USA & Canada
(800) 421-1587 & (800) 392-0123
(760) 438-7000
Toll Free FAX (800) 468-1340
INSTALLATION AND
OWNER’S MANUAL
AUJ-S & AUH-S
AU SERIES WITH SOLID STATE CONTROL CIRCUITRY
JACKSHAFT COMMERCIAL
VEHICULAR DOOR OPERATORS
107172
Serial #:
READ THIS MANUAL
Date Installed:
CAREFULLY BEFORE
Your Dealer:
As of date of manufacture,
meets all ANSI/UL 325
Safety Requirements for
Vehicular door operators.
INSTALLATION OR USE
SAVE THESE INSTRUCTIONS !
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT FEATURES
3
Momentary Contact To Close: Standard operating mode.
Requires a photo-beam as described above or one of the Miller
Edge family of Door Edge devices as described on this page to
be properly installed on the door and connected to the
operator. See Page 12 for the entrapment protection
installation guide.
The purpose of this booklet is to provide assembly, installation
and operation information concerning Model AUJ-S & AUH-S
Commercial Vehicular Garage Door Operators and related
Accessory Products.
NOTICE
JACKSHAFT OPERATOR APPLICATIONS
IT IS IMPORTANT THAT THIS INSTRUCTION MANUAL BE
READ AND UNDERSTOOD COMPLETELY BEFORE
INSTALLATION OR OPERATION IS ATTEMPTED. IT IS
INTENDED THAT THE INSTALLATION OF THIS UNIT WILL
BE DONE ONLY BY PERSONS TRAINED AND QUALIFIED
IN THE INSTALLATION, ADJUSTMENT AND SERVICE OF
COMMERCIAL OVERHEAD DOORS AND DOOR
Jackshaft operators are intended for commercial and industrial
use to raise or lower sectional overhead doors by chain coupling
or direct coupling to the door shaft. Jackshaft operators are
suitable where all or part of the door remains in a vertical position
when fully open such as doors with at least 18 inches of lift
clearance or full vertical lift doors. Jackshaft operators may also
be used with roll up service doors and grills when appropriately
modified at the factory to obtain the correct speeds.
OPERATORS AND BY QUALIFIED ELECTRICIANS.
NOTICE
A jackhaft operator DOES NOT LOCK THE DOOR IN ITS
CLOSED POSITION. However, because the cross-header
shaft is prevented by the operator from turning, the torsion
springs provide no assistance in lifting the door should an
attempt be made to raise it manually.
THE IMPORTANT SAFEGUARDS AND INSTRUCTIONS IN
THIS MANUAL CANNOT COVER ALL POSSIBLE
CONDITIONS AND SITUATIONS WHICH MAY OCCUR
DURING ITS USE. IT MUST BE UNDERSTOOD THAT
COMMON SENSE AND CAUTION MUST BE EXERCISED
BY THE PERSON(S) INSTALLING, MAINTAINING AND
OPERATING THE EQUIPMENT DESCRIBED HEREIN. DO
NOT USE THIS EQUIPMENT FOR ANY OTHER THAN ITS
INTENDED PURPOSE - OPERATING OVERHEAD
COMMERCIAL VEHICULAR GARAGE DOORS.
The jackshaft operators as described in this manual are
used in the following applications:
- Continuous Duty, Medium Cycle Commercial
installations only
- Indoor Use Only
STANDARD FEATURES:
- Up to 24 foot high doors with a maximum area of 480
square feet for 3/4 HP, 280 square feet for 1/2 HP and
200 square feet for 1/3 HP - maximum area slightly
higher for lighter doors - consult factory
Solid State Controls: The openers employ solid state
technology with advanced standard features to provide for a
complete commercial door operating system.
- To operate in Momentary Contact To Close mode and
Switch Selectable Operating Modes: Six distinct base
operation modes can be selected by resetting the switches on the
motor control board: a standard Open, Close, Stop (B2,
momentary button push); three constant pressure modes (C2, D1,
and E2); two Timer to Close modes (T and TS). See page 17 for
complete description of the modes.
comply with the UL325 Entrapment Protection requirements
effective Aug. 29, 2010, the door system must include one of
the following (a, b, or c):
(a) Linear Corp. Photo-Beam System that consists of an
emitter, Part No. 217792 and detector, Part No. 217800 for
doors as described above up to 30 FT wide. See Page 13.
(b) Any Miller Edge ME, MT/MU, and CPT family of edges,
with suffix T2, must be connected to the SM-102 Edge
Module, Recognized by UL as per UL325 2010 on 08-29-
2010 for door as described above. See Page 13.
(c) A Vitector Fraba OSE 2-wire Photosystem as Recognized
by UL as per UL325 2010 on 08-29-2010 for door as
described above. See Page 13.
Switch Selectable Characteristic Modes: Five different
operating characteristics can be activated and/or modified
through the switches on the motor control board: Delay On
Reverse, Close Limit Delay, Mid Stop Travel, Timer to Close,
Maximum Run Timer.
Limit Switches: Driven limit switches, easily adjusted over a
wide range. The motor may be removed without affecting the
limit switch adjustments
- The manufacturer of this operator strongly recommends
installation of one of the entrapment protection device above
and states that one is REQUIRED where any automatic,
remote or manual control is used to activate the door.
Manual Release: Permits manual operation of the door in the
event of a power failure. The Model AUH-S is equipped with a
chain hoist to aid in manual operation.
Control Circuit: Standard three button open, close and stop.
5 Volts DC.
OPTIONAL FEATURES:
Digital Radio Controls: Open, Close and Stop operation.
Radio units are available to control up to 27 doors from one
transmitter
Connections For Auxiliary Entrapment Protection
Devices: For the ultimate in protection, terminals are provided
to connect a Linear Corp. Photo-Beam System that consists of an
emitter, Part No. 217792 and detector, Part No. 217800. This
device when connected is a monitored photo-beam system.
Additional connection terminals for a Normally Open and
Normally Closed reversing devices such as a reversing door edge
or a three wire photo-beam are provided.
Keyless Entry System: Connection terminals provided for
hard wired or wireless keyless entry systems.
Direct Coupling (FS or FC Mount): Must be pre-ordered
from the factory. Flange couplers direct connect the operator
output shaft and the door shaft. Door shaft speed is 30 RPM
unless otherwise specified.
Download from Www.Somanuals.com. All Manuals Search And Download.
PREPARATION
4
verify that it is the correct model for the intended application
and that the voltage and phase are in accordance with
electrical power provided at the job site. If the operator was
ordered with the optional chain hoist, ..H.. suffix, see that it is
so equipped. A chain hoist CANNOT be added in the field.
WARNING
ELECTRIC DOOR OPENERS ARE DESIGNED
FOR DOORS IN GOOD WORKING CONDITION,
PROPERLY COUNTERBALANCED AND
PROPERLY ADJUSTED IN ACCORDANCE
WITH THE DOOR MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
Warning: Rope off the area to keep personnel and
vehicles clear of the door and floor space in the vicinity of
the operator during the installation.
Before starting the installation of the operator, the door must be in
good working condition and properly counterbalanced. Inspect the
door and track for loose or missing hardware. Test the door
manually for balance and ease of operation. Lubricate door hinges
and rollers. If necessary, employ a qualified technician to adjust the
springs for proper counterbalance of the door.
WARNING
SPRINGS ARE SUBJECT TO VERY
HIGH FORCES AT ALL TIMES AND
ADJUSTMENTS MUST BE MADE
ONLY BY A QUALIFIED
Stops should be installed at the top end of each track to prevent the
possibility of the door rollers moving beyond the ends of the track.
PROFESSIONAL DOOR INSTALLER.
If the cross header shaft is made from hollow tubing rather than
solid rod, it is recommended that it be plugged with a short length of
solid bar for a more secure installation of the shaft sprocket or
flange coupler.
WARNING
REMOVE OR DISABLE ANY LOCKING
DEVICES FROM DOOR AND REMOVE
ALL ROPES
Before removing the operator powerhead from the shipping carton,
inspect the nameplate on the cover of the operator control box to
COMPONENT IDENTIFICATION
Figure 1
107170
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT INSTALLATION INSTRUCTIONS!
5
TO REDUCE THE RISK OF SEVERE
INJURY OR DEATH:
WARNING
READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS!
