Omron Sewing Machine DDAA1000 SRM User Manual

USER GUIDE  
DDAA1000/SRM  
Discrete/Analog Wireless Multiplexer  
It is essential that all instructions contained in the User Guide are followed precisely to ensure proper operation of equipment.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Table of Contents  
Page  
Introduction  
3
Discrete Operation  
5
Analog Operation  
8
Changing System or Radio Configurations  
12  
Technical Specifications  
Troubleshooting  
13  
14  
Technical Support  
Return MaterialAuthorization  
Contact Information  
15  
15  
15  
AppendixA  
Enclosure Dimensions  
16  
17  
Appendix B  
System Configuration  
Appendix C  
Radio Configuration  
21  
23  
25  
26  
28  
33  
35  
38  
Main Menu Option (0): Set Operation Mode  
Main Menu Option (1): Set Baud Rate  
Main Menu Option (2): Edit Call Book  
Main Menu Option (3): Edit Radio Transmission Characteristics  
Main Menu Option (4): Show Radio Statistics  
Main Menu Option (5): Edit Multi-Point Parameters  
Main Menu Option (8): Password  
Modem Placement Locations  
39  
PN 161-09981-002C  
1
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Introduction  
The DDAA1000/SRM and DD1000/SRM are discrete/analog signal multiplexers. They are designed to provide increased  
communication distance where wire lengths are too long or not possible. In general, these units behave as if they replace a  
set of wires between the two or more locations. These units are normally factory configured and eliminate the necessity of  
having to preset the system configurations. The units are ready for installation into the system upon receipt. If the system  
changes, these units do have the capability to be field reconfigured and to have access to the radio setup parameters using  
jumper settings and a serial cable to a PC.  
Two version of the product exist. The DDAA1000/SRM has both analog and discreet inputs and outputs. The DD1000/SRM  
has only the discrete inputs and outputs. Discrete (digital) connections and operations are the same for both of the models.  
Only the DDAA1000 has 4-20 mA inputs and outputs. Both the DDAA1000/SRM and the DD1000/SRM have distinct  
master and remote units. Each system must have one and only one master, and can up to 8 Remotes.  
Both the DDAA1000 and the DD1000 take an input at one end and reproduce it at the other end. The Master unit has a  
possible total of 8 discrete inputs, 8 discrete relay drive outputs. The Master has eight 4-20 mA inputs and eight 4-20 mA  
outputs. When designing a system that use these units, keep in mind that if using more than one remote (8 possible) that  
the Master unit can never have more that 8 digital-in, 8 digital-out, 8 analog-in, and 8 analog-out.  
Communication is accomplished using radio transmissions. A six inch unity gain whip antenna is supplied with each unit  
for test purposes. Note that line of sight is required for communications. In some instances, under 1/2 mile (.80 km), line of  
sight may not be necessary. If line of sight does not exist or the units are to be mounted into grounded metal enclosures,  
an external antenna may be needed. If external antennas were not purchased with this equipment, contact Data-Linc Group  
for information.  
Figure 1: DDAA1000 and DD1000  
8
7
6
5
4
3
2
1
G
8
7
6
5
4
3
2
1
G
Contact Closure Input  
Contact Closure Output  
Status  
CD  
Tx  
Rx  
Power  
(425) 882-2206  
DDAA1000/SRM/M  
Pwr  
4-20mA Output  
4-20mA Input  
G
1
2
3
4
5
6
7
8
G
1
2
3
4
5
6
7
8
PN 161-09981-002C  
rev 8/04  
3
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Table 1: LED Description  
CD  
Tx  
Carrier Detect LED. When the units have established an RF Link this LED will be on solid.  
Transmit LED. Will flash when the unit is sendng data to the receiving unit.  
Receive LED. Flashes when receiving data being sent by transmitting unit.  
Power LED. Flashes on solid when unit has power applied.  
Rx  
Pwr  
The status LED will be off when communication is working properly. LED flashes or stays on  
steadily when a communication problem exists. (Master unit only)  
Status  
Figure 2: Normal User Connection  
Power  
Antenna  
Antenna Connectoin Type  
Thread Type  
Standard Thread  
Female  
Gender  
Connector  
SMA  
Power Connector  
Dimensions of Post  
Dimensions of Hole  
Polarity  
2 mm  
6.5 mm  
Center Pin Positive  
12VDC Nominal , 10.5-18VDC  
160mA Idle, 660mA Peak on Transmit  
Voltage  
Current  
Teminal Block  
Wire Size  
12-26 AWG  
PN 161-09981-002C  
rev 8/04  
4
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Discrete Operation  
Requirements  
1. The outputs of the units cannot directly drive a relay. The digital outputs are open collector current sinking to the  
common ground. An external power supply must be used to provide DC power to any relays.  
2. The maximum voltage on the relay driver outputs is 24 VDC.  
3. Ensure that the pull up voltage is sufficient for your relay. i.e. a 12 VDC relay needs 12 VDC, a 24 VDC relay needs 24  
VDC.  
4. Each digital output can sink up to 100 mA for the purpose of controlling the relay coil.  
5. If driving inductive loads, place a voltage suppression diode across the relay coil.  
6. There is one common ground for all input and output connections.  
Connections  
The discrete connection to the device is made via the terminals labeled Contact Closure Input” and  
“Contact Closure Output.” The digital input expects a dry contact, such as a switch or even just a jumper wire.  
The output is open collector. The following diagram illustrates the output drive circuit connection for a discrete unit.  
Figure 3: Simplified Open Collector  
Customer  
Supplied  
Relay  
Output  
1,2,3...,8  
DDAA1000  
Output  
Common  
PN 161-09981-002C  
5
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Point-to-Point Discrete Operation  
The following illustrates an example of a point-to-point discrete system. The “Contact Closure Input” may be as simple as a  
bare wire or be connected to an output of an I/O module. This is an example of turning a lamp at the Master unit by closing  
a contact at the Remote unit using a discrete output.  
Point-to-point discrete operations are bi-directional.An input on the Remote will activate same numbered output on the  
Master. A contact closure on an input of the Master will close the output on the Remote on the same contact.  
Figure 4: Point-to-Point Discrete Operation Example  
DC Supply  
+
-
Dry Contact Closure  
8
7
6
5
4
3
2
1
G
8
7
6
5
4
3
2
1
G
8
7
6
5
4
3
2
1
G
8
7
6
5
4
3
2
1
G
Contact Closure Input  
Contact Closure Output  
Contact Closure Input  
Contact Closure Output  
Master  
Remote  
PN 161-09981-002C  
rev 8/04  
6
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Point-to-Multipoint Discrete Operation  
A multipoint system will involve two or more remote locations, which may be transmitting contact input information,  
providing discrete outputs or both. The following is an example of a multipoint configuration.  
In this example, the Master is transmitting a contact closure input to both Remotes. Note that input #1 on the Master will  
trigger the same numbered output on all Remote units at the same time.  
Since there are more remote inputs than master outputs, the contact closures at the Remote inputs are ‘OR’d at the  
Masters outputs. The closure of any Remote input will cause the Master output to be On (sinking current). If any Remote  
input is closed the Master output will be On for that position. For the Master output to be Off, all Remote inputs must be  
open (Off).  
