the warranty:  
-
High voltage at INPUT (i.e. 48V at the Battery INPUT of COMPACT 1600-12)  
Reverse polarity on Battery connections (+/- reversed)  
Running liquid or oxidation through condensation in the appliance  
Defects caused by force, physical or mechanical means  
Changes not explicitly authorized by Studer INNOTEC  
Not or only partly tightened screws and nuts after change of fuses or connecting cables  
Connecting other sources of energy such as PV-Modules on the INPUT „SOLAR +/-„  
Transport damage, i.e. through bad handling and /or packing.  
1.4 Liability Disclaimer  
Respecting this manual, servicing and method of installation, functioning, application and  
maintenance of the appliance can not be controlled or supervised by Firma Studer INNOTEC.  
Hence we do not accept any liability and responsibility for damages, loses and costs which result  
through the use of this appliance or which result through incorrect installation, incorrect operation  
or wrong application and maintenance or which by some other means maybe connected together  
to these. Similarly, we do not accept any responsibility for any violation of the patents rights or  
violation of any third party’s rights resulting from the use of this appliance  
Studer INNOTEC reserves the right to modify the technical data or these operating instructions  
without issuing any prior notice.  
1.5 Precautions  
This manual must be readily available for the user at all times. The user must be familiar with the  
precautions and safety aspects.  
User manual  
COMPACT V4.0 E  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
During operation of COMPACT, high tensions are generated at the connections and inside of the  
appliance which could be deadly fatal. Work on the appliance and on the installation should only  
be carried out by qualified and trained personnel.  
The whole installation connected with the COMPACT must comply with the respective valid codes  
and ordinances.  
Persons without the written authorization from Studer INNOTEC are strictly forbidden to carry out  
any changes or repairs on the appliances. For authorized changes only original parts are to be  
used.  
The COMPACT may only be used when it has been installed in accordance with these instructions  
and all parts have been correctly assembled and installed.  
On the IN- and OUTPUT points of the COMPACT only the already selected energy sources and  
consumer devices should be connected.  
In order to carry out any maintenance or repair work on the COMPACT without danger, all  
connections must be disconnected beforehand.  
Caution: Even when a COMPACT has been disconnected from the all connections, at the  
OUTPUT point there could still be deadly fatal tensions present. To remove these tensions  
you must switch on the COMPACT ON with the ON/OFF switch. After one minute the  
electronics are discharged and any work can now be safely carried out.  
The COMPACT is only suitable for internal use and under no circumstances should it be subjected  
to snow, rain, or any other wet conditions  
By installations in motorized vehicles the COMPACT must be protected from water-spray and any  
other wet conditions.  
The COMPACT may only be connected to lead –acid or lead-gel batteries.  
Caution: In normal use lead-acid and lead-gel batteries give out explosive gases. Never smoke  
or allow a spark or flame in the vicinity of batteries. The batteries must always be stored or placed  
in a well ventilated area, they should be placed in such a way that there is no danger of short  
circuiting through carelessness. Never charge frozen batteries.  
The COMPACT is not to be used or sold for life support equipment or applications.  
1.6 Special Precautions  
While working on batteries there should always be a second person close to you or within your  
voice range, in case help is needed.  
Plenty of fresh water and soap must be ready at hand so that in case of acid coming in contact with  
skin, eyes and clothes, the areas in question can be thoroughly washed.  
If acid enters the eyes, you must thoroughly wash the eyes with cold running water for at least 15  
minutes. It is recommended that you immediately consult a medical doctor.  
Baking powder neutralizes battery acid electrolyte. Always keep some at hand.  
Special care must be taken when working with metal tools near or on the batteries. With tools such  
as screwdrivers, spanners etc. short-circuits can result. Sparks produced by the short circuit can  
cause an explosion.  
When working on batteries all personal metal items such as rings, necklaces and bracelets must  
be removed. Batteries are so powerful that short-circuit with these items can melt them and thus  
cause severe burns. Always follow the battery manufacturer instructions.  
Under certain conditions COMPACT or a connected generator can start automatically. While  
working on an electrical installation you must ensure that these appliances are disconnected  
beforehand from the installation.  
User manual  
COMPACT V4.0 E  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
2 Introduction  
The COMPACT is a sine wave inverter with integrated battery charger and solar charger controller  
with many additional functions, it has been developed to be used as stand-alone (independent of a  
grid-system) AC provider, or as continuous / break-free current supply provider.  
2.1 Principle schematic  
AC IN  
AC OUT  
10nF  
1uF  
L
L
100nF  
Input  
PE  
N
Output  
230Vac  
PE  
N
230Vac  
10nF  
4x2,7M  
Filter  
AUX. CONT.  
Battery  
Inverter  
Charger  
BATTERY  
150A  
1uF  
1uF  
CT35  
Temp. Sensor  
Microprocessor,  
Control, Adjustment  
SOLAR  
Display  
Solarmodule  
Max. 6m  
Remote control  
INVERTER - CHARGER  
RJ11  
RCC-01  
COMPACT  
TRANSFER  
A
%
AC IN  
AC OUT  
INVERTER  
6p  
8p  
160  
Remote control  
130  
CHARGER  
Temp.  
70  
60  
100  
80  
RESET  
ALARM  
SOLAR CHARGE  
EQUALIZE  
(Select)  
Max. 40m  
50  
40  
30  
60  
40  
20  
Over Temp.  
20  
10  
Ch Inv  
arg  
er  
10  
5
Overload  
Battery  
Program  
Contact active  
Low/High  
ert  
er  
Contact manual  
OFF  
A
U
X
I
L
I
A
R
Y
(
C
P
O
ro  
N
g
TraA  
m
C
)
T
(C  
O
h
Nan/ gOFsFtatus)  
e
2.2 Description of main functions  
2.2.1 The Inverter  
The sine wave inverter built in the COMPACT generates a sinusoidal AC voltage with an  
exceptionally precise voltage and stabilized frequency. In order to start large electric motors, the  
user has the possibility to employ a short-start-power which is 3-times the nominal power of the  
COMPACT.  
The inverter is protected against overload and short circuit. A power-stage with the latest MOS-  
FET power transistors, a toroidal transformer, and a fast regulating system make-up a robust and  
reliable inverter with highest efficiency. A 1-20 Watt adjustable charge detection system serves to  
provide the smallest energy consumption and ensures a long life for the battery.  