• Install only on a properly operating and balanced
garage door. A door that is operating improperly
could cause severe injury. Have qualified service
personnel make repairs to cables, spring assemblies
and other hardware before installing the opener.
• Install the door operator at least 8 feet or more
above the floor if the operator has exposed moving
parts.
• Do not connect the opener to the source of power
until instructed to do so.
• Remove all pull ropes and remove, or make
inoperative, all locks (unless mechanically and/or
electrically interlocked to the power unit) that are
connected to the garage door before installing the
opener.
• Locate the control station:
a) within sight of the door,
b) at a minimum height of five feet above the
floor so small children cannot reach it,
c) away from all moving parts of the door, and
d) far enough away from the door, or positioned
• Lightweight doors (fiberglass, aluminum etc.)
must be reinforced to avoid door damage. Check
the door manufacturer’s instruction manual for a
bracing procedure or the availability or a
Reinforcement Kit.
such that the user is prevented from coming in
contact with the door while operating the
controls.
• Model AUJ and AUH are Commercial Vehicular
Door Operators and as such ARE NOT
Do not overtighten the clutch adjustment to
compensate for a poorly working door.
recommended for pedestrian traffic. In
installations where it is known that pedestrians will
be nearby ensure a pedestrian door is available for
entrance and exit to the building. In addition YOU
MUST install an auxiliary entrapment protection
device (reversing door edge or photoelectric beam
device).
Install the Entrapment Warning Placard next to
the control station in a prominent location.
All warning signs and placards must be installed
so they are visible in the area of the door.
After installing the opener, all safety features
must be tested for proper operation (see page 22).
• Connect an auxiliary entrapment protection
device (reversing edge or photoelectric device across
the door opening). A device of this type is
For products having a manual release, instruct the
end user on the operation of the manual release.
STRONGLY ADVISED FOR ALL commercial
operator installations. An auxiliary entrapment
protection device is REQUIRED when the three
button control station is out of sight of the door or
any other automatic or manual control is used.
COMPONENT IDENTIFICATION LISTING
ITEM #
PART#
005031
105193
DESCRIPTION
QUAN.
ITEM #
PART#
DESCRIPTION
QUAN
1
2
3
4
5
Operator Power Head
3 Button St ation
30 Tooth Sprocket, 1” Bore, 1/4 Key
20 Tooth Sprocket, 1” Bore, 1/4 key
Release/Hand Chain Wall Bracket
1
1
1
1
1
6
7
8
9
10
11
100413
006119
105323
100315
1/4” Square Key
5/16-18 x 1 Square Head Set Screw
Steel #80 Release Chain
#3 Hand Chain - Precut to 26 Ft.
Drive Chain to Door Shaft, 4 Ft.
3 Piece Chain Connecting Link
2
4
AR
1
1
1
—— AR - As Required
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS
6
SPRINGS, PULLEYS, CABLES AND MOUNTING HARDWARE USED TO
BALANCE YOUR GARAGE DOOR ARE UNDER EXTREME TENSION AT ALL
TIMES AND CAN CAUSE SEVERE INJURY OR DEATH IF DISTURBED.
DO NOT ATTEMPT ADJUSTMENT.
WARNING
construction of the surface supporting the operator or noticeable
Figure 4, page 8 illustrates several positions suitable for
mounting the operator; right hand or left hand, either wall mount
or ceiling mount and center mount with direct coupling to the
torsion shaft. Direct coupling may also be used in a side mount
installation. Operators intended for direct coupling require an
internal speed modification and must be ordered from the factory.
deflection of the door shaft, it is advisable to install a shaft
support between the operator jackshaft and the door shaft to
prevent the loss of limit settings due to the possibility of the
chain jumping over the sprocket teeth. Shaft supports are
available from the factory.
BEFORE PROCEEDING WITH THE
OPERATOR INSTALLATION AND SETTINGS,
MAKE A FINAL CHECK FOR TIGHTNESS OF
ALL MOUNTING HARDWARE AND SET
SCREWS.
CHAIN COUPLING MOUNTING
Refer to Figure 2 (at right), Figure 1, page 4 and Figure 5, page
9 for component identification and the operator mounting slot
locations. Place the sprockets [ 3 ] and [ 4 ] on the chosen side of
the torsion shaft of the door and on the corresponding end of the
output shaft of the operator. The sprockets should be kept as
close as possible to the bearings. Fasten the connecting link to
each end of the door chain and loop the chain over the sprocket
[ 3 ] on the torsion shaft. Temporarily suspend the operator in its
mounting position using the chain over the sprocket [ 4 ] at one
end of the jackshaft and a rope or chain at the mid point (to
support the operator weight). With the chain tight and straight
and the jackshaft parallel with the torsion shaft, trace the
mounting slot on the mounting surface then lower the operator to
the floor.
Proceed to “Chain Hoist and Floor Disconnect Installation”.
IT IS ESSENTIAL THAT THE SURFACE
SUPPORTING THE OPERATOR BE RIGID
AND SECURE. FAILURE TO PROVIDE A FIRM
MOUNTING SURFACE WILL RESULT IN
DAMAGE TO THE DOOR TORSION SHAFT
AND THE PREMATURE FAILURE OF THE
OPERATOR.
1.50
107171
15.00
If the construction permits, the operator should be mounted with
3/8 inch diameter bolts through the wall. If it is not feasible to go
through the wall, then use lag bolts to fasten the operator to the
mounting surface. Locate the four holes within the tracings of the
slots made in the previous step at the positions which will allow
for adjust-ment of the chain tension. After drilling the mounting
holes and instal-ling lag shields, if necessary, bolt the operator to
the mounting surface but do not completely tighten the bolts at
this time. Check the alignment of the sprockets, adjust their
positions on the shafts if necessary and tighten the set screws
securely on both sprockets. pulling downward on the operator to
remove slack from the chain, tighten the four mounting bolts.
3.00
Figure 2
Inspect the installation. There should be no slack in the chain but
neither should it be under severe tension which might shorten the
life of the bearings. If there is any flexibility in the system due to
7.75
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS
7
DIRECT COUPLING MOUNTING
CHAIN HOIST AND FLOOR DISCONNECT
INSTALLATION
Figure 4, page 8 illustrates several positions suitable for
mounting the operator including center mount with direct
coupling to the torsion shaft. Direct coupling may also be
used in a side mount installation. Operators intended for
direct coupling require an internal speed modification and
must be ordered from the factory.
If the operator is furnished with a chain hoist (Model AUH-S), pass
the hand chain over the chain wheel and through the chain guides
on the operator clutch shaft (opposite end from the large pulley).
Fasten the ends of the chain together by opening and re-closing one
link using two pairs of pliers. If the chain is too long (standard
length for 16 foot high doors and below is 26 feet total length of
chain), shorten it to the desired length using the method described
above and discard the unused portion.
Refer to Figure 2, page 6 and Figure 5, page 9 and Figure 6,
Page 10 for the location of the operator mounting holes.
Fasten the chain hoist holding bracket furnished with the operator
to the wall approximately four feet from the floor. This bracket is
also used to hold in place the release chain for both the chain hoist
equipped units (Model AUH-S) and floor disconnect models
(Model AUJ-S).
IT IS ESSENTIAL THAT THE OUTPUT
SHAFT OF THE OPERATOR AND THE
DOOR SHAFT BE CAREFULLY ALIGNED.
MISALIGNMENT OF THE SHAFTS WILL
CAUSE EXCESSIVE STRESS AND WEAR.
Raise the operator to a position which brings the door and
operator shafts into alignment and connect them together
with the flange coupling supplied with operator. Support the
other end of the operator jackshaft from the ceiling with a
chain or rope. Holding the operator in a vertical position,
carefully measure the distance from the operator mounting
plates to the wall. Lower the operator to the floor and
construct a secure mounting surface using the dimension
measured in the previous step. Again raise the operator to its
mounting position and re-connect the shafts. Mark the
mounting slots in the support structure, drill and securely bolt
the operator into place.
107174
BEFORE PROCEEDING WITH THE
OPERATOR INSTALLATION AND
SETTINGS, MAKE A FINAL CHECK FOR
TIGHTNESS OF ALL MOUNTING
HARDWARE.