Figure 5: Point-to-Multipoint Discrete Operation Example  
DC Supply  
+
-
8
7
6
5
4
3
2
1
G
8
7
6
5
4
3
2
1
G
Contact Closure Input  
Contact Closure Output  
Dry Contact Closure  
Remote 0  
8
7
6
5
4
3
2
1
G
8
7
6
5
4
3
2
1
G
Contact Closure Input  
Contact Closure Output  
DC Supply  
+
-
Master  
8
7
6
5
4
3
2
1
G
8
7
6
5
4
3
2
1
G
Contact Closure Input  
Contact Closure Output  
Remote 1  
PN 161-09981-002C  
rev 8/04  
7
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Analog Operation  
Specifications  
1. This unit does not provide loop power to devices.  
2. The outputs can operate on loops with a maximum total resistance of 300 ohms.  
3. The resolution of this unit is 8 bits with accuracy of 2%.  
4. All inputs use a common ground connection labeled “G”.  
5. This system is not designed to replace PLCs.  
6. It is not recommended to use this product with PLC applications.  
7. The input signal must be a 4-20 mA signal.  
Point-to-Point Analog System  
These units are bi-directional, they send and receive analog information both directions. The following is a common example  
of analog use for the DDAA1000/SRM units. Again, the Master’s input corresponds to the same numbered output on the  
Remote and vice versa. The 8 Master inputs match the 8 Remote outputs and the 8 Remote inputs match the 8 Master  
outputs.  
Figure 6: Point-to-Point Analog Example  
Master  
Remote  
Pwr  
Pwr  
4-20mA Output  
4-20mA Output  
4-20mA Input  
4-20mA Input  
G
1
2
3
4
5
6
7
8
G
1
2
3
4
5
6
7
8
G
1
2
3
4
5
6
7
8
G
1
2
3
4
5
6
7
8
13.7  
mA  
Sensor  
with 4 -20 mA  
Output  
mA  
Note: Aloop power supply may be  
needed. The DDAA1000 unites do not  
supply loop power.  
PN 161-09981-002C  
rev 8/04  
8
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Figure 7: Connection of a flow meter to the DDAA1000/SRM unit  
Master or Remote  
Pwr  
4-20mA Output  
4-20mA Input  
G
1
2
3
4
5
6
7
8
G
1
2
3
4
5
6
7
8
B
A
4-20mA Out  
In from Sensor  
Flow Meter  
PN 161-09981-002C  
rev 8/04  
9
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Point-to-Multipoint Analog System  
Unlike the discrete versions, the system must be configured for where specific inputs and outputs are directed. Each unit is  
normally factory configured and designed to interface with the specific system. Alterations to this configuration are possible  
using an accessory cable and jumpers and software provided by Data-Linc Group. Reconfiguring the units requires the  
removal of the cover and uses a custom serial data cable connected to a computer. The reconfiguration of the Master and  
Remotes should normally be left to qualified personnel or performed under Data-Linc Group supervision  
Factory Configuration Process  
At the factory, each remote unit is given an address, which is zero (0) to seven (7). Each unit is then programmed for a  
specific number of analog inputs and outputs, which should to be predetermined prior to sale. Also consider if the system is  
to be expended in the future. Note that any system will have one Master and a maximum of 8 Remotes.  
Limitations of the Configuration Process  
Each master unit has eight analog inputs and eight analog outputs. These inputs and outputs can be spent in a variety of  
ways when configuring a multipoint system. Note that with analog operation, each remote unit’s input corresponds with a  
specific master output. Two remote units cannot share the same inputs and outputs as with the discrete section. The  
following is a sample diagram of a point to multipoint configuration.  
PN 161-09981-002C  
10  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Point-to-Multipoint Analog Operation  
A system is to be built where one analog input exist at one remote and one at another. The maximum possibility of master  
outputs is eight, so this is a valid configuration. Remote 0 being the first remote in the Master’s poll list will be assigned  
Master output one. Remote 1 being next in the poll list will be Master output two.  
Figure 8: Point-to-Multipoint Analog Example  
Remote 0  
Pwr  
4-20mA Output  
4-20mA Input  
G
1
2
3
4
5
6
7
8
G
1
2
3
4
5
6
7
8
Master  
Note:Aloop power supply may be  
needed. The DDAA1000 unites do not  
supply loop power.  
Sensor  
with 4 -20 mA  
Output  
Pwr  
4-20mA Output  
4-20mA Input  
G
1
2
3
4
5
6
7
8
G
1
2
3
4
5
6
7
8
Remote 1  
Pwr  
13.7  
mA  
4-20mA Output  
4-20mA Input  
G
1
2
3
4
5
6
7
8
G
1
2
3
4
5
6
7
8
mA  
Note: Aloop power supply may be  
needed. The DDAA1000 unites do not  
supply loop power.  
Sensor  
with 4 -20 mA  
Output  
*** Systems with only one  
analog input on each remote  
PN 161-09981-002C  
rev 8/04  
11  
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Changing System or Radio Configurations  
To access the system or radio setups the user must remove all connectors from the DDAA1000/SRM or DD1000/SRM,  
then remove the cover and change the jumpers at location P1 and P2, and add a serial data cable (SRM6200E-SLC),  
supplied by Data-Linc Group, to connector P3. These jumper settings must be returned to the RUN/RF settings after  
reconfiguring the system or the radio or the units will not operate. See layout drawing.  
There are 4 configurations of the jumpers.  
1. RUN / RF  
Normal DDAA/1000 and DD1000/SRM operations  
Serial port P3 to PC (computer) to access the radio parameters  
To reprogram the system configuration setup memory  
Factory use only - do not use  
2. CONFIG / RF  
3. CONFIG / PIC  
4. RUN / EXT  
If changing the system configuration go toAppendix B.  
If changing the radio parameters go toAppendix C.  
Figure 9: Layout Drawing  
PN 161-09981-002C  
rev 8/04  
12  
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Technical Specifications  
Channels  
DD1000/SRM has 8 discrete inputs and 8 discrete outputs.  
DDAA1000/SRM has 8 discrete inputs, 8 discrete outputs, 8 analog inputs and 8 analog outputs.  
Channel Specifications  
Analog: 2% accuracy or better with a maximum output load of 300 ohms.  
Discrete: Open collector outputs which can handle up to 24V and can sink up to 100 mA for controlling relay coil.  
Temperature  
32o to 140o F (0o to 60o C)  
Power  
10.5 - 18 VDC. Maximum current draw is 660 mA.  
RF Specifications  
Spread spectrum frequency hopping  
Modulation: GFSK  
Frequency Range: 902-928 MHz  
Channel Spacing: 230.4 kHz  
Error Detection: 32 bit CRC  
Operating Mode: ClassA  
Method of Tuning: Digital Synthesizer  
RF Power: 1 Watt  
Receiver Sensitivity: -110 dBm  
PN 161-09981-002C  
13  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Troubleshooting  
I have the units setup on a bench for testing, but the Master’s status LED keeps flashing or is solid and I do  
not have a carrier.  
When shipped, the units are setup for a maximum transmit power of 1 watt. If there are only a couple feet of separation  
between them, the supplied whip antenna may need to be removed. Note that this will not damage the unit.  
The units are installed in the field, but I have a flashing or solid LED on the status and no carrier.  
The Master’s status LED only comes on when a responce from a remote is not obtained after 3 tries, then the Master  
moves on to the next Remote. A solid light indicates that the Master can not connect to any remotes. A blinking light  
indicates that the Master has lost communication with at least one remote. Most likely problem is a radio line-of-sight  
problem exists If external antennas are being used, verify that they are grounded and that line of sight exists. Also verify  
that the input power is OK. A UPS is recommended in areas where clean power may not exist. If units are bench  
tested, and ther is no communications, then you may have a mis-configured system. If the system has been working  
and then fails, check for cable and antenna connections, and DC power levels.  
The power LED on one or both of my units is out and I have no communication.  
Try cycling power on either of the units, the resettable fuse may have tripped. If communications do not come up again,  
verify that there is power to the device. The supplied wall transformer output is nominally around 18 VDC when the radio  
is not transmitting, and drops to 12 VDC when the transmitter is on. If the supply is okay and cycling power does not  
fix the problem, contact Data-Linc Group.  
