| DVP-120 Installation & Operating Instructions   Download from Www.Somanuals.com. All Manuals Search And Download.   Figure 3-4 Normal System Display..................................................................................................................... 17   Figure 3-5 Sensor prompt.................................................................................................................................... 17   Figure 3-6 Alarm display..................................................................................................................................... 17   Figure 3-7 Alarm Silenced message .................................................................................................................... 18   Figure 3-8 Warning display................................................................................................................................. 18   Figure 3-9 Warning Silenced message ................................................................................................................ 18   Figure 3-10 Trouble display ................................................................................................................................ 18   Figure 3-11 Trouble Silenced message................................................................................................................ 19   Figure 3-12 Zone Signal display.......................................................................................................................... 19   Figure 3-13 Zone Signal Silenced message......................................................................................................... 19   Figure 3-14 Hardware Summary ......................................................................................................................... 20   Figure 3-15 Save Configuration? Prompt............................................................................................................ 20   Figure 3-16 Set Time of Day............................................................................................................................... 21   Figure 3-17 Enter Hours...................................................................................................................................... 21   Figure 3-18 Enter Minutes................................................................................................................................... 21   Figure 3-19 Set Day of the week ......................................................................................................................... 22   Figure 3-20 Load Default Configuration............................................................................................................. 22   Figure 3-21 Enter Password................................................................................................................................. 23   Figure 3-22 Password Prompt ............................................................................................................................. 23   Figure 3-23 Wrong Password Prompt ................................................................................................................. 23   Figure 3-24 Sensor Summary.............................................................................................................................. 24   Figure 3-25 Sensor Type ..................................................................................................................................... 24   Figure 3-26 Sensor’s Alarm Level ...................................................................................................................... 24   Figure 3-27 Sensor’s Warning Level................................................................................................................... 25   Figure 3-28 Sensor’s Range................................................................................................................................. 25   Figure 3-29 Relay Summary................................................................................................................................ 26   Figure 3-30 Relay Mode...................................................................................................................................... 26   Figure 3-31 Turn On Delay ................................................................................................................................. 26   Figure 3-32 Minimum on time ............................................................................................................................ 26   Figure 3-33 Horn Summary................................................................................................................................. 27   Figure 3-34 Horn Mode....................................................................................................................................... 27   Figure 3-35 Horn Turn On Delay........................................................................................................................ 27   Figure 3-36 Horn Minimum on time ................................................................................................................... 27   Figure 3-37 Strobe Summary............................................................................................................................... 28   Figure 3-38 Strobe Mode..................................................................................................................................... 28   Figure 3-39 Strobe Turn On Delay...................................................................................................................... 28   Figure 3-40 Strobe Minimum on time ................................................................................................................. 28   Figure 3-41 Zone Controls................................................................................................................................... 29   Figure 3-42 Zone Group Type............................................................................................................................. 29   Figure 3-43 Timer Days Selection....................................................................................................................... 30   Figure 3-44 Start Time Selection......................................................................................................................... 30   Figure 3-45 Stop Time Selection......................................................................................................................... 30   Figure 3-46 Sensor Selection............................................................................................................................... 30   Figure 3-47 Add/Remove sensor prompt............................................................................................................. 30   Figure 3-48 Rising Trip Point Entry.................................................................................................................... 31   Figure 3-49 Falling Trip Point Entry................................................................................................................... 31   Figure 3-50 Sensor Mode Selection..................................................................................................................... 31   Figure 3-51 Quorum Entry .................................................................................................................................. 31   Figure 3-52 Alarm Signals................................................................................................................................... 32   Figure 3-53 Buzzer Alarm Signal........................................................................................................................ 32   Figure 3-54 Horn Alarm Signal........................................................................................................................... 32   Figure 3-55 Strobe Alarm Signal......................................................................................................................... 33   Figure 3-56 Warning Signals............................................................................................................................... 33   Figure 3-57 Buzzer Warning Signal .................................................................................................................... 33   Figure 3-58 Horn Warning Signal ....................................................................................................................... 33   Figure 3-59 Strobe Warning Signal..................................................................................................................... 34   Figure 3-60 Trouble Signals ................................................................................................................................ 34   Figure 3-61 Buzzer Trouble Signal ..................................................................................................................... 34   Figure 3-62 Horn Trouble Signal ........................................................................................................................ 34   Figure 3-63 Strobe Trouble Signal ...................................................................................................................... 35   Revision 0.07   3 Download from Www.Somanuals.com. All Manuals Search And Download.   