Figure 3
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 4 - OPERATOR MOUNTING POSITIONS
8
Center
Mount
Right Side
Mount
Left Side
Mount
Direct
Couple
Ceiling
Mount
Ceiling
Mount
Wall
Mount
Wall
Mount
100719
Figure 4
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 5 - OPERATOR DIMENSIONS - MODEL AUH-S
9
7.75
107173
Figure 5
NOTE: Dimensions for Model AUJ-S are similar to above,
Model AUJ-S is not provided with a chain hoist.
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 6 - OPERATOR DIMENSIONS - MODEL AUJ-S
10
15
7.75
107173
NOTE: Dimensions for Model AUH-S are similar to above,
Model AUH-S is provided with a chain hoist.
Figure 6
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS
11
4) Depress the limit nut retaining Plate (D) so it disengages
from the slots in the limit nuts. Turn the OPEN limit nut (E) on
the shaft until it engages the Open Limit Switch (A). You will
need to listen for an audible click. Release the retaining plate
and be sure that it engages in slots of both limit nuts.
WARNING
TO AVOID RISK OF ENTRAPMENT AND
POSSIBLE DAMAGE TO THE DOOR AND
OPERATOR THE LIMITS MUST BE ADJUSTED
BEFORE APPLYING POWER TO THE
OPERATOR.
5) Manually lower the door to approx. 4 inches shy of the
fully closed position and repeat Step #4 with the Close Limit nut
(C) and the Close Limit switch (B).
6) Manually move the door to a half open position. With the
door in a mid position there will be time to stop the door if
something or someone were in the door path when initially
starting the door.
SETTING THE LIMIT SWITCHES
1) With the cover open on the electrical enclosure, reference
Figure 7 below. There are two (2) switches (A and B) mounted to
the „V‟ bracket (F). The Close Limit switch (B) and the Open
Limit switch (A) are mounted to the top side of the „V‟ bracket as
shown. These switches are activated by the two limit nuts (E & C)
on the threaded shaft which move laterally along the shaft as the
operator opens and closes the door. When a limit nut nears the
end of the shaft it activates a switch.
7) An additional limit adjustment may be necessary after the
connection of the power supply in order to ensure the door stops
at the proper Open and Close positions.
8) If needed, a fine adjustment of the Close Limit switch (B)
or Open Limit switch (A) is possible by loosening the screws
slightly that hold the switch to the V bracket and moving the
switch within its mounting slots. Ensure to retighten the switch
mounting screw. Moving the Reverse Cutout switch closer to
the center of the box will increase the point where the reversing
feature cuts out (to allow for irregularity in the floor, etc.). The
reverse cutout point is factory adjusted to approx. 4 inches off
the floor.
2) Depress the Limit Nut Retention Plate (D) so it disengages
from the slots in the limit nuts and move the Limit nuts to the
center of the threaded shaft. Re-engage the Limit Nut Retention
Plate (D).
3) Manually raise the door to a fully open position.
E
D
A
113116
C
B
A - OPEN LIMIT SWITCH
B - CLOSE LIMIT SWITCH
C - CLOSE LIMIT NUT
D - LIMIT NUT RETAINING PLATE
E - OPEN LIMIT NUT
Figure 7
Limit Assembly
F
F - “V” BRACKET
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS - ELECTRICAL WIRING
12
WARNING
WARNING
RISK OF ENTRAPMENT THAT MAY
RESULT IN SERIOUS PERSONAL INJURY OR
DEATH. DISCONNECT POWER TO THE
OPENER BEFORE AND DURING
TO PREVENT THE RISK OF PERSONAL INJURY
OR DEATH :
• DISCONNECT POWER AT THE FUSE BOX
BEFORE PROCEEDING.
INSTALLATION OF AN ACCESSORY
REVERSING DOOR EDGE OR
• ELECTRICAL CONNECTIONS MUST BE MADE
BY A QUALIFIED INDIVIDUAL.
PHOTOELECTRIC DEVICE. DO NOT
RECONNECT POWER TO OPENER UNTIL
INSTRUCTED TO DO SO. ENSURE DOORWAY
IS CLEAR BEFORE STARTING TESTING OF
• OBSERVE LOCAL ELECTRICAL CODES WHEN
WIRING THE OPERATOR.
WARNING: The AUJ-S and AUH-S Series operators
have been designed and constructed for use with voltages
from 115 Volts AC to 480 Volts AC, in single or three
phase. Check the operator nameplate label on the
control box cover for the proper voltage and phase. The
application of an improper input voltage or phase will
result in catastrophic failure to the internal electrical
components.
Note: AUJ-S and AUH-S Series model operators are pre-wired
for entrapment protection devices. To operate in Momentary
Contact To Close mode and comply with the UL325
Entrapment Protection requirements effective Aug. 29, 2010,
an approved external entrapment device as described on Page 3
must be installed and connected to the operator. Refer to Figure
8 and the manufacturer‟s instructions to install and connect one
of the approved door edge devices. One or more contact
sensors shall be located at the bottom edge of a vertically
moving door. Refer to the instructions on Page 13 & 14 for the
Linear photoelectric system installation and wiring.
Observe local electrical codes when wiring the operator.
When hard wiring, observe state and local electrical codes. A
wiring diagram is attached to the inside of the control box cover.
Connect the appropriate voltage and phase power leads to the
appropriate terminals as per the wiring diagram and connect a
ground wire to the grounding screw. On three phase units,
incorrect phasing of the power supply will cause the motor to
rotate in the wrong direction (open when CLOSE button is pushed
and vice versa). To correct this, interchange any two of the
incoming three phase conductors.
If the external entrapment protection device is connected, the
selector switches are set properly (Page 17) and the device
detects an obstruction or becomes inactive, an opening door
continues to open and a closing door stops, pauses and starts
open. While in this mode, if a problem is detected while the
operator is stopped, a close will require constant activation of
the control Close button. If an entrapment protection device as
described above is attached and is properly working for 1
second, it will be auto detected and the monitored function will
be turned on. Once the monitoring function is active, it will
remain active even if the power is removed and the entrapment
protection device is disconnected and power is restored. While
in this mode, if a problem is detected while the operator is
stopped, a close will require constant activation .
The wiring diagram attached inside the cover of the control box
details all of the field wiring terminal connections for the operator.
Always connect the wires to the push-button controls and auxiliary
devices exactly as shown.
Warning: Control voltage of the opener is 5 volts DC, Class 2.
Do not run the power leads and control circuit wiring in the same
electrical conduit.
Operators which have an operational entrapment protection
device as described above may have one or more additional
means of control which should be wired in accordance with the
diagram supplied in the opener and also illustrated on Pages 23
& 24. To add a second three button station, refer to Figure 11.
WARNING
TO PREVENT THE RISK OF PERSONAL INJURY
AND/OR DAMAGE TO DOOR OR PROPERTY,
ONLY OPERATE DOOR CONTROL WHEN
DOOR IS IN CLEAR VIEW. IF CONTROL
STATION CANNOT BE LOCATED WHERE THE
DOOR IS VISIBLE OR IF ANY OTHER DEVICE IS
USED TO CONTROL THE DOOR AN AUXILIARY
ENTRAPMENT DEVICE (DOOR EDGE OR
PHOTOELECTRIC) MUST BE CONNECTED.
Number 22 gauge wire or heavier must be used for wiring
the control stations and auxiliary control devices to the
operator. Smaller gauge wire will cause operational
problems, especially when multiple push-button stations are
used or during summer months.
Download from Www.Somanuals.com. All Manuals Search And Download.
DOOR EDGE and PHOTOELECTRIC INSTALLATION
13
Note: See the door edge manufacturer‟s installation instructions for the complete installation procedure. See Figure 9 for connecting the
edge to the operator. See Page 17 for proper setting of the selector switches. These switches must be properly set and an approved photo-
electric device or approved door edge device connected to the operator to obtain B2 Mode of Operation, Momentary Contact to Close.
Figure 8
Door Edge
Device
Door Edge Installation Illustration
9. See Figure 9 for
connecting the
photoelectric
device to the
operator. See Page
CAUTION
17 for proper
setting of the
selector switches.
These switches
must be properly set and an approved photoelectric device or
approved door edge device connected to the operator to obtain
TO AVOID DAMAGE TO DOOR AND
OPERATOR ENSURE ALL DOOR LOCKS ARE
DISABLED.
USE AN INTERLOCK SWITCH IF A LOCK IS
REQUIRED TO RETAIN FUNCTIONALTY.
B2 Mode of Operation, Momentary Contact to Close.
