Rinnai Water Heater 2424WC User Guide

How to use your New  
Continuous Flow  
Commercial Water Heater  
Model 2424WC  
(outdoor unit)  
WARNING: If the information in these instructions is not followed exactly,  
a fire or explosion may result causing property damage, personal injury or  
death.  
-Do not store or use gasoline or other flammable vapors and liquids in  
the vicinity of this or any other appliance.  
-WHAT TO DO IF YOU SMELL GAS  
* Do not try to light any appliance.  
* Do not touch any electrical switch; do not use any phone in your  
building  
* Immediately call your gas supplier from a neighbor’s phone. Follow  
the gas supplier’s instructions.  
* If you cannot reach your gas supplier, call the fire department.  
- Installation and service must be performed by a qualified installer,  
service agency or the gas supplier.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S P E C I F I C A T I O N S  
Appliance - AC 120 Volts - 60Hz.  
Remote control DC 12 Volts (Digital)  
Flame failure - Flame rod  
Boiling protection - 203°F  
Remaining flame (OHS) 194°F bi-metal switch  
Thermal fuse 279°F  
Safety devices  
Automatic frost protection - Bi metal sensor & anti-frost heaters  
Combustion fan rpm check - Integrated circuit  
Over current - Glass fuse (3 amp)  
If remote fails or becomes disconnected unit defaults to 100°F with water  
flowing, this is an anti-scald feature.  
Remote control  
MCC-45-3 US  
Main control  
Remote control cable  
Non-polarized two core cable  
Top of heater  
Front of heater  
Sides of heater  
Back of heater  
Ground  
12"  
24"  
6"  
Clearances from combustibles  
0"  
12"  
Below eaves, porches, overhangs = 36"  
Natural Gas : *Minimum 6" W. C. Propane Gas: *Minimum 10" W. C.  
Minimum and Maximum gas supply pressure  
Manifold Gas Pressure  
Warranty  
(NAT.)  
**Maximum 10.5" W. C. (LPG)  
**Maximum 14" W. C.  
Natural Gas  
LPG:  
5.3" W. C. high fire  
8.7" W. C. high fire  
0.43" W. C. low fire  
0.59" W. C. low fire  
Five years heat exchanger / five years parts (see unit's warranty for details)  
*Minimum input pressure is for the purpose of input adjustments.  
**Do not exceed maximum pressure.  
Model 2424WC  
3
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W
A
R
R
A
N
T
Y
Rinnai warrants the  
continuous Commercial Water Heater Model 2424WC, including any parts and  
components thereof, to be free from any defects in materials and workmanship for the period specified below,  
subject to the terms specified in this warranty. This warranty gives you specific legal rights and you may also have  
other rights which vary from state to state.  
This Warranty shall apply to the Continuum Continuous Water Heater as follows:  
CONDITION AND EXCEPTIONS  
Item  
Type of Failure Covered  
Period of Coverage  
Heat Exchanger  
Defective Materials or  
Workmanship  
5 Years from Date of  
Purchase  
All other parts  
and components  
Defective Materials or  
Workmanship  
5 Years from Date of  
Purchase  
In the event of a malfunction, operational difficulty or failure of the product, or any part or any component thereof,  
during the warranty term, resulting from defects in materials or workmanship, Rinnai will remedy the malfunction,  
operational difficulty, or failure without charge to the owner of the water heater. The remedy will consist of repair  
or replacement of the product at the option of Rinnai.  
Rinnai will only provide those remedies listed above. The owner shall be responsible for all other costs, including  
but not limited to shipping and delivery charges, labor associated with the removal and reinstallation of the prod-  
uct or its components, and any other incidental costs such as other materials or permits that may be required for  
installation.  
This warranty DOES NOT cover any failures, operational difficulty or malfunction due to accident, abuse, misuse, alter-  
ation, Acts of God, misapplications, improper installation or improper maintenance or service, lime damage, or from any  
other cause other than defects in materials or workmanship. Warranty does not cover use as a pool or spa heater.  
PROCEDURE FOR MAKING A CLAIM  
In order to obtain the benefits of the warranty, contact your selling dealer or Rinnai at 800-621-9419 for the  
location of the servicing dealer nearest you.  
Proof of Purchase is required to institute a claim under this warranty. This document does not constitute proof-of  
purchase.  
LIMITATION ON IMPLIED WARRANTIES  
Any implied warranties of merchantability and fitness applicable to the equipment arising under state law are  
limited in duration to the period of coverage provided by this limited warranty, unless the period provided by state  
law is less. Some States do not allow limitations on how long an implied warranty lasts, so the above limitation  
may not apply to you.  
DISCLAIMERS  
Rinnai is not liable for any special, indirect or consequential damages, such as water damage, loss of use, incon-  
venience, damage to person or property, whether arising in contract or tort.  
Rinnai does not authorize any person or company to assume for it any other obligation or liability in connection  
with the sale, application, engineering, installation, use, removal, return or replacement of its product, and no such  
representations are binding on Rinnai.  
Please DETACH the enclosed warranty registration card, fill it out, and drop it in the mail. Receipt of this  
completed card by Rinnai will constitute proof-of purchase for your Rinnai Continuum 2424WC.  
4
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C
O
N
T
E
N
T
S
Specifications.............................................................. 2,3  
Warranty ........................................................................ 4  
Owner's Installation Information................................... 6  
Features of your new Continuum ................................ 7  
Safety Issues.............................................................. 8,9  
Basic Operation........................................................... 10  
About Hot Water ......................................................... 11  
Scalds-First Aid ........................................................... 11  
Remote Control Operation ......................................... 12  
Error Messages........................................................... 13  
Maintenance & Service Information...................... 14,15  
Trouble Shooting and Common Questions ............... 16  
Operating Instructions............................................ 17,18  
Care & Lime Condition Warning ................................ 18  
Model 2424WC  
5
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
O W N E R ’ S I N S TA L L AT I O N I N F O R M AT I O N  
This product must be installed by a Rinnai certified installer. Failure to  
have the product installed by a Rinnai certified installer may result in a  
voiding of the product’s warranty.  
This appliance must be installed in accordance with local codes, or in  
the absence of local codes, the National Fuel Gas Code, ANSI Z223.1  
and/or the CAN/CGA-B149, Installation Codes.  
Install this product outdoors, DO NOT install indoors.  