LIST OF TABLES   Table 2-1 Main Power Connections .................................................................................................................... 10   Table 2-2 Recommended Wire Gauge................................................................................................................. 10   Table 2-3 Connector to Sensor Channel Mapping............................................................................................... 11   Table 2-4 Sensor Connectors: Channel and Pin Assignments............................................................................. 11   Table 2-5 Relay Interface Signals and Connector Assignments.......................................................................... 12   Table 2-6 Horn & Strobe signals and Connector Assignments ........................................................................... 13   Table 2-7 Wire gauge for Horn & Strobe functions ............................................................................................ 13   Table 2-8 Macurco Transducers.......................................................................................................................... 14   Revision 0.07   4 Download from Www.Somanuals.com. All Manuals Search And Download.   1 INTRODUCTION   1.1 General Information   The DVP-120 Gas Detection and Ventilation Control Panel is a microcomputer based control panel used to   operate ventilation fans based on the inputs from remotely mounted gas transducers. The unit is fully tested   prior to leaving the factory, and is ready for operation after the wiring is complete and the user system   configuration is entered.   System wiring includes the main power connection for the DVP-120, current loop and power connections   between the remote sensors and the DVP-120, the fan control connections and/or alarm connections from the   DVP-120 to the building ventilation and automation systems. Refer to Figure 1-1 for a representative system-   wiring diagram.   The system configuration is entered by the user through the LCD display and keypad. Refer to Figure 1-2 for   equipment locations. The system display provides the user with the system status, and the status of each   configured sensor. In addition, all control functions of the DVP-120 may be accessed through the system   display and keypad.   1.2 Features   – Twelve analog (current loop) input channels   – Three 16A, 240 VAC SPDT fan/alarm relays   – Drivers for external Horn and Strobe   – Externally visible system, alarm and relay status indicators   – Externally visible LCD display showing the status of each transducer and relay   – External keypad for user selection of the transducer/alarm display and setting the configuration   (password protected)   – Up to three ventilation control zones can be defined   – Each zone can be controlled based on transducer signals and/or time of day   – Each relay is configurable for delay before activation and minimum on time   – Fail safe operation can be implemented   – Lockable Nema 1 type enclosure   – Modular input and output connectors   1.3 Compatible Macurco Transducers   Carbon Monoxide (CO):   – CM-2B – Solid State sensor with local concentration display (ppm)   – CM-3 – Electrochemical sensor with local concentration display (ppm)   Nitrogen Dioxide (NO):   – ND-2 – Electrochemical sensor with local concentration display (ppm)   Combustible Gasses (EX):   – GT-11A – Solid State Sensor   Revision 0.07   5 Download from Www.Somanuals.com. All Manuals Search And Download.   NOTE:   ENGINEER AND ARCHITECT SPECIFICATIONS   1. Power connections at the sensor are non-polarized.   Gas detection and exhaust fan control is provided by a Macurco DVP-120   system. This System will use CM-2B or CM-3 Carbon Monoxide (CO) to   current transducers, ND-2 Nitrogen Dioxide to current transducers or GT-   11A Combustible Gas to current transducers. Each transducer will measure   the level of the target gas and provide this information to the DVP-120 over   a 4-to-20 mA current loop. The Transducers are mounted in a standard 6"   x 6" electrical enclosure, and operate on low voltage (24 VDC).   2. DVP-120 connections are representative of J7, J8, J10, J11, J13 and J14.   CM-2B   GT-11A   output   mA   V output   power   power   output   B - A + D C D C - - + + All power and signal connections for the transducers are provided from the   DVP-120 control panel, via unshielded four conductor cable. The DVP-120   control panel provides three relays which can be used for ventilation fan   control or alarm signaling . These relays (SPDT - Form C) are for pilot duty   only, capable of switching 10 amp loads up to 240 VAC .   J7, J8,   J10, J11,   J13, L14   8 7 6 5 4 3 2 1 Main Fan Power   J2   - Strobe   + Strobe   - Horn   4 MACURCO DVP-120   GAS DETECTION AND   VENTILATION CONTROL PANEL   coil   3 2 1 Exhaust Fans   + Horn   Relay 1   Relay 2   Relay 3   coil   Panel Power   120/250 VAC   Gnd   120 VAC   ALARM   N L STARTER RELAYS   120 VAC COILS   1 2 3 4 5 6 7 8 9 J4   1 3 J2   120 VAC   Power   NOTE   1. Typical coverage for a CO sensor is 5000 sq. ft., 900 sq. ft. for combustible gasses.   Extra sensors may be needed near areas where people work, such as toll booths.   2. Macurco provides only the control panels and sensors. Fans, relays, and other devices are provided by the contractor.   3. See the appropriate building code for the size of fans and air changes per unit of time.   Typical layout in Parking Garage   exhaust fan   Air inlet:   door, damper,   louvier   DVP-120   panel   CM-2B,   CM-3 or   SS102HC-1   CM-2B,   CM-3 or   SS102HC-1   CM-2B,   CM-3 or   SS102HC-1   space sensors equally,   mount 5 feet above floor   Air inlet:   door, damper,   louvier   exhaust fan   Figure 1-1 System Wiring Diagram   Revision 0.07   6 Download from Www.Somanuals.com. All Manuals Search And Download.   Figure 1-2 DVP-120 Internal View   Revision 0.07   7 Download from Www.Somanuals.com. All Manuals Search And Download.   1.4 Specifications1   – Size:   10” x 12” x 2” (254 mm x 305 mm x 51 mm)   TBD   – Weight:   – Enclosure:   Nema 1 equivalent steel   – Operating Temperature:   0° to 50 °C (-32 to 122 °F)   – Operating Humidity:   – Power Input:   0% to 95% RH non-condensing   100 – 240 VAC, 1 Amp, 47 – 63 Hz, single phase   SPDT, 120/240 VAC, 16 A resistive   2 rows of 16 characters with backlight   Power, ALARM/warning, Silenced, Relay 1, Relay 2 & Relay 3   Internal buzzer, 90 dbA at 1ft   24VDC, maximum 250 mA   – Relay Rating (3):   – LCD Display:   – Status Indicators (LED):   – Audible indicator:   – External Drivers (2):   – CO Transducer Range:   – NO Transducer Range:   – EX Transducer Range:   – Relay On Delay:   0 – 250PPM   0 – 9.0 PPM   0 – 10,000 PPM   0 – 15 minutes in 1 second increments   0 – 15 minutes in 1 second increments   – Relay Off Delay:   1.5 Warranty   The DVP-120 Gas Detection and Ventilation Control Panel is warranted to be free from defective material and   workmanship for a period of two (2) years from the date of manufacture (stamped on the unit). If any   component becomes defective during the warranty period, it will be replaced or repaired free of charge, if the   unit is returned in accordance with the instructions below. This warranty does not apply to units that have been   altered or had repair attempted, or that have been subjected to abuse, accidental or otherwise. The above   warranty is in lieu of all other express warranties, obligations, or liabilities.   THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE   ARE LIMITED TO A PERIOD OF TWO (2) YEARS FROM THE PURCHASE DATE.   Macurco shall not be liable for any incidental or consequential damages for breach of this or any other warranty   express or implied, arising out of or related to the use of the control panel. Manufacturer or its agent’s liability   shall be limited to replacement or repair as set forth above. Buyer’s sole and exclusive remedies are return of   the goods and repayment of the price, or repair and replacement of non-conforming goods or parts. (The   Uniform Commercial Code applicable in the State of Colorado shall govern)   1.6 Return Instructions   Call (303) 781-4062 for a Return Authorization form. Then carefully pack the control panel with a written   description of the nature of the return. Send the unit to the following address:   Aerion Technologies Inc.   6555 S. Kenton St., Ste 304   Centennial, CO   USA 80111   1 Macurco reserves the right to modify or change the specifications of all products without prior   notification to the user.   Revision 0.07   8 Download from Www.Somanuals.com. All Manuals Search And Download.   2 Installation & Connection   2.1 Mounting the DVP-120   Mounting holes are provided in the DVP-120 case at the four corners. The top two are keyhole shaped so that   the panel can be hung and then the two bottom screws driven to hold the panel. Conduit entry holes are   provided on the top, bottom and right side of the panel. The panel should be mounted with sufficient space all   around, depending on the complexity of the installation.   Main power wiring should conform to national and local electrical codes, and may require separate inspections   and certification. Contact your local building authority for further details. If safety certification is required to   obtain your occupancy certificate, Macurco can contract to provide testing services to obtain certification (such   as the ETL label) by a national testing laboratory. Contact the Macurco Sales Department for further details.   