My analog output reads 4 mA all the time.  
Verify that the connection of the transducer at the transmitter is okay. Put a milliamp meter in the loop, and verify that  
the connected transducer is supplying more than 4 mA into the unit. Verify that the correct current polarity is used.  
Note that Data-Linc Group unit does not supply loop power.  
My analog output is 0 or below 4 mA.  
Contact Data-Linc Group. The analog output has failed. This is a hardware problem.  
The discrete output will not activate my relay.  
The discrete output of the DDAA1000 or DD1000 does not supply power for a relay coil. Refer to the open collector  
diagram for connections.  
My relay switches on and off constantly.  
Verify that the Master’s status LED does not light. The status LED refers to loss of RF communication data stream.  
Make sure the relay coil does not require more than 100 mA. The discrete outputs can only sink 100 mA.  
The relay never switches.  
Verify that the switch on the input side is wired properly to the DDAA1000 or DD1000. Check the discrete output with a  
multimeter. Set the meter for continuity and place the “+” lead on the “G” or common terminal and “-” on the correct  
discrete output.  
PN 161-09981-002C  
14  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Technical Support  
Data-Linc Group maintains a fully trained staff of service personnel who are capable of providing complete product  
assistance. They can provide you with technical, application and troubleshooting, spare parts and warranty assistance.  
Our technical staff is based in Bellevue, Washington USA and may be reached at (425) 882-2206 or e-mail  
Product Warranty  
Data-Linc Group warrants equipment of its own manufacture to be free from defects in material and workmanship for one  
year from date of shipment to original user. Data-Linc Group will replace or repair, at our option, any part found to be  
defective. Buyer must return any part claimed defective to Data-Linc Group, transportation prepaid.  
Return Material Authorization  
If a part needs to be sent to the factory for repair, contact Data-Linc Group’s corporate office and request a Return Material  
Authorization (RMA) number. The RMAnumber identifies the part and the owner and must be included with the part when  
shipped to the factory.  
Contact Information  
Corporate Office  
Data-Linc Group  
3535 Factoria Blvd. SE  
Suite 100  
Bellevue, Washington 98006 USA  
Telephone: (425) 882-2206  
Fax: (425) 867-0865  
PN 161-09981-002C  
rev 8/04  
15  
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Appendix A  
Enclosure Dimensions  
TOP  
6.85  
5.655  
8
7
6
5
4
3
2
1
G
8
7
6
5
4
3
2
1
G
CONTACT CLOSURE OUTPUT  
CONTACT CLOSURE INPUT  
STATUS  
CD  
Tx  
Rx  
4.80  
approx  
3.935  
POWER  
4.065  
3.18  
DATA-LINC GROUP  
(425) 882-2206  
DDAA1000/SRM/M  
PWR  
4 - 20mA INPUT  
4 - 20mA OUTPUT  
G
1
2
3
4
5
6
7
8
G
1
2
3
4
5
6
7
8
Ø 0.19  
6.35  
SIDE  
1.65  
1.725  
1.80  
PN 161-09981-002C  
rev 8/04  
16  
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Appendix B  
Figure 10: PCB Layout  
DDAA1000 - DD1000 Configuration  
The system configuration parameters are stored in an EEprom memory. This memory can only be changed by the onboard  
microprocessor using serial commands via port P3. The easiest method is to use the Data-Linc Group program provided  
with the master unit, to be run on a PC. If the program is missing contact Data-Linc Group Technical Support.  
A DDAA1000/DD1000 system is normally factory pre-configured. Changes to the system are possible, but it is  
recommended that the user perform this function under direction of Data-Linc Group Technical Support personnel. If the  
utility program is missing, it is possible to change the setting using a PC with a terminal program, but Data-Linc Group help  
must be used as the system setting can be confusing. An internal knowledge of the microprocessor operation is vital to  
understand how to set the system memory. Setting any of the system configuration parameters wrong will make a broken  
system.  
To access the system configurations the user must remove all connectors from the DDAA1000/DD1000, the remove the  
cover, and change a set of jumpers at location P1 and P2 and add a serial data cable (SRM6200E-SLC) available from  
Data-Linc Group to connector P3. See Figure 10, PCB layout drawing. Use the CONFIG-PIC layout as shown on the PCB  
drawing.  
To change the system configuration, set the P1 and P2 jumpers as shown on the layout drawing. Use the CONFIG-RF  
layout as shown on the PCB drawing. The dark lines represent the three small jumpers. Then insert the Data-Linc Group  
serial cable into connector P3 located next to the power connector. Attach the serial cable to a PC.  
Remember that there are two different part numbers for Masters and Remotes. They contain different firmware. AMaster  
cannot be made into a Remote, and a Remote cannot be made into a Master. However, either a Master or Remote can  
have the ability to reprogram an EEprom from either a Master or Remote. This involves removing and replacing the EEprom  
(U3) on the PCB. Not recommended for most users.  
PN 161-09981-002C  
17  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
If you have the Data-Linc Group PC program DDAAEEprom.exe it is designed to run in Windows. Load the program  
DDAAEEprom.exe into your PC. Start the program. When the system layout window appears fill in the following  
information:  
1. Select Model DDAA or DD1000 with mouse click.  
2. The PCs Comm (serial port) number 1 or 2 with a mouse click.  
3. The serial Baud rate that the DDAA1000/DD1000 uses to talk to the radio module. This is not the connection speed to  
the computer. This must match the Baud rate set in the radio module. The factory default for the radio module is 9600.  
4. Select System Configuration as either a Point-to-Point (one remote) or a Multipoint system (more than one remote) with  
mouse click.  
5. Select this unit is a Master or a Remote. This must agree with the code in the microprocessor. You can not change a  
units Master/Remote type in the field.  
6. The number of remotes if a Multipoint System.  
7. If programming a Multipoint Remote select Remote ID or address you are changing. Remotes have addresses of zero(0)  
to seven(7).  
If the unit is a DD1000 click on the “Make an EEprom” button and follow the prompting instructions on the screen. . If any  
previous setting are in conflict or you have not made a needed selection, the parameter will highlight to red. To proceed,  
correctly fill in the parameter and click the “Make an EEprom” again.  
The program will write several characters into the boxes at the bottom, and lower left of the display. These are the serial  
commands containing the system parameters that are sent and received by the DDAA1000/DD1000 units.  
Repeat this procedure once for each Master, and once for each Remote in the system. Make sure you change the address  
for each Remote.  
Each time the program finished making an EEprom, and if a printer is connected to the computer, you can click on the  
PRINT button on the lower right corner to make a record of the system configuration. It will be handy later when you call  
Data-Linc Group to try to figure out why your system won’t work.  
When done, click on the EXIT button at the lower right corner of the window.  
If the unit is a DDAA1000, fill in the Master DDAA chart. The ‘X’s in the chart are the system configuration. The Remotes  
ID is the left side of the chart, the IN columns are the 4-20ma input numbers on the Masters connectors. Assign analog  
input(s) to each Remote by clicking the cursor on the row (address) and column (input #) for the Remote and the input to  
use. This will toggle the ‘X’ on or off. Assign the analogs for Remote zero (0) first, then Remote one (1), Remote two (2) thru  
seven (7). If there are less than seven remotes toggle the remaining ‘X’s off. The default for the system is all 8 analog inputs  
assigned to Remote zero( 0).  
The program will not allow the user to assign analog inputs in a wrong order. If a wrong assignment is made then program  
removes the ‘X’ selection. The maximum number of rows used is set by the number of remotes selected in step 6 above.  