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS
ENTRAPMENT PROTECTION DEVICES WIRING INSTRUCTIONS
Note A: Connect only one (1) approved entrap-
14
ment protection device to terminals “Photo” and
Any Miller Edge ME, MT/MU, and CPT
“Com”. If additional entrapment protection is desired
connect additional photoelectric and door edges devices
to “NC REV”, “NO REV” and “COM” terminals as
shown here.
family of edges, must be connected to the
SM-102 Edge Module, Recognized by UL
as per UL325 2010 on 08-29-2010.
See Note A to the left.
TB1
MOTOR
CONTROL
BOARD
Figure 9
Linear Approved
2 Wire Door Edge
Photoelectric
Entrapment
Protection Device
Detector
Part #
217800
Emitter
Part #
217792
Protection Device wiring. Note: This device can be used for
additional Entrapment protection but connection of this device
will not enable the Momentary Contact to Open Mode.
See Note A above
Note: When adding a photocell device with a
Normally Closed output remove the factory
installed jumper from the connection terminals.
3-WIRE PHOTOBEAM
3 Wire Photoelectric Entrapment
Protection Device wiring. Note: This device can be used for
additional Entrapment protection but connection of this device
will not enable the Momentary Contact to Open Mode.
Door Edge and Photoelectric Wiring
After properly connecting an approved Entrapment Protection Device (see above and Page 3) to the operator, see Page 17 for
setting of the selector switches. These switches must be properly set and an approved photoelectric device or approved door
edge device connected to the operator to obtain B2 Mode of Operation, Momentary Contact to Close.
Download from Www.Somanuals.com. All Manuals Search And Download.
3/SINGLE BUTTON STATION / INTERLOCK FIELD WIRING
15
R5
D3
R57
R25
R65
RADIO
MOTOR
C1
D2
R84
R2
R3
U5
MOTOR
CONTROL
BOARD
C25
CONTROL
PB1
PB2
BOARD
P7
R3
R8
R94
R95
R2
R54
OPEN
CLOSE STOP
R55
R56
R3
C25
PB1
PB2
PB3
D12
OPEN
CLOSE STOP
Single 3 Button Station
Figure 10
Multiple 3 Button Station
Figure 11
R93
D1
U5
R4
C21
R8
R24
Figure 12
MOTOR
CONTROL
TB1
BOARD
Single Button and External Interlock Wiring
Note: When adding an External Interlock
remove the factory installed jumper from
the connection terminals.
EXTERNAL INTERLOCK
TURNING ON THE POWER TO THE OPERATOR
NOTE: It is now necessary to turn on the power in order to change the Operating Mode (if
applicable), program any changes desired to the operator’s other settings, check for proper
performance of all the operator’s features to include the brake (if applicable) and clutch
(adjusting settings if necessary); and to set and finalize any adjustments to the limit settings.
Before doing so, ensure that all mounting hardware are installed and properly tightened, that all
electrical connections are per local code requirements, and that proper wiring practices have been
followed. Also, double-check that all ropes have been removed from the door and that the
doorway is clear.
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION & ADJUSTMENT INSTRUCTIONS
16
IMPORTANT SAFETY INSTRUCTIONS FOR OWNER
TO REDUCE THE RISK OF SEVERE
WARNING
INJURY OR DEATH:
READ AND FOLLOW ALL INSTRUCTIONS!
Understand all of the operating features of your door control system at the time of its installation.
Your installing dealer will demonstrate them for you.
NEVER let children operate or play with door controls. Keep the Remote Control (where
provided) away from children.
Personnel should keep away from a door in motion and keep the moving door in sight until the
door is completely closed or opened. NO ONE SHOULD CROSS THE PATH OF A MOVING
DOOR.
TEST THE DOOR OPENER’S SAFETY FEATURES AT LEAST ONCE A MONTH. After
adjusting either the force setting or the limit of travel, ALWAYS RETEST the Operator’s safety
features. Failure to ADJUST THE OPERATOR PROPERLY may cause SEVERE INJURY OR
DEATH.
DO NOT over adjust the force setting to compensate for a poorly working door.
If possible, USE THE MANUAL RELEASE only when the door is closed. Use caution when using
this release when the door is open. WEAK OR BROKEN SPRINGS MAY ALLOW THE DOOR
TO CLOSE RAPIDLY, CAUSING SEVERE INJURY OR DEATH.
KEEP THE GARAGE DOOR PROPERLY BALANCED. See the door manufacturer’s owner's
manual. An improperly balanced door COULD CAUSE SEVERE INJURY OR DEATH. Have a
TRAINED DOOR SYSTEMS TECHNICIAN MAKE REPAIRS TO CABLES, SPRING
ASSEMBLIES AND OTHER HARDWARE.
Inspect and maintain your door system as described in this manual.
SAVE THESE INSTRUCTIONS
WARNING
WARNING
AVOID ELECTROCUTION:
DO NOT ROUTE LOW VOLTAGE WIRES IN
SAME CONDUIT AS HIGH VOLTAGE
WIRES. FOLLOW ALL LOCAL
ELECTRICAL CODES OR THE NATIONAL
ELECTRICAL CODE.
FAILURE TO TEST REVERSING
SYSTEM COULD RESULT IN DEATH
OR SERIOUS INJURY. TEST THIS
SYSTEM ONCE A MONTH.
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION & ADJUSTMENT INSTRUCTIONS
17
SETTING THE SWITCH SELECTABLE OPERATING MODES
Changing the Switch Selectable Operation Modes
The following modes are selected by setting the on-board dip
switches, Figure 20 at right shows where the switches are
located on the operator control board. For each Operational
Mode, the switches are set to either ON or OFF according to the
table at right below. For all the modes, if an approved
Settable
Switches
Location
P4
K5
K3
K4
K2
HIGH VOLTAGE
K6
P1
MO4
TR3
STATUS
POWER
SW1
OFF
MO3
MO2
MO1
ILK
S4
S3
S2
S1
P2
P3
LD2
R49
R62
R47
R51
R19
R17
R13
R1
R10
LD3 LD4
R89
TR1
R34
R22
C16
R33
24V
entrapment protection (EP) reversing device as described on
page 3 of this manual is attached to the input labeled “Photo”, it
will function as noted. Once an approved EP device is
recognized by the control board it is monitored for correct
operation. If the device becomes inactive then the mode will
default to constant pressure activation for close regardless of the
dip switch setting. In order for any of the Momentary Contact to
Close operation modes (B2, TS, T) to become active an
approved Entrapment Protection (EP) Reversing device (see
Page 3) must be properly installed and connected to the operator.
The switches must be set to one of the six Operational Mode
combinations for the operator to function. In order for the NO
(Normally Open) Reverse or NC (Normally Close) Reverse
inputs to function, you must first install an operational approved
Entrapment Protection (EP) Reversing Device.
R23
R9
R27
R28
R83
R53
R46
R45
R57
COM
R61
C6
R60
R5
R20
R18
R14
R21
R82
D3
R48
TR2
C13
R25
C24
R65
RADIO
C10
D2
24V
COM
D8
R52
TR4
C14
R31
RM3
RM2
RM1
VCC
EDGE
FRA
VCC
COM
24V
C30
P7
S1
R85
R11
R15
R6
C2
R38
R87
R94
R95
R2
R54
R12
R16
R7
R55
R56
R58
C12
P6
Q1
C7
R84
R90
R93
R4
R3
D1
U5
C25
R8
R24
C21
PB1
PB2
PB3
D12
OPEN
CLOSE STOP
TB1
Figure 13
MOTOR CONTROL BOARD
Operating Mode Switch 1 Switch 2 Switch 3 Switch 4
B2 Operation
C2 Operation
D1 Operation
E2 Operation
TS Operation
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
B2 Operation (Factory Default)
Open Button: Momentary activation; open override of closing
door.
Close Button: Momentary activation.
Stop Button: Momentary activation; stops open, close or reverse
action.
Single Button: Momentary activation to open; open override of
closing door, closes door from mid-stop or open limit.
EP Reverse (Photo Input): Momentary activation will reverse a
closing door, reverse to full open (ignores mid-stop) unless
stopped by stop pushbutton input.
ON
OFF
ON
OFF
OFF
T Operation
ON
D1 Operation
Mid-Stop: Activation stops an opening door; momentary contact
of open button at mid stop will restart door to full open position;
if door is moving open, constant pressure on open button will
bypass mid-stop.