2.2 General Wiring Information   WARNING   High voltage terminals (120/240 VAC) are located within the   DVP-120, presenting a hazard to service technicians. Only   qualified technicians should open the DVP-120 case and   service the internal circuits. Ensure power is removed from the   DVP-120 prior to servicing the unit.   With the exception of the safety ground, all field wiring is done via modular connectors (provided) so that the   wiring can be done easily and then simply plugging the modular connectors into the matching connectors on the   PCB.   The power and signal connections to the remote mounted sensors should be size AWG18 (minimum) for short   runs. Refer to Table 2-2 for recommended wire gauges. Four conductor cables may be used in all cases since   the DVP-120 employs DC power for remote sensors to prevent electrical noise from interfering with the sensor   output signal.   Do not bundle sensor power and/or signal connections with other AC power cables to prevent electrical   interference. If other AC power connections must be bundled with the DVP-120 sensor cables, Macurco   recommends that the sensor connections be made with two twisted pairs of the appropriate gauge, with an   overall foil and braid shield. All shields should be terminated at the DVP-120 end of the cable only. A ground   stud is provided near the bottom left corner of the panel.   Typical part numbers for AWG18 are:   – – Alphawire 55132   Belden TBD   Revision 0.07   9 Download from Www.Somanuals.com. All Manuals Search And Download.   2.3 Main power Connection   The main power cable should be routed into the bottom left conduit entry.   Macurco recommends a minimum wire size of AWG18. The modular connector will accept wire from 12 to 24   AWG.   The safety ground wire should be secured to the ground stud at the bottom left of the cabinet with the lock   washer and nut supplied. Macurco recommends the use of a ring terminal for the ground connection.   Refer to Table 2-1 for DVP-120 power connections.   The line and neutral wires should be stripped 1/4 in. (6.5 mm), insert the wire into the wire cavity of the   modular connector and tighten the screw clamp. Ensure that the wire cannot be easily pulled from the   connector. Plug the modular connector into J4 on the PCB and ensure that it latches into the header properly.   Signal   Line (120/220/240/250 VAC)   Neutral   Terminal Connection   J4-3   J4-1   Ground   Ground Stud   Table 2-1 Main Power Connections   2.4 Remote Sensor Connection   Each remote sensor is connected by a four-wire connection – two wires for DC power and two wires for the 4 –   20 mA loop connection. The sensors are connected to the control panel PCB with modular connectors, two   sensors per connector. See Figure 2-1 for a view of a typical sensor connector. Refer to Table 2-2 for wire size   recommendations.   1 8 Insert this face of connector   into mating connector on   control circuit board.   Figure 2-1 Sensor Interface Connector   Wire gauge   Maximum Run Length (ft.)   (feet)   500   800   (meters)   152   244   18   16   14   1250   381   Table 2-2 Recommended Wire Gauge   Revision 0.07   10   Download from Www.Somanuals.com. All Manuals Search And Download.   Each 8-terminal sensor modular connector may be disconnected from the PCB connector to ease wire   installation. The terminals will accept wire from 16 to 28 AWG. To install a wire, strip back approximately 0.25   in. (6 mm) of insulation, and insert the bare wire into the terminal. Tighten the screw clamp and ensure that the   wire cannot be easily pulled from the connector. Table 2-3 lists the connector to sensor channel correspondence.   While Table 2-4 lists channel signals, connector and terminal assignments for all 12 input channels.   Control Board Connector   Sensor Channels   J7   1, 2   3, 4   5, 6   J10   J13   J8   7, 8   J11   J14   9, 10   11, 12   Table 2-3 Connector to Sensor Channel Mapping   Signal Name   Connector Signal Name   -Pin   Connector Signal Name   -Pin   Connector   -Pin   Number   J7-5   J7-6   J7-7   J7-8   J7-1   J7-2   J7-3   Number   J13-5   J13-6   J13-7   J13-8   J13-1   J13-2   J13-3   J13-4   J8-5   J8-6   J8-7   J8-8   J8-1   J8-2   J8-3   J8-4   Number   J11-5   J11-6   J11-7   J11-8   J11-1   J11-2   J11-3   J11-4   J14-5   J14-6   J14-7   J14-8   J14-1   J14-2   J14-3   J14-4   CH 1 +24 Vdc   CH 1 +I loop   CH 1 -I loop   CH 1 24Vdc Ret   CH 2 +24 Vdc   CH 2 +I loop   CH 2 -I loop   CH 2 24Vdc Ret   CH 3 +24 Vdc   CH 3 +I loop   CH 3 -I loop   CH 3 24Vdc Ret   CH 4 +24 Vdc   CH 4 +I loop   CH 4 -I loop   CH 5 +24 Vdc   CH 5 +I loop   CH 5 -I loop   CH 5 24Vdc Ret   CH 6 +24 Vdc   CH 6 +I loop   CH 6 -I loop   CH 6 24Vdc Ret   CH 7 +24 Vdc   CH 7 +I loop   CH 7 -I loop   CH 7 24Vdc Ret   CH 8 +24 Vdc   CH 8 +I loop   CH 8 -I loop   CH 9 +24 Vdc   CH 9 +I loop   CH 9 -I loop   CH 9 24Vdc Ret   CH 10 +24 Vdc   CH 10 +I loop   CH 10 -I loop   CH 10 24Vdc Ret   CH 11 +24 Vdc   CH 11 +I loop   CH 11 -I loop   CH 11 24Vdc Ret   CH 12 +24 Vdc   CH 12 +I loop   CH 12 -I loop   CH 12 24Vdc Ret   J7-4   J10-5   J10-6   J10-7   J10-8   J10-1   J10-2   J10-3   J10-4   CH 4 24Vdc Ret   CH 8 24Vdc Ret   Table 2-4 Sensor Connectors: Channel and Pin Assignments   Revision 0.07   11   Download from Www.Somanuals.com. All Manuals Search And Download.   2.5 Relay Connection   All poles of the three relays are available at the modular connector J2 (see Figure 2-2 for details). J2 is a 9-   position variant of the high voltage modular connector used for power input. Each terminal can accommodate a   wire size 12 to 24 AWG.   1 9 Insert this face of connector   into mating connector on   control circuit board.   Figure 2-2 Relay Connector   To install the wiring for the relays, disconnect the connector from the header on the PCB. Strip the insulation of   each wire back approximately 1/4 in. (6.5 mm), insert the bare wire into the terminal and tighten the screw   clamp. Ensure that the wire cannot easily be pulled from the connector.   Note that the panel configuration can designate Relay-1 as an ALARM signal relay. Relay-2 and Relay 3 are   general purpose in function.   Refer to Table 2-5 for output signals, connector and terminal assignment for all three relays.   Signal Name   Connector-   Pin Number   J2-1   Signal Name   Connector-   Pin Number   J2-4   Signal Name   Connector-   Pin Number   J2-7   Relay 1 NC   Relay 2 NC   Relay 2 NC   Relay 1 NO   J2-2   Relay 2 NO   J2-5   Relay 2 NO   J2-8   Relay 1 Common   J2-3   Relay 2 Common   J2-6   Relay 2 Common   J2-9   Table 2-5 Relay Interface Signals and Connector Assignments   Revision 0.07   12   Download from Www.Somanuals.com. All Manuals Search And Download.   2.6 Horn & Strobe Connection   The external horn and strobe connections are available at the modular connector J5 (see Figure 2-3 for details).   J5 as a 4-position connector, similar to the sensor interface connectors.   1 4 Insert this face of connector   into mating connector on   control circuit board.   Figure 2-3 Horn & Strobe Connector   To install the wiring for the horn or strobe, disconnect the connector from the header on the PCB. Strip the   insulation of each wire back approximately 0.25 in. (6 mm), insert the bare wire into the terminal and tighten   the screw clamp. Ensure that the wire cannot easily be pulled from the connector.   When all wires are connected, seat the modular connector into the PCB header; ensure that the latch engages.   Refer to Table 2-6 for signals, connector and terminal assignment for the horn and strobe.   Signal Name   Connector-Pin   Number   J5-1   Signal Name   Connector-Pin   Number   J5-3   Horn +   Horn -   Strobe +   Strobe -   J5-2   J5-4   Table 2-6 Horn & Strobe signals and Connector Assignments   Refer to Table 2-7 for recommended wire gauge vs. run length for the horn & strobe functions (maximum 2.5   volt drop in the wire).   Maximum Run Length (ft.)   Wire gauge   (feet)   200   340   480   850   (meters)   61   103   147   215   24   22   20   18   Table 2-7 Wire gauge for Horn & Strobe functions   Revision 0.07   13   Download from Www.Somanuals.com. All Manuals Search And Download.   2.7 Interfacing Macurco Sensors   All Macurco CO, NO2 and combustible gas sensors with current loop outputs may be used with the DVP-120.   Data sheets for the Macurco sensors listed in Table 2-8 are provided as an appendix to this manual.   Power connections to Macurco sensors used with the DVP-120 are polarity-insensitive, since a bridge rectifier   is connected to the power input terminals. All sensors used with the DVP-120 panel employ screw clamp   terminal blocks for power and signal connections.   Polarity of the current loop connections is marked on the printed circuit board of the sensor.   Description   Order Part Number   CM-2B   Carbon Monoxide Transducer with solid-   state sensor   Carbon Monoxide Transducer with   Electro-chemical sensor   CM-3   Nitrogen Dioxide Transducer with a 5A   relay   ND-2   Combustible Gas Transducer   GT-11A   Table 2-8 Macurco Transducers   Revision 0.07   14   Download from Www.Somanuals.com. All Manuals Search And Download.   3 Operation   3.1 Initial Operating Mode   When power is first applied to the DVP-120, a few simple tests will be performed, e.g. cycle through all status   lights, and display the system name and model # (Figure 3-1). The system will then proceed to normal mode, if   the operating parameters have been entered.   DVP - 1 2 0 Ve r 1 . 