Do Not use this appliance if any part has been underwater. Immedi-  
ately call a qualified service technician to inspect the appliance and to  
replace any part of the control system and any gas control which has  
been underwater.  
Detailed instructions on the proper installation practices to follow for  
the installation of your new continuous hot water heater are included  
at the back of this manual.  
For the Rinnai Certified Installer nearest  
you call:  
1-800-621-9419.  
6
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F E AT U R E S O F Y O U R N E W C O N T I N U U M  
The Continuum 2424WC is one of the most advanced water heaters available. It supplies  
hot water continuously at the temperature preset in the unit or at the temperature set on  
the optional remote control. The remote control is recommended for optimum perfor-  
mance.  
)
The Continuum 2424WC never runs out of hot water. While electricity, water and gas  
supplies are connected, hot water is available whenever the hot tap is open.  
)
)
The gas burner lights automatically when the hot water tap is opened, and goes out  
when the tap is closed. Ignition is electronic, there is no pilot light. When the hot water  
tap is off, no gas is used. You save energy and money with the Continuum 2424WC.  
The temperature of the outgoing hot water is constantly monitored by a built in sensor. If  
the temperature of the outgoing water rises to more than 6 degrees above the selected  
temperature (shown on the optional digital remote control) the gas burner will automati-  
cally go out. The gas burner will re-ignite once the outgoing hot water temperature falls  
below the selected temperature.  
)
Built into the microprocessor of the Continuum 2424WC is the ability to LIMIT THE  
MAXIMUM TEMPERATURE of the hot water supplied by the Continuum 2424WC. With-  
out the connection of the optional remote control, the Continuum 2424WC is preset to  
deliver 120 degree water.  
)
)
With the optional remote the water temperature is adjustable from 140°F to 180°F. The  
water temperature can be preset at 108, 120, 130, 140, 150, 160, 170 or 180 by a certi-  
fied Rinnai technician. If you require a temperature other than 120 or what the remote  
will give you, please contact your Rinnai certified technician.  
Error messages are displayed on the optional remote control, simplifying service calls.  
)
)
The Continuum 2424WC incorporates a device to prevent the temperature from varying  
when the water is off, then on again. It also incorporates a rapid response device for  
fast heating.  
The sound (noise) level from the Continuum 2424WC is very low.  
)
)
The Continuum 2424WC is a very compact direct vent device. It saves valuable floor and  
wall space.  
Model 2424WC  
7
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S A F E T Y  
I S S U E S  
Always check water temperature by hand  
before entering a shower or bath. The  
temperature may have been changed.  
The water temperature can not be adjusted  
when a hot water tap is open or when hot  
water is flowing through the water heater.  
Do not clean Remote Control with  
solvents. Use a soft damp cloth.  
Do not touch the cover or insert objects  
into the flue outlet of the Continuum  
2424WC.  
On cold days steam may be discharged  
from the flue outlet, this is normal with a  
high efficiency appliance and does not  
indicate a fault.  
8
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S A F E T Y  
I S S U E S  
If the external Continuum 2424WC is  
disconnected from the power supply and  
freezing conditions are expected, turn off  
water and gas, and drain all water from  
the appliance.  
Keep flammable materials, trees, shrubs etc.  
away from the Continuum 2424WC.  
Water Off  
Gas Off  
DRAIN  
Drain Water  
FILTER  
WATER  
Do not spray water directly into the flue  
terminal.  
GAS  
If power and the automatic frost protection are  
connected, freezing will be prevented in conditions  
as cold as -30°F.  
Depending on the weather conditions and the  
length of the pipe between the Continuum  
2424WC and the tap in use, there may be a  
variation between the temperatures displayed  
at the Remote Control and the temperature of  
the water at the tap.  
The Continuum 2424WCcontrols the  
water temperature automatically. To do  
this it sometimes needs to change the  
water flow accordingly. The water flow  
from the hot water tap may vary after the  
selected temperature at the Remote Con-  
trol is altered. The water flow may also  
vary from summer to winter, as incoming  
water temperatures differ.  
140  
142°F  
Summer  
60°F  
Incoming  
Water  
Winter  
40°F  
Incoming  
Water  
Model 2424WC  
9
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B A S I C  
O P E R A T I O N  
Adjusting Temperature  
1
2
The setpoint temperature of the Con-  
tinuum 2424WC can only be adjusted by  
the user using the Remote Control. To  
adjust the setpoint temperature of the  
Continuum 2424WC, all hot water taps  
must be closed, and all circulating  
pumps turned off.  
TEMPERATURE CANNOT BE  
ADJUSTED WHEN ANY HOT  
WATER TAP IS OPEN, OR  
WATER IS FLOWING THROUGH  
THE WATER HEATER.  
To operate the Continuum 2424WC simply turn  
any hot water tap on, or initiate water flow  
through the unit with a circulating pump. This  
will automatically light the burner providing hot  
water at the preset temperature. If the optional  
remote control has been installed, the green IN  
USE indicator will glow on the remote control.  
Simply press the  
or  
button  
until the required temperature is dis-  
played on the Digital Monitor.  
140°F  
The Remote Control will display the water  
heaters current setpoint temperature.  
CHECK LOCAL CODES FOR THE MAXIMUM  
WATER TEMPERATURE SETTING ALLOWED  
WHEN USED IN NURSING HOMES,  
SCHOOLS, DAY CARE CENTERS, AND ALL  
OTHER PUBLIC USE APPLICATIONS.  
Rinnai recommends fixing the water heater  
setpoint temperature at 108°F for ALL public use  
applications.  
1 0  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A B O U T  
H O T  
W A T E R  
Hot Water Is Dangerous, especially for the young and the elderly or the infirm. The  
Continuum 2424WC allows you to precisely control the temperature of your hot water,  
ensuring safe hot water temperatures.  
Water Temperatures over 125°F can cause  
severe burns instantly or death from scalds.  
Hot Water can cause first degree burns with  
exposure for as little as:  
3 seconds at 140 °F  
20 seconds at 130 °F  
8 minutes at 120 °F  
Test the temperature of the water with your  
elbow before placing a child in the bath or  
shower.  
Do not leave a child or an infirm person in  
the bath unsupervised.  
BURN  
S c a l d s  
-
F i r s t  
A i d  
1) Remove clothing; Remove all wet clothing, quickly. Wet clothing retains the heat.  