Open Button: Constant activation; open override of closing door.
Close Button: Constant activation, door will stop when button is
released.
Stop Button: Momentary activation; stops open, close or reverse
action (not required).
Auto Close Timer: N/A.
Single Button: N/A.
EP Reverse (Photo Input): Momentary activation will stop a
closing door.
Mid-Stop: Activation stops an opening door; after the door stops
at the mid stop, constant contact of open button at mid stop will
restart door to full open position.
C2 Operation
Open Button: Momentary activation; open override of closing
door.
Close Button: Constant activation, door will stop when button is
released.
Stop Button: Momentary activation; stops open, close or reverse
action.
Auto Close Timer: N/A.
Single Button: Momentary activation to open; open override of
closing door.
EP Reverse (Photo Input): Momentary activation will reverse a
closing door, reverse to full open (ignores mid-stop) unless
stopped by stop pushbutton input.
Mid-Stop: Activation stops an opening door; momentary contact
of open button at mid stop will restart door to full open position;
if door is moving open, constant pressure on open button will
bypass mid-stop.
E2 Operation (roll-back)
Open Button: Momentary activation; open override of closing
door.
Close Button: Constant activation, door will reverse to full open
(ignores mid-stop) when button is released.
Stop Button: Momentary activation; stops open, close or reverse
action.
Single Button: N/A.
EP Reverse (Photo Input): Momentary activation to reverse a
closing door, reverse to full open (ignores mid-stop) unless
stopped by stop pushbutton input.
Auto Close Timer: N/A.
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION & ADJUSTMENT INSTRUCTIONS
18
Mid-Stop: Activation stops an opening door; momentary contact
of open button at mid stop will restart door to full open position;
if door is moving open, constant pressure on open button will
bypass mid-stop.
will reactivate the auto close timer or reset the auto close timer
when the door is at the mid-stop or open limit.
T Operation, Dip-Switch Setting
Open Button: Momentary activation; open override of closing
door.
Auto Close Timer: N/A
Close Button: Momentary activation.
Stop Button: Momentary activation; stops open, close or reverse
action.
TS Operation
Open Button: Momentary activation; open override of closing
door.
Close Button: Momentary activation.
Stop Button: Momentary activation; stops open, close or reverse
action.
Single Button: Momentary activation to open; open override of
closing door, closes door from mid-stop or open limit.
EP Reverse (Photo Input): Momentary activation will reverse a
closing door, reverse to full open (ignores mid-stop) unless
stopped by stop pushbutton input.
Single Button: Momentary activation to open; open override of
closing door, closes door from mid-stop or open limit.
EP Reverse (Photo Input): Momentary activation will reverse a
closing door, reverse to full open (ignores mid-stop) unless
stopped by stop pushbutton input.
Mid-Stop: Activation stops an opening door; momentary contact
of open button at mid stop will restart door to full open position;
if door is moving open, constant pressure on open button will
bypass mid-stop.
Mid-Stop: Activation stops an opening door; momentary contact
of open button at mid stop will restart door to full open position;
if door is moving open, constant pressure on open button will
bypass mid-stop.
Auto Close Timer: Closes door from mid-stop or open limit after
pre-set time. Stop will deactivate the auto close timer. Open will
reactivate the auto close timer or reset the auto close timer when
the door is at the mid-stop or open limit. Single button will reset
the auto close timer from the mid-stop or open limit. Reverse
Auto Close Timer: Closes door from mid-stop or open limit after
pre-set time. Stop will deactivate the auto close timer. Open will
reactivate the auto close timer or reset the auto close timer when
the door is at the open limit. Single button will reset the auto
close timer from the mid-stop or open limit. Reverse deactivates
the auto close timer if the door is closing. Reverse will reset the
auto close timer at the mid-stop or open limit if the auto close
timer has not been previously deactivated.
SETUP MODES
Setup Mode
Switch Switch Switch Switch
Setup Modes
Various operating characteristics can be modified via the setup
modes. The operator is moved to the close limit position and the
on-board dip switches (see Figure 13, page 17) are
TEMPORARILY set according to the table at right to enter a Setup
Mode. The on board OPEN and STOP buttons are used to
modify the characteristic. Once set, the values are stored in non-
volatile memory.
1
2
3
4
Delay on Reverse
Close Limit Delay
Mid-Stop Limit
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
OFF
ON
Auto Close Timer
OFF
OFF
These values are set to factory defaults that should be
satisfactory for many applications. ALL VALUES AS
DESCRIBED HERE CAN BE RESET TO THE FACTORY
DEFAULTS AS FOLLOWS:
Remove 24 VAC power from the control board.
Press and hold the on-board stop button.
Re-apply 24 VAC while holding the on-board stop button.
After completing the procedure to modify the operating
characteristic the switches must be returned to the originally set
Operating Mode setting (see section previous).
Maximum Run
Time
Changing the dip-switch setting to any other setting will save
the new time. Return the dip switches to the originally set
Operating Mode setting (see section previous).
Close Limit Delay Setup
To provide for irregularities in the floor, this feature allows for
the door to continue to travel down after the Reverse Cutout
Limit is activated. The factory default time is 0.32 seconds; the
minimum time is 0.12 seconds; the maximum time is 0.66
seconds.
Delay on Reverse Setup
To help prevent stress on the door components, this feature
allows for a delay time between the door stopping and reversing
when a command to reverse is received as the door is closing.
The factory default time is 0.75 seconds; the minimum time is
0.4 seconds; the maximum time is 2 seconds.
After moving the door to the close position and temporarily
setting the switches to the appropriate settings in the table,
pressing STOP will reset the time to the minimum setting.
Every time OPEN is pressed, 0.02 seconds are added to the time
(up to the maximum).
Changing the dip-switch setting to any other setting will save
the new time. Return the dip switches to the originally set
Operating Mode setting (see section previous).
After moving the door to the close position and temporarily
setting the switches to the appropriate settings in the table,
pressing STOP will reset the time to the minimum setting.
Every time OPEN is pressed, 200 mS is added to the time (up to
the maximum).
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION & ADJUSTMENT INSTRUCTIONS
19
After moving the door to the close position and temporarily
setting the switches to the appropriate settings in the table,
pressing STOP will clear and turn off the auto close timer.
Every time OPEN is pressed, 5 seconds is added to the time.
Changing the dip-switch settings to any other settings will save
the new time. Return the dip switches to the originally set
Operating Mode setting (see section previous).
Mid-Stop Limit Setup
This features provides a timing function to stop a door as it is
traveling open at a Mid Stop position instead of the full open
position. The door can then be moved to the full open position
if desired by pressing the Open button. A single button input
when the door is at the mid stop position will cause the door to
begin moving in the close direction. The factory default is not
set; the minimum run time to mid-stop limit is 6 seconds.
After moving the door to the close position and temporarily
setting the switches to the appropriate settings in the table,
pressing STOP will remove the mid-stop limit setting.
Pressing OPEN will start the door open. When the door reaches
the desired mid-stop position, press STOP.
Maximum Run Time Setup
This feature provides for a maximum amount of time the motor
will be energized after an input is recognized. The factory
default time is 30 seconds; the maximum time is 60 seconds.
After moving the door to the close position and temporarily
setting the switches to the appropriate settings in the table,
pressing STOP will reset the time to the factory default setting.
Pressing OPEN will start the door open. The run time will be
recorded when the door reaches the open limit. To prevent
nuisance problems, 0.75 seconds are added to this time. Pressing
stop before the door reaches the open limit will stop the door
and reset the time to the factory default.
Changing the dip-switch setting to any other setting will save
the mid-stop limit position. Return the dip switches to the
originally set Operating Mode setting (see section previous).
Note: The door must move a sufficient distance to fully
disengage the Reverse Cutout Limit nut from the Reverse Cutout
Limit switch to set the mid-stop limit.
Changing the dip-switch setting to any other setting will save
the new time. Return the dip switches to the originally set
Operating Mode setting (see section previous).
Auto Close Timer Setup
This feature allows for a modification of the amount of time
between the door reaching either the Mid Stop or the Full Open
position and automatically starting in the close direction. The
Auto Close feature is only active when the operator is set to the
T or TS Operating Mode (see section previous). The factory
default is 30 seconds; the minimum time is 5 seconds; the
maximum time is 5 minutes.