0 1   Figure 3-1 Model Display   If the user has not entered any parameters, the system WILL NOT be monitoring the sensors or controlling the   ventilation system. The relays will be in the not actuated state and the horn and strobe outputs will be off. The   power status light will show NORMAL (steady green) and the system will immediately enter the   CONFIGURATION mode, see section 3.2 for details to set the configuration parameters.   If a valid set of configuration parameters have been entered the panel will wait for all sensors to warm up.   During this time, the display will show a count down, minutes and seconds, until the end of the warm-up period,   Figure 3-2.   D V P - 1 2 0 V e r . 1 . 0 1   W a r m - u p   2 : 3 0   Figure 3-2 Warm-Up display   During the warm-up period, the keypad will be locked. When the warm-up period ends, the LCD will start   showing the normal display, Figure 3-4.   3.1.1 Status Light Display   The POWER, ALARM/WARNING, SILENCE, RELAY 1, RELAY 2 and RELAY 3 status lights indicate the   system status and provide the following data:   ? ? POWER   ?Green (steady) – Power is good and there are no trouble indications   ?Yellow (steady) – Trouble is indicated by a transducer or the panel itself   ALARM/WARNING   ?Off   ?Red (steady)   – All indicated gas levels are below the warning level   – One or more gas levels is at or above the alarm level   ?Amber (steady) – One or more gas levels is at or above the warning level   SILENCE   ?Off   ? –There are no silenced alarms or warnings   ?Red (flashing) –There are alarms and/or warnings that have been silenced (gas levels may   or may not still be at alarm or warning levels)   ? ? ? RELAY 1   ?Off   ?Green (steady) – Relay 1 is on   RELAY 2   ?Off   ?Green (steady) – Relay 2 is on   RELAY 3   ?Off   ?Green (steady) – Relay 3 is on   – Relay 1 is not on   – Relay 2 is not on   – Relay 3 is not on   The overall system status is visible at a distance via the status lights as described above. More detailed system   information is displayed on the LCD, which can show the status of each relay and sensor. A typical status   display is shown in Figure 3-4.   Revision 0.07   15   Download from Www.Somanuals.com. All Manuals Search And Download.   3.1.2 User Interface   The LCD display is used to show detailed information about the status of the control system and the   configuration parameters to the user. The keypad (Figure 3-3) is used to select the information displayed and to   enter the configuration parameters, which are stored in the DVP-120 non-volatile memory. The keypad consists   of the usual ten digit keys, the normal four direction keys, plus a MENU key that is used to access the   configuration menu and a HUSH key that will silence the audible alarm indicators.   Figure 3-3 Keypad layout   In normal mode, no warnings or alarms that have not been silenced, the up and down cursor keys will scroll the   display to any configured sensors’ status.   In normal mode, the left and right cursor keys will scroll through all relays’ status. When the left (or right) key   is used to scroll to another relay the display will remove the underlining under the sensor number and underline   the relay number, this indicates that the digit keys can be used to jump directly to a particular relay’s status.   When the up or down key is again used the display will switch back to the digit keys jumping to a particular   sensor.   The MENU key has three functions. First, when the system is presenting the normal display, pressing the   MENU key will cause the system to shift to the Configuration Menu. The second function of the MENU key is   to return to the next-higher menu level, e.g. from the sensor configuration menu to the system menu, or from the   system menu out to normal mode. When the MENU key is used to return to normal mode, any changed   configuration parameters are saved in the DVP-120’s non-volatile memory. The third function of the MENU   key is to change the LCD contrast by holding the MENU key for five (5) seconds, at which point the LCD will   prompt for further activities, see sections 4.4 for more detail..   The HUSH key is only used to silence the audible indicators (internal buzzer and possible external Horn and   Strobe devices). Pressing and releasing the button will silence the internal buzzer. The HUSH button must be   held for 3 seconds to silence the Horn and Strobe devices. See sections 3.1.4, 3.1.5 and 3.1.6 for more detail.   In normal mode, holding the zero key for three (3) seconds can be used to lock the keypad against accidental (or   unauthorized) use. See section 4.5 for details.   Revision 0.07   16   Download from Www.Somanuals.com. All Manuals Search And Download.   3.1.3 Normal Status Display   MO N 1 0 : 2 3 R 1 O F F   S 0 1 C O 5 P P M   Figure 3-4 Normal System Display   The display shows the day of the week and the time of day, in 24-hour format. It also shows the status of one of   the relays, R1 in this example, and the type and indicated gas concentration of one of the configured sensors,   S01 is a CO sensor indicating 5 ppm in this example.   Notice in Figure 3-4 that the digits 01 are underlined, this indicates that the digit keys can be used to jump   directly to another sensor’s status. When the first digit is pressed, the display will prompt for the sensor to   display.   S h o w S e n s o r _ 1   Figure 3-5 Sensor prompt   In this example, the first digit entered was 1. Since the DVP-120 can handle 12 sensors, the first digit for a   sensor number is either 0 or 1. The leading zero must be entered when selecting a sensor less than ten. When the   second digit is entered, the normal display will be restored; showing the type and value for the selected sensor.   As mentioned above, the left and right scroll keys will display the next (previous) relay’s status. The display   will also change the underline to indicate that the digit keys (zero, one and two) can be used to jump directly to   a particular relay. Since only one digit is needed to select a relay, the system does it immediately rather than   prompting to show the relay.   If the sensor is indicating a gas level that is greater than the alarm or warning levels the gas reading will   alternate with the words ALARM or WARNING as appropriate. If the sensor is indicating a trouble condition   the gas reading will be replaced by the word TROUBLE.   3.1.4 ALARM Status Display   When any sensor indicates a gas level that is at or above the configured alarm level for the sensor, the panel will   enter ALARM mode, during which the internal buzzer will sound, the alarm lamp will be red and the LCD will   show the sensor type and channel number.   A L A RM   C O S E N S O R 0 2   Figure 3-6 Alarm display   The display will cycle through all sensors that are signaling alarm levels, at five seconds per display. Pressing   any key (except HUSH) will advance the display to the next sensor that is signaling an alarm level.   If an external horn and/or strobe are connected and configured to signal an alarm condition, they will also sound   when an alarm condition occurs, after a delay if that configuration option is used.   When the HUSH key is pressed, the internal buzzer will be silenced for five (5) minutes. If the horn or strobe   turn on delays have not finished then they will also be silenced. If the delays have finished the HUSH key must   be held for three (3) seconds in order to silence the horn and strobe.   When all indicators have been silenced, the display will show that alarms have been silenced for five minutes.   After any key press (or five seconds), the display will return to normal mode.   Revision 0.07   17   Download from Www.Somanuals.com. All Manuals Search And Download.   A L A RM S I L E N C E D   F O R 5 M I N U T E S   Figure 3-7 Alarm Silenced message   If Relay 1 has be configured as an ALARM relay it will be turned on when an alarm condition is recognized   and will be turned off when all audio indicators have been silenced.   Silencing applies to the cause(s) of the alarm when the HUSH key is pressed.   3.1.5 Warning Status Display   When any sensor indicates a gas level that is at or above the configured warning level for the sensor, the panel   will enter WARNING mode during which the internal buzzer will sound, the alarm/warning lamp will be amber   and the LCD will show the sensor type and channel number.   WA R N I NG   C O S E N S O R 0 2   Figure 3-8 Warning display   The display will cycle through all sensors that are signaling warning levels, at five seconds per display. Pressing   any key (except HUSH) will advance the display to the next sensor that is signaling a warning level.   If the buzzer and/or an external horn and/or external strobe are connected and configured to signal a warning   condition, they will also sound when a warning condition occurs. There is a configurable delay for the horn or   strobe will sound, see sections 3.3.5.3 and 3.3.6.3.   When the HUSH key is pressed, the internal buzzer will be silenced for fifteen (15) minutes. If the horn or   strobe turn on delays have not finished then they will also be silence. If the delays have finished, the HUSH key   must be held for three (3) seconds in order to silence the horn and strobe.   When all indicators have been silenced, the display will show that warnings have been silenced for fifteen   minutes. After any key is pressed (or five seconds) the display will return to normal mode.   WA R N I NG S I L E N C E D   F O R 1 5 M I N U T E S   Figure 3-9 Warning Silenced message   3.1.6 Trouble Status Display   If a sensor indicates a trouble, or the panel detects an internal fault, the panel will enter TROUBLE mode during   which the internal buzzer will sound, the power lamp will be yellow and the LCD will show the problem.   