2.2.2 The Transfer system  
COMPACT can be connected to an AC source. For example a stand-by emergency generator or  
the AC network. With the transfer system, on one side you have an alternating voltage at the  
output for use by the connected consumer devices. On the other side the batteries are charged.  
The distribution of energy between the consumer devices and battery charger is automatic.  
2.2.3 The Battery charger  
The built-in battery charger is so arranged that it can charge the batteries quick very completely. A  
microprocessor controlled, 3 to 4 Step charging process ensures the optimum charging of the  
batteries. The desired charging current can be set continuously from 0 – 55A (C 4000-48: 0 - 50A).  
The battery charger is meant for the lead-acid and lead-gel batteries. Thanks to the floating charge  
system the batteries can remain continuously connected.  
User manual  
COMPACT V4.0 E  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
2.2.4 The solar charge controller (optional)  
With the built-in solar charge controller, the COMPACT is a complete solar-power-center. In a solar  
installation this controller ensures that the batteries are charged correctly. With the COMPACT,  
batteries can be charged with a generator and with the solar modules at the same time. The  
charging of batteries with both energy sources is carried out fully automatically.  
2.2.5 Remote control  
As an option, a remote control can be connected to COMPACT. All operating elements and  
displays with the exception of the level adjustment are available on the remote control. The remote  
control is furnished with a 20m long cable. This cable can go to 40m long. On the remote control  
output power and charging current are also shown.  
2.3 Battery connections  
Lead-acid batteries are normally available in blocks of 2V, 6V or 12V. In most cases, to generate  
the necessary operating voltage and the capacity of the batteries for the COMPACT many  
batteries have to be connected together in parallel and or in series. Following three examples are  
shown:  
2.3.1 Parallel Connection  
12V  
12V  
12V  
C 1600-12  
C 1600-12  
2.3.2 Series Connection  
2V  
2V  
2V  
2V  
2V  
2V  
2V  
2V  
2V  
2V  
2V  
2V  
2V  
2V  
2V  
2V  
2V  
2V  
C 2600-24  
C 4000-48  
12V  
12V  
12V  
12V  
User manual  
COMPACT V4.0 E  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
2.3.3 Parallel- Series Connection  
12V  
12V  
12V  
12V  
C 2600-24  
3 Assembly  
3.1 Place of assembly  
The location of the COMPACT must be chosen by the following criteria:  
Protection from unauthorized handling.  
Dry dust free room, no condensation.  
Never install directly over the battery and never in a cabinet together with the batteries.  
Keep ventilation holes free. The ventilation of COMPACT is designed in such a way that it can only  
work efficiently when the appliance is fully laying on its back.  
In mobile installation it is important to keep the vibrations down to as low as possible.  
3.2 Fixing  
3.2.1 Compact  
Basically the COMPACT can be installed in any desired location. Preferred is that the appliance be  
wall mounted with battery cables downwards. The COMPACT is fixed on the wall with four screws  
through the four holes (diameter 5.5mm) which are accessible from the outside. In motor vehicles  
COMPACT must be fixed on vibrations reducing elements. The COMPACT must not be fixed on a  
combustible base, as the back of the casing can get hot and reach up to 80 degree Celsius.  
3.2.2 Protection cover IP23  
This cover IP23 (Order ref. CIP-23) can be easily installed after  
the fixation of the COMPACT. For that’s release a little the too  
screws down and more the tow up. Then it’s possible to pass the  
IP 23 cover between the COMPACT and the wall. The cover must  
touch the screws. Lock on the four screws, it’s ready.  
3.3 Connection  
3.3.1 General instructions on connecting  
The cable connection on the terminals AC INPUT / AC OUTPUT / 15A 230VAC are carried out  
with a screwdriver Nr.1 and the connection on the SOLAR terminal with a screwdriver Nr.2.  
The conductor cross section on the terminals AC INPUT / AC OUTPUT / 15A 230VAC of the  
connecting cable must be minimum 2.5mm2.  
All connecting cables and also the mounted battery cables, must be fixed with strain relief clamps.  
The COMPACT is delivered with battery cables already connected.  
The battery cables must never be extended. If the extension is unavoidable then the conductor  
cross section must be elevated accordingly.  
To protect the battery cable, a fuse corresponding to the conductor cross section must be fixed  
directly on to the battery.  
All cables must be tightly screwed in place. For safety, a yearly control is recommended. In mobile  
installations control must be carried out more often.  
Connecting must be done by qualified personnel. Material such as cable, connectors and  
distribution boxes, fuses etc. used in the installation must comply with the respective valid low-  
voltage installation rules and regulations.  
User manual  
COMPACT V4.0 E  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
3.3.2 Protection cover for the terminals  
connections  
The protection is available as an option (Order ref.  
CFC-01) and avoid to do wrong hazardous  
connection on the terminals 230Vac. It mounted  
with strain relief clamps for the cable.  
3.4 Connecting Plan / Front side  
M
A
L
N
O
Don't open before  
disconnect line  
and battery  
Caution: Check battery  
polarity (+/-) before connecting!  
Remote  
Power  
sharing  
A wrong connection could  
damage the system.  
BATTERY  
.
Auxiliary Contact  
SOLAR  
16A-250Vac  
T y p :  
N ° :  
C 2600-24  
AC Output  
AC Input  
Ubat:  
22-32 Vdc  
Pnom: 2300 VA  
Uin: 150 - 250 Vac  
Uout: 230 V/50 Hz  
I Solar: 30A max.  
I Charge: 70A  
Remote  
control  
Temp.  
B
D E F G  
K
C
H
J
A
B
C
D
E
F
Battery +/-  
SOLAR +/-  
Remote contr.  
Equalize  
Transfer delay  
Temp.  
Battery cable (already installed)  
Connecting terminal for Solar modules  
Connecting terminal for Remote Control RCC-01  
Slide switch for equalization of the Battery  
Slide switch for Transfer Delay  
Connecting terminal for Temperature sensor CT-35  
User manual  
COMPACT V4.0 E  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
G
H
Aux. Contact  
AC Input  
Connecting terminal for Auxiliary Contact  
Connecting terminal for AC-input. Located directly above  
this terminal is the automatic safety cut-out for this  
terminal.  
J
K
L
ID Plate  
AC Output  
Caution…  
Identification plate with Technical data and Serial number  
Connecting terminal for AC-output  
Caution: Check Polarity (+/-) before connecting the  
battery !  
Polarity reversal can damage the COMPACT.  