Do not leave any columns blank if a later column has an ‘X’. The data transfer from Master to Remote will stop when a  
blank filed is reached. Blank columns at the right side of the table are okay. Not all analog inputs need to be assigned, just  
no orphaned –empty columns.  
PN 161-09981-002C  
18  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
The number of analog values received from a remote is the same as the number of analog inputs sent to a remote. If a  
DDAA remote unit has no analog input/outputs assigned it must have an address(1 to 7) higher than any remote using the  
analog input. i.e. All remotes using 4-20mA input/outputs must be assigned addresses lower than any digital only remotes.  
After filling in the chart click on the “Make an EEprom” button and follow the prompting instructions on the screen. If any  
previous setting are in conflict or have not been made the parameter will highlight to Red. To correct fill in the parameter and  
click the “Make an EEprom” again.  
The program will write several characters into the boxes at the bottom, and lower left of the display. These are the serial  
commands containing the system parameters that are sent and received by the DDAA1000/DD1000 units.  
Repeat this procedure once for each Master, and once for each Remote in the system. Make sure you change the address  
for each Remote.  
Each time the program finished making an EEprom, and if a printer is connected to the computer, you can click on the  
PRINT button on the lower right corner to make a record of the system configuration. It will be handy later when you call  
Data-Linc Group to try to figure out why your system won’t work.  
When done, click on the EXIT button at the lower right corner of the window.  
If you lost the program DDAAEEprom.exe either contact Data-Linc Group service for a new copy or you can use a  
terminal program such as “Hyper-terminal” with port settings of 9600 baud, 8 data bits, no parity and one stop bit. This  
process requires a very good understanding of how the units work internally or help from Data-Linc Group Technical  
Support.  
1. Apply DC power to the unit. A line of characters will appear on the terminal screen. It must say:  
*DDAA EEPROM MENU**  
*SET CAPLCK  
B# 1=12 2=24 3=48 4=96 5=19  
If not the connection is wrong, or more likely the terminal program’s baud setting is not 9600. Close the terminal  
connection, reset the baud to 9600 and reopen the terminal connection. Now remove and reapply the units DC power. If  
these instruction are confusing to you, do not proceed. Find someone who has computer knowledge of serial ports and  
terminal programs, and call Data-Linc Group service support.  
2. Make sure the CapsLock light is set ON at your keyboard.  
3. Now select the baud rate that matches the setting of the radio module. The most common setting are 5 for 19.2K baud,  
or 4 for 9600 baud. If your not sure use 5 and later check the radio baud setting to match.  
4. Display shows ‘M or S’. Select ‘M’ if these settings are for a Master unit. Select ‘S’ if this is to be a Remote/Slave unit.  
If CapsLock not on the unit will jump back to step 1.  
5. Display shows ‘#Slvs1-8’. It is asking for the number of remotes/slave units in the system. A point to point would be  
one (1). You can have as many as eight (8). Press 1 to 8.  
PN 161-09981-002C  
19  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
6. The unit will now ask for the number of ADs (analog inputs) on each Remote. ‘#ADsSlv0’. The question is repeated for  
each Remote unit. ‘#ADsSlv1’.etc. Any units that have no (zero) active analog channels must be put after any remotes that  
do have analog channels. Enter the number of analogs channels for each Remote.  
7. The display now asks for the number of analog inputs at the Master unit. ‘0-8 MstrAD’ The number of master analog  
inputs must equal the total number of analog inputs entered for each remote in step 6 above.  
8. The display now asks for the number of analog outputs on each Remote ‘#DAsSlv0’. The question is repeated for each  
Remote unit. ‘#DAsSlv1’ etc. These values must be the same as the numbers entered in step 6 above.  
9. The display now asks for number of analog outputs at the Master unit. ‘0-8 MstrDA’ This number is the same as entered  
in step 7 above.  
10. The display now prints out a status of your entries. Write these down and keep for use when you call Data-Linc Group  
technical support. Note the first line may say Master or Slave/Remote. Review the settings. The EEprom has been  
changed. The print out has been read from the changed EEprom. The data shown is from a master unit. The Remote  
display is similar.  
Mstr EEP:  
B# AD DA Slvs  
5 3 3 3  
ADs/Slave 1 2 0 0 0 0 0 0  
DAs/Slave 1 2 0 0 0 0 0 0  
Check  
11. Remove DC power, remove the serial cable, replace the jumpers on P1 and P2 back to the RUN/NORMAL position.  
Repeat the procedure for all of the units that you are reconfiguring.  
12. After all units are changed, bench test the system. The most likely problem is the baud rate setting does not match the  
setting in the radio modules.  
PN 161-09981-002C  
20  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Appendix C  
Radio Configuration  
The radio module in the DDAA1000/DD1000 can be set to suit your particular application. All adjustments are done through  
the built-in setup program, with a user interface that eliminates the need for setup diskettes or custom software.  
The radio modules used in the DDAA1000/DD1000 are factory pre-configured. The likely times the user would need to  
change a parameter would be to replace a defective radio module, add the repeater function to a radio, or change the  
system configuration. The user in encouraged to contact Data-Linc Group before making any changes, as a wrong setting  
may cause the radios to stop communicating. The main parameters that might need to be changed are:  
call book (phone) number  
network ID  
system operating mode  
repeater mode  
frequency key  
baud rate (if changing the radio)  
To access the radio setups the user must remove all connectors from the DDAA/DD1000, the remove the cover, and change  
a set of jumpers at location P1 and P2 and add a serial data cable supplied by Data-Linc Group to connector P3. See  
Figure 10, PCB layout drawing (Appendix B).  
To access the radio configuration menu, set the P1 and P2 jumpers as shown on the PCB layout drawing (Appendix B).  
Use the CONFIG-RF selection as shown on the PCB drawing. The dark lines represent the three small jumpers. Then insert  
the Data-Linc Group serial cable into connector P3 located next to the power connector. Attach the serial cable to a PC.  
Start a terminal program such as “Hyperterminal” with port settings of 19.2 K baud, 8 data bits, no parity and one stop bit.  
Apply DC power to the unit. Press the Configure button label SW1 located at the end opposite the power connector. While  
any terminal program that can be set to 19200 baud will work, examples for this manual were generated using the Microsoft  
Windows 2000 application “HyperTerminal.”  
Note that the computer setup communications to configure radio modules will always be at a baud rate of 19.2 K. The baud  
rate of the DDAA communications may be different. The radio module baud rate setting is for talking to the DDAA circuit  
board, not the computer terminal program.  
Note: When using HyperTerminal, set Handshaking to none.  
Table 2: Terminal Settings  
Parameter  
Baud Rate  
Data Bits  
Parity  
Setting  
19200  
8
None  
1
Stop Bits  
Flow Control  
None  
PN 161-09981-002C  
rev 8/04  
21  
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
When the setup program the main menu will appear on the screen. The main menu also displays the radios unique ID  
number and firmware version. The user selects the parameter group by pressing a single key. The next level menu is then  
displayed. Select the parameters you want to change with a single keystroke. Now you can enter the parameter or data  
value. To return to the previous menu press the ‘ESC’ escape key. When done making changes, press the ‘ESC’ key at  
least 3 times.  
Figure 11: Main Menu  
PN 161-09981-002C  
22  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Main Menu Option (0): Set Operation Mode  
When item (0) is selected, the Operation Mode Menu appears as shown in figure 12. The Operation Mode option is used to  
designate the method in which the particular DDAA1000/SRM will be used. The DDAA1000/SRM operates in a master to  
remote configuration; therefore, any radio modems that are intended to operate together must be set up as such. In a point-  
to-point setup, either the master or remote may be used on either end of the communications link. One consideration when  
setting up the radio modems is that a number of parameters are controlled by the settings in the master; therefore, you may  
wish to deploy the master on the communications end where you will have easier access to the radio modem.  