2) Apply cold water for 30 minutes; Immediately submerge the burnt area in cold  
water for 30 minutes to reduce the heat in the skin, preventing deeper burning.  
Never use butter, oils or ointment to cover the burn. They may retain the heat.  
3) Keep the scalded person warm; Place a blanket around the person.  
4) Seek Medical Advice; Call your medical advice hotline and describe the scald,  
follow their directions.  
Model 2424WC  
1 1  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R E M O T E C O N T R O L O P E R A T I O N  
In Use Indicator  
Indicates that a hot water  
tap is open. (The setpoint  
temperature cannot be ad-  
justed when indicator is il-  
luminated.)  
Digital Monitor  
Indicates the selected  
water temperature. Error  
messages flash in the  
event of a failure.  
Maintenance Button  
Pressing repeatedly shows  
sequence of error codes  
water heater has experi-  
enced.  
Maintenance  
°F  
M
Set Temperature  
In Use  
C
Thermostat  
Increase or decrease  
the desired water  
temperature.  
Main Controller  
MCC - 45 - 3US  
H
endless hot water system  
CAUTION: Hotter water increases the risk  
of scald injury. Before changing tempera-  
ture setting, see instruction manual  
When the Main Controller MCC-45-3US is used in public use applications,  
it should be installed where it can not be adjusted by the public (i.e. a  
maintenance room or manager’s office.  
DIAGNOSTIC USE OF REMOTE CONTROL  
1. To Display Error Codes -- Press Maintenance Button, “M”. To sequence  
throuh stored error codes, press “M” followed by the “H” thermostat button.  
2. To Display Water Flow through water heater -- Press “H” thermostat but-  
ton, hold for 2 seconds and simultaneously press “M” button.  
3. To Display Outlet Water Temperature -- Press “C” thermostat button, hold  
for 2 seconds and simultaneously press “M” button.  
1 2  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E R R O R  
M E S S A G E S  
The Continuum 2424WC has the ability to check its own operation continuously. If a fault oc-  
curs, an Error Message will flash on the Digital Monitor of the Remote Controls. This assists  
with diagnosing the fault, and may enable you to overcome a problem without a service call.  
Please quote the code displayed when inquiring about service.  
NOTE: Failure to remedy faults may result in severe burns, scalds, and/or death.  
Fault  
Remedy  
Code  
Displayed  
10  
Check that nothing is blocking  
the air intake or exhaust.  
Air Supply or Exhaust Blockage  
11  
12  
Check that the gas is turned  
on at the water heater, gas  
meter or cylinder.  
No Ignition  
Check that the gas is turned  
on at the water heater and gas  
meter. Check for obstructions  
in flue outlet.  
Flame Failure  
Earthing Failure  
Remaining Flame Safety Device  
Over Temperature Warning  
Service Call  
Service Call  
Service Call  
14  
16  
31  
Heat Exchanger Incoming Water  
Temperature Sensor Faulty  
Outgoing Water Temperature Sensor Faulty  
Mod. Solenoid Valve Answer Abnormal  
Combustion Fan Failure  
Service Call  
Service Call  
Service Call  
Service Call  
Service Call  
Service Call  
32  
52  
61  
71  
72  
LC  
Solenoid Valve Driving Circuit Faulty  
Flame Sensing Device Faulty  
Scale build-up in Heat Exchanger  
Model 2424WC  
1 3  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE & SERVICE INFORMATION  
Warning: Always turn off the electrical power supply, the manual gas valve  
and the manual water control valve whenever servicing the unit.  
The Continuum 2424WC should be checked by a Rinnai Certified  
Technician once a year. A Rinnai Certified Technician should  
perform any repairs that may be necessary.  
The following items should be checked each inspection:  
1) The area around the Continuum 2424WC unit should be free from combustible  
materials such as cloth, vegetation and building materials. (see page 9)  
2) Check burners for presence of foreign debris.  
3) Remove and clean the inlet water filter.  
4) Keep the appliance area clear and free from combustible materials, gasoline, and other  
flammable vapors and liquids.  
5) Do not obstruct flow of combustion and ventilation air.  
In the case of any fault or error message from the Continuum 2424WC, first  
turn all hot water taps off. Wait for 5 seconds. Turn the hot water tap back on. If  
this does not correct the fault or eliminate the error message from the remote  
control, press the priority button on and off twice to reset the system. If the error  
message still remains, call your Rinnai Authorized Service Representative or Rinnai  
at 800-621-9419.  
Should overheating occur or the gas supply fail to shutoff, turn off the  
manual gas control valve to the appliance.  
DO NOT ATTEMPT TO SERVICE YOUR Continuum 2424WC YOURSELF.  
Call a Rinnai Authorized Service Technician or call Rinnai at 800-621-9419.  
1 4  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE & SERVICE INFORMATION  
MAINTENANCE SUGGESTIONS  
This water heater has been designed and constructed  
for a long performance life when installed and operated  
properly under normal conditions. Regular inspections,  
as outlined in this section, are strongly recommended  
as a means of keeping your heater operating efficiently.  
1. Cleaning  
The water heater must be cleaned annually.  
Keep the water heater clear of dust and debris  
especially in and around burner.  
Cleaning procedures for the Continuum are as  
follows:  
1) Turn off and disconnect electrical power. Allow  
to cool for one hour.  
2) Remove the Front Panel by removing screws.  
See parts breakdown on panels.  
3) Use pressurized air to remove dust from around  
main burner.  
4) Use soft dry cloth to wipe cabinet.  
DO NOT DAMAGE OR DISTORT ANY  
PARTS OF HEATER.  
* VENT MAINTENANCE  
* VENT SYSTEM  
Must be checked annually for  
blockage or deterioration.  
DO NOT USE WET CLOTH OR  
SPRAY CLEANERS ON BURNER.  
* MAINTENANCE-  
ELECTRIC MOTORS  
Motors are permanently lubri-  
cated and need no lubrication.  
Keep fan and motor free of  
dust and dirt, clean annually.  
2. Visual check of main burner flames.  
The burner must flame evenly over the entire sur-  
face when operating correctly. The flame must burn  
with a clear, blue, stable flame. See the parts  
breakdown of the burner for the location of view  
ports. Any and all parts removed for inspection or  
service must be replaced before operating the unit.  
The flame pattern should be as shown in the fol-  
lowing Figures.  