Do not open without disconnecting all terminals  
16A Protection switch for the Transfer system  
Input current repartition  
M
N
O
Don‘t …  
16A Protection  
Remote Power  
Sharing  
3.5 Cabling/wiring  
Connecting of the COMPACT is a very important step in the installation. You must take care that  
all connecting work is carried out in a clean and correct manner and under no circumstances that a  
cable is connected to a wrong terminal.  
Connecting of the COMPACT must be carried out in the following order. In case of dismantling this  
order must be reversed.  
3.5.1 Pre-installation settings  
Before you start with the cabling of the COMPACT you must set the type of battery. In case that  
sealed-gel batteries are used then you must set the small slide-switch „Equalize“ which is on the  
front with the connecting terminals, to OFF position. In case of „normal“ lead-acid – batteries, these  
can handle a higher equalizing charge, the same slide switch can be set to ON position. In case of  
doubt leave the setting in OFF position.  
3.5.2 Connection to battery  
Get the batteries ready for connection: Matching battery terminals, matching fuse on a clamp.  
Prepare battery cables, if necessary press on cable tabs/shoes. Connect red cable on Plus (+)-  
Pole and the black cable on the Minus (-) Pole. On connecting the second cable to the battery pole  
a spark is produced, because for a short time high current flows in the COMPACT to charge the  
capacitors. For this reason follow strictly the safety measures described in this manual. Check if  
the red LED OFF (13) is lit. If it is not lit, press shortly on the switch ON/OFF (19), now OFF should  
be lit.  
On connecting the battery the COMPACT needs 1 – 2 Minutes to calculate the actual capacity of  
the battery. During this time the battery condition is shown as 100% charged. (LED 14 – 17 lit).  
If the LED 12 Battery Low/High is lit, the battery charge is too low. If the LED 12 Battery Low/High  
is blinking, the battery charge is too high.  
Caution: With a wrong battery voltage the COMPACT can be destroyed. (for example: connecting  
a C 1600-12 to a 48V-Battery).  
Nevertheless, if the COMPACT had been connected with reverse polarity, it is highly probable that  
the fuse inside the casing is defect. Before opening the casing cover all terminals must be  
disconnected including the battery. If the COMPACT does not function after the changing of the  
fuse and correcting of the polarity, it means that it is defect and must be sent for repair.  
3.5.3 Connection the 230Vac-Consumer Device (AC OUTPUT)  
The 230V consumer device must be connected to the screw terminal AC OUTPUT. For this, use a  
3-core cable with a conductor cross section of 2.5mm2. Connections are marked as follows “N“  
Neutral, “PE“ Earth, “L“ Live.  
Caution: High tension can by there. By sure that’s the compact is turn off (LED 13 alight) before  
the connection.  
User manual  
COMPACT V4.0 E  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
3.5.4 Connection the 230Vac Input (AC INPUT)  
The 230V-supply from network or from a generator must be connected to the screw terminals AC  
INPUT. For this use a 3-core cable with a conductor cross section of 2.5mm2. Connections are  
marked as follows “N“ Neutral, “PE“ Earth, “L“ Live.  
3.5.5 Connect the solar modules: SOLAR +/- (Only for solar option)  
Solar modules are connected on these terminals. Under no circumstances should any other energy  
source i.e. wind generator be connected to these terminals! Only solar modules must be connected  
with two cables +/-. Depending on the power of the modules, the cable cross section should be 2.5  
up to 6mm2. Before connecting it is necessary to check with a Voltmeter that the voltage of the  
Module meets the following values:  
C 1600-12 17-25V/30A, C 2600-24 34 – 45V/30A,C 4000-48 68 – 90V/20A.  
3.5.6 Connection to Auxiliary Contact  
On these tree terminals is a potential free change-over contact). The maximal permitted current  
and voltage for this is 16A/250Vac. The DEL 5 “Contact active” show the position of them: alight  
mind active and off mind non-active. The schematic view of the connections on the front, show the  
relay in the non-active mode.  
3.5.7 Connection to Remote control  
The Remote Control RCC 01 is connected in the terminal marked „Remote control“ with a RJ11/8  
connector. The Remote Control can be plugged IN or plugged OUT during any operation situation.  
Push in the connector, without forcing it, until you hear the „click“, now the connector is locked in  
place. The same applies to the plug in the Remote Control. The length of the cable for Remote  
Control should not exceed 40m. We deliver it with 20m cable.  
3.5.8 Connection to Temperature Sensor (Temp.)  
The Temperature sensor CT-35 is connected in the terminal marked „Temp“ with a RJ11/6  
connector. The Temperature Sensor can be plugged IN or plugged OUT during any operating  
situation. Push in the connector without forcing it, until you hear a „click“, now the connector is  
locked in place. The Temperature Sensor must be glued to the wall of the battery or near it. The  
Temperature Sensor cable must not be tied together with the battery cables or laid in a  
rope/bundle.  
User manual  
COMPACT V4.0 E  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
4 Operating  
4.1 Display and operating control elements  
POWER  
MONITOR  
Inverter  
output  
power  
Charge  
current  
[%]  
Ch a r g er - I n ver t er  
200  
160  
130  
100  
80  
[A]  
INPUT LIMIT  
16A  
CHARGER  
TRANSFER STANDBY  
70  
60  
50  
40  
30  
20  
10  
60  
40  
20  
230V  
20W  
70A  
10  
5
25  
23  
24  
0
0
150V  
OFF  
26  
22  
AC IN  
8
AC OUT  
1
2
7
CHARGER  
INVERTER  
9
20  
SOLAR CHARGE  
EQUALIZE  
RESET ALARM  
Lock (select)  
3
10  
11  
14  
Over Temp  
Overload  
4
5
6
15  
16  
Program  
Contact active  
Contact manual  
12  
Batt Low/High  
13  
OFF  
17  
18  
AUX. CONTACT  
(Program)  
ON/OFF  
(Change status)  
21  
19  
User manual  
COMPACT V4.0 E  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
4.2 Light Emitting Diodes  
LED  
Marking  
LED lit  
LED blinks  
1
AC IN  
Voltage corresponding to self- Voltage, outside of the self-  
adjusted values is at the AC IN adjusted values is at the AC IN  
input.  
input.  
2
3
4
CHARGER  
Battery Charger is working  
The input voltage is out value  
(voltage or frequency)  
SOLAR  
CHARGE  
Program  
Connected  
solar modules are  
delivering energy  
Programming mode for Aux.  