T R O U B L E   C O S E N S O R 0 2   Figure 3-10 Trouble display   The display will cycle through all trouble indications, at five seconds per display. Pressing any key (except   HUSH) will advance the display to the next trouble indicator.   If an external horn and/or strobe are connected and configured to signal a trouble condition, they will also sound   when a trouble condition occurs, after a delay if that configuration option is used.   Revision 0.07   18   Download from Www.Somanuals.com. All Manuals Search And Download.   When the HUSH key is pressed, the internal buzzer will be silenced for eight (8) hours. If the horn or strobe   turn on delays have not finished then they will also be silence. If the delays have finished, the HUSH key must   be held for three (3) seconds in order to silence the horn and strobe.   When all indicators have been silenced, the display will show that trouble indications have been silenced for   eight hours. After five seconds (or any key press), the display will return to normal mode.   T R O U B L E S I L E N C E D   F O R 8 H O U R S   Figure 3-11 Trouble Silenced message   3.2 Ventilation control   The ventilation control function operates independently from the alarm function. It provides the ability to   configure the DVP-120 for control of one to three zones. Each zone can respond to gas levels indicated by one   or more of the three types of sensors, with configurable turn on and turn off concentrations for each gas type.   Each zone can also be controlled based on the time of day and/or two of the sensor types.   Each zone can be configured to control one, two or all three of the relays and the external horn and strobe if   desired. When more than one zone is controlling a relay it only takes one zone to activate the relay, but all   controlling zones must release the relay before it will turn off.   Each of the relays, horn and strobe have independent turn on delays (to ignore short duration transients) and   turn off delays (to ensure minimum run times for fans that must run for internal cooling).   3.2.1 Zone Signal Display   When a zone is controlling the horn or strobe and they turn them on, the panel will enter ZONE SIGNAL mode   during which the horn and/or strobe will be turned on and the LCD will show the zone that is signaling.   Z O N E S I G N A L   Z O N E 1   Figure 3-12 Zone Signal display   The display will cycle through all zones that are controlling the horn or strobe and are signaling, at five seconds   per display. Pressing any key (except HUSH) will advance the display to the next zone that is signaling.   When the HUSH key is held for three (3) seconds, the horn and/or strobe will be silenced for fifteen (15)   minutes. When silenced, the display will show that zone signals have been silenced for fifteen minutes. After   any key is pressed (or five seconds) the display will return to normal mode.   Z O N E S I L E N C E D   F O R 1 5 M I N U T E S   Figure 3-13 Zone Signal Silenced message   Revision 0.07   19   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3 Setting the System Configuration   The configuration menus can be entered from normal mode by pressing the MENU key. While in configuration   mode, the user can review all configuration parameters to check the current operating conditions.   As an aid when configuring the control panel, the first entry in the top menu summarizes the number of sensors   and relays that the panel is currently recognizing.   5 S E N S O R S F O U N D   3 R E L A Y S F O U N D   Figure 3-14 Hardware Summary   The MENU key is also used to return to a higher-level menu and finally exit the configuration menus back to   normal mode.   When exiting from the menu system to normal mode, if any configuration changes have been made, the panel   will ask whether changes are to be saved,   S a v e C o n f i g . ?   ( 0 = N O , 1 = Y E S )   Figure 3-15 Save Configuration? Prompt   Pressing the zero (0) key at this point will cancel all changes except time and day of week. Pressing the one (1)   will save all changes to non-volatile memory, and the changes will then become effective in controlling the   ventilation system.   While the DVP-120 is in the configuration mode, alarm and ventilation control functions continue in the   background with the previously set configuration values. In particular, if an alarm condition is detected the   alarm lamp, the buzzer, the horn and the strobe will operate as configured but the LCD will not display the   detailed information. The HUSH key can be used to silence any alarm, warning or trouble indicators without   having to exit the configuration mode. If the MENU key is used to exit the configuration mode before using the   HUSH key, the LCD will display the cause of the audible indicator.   The numeric keys are used to change the particular parameter displayed. The underlined character, or space, on   each display indicates what will be changed by the digit keys.   The left and right cursor keys will enter the particular submenu and scroll through the items of the same type   where appropriate, e.g. enter the Configure Sensors submenu and scroll through the parameter lists for the   existing sensors.   The up cursor key scrolls through the menu entries in the order listed here, while the down cursor key scrolls in   the reverse order.   Changing the configuration parameters requires the entry of a password before changes can be made. The   password is 1234. See Figure 3-22 for an example of the password prompt.   In many cases the parameter is entered as a string of digits, but some parameters are selected by pressing a   single key, e.g. pressing 1 selects Monday, 2 selects Tuesday, etc.   Revision 0.07   20   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.1 System Menu   The top menu level allows the user to select:   – – – – – Configure System   Configure Sensors   Configure Relays, Horn & Strobe   Configure Zones   Configure Signals   The up and down cursor keys can be used to scroll through the entries in the list, while the left or right key will   enter the particular submenu.   The MENU key will return to normal mode, at which time the changes are saved in non-volatile memory   and become effective in controlling the ventilation system and for alarm level detection.   3.3.2 Configure System Submenu   The system configuration submenu provides entries to:   – – – Set the time of day, 24 hour format   Set the day of the week, day 1 is Monday   Load Default Configuration   3.3.2.1 Set Time of Day   T i m e : 2 2 : 5 5   D a y : T u e s d a y   Figure 3-16 Set Time of Day   This display example shows that the time is 22:55 (10:55 PM). The underlined characters indicate that the   numeric keys can be used to set the current time of day. When the first digit is entered (and after the password is   entred if required), the display will change to show that the hours portion of the time is currently being entered.   T i m e : 0 1 : 5 5   D a y : T u e s d a y   Figure 3-17 Enter Hours   In this example the first digit entered was 1 (one), and the panel is waiting for the second digit of hours to be   entered. If the second digit is not entered within five seconds, the time will revert to the previous value. After   the second digit of the hours is entered, the display will prompt for the minutes entry:   T i m e : 1 6 : 5 5   D a y : T u e s d a y   Figure 3-18 Enter Minutes   In this example, the hours (16) have been accepted and the panel is waiting for the minutes to be entered. If no   digits are entered for 5 seconds the entry will be finished without changing the minutes, however the hours will   be changed to the value entered.   Revision 0.07   21   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.2.2 Set Day of Week   T i m e : 2 2 : 5 5   D a y : 2 T u e s d a y   Figure 3-19 Set Day of the week   This display example shows that Tuesday is the current day of the week. The underline character indicates that   the day can be changed by entering the corresponding digit:   – – – – – – – 1 2 3 4 5 6 7 Monday   Tuesday   Wednesday   Thursday   Friday   Saturday   Sunday   3.3.2.3 Load Default Configuration   1 L o a d D e f a u l t   C o n f i g u r a t i o n   Figure 3-20 Load Default Configuration   When the one (1) digit is pressed, the panel will prompt for the password, even if it has been entered previously.   If the password is entered correctly, the panel will overwrite the existing configuration with the default   configuration. This operation is intended to restore the panel to a known basic condition if it is removed from   one installation and installed in another.   The default configuration is:   ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? Password   Sensors   1234   Undefined   Alarm levels   Alarm signals   Warning signals   Trouble signals   Warning Levels   Sensor Range   Relay 1   Relay 2   Relay 3   Horn   Strobe   CO = 200 ppm, HS = 5.0ppm, EX = 4,000 ppm   Buzzer = Intermittent, Horn = Intermittent, Strobe = Continuous   Buzzer = Double Tap, Horn = Off, Strobe = Off   Buzzer = Triple Tap, Horn = Off, Strobe = Off   CO = 200 ppm, HS = 5.0 ppm, EX = 4,000 ppm   CO = 200ppm, HS = 6.0 ppm, EX = 10,000 ppm   Normally off, 1 minute turn on delay, 1 minute minimum on time   Normally off, 1 minute turn on delay, 1 minute minimum on time   Normally off, 1 minute turn on delay, 1 minute minimum on time   Normally off, 1 minute turn on delay, 0 (zero) minimum on time   Normally off, 1 minute turn on delay, 0 (zero) minimum on time   Controls nothing, no sensors assigned, Voting mode, Quorum = 1   Controls nothing, no sensors assigned, Voting mode, Quorum = 1   Controls nothing, no sensors assigned, Voting mode, Quorum = 1   Zone1   Zone2   Zone3   Rising Trip Levels CO = 100 ppm, HS = 2.5ppm, EX = 2,000 ppm   Falling Trip Levels CO = 50 ppm, HS = 1.2 ppm, EX = 1,000 ppm   Revision 0.07   22   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.2.4 Enter Password   P a s s w o r d   * * * *   Figure 3-21 Enter Password   ? This display shows that the password is 4 digits long. When the first digit is entered, the panel will   show.   