Model 2424WC  
1 5  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLE SHOOTING AND COMMON QUESTIONS  
- I don't have any hot water when I open the tap!  
Q
A - Make sure there is gas and electricity to the Continuum 2424WC.  
(the power is turned on and the gas is turned on)  
- When I was using the hot water, the water got cold!  
Q
A - If you adjusted the flow from the tap to lessen it, you may have gone  
below the minimum flow required. The Continuum 2424WC requires .6  
GPM to operate. If you mix the water with a tap and attempt to get a  
temperature well below the temperature being controlled by the unit, it  
may drop the flow below .6 GPM. Decrease the temperature supplied  
by the Continuum 2424WC at the remote control or increase your  
total flow.  
- White smoke comes out of the exhaust!  
Q
A - During colder weather when the exhaust temperature is hotter than  
the air, the exhaust fumes condense producing white steam.  
- When I open a hot tap. I do not immediately get hot water!  
Q
A - Hot water must travel through your plumbing from the Continuum  
2424WC to the faucet. This can take from 2 to 10 or more seconds  
depending upon your plumbing system.  
- After I turn off the hot water tap, the fan on the Continuum 2424WC  
Q
continues to run!  
A - The fan is designed to be on for 65 seconds after the flow of water  
stops.This is to ensure constant water temperatures during rapid start-  
ing and stopping, as well as exhausting any residual gas flue prod-  
ucts from the unit.  
1 6  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR YOUR SAFETY READ BEFORE OPERATING  
Warning: If you do not follow these instructions exactly, a fire or explosion  
may result causing property damage, personal injury or loss of life.  
A. This appliance is equipped with a direct igni-  
tion device which automatically lights the  
If you cannot reach your gas supplier, call  
the fire department.  
burner. Do not try to light the burner by hand.  
C. Use only your hand to operate remote con-  
trol keypad. Do not use tools. Force or  
attempted repair may result in a fire or ex-  
plosion. If the remote keypad doesn’t work,  
call a qualified service technician.  
B. BEFORE OPERATING: Smell all around  
the appliance area for gas. Be sure to  
smell below the unit because some gas is  
heavier than air and will settle to the  
ground.  
D. Do not use this appliance if any part has  
been under water. Immediately call a quali-  
fied service technician to inspect the appli-  
ance and to replace any part of the control  
system and any gas control which has been  
under water.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Do not touch any electric switch, do not  
use any phone in your building.  
Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas  
supplier’s instructions.  
O P E R A T I N G  
I N S T R U C T I O N S  
1) STOP! Read the safety information above  
before proceeding.  
Closed manual valve  
(“OFF” position)  
2) Set the thermostat to lowest setting.  
3) Turn off all electric power to the appliance.  
Open Manual valve  
(“ON” position)  
4) This appliance is equipped with a direct igni-  
tion device which automatically lights the  
burner. Do not try to light the burner by hand.  
6) Wait (5) minutes to clear out any gas. If  
you then smell gas, STOP! Follow “B” in  
the safety information above on this label.  
If you don’t smell gas, go to next step.  
5) Turn the manual valve located at gas  
inlet of the appliance clockwise  
to “OFF”.  
Model 2424WC  
1 7  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR YOUR SAFETY READ BEFORE OPERATING  
7) Turn the manual valve located at the gas  
9) Set thermostat to desired setting.  
inlet of appliance counterclockwise  
to “ON”.  
10) If the appliance will not operate,  
Follow the instructions “To Turn Off  
Gas To Appliance” and call your  
service technician or gas supplier.  
8) Turn on all electric power to the appliance.  
To Turn Off Gas To Appliance  
1) Set the thermostat to lowest setting.  
2) Turn off all electric power to the appliance if service is to be performed.  
3) Turn the manual valve at gas inlet of appliance clockwise to “OFF”  
C A R E & L I M E C O N D I T I O N W A R N I N G  
Care of Unit’s Exterior:  
Keep the exterior cabinet clean. Use a soft cloth and warm water when cleaning the cabinet.  
Do Not use volatile substances such as benzene and thinners, as they may ignite, or cause  
fading of the paint.  
Lime Condition Warning Signal:  
If you notice “LC” flashing on the remote key pad, this means the unit is beginning to lime up,  
and MUST be flushed. Contact a qualified Rinnai service technician to flush the appliance.  
Failure to flush the appliance when “LC” is flashing, will cause damage to the heat exchanger.  
Damage caused by lime build up is not covered by the unit’s warranty.  
1 8  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Instructions  
This section is for the Rinnai Certified  
Installer only. If you are not certified  
you are not authorized to install this  
unit. The warranty may be voided due to  
installation by a non-certified installer. For  
information on becoming a Rinnai Certified  
Installer, call  
1-800-621-9419.  
Warnings....................................................20  
Performance Data..........................................21  
Locating the Unit.........................................22  
Dimensions.................................................22  
Recommended Piping for Installation........23  
Power Failure Freeze Protection..................24  
Gas Piping Sizing Charts.............................27  
Gas Piping Notes.........................................28  
Water Piping Notes......................................29  
Pressure Relief Valve................................29  
Electrical Connection Notes.........................30  
Wiring Diagram........................................30,32  
Lighting the Unit.........................................33  
Remote Controls.....................................34,35  
Testing........................................................36  
Diagnostic Points.......................................37  
Schematic Diagram.....................................38  
Exploded View..................................39-42  
Parts List..............................................43-47  
Contents  
of Installer’s  
Manual  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
-Warnings-  
This manual must be followed exactly.  
1) Read the safety issues completely before installing the Continuum 2424WC.  
2) This water heater is suitable for water (potable) heating or space heating.  
- The piping connected to the Continuum 2424WC must be approved for use in  
potable water systems.  
- Toxic chemicals such as those used for boiler water treatment are NOT to be  
introduced to the Continuum 2424WC.  
- The Continuum 2424WC, if it will be used as a potable water source, it must  
not be connected to a system that was previously used with a nonpotable  
water heating appliance.  
3) The Continuum 2424WC is not suitable for use as a pool or spa heater.  
4) The dip switches on the computer board have been preset at the factory and  
should not be readjusted without the express knowledge and involvement of  
Rinnai.  
5) Install the Continuum 2424WC outdoors only.  
6) Maintain proper space around the unit for proper servicing and operation.  
Minimum clearances from combustible materials are listed below.  
