| FP-1600 FieldPoint Quick Start Guide   What You Need to Get Set Up   · Network Module   · Power Supply   · Mounting Hardware (DIN rail   or panel mount accessory)   · Terminal Base(s)   · FieldPoint Software CD   · Accessories: Ethernet cable,   screwdriver   · I/O Module(s)   Install the Network Module   1 DIN Rail Mount   Panel Mount   A. Unlock rail clip.   A. Unlock rail clip.   1 Download from Www.Somanuals.com. All Manuals Search And Download.   Install the Terminal Base(s)   2 CAUTION: Terminal bases must be connected to the network module   before applying power to the module. Do not connect or disconnect   terminal bases while power is applied to the network module.   DIN Rail Mount   Panel Mount   A. Unlock rail clip.   A. Use template that came with your   accessory to drill pilot holes.   B. Connect terminal base to network   module connector, being careful not   to bend any connector pins.   B. Press base onto rail.   C. Fasten terminal base to panel.   3 Download from Www.Somanuals.com. All Manuals Search And Download.   DIN Rail Mount   Panel Mount   C. Slide into position and lock the rail   clip. Be careful not to bend any pins.   D. Repeat for each terminal base, up to   nine for each network module in   most cases. You can use one or two   extender cables (which you can order   separately) if your FieldPoint bank is   too long for your available space.   E. Place protective cover on last base.   D. Repeat for each terminal base, up   to nine for each network module in   most cases. You can use one or   two extender cables (which you can   order separately) if your FieldPoint   bank is too long for your available   space.   E. Place protective cover on last base,   and install rail locks at each end.   4 Download from Www.Somanuals.com. All Manuals Search And Download.   Install the I/O Module(s)   3 It does not matter where you install each I/O module, except for   these types of situations:   · If you plan to cascade power between any I/O modules using the   V and C terminals, those modules should be grouped together.   For more accurate measurements, you might want to locate any   thermocouple modules away from heat sources, including network   modules or relay modules, unless you are mounting them on an FP-TB-3.   · A. Align slots on module with guide rails on   base, and press onto base until terminal   base’s latch locks the module in place.   B. Repeat for each I/O module.   Connect the Network Cables   4 Connect the FP-1600 to an Ethernet network by connecting the RJ-45   Ethernet port of the FP-1600 to an Ethernet hub using a standard Category 5   Ethernet cable.   Straight-Through   UTP Cable   Straight-Through   UTP Cable   5 Download from Www.Somanuals.com. All Manuals Search And Download.   Optionally, you can connect an FP-1600 directly to a computer using an   Ethernet crossover cable.   Cross-Over Cable   Do not use a cable longer than 100 m. If you are using a 100 Mbps Ethernet,   National Instruments recommends using a Category 5 shielded twisted-pair   Ethernet. If you need to build your own cable, refer to the FP-1600 User   Manual for cabling details.   Wire Power to Your FieldPoint System   5 A. Connect 11-30 VDC power supply leads to V and C terminals of the   network module. If you want to verify that your power supply is sufficient   for your modules and devices, refer to your FieldPoint hardware   documents for instructions on calculating power requirements.   B. Connect power to the FieldPoint modules that require external power for   outputs (output modules, counter modules, PWM, PG, QUAD). Refer to   the I/O module’s operating instructions for power requirement details.   You can power a module by connecting the V and C inputs on its terminal   base to a separate power supply, connecting the V and C outputs of a   neighboring terminal base or network module, or using a combination of   both methods. If you want to power field I/O devices from a terminal   base, supply power to the terminal base, and then connect the terminal   base V and C output terminals to the field device.   6 Download from Www.Somanuals.com. All Manuals Search And Download.   CAUTION: Cascading power from neighboring bases or network modules   defeats isolation between cascaded modules.   Separate Power Supply   (Recommended)   No External   Power Required   Cascaded Power   (Reduces Isolation)   FP-1600   FP-AI-100   FP-AO-200   FP-RLY-420   FP-TC-120   Power Supply   Power Supply   V 1 16   V 2 3 15   CAUTION: Cascading   power defeats isolation.   