P a s s w o r d   _ _ _ 1   Figure 3-22 Password Prompt   ? ? If the password is not entered correctly the panel will display   W r o n g P a s s w o r d   Figure 3-23 Wrong Password Prompt   Once the current password has been entered, the panel will prompt for the configuration parameter   being changed.   Revision 0.07   23   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.3 Configure Sensors Submenu   There is a list of parameters for each sensor in the system, either currently wired or configured but presently   disconnected. The left and right cursor keys can be used to move from one sensor to another; doing so always   goes to the first display (summary). The up and down keys will scroll through the parameters for the particular   sensor.   3.3.3.1 Sensor Summary   S e n s o r 0 1   A : 2 0 0 W :   C O   5 0   Figure 3-24 Sensor Summary   This display example shows that the sensor on channel 01 has been configured as a Carbon Monoxide sensor   with an Alarm level of 200 ppm and a Warning level of 50 ppm.   Notice that the sensor number, 01 in this example, is underlined. This indicates that the digit keys can be used to   jump to a particular channel, even if there is no sensor connected to the channel. When the first digit is entered,   the display will prompt for the sensor to show.   3.3.3.2 Sensor Type   S e n s o r 0 1   T y p e : 1   C O   Figure 3-25 Sensor Type   This display example shows that the sensor on channel 01 has been configured as a Carbon Monoxide sensor.   The valid entries for the sensor type are:   – – – – 1 2 3 0 Carbon Monoxide   Nitrogen Dioxide   Combustible   None   (CO)   (NO2)   (EX)   (---)   Setting the sensor type to 0 (zero) will cause the display to ask if the user wants to DELETE the sensor. If the   answer is yes, the configuration record for this sensor channel will be deleted and the channel will no longer be   used to control the ventilation system. If a sensor indicates trouble (or there are wiring problems on a channel),   this will stop any annoying trouble signals for this channel.   When a sensor’s type is changed, the alarm level, warning level and range will be set to the default for the   sensor type.   The following three parameters are not accessible until a sensor type of 1, 2 or 3 is selected.   3.3.3.3 Alarm Set Point   S e n s o r 0 1   A l a r m :   C O   _ 2 0 0 p p m   Figure 3-26 Sensor’s Alarm Level   The default alarm levels for the sensors are:   – – – Carbon Monoxide   Nitrogen Dioxide   Combustible   200 ppm   5.0 ppm   4,000 ppm (10% LEL for methane)   Setting an alarm level of 0 (zero) will disable alarm detection for this particular sensor.   Revision 0.07   24   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.3.4 Warning Set Point   S e n s o r 0 1   C O   W a r n i n g : _ _ 5 0 p p m   Figure 3-27 Sensor’s Warning Level   The default warning levels for the sensors are:   – – – Carbon Monoxide   Nitrogen Dioxide   Combustible   50 ppm   3.0 ppm   2,000 ppm (5% LEL for methane)   Setting a warning level of 0 (zero) will disable warning detection for this particular sensor.   3.3.3.5 Range   S e n s o r 0 1   R a n g e :   C O   _ 2 0 0 p p m   Figure 3-28 Sensor’s Range   The range for each sensor is the gas concentration that corresponds to the 20 mA signal level.   The default range values for the sensors are:   – – – Carbon Monoxide   Nitrogen Dioxide   Combustible   200 ppm   6.0 ppm   10,000 ppm (25% LEL for methane)   Revision 0.07   25   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.4 Configure Relays, Horn & Strobe Submenu   There is a list of parameters for each relay in the system. The left and right cursor keys can be used to move   from one relay, horn or strobe to another. Doing so always goes to the first (summary) display. The up and   down keys will scroll through the parameters for the particular relay, horn or strobe.   3.3.4.1 Relay Summary   R e l a y 1 N o r m . O f f   D e l a y O n , M i n . O n   Figure 3-29 Relay Summary   This display example shows that Relay 1 is configured to operate Normally Off, with a turn on delay and a   minimum on time.   Notice that the relay number, 1 in this example, is underlined. This indicates that the digit keys can be used to   jump to a particular relay, horn or strobe. The relays are numbers 1, 2 and 3; the horn is number 4 and the strobe   is 5.   3.3.4.2 Relay Mode   R e l a y 1 N o r m . O f f   M o d e : 2   Figure 3-30 Relay Mode   This display example shows that relay 1 is configured to operate in the Normally Off mode. The relay modes   are:   – – – 1 2 3 ALARM   Normally Off (default)   Normally On   Relay mode 1 is a special case. This mode is only available on relay 1 and dedicates the relay to function as an   alarm signal to a subsequent alarm or monitoring panel. This mode forces the relay to normally off mode with   no turn on delay or minimum on time. See section 3.1.4 for more detail regarding alarms   Fail Safe operation can be implemented by configuring a relay to operate Normally On, and wiring the circuit   using the NC (normally closed) contact. In this way, if the control panel looses power the relay will turn on the   controlled device if it still has power.   3.3.4.3 Relay Turn On Delay   R e l a y 1 D e l a y O n   ( mm : s s ) 0 1 : 0 0   Figure 3-31 Turn On Delay   The default turn on delay is one minute and the maximum allowed value is fifteen minutes. The value is entered   in two groups, 2 digits for the minutes and then 2 digits for the seconds. A leading zero must be entered for each   group if applicable.   3.3.4.4 Relay Minimum On Time   R e l a y 1   M i n . O n   ( mm : s s ) 0 1 : 0 0   Figure 3-32 Minimum on time   The default minimum on time is one minute and the maximum allowed value is fifteen minutes.   Revision 0.07   26   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.5 Configure Horn Submenu   The configuration parameters for the horn are the same as those for relays. A horn would not normally require a   minimum on time but this parameter allows a more versatile configuration.   3.3.5.1 Horn Summary   H o r n 4   N o r m . O f f   D e l a y O n   Figure 3-33 Horn Summary   This display example shows that the horn has been configured to operate Normally Off, with a turn on delay   and no minimum on time.   Notice that the horn number, 4, is underlined. This indicates that the digit keys can be used to jump to a   particular relay, horn or strobe. The relays are numbers 1, 2 and 3; the horn is number 4 and the strobe is 5.   3.3.5.2 Horn Mode   H o r n   N o r m . O f f   M o d e : 2   Figure 3-34 Horn Mode   This display example shows that the horn is configured to operate in the Normally Off mode. The valid modes   are:   – – 2 3 Normally Off (default)   Normally On   3.3.5.3 Horn Turn On Delay   H o r n   D e l a y O n   ( mm : s s ) 0 1 : 0 0   Figure 3-35 Horn Turn On Delay   The default turn on delay is one minute and the maximum allowed value is fifteen minutes.   3.3.5.4 Horn Minimum On Time   H o r n   M i n . O n   ( mm : s s ) 0 0 : 0 0   Figure 3-36 Horn Minimum on time   The default minimum on time is zero and the maximum allowed value is fifteen minutes.   Revision 0.07   27   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.6 Configure Strobe Submenu   The configuration parameters for the strobe are the same as those for relays. A strobe would not normally   require a minimum on time but this parameter allows a more versatile configuration.   3.3.6.1 Strobe Summary   S t r o b e 5 N o r m . O f f   D e l a y O n   Figure 3-37 Strobe Summary   This display example shows that the strobe has been configured to operate Normally Off, with a turn on delay   and no minimum on time.   Notice that the strobe number, 5, is underlined. This indicates that the digit keys can be used to jump to a   particular relay, horn or strobe. The relays are numbers 1, 2 and 3; the horn is number 4 and the strobe is 5.   3.3.6.2 Strobe Mode   S t r o b e   M o d e : 2   N o r m . O f f   Figure 3-38 Strobe Mode   This display example shows that the strobe is configured to operate in the Normally Off mode. The valid modes   are:   – – 2 3 Normally Off (default)   Normally On   3.3.6.3 Strobe Turn On Delay   S t r o b e   D e l a y O n   ( mm : s s ) 0 1 : 0 0   Figure 3-39 Strobe Turn On Delay   The default turn on delay is one minute and the maximum allowed value is fifteen minutes.   3.3.6.4 Strobe Minimum On Time   S t r o b e   M i n . O n   ( mm : s s ) 0 0 : 0 0   Figure 3-40 Strobe Minimum on time   The default minimum on time is zero and the maximum allowed value is fifteen minutes.   Revision 0.07   28   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.7 Configure Zones Submenu   The DVP-120 ventilation control can support up to three zones. The zone functionality makes the DVP-120   very flexible. For example, each zone can be configured to monitor a separate set of 4 sensors and control a   single relay.   