M060501
Issue 4, revised 09/98
Catalogue section 75
R
The Generator Controls Division of
ELD series
EARTH LEAKAGE DETECTOR UNITS
A range of versatile and economical earth leakage
detection relays. Each unit is housed in a robust, glass
filled nylon case: an aperture in the casing allows the
installation cabling to be passed through the integral
core balance transformer.
The electronic circuitry combines a stable amplification
of the transformer output with an ability to give high
sensitivity and fast operating speeds. Detection of an
earth fault results in the energisation and latching of the
unit's SPCO relay. The unit is reset by momentarily
removing the auxiliary supply.
Protection from excessive fault current and supply
transients are fitted as standard, as is filtering to allow use
with chopped waveform and variable drive applications.
A 'test' facility is supplied in the form of a button, either
pre-fitted into the unit's front facia or connected remotely.
Product Specification
Power supply:
operating voltages (ranges)
110V AC (100 – 120 V)
230 V AC (200 – 250 V)
415 V AC (380 – 440 V)
< 100mA
(all for 50/60Hz.)
Electrical connection on standard units is by a colour coded,
6 way flying lead, with terminal blocks available as an
option. Each unit may be mounted on a front panel or back-
plate using two 3mm threaded inserts; an optional mounting
assembly (part no. EMA) is also available for front access
back-plate mounting.
power consumption
Control:
trip levels
trip point accuracy
fixed and variable, 10mA to 30A
to BS4293
Relay output:
(ratings for resistive load)
Standard units include:
SPCO contacts, rated
3A @ 250V AC/30V DC,
1A @ 440V AC
ELD2 Basic unit, with 20mS typical trip time.
Fast response to earth leakage faults.
ELD4 As ELD2, but with longer trip delays, 80mS
to 5 secs. Prevents nuisance tripping in motor
protection circuits and allows time discrimination
in distribution networks.
Physical:
operating temperature
standard unit: –25 to +40°C
'HT' spec.: –25 to +60°C
approx. 330 g
weight (with EMA)
ELD5 As ELD4, but with an adjustable trip delay.
Available in various time ranges up to 2 seconds.
Connection (standard unit)
With options:–
RED
L1
GREEN
WHITE
'VS'
'HT'
'TB'
'RC'
Adjustable trip current (via front facia potentiometer.)
High temperature specification (to +60°C ambient).
Screw terminal connectors instead of flying leads.
Special calibration and 1m wiring for use with
remote CTs (for RTCs of >125mA).
External
Test
Button
ELD
Test
BLUE
Variations on our standard units and options are also
available: please call with your requirements.
When ordering, please specify:–
YELLOW
a) Product type number (ELD2, ELD5, etc.)
b) Auxiliary supply voltage
BLACK
L2 or N
c) Trip current (fixed, or variable range for VS option)
d) System frequency (50, 60 or 400 Hz.)
e) Trip delay time (fixed or variable, according to model)
f) Additional options, if required.
Dimensions (mm)
EMA
ELD
4
31
Accessories:–
162
136
EMA
Mounting assembly for ELD series.
Remote CTs A range of remote core balance/current
transformers, enabling specially
176
148
calibrated ELD units to be used with
larger cables. Available in a range of
sizes, with or without a magnetic screen
(see sheet M060101 for full details).
3
59
25
25
Frank W. Murphy Ltd.
Frank W. Murphy Ltd. en France
Frank W. Murphy Southern Division
Murphek Pty. Ltd.
Incorporating Modex Automation
Church Road, Laverstock, Salisbury U.K.
Tel: +33 (1) 30 76 26 26 Fax: +33 (1) 30 76 39 89 PO Box 1819, Rosenberg, Texas 77471, USA
1620 Hume Highway, Campbellfield, Vic. 3061 Australia
Tel: + 61 3 9358 5555 Fax: + 61 3 9358 5558
Direct usine Tel: + 44 1722 410697
Tel: + 1 281 342 0297 Fax: + 1 281 341 6006
email: sales@fwmurphy.com
Since 1939
Pour service en Français, tél: + 44 1722 410697
Frank W. Murphy Manufacturer
PO Box 470248, Tulsa, Oklahoma 74147, USA
Tel: + 1 918 627 3550 Fax: + 1 918 664 6146
email: sales@fwmurphy.com
Frank W. Murphy Pte, Ltd.
Murphy Switch of California
Murphy de Mexico S.A. de C.V.
email: sales@fwmurphy.co.uk
No. 2 Tuas South Street 2, Sprintecs Building
PO Box 900788, Palmdale, California 93590, USA Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje
02-01/02, Singapore 637895
Tel: + 1 805 272 4700 Fax: + 1 805 947 7570
email: sales@murphyswitch.com
San Luis Potosí, S.L.P. México 78384
Tel: + 52 48 206264 Fax: + 52 48 206336
email: murmexsl@sanluis.podernet.com.mx
Tel: + 65 863 1398 Fax: + 65 863 0208
email: fwmsales@fwmurphy.com.sg
Download from Www.Somanuals.com. All Manuals Search And Download.
|