Contact  
5
6
7
Contact active Auxiliary Contact is activated  
Contact manual Aux. Cont. manually activated  
Transfersystem is active. In-  
coming voltage is being sent  
directly to AC OUT outlet  
8
AC OUT  
There is voltage at the AC OUT The Inverter is in Standby-Mode  
outlet  
9
10  
INVERTER  
Over Temp.  
Inverter is working  
Forced -Inverter Mode  
For the time being the COMPACT  
is out of service because of  
overheating.  
11  
Overload  
The COMPACT is out of service  
because of overload or short-  
circuit  
12  
13  
Batt. Low/High Battery voltage is too low  
Battery voltage is too high  
OFF  
COMPACT is turned off. Turning it COMPACT is for the time being  
back on is only possible manually. turned off. Turning it back on will  
follow automatically!  
14  
Battery Charger and or  
Solar  
Charge Controller are doing an  
equalization cycle  
15–18  
25  
Charge condition of Battery  
LED 15 – Absorption time is  
running  
CURRENT  
MONITOR  
Display the value of the output power in % of Pnom (in Inverter Mode)  
and the charge current in Amps. (in Charger Mode) In this mode the  
200% LED indicate that power sharing is in use.  
4.3 Push buttons  
19  
20  
21  
ON/OFF  
RESET  
Aux. Contact  
Turning the COMPACT on and off (Help Button for Programming)  
Alarm Signal off (Help Button for Programming)  
Control Aux. contact (Help Button for Programming)  
4.4 Turning Knobs  
22  
23  
24  
26  
CHARGER  
TRANSFER  
STANDBY  
Adjustment for max. Charging Current (Not for Solar charge controller)  
Adjustment for Transfer Voltage Threshold (TRANSFER – INVERTER)  
Adjustment for „Standby“ system  
Must be adjusted to the maximal available current of your AC INPUT  
supply (see on chap. 4.6.3)  
INPUT LIMIT  
User manual  
COMPACT V4.0 E  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
4.5 The Inverter  
An Inverter is built in the COMPACT, which generates a sinusoidal alternating voltage of a very  
high quality. With this Inverter any alternating voltage consuming device 230Vac up to the nominal  
power of your COMPACT can be operated. Thanks to the generous dimensioning of the  
COMPACT, you can operate appliances requiring higher power than the nominal power of the  
COMPACT for a short time. The COMPACT provide up to 3-times the nominal power to start  
motors.  
The Inverter mode is displayed through LED 9 (Inverter). If the Inverter Mode is disabled (see  
chap. 5.5) LED 9 will blink. If the LED 9 is lit, the Inverter is in operation and you have 230Vac at  
output AC OUT. The actual power of the connected consumer device is displayed on the power  
monitor 25 and on the remote Control.  
4.5.1 Charge detection system „Standby“  
In order to avoid unnecessary discharge of the battery, the inverter switches OFF automatically if  
no consuming device is connected and switches ON automatically again if a consuming device is  
connected. The LED 8 blinks if the inverter is in Standby-Mode. The switching-on/starting level can  
be adjusted with the turning knob 24 „STANDBY. Adjusting the switching-on level is as follows:  
Switch off all consuming devices; turn the Turning Knob 24 to the right until the LED 8 is blinking,  
switch on the smallest consuming device (i.e. Mobile phone charger); turn the Turning Knob slowly  
to the left until LED 8 is lit.  
If the Standby- Mode is not wanted, turn the Turning Knob 24 to the left, to the OFF position.  
4.5.2 Overload  
If the Inverter is too long or too heavily overloaded, it switches off. The LED 11 „Overload“ is lit and  
LED 13 „OFF“ blinks. After ca. 10 seconds the Inverter switches on automatically. If the Inverter is  
overloaded four times one after the other in a short time, then it no longer switches on  
automatically. The LED 13 remains lit. Press the push button 19 „ON/OFF“ in order to switch on  
the Inverter.  
4.5.3 Overheating (Over Temp)  
If the Inverter has been overloaded for a long time or it has been working at too high surrounding  
temperatures, it will switch off. The LED 10 „Over Temp.“ is lit and the LED 13 „OFF“ blinks. After  
cooling down, the inverter switches back on automatically. One minute before the inverter switches  
off for to high temperature it gives out an acoustic alarm signal. If the Auxiliary Contact has been  
programmed to detect the high temperature then it synchronizes the relay with the alarm signal. In  
this way, for example, an emergency back up system can be started without any break in the  
energy supply.  
4.5.4 Battery Condition  
Deep discharging of the lead-acid batteries leads to high losses in capacity and early aging. That is  
why battery condition is continuously controlled and supervised. With low voltage the inverter  
switches off. The LED 12 „L/H Batt.“ is lit and the LED 13 „OFF“ blinks. When the battery voltage  
gets up to 12.1V / 24.2V / 48.4V, the Inverter switches on automatically. One minute before the  
Inverter switch off due to low voltage it gives out an acoustic alarm signal. If the Auxiliary Contact  
has been programmed to detect the low voltage then it synchronizes the aux. contact with the  
alarm signal. In this way, for example, an emergency back up system can be started without any  
break in the energy supply.  
The low voltage is set to 11.8V / 23.6V / 47.2V. These settings are standard for most batteries.  
These voltage levels are maintained by the built-in Battery-Management-System of COMPACT by  
matching the load and the battery condition.  
This setting is comparable with the levels of 10.8V/ 21.6V / 43.2, which are given for most batteries  
on nominal load.  
All voltage levels can be programmed. See the instructions under the section on Programming.  
Check your battery supplier as to which voltage values are necessary to be set.  
User manual  
COMPACT V4.0 E  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
4.6 The Battery charger  
4.6.1 Cycle of charge  
The full automatic COMPACT Battery Charger is adjusted at the factory so that most lead-acid and  
lead-gel batteries can be charged to the maximum. As soon as the minimum alternating voltage for  
the AC IN set on the Turning Knob 23 is available at the input (LED 1 AC IN is lit), the Battery  
Charger is switched on automatically (LED 2 CHARGER is lit). The battery is fully automatically  
charged matching to the charge level, the adjusted voltage levels and the charge current. Thanks  
to the built-in Float Charge System, the batteries can be left connected for unlimited time with the  
Battery Charger switched on.  
During the charging phase the consuming devices at the outlet AC OUT are continually supplied  
with power (LED 8 AC OUT is lit).  