31 32 C   C17   18   Shades of gray indicate   different voltage potentials.   7 Download from Www.Somanuals.com. All Manuals Search And Download.   Connect to Field Devices   6 Use each I/O module’s operating instructions, or the diagram under its   removable label, to help you connect your field devices.   FP-AI-110   8 Channel, 16-Bit Analog Input Module   Highlights   FP-AI-110   To Power   Supply   Overview   Input   A m 0 Analog   , 2 , V V 16-Bit   m 8-Ch.   0 17   2 15   32   1 11   - I A - P FP-AI-110   Self-Powered   Floating Sensor   Loop-Powered   Sensor   8-Ch. 16-Bit Analog Input   FP-AI-110   POWERED   ISensor   Channel 0   V CURRENT   VSensor   Channel 7   N   1 IIN   2 4 6 8 10   12   14   16   VSUP   17   19   21   23   25   27   29   31   COM   18   20   22   24   26   28   30   32   SOURCE   SOURCE   VSUP   CH0   CH1   CH2   CH3   CH4   CH5   CH6   CH7   3 5 7 9 11   13   15   VIN   VOUT   I IN   + - COM   VOLTAGE   SOURCE   C P READY   NOTE: Either the self-powered   sensor or power supply should be   floating (not tied to earth ground).   8 Download from Www.Somanuals.com. All Manuals Search And Download.   Power Up Your FieldPoint System   7 CAUTION: Terminal bases must be connected to the FP-1600 before   power is applied to the FP-1600.   Plug in each power supply to   your FieldPoint bank. You should   see all except the STATUS and   PROCESS LEDs flash once, and   the POWER LED come on and   stay on. After a few seconds, the   POWER and READY LEDs should   be lit on each I/O module. If this   is not the case, refer to your   FP-1600 user manual for   troubleshooting instructions.   POWER and READY LEDs Stay Lit   The READY LEDs will not light until an IP address is assigned. Likewise, the   STATUS LED will stay lit until an IP address is assigned.   After the hardware is installed, you should verify communication, configure   the modules, configure your power-up states and watchdog settings. If you   are using National Instruments FieldPoint software for these tasks, continue   to the following section.   9 Download from Www.Somanuals.com. All Manuals Search And Download.   Install the FieldPoint Software   8 9 A. Close all other applications. If you   plan to install National Instruments   development software such as   Lookout, LabVIEW, or Measurement   Studio, install them before you   install the FieldPoint software.   B. Insert the FieldPoint software CD and follow the onscreen instructions.   Verify the Installation   A. Select Start»Programs»National Instruments FieldPoint»FieldPoint   Explorer.   B. Right-click on the FieldPoint icon and select Add a comm resource to this   server.   10   Download from Www.Somanuals.com. All Manuals Search And Download.   C. In the Comm Resource   Configuration dialog box, select   Ethernet as the Type.   D. Click Browse, select the   FP-1600, and click the Device   Properties button.   11   Download from Www.Somanuals.com. All Manuals Search And Download.   E. In the FP-1600 Properties box, enter   values for the IP address, Subnet   mask, and Time server IP. You might   also want to enter a comment to help   you identify the FP-1600 module.   • IP address is the address of the   FP-1600 on the network.   • Subnet mask is the mask that is   applied to the IP address that the   device uses to find other devices on   the Ethernet network (255.255.255.0   is the most common).   • Time server IP is the address of the   host computer that the FP-1600 will synchronize its clock to. The   computer must have the Lookout Time Synch service (installed with   Lookout 4.x or FieldPoint 2.x).   F Click on Apply, then OK twice to return to the Comm Resource   Configuration dialog box.   G. Click on Find Devices.   H. Expand the +FP Res item on the left side of the Explorer window to see   the devices found on the network.   12   Download from Www.Somanuals.com. All Manuals Search And Download.   If your modules are not   listed, check the cable and   connections and make sure the   modules are all powered on. If   you still have problems, refer   to your FP-1600 user manual   for troubleshooting   information.   I. Select an input module and   click on the start monitoring button   to view live data.   J. Select an output channel and click on the write button   outputs.   to change   K. Select File»Save.   13   Download from Www.Somanuals.com. All Manuals Search And Download.   