Figure 12: Mode Menu  
Shown below are example settings. Please refer to supplied configuration sheets for your modem’s configuration.  
(0) Point-to-point Master  
The DDAA1000/SRM operates in a master/remote configuration. When designated as a master in point-to-point  
mode, the radio modem will call any or all remotes it is instructed to call in the call book. The master determines  
the settings used for all Radio Transmission Characteristics, regardless of the settings in the remotes and/or repeaters.  
(1) Point-to-Point Remote  
When set up as a point-to-point remote, a DDAA1000/SRM will communicate with any master in its call book,  
either directly or through one or two repeaters. When functioning as a remote, the Entry to Call feature in the  
radio modem’s call book (Figure 13) is not operational. The remote will communicate with any master on the list that  
calls.  
(2) Point-to-Multi-Point Master  
The DDAA1000/SRM may be set to run in multi-point mode, which allows one master to simultaneously be in  
communication with numerous remotes. A point-to-multi-point master will communicate only with other radio  
modems designated as point-to-multi-point remotes or point-to-multi-point repeaters.  
(3) Point-to-Multi-Point Remote  
Setting (3) allows the radio modem to operate as a remote in a multi-point network.  
Please refer to the section entitled multi-point Operation, for more information on running a multi-point network.  
PN 161-09981-002C  
23  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
(4) Point-to-Point Remote/Repeater  
Option 4 allows you to designate the radio modem to act as either a remote or a repeater, depending upon the  
instructions received from the master for the specific communications session. When a radio modem is placed in an  
ideal location, this setting offers the flexibility of using that radio modem as an end point in the communications link  
(remote) or to extend the link to a point further (repeater). These functions are not, however, available simultaneously (the  
radio modem cannot act as both a remote and a repeater at the same time).  
A word of caution: Configured as a repeater, a radio modem has no security features as explained below. When a  
radio modem is designated as a point-to-point remote/repeater, it will allow any master to use it as a repeater.  
(5) Point-to-Point Repeater  
Do not use this mode with the DDAA1000/DD1000  
If a repeater is need in the system do not use a DDAA1000/DD1000. If and extended range of non-line-of-sight situation  
exists, use the Data-Linc Group SRM6000 radio modem as a repeater. When designated as a repeater, a radio  
modem behaves as a pass-through link. All settings for the call book, baud rates, and radio transmission  
characteristics are disabled. A repeater will connect with any master that calls it (the repeater must still be set up in  
the master’s call book).  
The use of one repeater in a communications link will reduce the top data throughput available when compared to a  
direct master to remote link (generally on the order of 50%). This impact is generally noticed only when using the radio  
modems at 115.2 Kbaud. The throughput does not decrease further if two repeaters are used. The highest baud rate  
that can be used in a DDAA1000/DD1000 is 19200 bps.  
(6) Point-to-Point Remote/Master Switchable  
Do not use this mode with the DDAA1000/DD1000  
(7) Point-to-Multi-Point Repeater  
Do not use this mode with the DDAA1000/DD1000. See Mode 5 notes above.  
(F) Ethernet Options  
Do not use this mode with the DDAA1000/DD1000.  
PN 161-09981-002C  
24  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Main Menu Option (1): Set Baud Rate  
When option (1) is selected you will be able to change the radio modem’s RS-232 baud rate. This is the communication rate  
between the radio modem and the instrument to which it is connected. It is important to note that this is independent of the  
baud rate for the other radio modem(s) in the communication loop. For example, DDAA1000/SRMs may be used in an  
application to send data from remote process instrumentation to an engineer’s computer. In this application, the baud rate for  
the radio modem on the instrumentation might be set to 9600, and the radio modem on the computer might be set to 57,600  
or 115,200.  
In general, it is desirable to set the baud rate to the highest level supported by the device to which it is connected. However,  
please note that this may actually result in slower data communications if the UART chipset of the connected device does  
not support higher data rates.  
The DDAA/DD1000 use 8 Data Bits/ no Parity, 1 Stop bit only. Do not change. These settings are not used when setting  
radio operating values. The default setting is 0 (8,N,1).  
Table 3: Available data word length and parity selections  
Menu  
Setting  
Data Bits  
Parity  
Stop Bits  
0
1
2
3
4
5
8
7
7
8
8
8
None  
Even  
Odd  
1
1
1
2
1
1
None  
Even  
Odd  
Note: The RF parameter baud rate must match the internal set baud rate in the EEprom. A mismatched baud rate  
will cause communication to alway stop.  
ModBus RTU  
Do not use this mode with the DDAA1000/DD1000.  
PN 161-09981-002C  
25  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Main Menu Option (2): Edit Call Book  
If the DDAA1000/DD1000 system is only two (2) units, one Master and one Remote, then either Point-to-Point or Multipoint  
modes can be used. If the system has more than one Remote, then Point-to-Multipoint mode must be used. Use of the  
Call Book for multi-point systems is explained later in this chapter.  
The Call Book is an innovative feature in the DDAA1000/SRM that offers both security and flexibility in use. The Call Book  
accomplishes this by allowing the user to determine with which other DDAA1000/SRMs a given radio modem will  
communicate, based on the Call Book numbers for both the master and remote. The radio modem’s Call Book number is  
encoded in the microprocessor and identified on a label on the modem. The instructions provided in this section are for point-  
to-point mode only. Use of the Call Book for multi-point systems is explained later in this chapter. For two DDAA1000/SRM  
radio modems to communicate in point-to-point mode, three events must occur:  
1. The call book number for the master must be listed in the Remote’s Call Book.  
2. The call book number for the remote must be listed in the master’s Call Book.  
3. The master must be programmed to call the remote.  
As shown in figure 3, the Call Book allows users to set up a list of up to 10 DDAA1000/SRMs to communicate with.  
Designate up to 2 repeaters to be used in communicating with a given radio modem, and tell the master which remote to  
call. To direct the master to call a remote, the Remote must be in the Call Book Menu. A specific remote may be called by  
entering (C) at the prompt, followed by the menu number corresponding to that remote. To call any available remote in the  
list, the user should enter C and then A (for All).  
Note: To call a remote through one or two repeaters, you must call that remote directly (as opposed to using the  
Call All option). When Call All is selected the master is not able to connect with any remotes through repeaters.  
This is because the master calls every remote in the list when instructed to call all and will connect with the first  
remote to respond. When calling through a repeater, the master must first call that repeater and establish a  
communications link with it prior to making contact with the remote.  
Figure 13: Call Book Menu  
Shown below are example settings. Please refer to supplied configuration sheets for your modem’s configuration.  
PN 161-09981-002C  
26  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Entering or Modifying Numbers in the Call Book  
Entering or modifying call book numbers in the Call Book is a straightforward process. When in the Call Book menu, select  
the entry number (0 – 9) you wish to edit. You will be prompted for the new number (formatting is automatic, you do not need  
to enter the dash). Once the number is entered (unless it is 000-0000) you will be asked for the call number of the first  
repeater to be used. If no repeater is to be used, enter the escape key; your entry will be complete and you will be back in  
the Call Book menu screen. If you enter a repeater number, you will then be prompted for the call number of the second  
repeater to use. If a second repeater is being used, enter the call number at this time; if not, enter the escape key. Once  
again, the radio modem will retain your entries, as shown in the updated Call Book menu screen.  
Note: It is important that the Call Book slots (0 – 9) are filled sequentially beginning with 0, the first slot in the book.  
Call Book numbers do not need to be entered in numerical order; however, there must not be any 000-0000 numbers  
in the middle of the list of good Call Book numbers. The reason for this is that when a master is instructed to Call All  
available remotes, it will call all remotes listed until it reaches the first number of 000-0000. If a valid call book  
number is entered after the all zero number, it will not be recognized as a valid number to be called by the master.  