Another control scheme uses one zone to monitor all sensors and turn one relay on at a relatively low gas   concentration. A second zone monitors the same sensors and turns on a second relay if the gas concentration   reaches a higher level. The third zone can also monitor the same relays turning the last relay on as a signaling   device to a live monitor station, as well as turning on the external horn and strobe, under the assumption that the   ventilation system is not working.   In addition to controlling the relays based on the gas concentration, each zone can have a timed function, e.g.   turn on low volume ventilation fans at 7:00 AM and turn them off at 8:00 PM.   3.3.7.1 Zone Controls   Z o n e 1 C o n t r o l s   R 1 R 2 R 3 H 4 S 5   Figure 3-41 Zone Controls   This display example shows that Zone 1 is configured to control all of the relays plus the horn and the strobe.   Each of the relays, the horn and the strobe can be removed from (or added to) the zones control by pressing the   indicated digit key. By default, all three zones are configured not to control any devices. When a new panel is   first powered up this display will not show the digits, only the underlined positions.   The digit controls are:   – – – – – 1 2 3 4 5 Relay 1 added/removed form the zone’s control   Relay 2 added/removed form the zone’s control   Relay 3 added/removed form the zone’s control   Horn added/removed form the zone’s control   Strobe added/removed form the zone’s control   When controlled by a zone the default horn pattern is the Triple Tap pattern, see 3.3.8.7 and the strobe will turn   on continuously when a zone is controlling them.   Each zone can have up to three control groups defined. Each group either monitors a sensor type or implements   a timer function.   3.3.7.2 Zone Group Mode   Z 1 G r o u p 1   S e n s o r T y p e : 2   Figure 3-42 Zone Group Type   N O 2   This display example shows that group 1 in zone 1 will be monitoring Nitrogen Dioxide sensors. The valid   Modes are:   – – – – 0 1 2 3 Timed   Carbon Monoxide (CO)   Nitrogen Dioxide (NO2)   Combustible (EX)   Timed mode turns the zone’s outputs on at the START TIME if the current day is a weekday (or a weekend)   and turns them off at the next occurrence of STOP TIME. The other three modes turn the outputs on if the gas   concentration indicated by that type of sensor is at or above the Rising Trip Point and turns the outputs off if the   concentration is less than or equal to the Falling Trip Point.   Revision 0.07   29   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.7.3 Timed Day Selection   Z 1 G r o u p 1 T i m e d   D a y s : 1 W e e k d a y s   Figure 3-43 Timer Days Selection   Valid entries are:   – – 1 Weekdays, Monday thru Friday, (default)   2 Weekends, Saturday and Sunday   3.3.7.4 Start Time   Z 1 G r o u p 1 T i m e d   S t a r t T i m e : 0 7 : 0 0   Figure 3-44 Start Time Selection   The start time is entered in 24-hour format and the default value is 07:00 (7:00 AM).   3.3.7.5 Stop Time   Z 1 G r o u p 1 T i m e d   S t o p T i m e : 1 8 : 0 0   Figure 3-45 Stop Time Selection   The stop time is entered in 24-hour format and the default value is 18:00 (7:00 PM).   3.3.7.6 Sensor Selection   Z 1 G r o u p 1   N O 2   S e n s o r s : 0 2 , 0 4 , 1 1   Figure 3-46 Sensor Selection   Sensors are included or removed from the group by entering the two-digit channel number. After a sensor is   added or removed the list will be re-sorted so it does not matter in which order the sensors are added or   removed. The default is to include all sensors of the specified type.   When the first digit of a sensor number is entered (a leading zero must be entered if the number is less than ten),   the display will prompt to Add or Remove a sensor from the group.   Z 1 G r o u p 1   N O 2   A d d / R e m o v e : _ 0   Figure 3-47 Add/Remove sensor prompt   When the second digit is entered, the sensor will be added or removed from the control group, provided the   sensor is of the proper type, NO2 in this example. If the sensor is of the wrong type, or an invalid sensor   channel number is entered the request will be simply ignored.   Revision 0.07   30   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.7.7 Rising Trip Point   Z 1 G r o u p 1   R i s i n g :   N O 2   2 . 5 p p m   Figure 3-48 Rising Trip Point Entry   The default rising trip points are:   – – – Carbon Monoxide 100 ppm   Nitrogen Dioxide   Combustible   2.5ppm   2,000 ppm   3.3.7.8 Falling Trip Point   Z 1 G r o u p 1   F a l l i n g :   N O 2   1 . 0 p p m   Figure 3-49 Falling Trip Point Entry   The default falling trip points are:   – – – Carbon Monoxide   Nitrogen Dioxide   Combustible   50 ppm   1.2 ppm   1,000 ppm   3.3.7.9 Multiple Sensor Mode   Z 1 G r o u p 1   N O 2   M o d e :   2 V o t i n g   Figure 3-50 Sensor Mode Selection   When multiple sensors are being monitored by a group the output decision can be based on either voting, as   shown here, or the average of all sensors in the group. Valid modes are:   – – 1 2 Average   Voting   When the configuration is Average, the gas concentrations from all sensors in the group are averaged and if the   average is greater than or equal to the rising trip point the zone outputs(s) are activated. When the average is   less than or equal to the falling trip point the zone output(s) are de-activated. If the average is between the two   trip points, the outputs remain in there previous state.   When the configuration is Voting, the number of sensors in the group indicating a value greater than or equal to   the rising trip point is counted. If the count is greater than or equal to the quorum then the zone output(s) are   activated. If the count of sensors indicating less than or equal to the falling trip point is greater than or equal to   the quorum the zone output(s) are de-activated. Activating the output(s) is given priority if a group has an equal   number of sensors with gas readings ? the rising trip point and sensors with readings ? the falling trip point.   3.3.7.10 Multiple Sensor Quorum   Z 1 G r o u p 1   Q u o r u m : _ 2   N O 2   Figure 3-51 Quorum Entry   It is up to the installer to ensure that the quorum entry is appropriate for the configuration. Valid entries are one   to twelve, but a value greater than the number of sensors being monitored by the group, stops the group from   controlling the outputs.   Revision 0.07   31   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.8 Configure Signals Submenu   The DVP-120 can drive the buzzer, horn and strobe with different sound patterns to indicate the severity of the   current conditions. These patterns are selectable by the installer using this group of submenus. Once again, the   left and right keys will scroll through the signal types and the up and down keys will scroll to the signal sources.   3.3.8.1 Alarm Signal Summary   The alarm signals are in response to one or more sensors indicating gas levels at or above the sensors’   configured alarm level.   A l a r m S i g n a l s   B u z z , H o r n , S t r o b e   Figure 3-52 Alarm Signals   This display example shows that alarms are signaled by the internal Buzzer, the external horn and the strobe.   3.3.8.2 Alarm Buzzer Signal   A l a r m S i g n a l s   B u z z : 2 I n t e r m i t .   Figure 3-53 Buzzer Alarm Signal   This display example shows that the buzzer will signal an alarm condition with an intermittent signal. The   signal definitions are:   – – – – – 1 2 3 4 5 Continuous   Intermittent, one second on at two second intervals (default)   Double Tap, two beeps at 5 second intervals   Triple Tap, three short beeps at 15 second intervals   Off, buzzer will not sound   3.3.8.3 Alarm Horn Signal   A l a r m S i g n a l s   H o r n : 2 I n t e r m i t .   Figure 3-54 Horn Alarm Signal   This display example shows that the buzzer will signal an alarm condition with an intermittent signal. The   signal definitions are:   – – – – – 1 2 3 4 5 Continuous   Intermittent, one second on at two second intervals (default)   Double Tap, two beeps at 5 second intervals   Triple Tap, three short beeps at 15 second intervals   Off, horn will not sound   Revision 0.07   32   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.8.4 Alarm Strobe Signal   A l a r m S i g n a l s   S t r o b e : 1 C o n t i n .   Figure 3-55 Strobe Alarm Signal   This display example shows that the strobe will signal an alarm condition with a continuous signal. The signal   definitions are:   – – – – – 1 2 3 4 5 Continuous (default)   Intermittent, one second on at two second intervals   Double Tap, two beeps at 5 second intervals   Triple Tap, three short beeps at 15 second intervals   Off, strobe will not flash   3.3.8.5 Warning Signal Summary   The warning signals are in response to one or more sensors indicating gas levels at or above the sensors’   configured warning level.   W a r n i n g S i g n a l s   B u z z   Figure 3-56 Warning Signals   This display example shows that warnings are signaled by the internal Buzzer only.   3.3.8.6 Warning Buzzer Signal   W a r n i n g S i g n a l s   B u z z : 5   O F F   Figure 3-57 Buzzer Warning Signal   This display example shows that the buzzer will not signal a warning condition. The signal definitions are:   – – – – – 1 2 3 4 5 Continuous   Intermittent, one second on at two second intervals   Double Tap, two beeps at 5 second intervals   Triple Tap, three short beeps at 15 second intervals   Off, buzzer will not sound (default)   3.3.8.7 Warning Horn Signal   W a r n i n g S i g n a l s   H o r n : 5   O F F   Figure 3-58 Horn Warning Signal   This display example shows that the horn will not signal a warning condition. The signal definitions are:   – – – – – 1 2 3 4 5 Continuous   Intermittent, one second on at two second intervals   Double Tap, two beeps at 5 second intervals   Triple Tap, three short beeps at 15 second intervals   Off, horn will not sound (default)   3.3.8.8 Warning Strobe Signal   W a r n i n g S i g n a l s   Revision 0.07   33   Download from Www.Somanuals.com. All Manuals Search And Download.   