Configure I/O Modules   A. Right-click on the device name in FieldPoint Explorer and select Edit this   10   Device from the pop-up menu.   B. Click on the Channel Configuration button to bring up the Channel   Configuration dialog box.   C. Select the type of   channel to show,   then select the   channel(s) that   you want to   change. To select   more than one   channel, uncheck   the One channel   at a time box.   NOTE: Configuration options are module-dependent. The options   listed here might not be available for your particular module. Refer to   your I/O module operating instructions for details on configuration   options.   14   Download from Www.Somanuals.com. All Manuals Search And Download.   D. Set the range and output values of the selected channel(s).   E. Set the attributes for the selected channel(s) by selecting the attribute and   entering the desired value.   F. Send commands to the selected channel(s) by choosing a command and   value and clicking on Send.   G. Repeat this procedure for each channel you want to configure.   H. Click on the OK button when you are finished, or click on the Apply   button to save the changes and continue to configure channels. When   you click on OK or Apply, the changes are immediately sent to the device.   I. Select File»Save when you are done.   15   Download from Www.Somanuals.com. All Manuals Search And Download.   Where to Go from Here   11   After you get your hardware up and running, you might want to implement   features such as power-up defaults or network watchdog settings. Refer to   your FP-1600 user manual or online help for information about features,   configuration, application development, and troubleshooting.   16   Download from Www.Somanuals.com. All Manuals Search And Download.   FP-1600 Specifications   Network interface . . . . . . . . . . . . . . . . . . . . 10BaseT and 100BaseTX Ethernet   Compatibility. . . . . . . . . . . . . . . . . . . . . . . . IEEE 802.3   Communications rate . . . . . . . . . . . . . . . . . 10 Mbps, 100 Mbps, autonegotiated   Cabling distance . . . . . . . . . . . . . . . . . . . . . 100 m   Power supply range . . . . . . . . . . . . . . . . . . 11 to 30 VDC   Power consumption . . . . . . . . . . . . . . . . . . 7 W + 1.15   Maximum terminal bases per bank . . . . . . . 9   (I/O module power requirements)   * Maximum number of banks. . . . . . . . . . . . . determined by network topology   Operating temperature. . . . . . . . . . . . . . . . . –20 to +55 °C   Storage temperature . . . . . . . . . . . . . . . . . . –55 to +85 °C   Relative humidity . . . . . . . . . . . . . . . . . . . . 5% to 90% non-condensing   Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280 g (9.9 oz.)   Compliance   Electrical safety. . . . . . . . . . . . . . . . . . . . . . designed to meet IEC 1010   EMI emissions/immunity. . . . . . . . . . . . . . . CISPR 11   CE Mark Compliance   This product meets applicable EU directive(s) as follows:   EMC directive   Immunity . . . . . . . . . . . . . . . . . . . . . . EN 50082–1:1994   Emissions . . . . . . . . . . . . . . . . . . . . . EN 55011:1991 Group I Class A at 10 meters   17   Download from Www.Somanuals.com. All Manuals Search And Download.   Mechanical Dimensions   Dimensions are given in inches [millimeters].   4.22 [107.19]   4.31   [109.5]   3.60 [91.44]   18   Download from Www.Somanuals.com. All Manuals Search And Download.   United States 512 795-8248   Australia 03 9879 5166, Austria 0662 45 79 90 0, Belgium 02 757 00 20,   Brazil 011 284 5011, Canada (Calgary) 403 274 9391,   Canada (Ontario) 905 785 0085, Canada (Québec) 514 694 8521,   China 0755 3904939, Denmark 45 76 26 00, Finland 09 725 725 11,   France 01 48 14 24 24, Germany 089 741 31 30, Greece 30 1 42 96 427,   Hong Kong 2645 3186, India 91805275406, Israel 03 6120092, Italy 02 413091,   Japan 03 5472 2970, Korea 02 596 7456, Mexico (D.F.) 5 280 7625,   Mexico (Monterrey) 8 357 7695, Netherlands 0348 433466, Norway 32 27 73 00,   Singapore 2265886, Spain (Barcelona) 93 582 0251, Spain (Madrid) 91 640   0085, Sweden 08 587 895 00, Switzerland 056 200 51 51, Taiwan 02 2377 1200,   United Kingdom 01635 523545   © Copyright 1999, 2000 National Instruments Corporation.   All rights reserved. CVI™, FieldPoint™, LabVIEW™, Lookout™, Measurement Studio™, and   ni.com™ are trademarks of National Instruments Corporation. Product and company names   mentioned herein are trademarks or trade names of their respective companies.   Download from Www.Somanuals.com. All Manuals Search And Download.   |