Edit Call Book in Multi-Point Systems  
In a multi-point system, the remotes and repeaters are not listed in the master’s Call Book. When establishing such a  
system, it is necessary only to have the master’s Call Book number in each remote’s and repeater’s Call Book, and to have  
each repeater’s Call Book number in the Call Book of each remote which may potentially communicate through it.  
The following example shows the Call Books of a multi-point system comprised of a master, repeater and remote in which  
the remote can communicate either through the repeater or directly to the master:  
Multi-Point Master Call Book (Unit Call Book number 555-0001)  
Entry  
(0)  
Number  
000-0000  
000-0000  
Repeater 1  
Repeater 2  
(1)  
No call book number entries are necessary in the master’s Call Book  
The master’s Call Book may be programmed to call any entry  
Multi-Point Repeater Call Book (Unit Call Book number 555-0002)  
Entry  
(0)  
Number  
555-0001  
000-0000  
Repeater 1  
Repeater 2  
(1)  
Multi-Point Remote Call Book (Unit Call Book number 555-0003)  
Entry  
(0)  
Number  
555-0001  
555-0002  
000-0000  
Repeater 1  
Repeater 2  
(1)  
(2)  
PN 161-09981-002C  
rev 8/04  
27  
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Main Menu Option (3): Edit Radio Transmission Characteristics  
When option (3) is selected in the main menu the screen in figure 14 appears, which allows the user to modify the radio  
transmission characteristics of the radio modems. As stated in the warning, these parameters are for the experienced user  
who has a good understanding of the principles of radio data transmission. They should be changed only after consulting this  
user guide.  
It is important to note that the radio parameters between any radio modems in communication will be determined by the  
settings for the master (except when in multi-point mode, see (4) RF Data Rate below). While the settings may be modified  
for the remote(s) and/or repeaters, they will be overridden by the master’s parameters.  
Figure 14: Radio Parameters Menu  
Shown below are example settings. Please refer to supplied configuration sheets for your modem’s configuration.  
(0) FreqKey  
Selection (0) in the Radio Parameters menu allows the user to modify the hopping patterns of the radio modems to  
minimize the interference with other Data-Linc Group radios in operation in the area. For instance, if there were 10 pairs  
of Data-Linc Group radios in operation within a factory or refinery, changing the Frequency Key would ensure that they  
would not jump onto the same frequencies at the same time for the same length of time.  
There are 15 choices available for the Frequency Key (0-9 and A-E). It is recommended that a list be maintained of the  
settings for each master to ensure that each is set to a different hopping pattern.  
(1) Max Packet Size and (2) Min Packet Size Selections  
For DDAA1000/DD1000 use the user should not change this parameter.  
(1) and (2) allow the user to designate the size of the packets (in bytes) used by the radio modem in its communication  
link. Packet size is determined by a combination of the settings entered by the user and the RF Data Rate. In addition,  
the Max Packet Size is a function of the setting selected for the Min Packet Size. Tables 3, 4 and 5 provide the packet  
sizes for each different combination of settings.  
PN 161-09981-002C  
28  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Table 4: Minimum Packet Size Settings (bytes)  
Min Packet Size  
RF Data Rate = 2  
Min Packet Size  
RF Data Rate = 3  
Setting  
Setting  
0
1
2
3
4
5
6
7
8
9
16  
21  
26  
32  
37  
42  
48  
53  
58  
64  
0
1
2
3
4
5
6
7
8
9
8
12  
16  
20  
24  
28  
32  
36  
40  
44  
Table 5: Maximum Packet Size Settings where RF Data Rate=3  
Maximum Setting  
0
1
2
3
4
5
6
7
8
9
0
1
2
8
24  
28  
32  
40  
44  
48  
56  
60  
64  
72  
76  
80  
88  
92  
96  
104 120  
108 124  
112 128  
136 152  
140 156  
144 160  
12  
16  
3
4
5
6
7
8
9
20  
24  
28  
32  
36  
40  
44  
36  
40  
44  
48  
52  
56  
60  
52  
56  
60  
64  
68  
72  
76  
68  
72  
76  
80  
84  
88  
92  
84  
100 116 132  
104 120 136  
108 124 140  
148 164  
152 168  
156 172  
160 176  
164 180  
168 184  
172 188  
88  
92  
96  
112  
116  
128 144  
132 148  
100  
104  
108  
140 136 152  
124 140 156  
PN 161-09981-002C  
rev 8/04  
29  
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Table 6: Maximum Packet Size Settings where RF Data Rate=2  
Maximum Setting  
0
1
2
3
4
5
6
7
8
9
0
1
2
15  
20  
26  
36  
42  
47  
58  
63  
68  
79  
84  
90  
100  
105  
111  
121 143 164  
127 148 169  
132 153 175  
185  
190  
196  
206  
212  
217  
3
4
5
6
7
8
9
31  
36  
42  
47  
52  
58  
63  
52  
58  
63  
68  
74  
79  
84  
74  
79  
84  
90  
95  
95  
116  
137 159 180  
143 164 185  
148 169 190  
153 175 196  
159 180 201  
164 185 206  
169 190 212  
201 222  
206 228  
212 233  
217 238  
222 244  
228 249  
233 254  
100 121  
105 127  
111  
116  
132  
137  
100 121 143  
95 127 148  
(3) Xmit Rate  
There are two settings for the Transmit Rate parameter. For normal operation the DDAA1000/SRM should be set at  
Transmit Rate 1. Transmit Rate 0 is useful to qualitatively gauge signal strength. When set to Transmit Rate 0 the radio  
modems will transmit data back and forth continuously, and the strength of the signal may be gauged by viewing the  
Show Radio Statistics option.  
Due to the fact that the radio modems transmit continuously when Transmit Rate is set to 0 (whether or not they have  
data to send) they use radio frequency spectrum unnecessarily. Therefore, Transmit Rate 0 should be used only as a  
diagnostic tool and not for normal operation.  
(4) RF Data Rate  
The DDAA1000/SRM has two settings for the RF Data Rate (not to be confused with the RS232 Baud Rate). Setting 2  
should be used when the radio modems are close together and data throughput is to be optimized. Setting 3 should be  
used when the radio modems are farther away and a solid data link is preferred over data throughput.  
Note: The RF Data Rate setting must be identical for all units in the system. Any radio modem with a different RF  
Data Rate than the master will not establish a communication link.  
PN 161-09981-002C  
30  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
(5) RF Xmit Power  
The DDAA1000/SRM offers users the ability to modify the Transmission Power of the radio modem. There are 10 power  
settings available (1-10) which are roughly linear. Therefore a setting of 10 is full power (or 1 Watt) and 1 is 10% power  
(or 100 mw). The following guidelines should be followed when setting the RF Transmission Power:  
Table 6: Power Transmit Settings  
Setting  
Power Level Used When  
Pair of pairs of radio modems operating within the  
same or adjoning rooms.  
1-3  
Low  
More than one pair of radio modems operating  
withi the same facility.  
4-6  
Medium  
Full  
7-10  
Normal operation extending beyond a facility.  
(6) Remote Security  
With option 6 the user may disable the radio modem’s security so it will accept a call from any other DDAA1000/SRM.  
The default setting is 0 where security is enforced (the caller’s call book number must be in the remote’s Call Book).  
With a setting of 1 security is disabled.  
As mentioned in mode 6, Remote Security must be set to 1 when the unit is operating in a point-to-point system where  
it may need to accept calls from more than 10 different DDAA1000/SRMs. However, it is important to note that when  
Remote Security is set to 1, the radio modem will accept calls from any other DDAA1000/SRM, and additional system  
security measures should be taken to prevent unauthorized access.  