The charger functions are shown in the following diagram:  
[V/cell]  
[A]  
2.50  
Equalization  
70  
60  
Absorption  
2.3  
Floating  
Charging current (adjusted)  
Charging time  
A
B
C
2.1  
40  
20  
Egalization time  
Absorption time  
Floating  
D
1.9  
t
A
B
C
D
4.6.2 Equalization charging  
Before you program the COMPACT for Equalization-charge you must confirm with your supplier  
that the batteries are suitable for this process.  
Equalization is recommended for the lead-acid batteries in order to mix well the electrolyte fluid  
and to clean the lead plates.  
Equalization mode should never be used when using Gel-Batteries  
If the COMPACT is operating with a lead-acid battery, which is suitable for equalization, the slide  
switch „Equalize“ which is on the cable connection side, must be placed in the ON position. In this  
setting, at every 25 charge cycles an equalization is carried out for 20 min. (factory setting). During  
such a charge cycle the LED 14 is lit. Charge cycle with equalization can be started independently  
of the actual program. For this the slide switch must be slid from “OFF” to the “ON” position. The  
LED 14 will light up. If the periodic equalization is not required, slide switch must be slid back to the  
„OFF“ position after the completion of the manual cycle.  
CAUTION: During the equalization process, the batteries produce lot more gas.  
DANGER OF AN EXPLOSION !!  
4.6.3 Input current repartition (Power sharing)  
For manage the power available on the AC INPUT (depend the supply use) the COMPACT is  
equipped with a system usually called “Power sharing” or INPUT power distribution. With this  
function it’s possible to limit the AC INPUT current assigned to the charger. More current it uses on  
User manual  
COMPACT V4.0 E  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
the OUTPUT less it’s give to the charger. Priority to the OUTPUT.  
When the power sharing is used the LED 200% (red) is lit to point  
out that’s the charge is limited.  
Caution: If the power use on the OUTPUT is higher than the value  
of the INPUT LIMIT (26) the COMPACT limits the current, then the  
generator means to stop or the circuit breaker before means to  
break.  
In option, a remote control (RPS-01, 20m cable) allows the Power  
Sharing far from the COMPACT.  
4.6.3.1 Set the INPUT LIMIT (26)  
The current available for the COMPACT depend of the supply used  
i.e. motor generator, network limit in a camping or shore  
connections… The value of the turning knobs INPUT LIMIT (26)  
must by adjust lower or equal of the current available from the  
source.  
For example if you have a generator of 2kW you must adjust the  
turning knobs 26 to approximately 8.5A. For calculate this, we  
divide the nominal power (2000W) by the voltage (230V). If you  
have a circuit breaker (i.e. 6A) before the COMPACT, then you set  
this value on the turning knobs (26) (i.e. 6A).  
Generator  
power  
500W  
Current  
(230V)  
2A  
900W  
4A  
1500W  
2000W  
3000W  
6,5A  
8,5A  
13A  
4.6.4 Charging current  
The maximum charging current for the battery can be adjusted with the Turning Knob 22  
(CHARGER). The charging current of the battery should be set to approximately 10 – 20% of the  
battery capacity (at C10). This means that the charging current for a battery with 300Ah should be  
set between 30 – 60A.  
The charging current is displayed on CURRENT MONITOR (25) of the front panel or on the  
Remote Control.  
4.6.5 Battery Condition  
Built-in microprocessor with a specially developed  
algorithm calculates the actual state of charge of the  
battery and displays it on LED 15 – 18. The LED 14 is  
lit when the system is carrying out a charge cycle with  
equalization.  
Equalization cycle  
Battery 75 – 100%  
Battery 50 – 75%  
14  
15  
For safety reasons, you must get the recommended  
charge voltage and charge currents from your battery  
supplier. The voltage levels and charge characteristics  
can be changed through Programming. The instruction  
for programming of battery charger is in the section  
„Programming“ (Chap. 5.1.2). The correct charging is  
indispensable for a safe function and long-life of the  
battery.  
16  
17  
18  
Battery 25 – 50%  
Battery 0 – 25%  
4.7 The Transfer system  
When an ac voltage is at the input AC IN of the COMPACT, the LED 1 AC IN is lit. When this  
voltage matches the lowest adjusted value set by the Turning Knob 23 TRANSFER, and the  
frequency is between 44Hz and 65Hz, this voltage is switched directly to the battery charger and to  
the output AC OUT. The LED 7 TRANSFER is lit. The inverter is switched off and the battery  
charger switched on. This process is automatic, unless the charger mode or the transfer mode is  
disabled (see Chap.5.5)  
The maximum current of the Transfer switch is 16A. That means through this system, consuming  
devices up to a maximum of al 3700 Watt can be operated. When the Battery Charger is working,  
part of this power is used for the charging according with the power sharing system.  
User manual  
COMPACT V4.0 E  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
The Transfer system is protected against overload with an automatic safety fuse on the AC Input  
side of the COMPACT. If the system has been overloaded the button/pin of the fuse will pop-out.  
To put the automatic safety system back in to operating you must push this pin back.  
Note: In the Inverter operation, The COMPACT generates a true sinusoidal and quartz stabilized  
output voltage. When, however the COMPACT is supplied from a grid or a generator and the  
transfer contact is active, then you have at the output AC OUT the same voltage as that at the  
input. This voltage can not be modified by the COMPACT!  
4.7.1 Set the transfer voltage threshold  
The voltage threshold of the transfer can by adjust between 150 to 230V with the turning knobs  
(23). From factory this value is 200V. Most of appliances can work on this voltage. When the Input  
voltages reach the settled value on turning knob, the inverter switch off and the AC INPUT go  
directly on the AC OUTPUT. When the voltage INPUT is less of 20V the value set, the transfer is  
stop and the OUTPUT switch back on the inverter.  
Don’t use the turning knobs “TRANSFERT” (23) to adjust the AC OUTPUT voltage!  
This is only it’s only a voltage threshold level to enable or disable the transfer.  
4.7.2 FAST (UPS)- MODE for the Transfer Switch  
The quick and break free Transfer mode is programmed with a slide switch „Transfer Delay“ OFF,  
which is on the front side (cable connections side).  
The aim of the COMPACT is to supply the consuming device with a break-free alternating voltage.  