Top of Heater  
Back of Heater  
12 inches  
0 inch  
Front of Heater 24 inches  
Sides of Heater  
Ground  
6 inches  
12 inches  
DO NOT install the Continuum 2424WC under an overhang less than 3 feet  
from the top of the unit. The area under any overhang greater than 3 feet  
must be open on three sides.  
7) Installer must install a Pressure relief valve. Pipe pressure relief discharge to a  
drain or outside environment (see page 29).  
2 0  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
C O N T I N U U M O U T L E T F L O W D A T A  
INSTALLER’S INSTALLATION INSTRUCTIONS  
CONTINUUM PRESSURE DROP CURVE  
Model 2424WC  
2 1  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Locating the unit  
Eve, porche,  
or overhang  
C
A
Flue  
Continuum 2424WC  
C/L  
B
D
Window  
Door  
Vent termination clearances  
Minimum  
A.......Vertically below an openable window........................................................12”  
B.......Vertically above an openable window, door, etc.........................................12”  
C.......Below eves, porches, overhangs..............................................................36”  
D.......Horizontally from an openable window, door, etc.......................................12”  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Dimensions  
6 3/4  
13 3/4  
3
Height 23 /4 ”  
Side  
View  
Front  
View  
3
Width 13 /4 ”  
3
1 7/8”  
(Power)  
Depth  
6 /4 ”  
4 1/8”  
(Hot)  
3 7/16”  
(Gas)  
2 2  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RECOMMENDED PIPING FOR INSTALLATION  
Model 2424WC  
2 3  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
OPTIONAL:Power Failure Freeze Protection  
2 4  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
INSTALLATION WITH RECIRCULATION (i.e. Hair Salons, Restaurants, etc.)  
Model 2424WC  
2 5  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
BACKUP STORAGE INSTALLATIONS (i.e. Hotels, motels and other high flow applications)  
2 6  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Gas Pipe Sizing Chart  
Capacity Table for Natural Gas  
cubic feet / hour  
(table assumes .3 inch pressure drop, specific gravity of .60)  
Length of Pipe in Feet  
Nominal  
Iron Pipe  
Size  
Inches  
10  
20  
30  
40  
50  
60  
70  
96  
80  
90  
90 100 125 150 175 200  
84 79 72 64 59 55  
3/4  
1
278 190 152 130 115 105  
520 350 285 245 215 195 180 170 160 150 130 120 110 100  
1-1/4 1050 730 590 500 440 400 370 350 320 305 275 250 225 210  
1-1/2 1600 1100 890 760 670 610 560 530 490 460 410 380 350 320  
After determining the length of pipe required select the pipe size that will supply the  
cubic feet per hour of gas required for the input rating of the Continuum 2424WC.  
The formula for figuring the cubic feet per hour required is:  
Gas Input of Continuum 2424(BTU/HR)  
CFH =  
Heating Value of Gas(BTU/FT3)  
*Gas input requirement is on the water heater data plate  
*The heating value of the gas can be obtained from the local Natural Gas Utility  
Capacity Table for LP Gas  
BTUH of undiluted liquified petroleum gases  
(table assumes 11 inches of water column pressure at the inlet, .5 inch drop)  
Nominal  
Iron Pipe  
Size  
Length of Pipe in Feet  
Inches  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100 125 150  
1/2  
3/4  
1
275 189 152 129  
567 393 315 267 237 217 196 185 173  
1071 732 590 504 448 409 378 346 322  
162 146  
307 275 252  
630 567 511  
1-1/4 2205 1496 1212 1039 913 834 771 724 677  
Model 2424WC  
2 7  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Gas Piping Notes  
1) A manual gas control valve must be placed upon the gas inlet connection to the  
Continuum 2424WC before it is connected to the gas line. A union can be used on  
the connection of the Continuum for the future servicing or disconnection of the  
unit.  
2) Check the type of gas and the gas inlet pressure before connecting the Continuum  
2424WC. If the Continuum 2424WC is not of the gas type that the building is sup-  
plied with, DO NOT connect the water heater. Contact the dealer for the proper unit  
to match the gas type.  
3) Minimum and Maximum Gas pressures are listed below:  
* Minimum value is for input adjustment  
Natural Gas:  
Minimum 7" WC  
Maximum 10.5" WC  
Propane Gas:  
Minimum 10"WC  
Maximum 14" WC  
WARNING: Conversion of this unit from natural gas to propane or propane to  
natural gas CANNOT be done in the field.  
4) Always use approved connectors to connect the unit to the gas line. Always purge  
the gas line of any debris before connection to the water heater.  
5) The Continuum 2424WC must be leak tested before it is placed into operation.  
6) After completion of gas pipe connections, all joints including the heater must be  
checked for gas-tightness by means of leak detector solution, soap and water, or an  
equivalent nonflammable solution, as applicable. Caution: Since some leak test  
solutions, including soap and water, may cause corrosion or stress cracking, the  
piping must be rinsed with water after testing, unless it has been determined that  
the leak solution is non-corrosive.  
7) The Continuum 2424WC and its individual shut-off valve must be disconnected  
from the gas supply piping system when pressure testing of the gas supply  
piping system at test pressures equal to or greater than 1/2 psi.  
8) The Continuum 2424WC must be isolated from the gas supply piping system  
by closing it's individual manual shutoff valve during any pressure testing of  
the gas supply piping system at test pressures less than 1/2 psi.  
9) The Continuum 2424WC's Installation location must provide adequate Combustion  
and Ventilation airflow.  
2 8  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Water Piping Notes  
1) A manual water control valve must be placed upon the water inlet connection to the  
Continuum 2424WC before it is connected to the water line. Unions may be used on  
both the hot/cold water supply lines, for the future servicing or disconnection of the unit.  
2) All soldering materials and piping must be compatible with potable water.  
3) Purge the water line to remove from it all debris and air. Debris will damage the  
Continuum 2424WC.  
4) There is a wire mesh strainer on the Continuum 2424WC's inlet to discourage the  
introduction of debris to the unit. It will need to be cleaned periodically.  
DO NOT operate unit without filter in place.  
WARNING: DO NOT reverse the inlet and outlet (cold and hot water) connections on  
the unit. This would cause the Continuum 2424WCto operate dangerously or not at  
all.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Pressure Relief Valve  
1) ANSI code calls for the addition of an approved pressure relief valve to all water  
heating systems.  