(7) RTS to CTS  
For DDAA1000/DD1000 use the user should not change this parameter. Leave it disabled (0).  
(8) Retry Time Out  
The Retry Time Out parameter allows the use to determine when a remote will drop a connection to a master or repeater  
in multi-point mode. The default setting is 255, meaning that if one packet in 255 from the master is sent successfully to  
the remote, it will maintain a link. The lowest setting is 8, at which a remote will drop a connection much faster.  
The Retry Time Out parameter is useful when a multi-point system is used with a moving master or remotes. As the link  
gets weaker, a lower setting will allow a remote to drop it’s link and search for a stronger connection.  
While intended primarily for multi-point systems, the Retry Time Out parameter may also be modified in point-to-point  
systems. In point-to-point mode the Retry Time Out should not be set to a value of less than 151.  
PN 161-09981-002C  
31  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
(9) Lowpower Mode  
For DDAA1000/DD1000 use the user should not change this parameter. Do not enable the low power mode.  
(A) High Noise  
Use the menu to indicate if the modem will be operated in an environment with a high degree of radio noise and  
interference.  
With a setting of 1, the rejection of interference is improved, at the cost of reduced range and/or throughput.  
(B) MCU speed  
Use this menu to set the speed of the MCU (processor) in the modem.  
Note: Only needed when the DDAA1000/SRM is set to 115.2K baud . But the DDAA1000/SRM is limited to  
19.2K baud  
Setting  
Description  
Low speed  
High speed  
Notes  
0
1
Reduces current consumption  
Required for 230Kbaud  
PN 161-09981-002C  
rev 8/04  
32  
DATA-LINC GROUP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Main Menu Option (4): Show Radio Statistics  
Option (4) in the main menu allows the user to view data transmission statistics, which have been gathered by the  
Transceiver during the most recent session. Statistics are gathered during each data link and are reset when the next link  
begins. Ideally, noise levels should be below 30, and the difference between the average signal level and average noise level  
should be 15 or more. High noise levels tend to indicate other sources of RF interference, while low signal levels indicate a  
weak link. The “Local” stats are the statistics that are being gathered by the modem you are connected to while “Remote1,  
Remote2, and Remote3” are the stats of the repeater(s) that the modem you are attached to is using to get back to the  
master modem. The following sections provide information useful to the process of troubleshooting and improving radio links.  
Average Noise Level  
The average noise level indicates the level of background noise and interference at this modem and at each of the modems  
used as repeaters in the link. The number is an average of the noise levels measured at each frequency in the modems’  
frequency hop table. The individual measurement values at each frequency hop channel are shown in the frequency table.  
The frequency table is accessed by pressing the ENTER key on the computer when the radio statistics menu is displayed.  
Average noise levels will typically fall in the range of 15 to 30.Average noise levels significantly higher than this are an  
indication of a high level of interference that may degrade the performance of the link. High noise levels can often be improved  
with bandpass filters, antenna placement or antenna polarization. Please contact Data-Linc Group for more information.  
Average Signal Level  
The average signal level indicates the level of received signal at this modem and at each of the modems used as repeaters in  
the link. For each of these, the signal source is the modem that transmits to it. The number is an average of the received  
signal levels measured at each frequency in the modem’s frequency hop table. The individual measurement values at each  
frequency hop channel are shown in the frequency table. The frequency table is accessed by pressing the ENTER key on  
the computer when the radio statistics menu is displayed.  
For a reliable link, the average signal level should be at least 30 higher than the average noise level reading. The table below  
provides an approximate conversion of average signal level values into the more common dBm (decibel milliwatts). Low  
Average Signal Levels can often be corrected with higher gain antennas, antenna placement, and use of repeaters. Contact  
Data-Linc Group for more information.  
Average Signal Level 41  
49  
60  
66  
85  
Level in dBm  
-110  
-100  
-60  
-80  
-70  
Overall Rcv Rate (%)  
The Overall Rcv Rate measures the percentage of data packets that were successfully transmitted from the master to the  
remote on the first attempt without requiring retransmission.Anumber of 75 or higher indicates a robust link that will provide  
very good performance even at high data transmission rates. Anumber of 25 or lower indicates a weak or marginal link that  
will provide lower data throughput.An Overall Rcv Rate of 100% will provide approximately 100 Kbaud of bandwidth with an  
RF data rate of 3 (Radio Transmission Parameters Menu) and approximately 150 Kbaud of bandwidth with an RF Data Rate  
of 2. These numbers are reduced approximately 50% if there are one or more repeaters in the network.  
PN 161-09981-002C  
33  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Number of Disconnects  
If, during the course of performing a link test, the link between the master and the remote is broken, and the radios lose  
carrier detect, the occurrence is recorded in the Number of Disconnects value. The value indicates the total number of  
disconnects that have occurred from the time the link test started until the radio was put into config mode. Under normal  
operating conditions, the number of disconnects should be 0. One or more disconnects may indicate a very weak link, the  
presence of severe interference problems or loss of DC power to the Master or Repeater if one is present.  
Note: a remote and/or repeater will record a disconnect if the system master is placed into configuration mode or  
has power interrupted while the remote and/or repeater is linked to the master  
Radio Temperature  
The radio temperature value is the current operating temperature of the radio in degrees C (Celsius.) For proper operation,  
DDAA1000/SRM radio modems must be in the range of –400 to 750 C.  
Multi-Point Operation  
In a multi-point system, a radio modem designated as a master is able to simultaneously be in communication with  
numerous remotes. In its simplest form, a multi-point network functions with the master broadcasting its messages to all  
remotes and the remotes responding to the master as appropriate  
PN 161-09981-002C  
34  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Main Menu Option (5): Edit Multi-Point Parameters  
Figure 15: Multi-Point Parameters  
Shown below are example settings. Please refer to supplied configuration sheets for your modem’s configuration.  
In a multi-point network, it is critical to know how many radio modems are being used as repeaters. Any radio modem that is  
used as a repeater essentially becomes a master to the remotes and other repeaters to which it is communicating.  
Therefore, the user must first identify how many repeaters are connected to the master by assigning a value in parameter (0)  
Number Repeaters. This parameter must also be set for each repeater in the system (i.e., in the event that a repeater is  
connected to one or more other repeaters). This parameter does need to be set for multi-point remotes.  
In point-to-point operation, the DDAA1000/SRM radio modems acknowledge every data packet transmitted. In a multi-point  
network, the remotes do not acknowledge transmissions from a master to the remotes. This is to prevent system overload. If  
the remotes acknowledged all data transmissions from the master in a large multi-point system, then all system capacity  
would be spent having the master listen for acknowledgments from the remotes. Because the transmission is not  
acknowledged by the remotes, 100% confidence does not exist that every remote has received every message from the  
master. To address this issue, the user may modify option (1) Master Packet Repeat, assigning a value between 0 (the  
packet is transmitted once) to 9 (the packet is repeated 9 times). For networks with solid RF links, this parameter would be  
set at the lower end of the scale (0-1). If the network has some weak or marginal links, it would be set toward the higher  
values. If a remote receives a packet from a master more than once, it will discard the repeated packets received.  
While packets transmitted from the master to the remotes in a multi-point network are not acknowledged, packets  
transmitted from remotes to the master are. However, it is possible that more than one remote will attempt to transmit to the  
master at the same time, and it is therefore important that a protocol exists to resolve contention for the master between  
remotes.  
This is addressed through parameters (2) Max Remote Retry and (3) Retry Odds. The Max Remote Retry setting defines  
how many times (0 to 9) the remote will attempt to retransmit a packet to the master before beginning to use a back-off  
algorithm. Once the remote has unsuccessfully attempted to transmit the packet the number of times specified in Max  
Remote Retry, it will attempt to transmit to the master on a random basis.  