When the incoming voltage AC IN no longer matches values which have been set with the Turning  
Knob 23, the Inverter switches on at once. The transfer is carried out in 0.02 seconds. This quick  
transfer ensures a break-free function for most consuming devices. If you have an alternating  
voltage back at the input AC IN, transfer system starts up again without any break, and the inverter  
is stopped.  
4.7.3 Delayed mode of the Transfer System  
The delayed mode of the transfer system „Transfer Delay ON“ is programmed with the slide switch  
on front with the cable connections. The COMPACT provides a break-free alternating voltage for  
the consuming device. A quick transfer switch is not always sensible nor is it always desired. For  
example, when the consuming devices are operated by a small back-up generator. An overload of  
a short duration on such a generator, i.e. start of a vacuum cleaner etc., has the effect of  
decreasing the voltage for a short time. As in such cases the transfer to the Inverter is not  
desirable, the transfer system can be programmed with a delay. When the slide switch (Transfer  
delay) is in the „On“ position, the transfer to the inverter takes place with a delay of 5 seconds. If  
the voltage falls below 100Vac, the transfer takes place without delay! The transfer switching to the  
Inverter takes place without any break.  
4.8 The Solar charge controller (option)  
The COMPACT also has a Solar Charge Controller built in. For charging the batteries, Solar  
modules can be connected to the screw terminal SOLAR +/-. The in-built controller is a „Shunt  
controller“ for the maximum input current of 30A for C 1600-12 and C 2600-24 and 20A for C 4000-  
48. The operating voltage of solar panels to be connected must match the actual operating voltage  
of the COMPACT and never exceeds the max. rated value.  
Under no circumstances should any other systems such as wind-generator be connected at the  
input of the Solar Charge Controller.  
The Solar Charge Controller works automatically and is always in operation. As soon as the energy  
is delivered from the Solar Charge Controller, LED 3 “SOLAR CHARGE” is lit and the batteries are  
being charged. The Solar Charge Controller works even when the Battery Charger is functioning.  
The way of working is the principally the same as that of the Battery Charger. The function is  
described in the section on Battery Charger. The programming and the adjustments are carried out  
in accordance with the same conditions. Check with your battery supplier which adjustments must  
be carried out for your battery.  
User manual  
COMPACT V4.0 E  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
4.9 The Multifunctional Contact  
In the COMPACT there is a built-in programmable power relay. The potential-free change-over  
contact (NO – NC) of this power relay is connected to the screw terminal AUX CONTACT.  
Maximum Contact load:  
-230Vac /16Amp-30Vdc/1A !  
With the Push Button 21 „AUXILIARY CONTACT“ the contact can be manually switched on or off  
independent of programming and the operating situation. The LED 5 “Contact active” shows the  
state of the contact. The drawing up the screw terminal “AUX CONTACT” is the inactive position  
mode, LED 5 “Contact active” off.  
The switching on and off of this contact can be freely programmed for every operating situation of  
the COMPACT witch situation is indicated with a LED. There is no limitation to its application and it  
is left to your wishes and desires as to where and how you would like to use it. The example and  
the setting of this contact are explained chapter 5.4.2.  
In factory we program this for a dysfunction alarm. The contact is active when one of these  
situations is detected:  
Over temperature (LED 10 lit)  
Overload (LED 11 lit)  
Over or less voltage of batteries (LED 12 lit or blinking)  
COMPACT is turned off manually or with a fault (LED 13 lit)  
4.10 The Remote Control  
As an option a Remote Control can  
INVERTER - CHARGER  
COM PACT  
be connected to the COMPACT. All  
operating controls and displays  
except from level adjustment are  
available on the Remote Control.  
The Remote Control is supplied  
with a 20m long cable. It can be  
lengthened to 40m. The Remote  
Control is suitable for surface  
mounting on the wall or on to a  
switch board. It is fixed with 4  
screws. The COMPACT can also  
be programmed with the Remote  
Control. The Programming is  
described in the section „Program-  
ming“.  
RCC-01  
TRANSFER  
AC IN  
AC OUT  
A
%
160  
130  
100  
80  
60  
40  
20  
10  
5
CHARGER  
INVERTER  
70  
60  
50  
40  
30  
20  
10  
RESET  
ALARM  
(Select)  
SOLAR CHARGE  
Over Temp.  
Overload  
EQUALIZE  
Program  
Contact active  
Contact manual  
Battery  
Low/High  
Charger  
Inverter  
OFF  
ON/OFF  
(Change status)  
AUXILIARY CONTACT  
(Program)  
The output power and the charging  
currents are displayed on the  
Remote Control.  
In the Remote Control there is an  
additional Alarm Contact and a Control  
Input built in. These two functions are  
available through Tip-jack RJ11/4 for use.  
This Auxiliary Contact is Front / Work  
ON/OFF  
! -batt  
!
Contact  
(max.  
0.5A!),  
which  
is  
1 2 3 4  
independent of the Auxiliary Contact of the  
COMPACT. This contact is active in case  
of an alarm of the COMPACT.  
COMPACT  
Remote control  
60V/0,5A  
max  
.
Dry contact  
only  
The Control Input is connected in parallel to the ON/OFF- push button. The COMPACT can be  
switched on or off through this input with an impulse button or an impulse contact.  
Order Number for Remote Control: RCC-01  
Dimensions: H x B x T / 111.5 x 136.5 x 25mm  
User manual  
COMPACT V4.0 E  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
Caution: No external voltage should be connected to this Input Control.  
4.11 The Temperature sensor  
Operating voltage of lead-acid batteries change depends on the  
temperature. To correct the operating voltages according to the actual  
temperatures, a temperature sensor can be connected to the COMPACT.  
The compensation through the sensor is –3mV/°C/Cell.  
Order Number: CT-35  
Dimensions: H x B x T / 58 x 51.5 x 22mm  
5 Programming  
5.1 Standard setting  
The COMPACT is delivered with the default setting following:  
5.1.1 Working mode  
The working of the charger, the inverter and the transfer are described in chapter 5.3/5.4/5.5.  
5.1.2 Battery voltage  
Low voltage  
Float Charge  
End of Charge Voltage  
Equalization  
Absorption Time:  
11.6V / 23.2V / 46.4V  
13.5V / 27.0V / 54.0V  
14.4V / 28.8V / 57.6V  
15.3V / 30.6V / 61.2V  
2 Hours  
5.1.3 Auxiliary contact  
Active in case of defect or manual turn off with the LED 10/11/12/13  
5.2 Reset value  
When the COMPACT is to be connected to a battery or after an interruption (RESET), it is always  
programmed with these standard settings.  