BRAKE ADJUSTMENT
107103
The solenoid operated brake may require occasional
adjustment. Adjustment is necessary if door tends to
drift downward after reaching the open limit. Follow
the instructions below and use Figure 14 as a guide.
(1) Loosen shoe adjusting screw and bottom bracket
arm of solenoid.
Figure 14
(2) Move tab until drum has a slight drag.
(3) Reverse drag slightly from tab and tighten shoe
adjustment screw.
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION & ADJUSTMENT INSTRUCTIONS
CLUTCH ADJUSTMENT
20
RUBBING AGAINST THE DOOR STOPS OR
DEFECTIVE OR MISADJUSTED SPRINGS. ANY
WARNING
SERVICE REQUIRED TO THE DOOR, DOOR SPRINGS
OR DOOR OPERATOR MUST BE PREFORMED BY A
QUALIFIED PROFESSIONAL DOOR INSTALLER.
RISK OF ENTRAPMENT THAT MAY RESULT
IN SERIOUS PERSONAL INJURY OR DEATH.
DISCONNECT POWER TO THE OPENER
BEFORE SERVICING OR MAKING
ADJUSTMENTS. ENSURE DOORWAY IS
CLEAR BEFORE STARTING TESTING OF UNIT.
The clutch pad will wear during normal operation and should be
replaced when it becomes difficult or impossible to sufficiently
tighten the clutch to obtain smooth operation of the door when it
is in good working condition. To replace the clutch pad, first
loosen the motor mounting bolts and remove the V-belt then the
clutch adjusting nuts, spring and clutch pulley. Check condition
of V-belt before reassembly and replace if required. After
reassembly, adjust clutch as described above.
CAUTION
ALWAYS DISCONNECT POWER TO
OPERATOR BEFORE SERVICING OR MAKING
ADJUSTMENTS
107101
The clutch serves to protect the door, the electric operator and
other equipment from undue stress or damage caused by starting
forces and/or an obstruction to the door. It should be set no
tighter than is necessary to smoothly and consistently move the
door throughout its full range of travel. When properly set, it will
slip freely if the door should encounter an obstruction, and it
should be possible to stop the travel of the door by hand.
WARNING: Before adjustment remove power to the
operator.
To adjust the clutch, loosen the jamb nut, and turn the adjusting
nut, as shown at right Make adjustments in 1/4 turn increments.
Always re-tighten the jamb nut before running the operator to
prevent clutch from changing its setting.
Figure 15
CAUTION
NEVER COMPRESS CLUTCH SPRING BEYOND
POINT LIMITED BY THE DESIGN OF THE
OPERATOR OR REPLACE IT WITH A
HEAVIER SPRING
WARNING
IMPROPER ADJUSTMENT OF CLUTCH
SETTING COULD CAUSE ENTRAPMENT,
INJURY OR DEATH.
Due to changing conditions of the door and normal wear, it may
be necessary to occasionally readjust the clutch to obtain
dependable operation.
SET CLUTCH ADJUSTMENT FOR JUST
ENOUGH FORCE TO OPERATE THE DOOR
RELIABLY, BUT NO STRONGER. Contact a
service professional to correct any binding,
sticking or other door problems. DO NOT
OVER-ADJUST CLUTCH SETTING TO
COMPENSATE FOR A POORLY WORKING
DOOR.
WARNING: BEFORE DOING SO BE CERTAIN THAT
THE DOOR IS IN GOOD WORKING CONDITION,
PROPERLY COUNTERBALANCED AND THAT THE
CLUTCH IS NOT SLIPPING BECAUSE OF LOOSE OR
MISSING HARDWARE, BINDING IN THE TRACK,
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION & ADJUSTMENT INSTRUCTIONS
21
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION & ADJUSTMENT INSTRUCTIONS
TESTING
22
Following installation, the operator MUST be tested and
respond correctly to all controls as specified on the wiring
diagram. KEEP personnel and equipment clear of the area
beneath the door when performing the tests. When testing the 3
-button wall station, first observe that each button operates the
door in the direction indicated and that the STOP button
performs that function. With the door stopped at its full open
position, the OPEN button should be inoperative. This should
be verified and, likewise, the CLOSE button should be
inoperative with the door fully closed.
CAUTION
DO NOT STAND UNDER DOOR
TO TEST REVERSING FEATURE
USE A CORRUGATED BOX
OR OTHER SIMILAR OBJECT
If the operator is equipped with other means of control, such as
additional 3 button stations or radio controls, each of these
should be tested separately for proper operation.
Certain operator control circuits use only a single button or a
two button control station and may be designed to function
differently than the more common three-button circuit
described above. Test the controls in accordance with the
description of operation as indicated on the wiring diagram and
as selected on pages 17, 18, and 19, OPERATING and SET-UP
MODES.
To test the manual disconnect first move the door to the fully
closed position. Then disconnect the power to the operator.
Manual door operation mode should engage when the release
chain is pulled. The door can then be manually opened or
closed by physically moving the door (Model AUJ-S) or using
the hoist chain (Model AUH-S). If it is difficult to engage and/
or the jackshaft to doorshaft chain appears to be under
compression, reset the CLOSE limit slightly to reduce the door
travel in the close direction.
Observe the door when traveling in each direction for
smoothness of operation. Test the setting of the clutch by
restraining the door by hand. The clutch should slip. Re-check
the limit settings. The door should close tightly at the floor
without excessive impact. Likewise, it should fully clear the
door opening without the carrier striking the stops on the rail.
The AUJ-S and AUH-S series operators are equipped with a
reversing circuit and to allow for Momentary Close Contact
operation an approved entrapment protection device as described
on Page 3 needs to be properly installed and connected to the
operator. To test it for proper reversal, place an object beneath
the leading edge of the door. The door should instantly reverse
when it comes into contact with the object provided the height
of the object exceeds the cut out point built into the close limit
switch (approximately four inches).
WARNING
ALWAYS DISCONNECT POWER TO
THE OPERATOR BEFORE SERVICING,
CONNECTING ACCESSORY DEVICES
OR MAKING ADJUSTMENTS.
MAINTENANCE
CAUTION
Normally, very little maintenance is required. A monthly visual
inspection must be made for loose or missing hardware and for
excessive slack in the V-Belt and jackshaft chain. The clutch
must be tested periodically and adjustments made if necessary
(see page 20). The brake is adjusted at the factory and will need
periodic adjustment for wear. When adjustment becomes
necessary see Figure 14 on page 19 for the adjustment
procedure.
DO NOT STAND UNDER DOOR TO TEST REVERSING
EDGE - USE A CORRUGATED BOX
OR OTHER SIMILAR OBJECT
Lubrication of the operator is not required. It is important, for
trouble free service from the operator, that the door be kept free
from binding, properly counter balanced and periodically
lubricated. An annual inspection of the door by a qualified
overhead door professional is recommended.
Test the reversing edge circuit at least once a month by
permitting the door to contact an obstruction while closing.
Warning: Repairs and adjustments to the door and operator
should be performed only by someone qualified to service
commercial overhead doors and operators.
Download from Www.Somanuals.com. All Manuals Search And Download.
WIRING DIAGRAM/SCHEMATIC - SINGLE PHASE
23
CLOSE LIMIT
WHITE
GREY
GREY
RED
COM
NO
ORANGE
ORANGE
COM
NO
BLUE
YELLOW
OPEN LIMIT
WHITE
OVERLOAD
DEVICE
P4
BLACK
WHITE
L1
N
K5
K3
K4
HIGH VOLTAGE
K6
OPERATING MODES
SWITCH SETTINGS
MODE S1 S2 S3 S4
GROUND
SW1
P1
MO4
TR3
POWE
S4
MO3
MO2
MO1
ILK
S3
S2
S1
P2
P3
R49
R62
R47
R51
R19
R17
R13
R1
R10
R89
TR1
C2
B2
D1
E2
TS
T
OFF OFF OFF OFF
ON OFF OFF OFF
OFF ON OFF OFF
ON ON OFF OFF
OFF OFF ON OFF
ON OFF ON OFF
R22
C16
24V
OFF
COM
C6
R46
R20
R18
R14
R21
R82
D3
R45
R57
R48
TR2
C13
R65
LINE
RADIO
C24
24V
C10
D2
D8
R52
TR4
COM
C14
R31
RM3
RM2
RM1
VCC
EDGE
FRA
VCC
COM
24V
C30
P7
S1
R85
R11
R15
R6
C2
R38
R87
R54
24 VAC
TRANSFORMER
R12
R16
R7
R55
R56
R58
C12
P6
R3
Q1
C7
R90
R93
R4
C25
D1
R8
R24
C21
ON BOARD OPEN/CLOSE/
STOP CONTROL BUTTONS
PB1
PB2
PB3
LOAD
OPEN
CLOSE
STOP
TB1
OPEN
CLOSE
Note A:
STOP
YELLOW
YELLOW
Connect only one
(1) approved
entrapment
SINGLE BUTTON
protection device
(see Page 3) to
Terminals
EXTERNAL INTERLOCK
*
2-WIRE EDGE
“COM” and
“PHOTO” -
SEE
REMOVE FACTORY JUMPER
IF USING NC REV INPUT
NOTE A
additional devices
may be connected
to Terminals
“NC Rev”,
“NO REV” and
“COM”.