2) The pressure relief valve must meet the following criteria: The relief valve must  
comply with the standard for Relief Valves and Automatic Gas Shutoff Devices for  
Hot Water Supply Systems ANSI Z21. 22. This relief valve must be rated at 150  
PSI of pressure.  
3) The relief valve should be added to the hot water outlet line per manufacturer's  
instructions. DO NOT place any other type valve or shut off device between the  
relief valve and the hot water heater.  
4) The discharge from the pressure relief valve should be piped to the ground or into a  
drain system to prevent exposure or possible burn hazards to humans or other plant  
or animal life. Water discharged from the relief valve could cause severe burns  
instantly, scalds and/or death.  
5) Do not plug the relief valve and do not install any reducing fittings or other restric-  
tions in the relief line. The relief line should allow for complete drainage of the  
valve and the line.  
6) Pressure relief valve must be manually operated once a year to check for correct  
operation.  
7) Should overheating occur or the gas supply fail to shut off, turn off the manual gas  
valve on the Continuum 2424WC.  
Model 2424WC  
2 9  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Electrical Connection Notes  
WARNING: The Continuum 2424WC must be electrically grounded in accor-  
dance with local codes or in the absence of local codes with the most re-  
cent edition of the National Electrical Code, ANSI/NFPA 70. In Canada, all  
electrical wiring to the Continuum 2424WC should be in accordance with  
local codes and the Canadian Electrical Code, CSA C22.1 Part1. Do not rely  
on the gas or water piping to ground the metal parts of the water heater.  
CAUTION: Label all wires prior to disconnection when servicing controls.  
Wiring errors can cause improper and dangerous operation. Verify correct  
operation after servicing.  
1 The Continuum 2424WC requires 120VAC/60 HZ. Power from a properly  
grounded circuit, GFI.  
2 An on/off switch must be provided and installed for the incoming 120VAC  
power.  
3 Wire the Continuum 2424WC exactly as shown in the wiring diagram on the  
next page and on the inside of the cover panel. The blue wire is the hot leg  
wire; the brown wire is the neutral wire.  
4 A green screw is provided in the junction box for the grounding connection.  
Ground  
ON/OFF  
Your disconnect switch should be a type that is suitable for  
outdoor use. Check National Electrical Codes for proper type  
switch to use in your area.  
3 0  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Wiring Diagram  
Model 2424WC  
3 1  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Wiring Diagram  
3 2  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Lighting the Unit  
WARNING: If you do not follow these instructions exactly, a fire or  
explosion may result causing property damage, personal injury or loss  
of life.  
1) This water heater does not have a pilot. It is equipped with a direct ignition  
device which automatically lights the burner. DO NOT TRY TO LIGHT THE  
BURNER BY HAND.  
2) Before operating the Continuum 2424WC smell all around the unit for gas. Be  
sure to smell near the ground as leaking gas may settle there.  
3) Turn the manual gas control valve on.  
STOP!! READ THE SAFETY ISSUES ON PAGES 8 & 9  
4) Turn on any hot water tap. The Continuum 2424WC should light and begin  
heating your water.  
If the Continuum 2424WCfails to light  
1) DO NOT ATTEMPT TO LIGHT BY HAND.  
2) Turn off the electrical power to the unit.  
3) Turn off the manual gas control.  
4) Wait 5 minutes, if you smell gas, go to a neighbor's house and call the gas  
company or the fire department. If you do not smell gas, go to the next step.  
5) Turn the manual gas control valve on.  
6) Turn the electrical power to the unit on.  
7) Turn on any hot water tap.  
8) If the unit still fails to light, turn off the electricity and gas to the unit and call  
Rinnai 1-800-621-9419.  
Model 2424WC  
3 3  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Remote Controls- General  
The remote control for the Continuum 2424WC allows the customer to control the  
functions of the water heater and to diagnose certain fault conditions.  
The Main Controller model MCC-45-3US is intended to be installed in the kitchen  
or laundry area where the majority of the hot water is being used.  
NOTE: The MC-45-3US has a temperature setpoint range of 140-180°F. Other  
setpoint temperatures must be set through dip switch settings, Contact  
Rinnai at 800-621-9419 for dip switch settings.  
Before installing the remote control, determine the most convenient location. When  
deciding on the best location for the remote controls, please consider the following  
items:  
1) Place the controllers out of the reach of small children or unauthorised users.  
2) Avoid locations where the controller will become hot. (over a stove, near an  
oven or a radiant heater.  
3) Avoid direct sunlight. (The digital monitor can be difficult to read in direct  
sunlight)  
4) Avoid areas where the remote can be splashed with cooking water, oil or  
sauce.  
5) The remote control cables carry low voltage, 12VDC digital.  
NOTE: Only one controller can be connected to one Continuum 2424WC water  
heater. (i.e. Installations with two controllers will not function properly.)  
3 4  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S  
INSTALLATION  
INSTRUCTIONS  
Remote Controls - Installation  
outline of remote  
securing screw  
1) Determine a suitable location for the  
control.  
1 1/16”  
wire hole  
(21/32” dia.)  
3 1/4”  
2) Make three holes on the wall as shown.  
securing screw  
3) Run the cable between the control and  
the Continuum 2424WC or the control  
and the other control.  
Note: Remote Control Dimensions are:  
4 3/4” H x 4 3/4 W” x 1” D  
4) Remove the face plate from the remote control, using a screw driver.  
5) Connect the cable to the remote control.  
6) Mount the control to the wall using the holes drilled in step 2.  
Note: If the cable cannot be run in the wall cavity, the plastic knockout should be re-  
moved from the top or bottom of the control to allow flush mounting with the wall  
7) Disconnect the power from the Continuum 2424WC.  
8) Remove the cover of the Continuum 2424WC.  
9) Remove the plastic cover from the PCB and electrical connections.  
DO NOT ATTEMPT TO CONNECT THE REMOTE CON-  
TROLS WITH THE POWER ON, THERE'S 120 VOLT PO-  
TENTIAL, NEXT TO THE REMOTE CONTROL CONNEC-  
TIONS INSIDE THE UNIT. All service and wiring should be  
performed by a certified installer.  
TERMINAL  
10) Thread the cable through the access hole at the  
CLAMP  
base of the unit and connect the wires to the con-  
trol terminals on the right hand side bottom of the  
PCB. Note: Connect remote control cable to  
location labeled “TERMINAL” in the drawing at  
right.  