S t r o b e : 5   O F F   Figure 3-59 Strobe Warning Signal   This display example shows that the strobe will not signal a warning condition. The signal definitions are:   – – – – – 1 2 3 4 5 Continuous   Intermittent, one second on at two second intervals   Double Tap, two beeps at 5 second intervals   Triple Tap, three short beeps at 15 second intervals   Off, strobe will not flash (default)   3.3.8.9 Trouble Signal Summary   The trouble signals are in response to one or more sensor faults, either as a defined current level, or because of   wiring problems   T r o u b l e S i g n a l s   B u z z   Figure 3-60 Trouble Signals   This display example shows that troubles are signaled by the internal Buzzer only.   3.3.8.10 Trouble Buzzer Signal   T r o u b l e S i g n a l s   B u z z : 4   T r i p l e   Figure 3-61 Buzzer Trouble Signal   This display example shows that the buzzer will signal a trouble condition with a triple tap signal. The signal   definitions are:   – – – – – 1 2 3 4 5 Continuous   Intermittent, one second on at two second intervals   Double Tap, two beeps at 5 second intervals   Triple Tap, three short beeps at 15 second intervals (default)   Off, buzzer will not sound   3.3.8.11 Trouble Horn Signal   T r o u b l e S i g n a l s   H o r n : 5   O F F   Figure 3-62 Horn Trouble Signal   This display example shows that the horn will not signal a trouble condition. The signal definitions are:   – – – – – 1 2 3 4 5 Continuous   Intermittent, one second on at two second intervals   Double Tap, two beeps at 5 second intervals   Triple Tap, three short beeps at 15 second intervals   Off, horn will not sound (default)   Revision 0.07   34   Download from Www.Somanuals.com. All Manuals Search And Download.   3.3.8.12 Trouble Strobe Signal   T r o u b l e S i g n a l s   S t r o b e : 5 O F F   Figure 3-63 Strobe Trouble Signal   This display example shows that the strobe will not signal a trouble condition. The signal definitions are:   – – – – – 1 2 3 4 5 Continuous   Intermittent, one second on at two second intervals   Double Tap, two beeps at 5 second intervals   Triple Tap, three short beeps at 15 second intervals   Off, strobe will not flash (default)   Revision 0.07   35   Download from Www.Somanuals.com. All Manuals Search And Download.   4 Troubleshooting   The DVP-120 is extensively tested at the factory to ensure reliable operation. Most problems can be traced to   the set-up of configurable features and modes, system wiring or trouble with the sensors.   4.1 System Status Light Flashing   The system status light (section 3.1.1) is normally green indicating power is present, but will change to yellow   whenever the controlling firmware detects a trouble condition. Possible trouble conditions are   – – – – Any configured channel has less than 4 mA flowing in the current loop   A sensor is reporting a trouble condition   Any configured channel wiring is open.   Internal controller board problems are detected.   4.1.1 Input Channel Trouble   Any time the POWER light is yellow, the first thing the technician should consider is that one of the input   channels is in trouble. Reviewing the Sensor Status displays (using the up and down keys), should reveal which   channel has a problem since the gas reading will be replaced with the word TROUBLE.   A common source of trouble is an input channel that is configured for a sensor that does not exist. In this case,   the system expects to see current flowing within the current loop, but there cannot be current if there is no   sensor connected. Either fix the miss-wired sensor, or change the sensor type to NONE, section 3.3.3.2. After   returning to normal mode (using the MENU key), the power light should return to steady green.   If all channels are configured properly, another source of trouble could be the type of sensor attached to an input   channel. Macurco Toxic sensors can indicated high gas concentrations with signals of up to 24 mA in the   current loop. However, the combustible sensor (GT-11A) can indicate trouble with a 21 mA signal. Therefore, a   Toxic sensor connected to channel which is configured for a combustible sensor can cause a fault indication if   the gas concentration is high enough.   All Macurco sensors are either supplied with a STATUS lamp that will indicate the health of the device, or will   display a trouble message on the digital display. Macurco sensors may be tested by depressing the TEST button   on the sensor printed circuit board, or (depending on the type of sensor), the button on the interior front panel of   the unit. Macurco sensors will step the output current level from 4 mA to 20 mA over the course of the warm-up   period, allowing the technician to determine where the trouble exists. If the sensor is still in trouble, resetting   the power may clear the trouble. Remove one of the power wires from the sensor terminal strip causing the   sensor to go through a power-up reboot.   Finally, the wiring between the DVP-120 and the sensor should be investigated. The power input to the sensor   should be investigated at the sensor. Since Macurco sensors are rated for operation between 12 and 24 VDC or   VAC, the voltage drop between the DVP-120 and the sensor should not be an issue if the wiring guidelines in   Table 2-2 are followed. A multimeter can be inserted to check the current flow within the loop, or a continuity   test can be performed on all four wires between the DVP-120 and the sensor. Ensure power is removed from the   DVP-120 prior to removing the input or output connectors from the DVP-120 controller board.   Each sensor channel is provided with a PTC-resettable fuse internal to the DVP-120 to protect against over   current situations. To reset a sensor channel, power should be removed from the channel. This can be   accomplished by removing power from the sensor – causing the loop current to go to zero, or by completely   removing power from the DVP-120.   4.1.2 Internal Controller Board Trouble   If the sensor status display and investigative efforts reveal no problems with the input channel current loops and   channel configuration, the most likely trouble is an internal problem detected by the DVP-120 controller. In this   case, contact the Macurco Technical Department for advice and help.   4.2 Timed ventilation problem   When using the timed ventilation mode the system clock should be checked regularly (at least twice a year).   The battery backed real time clock in the DVP-120 does not adjust for daylight saving time so the spring and   fall switch over points are good choices to check the system clock.   Revision 0.07   36   Download from Www.Somanuals.com. All Manuals Search And Download.   4.3 No Power   WARNING   120/240 VAC terminals are located within the DVP-120,   presenting a hazard to service technicians. Only qualified   technicians should open the DVP-120 case and service the   internal circuits. Ensure power is removed from the DVP-120   prior to servicing the unit.   The DVP-120 starts up as soon as power is applied to the microcontroller, and the DVP-120 is designed to have   power continuously applied to the unit. An external indication of successful power application to the unit is the   immediate operation of the Status Lamps grouped around the LCD. If the operator does not see immediate   response from the status lamps, power should be checked at J4 (refer to Figure 1-2 for connector locations).   If the correct voltage is noted at J4, then the internal fuse of the DVP-120 should be investigated. The DVP-120   is protected from over-current and transient situations by the fuse at F3. AFTER removing power from the   DVP-120, F3 can be checked by removing the safety cover. If necessary, replace F3 with a 5x20 mm SLO-BLO   fuse with a rating of 1 Amp 250V, e.g. Littlefuse P/N 218001. Be sure to REPLACE THE SAFETY COVER on   F3 before re-applying power to the DVP-120.   4.4 LCD Display unreadable   It is possible that the LCD is unreadable due to temperature or aging of the control panel. If this is the case the   following steps should rectify the problem:   4.4.1 Hold the MENU key for three (3) seconds.   After three seconds, the power led will turn red. After a further two seconds, the LCD backlight will also be   turned off.   4.4.2 Press the UP and DOWN cursor keys to change the LCD contrast.   Each press of the UP or DOWN cursor key will change the contrast by a step in that direction. Adjust the   contrast for best viewing.   4.4.3 Press any other key to exit the contrast-setting mode.   4.5 The Keypad does not respond (LCD shows KEYS LOCKED)   The keypad can be unlocked by holding the zero (0) key for three seconds. At which time the backlight will turn   on and the display will return to normal mode..   The keypad can again be locked by holding the zero key for three seconds, until the display shows KEYS   LOCKED.   4.6 After a power failure   After any power failure, the user should check the system clock. While system parameters are maintained in   non-volatile memory, the system clock is backed-up by a limited-capacity button cell battery. Even though the   button cell can run the clock for several years, it will eventually wear out.   Revision 0.07   37   Download from Www.Somanuals.com. All Manuals Search And Download.   |