In order to get to these settings during operation you must press the three Push Buttons 19/20/21  
simultaneously for a minimum of 2 seconds.  
5.3 Battery voltages and absorption time  
The voltage levels (low voltage, float charge, end of charge and equalization) and the duration of  
the absorption charge can be changed.  
The display of these voltages and the times in the program mode are in accordance with the  
diagram shown below:  
5.3.1 Table of voltage and timing threshold  
Low voltage  
LED 13  
Float Charge  
LED 12  
Absorption  
LED 11  
Equalization  
LED 10  
Absorpt.  
Time  
LED 10->13  
LED 12V 24V 48V 12V 24V 48V 12V 24V 48V 12V 24V 48V 12/24/48V  
14  
15  
16  
17  
18  
12.0 24.0 48.0 13.7 27.4 54.8 16.2 32.4 64.8 16.2 32.4 64.8 4 h  
11.8 23.6 47.2 13.6 27.2 54.4 15.6 31.2 62.4 15.9 31.8 63.6 3 h  
11.6 23.2 46.4 13.5 27.0 54.0 15  
11.4 22.8 45.6 13.4 26.8 53.6 14.4 28.8 57.6 15.3 30.6 61.2 1 h  
11.2 22.4 44.8 13.3 26.6 53.2 14.2 28.4 56.8 15 30 60 0 – 1Min.  
30  
60  
15.6 31.2 62.4 2 h  
The heavy printed values show the standard settings.  
User manual  
COMPACT V4.0 E  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
5.3.2 Set the voltage and timing  
threshold  
The programming is done in accordance  
with the following steps:  
3
RESET ALARM  
lock  
20  
14  
15  
10  
11  
12  
Over Temp  
Overload  
Push and hold down, the Push Button 21  
(Program) and the Push Button 19  
(Change status) for minimum 2 seconds  
simultaneously.  
With the Push Button 20 (select) select  
with of the battery level and the absorption  
time to be changed.  
4
5
6
Batt Low/High  
16  
17  
18  
13  
19  
OFF  
ON/OFF  
(Change status)  
21  
These four red LED show the function set:  
Low voltage  
LED 13  
Float charge  
Absorption (End of charge)  
Equalization  
LED 12  
LED11  
LED 10  
Absorptions Time  
LED 10/11/12/13  
With the Push Button 19 (Change status) set the desired parameter (voltage or the time) to modify  
(LED 14/15/16/17/18). Push Button 19 (Change status) to set the desired value according to the  
table 5.3.1.  
If desired, repeat the operation with any other parameter (voltage or time) to be changed.  
If during 10 seconds no buttons are pressed, the selected values are automatically stored and the  
COMPACT switches back in to the normal operating status.  
The voltage levels and times changed through programming are only first active with the next  
charge cycle!  
The voltage level which are not suitable can greatly reduce the battery life or could even destroy it !  
Therefore check beforehand with your battery supplier.  
5.4 Programming the auxiliary contact  
5.4.1 Principle  
The Auxiliary Contact can be basically programmed for any operating situation of the COMPACT  
which is indicated with a LED. The programming is possible for one or more operating situations. If  
the contact is programmed for many situations, it is activated as soon as the COMPACT finds itself  
in any one of the programmed situations. That means that the work of the contact meets that of the  
logic OR–Function.  
5.4.2 The programming of the Auxiliary Contact is carried out in the following Steps  
The Push Button 21 (Program) press down for min. 2 seconds. The LED 4 „Program“ is lit as an  
indication, that the COMPACT is in program mode.  
A lit LED shows the programmed condition for the auxiliary contact. (LED 10/11/12/13 factory  
setting)  
With the Push Button 20 (select), select the desired condition in which the contact should be  
activated.  
With the Push Button 19 (Change status) confirm or change the status for this condition.  
If desired, with the Push Button 20 (select) select another condition in which the contact should be  
activated.  
With the Push Button 19 (Change status) confirm or change the status for this condition.  
If during 10 seconds no buttons are pushed, then the settled values are automatically stored and  
the COMPACT switches back to normal operating condition.  
User manual  
COMPACT V4.0 E  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
5.4.3 Examples  
5.4.3.1 Auxiliary Contact as generator starter  
As per the battery capacity  
When in the programming of the Auxiliary Contact, the Battery Capacity (LED 15-18) is used as a  
condition, then you must take note of the following requirements.  
If you have to start an emergency back-up supply with a battery having a certain residual capacity,  
then two battery levels must be programmed. The first (i.e. Battery 25% LED 17) for the starting or  
activating the Auxiliary Contact and the second (i.e. Battery 100% LED15) for stopping or  
deactivating the Auxiliary Contact. By programming like this the Auxiliary Contact works with the  
lowest set condition and stops when it has reached the highest programmed condition through  
charging.  
As per the inverter output power (not available with some special executions)  
Activating the auxiliary contact for the generator start can be programmed also on a pre-  
determined output power of the inverter. The auxiliary contact will be activated if the inverter output  
power exceeds 80% of the inverter nominal power during 3 minutes and/or 100% during 30  
seconds.  
The auxiliary contact will remain activated 30 minutes after the input current has come back to a  
value lower than the one adjusted by the “INPUT LIMIT” (chap. 4.6.3). In other words, the contact  
will be deactivated 30 minutes after the lighting out of the LED 200%.  
This programming is achieved accordingly to chap. 5.4.2 of the user manual and by activating the  
contact on LED 100% of “Power Monitor” (25).  
5.4.3.2 Auxiliary Contact as Twilight Switch (with solar charger option)  
The Auxiliary Contact of the COMPACT can also be used as a twilight switch, i.e. to operate  
automatically the exterior lighting. With it the connected solar modules measure the light intensity.  
If the COMPACT is operating without solar modules and a twilight-switching function is desired,  
you can connect small solar cells with the nominal voltage of the COMPACT on to the SOLAR  
terminals for the purpose of measuring the light intensity. To function as a twilight-switch the  
Auxiliary Contact must be programmed so that the condition SOLAR CHARGE (LED 3) is active.  
Programming must be carried out in steps and in accordance with the description for the  
programming of the Auxiliary Contact.  
5.4.4 Manual operating of Auxiliary Contact  
The Auxiliary Contact can be operated at any time with the Push Button 21 (AUX. CONTACT). The  
LED 6 „Contact manual“ lights up as information that the Contact is manually operated, and LED 5  
„Contact active“ lights up when the Contact is active. By pushing the Push Button 21 a second  
time, the Contact is deactivated. By pushing it the third time, automatic functions are restored.  