The Retry Odds parameter determines the probability that the remote will attempt to retransmit the packet to the master; a  
low setting will assign low odds to the remote attempting to transmit and conversely a high setting will assign high odds. An  
example of how this parameter might be used would be when considering two different remotes in a multi-point network, one  
close in with a strong RF link and the other far from the master with a weak link. It may be desirable to assign a higher Retry  
Odd to the remote with the weaker link to give it a better chance of competing with the closer remote for the master’s  
attention.  
PN 161-09981-002C  
35  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
Another parameter in a multi-point network is (4) DTR Connect. When set at (1), the remote will connect to the master if it  
is free when the DTR line goes high on the 9-pin RS232 connector. In setting (2), the radio modem will accumulate data in its  
buffer and transmit in a burst when the buffer is full. This mode is valuable when a network has many low data rate devices  
and it is desirable to increase overall network capacity. In setting (0), the radio modem will transmit when RS232 data is  
received.  
The repeater’s hopping pattern must also be set in a multi-point network; this is accomplished with parameter (5) Repeater  
Frequency. Setting this parameter is in contrast with point-to-point mode where the repeater automatically uses the  
master’s hopping pattern. The repeater may be programmed to either use the master’s hopping pattern selection (0) or its  
own selection (1).  
Option (6) NetWork ID allows multi-point networks to be established without the use of the Call Book. If the NetWork ID is  
set to any value lower than the default (255), the remotes in the multi-point network will communicate with the first multi-  
point master or repeater heard with the same NetWork ID. When the NetWork ID is used, multi-point masters and repeaters  
may be replaced without reprogramming all of the remotes in the network. In addition, this allows a remote to establish  
communications with different masters (though not at the same time) without having the call book numbers in the Call Book.  
This is very useful in mobile multi-point applications. (8) MultiMaster Synch is reserved for multi-point applications with  
concentrations of master units where it is necessary to reduce interference between the masters. Please contact the factory  
for more information on the use of this feature. The (9) 1PPS Enable/Delay This setting should not be changed from its  
default of 255. Contact the factory for further information.  
(A) Remote/Repeater  
The remote/repeater mode allows a DDAA1000/DD1000 in a multi-point system to simultaneously act as a remote and  
a repeater. When in this mode, a radio will repeat transmit any packets sent from a master as well as send them out  
the RS232 port. This allows a DDAA/DD1000 set as a slave/repeater to act as a remote at the same time. 0 disables  
this mode, 1 enables it.  
(B) Diagnostics  
The DDAA1000/DD1000 has no connection point for diagnostics.  
(C) SubNet ID  
The default setting is “Disabled.” Please see the SubNet ID section of this manual.  
(D) Radio ID  
Not used for DDAA1000/DD1000.  
PN 161-09981-002C  
36  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
SubNet ID  
The DDAA1000/SRM series modems offer a SubNet ID system for use in multi-point networks using Network ID. This feature  
allows the users to dictate what path a given repeater or remote will use to achieve a link to the network master. For  
example, if a remote modem in a given network has line of sight to the network master and one or more repeaters, but only  
one repeater is close to that remote, SubNet ID can be used to link that master with the proper repeater only.  
Note: This feature can only be used in networks using Network ID with one or more repeaters.  
There are two components to SubNet ID. The first is the Xmit (transmit) SubNet ID, and the second is Rcv (receive) SubNet  
ID. The Xmit SubNet ID is used only by repeaters and is the ID that a repeater sends out when sending data to other  
repeaters or remotes. The Rcv SubNet ID is the ID that repeaters or remotes look for to receive data.  
Note: The master is not affected by these settings. Only repeaters and remotes use these settings. Remotes only  
use Rcv SubNet ID  
Modem configurations are as follows:  
Master  
No setting used  
Repeaters  
Any repeater that should be linked directly to the master should have the Rcv SubNet ID set to 0. Any  
repeater using another repeater as its link, needs the Rcv SubNet ID set to the Xmit SubNet ID of that  
repeater. The Xmit SubNet ID can be set to anything from 1 to E.  
Remotes  
Any remote that should be linked directly to the master should have the Rcv SubNet ID set to 0. Any  
remote using a repeater as its link should have the Rcv SubNet ID set to the Xmit SubNet ID of that  
repeater  
Main Menu Option (8): Password  
Caution: If the password feature is enabled and you want cannot remember the password, the radio modem will  
have to be returned to Data-Linc Group to have the password disabled. Use with caution.  
Option (8) in the Main Menu allows the user to set a password, which will prevent unauthorized users to change the  
configuration of the modem.  
Setting a Password  
To enable the Password feature choose (8) from the Main Menu. You will be prompted with “New PW?” (<esc> to exit)  
PN 161-09981-002C  
37  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
To back out of the process and not enable the password, hit escape. To set a password, type in exactly 4 characters. At any  
point in the process you can cancel by hitting the escape key. Once the 4 characters have been entered, you will be  
prompted with “<enter> to accept, <esc> to quit”.  
At this point, if you wish to accept the password entered and enable the feature, press the enter key. The password that you  
have chosen is displayed on the line above (please note that the password is case sensitive). To quit the process and not  
enable the password, press escape.  
Changing a Password  
Once the password feature has been enabled, it is possible to change to a new password. To enter a new password select  
(8) from the Main Menu. You will be prompted with “Enter Security Code”. Enter the current password. Once the password  
has been entered correctly (it is case sensitive) you will be prompted to enter the new password. At any point this process  
may be cancelled by pressing escape.  
Disabling Password  
The process to disable the password is similar to the process to change the password. However, when prompted to enter the  
new password, the following procedure needs to be followed:  
1. Hold the “Alt” key down and using the number key pad (not the numbers across the top of the keyboard)  
type “0255”  
2. Release the “Alt” key  
3. Repeat steps 1 and 2 three more times (this will enter 0255 a total of four times).  
4. You will be prompted with “<Enter> to accept, <esc> to quit.  
5. Hit the “Enter” key to disable the password or hit the escape key to keep the password  
PN 161-09981-002C  
38  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DDAA1000/SRM User Guide  
DDAA1000/SRM and DD1000/SRM Placement Locations  
Placement of your DDAA1000/DD1000 is likely to have a significant impact on its performance. In general, the rule of  
thumb with the DDAA1000/DD1000 is that the higher the placement of the antenna, the better the communication. In  
practice you should also place the radio itself away from computers, telephones, answering machines, and other similar  
equipment. To improve the data link, Data-Linc Group offers directional and omni directional antennas with cable lengths  
ranging from 10 to 200 feet.  
When using an external antenna, placement of that antenna is critical to a solid data link. Other antennas in close  
proximity are a potential source of interference. It is also possible that slight adjustments in antenna placement (as little  
as 2 feet) will solve noise problems. In extreme cases, such as when the radio modem is located close to pager or  
cellular telephone transmission towers, Data-Linc Group offers a band pass filter to reduce the out of band noise.  
PN 161-09981-002C  
39  
DATA-LINC GROUP  
rev 8/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Mr Coffee Hot Beverage Maker HC4 User Manual
Network Computing Devices Server KNS30 User Manual
NewAir Ice Maker AI 200 User Manual
Nokia Cell Phone RH 105 User Manual
Nokia Crib Toy C3 00 User Manual
Nokia Headphones BH 505 User Manual
Oregon Scientific Fitness Electronics SE332 User Manual
Packard Bell Personal Computer REFDOCS02420200 User Manual
Panasonic Scanner KV S1020C User Manual
Parkside Caulking Gun PSG 50 A1 User Manual