11) Secure the control cable using the clamp provided.  
12) Replace plastic cover over PCB and then replace  
the cover of the Continuum 2424WC.  
Model 2424WC  
3 5  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Testing  
1) Turn on the gas and water.  
2) Check for water and gas leaks. Use soapy water to test for gas leaks.  
3) Remove pressure test point screw, attach pressure gauge to test point.  
4) Turn Power on.  
5) Open any hot water tap fully.  
6) Check test point or supply pressure in water columns per inch.  
Manifold Pressure:  
Supply pressure:  
Natural Gas 5.3" Hi. fire  
0.43" Lo. fire Natural Gas Min. 7" Max. 10.5"  
LPG  
8.7" Hi. fire  
0.59" Lo. fire LPG  
Min. 10" Max. 14"  
NOTE: The pressure may be low due to too little flow, too high an incoming tempera-  
ture, and/or undersized gas piping. Examine these areas before determining that  
the pressure needs to be adjusted. Contact Rinnai before adjusting manifold  
pressures at 1-800-621-9419. Failure to contact Rinnai, could void unit’s  
warranty.  
7) If it is determined that the gas pressure needs adjusting, first check the in  
coming pressure at the test point on the gas inlet. If it is correct follow the  
adjusting procedure contained in the pouch of the unit EXACTLY. If in doubt  
call Rinnai 1-800-621-9419.  
The regulator is pre-set at the factory, it should not need resetting.  
8) Turn the hot water off. Turn the power off. Remove the pressure guage and  
replace the test point screw. Check for a gas leak around the test point  
screw.  
9) Replace the front cover.  
10) Turn the power back on.  
11) Check the operation of the unit. Check the operation of each of the remote  
controls. Check the operation of the Power failure protection system.  
12) Explain the proper operation of the Continuum 2424WC to the customer.  
3 6  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Diagnostic Points  
Flow  
Chart  
N0  
Measurement Point  
Normal Value  
Component  
Con N0  
Wire Color  
1
2
J4  
Brown - Blue  
AC 108 - 132 V  
DC 11 - 13 V  
DC 11 - 13 V  
DC 2 - 10 V  
DC 2 - 9 V  
Surge Protector  
Remote Control  
H1  
C2  
Black - Black  
Red - Black  
3
Water Flow Sensor  
Yellow - Black  
White - Black  
Red - Yellow  
4
5
D
Combustion Fan Motor  
Flame Rod  
60 - 350 Hz  
AC 100 - 160 V  
(over DC 1µA)  
A2  
Yellow - Cabinet Ground  
Thermistor resistance value  
Temp  
15°C  
30°C  
45°C  
60°C  
105°C  
Resistance  
11.4 - 14.0 KΩ  
6.4 - 7.8 KΩ  
3.6 - 4.5 KΩ  
2.2 - 2.7 KΩ  
0.6 - 0.8 KΩ  
6
C1  
White - White  
Thermistor  
7
8
9
B2  
B3  
I4  
Red - Red  
Red - Red  
Grey - Grey  
Below 1Ω  
Thermal Fuse  
Over-heat Switch  
Ignitor  
Below 1Ω  
AC 90 - 110 V  
DC 80 - 100 V  
1.3 - 1.6 KΩ  
10  
11  
12  
13  
14  
I1  
Pink - Black  
Yellow - Black  
Pink - Pink  
Solenoid Valve (SV1)  
Solenoid Valve (SV2)  
Modulating Valve  
Solenoid Valve (SV3)  
Geared Motor  
DC 80 - 100 V  
1.7 - 2.1 KΩ  
I2  
DC 80 - 100 V  
60 - 100 Ω  
B1  
I3  
DC 80 - 100 V  
1.7 - 2.1 KΩ  
Blue - Black  
Red - Blue  
Orange - Grey  
E1  
DC 11 - 13 V  
Connector  
Wire Color  
Nomal Value  
AC 90 - 110 V  
19 - 23  
AC 12 - 16V  
3.6 - 4.8 Ω  
AC 13 - 30V  
0.6 - 0.8 Ω  
AC 30 - 50 V  
2 - 4 Ω  
AC 108 - 132 V  
20 - 24 Ω  
AC 180 - 220 V  
0.23 - 0.3 KΩ  
J
F
A
Red - Black  
A
J5  
A
Brown-Grey  
Green - Green  
Black - White  
Orange - Orange  
Yellow - Brown  
Model 2424WC  
3 7  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Schematic Diagram  
3 8  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Exploded View - Cabinet  
Model 2424WC  
3 9  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Exploded View - Internals  
4 0  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Exploded View - Internals  
Model 2424WC  
4 1  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Exploded View - Electrical  
4 2  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Parts List  
Quantity  
Part Number  
DU195-100-2  
Description  
Casing Assembly  
Number  
1
001  
1
1
2
1
2
1
1
1
1
1
2
1
1
1
1
1
18  
1
1
BU155-110  
DU195-1615-2  
BU195-121  
BU195-167  
AU115-163  
BU169-120  
BU169-125  
BU56-602-N  
AU169-126  
CU195-211-2  
C10D-5  
004  
007  
012  
016  
017  
018  
019  
022  
023  
100  
101  
103  
104  
104  
106  
107  
110  
111  
112  
Heat Protection Plate  
Front Panel Assembly  
Wall Installation Bracket  
Front Panel Packing  
Front Panel Packing - Side  
Connection Reinforcement Panel  
Gas Control Bracket  
Cable Connection  
Cable Seal Packing  
Gas Connection (3/4” NPT)B  
Test Point Screw  
C36E-30-S  
CU195-200-A  
CU195-200-B  
DU195-255  
CU169-257  
B3A1-4  
Gas Control Assembly  
Manifold Assembly - A (LPG)  
Manifold Assembly - B (Nat)  
Burner Case Front  
Sound Proofing Panel  
Side Type Sleeve Burner Assembly  
Burner Case Back Panel  
CU169-256  
CU195-920  
Comb. Chamber Front Panel  
(Complete Assembly)  
1
1
1
CU195-310  
BU195-315  
BU195-316  
113  
114  
Comb, Chamber Front Panel (Assy)  
Upper Packing - Comb. Chamber  
Lower Packing - Comb. Chamber  