5.5 Disabling some of the Compact functions  
Each different function charger, inverter and transfer can be disabled. This is useful for specific  
applications which are required to disable some of these three functions.  
If you press the button (20) more than 2 seconds, you can have the access to the different  
possibilities shown in the following diagram.  
In programming mode the display show only the different types of program with the three LED 2,7  
and 9 to each functions. To change the type of programming press shortly the button 20 until your  
reach to the right function use according table below. After 10 seconds the COMPACT exit the  
programming mode and load the new change.  
In user mode, the disabled functions are displayed by blinking LED. So you can see in witch mode  
is disabled.  
User manual  
COMPACT V4.0 E  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
5.5.1 Diagram of the different modes  
Show an off LED  
Show a blinking LED  
Show a lighted LED  
9
All the functions are enabled. This is the  
factory setting.  
1
2
8
9
AC IN  
AC OUT  
7
7
7
7
CHARGER  
INVERTER  
The inverter is disabled. Only the transfer  
switch and the charger will work normally.  
1
2
8
9
AC IN  
AC OUT  
CHARGER  
INVERTER  
Charger and transfer switch are disabled. the  
inverter will work continuously even if there is  
a correct AC voltage at the input  
1
2
8
9
AC IN  
AC OUT  
CHARGER  
INVERTER  
Inverter and charger are both disabled.  
Only the transfer switch function is enabled in  
input voltage and frequency is OK.  
1
2
8
9
AC IN  
AC OUT  
CHARGER  
INVERTER  
6 Maintenance  
Apart from the periodic controls mentioned for the connections, the COMPACT does not need any  
maintenance. Keep the appliance clean and from time to time wipe it clean with a damp cloth.  
7 EC Compliance  
We hereby state that the products described in this user manual meets the following standards:  
EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2, Dir. 89/336/EEC,  
LVD 73/23/EEC  
CH-1950 Sion, 31st of March 2000  
STUDER INNOTEC (R. Studer)  
User manual  
COMPACT V4.0 E  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STUDER INNOTEC  
COMPACT  
8 Technical Data  
Technical data  
C 1600-12  
C 2600-24  
C 4000-48  
Model  
Inverter  
Nominal battery voltage  
Input voltage range  
Continuous power @ 25°C  
Power 30 min. @ 25°C  
Maximum power load 5 sec.  
Maximum load  
Maximum asymmetric load  
Stand-by adjustment  
Cos ϕ  
12V  
24V  
19 - 32V  
2300VA  
48V  
9.5 - 16V  
1300VA  
1600VA  
38 - 64V  
3500VA  
4000VA  
2600VA  
3 x Pnom  
up to short circuit  
up to Pcont.  
1 to 25W  
0.1 - 1  
Maximum efficiency  
94%  
95%  
Consumption OFF/Stand-by/ON  
Output voltage  
0.5/0.6/6W  
0.8/0.9/9W  
230Vac (- 10% / 0)  
50Hz +/- 0.05%  
< 2%  
1.2/1.4/12W  
Output frequency crystal controlled  
Total harmonic distortion  
Dynamic behaviour on load change 0 to 100%  
Overload and short circuit protection  
Overheat protection  
0.5 ms  
Automatic disconnection with 3 time restart attempt  
Acoustic warning before shut-off - with automatic restart  
Battery charger (4 STEP) I-U-Uo-Equalize (every 25 cycles)  
Charging current adjustable  
Input current balance adjustment (Power Sharing)  
Maximum input voltage  
0 - 55A  
0 - 55A  
1 - 16A  
265Vac  
0 - 50A  
Minimum input voltage  
Input frequency  
Adjustable threshold from 150 to 230Vac  
45 - 65Hz  
Power Factor Correction (PFC)  
EN 61000-3-2  
Optional solar charger (4 stages) I-U-Uo-Equalize (every 25 cycles)  
Maximum PV open circuit voltage (V)  
Maximum charge current (A)  
25V  
30A  
45V  
30A  
90V  
20A  
Working principle: I-U-Uo-Equalize (every 25 cycles)  
Shunt  
Battery control (thresholds and times adjustable by the user)  
Absorption time  
End charge cycle voltage  
Floating voltage  
Equalization voltage  
Deep-discharge protection  
Temperature compensation (optional CT-35)  
0-4 h  
28.8V  
27.2V  
14.4V  
57.6V  
54.4V  
62.4V  
43.2V  
13.6V  
15.6V  
10.8V  
31.2V  
21.6V  
-3mV / o C / cell  
General data  
Multifunction contact - potential free (3 points)  
Max. current on transfer relay  
Transfer time  
16A - 250Vac  
16A/3.7kVA  
< 20 ms  
16A/3.7kVA  
16 kg  
16A/3.7kVA  
Weight  
17.1 kg  
29.4 kg  
Dimension h x l x L [mm]  
Protection index IP20  
124x215x480  
IP23 with top cover CxxxxIP23  
124x215x670  
EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022,  
EC conformity  
EN 61000-3-2, Dir. 89/336/EEC, LVD 73/23/EEC  
Operating temperature range  
Ventilation  
-20 to 55 oC  
from 45 oC  
Acoustic level without / with ventilation  
Warranty  
< 10 dB / < 35 dB  
2 years  
Options  
Solar charge controller  
Remote control (112 x 138 x 25mm / 20 m. cable)  
Remote power sharing (20 m. cable)  
IP-23 top cover  
C-xxxx-S  
RCC-01  
RPS-01  
C-xxxx-IP23  
CFC-01  
AC cable cover  
Battery temperature sensor (58 x 51.5 x 22mm / 3 m. CT-35  
cable)  
Data may change without any notice  
User manual  
COMPACT V4.0 E  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sharp CRT Television LC 52LE920UN User Manual
Shure Headphones M75E 95C 7 User Manual
Snapper Lawn Mower 150Z ZTR Series User Manual
SonicWALL Network Router EM5000 User Manual
Sony Car Stereo System CDX 3250 User Manual
Sony Car Stereo System GT430IP User Manual
Sony Laptop PCG FRV30 User Manual
Sony Pet Fence XL 2200 User Manual
Sunbeam Air Cleaner 2571 User Manual
Sun Microsystems Network Card 806 2989 10 User Manual