*
at left
SINGLE PHASE
3-WIRE
PHOTOBEAM
CAPACITOR START
MOTOR - 120 VAC
CDO OPERATORS WITH CDO-MCB MOTOR CONTROL SYSTEM
MOTOR WIRING CHART
BALDOR
DUAL VOLTAGE MOTOR - 115V 1P
A.O. SMITH
SINGLE VOLTAGE - 115 VAC, 1P MOTOR
1
5
8
3
BL/BLK
BL/BLK
BL/BLK
L1
YELLOW
RED (AU)
BLUE (T,J,H)
RED (AU)
BLUE (T,J,H)
RED
BL/BLK
RED
3
RED (AU)
BLUE (T,J,H)
RED
BLUE (AU)
RED (T,J,H)
BLUE
3
2
4
1
BLUE
WHITE
L1
4
2
YELLOW
BLUE (AU)
RED (T,J,H)
ORANGE
BLACK
ORANGE
BLACK
BLUE
YELLOW
BLUE (AU)
RED (T,J,H)
RED (AU)
1
BLUE (T,J,H)
3
BLACK
WHITE
WHITE
2
4
BL/BLK
BL/BLK
BL/BLK
4
WHITE
YELLOW
WHITE
YELLOW
YELLOW
YELLOW
BL/BLK
WHITE
L2
L2
TO REVERSE MOTOR DIRECTION, SWITCH
INCOMING LEADS TO TERMINALS 5 AND 8.
Wire Nut Connection
Wire Nut Connection
TO REVERSE MOTOR, SWITCH LEADS 1 & 3
TO REVERSE MOTOR, SWITCH LEADS 3/4 & 2/1 TO REVERSE MOTOR, SWITCH LEADS L1 & L2
BALDOR
208/230 VOLTS, 3 PHASE
460 VOLTS, 3 PHASE
575 VOLTS, 3 PHASE
DUAL VOLTAGE MOTOR - 230V 1P
DUAL VOLTAGE MOTOR
DUAL VOLTAGE MOTOR
SINGLE VOLTAGE MOTOR
1
BL/BLK
YELLOW
BL/BLK
BL/BLK
BL/BLK
WHITE
WHITE
WHITE
3
5
2
BLUE (AU)
RED (T,J,H)
BLUE (AU)
RED (T,J,H)
BLUE (AU)
RED (T,J,H)
8
4
RED (AU)
BLUE (T,J,H)
BL/BLK
WHITE
RED (AU)
BL/BLK
RED (AU)
BL/BLK
RED (AU)
BL/BLK
BLUE (T,J,H)
BLUE (T,J,H)
BLUE (T,J,H)
TO REVERSE MOTOR DIRECTION, SWITCH
INCOMING LEADS TO TERMINALS 5 AND 8.
TO REVERSE MOTOR DIRECTION, SWITCH
ANY TWO INCOMING LEADS.
TO REVERSE MOTOR DIRECTION, SWITCH
ANY TWO INCOMING LEADS.
TO REVERSE MOTOR DIRECTION, SWITCH
ANY TWO INCOMING LEADS.
Download from Www.Somanuals.com. All Manuals Search And Download.
WIRING DIAGRAM/SCHEMATIC - THREE PHASE
24
CLOSE LIMIT
WHITE
GREY
GREY
RED
COM
NO
ORANGE
ORANGE
COM
NO
BLUE
+CONNECTION SHOWN FOR 208 &
230V - FOR 460V SEE MOTOR DIAG.
ON INSIDE OF CONT. BOX COVER
OPEN LIMIT
OVERLOAD
DEVICE
P4
L3
L1
L2
ORANGE
BLACK
WHITE
K5
K3
K4
HIGH VOLTAGE
K6
OPERATING MODES
SWITCH SETTINGS
MODE S1 S2 S3 S4
GROUND
SW1
P1
MO4
TR3
POWE
S4
MO3
MO2
MO1
ILK
S3
S2
S1
P2
P3
R49
R62
R47
R51
R19
R17
R13
R1
R10
R89
TR1
C2
B2
D1
E2
TS
T
OFF OFF OFF OFF
ON OFF OFF OFF
OFF ON OFF OFF
ON ON OFF OFF
OFF OFF ON OFF
ON OFF ON OFF
R22
C16
24V
OFF
COM
C6
R46
R20
R18
R14
R21
R82
D3
R45
R57
R48
TR2
C13
R65
LINE
RADIO
C24
24V
C10
D2
D8
R52
TR4
COM
C14
R31
RM3
RM2
RM1
VCC
EDGE
FRA
VCC
COM
24V
C30
P7
S1
R85
R11
R15
R6
C2
R38
R87
R54
24 VAC
TRANSFORMER
R12
R16
R7
R55
R56
R58
C12
P6
R3
Q1
C7
R90
R93
R4
C25
D1
R8
R24
C21
ON BOARD OPEN/CLOSE/
STOP CONTROL BUTTONS
PB1
PB2
PB3
LOAD
OPEN
CLOSE
STOP
OVERLOAD
DEVICE
TB1
OPEN
CLOSE
Note A:
Connect only one
(1) approved
entrapment
STOP
YELLOW
YELLOW
SINGLE BUTTON
protection device
(see Page 3) to
Terminals
EXTERNAL INTERLOCK
*
2-WIRE EDGE
“COM” and
“PHOTO” -
SEE
REMOVE FACTORY JUMPER
IF USING NC REV INPUT
additional devices
may be connected
to Terminals
“NC Rev”,
“NO REV” and
“COM”.
NOTE A
*
at left
THREE PHASE
MOTOR
208/230/460 VAC
3-WIRE
PHOTOBEAM
CDO OPERATORS WITH CDO-MCB MOTOR CONTROL SYSTEM
MOTOR WIRING CHART
BALDOR
DUAL VOLTAGE MOTOR - 115V 1P
A.O. SMITH
SINGLE VOLTAGE - 115 VAC, 1P MOTOR
1
5
8
3
BL/BLK
BL/BLK
BL/BLK
L1
YELLOW
RED (AU)
BLUE (T,J,H)
RED (AU)
BLUE (T,J,H)
RED
BL/BLK
RED
3
RED (AU)
BLUE (T,J,H)
RED
BLUE (AU)
RED (T,J,H)
BLUE
3
2
4
1
BLUE
WHITE
L1
4
2
YELLOW
BLUE (AU)
RED (T,J,H)
ORANGE
BLACK
ORANGE
BLACK
BLUE
YELLOW
BLUE (AU)
RED (T,J,H)
RED (AU)
1
BLUE (T,J,H)
3
BLACK
WHITE
WHITE
2
4
BL/BLK
BL/BLK
BL/BLK
4
WHITE
YELLOW
WHITE
YELLOW
YELLOW
YELLOW
BL/BLK
WHITE
L2
L2
TO REVERSE MOTOR DIRECTION, SWITCH
INCOMING LEADS TO TERMINALS 5 AND 8.