115  
Model 2424WC  
4 3  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Parts List  
Number  
Description  
Part Number  
Quantity  
116  
Ignition target  
AU168-325  
1
117  
118  
119  
120  
121  
125  
127  
128  
129  
130  
131  
132  
133  
150  
151  
153  
154  
400  
401  
402  
403  
405  
408  
Electrode  
Flame Rod  
AU168-321  
AU168-322  
AU195-312  
AH43-262  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Electrode Packing  
Electrode Holder  
Electrode Sleeve  
AU102-681  
DU-195-1840  
AU195-330  
AU195-321  
AU195-322  
BU169-470  
BU169-471  
BU169-472  
AU155-111-1  
BU195-565  
BU169-552  
BU169-555  
AU169-656  
H73-511  
Heat Exchanger Complete Assy  
PCB Bracket  
Stop Bracket A  
Stop Bracket B  
Flue Outlet ( Assy)  
Flue Outlet  
Flue Outlet Packing  
Flue Outlet Packing A  
Blower Motor Assy  
Fan Casing Assy A  
Fan Connection  
Fan Connection Packing  
Water Inlet ( 3/4” NPT) B  
Water Filter Assy  
H73-501-2  
M8D1-11  
Rectifier  
Water Flow Servo & Sensor  
120V Anti-Frost Heater  
Hot Water Outlet (3/4”NPT) C  
M8E-4-4  
BU195-1878  
BU132-363-C  
4 4  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Parts List  
Part Number  
Quantity  
Description  
Number  
AU142-445  
1
Plug Band B  
409  
AU142-444  
BU195-601  
BU195-602  
BU195-1877  
BU195-604  
BU195-605  
CU195-1870  
BBF9-630  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
3
1
1
6
2
2
1
1
Drain  
Modulating Solenoid Valve Harness  
Fan Motor Harness  
Sensor Harness  
410  
415  
416  
417  
418  
420  
700  
701  
705  
706  
708  
709  
710  
711  
712  
713  
715  
716  
717  
718  
719  
720  
723  
Water Flow Servo Harness  
Flame Rod Harness  
PCB  
Surge Protector  
BU168-707  
BU195-507  
EI-144  
PCB Front Cover  
PCB Side Cover  
Ignitor  
BH38-710-200  
ET-259  
High Tension Cord  
Transformer  
BU195-1879  
AU195-675  
AU100-721  
BU129-824-2  
CU195-610-2  
CP-80531  
120V Anti-Frost Heater B  
Anti-Frost Heater Clip  
Anti-Frost Heater Clip  
Over Heat Switch  
Thermal Fuse Harness  
Thermal Fuse Clips  
Thermistor  
BH45-650  
CP-90172  
Thermistor Clip  
BU189-530  
BU195-1630  
Frost Sensing Switch  
3 Amp Fuse Harness  
Model 2424WC  
4 5  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Parts List  
Number  
801  
Description  
Screw  
Part Number  
ZBA041OUK  
Quantity  
802  
803  
804  
805  
806  
807  
808  
809  
810  
811  
812  
816  
817  
819  
820  
821  
822  
823  
899  
900  
901  
903  
904  
Screw  
Screw  
ZBA051OUK  
ZEAB0408SZ  
ZBA0408UK  
ZBD0408UK  
ZAD0408UK  
CP-21478-412  
ZEA0408UK  
ZAA0408UK  
ZBA0412UK  
ZAG0512UK  
ZBA0512UK  
ZEDB0408SZ  
CP-80452  
2
1
2
1
1
Screw  
Screw  
Screw  
Screw  
Screw  
Screw  
Screw  
Screw  
Screw  
Screw  
Screw  
Screw  
ZEAB0406UK  
ZIAA0410SZ  
ZAG0514UK  
CF83-41430  
CP-90331  
Screw  
Screw  
Washer  
Tie backs  
“O” Ring (S4)  
“O” Ring (P24)  
Packing  
“O” Ring (P4)  
“O” Ring (P7)  
M10B-13-4  
M10B-1-24  
C36F8-1  
MlOB-2-4  
MlOB-2-7  
4 6  
Model 2424WC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLER’S INSTALLATION INSTRUCTIONS  
Parts List  
Number  
Description  
Part Number  
Quantity  
905  
“O” Ring (P16)  
M10B-2-16  
1
906  
907  
908  
“O” Ring (P12.5)  
“O” Ring (P14)  
M10B-2-12.5  
M10B-2-14  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
“O” Ring (P18)  
M10B-2-18  
Manual 3/4" gas control value  
Remote control kit  
BU195-1865  
MCC-45-3US  
AU195-1680-2  
BU195-1882X01  
AU195-1881  
View Window Sticker  
Continuum Label  
Model Number Label  
Wiring Diagram  
CU195-1887  
AU169-206X02  
CU195-1889-1X03  
CU195-1889-2X03  
CU195-1886X01  
AU195-1890  
Manifold Seal  
Rating Plate (NG)  
Rating Plate (LP)  
Warning Label  
Warning Repair Label  
Gas Type Label (NG)  
Gas Type Label (LP)  
Gas Type Label (Bottom of Unit - NG)  
Gas Type Label (Bottom of Unit - LP)  
CP-71201X01  
CP-71571X01  
CP-71070  
CP-71572  
Model 2424WC  
4 7  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sk about Rinnai’s other fine products:  
A
The Silent Servant  
*North America’s only vent-free convection  
heater  
*99% efficient  
*whisper quiet  
*perfect for hard to heat areas  
The Energy Savers  
*Direct Vent Heating with style and  
performance  
*whisper quiet  
*available with multi-step set back  
thermostats  
The Infra-reds  
*Vent free radiant heaters  
*99.9% efficient  
*Heat like the sun  
Portable Cooking Products  
*One, two and two burner with  
broiler models.  
*Perfect for camping, a picnic or a  
tailgate party  
Printed in Japan 2001.3  
800-621-9419  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Ricoh All in One Printer 3260C User Guide
RocketFish Speaker RF TRSPIPAD User Guide
Rosen Entertainment Systems GPS Receiver GM series User Guide
Rotel Stereo Amplifier RA 06 User Guide
RSA Lighting Indoor Furnishings 500DCS User Guide
Ryobi Saw RJ165V User Guide
Samsung Car Satellite TV System Series 5 User Guide
Samsung DVD Player AK68 00422L User Guide
Samsung Headphones A560 User Guide
Samsung Security Camera 46C User Guide