Wire Nut Connection
Wire Nut Connection
TO REVERSE MOTOR, SWITCH LEADS 1 & 3
TO REVERSE MOTOR, SWITCH LEADS 3/4 & 2/1 TO REVERSE MOTOR, SWITCH LEADS L1 & L2
BALDOR
208/230 VOLTS, 3 PHASE
460 VOLTS, 3 PHASE
575 VOLTS, 3 PHASE
DUAL VOLTAGE MOTOR - 230V 1P
DUAL VOLTAGE MOTOR
DUAL VOLTAGE MOTOR
SINGLE VOLTAGE MOTOR
1
BL/BLK
YELLOW
BL/BLK
BL/BLK
BL/BLK
WHITE
WHITE
WHITE
3
5
2
BLUE (AU)
RED (T,J,H)
BLUE (AU)
RED (T,J,H)
BLUE (AU)
RED (T,J,H)
8
4
RED (AU)
BLUE (T,J,H)
BL/BLK
WHITE
RED (AU)
BL/BLK
RED (AU)
BL/BLK
RED (AU)
BL/BLK
BLUE (T,J,H)
BLUE (T,J,H)
BLUE (T,J,H)
TO REVERSE MOTOR DIRECTION, SWITCH
INCOMING LEADS TO TERMINALS 5 AND 8.
TO REVERSE MOTOR DIRECTION, SWITCH
ANY TWO INCOMING LEADS.
TO REVERSE MOTOR DIRECTION, SWITCH
ANY TWO INCOMING LEADS.
TO REVERSE MOTOR DIRECTION, SWITCH
ANY TWO INCOMING LEADS.
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS IDENTIFICATION
25
Description
Parts
Ref Part#
Description
Assemblies
1
2
3
4
5
6
7
8
9
009020 Shaft Collar, 3/4”
Ref Part#
008071 Flange Bearing, 3/4”
A
C
109351 Frame Assembly w/Shafts. AUJ
109358 Frame Assembly w/Shafts, AUH
110076 Clutch Shaft Assembly, AUJ
106810 Pillow Block Bearing, 1”
105549 Snap Ring, 3/4”
100315 Hand Chain, AUH
106814 Sprocket, 65B10, 3/4” Bore, AUJ / H
106815 Sprocket, 65B27, 3/4” Bore, AUJ / H
100210 Sprocket, 65B10, 3/4” Bore, AUJ Disconnect
009070 Sprocket, 65B30, 1” Bore, AUJ / H (1/3 HP)
110077 Clutch Shaft Assembly w/Hoist, AUH
E
G
I
109848 Secondary Shaft Assembly, AUJ / H (1/3 HP)
109274 Secondary Shaft Assembly, AUJ / H (1/2 & 3/4 HP)
109273 Brake Assembly, AUJ / H, 115 VAC
109274 Brake Assembly, AUJ / H, 230 / 460 VAC
CALL Control Box Assembly
10 100134 Sprocket, 41B10, 3/4” Bore, AUJ / H (1/2 & 3/4 HP)
11 009062 Sprocket, 41B30, 1” Bore, AUJ / H (1/2 & 3/4 HP)
12 009061 Drive Sprocket, 41B20, 1” Bore, AUJ / H (1/3 HP)
13 009062 Driven Sprocket, 41B30, 1” Bore, AUJ/H (1/3 HP)
14 009057 Drive Sprocket, 40B20, 1” Bore, AUJ/H (1/2 & 3/4 HP)
15 009136 Driven Sprocket, 40B30, 1” Bore, AUJ/H (1/2 & 3/4 HP)
16 107144 Limit Chain, #65, 17” with Master Link
17 009246 Secondary Chain, #40, 18”, AUJ
Motors
K
100465 Motor, 1/3 HP, 48 ODP, 115 VAC, 1 PH
100466 Motor, 1/2 HP, 48 ODP, 115 VAC, 1 PH
005156 Motor, 1/3 HP, 56 ODP, 115/230 VAC, 1 PH
005026 Motor, 1/2 HP, 56 ODP, 115/230 VAC, 1 PH
005027 Motor, 3/4 HP, 56 ODP, 115/230 VAC, 1 PH
Parts
009244 Secondary Chain, #41, 18”, AUH
19 009249 Primary Chain, #65, 24”, AUJ / H (1/3 HP)
009242 Primary Chain, #41, 24”, AUJ / H (1/2 & 3/4 HP)
21 009239 Drive Chain, #41, 4’, AUJ / H, (1/3 HP)
009240 Drive Chain, #40, 4’, AUJ / H, (1/2 & 3/4 HP)
23 105385 Brake Solenoid, 115 VAC
30 009087 V Belt, 4L390
31 009155 Clutch Pulley w/Bushing, 4L
32 009028 Clutch Fiber Disk
33 100133 Clutch Plate
105386 Brake Solenoid, 230 VAC (also used on 460 VAC units)
25 110042 Brake Shoe
34 105308 Clutch Spring
35 100636 Clutch Lock Nut
36 107517 Clutch Adjusting Nut
26 106806 Brake Drum w/4L Pulley, 5/8” Bore
Download from Www.Somanuals.com. All Manuals Search And Download.
26
SPECIFICATIONS
SPECIFICATIONS
MODEL : AUH _ _ _ _ S
HP :_____
MODEL : AUJ_ _ _ _S
HP:_____
VOLTS : _____ PHASE : _____
VOLTS : _____ PHASE : _____
* UL AND CANADIAN UL LISTED
* UL AND CANADIAN UL LISTED
* HIGH STARTING TORQUE, CONTINUOUS DUTY MOTOR
* MOTOR OVERLOAD PROTECTION
* HIGH STARTING TORQUE, CONTINUOUS DUTY MOTOR
* MOTOR OVERLOAD PROTECTION
* CLASS 2 (24 VOLT) CONTROL CIRCUIT
* SOLENOID BRAKE
* CLASS 2 (24 VOLT) CONTROL CIRCUIT
* SOLENOID BRAKE
* SOLID STATE MOTOR CONTROL CIRCUITRY WITH
ADVANCED OPERATIONAL FEATURES STANDARD
* THREE BUTTON CONTROL: OPEN, CLOSE, STOP
* WIRED TO ACCEPT REVERSING EDGE INPUT
* HEAVY GAUGE, POWDER-COATED STEEL
FRAME RAILS AND CONTROL BOX
* SOLID STATE MOTOR CONTROL CIRCUITRY WITH
ADVANCED OPERATIONAL FEATURES STANDARD
* THREE BUTTON CONTROL: OPEN, CLOSE, STOP
* WIRED TO ACCEPT REVERSING EDGE INPUT
* HEAVY GAUGE, POWDER-COATED STEEL FRAME
RAILS AND CONTROL BOX
* ALL SPROCKETS AND PULLEYS PINNED OR KEYED,
SOLID STEEL DRIVE SHAFTS
* ALL SPROCKETS AND PULLEYS PINNED OR KEYED,
SOLID STEEL DRIVE SHAFTS
* FULLY ADJUSTABLE FRICTION CLUTCH
* HEAVY DUTY PILLOW BLOCK BEARINGS ON OUTPUT
SHAFT
* FULLY ADJUSTABLE FRICTION CLUTCH
* HEAVY DUTY PILLOW BLOCK BEARINGS ON OUTPUT
SHAFT
* INTEGRAL MANUAL CHAIN HOIST WITH FLOOR LEVEL
ENGAGEMENT AND DISCONNECT.
* FLOOR LEVEL DISCONNECT
* FULLY ADJUSTABLE, INTERNAL, SHAFT DRIVEN LIMITS
* FULLY ADJUSTABLE, INTERNAL, SHAFT DRIVEN LIMITS
LINEAR LIMITED WARRANTY
This Linear product is warranted against defects in material and workmanship for 2 years. This
warranty extends only to wholesale customers who buy direct from Linear or through Linear‟s normal
distribution channels. Linear does not warrant this product to consumers. Consumers should inquire
from their selling dealer as to the nature of the dealer‟s warranty, if any. There are no obligations or
liabilities on the part of Linear LLC for consequential damages arising out of or in connection with
use or performance of this product or other indirect damages with respect to loss of property, revenue,
or profit, or cost of removal, installation, or reinstallation. All implied warranties, including implied
warranties for merchantability and implied warranties for fitness, are valid only until the warranty
expires. This Linear LLC Warranty is in lieu of all other warranties express or implied.
All products returned for warranty service require a Return Product Authorization Number (RPA#).
Contact Linear Technical Services at 1-800-421-1587 for an RPA# and other important details.
P/N230769
REV X7
April 2011
Copyright © 2011 Linear LLC
Download from Www.Somanuals.com. All Manuals Search And Download.
|